Intertek__Functional Safety Certification - Program & Mark Guidance (2019)

The document outlines Intertek's Functional Safety Certification Program and guidance for ensuring machine safety in industrial automation and related sectors. It emphasizes the importance of integrating functional safety into machine design to enhance productivity and compliance with international safety standards. The guidance includes a conformity framework, definitions, and the scope of certification applicable to various machinery and equipment types.

Uploaded by

Pam Blue
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

Intertek__Functional Safety Certification - Program & Mark Guidance (2019)

The document outlines Intertek's Functional Safety Certification Program and guidance for ensuring machine safety in industrial automation and related sectors. It emphasizes the importance of integrating functional safety into machine design to enhance productivity and compliance with international safety standards. The guidance includes a conformity framework, definitions, and the scope of certification applicable to various machinery and equipment types.

Uploaded by

Pam Blue
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 39

FUNCTIONAL SAFETY CERTIFICATION

PROGRAM & MARK GUIDANCE


Guidance Document for Intertek’s Functional Safety Propriety Standard (INT/FS/2019) and Certification Program
for Industrial Automation, Process Machinery, and Associated Equipment

intertek.se/provning/functional-safety
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

CONTENTS
Introduction 3
Section 1: Conformity Framework 4
Section 2: Terms & Definitions 10
Section 3: Scope 11
Section 4: Engineering Block Structures 12
Section 5: Conformity Modules 13
Section 6: Certification: General Requirements 16
Section 7: Conformity Modules/Validation: General Description 21
Section 8: Evaluation, Validation & Verification 23
Section 9: Functional Safety Management 28
Section 10: Common Abbreviations 31
Section 11: Customer Supplied Technical Documents & Specifications 33
Contact Information 38

intertek.se/provning/functional-safety/ 2
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

INTRODUCTION
Machine safety is one of the most rapidly growing areas of importance in industrial digitisation and
automation – an important aspect of Industry 4.0, robotics, smart buildings, and smart cities. New
safety strategies offer manufacturers a way of improving productivity and competitiveness in the
market. Safety becomes an integrated part of machine functionality and operability, rather than as
an after-thought added on to meet regulation.
In developed economies, national laws require that machines meet essential health and safety
requirements, meaning new machinery must meet basic requirements when imported and
supplied to the manufacturing base. Manufacturers comply by designing machines to meet
international standards specifically for machine safety. These standards are recognized globally and
equivalency charts between requirements facilitate machinery trade and shipments between
countries.
Functional Safety (FS) is an engineering process that emphasizes safe design, operation, and control
of protection systems as individual components, sub-assemblies, and complete machines to
mitigate unreasonable risk caused by the application of the system. Best practice in functional safety
is not to simply conform to industry standards and protect against accidents, but to drive a more
effective and productive operation, reducing downtime and costly repairs to equipment.
Manufacturers that adopt FS into their processes and equipment will have the advantage of an
internationally recognized safety rating that enables their solutions to be sold on a global stage.
Machine systems designed for functional safety risk mitigation and hazard reduction provide:
• Increased machine safety
• Availability (reduced downtime)
• Reliability (on demand durability)
• Maintainability (lifecycle capability)
• Increased productivity (performance)
• Cost efficiencies

There are various FS standards for different disciplines that address necessary safety measures,
potential failures, development requirements, and recommendations for a specific safety critical
system. One such standard that addresses the general functional safety requirements for machine
systems design is the ISO 12100 standard.
Intertek’s Functional Safety Propriety Standard (INT/FS/2019) has been developed with the
objective to satisfy each stakeholder of the industrial value chain. Our modular solutions provide
flexible options for manufacturers, while our comprehensive services and certifications provide
industrial stakeholders the option to review safety measures in more detail, a common request
from buyers and regulators.
This guidance document defines the evaluation and validation process for the determination of
machine design using international standards, national standards, and the Intertek Functional Safety
Propriety Standard (INT/FS/2019) as reference material for a risk-based reverse design evaluation
approach in order to validate and certify the functional and general safety of machines.

intertek.se/provning/functional-safety/ 3
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 1
CONFORMITY
FRAMEWORK
The primary purpose of this guide is to provide an overview of the conformity framework for the Intertek
methods to be used to validate the design integrity and to determine claimed machine safety,
performance levels (PL), and safety integrity levels (SIL) of machinery leading to the awarding the Intertek
Functional Safety (FS) Mark.
The approach taken is risk based and validation of design basis by calculation, using IS0 12100 as the basic
horizontal standard, Intertek Functional Safety Propriety Standard (INT/FS/2019), and specific equipment
or product standard/s as the vertical platform for the consideration of machine design basis, machine
design evaluation, risk assessment, validation, verification, and inspection methodologies.
INT/FS/2019 Proprietary Standard:
• Modular Levels of Conformity Approach
• Engineering Block Structures
• Risk-Based Approach / Design Evaluation Method
• PL and SIL Calculations
• Hardware and Software Integration

Whether you are at the stage of concept design, pre-prototype, prototype, or incorporating all safety
elements within production, our modular functional safety solutions provide industrial stakeholders the
option to review the safety requirements in more detail.

intertek.se/provning/functional-safety/ 4
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

The outcome of this conformity assessment approach is the validation of performance levels (PL)
and safety integrity levels (SIL) claimed, and general safety for the purpose of granting certification
and marking (FS Mark) of machine systems or processes in accordance to the critical decision path
of ISO/IEC 17065 process for product certification methods. Those methods being application,
evaluation, certification review, and certification final decision for the conformity of complete
systems, sub systems, or component/individual standalone equipment level.

Fig 1.0 (Example - General Conformity Approach)

SAFETY INTEGRITY LEVELS


SIL stands for safety integrity level and is a means to express the required risk reduction
needed to reduce the risk to an acceptable level. According to IEC 61508, the safety levels are
1, 2, 3 and 4 with an order of magnitude increase in safety requirements as you go from one
level to the next. SIL 4 is not seen in machinery and factory automation where generally no
more than one person is typically exposed to a hazard. It is rather reserved for applications
like nuclear and rail where hundreds or even thousands of people are involved.

