CS7190050 - NCU Controller user manual M830B
CS7190050 - NCU Controller user manual M830B
Electrical Safety
Hazardous voltage
DANGER! Some components of the outdoor power system carry hazardous voltage in
operation. Direct contact or indirect contact through moist objects with these components
will result in fatal injury.
Observe safety rules in the industry when installing the AC power system. The installation
personnel must be licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects such as
watches, bracelets, bangles, rings.
When water or moisture is found in the cabinet, just turn off the power immediately. In moist
environment, precautions must be taken to keep moisture out of the power system.
Attach ‘Prohibit’ warning label to the switches and buttons that are not permitted to operate
during installation.
DANGER! High voltage operation may cause a fire or electric shock. The connection and
wiring of AC cables must be in compliance with the local rules and regulations. Only those
who are licensed to operate high voltage and AC power can perform high voltage operations.
DANGER! To avoid electric shock hazard of outdoor environment and outdoor equipment,
the non-professionals are prohibited to operate or maintain the outdoor power system.
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection
devices remain de-energized during installation at loads, as required.
Tools
WARNING! In high voltage and AC operation, special tools must be used. No common or self-
carried tools should be used.
Thunderstorm
DANGER! Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the
equipment should be well earthed in time to avoid damage by lightning strikes.
Others
Sharp object
WARNING! When moving equipment by hand, wear protective gloves to avoid injury by
sharp object.
Cable connection
NOTE! The signal lines should be bound separately from heavy current and high voltage
lines, with binding interval of at least 150mm.
Overview
The NCU performs the following functions:
• Rectifier Control, including an Energy Optimization Mode
• Solar Converter and Converter Control
• System Components Monitoring and System Alarms Generation (including recording alarms
in logs)
• Operating Data Acquisition and Data Logs
• Battery Management
• Energy Management via Energy Optimization Mode
• Power Split Feature
• Diesel Management Feature
• Supervisory Module (SM Modules) Monitoring
• Hybrid Control Function (Supporting Generator, Solar and Wind Energy Input, and
Optimization).
• Maximum Current Limit Function
• Communications Function
• Consumption Map Function
The NCU controls the system automatically via configured parameters.
A User can interface with the NCU locally using the local keypad and LCD display or locally/remotely
using the Web Interface.
The NCU can also be accessed via SNMP (v2 and v3). A machine-to-machine HTTP interface is also
available.
Figure 1 illustrates the various applications that can be used to interface with the NCU.
Function Descriptions
Rectifier, Solar Converter, and Converter Control
The NCU controls rectifiers, solar converters, and converters automatically.
NOTE! Solar Mode has to be enabled for NCU control of solar converters (see “Enabling Solar
Mode” on page 43).
System Components Monitoring and System Alarms Generation
The NCU monitors the components comprising the system (such as the rectifiers, solar converters,
converters, and supervisory modules) and generates alarms if a fault condition occurs. The NCU
also maintains an alarm history log.
The available system alarms are programmed with an Alarm Severity Level. Each Alarm Severity
Level has different visual/audible alarm attributes. Available Alarm Severity Levels and their
attributes are listed in Table 1.
The available system alarms can also be mapped to alarm relays (located on controller interface
boards) that can be wired to external alarm circuits.
V TempComp Coeff
setting (mV/°C).
Tnom
Nominal temperature (no temperature compensation is done at this temperature).
Tnom
This is the Temp Comp setting.
Overview
Via the Web Interface, a User (with proper access level) can:
• View real-time operating information (rectifiers, converters, solar converters, AC, DC,
batteries, etc.).
• View and download information recorded in logs.
• Send control commands.
• Set programmable parameters.
• Download and upload the “SettingParam.tar” file.
• Download firmware to the controller.
Multiple Browsers Supported
Multiple browsers are supported in the Web Interface. The User can use Internet Explorer,
Chrome, Safari, or Firefox.
Web Interface Screens
Refer to “Web Interface Screens” on page 122.
Setup Procedures
Setting IPv4 Communications Parameters (if controller not set as DHCP)
The controller’s IPv4 parameters (IP, subnet mask, and gateway addresses) must be set to match
your company’s network settings. The default settings for these parameters are shown below.
