post tension (Extract of IRC 112)
post tension (Extract of IRC 112)
SECTION 12
SERVICEABILITY LIMIT STATE
12.1 General
(1) In order to verify that the structure and structural elements perform adequately during
service life. The serviceability limit states shall have to be satisfied. The serviceability limit
states are:-
- Stress level
- Crack width
- Deflection
Other limit states such as vibration may be of importance in a particular structure, but are
not covered in this Section.
(2) In calculation of stresses and deflection, the cross-section shall be assumed as uncracked
provided tensile stress in concrete does not exceed fctm or fctm.fl and calculation of minimum
tension reinforcement is also based on the same value of fctm or fctm.fl .Where tensile stresses
exceed fctm or fctm.fl cross-section shall be considered as cracked.
100
IRC:112-2020
12.3 Limit State of Cracking
12.3.1 General
Cracking takes place in tensile regions of concrete structures due to load effects, such as bending,
shear, torsion and direct tension. Cracks may also be caused due to internal deformations such as
shrinkage and temperature effects. The intent of the following provisions is to ensure, with acceptable
probability, that the cracks will not impair the proper functioning or durability of the structure or cause
its appearance to be unacceptable. Cracks due to other effects such as expansive chemical reactions
need to be controlled by measures given under Section 14.
(2) For the crack width checks under combinations which include temperature distribution, the
resulting member forces should be calculated using gross section concrete properties. The
effect of self-equilibrating thermal stresses within a section may be ignored.
101
IRC:112-2020
(3) For members with only unbonded tendons, requirements for reinforced concrete elements
apply. For members with a combination of bonded and unbonded tendons, requirements for
prestressed concrete members with bonded tendons apply.
(4) Crack width may be calculated according to Clause 12.3.4. Alternatively, limiting maximum
bar size or spacing as per Clause 12.3.6 may be deemed to satisfy crack control criteria for
reinforced concrete members.
fct.eff fct.eff
σc.web
103
IRC:112-2020
(3) Contribution of prestressing steel towards minimum reinforcement for crack control
shall be ignored.
(4) In prestressed members, no minimum reinforcement is required in sections where the
concrete is in compression under the rare combination of loads and the characteristic value
of prestress.
However minimum reinforcement for other considerations such as, early thermal and
shrinkage cracking, prior to application of prestressing, shall be provided as per Section 16.
104
IRC:112-2020
(3) In situations where spacing of bonded reinforcement within the tension zone is reasonably
close (i.e. ≤ 5(c+φ/2)), the maximum final crack spacing may be calculated from Eq. 12.8.
0.425 k1 k2
Sr.max
3.4c
.eff
Eq. 12.8
where
φ is the bar diameter. Where bars of different diameters are used in a section, an
equivalent diameter, φeq, should be used. For a section with n1 bars of diameter φ1 and
n2 bars of diameter φ2, the Eq. 12.9 should be used.
n1 12 n2 22
eq
n11 n22 Eq. 12.9
c is the clear cover to the longitudinal reinforcement. Wherever the clear cover exceeds
50 mm a value of 50 mm shall be used in the calculation.
k1 is a coefficient which takes account of the bond properties of the bonded reinforcement:
= 0.8 for deformed bars
= 1.6 for bars with an effectively plain surface
For epoxy coated bars, the above values shall be increased by 25 percent.
k2 is a coefficient which takes account of the distribution of strain:
= 0.5 for bending
= 1.0 for pure tension
For cases of eccentric tension or local areas, intermediate values of k2 should be used
which may be calculated from Eq. 12.10:
105
IRC:112-2020
k2 1 2
21 Eq. 12.10
Where ε1 is the greater and ε2 is the lesser tensile strain at the boundaries of the section
considered, assessed on the basis of a cracked section.
For the case of deformed bars associated with pure bending
3.4c 0.17
Sr.max
,eff
Eq. 12.11
Where the spacing of the bonded reinforcement exceeds 5(c+φ/2) or where there is no
bonded reinforcement within the tension zone, an upper bound limit to the crack width may
be found by assuming maximum crack spacing:
Sr.max= 1.3(h-x)
Eq. 12.12
Where ‘h’ is the effective depth and ‘x’ is depth of neutral axis from the compression face.