PERFORMANCE LEVELS
ISO 13849. Its performance levels A, B, C, D, and E can be mapped to the SIL 1 to SIL 3 scale.
Common cycle data (MTTFd) is used for the calculation of both PL and SIL ratings.
Calculation of SIL alone to IEC 6I508 cannot map to PL category A, B, C, D, or E.

intertek.se/provning/functional-safety/ 5
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

The meaning and purpose of functional safety is to protect from harm, foreseen and unforeseen
hazards, in the event of real time failure impacting:
• People
BENEFITS
• The environment Incorporating Functional Safety design
principles provides:
• The asset (machine)
• Reduction of risk levels
• Safe machine design
Functional safety achieves this by design intent on implementation of control and protection
• Protections and safeguards for:
concepts that lower the probability of undesired events, thereby minimizing failure across the full
operator, environment, machine
life cycle of the machine.
life cycle
Safety standards define safety as freedom from unacceptable risk. The most effective way to
eliminate risks is to design them away. But as risk reduction by design is not always possible or
practical, safeguarding with static guards are often the next best option for several reasons.
Stopping a machine quickly and safely not only reduces risk but also increases machine uptime
and productivity compared with abrupt safety stops. At the same time, the legal obligations are
met, and the safety of people, the environment, and the asset are assured.
Functional safety in machinery usually means systems that safely monitor and, when necessary,
override the machine applications to ensure safe operation. A safety-related system thus
implements the required safety functions by detecting hazardous conditions and bringing
operation to a safe state by ensuring that a desired action, e.g. safe stopping, takes place.

1.1 System Conformity Framework: General


For the purposes of conformity assessment, Intertek will use ISO 12100 and Intertek Propriety
Standard INT/FS/2019 as the risk-based approach, and normative references contained within
shall provide the basic safety framework for covering the machine lifecycle by determining safe
design, claimed functional safety (PL and SIL), and general safety of machines.
ISO 12100 specifies basic terminology, principles, and a methodology for achieving safety in the
design of machinery. It specifies principles of risk assessment and risk reduction for design
requirements. These principles are based on knowledge and experience of the design, use,
incidents, accidents, and risks associated with machinery.
ISO 12100 defines three types (or ‘classifications’) of standards representing different levels of
granularity:
• Type A standards establish general, overarching guiding principles – all machines (horizontal)
• Type B standards have specific design principles for a specific technology (horizontal)
• Type C standards are application-specific or product standards (vertical)

intertek.se/provning/functional-safety/ 6
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

1.2 Functional Safety (FS) Mark – Conformity Framework (All System Levels)
Overall, ISO 12100 applies to the system level (entire machine), but specific elements trace down to
the product or component level. ISO 12100 is a Type A standard that applies to everything that is
defined as a machine. Type B standards relate the sub systems or sub-assemblies of the machine,
while Type C standards are dedicated to the specific product or machine, or to a component of the
machine.

Fig 1.1 (Standards Classification Structure)

1.3 Type A Classification: Systems Conformity Assessment


Table 1.1 illustrates an example of typical Class A standards used for the risk assessment framework of
a full systems (the complete machine).

Type A Classification (Full Systems) ISO Standard

Safety of machinery, general principles for design — risk assessment and ISO 12100
risk reduction (full system)

Robots and robotic devices — Safety requirements for industrial robots ISO 10218
Table 1.1

intertek.se/provning/functional-safety/ 7
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

1.4 Type B1 Classification: Sub-Systems Conformity Assessment


Table 1.2 provides an example of typical Class B1 standards applied for a sub-systems conformity
assessment framework.

Type B1 Classification (Sub-Systems)


ISO Standard
Specific Aspects

Fixed and movable guards (safety fences, barriers, covers) ISO 14120

Interlocking devices associated with guards (interlocking of safety gates, etc.) ISO 14119

Prevention of unexpected start-up ISO 14118

Protective devices (light grids, light beam devices, scanners, pressure- ISO 13856
sensitive mats, etc.)

Two-hand control devices ISO 13851

Adjustable safeguards that restrict access fixed and movable guards ISO 14120

Emergency stop ISO 13850


Table 1.2

intertek.se/provning/functional-safety/ 8
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

1.5 Type B2 Classification: Sub-Systems Conformity Assessment


The example given in Table 1.3 is for a typical Class B2 standard applied for sub-systems conformity
assessment framework.

Type B2 Classification (Sub-Systems)


Standards
Functional Safety and Safety-Related Controls

Safety-related parts of control systems ISO 13489


IEC 62061

Safety-related requirement of pneumatics ISO 4414

Safety-related requirement of hydraulics ISO 4413

General Safety Electrical equipment IEC 60204


ISO 62061

Electrical Systems and Controls IEC 61508

Electrical Instrumentation IEC 61551


Table 1.3

1.6 Type C Classification: Standalone or Component Level


Example of typical Class C standards in Table 1.4 for product conformity assessment framework.

Type C Classification
Standard
Specific Equipment

Hydraulic presses ISO 16092

Robots, robotic systems ISO 10218 – 1&2

Collaborative robots ISO TS 15066

Woodworking machines ISO 19085

Automated guided vehicles (AGV) ISO 3691

Semi-Conductor Devices IEC 60747


Table 1.4

intertek.se/provning/functional-safety/ 9
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 2
TERMS &
DEFINITIONS
Terms and definitions applied under this document reference shall be made in all cases to the
specific standards and clauses listed in Table 1.5 below. The year of issue has intentionally been
removed on the basis that the current issue of the standard is referred.

Standards & Clauses

ISO 12100: Safety of machinery — General principles for design — Risk assessment and risk reduction, Clause 3.

ISO 10218-1: Robots and robotic devices — Part 1 Robots. Safety requirements for industrial robots, Clause 3.

ISO 10218-2: Robots and robotic devices — Safety requirements for industrial robots. Part 2: Robot systems and integration. Clause 3.

IEC 61508-1: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 1 General Requirements. Clause 3.

IEC 61508-2: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 2 Requirements for
electrical/electronic/programmable electronic safety-related systems Clause 3.

IEC 61508-3: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 3 Software requirements. Clause 3.

IEC 61508-4: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 4 Definitions and abbreviations.
Clause 3.

IEC 61508-5: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 5 Examples of methods for the
determination. Clause 3.

IEC 61508-6: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, Part 6: Application of IEC 61508-2 and
IEC 61508-3. Clause 3.

IEC 61508-7: Functional Safety of Electrical / Electronic / Programable Electronic Safety Related Systems, part 7 Overview of techniques and
measures. Clause 3.

IEC 61511 -1: Functional safety - Safety instrumented systems for the process industry sector - Part 1: Framework, definitions, system, hardware,
and application programming requirements. Clause 3.

IEC 61511-2 Functional safety — Safety instrumented systems for the process industry sector —Part 2: Guidelines for the application. Clause 3.

IEC 61511-3: Functional safety — Safety instrumented systems for the process industry sector Part 3: Guidance for the determination of the
required safety integrity levels. Clause 3.

ISO 13489-1: Safety of machinery — Safety related parts of control systems. Part 1: General principles for design. Clause 3.