• IP Address: 192.168.100.100
• Subnet Mask Address: 255.255.255.0
Connecting the Controller to your Local Area Network (LAN) when the System IS Equipped with an
IB4 Board
NOTE! Your system may be furnished with an IB4 board. The IB4 board provides a second
Ethernet port. The Ethernet port located on the NCU Controller’s front panel can ONLY be
used to connect a computer directly to the NCU. The Ethernet port located on the IB4 board
can be used to connect the NCU to your Local Area Network (LAN). Refer to your system’s
documentation for location of the IB4 board (if furnished).
NOTE! If your system has an IB4 board, DO NOT connect your Local Area Network (LAN) to
the NCU front Ethernet port.
Some systems may have an IB4 board with a second Ethernet port. This port supports Dynamic
Host Configuration Protocol (DHCP) function. Refer to your system’s documentation for location of
the IB4 board (if furnished).
If your system has an IB4 board, connect the Local Area Network (LAN) to the IB4 board port. The
IB4 board port can be assigned an IP address or can be set for DHCP. If it is set for DHCP, it will get
its IP address from a DHCP server on the network. Refer to “Setting IPv4 Communications
Parameters (if controller not set as DHCP)” on page 25 or “Setting IPv6 Communications
Parameters (if controller not set as DHCPv6)” on page 26 to set the port parameters;
or,
“Setting for DHCP and DHCPv6” on page 26 to set the port as DHCP or DHCPv6.
Connecting a Local Computer Directly to the Controller when the System is NOT Equipped with an
IB4 Board
An Ethernet port is located on the front panel of the NCU. This port supports Dynamic Host
Configuration Protocol (DHCP) function.
If your system does not have an IB4 board, perform the following procedure.
Procedure
1. Before connecting your computer directly to the controller’s Ethernet port, use the
following procedure to record your computer’s network settings (so they can be
returned to these values when done) and then change these settings in your
computer to match the communications settings programmed in the controller.
NOTE! Windows 7 operating system is used in this procedure, other operating systems are
similar.
a) Record your computer’s network settings by launching Control Panel in your computer.
Navigate through Network and Sharing Center Local Area Connection Properties
Internet Protocol Version 4 (TCP/IPV4) Properties.
b) Record whether the "Obtain an IP address automatically" or "Use the following IP
address" button is selected. If "Use the following IP address" button is selected, also
record the following:
Connecting a Local Computer Directly to the Controller when the System IS Equipped with an IB4
Board
NOTE! Your system may be furnished with an IB4 board. The IB4 board provides a second
Ethernet port. The Ethernet port located on the NCU Controller’s front panel can ONLY be
used to connect a computer directly to the NCU. The Ethernet port located on the IB4 board
can be used to connect the NCU to your Local Area Network (LAN). Refer to your system’s
documentation for location of the IB4 board (if furnished).
An Ethernet port is located on the front panel of the NCU. This port supports Dynamic Host
Configuration Protocol (DHCP) function.
Some systems may have an IB4 board with a second Ethernet port. Refer to your system’s
documentation for location of the IB4 board (if furnished).
If your system has an IB4 board, perform the following procedure.
Procedure
1. Connect your computer directly to the controller’s Ethernet port (RJ-45 jack located
on the front of the controller). See Figure 8. The NCU’s front panel port will have the
following IPv4 Address: 192.168.100.100. Enter the address 192.168.100.100 in your
Web browser to access the NCU’s Web Interface via IPv4. The NCU’s front panel port
will have the following IPv6 Address. IPv6 Link-Local Address: fe80::209: f5ff:
fe09:1002/64 or IPv6 Address: 20fa: fffd: fffc:fffb:fffa:fff9:fff8:fff7. Enter the IPv6
Link-Local Address: [fe80::209: f5ff: fe09:1002/64] or IPv6 Address:
[20fa:fffd:fffc:fffb:fffa:fff9:fff8:fff7] to access the NCU’s Web Interface via IPv6.
2. When finished, disconnect your computer from the NCU.
Disabling Proxy Server Settings to Enable a Connection to the Controller over an Intranet Network
(if required)
NOTE! This procedure needs to be performed only when the controller is connected to an
Intranet and the User’s computer is set to access the Intranet through a proxy server. Note
that if the controller is connected to the Internet and the User’s computer is connected to an
Intranet, the User may not be able to disable the proxy server and access the controller.
If the controller’s Ethernet port is connected to your company’s Intranet Network and your
computer is also connected to the Intranet Network but requires access via a proxy server, you
must disable the proxy server settings to access the controller. Follow the procedure below to
disable the proxy server settings.