(4) Where the angle between the axes of principal stress and the direction of the reinforcement,
for members reinforced in two orthogonal directions ‘y’ & ‘z’, is significant (>15°), then
the crack spacing Sr,max may be calculated from the following expression:
1
Sr ,max
cos sin
Sr ,max. y Sr ,max.z
Eq. 12.13
Where
θ is the angle between the reinforcement in the y direction and the direction of the
principal tensile stress.
Sr,max,y Sr,max,z are the crack spacings calculated in the y and z directions respectively,
according to Clause 12.3.4 (3).
Note: Where simplified methods of calculating crack width are used they should be based on the
properties given in this Code or substantiated by tests.
106
IRC:112-2020
fctk.0.05 is lower characteristic tensile strength (Table 6.5)
(2) The larger tensile principal stress in the web σ1 is compared with the corresponding strength
fctb obtained from Eq. 12.14.
If σ1 < fctb , the minimum reinforcement in accordance with Clause 12.3.3 should be provided
in the longitudinal direction.
If σ1 ≥ fctb, the crack width should be controlled in accordance with Clause 12.3.6 or
alternatively calculated and verified in accordance with Clause 12.3.4 taking into account
the angle of deviation between the principal stress and reinforcement directions.
107
IRC:112-2020
Table 12.3 Maximum Bar Spacing for Crack Control
12.4.1 General
Cable supported bridges are not in the purview of this Code, for which specialist literature may be
followed.
(1) The deflections/deformations of a member or structure shall not be such that it adversely
affects its proper functioning or appearance. In some cases, expected deflections may need
to be adjusted in the structural geometry by pre-cambering, so as to attain the requisite
profile at the time of placing expansion joints and wearing course.
(2) Appropriate limiting values of deflection taking into account the nature of the structure,
bridge deck furniture and functional needs of the bridge, should be established. In the
absence of other criteria, the following deflection limits for live load under frequent load
combination may be considered.
Vehicular : Span/800,
Vehicular and pedestrian or pedestrian alone : Span/1000,
Vehicular on cantilever : Cantilever Span/300, and
Vehicular & pedestrian and pedestrian only on : Cantilever Span/375
cantilever arms
108
IRC:112-2020
Mn Cr+Mo+V Ni+Cu
C.E=C+ + + shall not be more than 0.53 percent, when microalloys/low alloys
6 5 15
are used. When microalloys/low alloys are not used, carbon equivalent using the formula:
Mn
C.E C
6
shall not be more than 0.42 percent.
Reinforcement bars/wires with carbon equivalent above 0.42 percent should, however
be welded with precaution. Use of low hydrogen basic coated electrodes with matching
strength bars/wires is recommended.
(3) Welding shall conform to IS 2751 and IS 9417 except as provided herein.
(4) Generally, shop welding in controlled conditions is to be preferred, where feasible. Site
welding where necessary shall, however, be permitted when the facilities, equipment,
process, consumables, operators, welding procedure are adequate to produce and maintain
uniform quality at par with that attainable in shop welding to the satisfaction of the engineer.
(5) Welding may be carried out by metal arc welding process. Oxyacetylene welding shall not
be permitted. Any other process may be used subject to the approval of the engineer and
necessary additional requirements to ensure satisfactory joint performance. Precautions on
over heating, choice of electrode, selection of correct current in arc welding etc., should be
strictly observed.
(6) All bars shall be butt welded except for smaller diameter bars with diameter of less than 20
mm which may be lap welded. Single-V or Double-V butt joints may generally be used. For
vertical bars single bevel or double bevel butt joints may be used.
(7) Welded joints shall be located well away from bends and not less than twice the bar diameter
away from a bend.
(8) Joint welding procedures which are to be employed shall invariably be established by
a procedure specification and shall be qualified prior to use by tests as prescribed in IS
2751. All welders and welding operators to be employed shall have to be qualified by tests
prescribed in IS 2751. Inspection of welds shall conform to IS 822 and destructive or non-
destructive testing may be undertaken when deemed necessary. Joints with weld defects
detected by visual inspection or dimensional inspection shall not be accepted.
132
IRC:112-2020
(2) At location of mechanical splices reduction in minimum cover may be accepted but should
not be less than 30 mm.
15.2.6
Additional rules for high yield steel deformed (HYSD) bars exceeding 32 mm in diameter
15.2.6.1 General
(1) The rules given below are complementary to those given in Clause 15.2.3.