ISO 13489-2: Safety of machinery — Safety related parts of control systems. Part 2: Validation. Clause 3
Table 1.5

intertek.se/provning/functional-safety/ 10
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 3
SCOPE
The determination of Performance Level, Safety Integrity Level of Safety Related Parts of a Control
System (SRP/CS), and the downstream impacts of machine construction design is subjected to a
design evaluation, inspection, and certification process which includes affixing the Intertek Functional
Safety Mark. This process applies to the following industry sectors:

• Stand-alone industrial and commercial machinery and equipment


• Stand-alone industrial and service robotics
• Bespoke integrated/automated industrial machinery (incorporating industrial robotics and
indexing systems)
• Energy storage and charging systems and automated guided vehicles (AVGs)
• Machine tools
• Automation systems
• Industrial furnaces
• Refrigeration systems
• Packaging machinery
• Agricultural machines
• Food Processing equipment
• Construction equipment
• Equipment for explosive atmospheres
• Mining
• Oil/Gas/Chemical equipment
• Processing
• Earth-moving & tunnelling
• Cranes/Lifts/MHE
• Forestry/Plant machinery
• And many others

intertek.se/provning/functional-safety/ 11
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 4
ENGINEERING
BLOCK STRUCTURES
To evaluate and determine machine performance and safety integrity levels, including upstream and
downstream impacts on the overall machine design, engineering block structure architecture is used
by selection of Classification Levels A, B1, B2, and C, which form the overall conformity approach
upon selection.
The example below in Figure 1.2 represents a fully integrated automated machinery system,
incorporating standalone machines integrated together to form one complete end-to-end machine
system.
Class A (+Class C) Engineering Block Structure:

intertek.se/provning/functional-safety/ 12
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 5
CONFORMITY
MODULES
5.1 All machinery on application for functional safety shall be subject to a design evaluation,
validation, verification, and certification process using ISO 12100 as the basis of conformity.
5.2 Pending the machine status within the design stage gate, conformity is determined based
on subjecting the machine design to a defined evaluation module, each module uses
selected clauses from ISO 12100 to determine machine conformity by reverse design
calculation as a means of validating and verifying the design intent or protection concept
incorporated into the intended design or build construction of the machine (Intertek
Propriety Standard (INT/FS/2019)).
5.3 The four conformity modules are and illustrated in Figure 1.3 below:
• Conformity Module 1 - Concept (Design Phase)
• Conformity Module 2- Pre-prototype (1st Build)
• Conformity Module 3 - Prototype (Pre-Production Build Phase)
• Conformity Module 4 - Production (In service build)

General outline of design stage gate and conformity module deliverables:

5.4 This figure illustrates the variation of selected clauses of Class A & B standards applied per
specific conformity module when applicable for the determination of conformity.

intertek.se/provning/functional-safety/ 13
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

5.5 Each FS conformity module (ISO 12100 basic level) shall follow the same process of
evaluation by breaking down the risk assessment into four sub modules. This sub module
approach is designed to identify, quantify, validate, and evaluate the risk as illustrated by
Figure 1.4 below.

Risk Mitigation Risk Assessment Risk Reduction Review of Risk


(CI 4) (CI 5) (CI 6) File (CI 7)

Fig. 1.4 (Basic Conformity Approach Topics)

5.6 The engineering block structure as defined within the previous section, Class A standard
(ISO 12100), is the horizontal basis for the machine end-to-end design evaluation
incorporating Class B1 and B2 standards to evaluate by calculation for claimed PL (ISO
13489) and SIL (IEC 62061, 61508, and 61151 Standards series).
Note: Electrical safety of machines is not covered by any of the Functional Safety Standards
ISO 13489, IEC 61508, or IEC 61511 series. For Electrical Safety refer to IEC 60204 series
standards.
5.7 The described same modular approach and sub-module structure, in addition to using the
engineering block structure shall be applied to:
• The complete machine, known as the full system
• A sub system or sub assembly of the complete machine
• A component part of the complete machine or standalone machine

intertek.se/provning/functional-safety/ 14
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 6
CERTIFICATION:
GENERAL REQUIREMENTS
Overview
6.1 The general certification process to be followed for the evaluation of a complete machine,
sub system, assembly, component, or standalone product leading onto the award of an
attestation of conformity or type certificate and affixing of the Intertek Functional Safety (FS)
Mark shall be that outlined in ISO/IEC 17065 and 17067.
APPLICATION REVIEW

6.2 In all cases, the conformity assessment system to be adopted for issuing an attestation of

conformity or type certificate shall undergo a Type 1, 1a, or 3 conformity approach in PLANNING PHASE
accordance with ISO IEC 17067.

6.3 In accordance with ISO 17065, the process for the evaluation of functional safety and the
safe design of a full system (complete machine assembly or standalone machine), sub- DESIGN EVALUATION
system or part assembly of a full system shall undergo and be subject to: ↓
• An application by the applicant for certification (Intertek FS Mark) MANAGEMENT OF
• Signing of a certification agreement specific to the FS Mark and certification program. FUNCTIONAL SAFTEY
• Draw up of the certification plan (defining the standards classification, engineering block (FS MARK ONLY)
structure and conformity module applied).

• Evaluation and validation by design evaluation of the manufacturers risk
assessment/FMEDA for the full system, sub-system or assembly, or standalone VALIDATION
product/component level, PL and SIL claims and applied factor of safety (FoS) applicable ↓
to the safety levels applied to the build construction by assessment to a defined module
of conformity and applicable C classification standards. REVIEW PHASE
• Verification of critical build/assembly aspects related to the construction build by onsite ↓
inspection of key elements identified from the design evaluation/testing and validation
phase. CERTIFICATION PHASE
• Technical review for certification by validation that the full system (complete machine),
subsystem or assembly or standalone product/component meets the conformity
module applied and confirms the PL and SIL claim before recommending an attestation
or type certificate of E.
• Final certification decision is made by ensuring all the steps proceeding the final decision
have been carried out in full before issuing any certification and awarding the affixing of
the Intertek FS Mark.

intertek.se/provning/functional-safety/ 15
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Certification Process
6.4 All calculations and value tables (example MTTFd values) used for the means of design
evaluation and validation confirmation related to functional safety or safe machine design
shall be derived from normative functional safety standards, product, engineering
application standards, and known art from engineering science reference material.
6.5 The design evaluation, validation, and verification (inspection) shall be conducted to
confirm overall safe build of the full system, subsystem or assembly, or standalone
product/component by reverse design engineering techniques (calculation check) or
application of engineering knowledge of sound engineering practices (SEP) and
documented by engineering statement confirmation of design intent as to the safety
integrity of the design build.
6.6 Attestations of conformity shall be issued on successful evaluation, validation, verification,
certification review, and final decision by undergoing and meeting the applicable
requirements of conformity modules 1 and 2 in full, issued for full systems (complete
machines), subsystems or assemblies, or product/component level at the following design
stage gate levels:
• Conformity Module 1 - Concept (Design Phase)
• Conformity Module 2 - Pre-Prototype (1st Build)