5. Click on the LAN Settings... button. The following window opens. In the LAN Settings
window, uncheck the Proxy Server box and click OK.
Internet Security Settings for Loading Files or Downloading Files into the NCU
Your computer’s security settings may prevent you from loading files or downloading files into the
NCU. Refer to the following procedure to set your computer’s security settings to allow for this.
Procedure
NOTE! Internet Explorer is used in this procedure, other browsers are similar.
5. Click on Trusted sites. With “Trusted sites” selected, click “Sites”. The following
window opens. Uncheck the “Require server verification (https:) for all sites in the
zone:” box if https is not being used.
7. Click Add. The NCU URL is listed in the Websites: box. Click Close.
3. After entering a valid User Name and Password and clicking LOGIN, the Web Interface
"HOMEPAGE" window opens. Refer to “Web Interface Screens” on page 122.
• To set up the “Forgot Password” feature, you must have a User set up with an email address
and you must set up the Alarm Reporting SMTP section. To program the User, in the Web
Interface, go to Advanced Settings Menu / Users Tab / select the User / enter a valid email
address for this User / repeat for all Users (see “Users Tab” on page 184). To program the
Alarm Reporting SMTP section, in the Web Interface, go to Advanced Settings Menu / Alarm
Report Tab / SMTP Section / enter at a minimum the following parameters: “Email To”
address, Server IP (IPV4 Server address), Server Port, “Email From” address. If email
authentication is required, then the SMTP Account and SMTP Password needs to be
configured as well. (See “Alarm Report Tab” on page 204.)
Start Wizard
For initial startup, perform the Start Wizard from the local keypad and display to enter basic
programmable parameters in one session. Refer to “Start Wizard Sub-Menu (accessed from
Settings Menu)” on page 107 and “Start Wizard Now” on page 119.
Viewing Alarms
Local Menu Navigation:
Main Menu / Alarm Icon / ENT.
Web Menu Navigation:
Active alarms are listed in the lower right window pane. If the window pane is collapsed, click the
"arrow" icon to expand the alarm list.
Clearing Logs
Local Menu Navigation:
None.
Web Menu Navigation:
Advance Settings Menu / Clear Data Tab / select log to clear.
Checking the Controller’s Current Limit Point after Adding or Removing a Rectifier or Converter
Module
If a rectifier or converter module is added; the respective current limit point in amps will
automatically increase to maintain the same percentage. For example, if the current limit was set
to 100% of combined capacity and a module is added, the new current limit setpoint will be 100%
of the combined capacity including the new module.
If a rectifier or converter is removed from the system (and the Rect Comm Fail or Conv Comm Fail
alarm is cleared); the respective current limit point will remain unchanged unless the capacity of
the remaining rectifiers or converters is not sufficient to maintain this current limit point. If that
happens, the current limit point will automatically decrease to the maximum (121% of the
remaining rectifiers or 116% of the remaining converters).
Setting Battery Block and Battery Midpoint Monitoring (if equipped with an EIB Assembly)
Local Menu Navigation:
None.
WEB Menu Navigation:
Settings Menu / Battery Charge Tab / and enter the following parameters.
Parameters
• EIB-# Voltage Type
• EIB-# Block In-Use Num
• EIB-# Block Voltage Diff or Block Voltage Diff (Mid)
2. Connect the USB memory device to the USB port on the front of the controller.
3. Navigate to “Main Menu / Settings Icon / Sys Settings / Update App / select yes”.
Once Yes is selected and confirmed, the configuration file located on the memory
device located in the controller's USB port is loaded into the controller.
4. A percent (%) complete will be displayed and when finished the NCU will reboot
automatically
5. The controller enters an initialization routine, which takes a few minutes. The routine
is complete, and the controller is operational when normal system voltage is
displayed on the screen.
6. Remove the memory device.
Web Menu Navigation (To Download an Application ("All") Package):
Advance Settings Menu / SW Maintenance Tab.
See “Upload/Download Procedure” on page 196 to download an Application (“All”) Package into
the controller.
Changing the Names of Items Displayed in the LCD and Web-Interface Menus
Local Menu Navigation: none.
WEB Menu Navigation:
Navigate to the appropriate tab in the Advance Settings menu. Press “Modify” and enter the signal
name parameter(s). When done, press “Set”.
Digital Inputs
Advance Settings Menu / DI Alarms Tab.
Shunts
Advance Settings Menu / Shunts Tab.