(2) Splicing by lapped joints shall not be used either for tension or compression bars.
(3) Bars of φ>32 mm shall be used only in elements whose minimum depth is not less than 15
times, the diameter of the bar.
(4) When large bars are used, adequate crack control shall be ensured either by using
surface reinforcement as per Clause 16.3.4(3), or by calculation as per Section 12.
(5) Splitting forces are higher and dowel action is greater with the use of large diameter bars.
Such bars should be anchored with mechanical devices. As an alternative they may be
anchored as straight bars, but links should be provided as confining reinforcement.
(6) Generally large diameter bars should not be lapped. Exceptions include sections with a
minimum dimension 1.0 m or where the stress in steel is not greater than 80 percent of the
design ultimate strength.
(7) Transverse reinforcement, additional to that for shear, should be provided in the anchorage
zones where transverse compression is not present.
(8) For straight anchorage lengths (see Fig. 15.6 for the notation used) the additional
reinforcement referred to in (7) above should not be less than the following:
- in the direction parallel to the tension face:
Ash = 0.25 As.n1 Eq. 15.4
- in the direction perpendicular to the tension face:
Asv = 0.25 As.n2 Eq. 15.5
where
AS is the cross sectional area of an anchored bar,
n1 is the number of layers with bars anchored at the same point in the member
n2 is the number of bars anchored in each layer.
(9) The additional transverse reinforcement should be uniformly distributed in the anchorage
zone and the spacing of bars should not exceed 150 mm.
(10) For surface reinforcement provisions of Section (16.5.4) applies.
The area of surface reinforcement should not be less than 0.01 Act, eff where Act,eff is the area
of cover portion outside the stirrups/links.
133
IRC:112-2020
15.2.7.1 General
(1) Bundle of same Types of Bars
Unless otherwise stated, the rules for individual bars also apply for bundles of bars. In a
bundle, all the bars shall be of the same characteristics, type and grade, and preferably of
same dia. Bars of different diameters can be bundled provided the ratio of diameters does
not exceed 1.7.
(2) Equivalent Diameter
In design, the bundle is replaced by a notional bar having the same sectional area and the
same centre of gravity as the bundle.
The ‘equivalent diameter’ φn of this notional bar is such that:
n nb 55mm
Eq. 15.6
where nb is the number of bars in the bundle, which is limited to:
- Four for vertical bars in compression and for bars in a lapped joint for lap length
portion.
- Three for all other cases.
(3) Use of Equivalent Diameter
For a bundle, provision of Section 15.2.1 applies using the equivalent diameter φn, in
place of φ. Where two touching bars are positioned one above the other, and where bond
conditions are favourable, such bars need not be treated as a bundle.
(4) Minimum Concrete Cover and Spacing of Bar
The equivalent diameter φn, is taken into account in evaluation of the minimum cover and
134
IRC:112-2020
spacing between bundles. However, the minimum cover and spacing are measured from the
actual outside contour of the bundle of bars.
lo lo lo
(3) For compression anchorages, bundled bars need not be staggered. For bundles with an
equivalent diameter ≥32 mm, at least four links having a diameter of ≥12 mm should be
provided at the ends of the bundle within distance of 0.33 lo. One number of further link
should be provided just beyond the end of the curtailed bar.
135
IRC:112-2020
this case the diameter of a single bar may be used to calculate lo. Care should be taken to
ensure that there are not more than four bars in any lap cross section.
136
IRC:112-2020
- Between pair of ducts & next pair ≥ φduct or 50 mm or single duct;
where φduct denotes the outer diameter of the duct (local reduction in spacing at externally jointed
locations of ducts is acceptable).
dg+10mm
Ø
50mm
dg+10mm
Ø
50mm
dg+10mm
Ø
50mm
Note: Where φ is the diameter of post-tension duct and dg is the maximum size of aggregate
Fig. 15.9 Minimum Clear Spacing between Ducts
Note: Where φ is the diameter of pre-tensioned tendon and dg is the maximum size of Aggregate
Fig. 15.10 Minimum Clear Spacing between Pre-tensioned Tendons
137
IRC:112-2020
15.3.1.4 Cable spacing for thin sections and curved portions of cables
Refer Clause 7.10 for special checks and additional recommendations.