Not under any circumstances can a type certificate bearing the Intertek FS Mark be issued
for only completing conformity modules 1 and 2.
6.7 A full type certificate bearing the FS Mark shall be issued on successful evaluation,
validation, verification, certification review, and final decision by undergoing and meeting
the applicable requirements of conformity modules 3 and 4 in full, issued for full systems
(complete machines), subsystems or assemblies, or product/component level at the
following design stage gate levels:
• Conformity Module 3 - Prototype (Pre-production Build Phase)
• Conformity Module 4 - Production (In-service build)

6.8 Certificate ongoing validity for an attestation of conformity or type certificate depends on
the type approved remaining to type during its life cycle. Authorised design changes
impacting the PL, SIL, FoS, and general safety integrity can only be approved by the issuing
body.

intertek.se/provning/functional-safety/ 16
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Functional Safety Mark Usage


6.9 Unauthorised design changes impacting the PL, SIL, FoS integrity, and general safety shall
result in the issued certificate and FS Mark being withdrawn and the application for license
(FS Mark) terminated.
6.10 Abuse or unauthorised use of the Intertek FS Mark by false claim or by advertising through
inappropriate use in all cases shall result in the FS Mark being withdrawn and the
application for licence use (FS Mark) terminated.
6.11 The Intertek Functional Safety (FS) Mark, as illustrated below, shall be awarded on
successfully completing the conformity assessment approach as detailed the section
“Evaluation, Validation and Verification” and demonstrated by Figure 1.5.

Fig. 1.5

Note: “Claims” in the sample Mark above will be annotated with the claim of capability to
respective functional and general international and national standards.

intertek.se/provning/functional-safety/ 17
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Functional Safety Type Examination Certificate: Example


6.12 Example of the functional safety type examination certificate issued for successfully
meeting conformity modules 3 and 4:

TYPE EXAMINATION
CERTIFICATE
• Type Approval Certificate
• Issued for complete Machine Systems
conforming to Modules 1–4
• Issued for E/E/PE Control Systems
• Issued for Component Level/
Standalone Machines
• Covers Management of Functional
Safety (IEC 61508-1 Cl 6)
• Intertek Functional Safety Mark
• 5 Year Certificate Validity Period
• Product Conformity to Class A, B1, or
Class C standards and supporting
evaluation reports
• PL & SIL calculated results
• PL and SIL validated Levels
• Reference to Evaluated Technical
Construction File and Contents
• Accredited to ISO IEC 17065

intertek.se/provning/functional-safety/ 18
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Functional Safety Attestation of Conformation Certificate: Example


6.13 Example of the functional safety attestation of conformity certificate issued for
successfully meeting conformity modules 1 and 2.

ATTESTATION OF
CONFORMITY
• Issued as Type Approval on
completing only Modules 1–4
• No Validity Period
• Issued for either PL rating or SIL
rating, or both
• Validation using A, B, and C
classifications
• Issued for concept or pre prototype
design stage
• Issued for production or prototype
stage of build
• Intertek Functional Safety Mark not
awarded
• Reference to Evaluated Technical
Construction File and Contents
• Accredited to ISO/IEC 17065

intertek.se/provning/functional-safety/ 19
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Functional Safety Certificate of Unit Verification: Example


6.14 Example of the functional safety Certificate of Unit Verification issued for bespoke machines.

CERTIFICATE OF UNIT
VERIFICATION
• Type Approval Certificate
• Issued for bespoke Integrated
Complex Machines & Systems
• Issued for bespoke Standalone
Complex Machines & Systems
• No Assigned Period of Validity
• Type Approval Based on Single one-
off Design
• Product Certification Conformity
(Class A, B1, or Class C)
• PL & SIL Determined
• PL / SIL calculated results
• FSM Required - IEC 61508-1 Cl 6 as a
single one-off event
• Intertek Functional Safety Mark
awarded
• Reference to Evaluated Technical
Construction File and Contents
• Accredited to ISO IEC 17065

intertek.se/provning/functional-safety/ 20
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 7
CONFORMITY
MODULES/VALIDATION:
GENERAL DESCRIPTION
7.1 Reference to Class A, B, and C standards shall be used for the evaluation and validation of
functional safety claims for PL, SIL, and machine safe design. To be achieved by validating
(by calculation) and determination of design FMEDA risk assessment outputs (ISO 12100)
and overall general machine design (determination of FoS and SEP applied). Thereby
demonstrating the machine’s intended safety function(s) during its life cycle and risk has
been adequately reduced.
7.2 Demonstration of PL, SIL, and machine safe design, engineering block structure
architecture, and conformity modules are combined and, when applied, form the FS
conformity evaluation method for:
• Full systems (complete machine or integration of multiple machines) – Class A
• Sub-systems (example SR control systems of a full system) – Class B
• Standalone machines or component(s) – Class C

7.3 Selecting the appropriate modules of conformity to determine the evaluation and
validation method for FS, PL, SIL, and integrity of machine safety to be applied depends
on the stage gate design build status of the machine.
7.4 The conformity modules (1, 2, 3, and 4), when applied as the evaluation and validation
methods, cover the general design intent and safety considerations associated with
industrial machinery and that of the automotive industry for related hazards using ISO
12100 (Class A) as the vertical standard for respective engineering applications within the
build construction:
• Mechanical
• Environment
• Chemical
• Electrical
• E/E/P control systems
• Software
• Cybersecurity (Optional)
• Ergonomics
• Commissioning
• Operability
• Maintenance
• Transportation

intertek.se/provning/functional-safety/ 21
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Engineering Block Structures


7.5 The Functional Safety conformity approach to determine PL, SIL, and overall machine safety is by
selection of Class A + B1 + B2 + C standards, a process demonstrated by forming an engineering block
structure. For example, a pre-production industrial integrated material processing unit incorporating
an input feeder and output conveyer system is illustrated by Figure 1.6 and Table 1.6.

Class A ( + Class C*) Class A ( + Class C*) Class C

B1 B2
+ B1 B2
Class A ( +Class C*)
+ B1
Prod
Std

Class B1 Sub System Class B2 Specific Class C Stand Alone


Controls Standards Systems Standards Standard(s)

INPUT FEEDER MATERIAL INTEGRATED


Fig 1.5: (Engineering Block Structure for Machine Integration):
UNIT PROCESSING UNIT OUTPUT UNIT
Fig. 1.6

FS FS Conformity Machine Applied


Machine Conformity Classification System Controls Reference FS & M/C Design Evaluation
Module (Process) Evaluation Standards
M/C Design Risk Assessment
A A
ISO 12100 & 14121 Evaluation
Material Processing Unit

B B2 IEC 61508-1 General - SIL Requirements


B B2 IEC 61508-2 Hardware - SIL Calculation
B B2 IEC 61508-3 Software - Evaluation
Safety of Electrical Control
B B2
ISO 13489 -1 & 2 Systems - PLr Calculation