Fuses
Advance Settings Menu / Fuse Tab.
NOTE! The same type of batteries with an equal amount of cells and the same charging
voltages must be used for both systems.
• The float voltage, equalize voltage, and battery test voltage of the NCU power system must
be set to the same levels as that of the existing power system.
• The remote sense, if available and connected, of both the NCU power system and existing
power system must be connected to the same point.
• If batteries are used, they must be of the same type.
• All the functions specific to the existing power system and NCU power system and which
depend on the voltage or which act on the voltage must be disabled from the existing power
system and NCU power system. This includes the following…
a) any equalization function,
b) any temperature compensation function,
c) any charge control function,
d) any battery discharge test function, and
e) any invalid current alarm.
In lieu of this, if battery charging and battery test functions are implemented in the existing power
system, they can remain if signals for starting are connected from the control system of the existing
system to the NCU system.
NOTE! Battery test is controlled by the existing power system via an incoming digital signal.
The system will remain at battery test as long as this signal is active.
Low Voltage Disconnect Setup
If low voltage disconnect functions are to be used, they must be implemented in the existing power
system and signals from its control unit must be connected to the NCU.
5. Using the Web Interface menus (see “Power Split Tab” on page 208), select the NCU
digital inputs connected to the low voltage disconnect control circuits.
Temperature Compensated Battery Charge
There is no possibility to activate the “Temperature Compensated Battery Charge” function when
the NCU power system is configured for “Power Split” mode.
However, the possibility to change the “Delta Voltage” enables the NCU power system to follow the
existing power system that has the functionality to a certain limit.
Example: The “Delta Voltage” in the NCU power system is set to 1.0V. The existing power system is
set to compensate 3.0 mV/cell/°C. This means that the NCU power system can follow the
temperature compensation of the existing; power system in the range of ±14 °C from the set
normal battery temperature (3.0 mV x 24 cells x 14 °C = 1.008 V).
Verifying the Operation of the Power Split Feature
After programming the “Power Split” feature, verify its operation as follows.
6. In a Power Split application where the NCU power system is taking the entire load and
the rectifiers in the existing power system are all in the standby mode, use an
external dry load bank of sufficient capacity to increase the load on the NCU power
system over the “SLAVE CURRENT LIMIT” value.
a) Verify that the NCU power system limits the total output of its rectifiers to the current
equivalent to this programmed percentage.
b) Verify that the NCU power system lowers its output voltage by the value of the
programmed “DELTA VOLTAGE”.
c) Verify that the rectifiers in the existing power system take the additional load as the load
increases pass the “SLAVE CURRENT LIMIT” value.
d) Further increase the load in order to exceed the total capacity of the rectifiers in the
existing power system (or shut down some of the rectifiers in the existing power system
if the capacity of the external dry load bank is not sufficient). Verify that the NCU power
system starts taking the additional load as soon as the total capacity of the rectifiers in
the existing power system is exceeded.
7. In a Power Split application where the NCU power system is taking only part of the
load (operating continuously at the current level equivalent to the programmed
“SLAVE CURRENT LIMIT” percentage) and the rectifiers in the existing power system
are taking the rest of the load, use an external dry load bank of sufficient capacity to
increase the load in order to exceed the total capacity of the rectifiers in the existing
power system (or shut down some of the rectifiers in the existing power system if the
capacity of the external dry load bank is not sufficient).
Resolving Alarms
Table 4 lists the alarms that are shown in the Web Interface Advance Settings Menu under the
Alarms Tab. These are also the possible alarms that display in the alarm screens on the local display
and Web Interface. Table 4 also provides guidelines for fixing the condition that caused the alarm.
NOTE! These instructions describe the complete functionality of the controller. Some
functionality is dependent on hardware connected to the controller. Some alarms listed may
not display in your system or may be named differently. Refer to the NCU Configuration
Drawing (C-drawing) furnished with your system.
Refer also to the NCU Configuration Drawing (C-drawing) furnished with your system for the factory
default “Alarm Severity Level” settings and “Alarm Relay” mapping to the available alarms.
Overview
This section provides descriptions of the Local Display Menus. Refer also to “Passwords and
Privilege Levels” on page 25 and “Description of Local Display Menus Programmable Parameters”
on page 112. For Web Interface, refer to “Web Interface Screens” on page 122.
Menus
Figure 10 to Figure 18 provide flow diagrams of the menus accessed via the NCU Controller local
display and keypad.