138
IRC:112-2020
distribution across the concrete section, is as per Eq. 15.11
(c) Anchorage length, lbpd , over which the tendon force Fpd in the ultimate limit state is
fully anchored in the concrete; see Section 15.3.2.2(3) (d).
ldisp σpd
σpt
lpt
lpt lbpd
ldtsp
139
IRC:112-2020
σpm.o = is the tendon stress just after release
(c) The design value of the-transmission length should be taken depending on the design
situation, given in Eq. 15.9 and 15.10.
lpt,1 = 0.8lpt Eq. 15.9
OR
lpt, 2 = l.2lpt Eq. 15.10
Note: The lower value is used for verifications of local stresses at release, the higher value for ultimate limit states
(shear, anchorage etc.).
(d) Concrete stresses may be assumed to have a linear distribution outside the dispersion
length.
2 2
ldisp
l pt d (Refer Fig. 15.11) Eq. 15.11
(e) Alternative build-up of prestress may be assumed, if adequately justified and if the
transmission length is modified accordingly.
(3) Anchorage of Tensile Force for the Ultimate Limit State
(a) The anchorage of tendons should be checked in sections where the concrete tensile
stress exceeds fctk,0.05. The tendon force should be calculated for a cracked section,
including the effect of shear according to Section 10.3.3.3(6). Where the concrete
tensile stress is less than fctk,0.05 no anchorage check is necessary.
(b) The bond strength for anchorage in the ultimate limit state is:
fbpd = ηp2 η1 fctd Eq. 15.12
where
ηp2 is a coefficient that takes into account the type of tendon and the bond situation
at anchorage
= 1.4 for indented wires or
= 1.2 for 7-wire strands
η1 is as defined in Eq. 15.7.
(c) Due to increasing brittleness with higher concrete strength, fctk,0.05 should here be
limited to the value for M75.
(d) The total anchorage length for anchoring a tendon with stress σpd is:
lbpd = lpt2 + α2φ (σpd - σpm.∞)/fbpd Eq. 15.13
where
l pt2 is the upper design value of transmission length = 1.2 lpt
α2 as defined in Clause 15.3.2.2 (2)
σpd is the tendon stress corresponding to the force described in (a).
σpm.∞ is the prestress after all losses.
(e) Tendon stresses in the anchorage zone are illustrated in Fig. 15.12.
(f) In case of combination of ordinary and pre-tensioned reinforcement, within the same
zone of concrete the anchorage capacities of each may be separately calculated and
added for design verification.
140
IRC:112-2020
(4) Deviators
(a) A deviator shall satisfy the following requirements:
- Withstand both longitudinal and transverse forces that the tendon applies to it
and transmit these forces to the structure;
- ensure that the radius of curvature of the prestressing tendon does not cause any
overstressing or damage to it.
(b) In the deviation zones the tubes forming the sheaths shall be able to sustain the radial
pressure and longitudinal movement of the prestressing tendon, without damage and
without impairing its proper functioning.
(c) The radius of curvature of the tendon in a deviation zone shall not be less than 40
times the diameter of wire/strand.
(d) Designed tendon deviations up to an angle of 0.01 radians may be permitted without
using a deviator. The forces developed by the change of angle shall be considered in
design.
141
IRC:112-2020
SECTION 16
DETAILING REQUIREMENTS OF STRUCTURAL MEMBERS
16.1 General
(1) Detailing requirements given below are in addition to those given in Section 15.
(2) Minimum areas of reinforcement are given in order to prevent a brittle failure, wide cracks
and also to resist forces arising from restrained actions.
(3) In addition to the detailing of reinforcement and prestressing steel, the dimensional
restrictions on various types of elements are also covered.
where
fyd is the design yield strength of the reinforcement,
NEd is the design axial compression force.
Ac is the gross cross-sectional area of concrete.
(4) The maximum cross-sectional area of reinforcement, outside lap portion shall not be more
than 0.04 Ac. At lap section, it shall not be greater than 0.08 Ac.
(5) The longitudinal bars should be distributed around the periphery of the section. For columns
of circular cross-section the minimum number of bars is six. For columns having a regular
142
IRC:112-2020
polygonal cross section or having two adjacent surfaces meeting at any angle, at least one
bar shall be placed near the junction of the two surfaces.
143
IRC:112-2020
16.3 R.C. Walls and Wall Type Piers
(1) These clauses deal with reinforced concrete walls of which the larger dimension measured
horizontally is more than four times the smaller dimension.