4 A
B2 IEC 60204 Machine Electrical Safety
B2 ISO 4413 Hydraulics
B2 ISO 4414 Pneumatics
B1 ISO 13850 Emergancy Stops
B1 ISO 14118 Unexpected Start Up
B1 ISO 14119 Interlocks
B1 ISO 14120 Fixed Moveable Guards
B2 ISO 11161 Machine Integration
Conveyer C C ISO 1049 Conveyer Feeder System
Table 1.6 (Module 4: Standards Classification A, B and C to be applied)

intertek.se/provning/functional-safety/ 22
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 8
EVALUATION,
VALIDATION,
& VERFICATION
8.1 The general approach for the evaluation, validation, and verification leading to
certification of the full system machine, sub-system, or component/standalone machine
for general safety, PL, and SIL is illustrated by the process flow diagram Figure 1.7 below:

EVALUATION PHASE CERTIFICATION PHASE

Design Basis
Evaluation Evaluation Plan

Technical
Design
Review
Evaluation

Design
Certification
Validation

Design
Verification
(On Site
Inspection)

Fig. 1.7 (Conformity Approach Evaluation, Inspection and Certification)

intertek.se/provning/functional-safety/ 23
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

8.2 Design Basis Evaluation


8.2.1 Depending on the stage gate cycle of the construction build the conformity module to be
applied shall be selected the from Table 1.8 below:

Conformity Module Life Cycle Stage Gate

1 Design Concept (Design Phase)

2 Pre-Prototype (First Build)

3 Prototype (Production Phase)

4 Production (In-Service Build)


Table 1.8 (Conformity Module Types)

8.2.2 The assessment criteria related to the risk method outlined in the process flow below (Fig
1.8) identifies the main clauses from ISO 12100 which form the basis of the conformity
modules when applied:

Risk Mitigation Risk Assessment Risk Reduction Review of Risk


(CI 4) (CI 5) (CI 6) File (CI 7)

Fig. 1.8 (Evaluation of Risk Conformity Approach)

8.2.3 The design basis evaluation shall determine that the risk assessment/design FMEDA outputs
of the respective full system (complete machine), sub-system assembly, or component are
representative to the construction build using ISO 12100 as the general guide as
confirmation that the design outputs specify:
• All risks and hazards are identified and are relative to the design intent of the
construction build
• Declared design outputs Identify the hazard mitigation concepts and reference
material (standards) met
• The construction design intent of operating and maximum limits
• A document register is generated listing all supplied design documents

8.2.4 Sub-modules: Determination of classification standards and block structure architecture


applicable (sub-modules within each conformity module and engineering block structure
and Class A + B sub modules) shall determine the horizontal standards (Class B1 and B2) to
be applied, and if applicable outline the C classification standards, (example - module 4:
conformity system process A, B, and C) to be applied.

intertek.se/provning/functional-safety/ 24
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

8.3 Design Evaluation


8.3.1 In general, the reference horizontal and vertical standards applied to evaluate and verify
conformity for functional safety (PL & SIL) and overall machine safety of the design FMEDA/risk
assessment will be dependent on the engineering block structure applied in relation to the overall
construction build, the tables below demonstrate the main normative standards to be used for
the conformity approach and evaluation and validation methods.
Table 1.9 is an example of design evaluation conformity and validation method reference material.

Full System (Integrated Automated Machine) Intended Use – Evaluation Conformity


Industrial Sector Standard

Safety of machinery, general principles for design, risk assessment and ISO 12100 (Applicable
risk reduction Parts)

Safety of Machinery - Principles for the design and integration of safety- ISO 13489-1
related parts of control systems

Safety of Machinery - Safety-related parts of control systems, Validation. ISO 13489 -2


(PLr)

Safety of machinery - Electrical equipment of machines IEC 60204-1

Safety of machinery - Functional safety of safety-related electrical, IEC 62061 or


electronic, and programmable electronic control systems (SIL) IEC 61508-1 / -2

Other Class B1 and B2 standards as applicable pending on construction Class B1 and B2 as


build Applicable

Other Class C Standards if integrated machine specific product standards Class C as Applicable
(if applicable)
Table 1.9 (Full System Machine conformity reference standards)

8.3.2 The conformity assessment process shall be based on the evaluation of the risk outputs of the
FMEDA (ISO 12100), the method of evaluation to determine conformity shall be by design
evaluation, to assure all design outputs meet the risk hazards identified, that applicable horizontal
and vertical classification of standards have been applied and are met in full for:
• Full systems (complete end-to-end build)
• Sub-system assemblies
• Component level or standalone machine

8.3.3 The conformity approach, pending on machine and level of build will use ISO 12100 to identify
engineering design applications incorporated in all types of machine, sub-system and
component/standalone machine level.

intertek.se/provning/functional-safety/ 25
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

8.4 Design Validation


8.4.1 The output results from the design evaluation (determination that all risks have been
identified and mitigated by design intent), the risk assessment design FMEDA
outputs/claimed integrity performance limits (PL), and safety integrity level (SIL) of the
SOURCES OF FAILURE
construction build shall be validated. Functional safety standards generally
recognize two types of failures and then
8.4.2 The validation of the design FMEDA/risk assessment outputs shall be conducted as an propose the means to address them.
example to the specific standards listed in Table 1.10 below.
Random hardware failures are the
easiest to understand in that they are
Validation Method Standard caused by, as the name suggests,
random unexpected failures in
Design intent validation by calculation of SEP applied by FoS & MoS ISO 12100 equipment. The probability of failure
(Margin of Safety) validation due to random failures is expressed as
the PFH (average frequency of
Validation of PLr claims from Design FMEDA, by re-calculation of ISO 13489-1 and Part 2 dangerous failure) for the system. The
declared PLr, calculation to validate PLa actual as confirmation of allowed PFH depends on the required
claimed result SIL and ranges from 10–5/h for SIL 1 to a
minimum of 10–7/h for SIL 3.
Validation of SIL claims from Design FMEDA, by re- calculation of IEC 62061 or Systematic failures are those inherent in
declared SIL, calculation to validate SIL actual as confirmation of IEC 60158 -1/-2 / -3 a design, in the sense that they can only
claimed result be fixed by a design change. Insufficient
EMC robustness can be considered a
Hydraulic Fluid Power – Safety of Systems and Components ISO 4413 systematic error, as can deficiencies in
requirements, insufficient verification
Pneumatic Fluid Power -- Safety of Systems and Components ISO 4414 and validation, and all software errors.
Systematic errors are effectively
Software requirements for E/E/PE IEC 60158-3 weaknesses that exist in every item
Table 1.10 (Listing – Evaluation & Validation) produced rather than being present in
individual units. If the right set of
circumstances arise, the failure will occur
with 100% probability.
8.5 Design Verification
8.5.1 Deemed critical elements of the construction build design appertaining to the overall To be suitable for use in a situation
safety and integrity related to the functional safety of the build and operation of the requiring a SIL X safety function, both
“product” shall be verified by physical inspection on site, either on initial the random and systematic
build/manufacture or on commissioning run up/sign over. requirements given in the standard for
that SIL level must be met. Compliance
8.5.2 The design evaluation and validation phase of the conformity assessment shall identify to the hardware requirements alone is
any deemed component, subassembly, or sub-system to be verified against the design not sufficient.
intent/design evaluation to verify safety and operational performance integrity.
8.5.3 The verification shall be a physical inspection with defined parameters through
measurement, site testing, or a combination of both to determine and confirm
calculations or design limit parameters appertaining to the overall safety and integrity of
the claimed design.
8.5.4 The design verification inspection results shall be used as the final validation of the
overall calculated and documented results to ascertain final safety and functional safety
levels claimed.
8.5.5 Functional safety management at this point shall be reviewed.