NOTE! These instructions describe the complete functionality of the NCU Controller. Some
functionality is dependent on hardware connected to the NCU Controller. Some menu items
shown may not be present in the NCU Controller used in your system.
Settings Menu
See Figure 13.
Maintenance Sub-Menu
• Auto/Man State:
- Auto: The controller automatically controls the power system.
- Manual: A User can manually change certain power system control settings. When you
return to Auto Mode, any settings changed in Manual Mode are returned to their
previous setting (setting before being placed in Manual Mode). This provides a
convenient means of making temporary adjustment changes for testing purposes.
• EQ/FLT Control: Places the system in Equalize Charge or Float Charge mode.
• LVD 1 Control: Temporarily connects or disconnects LVD 1 when the controller is in Manual
mode. Setting returns to original when controller is returned to the Auto mode.
• LVD 2 Control: Temporarily connects or disconnects LVD 2 when the controller is in Manual
mode. Setting returns to original when controller is returned to the Auto mode.
• Rect Curr Limit: Maximum rectifier current setting .
• Over Voltage 1: Sets the Over Voltage 1 alarm point.
• Over Voltage 2: Sets the Over Voltage 2 alarm point.
• Under Voltage 1: Sets the Under Voltage 1 alarm point.
• Under Voltage 2: Sets the Under Voltage 2 alarm point.
Energy Saving Sub-Menu
• ECO Mode: Enables or disables the Energy Optimization Mode feature for all rectifiers.
When enabled, the following parameters can be set.
ALERT! The Energy Optimization Mode should NOT be used in systems that operate without
batteries.
• Best Oper Point: Percent of full load capacity that the rectifiers operate under in the Energy
Optimization mode.
• Fluct Range: If load fluctuation is less than this value, rectifiers are not turned on or off for
Energy Optimization.
• Cycle Period: This is the time period that rectifiers are turned on and off to maintain an
equal operating time for all rectifiers in the system.
• Rects ON Time: Time all rectifiers are turned on at the end of the “Cycle Period”.
Homepage
In the Web Interface, after entering a valid User Name and Password and clicking LOGIN, the
"Homepage" window opens. See also “Logging into the Controller” on page 34.
Figure 21: System Status Information, System Specifications Information, Controller Specifications
Information, and Site Information Areas
Temperatur
e Reading
System
Current
Reading
NOTE! Settings that appear "grayed out" can only be made when the controller is in the
"manual control" state. If the controller is set for "automatic" control, change the
“Auto/Manual State” setting first to the “Manual” setting.
• DC On/Off Control: Temporarily turns the rectifier’s DC output on or off when the controller
is in Manual mode. Setting returns to original when controller is returned to the Auto mode.
• AC On/Off Control: Temporarily turns the rectifier’s AC input on or off when the controller is
in Manual mode. Setting returns to original when controller is returned to the Auto mode.
• LED Control: Temporarily sets whether or not the rectifier's local power indicator blinks
when the controller is communicating with the rectifier when the controller is in Manual
mode. Setting returns to original when controller is returned to the Auto mode.
• Rectifier Reset: Temporarily sets the rectifier’s over voltage reset feature when the
controller is in Manual mode. Setting returns to original when controller is returned to the
Auto mode.
• Rectifier ID: Sets the rectifier’s identification number.
• Rectifier Phase: Indicates the phase connected to the rectifier’s input.
Solar Converter Device Group Status Page Tab
This tab displays status values such as “Total Current”, “Number of Solar Converters”, etc.
NOTE! Settings that appear "grayed out" can only be made when the controller is in the
"manual control" state. If the controller is set for "automatic" control, change the
“Auto/Manual State” setting first to the “Manual” setting.
• DC On/Off Control: Temporarily turns the solar converter’s DC output on or off when the
controller is in Manual mode. Setting returns to original when controller is returned to the
Auto mode.
NOTE! Settings that appear "grayed out" can only be made when the controller is in the
"manual control" state. If the controller is set for "automatic" control, change the
“Auto/Manual State” setting first to the “Manual” setting.
• DC On/Off Control: Temporarily turns the converter’s DC output on or off when the
controller is in Manual mode. Setting returns to original when controller is returned to the
Auto mode.
• Converter Reset: Temporarily sets the converter’s over voltage reset feature when the
controller is in Manual mode. Setting returns to original when controller is returned to the
Auto mode.
• LED Control: Temporarily sets whether or not a converter's local power indicator blinks
when the controller is communicating with the converter when the controller is in Manual
mode. Setting returns to original when controller is returned to the Auto mode.
• Converter ID: Sets the converter’s identification number.
Example: Clicking on DU 2.2 in the Cabinet Map Status screen shown in Figure 39 displays Figure
40. Figure 40 shows there are two (2) branch circuits in DU2.2 and the current of the branch circuit
is 0 A.
In the Battery Device Group Status Page Tab, click the settings wheel icon to go to the individual
battery settings page. See Figure 46. Click to go back to the Battery Device Group Status
Page Tab. The actual display of an Individual Battery status is dependent on the NCU configuration
and if SMDU or EIB shunts are programmed as battery shunts (see Figure 47, Figure 48, and Figure
49.)
• Battery Management: Select Yes to use the battery management feature and No to not use
the feature for this battery.
• Rated Capacity: Enter the battery string's rated capacity.
Battery Management: Select Yes to use the battery management feature and No to not use the
feature for this battery.
Rated Capacity: Enter the battery string's rated capacity.
• Signal Settings:
- Float Charge Voltage: Float Charge output voltage setting.
- Equalize Charge Voltage: Equalize Charge output voltage setting.
- Temp Compensation Probe Number: Select "None" for no temperature compensation,
or the temperature probe [System Temp1 (bat), System Temp2 (bat), System Temp3
(bat), IB2-1 Temp1 (bat), IB2-1 Temp2 (bat), IB2-2 Temp1 (bat), IB2-2 Temp2 (bat), EIB-1
- ECO Mode: Enables or disables the Energy Optimization Mode feature for all rectifiers.
When enabled, the following parameters can be set.
Best Operating Point: Percent of full load capacity that the rectifiers operate under in the
Energy Optimization Mode.
Load Fluctuation Range: If load fluctuation is less than this value, rectifiers are not
turned on or off for Energy Optimization.
Cycle Period: This is the time period that rectifiers are turned on and off to maintain an
equal operating time for all rectifiers in the system.
All Rects ON Time: Time all rectifiers are turned on at the end of the “Cycle Period”.
- Outgoing Alarms Blocked:
Normal: Alarms are processed normally.
Blocked: Forces the alarm relays in the "off" state and blocks alarms from changing the
relay state.
- Batt1 Rated Capacity: Enter the battery string’s rated capacity.
- Batt2 Rated Capacity: Enter the battery string’s rated capacity.
- SMDU1Batt2 Rated Capacity: Enter the battery string’s rated capacity.
Set Cabinet Tab Programmable Parameter Descriptions
The Set Cabinet tab is shown in Figure 56.
The Set Cabinet tab is divided into two parts. The left part is the load branch list, which will be used
to designate the customer load branch circuits to be monitored for consumption. The right part is
the customer load icons displayed in a grid list.
Click this symbol to set the load branch circuit current rating
Click this symbol to set the load branch circuit current rating
2. The following window opens. Enter a value for the branch circuit current rating and click Set.
2. The following window opens. Enter the customer icon parameters and click Set.
• Name: The name of the customer.
• Alarm Level 1: If the customer load(s) exceeds the percent of the total branch circuit current
rating entered for Alarm Level 1, the icon representing the customer load turns yellow, which
indicates an observation alarm.
• Alarm Level 2: If the customer load(s) exceeds the percent of the total branch circuit current
rating entered for Alarm Level 2, the icon representing the customer load turns red, which
indicates a major alarm.
• Rated Power: Sets the rated power of the cabinet.
3. Select a Cabinet and a DU in the drop-down list boxes. The available load distribution branch
circuits are displayed as shown in the following window. Drag one of the displayed load
distribution branch circuits from the left side to the selected customer load icon in the grid list
displayed on the right side. Once a load distribution branch circuit has been designated, it will
become greyed out and cannot be dragged again. You can add up to twenty (20) load
distribution branch circuits to a customer load icon.
Select a Cabinet
and a DU in the
drop-down list
boxes. Drag a load distribution branch circuit
onto a customer icon.
Best Operating Point: Percent of full load capacity that the rectifiers operate under in the
Energy Optimization mode.
Load Fluctuation Range: If load fluctuation is less than this value, rectifiers are not turned on
or off for Energy Optimization.
System Energy Saving Point: Energy Optimization is disabled if the load is greater than this
setting.