intertek.se/provning/functional-safety/ 26
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

8.6 Evaluation Plan


8.6.1 An evaluation plan (certification or test plan) shall be drawn up to identify all areas of the full
system (complete machine), sub-system, or component/standalone machine to be
evaluated.
8.6.2 The evaluation plan shall identify assigned reference standards/methods of validation which
will ensure all areas of the intended design is adequately addressed in terms of evaluating
general and functional safety.

8.7 Technical Review for Certification


8.7.1 The technical review for certification shall consist of a review of the conformity assessment
process outputs and results and determination that the evaluated and validated results
meet the required limits specified within Annex A to F, the results and limit values declared
within the:
• Evaluation plan
• Review of the design basis for evaluation
• Design evaluation
• Design validation
• Design verification

8.8 Certification
8.8.1 The process for certification and award of the Intertek FS Mark shall be conducted in
accordance with Intertek’s internal procedures SMS-FS-OP-19 and Intertek Propriety
Standard INT/FS/2019. On final certification review, confirming that all parts of the technical
review have been satisfactorily completed and all criteria met, Intertek will award the
Functional Safety Mark.

intertek.se/provning/functional-safety/ 27
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 9
FUNCTIONAL SAFETY
MANAGEMENT
9.1 Functional safety management is required under IEC 61508 and IEC 61151 series
standards, the functional safety management infrastructure shall be audited as part of the
site visit inspection phase.
9.2 The objective is the assessment of the lifecycle model implemented, i.e. which parts
within the overall lifecycle are relevant, define responsibilities, and specify management
and technical activities that establish the documentation framework.
9.3 The documented functional safety management plan shall facilitate and demonstrate
compliance to the standards, plan the verification, validation, and assessment activities,
and provide a “live” planning document that can be maintained throughout the lifecycle.
9.4 A typical outline for a functional safety management plan should include:
• Responsibilities of the personnel involved
• The documented lifecycle
• Verification plan
• Validation plan
• Quality planning

9.5 The plan must always fit within the context of a company’s wider framework of risk
management. It cannot be seen in isolation. Functional safety systems implement risk
reduction factors that contribute to an overall risk management strategy.
9.6 The structure of the plan may require many levels of functional safety management
planning:
• An overall company-wide plan
• A plan for an individual operating facility
• A project plan for a specific project

9.7 The system vendors may have plans covering only their scope, similar to a quality process.
A company that has a quality plan will usually prepare separate project execution plans
for individual projects.

intertek.se/provning/functional-safety/ 28
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

9.8 The document/lifecycle plan identifies which stages of the lifecycle apply for the scope of
work planned, being:
• Conceptual design and requirements development
• System design and engineering
• Testing (FAT, SIT, SAT)
• Installation and commissioning
• Operations, maintenance, and ongoing modifications

9.9 Key documents to be identified as outputs from the Functional Safety management plan
and structure include:
• Risk analysis (Design FMEDA)
• Safety requirements specification (SRS)
• Detailed design specifications
• Test specifications

9.10 The Safety Requirements Specification (SRS) is a collation of many elements, including:
• Control and safeguarding philosophy
• SIS architecture specification
• HAZOP reports
• SIL determination report
• Cause and effect charts
• Functional specifications
• SIF narratives
• Ranges, alarm and trip settings schedule
• Overrides

9.11 Detailed design specifications are required; the common elements in detailed design are:
• Hardware fabrication specifications and drawings
• Software architecture
• Software standards
• Detailed functional requirements
• Detailed non-functional requirements

intertek.se/provning/functional-safety/ 29
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

9.12 Considerations for the quality plan include:


• Competency of management
• Procedures – internal operating procedures
• Techniques and measures
• Supplier quality
• Sub-contractors and third-party contractors
• Change management – design change
• Tracking and traceability
• Configuration management
• Issues management (complaints)
• Incidents and performance analysis
• FS audits and assessments

9.13 Key elements of a functional safety management plan are detailed in Figure 1.12:

FUNCTIONAL SAFETY SYSTEM DEVELOPMENT


MANAGEMENT MANAGEMENT

System description
• Safety Planning Concept and
• Development Practices Requirements
• Safety Assessments Safety Requirements

Design

Realisation
• Hazards
• Causes Identify • Residual hazards Safety Assessment
• Consequences
Hazards
Plans
Installation and
Commissioning
Safety Procedures

• Intolerable risks Assess


Assess Test Plans
Residual
Risks Validation
Risks
Safety Tests

Procedures
Operation and
Mitigate
• Severity
Risks • Mitigation action Maintenance
• Frequency • Verification Safety Procedures
• Tolerability • Validation
Procedures
Decommissioning
and Disposal
Fig. 1.12 (Functional Safety Management Process) Safety Procedures

intertek.se/provning/functional-safety/ 30
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 10
COMMON
ABBREVIATIONS
Abbreviation Meaning/Description

SIL Safety Integrity Level


One of four levels to specify the item's or element's necessary requirements.

CCF Common Cause Failures


Failure of two or more elements of an item resulting from a single specific event or root cause. Common cause failures are
dependent failures (DF) that are not cascading failures (CF).

CF Cascading Failure
Failure of an element of an item causing another element or elements of the same item to fail. Cascading failures are dependent
failures (DF) that are not common cause failures (CCF).

CMF Common Mode Failure


A type of common cause failure (CCF) where multiple items fail in the same mode. Analyse using fault tree analysis (FTA).

DC Diagnostic Coverage
Proportion of the hardware element failure rate that is detected or controlled by the implemented safety mechanisms.

DCLS Dual Core Lockstep


Processing system that runs the same set of operations at the same time in parallel.

DF Dependent Failure
Failures whose probability of simultaneous or successive occurrence cannot be expressed as the simple product of the
unconditional probabilities of each of them. Dependent failures include common cause failures and cascading failures.

DFA Dependent Failure Analysis


Aims to identify the single events or single causes that could bypass or invalidate a required independence or freedom from
interference between given elements and violate a safety requirement or a safety goal.