Cycle Period: This is the time period that rectifiers are turned on and off to maintain an
equal operating time for all rectifiers in the system.
All Rects ON Time: Time all rectifiers are turned on at the end of the “Cycle Period”.
Turn Off Delay: When the Energy Optimization feature determines a rectifier can be
switched off, this is the time delay before the rectifier is turned off.
• Reset Cycle Alarm: Resets the ECO Cycle Alarm. The only selection is Yes. Once Yes is
selected and confirmed, the alarm resets.
LVD Tab Programmable Parameter Descriptions
LVD Unit
• LVD 1: Enables or disables LVD 1. When enabled, the following parameters can be set.
LVD 1 Mode: Sets LVD 1 to disconnect on a voltage or time setpoint.
LVD 1 Voltage: LVD 1 low voltage disconnect setting (when LVD set for voltage)
LVD 1 Reconnect Voltage: LVD 1 reconnect setting (when LVD set for voltage).
LVD 1 Reconnect Delay: Delay time period until LVD 1 reconnects once voltage recovers
(when LVD set for voltage).
LVD 1 Time: The time period before LVD 1 disconnection once an AC fail condition occurs
( when LVD set for time).
LVD 1 Dependency: Select if LVD 1 can disconnect only if LVD2 has disconnected, or none.
Ethernet Tab
You can configure the controller's network parameters.
• IPv4: IP Address, Subnet Mask, and Default Gateway.
• IPv6: IPv6 Address, IPv6 Prefix, and IPv6 Gateway.
After modifying the network parameters, click "Save" to validate the change made to the
parameters.
NOTE! After changing the IP Address, you will need to login again with the new IP address.
Deleting a User
4. Select the User to be deleted from those listed in the "User Information" list.
5. Click the "Delete" button to delete this User.
Adding an Entry
1. Enter the parameters in the parameter fields.
2. Click the "Add" button to add the entry.
NOTE! To reset the form (i.e. to start over) and erase all information entered, click on the
“Reset” button.
Deleting an Entry
6. Select the Entry to be deleted from those listed at the top of the screen.
7. Click the "Delete" button to delete this Entry.
NOTE! To reset the form (i.e. to start over) and erase all information entered, click on the
“Reset” button.
Check the
IPV6 box
when
entering an
IPV6 trap
2. Click “OK” to confirm to overwrite the existing "SettingParam.tar" file in memory with
the stored "SettingParam.tar" file.
The controller will automatically reboot. All settings WILL BE restored to the defaults of the
stored "SettingParam.tar" file.
NOTE! After rebooting, you must exit your browser and re-login to see any changes made.
NOTE! SOME SYSTEMS REQUIRE CHANGES TO THE NCU CONFIGURATION DURING FINAL
TEST BEFORE BEING SHIPPED. These systems are supplied with a USB memory device that
contains a “SettingParam.tar” file as shipped. If provided, the “SettingParam.tar” file has a
seven-digit UIN (Unique Identification Number) preceding the “SettingParam.tar” filename.
The UIN identifies a “SettingParam.tar” file for use with a specific system. This file can be
used to restore your system to the configuration as shipped. Refer to “Reloading a Backed-Up
NCU Configuration” on page 51 to reload the supplied “SettingParam.tar” file.
TO RESTORE THESE SYSTEMS TO THE NCU CONFIGURATION AS SHIPPED, RESTORE DEFAULTS AS
DESCRIBED ABOVE; THEN RELOAD THE SUPPLIED "SETTINGPARAM.TAR" FILE.
To aid in file management, you may change the name of the “SettingParam.tar” file to
differentiate it from other "SettingParam.tar" files saved. The new name can use alpha and
numeric characters preceding the original “SettingParam.tar” name (the end of the new file
name must always be “SettingParam.tar”; for example, an acceptable filename would be
“seville4SettingParam.tar”).
3. Click "OK".
4. The following window opens.
ALERT! Never navigate from this Web page without first clicking on "Start Controller". If you
do, you will not have Web access. A manual system reset is required to restore Web access.
5. To download (from your computer into the controller) a configuration package,
application ("All") package, language package, or a "SettingParam.tar" file; click the
"Browse..." button and navigate to the folder where the file to download is located.
Select the file to be downloaded and then click the "Download to Controller" button.
Click "Start Controller" to restart the controller with the downloaded file installed.
To upload a file to your computer, select "Configuration Package" or "Language Package"
from the "File in Controller" drop-down list box, and click on the "Upload to Computer"
button to save the file to your computer. Select where you want the file to be copied to on
your computer. Click "Start Controller" to restart the Controller.
NOTE! Ensure Internet Explorer security settings are set to enable a file to be copied to your
computer.
NOTE! A Configuration Package is a package of files containing all the default parameter
settings and any User changes to alarm severity levels, relay assignments, signal names and
site information.
NOTE! An Application “All” package file has both the application (software) and
configuration package and is usually supplied for an application upgrade.
NOTE! A Language Package is a package of files containing all the default names of the
parameters in two languages. Typically, these would be in English and Spanish. The
language package cannot be changed by the User. Consult NOKIA if a different language
package is required.
NOTE! A file named “SettingParam.tar” is automatically created/appended by the Controller
whenever a User (or the factory at the time of shipment) makes changes to the NCU via the
local display or Web Interface. This file also contains the Configuration Package described
above.
• Allows you to define the alarm level for each alarm. (See also Table 1 on page 10.)
• Allows you to map alarms to the alarm relays.
Procedure
1. Select the equipment type to display the alarms associated to it. Also displayed is the
alarm level and alarm relay number assigned to this alarm.
2. To modify the alarm level and/or alarm relay number, click on the “Modify” button
for that alarm signal.
Procedure
If low voltage disconnect functions are to be used in a power split configuration, they must be
implemented in the existing power system and signals from its control unit must be connected to
the NCU.
2. For LVD1, LVD2, and/or LVD3; click on the “Modify” button and select the NCU digital
inputs connected to the low voltage disconnect control circuits.
Procedure
If the battery test function is to be used in a power split configuration, battery test must be
implemented in the existing power system and a test signal from its control unit must be connected
to the NCU.
3. For BATTERY_TEST, click on the “Modify” button and select the NCU digital input
connected to the existing systems battery test control circuit.
Procedure
If the equalize charge function is to be used in a power split configuration, equalize charge must be
implemented in the existing power system and an equalizing signal from its control unit must be
connected to the NCU.
4. For EQUALIZE_CHARGE, click on the “Modify” button and select the NCU digital input
connected to the existing systems equalize control circuit.
Monitor Protocol Tab
You can select "EEM", "YDN23", “Modbus “, or “TL1 “as the protocol. To make the new protocol
valid, click the “Valid after Restart" button.
EEM Protocol
You can set EEM protocol parameters.
The TL1 AID Group appears, select the TL1 AID Group tab, the AID Group appears, user can edit the
AID name, choose AID type and set the Sub AID Name Prefix. As shown in the following:
SNMP V3
ESR Configure
The EEM Protocol is used for communication between the Main Computer and the controller. The
Main Computer is the computer superior to the NCU (the client of the NCU). On this page, all
parameters needed for communication with a main EEM computer are to be set.
User Information Configuration: On this page, Users, their privilege and password are configured.
Time Synchronization: On this page, the system time and date are to be set.
Automatic time synchronization from time servers can also be configured.
Ident Group
System Group
psBattery Group
Battery Table
psInput Group
psTemperature Group
Temperature Table
Battery Mode
SM Series Group
Rectifier Group
Rectifier Table
The Distribution
Converter Group
Converter Table
Control Group
Event Traps
Configuration File
Part Number Label
M830B
Configuration File
Part Number Label
M830D
2. Performing this procedure may activate external alarms. Do one of the following. If
possible, disable these alarms. If these alarms cannot be easily disabled, notify the
appropriate personnel to disregard any future alarms associated with this system
while this procedure is being performed.
3. Connect an approved grounding strap to your wrist. Attach the other end to a
suitable ground.
Latch
Mechanism
M830D
Captive
ESC ENT Fastener
Latch
Mechanism
IB2 (Controller Interface Board) and EIB (Controller Extended Interface Board)
One or more IB2 (Controller Interface Board) and/or EIB (Controller Extended Interface Board) may
be connected to the NCU. The IB2 and EIB provide additional digital inputs and relay outputs. Note
that some digital inputs and/or relay outputs may be factory wired to the system. Refer to your
Power System documentation for IB2 and EIB connections and specifications.
+ - + - NO C NC NO C NC + - + - NO C NC NO C NC
DI 1 DI 2 DO 1 DO 2 DI 3 DI 4 DO 3 DO 4