DIA Development Interface Agreement


Agreement between customer and supplier in which the responsibilities for activities, evidence, or work products to be exchanged
by each party are specified.

DTI Diagnostic Test Interval


Amount of time between the executions of online diagnostic tests by a safety mechanism.

E/E/PE Electrical, Electronics, and Programmable Electronic


IEC 61508-4 defines this as based on electrical and/or electronic and/or programmable electronic technology.

EMI Electromagnetic Interference: Disturbance


Effect on an electrical circuit due to either electromagnetic induction or electromagnetic radiation emitted from an external source.

EOS Electrical Overstress

intertek.se/provning/functional-safety/ 31
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Electrical overstress failures can be classified as thermally-induced, electromigration-related, and electric field-related failures. Can
result in a latch-up short circuit.

ESD Electrostatic Discharge


A subclass of Electrical Overstress (EOS). The sudden flow of electricity between two electrically charged objects caused by contact,
an electrical short, or dielectric breakdown.

FIT Failure in Time


The number of failures that can be expected in one billion (1x10^9) device-hours of operation.
Mean time between failures (MTBF) = 1,000,000,000 x 1/FIT

FMEA Failure Mode and Effects Analysis


As opposed to fault tree analysis (FTA), failure mode and effects analysis (FMEA) is an inductive approach focusing on the individual
parts of the system, how they can fail, and the impact of these failures on the system. Analysis starts at faults, which can lead to
errors and then failures.

FMEDA Failure Mode Effects and Diagnostic Analysis


A procedure for the detailed determination of error causes and their impact on the system and can be very efficiently used in the
early stages of systems development for the purpose of early identification of weaknesses.

FTA Fault Tree Analysis


As opposed to failure mode and effects analysis (FMEA), fault tree analysis (FTA) is a deductive (top down) approach starting with
the undesired system behaviour and determining the possible causes of this behaviour.

FTTI Fault Tolerant Time Interval


The time between when a fault occurs and the system can transition to a safe state and be ready to experience another possible
hazard.
Maximum FTTI = DTI + Fault Reaction Time + Safe State

HSI Hardware-Software Interface


Hardware / Software compatibility of diagnostic analysis of input output signal.

LFM Latent Fault Metric


Latent faults are multiple-point faults (whose presence are not detected by a safety mechanism nor perceived by the driver within
the multiple-point fault detection interval (MPFDI). The latent fault metric (LFM) is a hardware architectural metric that reveals
whether or not the coverage by the safety mechanisms, to prevent risk from latent faults in the hardware architecture, is sufficient.

MBU Multiple Bit Upset


When two or more error bits occur in the same word. Cannot be corrected by simple single-bit.

MPFDI Multiple Point Fault Detection Interval


The time span to detect a multiple-point fault before it can contribute to a multiple-point failure.

PMHF Probabilistic Metric for (Random) Hardware Failures


The sum of the single point, residual, and multipoint fault metrics. Is expressed in FITs.

SEL Single Event Latch-up


A type of single event effect (SEE) caused by a single event upset (SEU) that causes a transient fault. This transient fault is "hard" and
can only be corrected by cycling the power.

TD Tool Error Detection


The confidence in measures that prevent the software tool from malfunctioning and producing corresponding erroneous output, or
in measures that detect that the software tool has malfunctioned and has produced corresponding erroneous output.

intertek.se/provning/functional-safety/ 32
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

SECTION 11
CUSTOMER SUPPLIED
TECHNICAL DOCUMENTS
& SPECIFICATIONS
The tables in Section 11 demonstrate the design and technical documents to be supplied in
support of Equipment Under Consideration (EUC) risk assessment mitigation outputs when
meeting ISO 12100 outputs and Design FMEDA for complete machines, (Full Systems) sub-
systems and components/standalone machines.
Note: Not all document references outlined in the tables below may apply, but shall be supplied if
applicable to the EUC.

EUC Technical Documents and Specifications (if applicable) for ISO 12100 risk evaluation

Mechanical design calculations and specifications for the EUC in relation to static / dynamic loads (Stress / Strain load tables) materials,
vibration, emissions, hazardous substances, radiation and impact to the environment.

Design specifications and schematic diagrams for Hydraulic and Pneumatic systems, integrated or standalone industrial Robotics, indexing
systems, welded / fabricated assemblies, cutting systems (abrasive, thermal, acoustic or hydraulic).

Design specification related to Structure stability, foundation type and load stressing, environmental external forces.

Design specifications and calculations for structural – EUC Design specifications for CoG, loads, SWL / MWL / YWL calculations, lifting points.

Specifications related to any chemical hazards used by or omitted from EUC.

Controls (ISO 13489-1 and 13489-2) Design specifications and calculations for EUC active or passive SRCS with related MTTFd values.

Electrical Safety: EUC Design specifications for meeting IEC 60204, composing of electrical systems layout, schematics electrical wiring stress
loading calculations / tables, identified critical components and safety approvals (if any). Component PLa and SIL coding (if any), Electrical
Insulation classifications.

EUC Technical specifications (if applicable) for Grid Code connection, accessibility / creepage and clearance considerations.

Design and calculation (SIL) related to the EUC, Controls IEC 61508 -1 and -2 (E/E/PE) systems, design specifications for component MTTDd,
SIL (If any) SILr calculations.

EUC Electronics: Design specifications and schematics for Analogue / digital electronic systems and components covering static / pulse loads,
deviation, clock sequencing and PCB population levels. Active controls safety chain / loop.

EUC Software – IEC 61508 -3, design specifications and linear or flow layout for safety related functions, such as safe state, fault indication,
error handling, sensor fault detection, fault analysis monitoring, online self - diagnosis, software revisions / uploads, function interfacing,
software communications revisions – safe status, (IEC 60158-2).

intertek.se/provning/functional-safety/ 33
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

EUC Technical Documents and Specifications (if applicable) for ISO 12100 risk evaluation - CONTINUED

EUC Software systems speciation capability, covering Independence Levels, 165 Safety Data Compatibility, Data interface (External Systems)
Inconsistent Data, Corrupt data, Unauthorised Access – Data, and Unauthorised Access -Personnel. Include hardware (IEC 61508-3) All
modes of operation & functions including set up / calibration. Architecture of the system. Logic Platform (if PLC?), Logic flow? Confidence
Scale Level (SF) 1-4 Determination to meet IEC 61508 – 4, Hardware integration and systematic capability, Capacity / Response time,
Equipment / Operator Interface and Self Diagnostic capability.

Ergonomics, Specifications related to Local Environment (Light, Access, Visual Displays), Control Access / Display.

Design specifications / instructions for Machine Set Up, 202 Pre - Machine Set Up, Calibration, Safety Measures – Check, Operation,
Operating Modes, Raw Material Handling, Operating Controls, Operating Parameters, Operating Manual, Management Controls and Final
Product Verification.

Technical Documents related to Commissioning, Machine Assembly, Adjustments, Connection Systems, Power Supply Connections,
Demonstration (Trial Run Up), Preparation - Pre -Maintenance, Fixings (Anchors), Foundation Preparation, Run up - No Load. Run Up - Max
Load.

Maintenance Manuals covering general Housekeeping - Cleaning / Lubrication / Fluid Levels) Disassembly / Re-assembly, Tool Replacement,
Re-setting / Adjustments, Repairs / Modifications, Fault Finding and Fault Modes Process.

Instructions covering Transportation Loading, Packaging, Transportation, Unloading, Unpacking, Dismantling / Disabling and Disposal Plan.

Clause EUC Technical Documents and Specifications for ISO 13489 -1

4.4 Design layout and structure of SRP/CS (component level (All Related Mechanical / Electrical / Electronic parts)

4.5.1 Technical specifications related to all SRP/CS referencing claims for PL, MTTFd, DC, CCF, Structure Claim

FMEA

Software ID code, systematic failure, environmental conditions claim, PL qualifying method, Architecture constraints.

4.5.2 PL Calculation Methods – From either Manufacturers Data, Tables from Annex C & D, Lifecycle Capability (# years)

4.5.5 Category calculation / PL claim less MTTFd calculation

4.7 Calculation method for Verification for PL achieved PLr and PL(sub SRP/CS) >= PLr

6.2.2 SRP/CS Architecture Block Structure documents

6.3 Method and demonstration of combined PL CAT for SRP/CS

intertek.se/provning/functional-safety/ 34
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Clause EUC Technical Documents and Specifications for ISO 13489 - 2

4.2 EUC overall validation plan

4.3 EUC generic System fault list and defined limits

4.4 EUC specific fault list, with mitigation of each fault

4.5 EUC system validation (Software, PL calculation for the entire system)

5 EUC system validation method – comprising of technique for validation adopted

6 Plan for EUC end - product testing / validation

7&8 Technical document related to the EUC safety functions – specification for safety function requirements. Validation plan for
testing and analysis of safety functions.

9 EUC adopted validation method of category specifications, validation of MTTFd, Dcavg and CCF, validation of measures
against systematic failures related to performance level and category of SRP/CS. Validation of safety-related software,
validation and verification of performance level. Validation of combined safety-related parts.

10, 11, 12 EUC validation plan for environmental analysis, maintenance, end user operator instructions

intertek.se/provning/functional-safety/ 35
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Documents to be submitted for IEC 62061

intertek.se/provning/functional-safety/ 36
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Clause EUC Technical Documents and Specifications for IEC 61508-1

7.3.2 Information concerning the EUC, intended operational environment and identified hazards.

7.4.2 Information defining scope of the hazard and risk analysis representative of the EUC.
7.5.2

7.6.2 Specification of the overall safety requirements in terms of the safety functions requirements and safety integrity
7.7.2 requirements. Information on the allocation of the overall safety functions, Detailing target failure measures, and associated
safety integrity levels Assumptions made concerning other risk reduction measures that need to be managed throughout
the life of the EUC.

7.8.2 to Information and results of the overall safety requirements allocation. A plan for the installation of the E/E/PE safety-related
7.15.2 systems;
Specification of the E/E/PE system safety requirements.
A plan for the installation of the E/E/PE safety-related systems; Plan for the commissioning of the E/E/PE safety-related
systems. Fully installed E/E/PE safety elated systems;
Overall safety validation plan for the E/E/PE safety-related systems; Information and results of the overall safety
requirements allocation including installation and maintenance.

Clause EUC Technical Documents and Specifications for IEC 61508-2

7.2.2 E/E/PE system design requirements and specification, describing the equipment and architectures for the E/E/PE system

7.3.2 Plan for the safety validation of the E/E/PE safety related systems

7.4.2 to Design of the E/E/PE safety related systems in conformance with the E/E/PE system design requirements specification Plan
7.4.11 for the E/E/PE system integration test PE system architectural information as an input to the software requirements
specification

7.5.2 Fully functioning E/E/PE safety-related systems in conformance with the E/E/PE system design Results of E/E/PE system
integration tests

7.6.2 E/E/PE system installation, commissioning, operation and maintenance procedures for each individual E/E/PE system

7.7.2 Fully safety validated E/E/PE safety-related systems Results of E/E/PE system safety validation

7.8.2 Results of E/E/PE system modification

7.9.2 As above – depends on the phase Results of the verification of the E/E/PE safety-related systems for each phase

8 Results of E/E/PE system functional safety assessment

7.2.2 E/E/PE safety requirements specification as developed during allocation (see IEC 61508-1) E/E/PE system safety
requirements specification (from IEC 61508-2)

intertek.se/provning/functional-safety/ 37
FUNCTIONAL SAFETY (FS) CERTIFICATION:
PROGRAM & MARK GUIDANCE

Clause EUC Technical Documents and Specifications for IEC 61508-2 - CONTINUED
7.3.2 EUC software safety requirements specification

7.4.3 EUC software safety requirements specification; E/E/PE system hardware architecture design (from IEC 61508-2)

7.4.4 EUC software safety requirements specification; software architecture design

7.4.5 EUC software architecture design; support tools and coding standards

7.4.5 EUC software system design specification; support tools and coding standards

7.4.6 EUC software module design specification; support tools and coding standards

7.4.7 EUC software module test specification; source code listing; code review report

7.4.8 EUC software system integration test specification software

7.5.2 EUC software architecture integration test specification; software/PE integration test specification (also required by IEC
61508- 2). Integrated programmable electronics.

7.6.2 EUC Design and Verification plan and specification for the above

7.7.2 EUC validation plan for software aspects of system safety

7.8.2 EUC software modification procedures; software modification updates on request

7.9.2 EUC appropriate verification plan (dependent on phase)

8 EUC software functional safety assessment plan

intertek.se/provning/functional-safety/ 38
Intertek is a leading Total Quality Assurance provider to industries worldwide. Our
network of more than 1,000 laboratories and offices and over 46,000 people in
more than 100 countries, delivers innovative and bespoke Assurance, Testing,
Inspection and Certification solutions for our customers’ operations and supply
chains. Intertek Total Quality Assurance expertise, delivered consistently with
precision, pace and passion, enabling our customers to power ahead safely.

FOR MORE INFORMATION


Americas
+1 800 WORLDLAB (967 5352)
+1 251 459 6173
Europe
+46 8 750 0000
Asia
+852 2173 8888

[email protected]

intertek.se/provning/functional-safety/

This publication is copyrighted by Intertek and may not be reproduced or transmitted in any form in whole or in part
without the prior written permission of Intertek. While due care has been taken during the preparation of this document,
Intertek cannot be held responsible for the accuracy of the information herein or for any consequence arising from it.
Clients are encouraged to seek Intertek’s current advice before acting upon any of the content.