(2) The amount and proper detailing of reinforcement may be derived from FEM analysis or
strut-and-tie model within the dispersal zone of concentrated loads. For walls subjected to
predominantly out of plane bending, the rules of slab apply if they are more severe.
144
IRC:112-2020
16.4.1 Detailing rules IRC:112-2011
(1) For wall type pier of non-circular hollow section with length less than four times the width,
the rules for solid columns stipulated in Clause 16.2 will apply.
(2) For wall type pier of non-circular of hollow section with length more than 4 times the
width, the rules as per Clause 16.3 will apply.
16.5 Beams
145
175
IRC:112-2020
16.5.1.3 Length of the longitudinal tension reinforcement and anchorage in tension Zone
The curtailment of longitudinal steel and anchorage of the same in tension zone is done as described
below with help of Fig. 16.2.
(1) Fs is the tensile force in the longitudinal reinforcement obtained by a cross-section analysis
according to Sections 8 & 9 including effect of axial force in member, if any.
(2) For members with shear reinforcement the additional tensile force in the longitudinal
reinforcement due to shear shall be provided in the tensile chord and should be calculated
from ∆Ftd = 0.5.VED (Cot θ-Cot α).
M M
The total force zEd Ftd should be taken not greater than Edz.max where MEd.max is the
maximum moment along the beam.
In the case of prestressed member the spare capacity in the prestressing cable if available
can be used for this requirement.
(3) For members without shear reinforcement ∆Ftd may be estimated by shifting the moment
curve a distance al=d in unfavourable direction according to Clause 10.3.2(6). This ‘shift
rule’ may also be used as an alternative for members with shear reinforcement,
Where
cot cot
aai l z Eq. 16.2
2
where θ is the angle of the concrete strut with the longitudinal axis for the shear reinforcement
calculated according to the variable strut inclination method, as per Section 10.
The additional tensile force is illustrated in Fig. 16.2.
(4) The envelope line of the tensile force carried by the longitudinal reinforcement is obtained
by a horizontal displacement ‘al‘ of the envelope line of Fs.
(5) The resistance of bars within their anchorage lengths may be taken into account, assuming
a linear variation of force as shown in Fig. 16.2. As a simplification this contribution may
be ignored.
(6) For reinforcement in the flange, placed outside the web al should be further increased by
the distance equal to the distance of the bar from the web. (distance x1, x2 in Fig. 16.1).
(7) Curtailed reinforcement should be effectively anchored beyond point where it is no longer
required. The anchorage length (lα) should not be less than larger of distance ‘d’ or lb.net
where ‘d’ is the effective depth of member and lb.net is calculated as per Eq. 15.2 of Section
15.
(8) The diagram of the resisting tensile forces should lie outside the envelope line of the acting
tensile force, displaced as described.
(9) The anchorage lengths of bent-up bars which contribute to the resistance to shear should be
not less than 1.3 lb.net when anchored in the tension zone and 0.7 lb.net when anchored in the
compression zone.
146
IRC:112-2020
Ftd
147
IRC:112-2020
148
178
IRC:112-2020
16.5.2 Shear reinforcement
(1) The shear reinforcement should form an angle of 45° to 90° with the longitudinal axis of
the structural element.
(2) The shear reinforcement may consist of a combination of
(a) Links enclosing the longitudinal tensile reinforcement as well as the compression
zone of concrete,
(b) Bent-up bars;
(c) Shear assemblies in the form of cages, ladders etc. of HYSD bars which do not enclose
the longitudinal reinforcement, but are properly anchored both in the compression
and tension zones.
(3) At least 50 percent of the necessary shear reinforcement should be in the form of links.
(4) Links should be effectively anchored. A lap joint may be allowed in web only for high yield
strength deformed bars.
(5) The shear reinforcement ratio is given by Eq. 16.4
ASW
w
s.bw .sin Eq. 16.4
The minimum value ρw.min for ρw is as given by:
w.min
0.072 fck
f yk
Eq. 16.5
In above equations:
ρw = is the shear reinforcement ratio.
Asw = is the area of shear reinforcement within lengths.
s = is the spacing of the shear reinforcement, measured along longitudinal axis of the
member.
bw = is the minimum breadth of the web of the member.
α = is the angle between the shear reinforcement and the longitudinal axis (i.e. for
vertical stirrups α = 90° and sin α = 1).
(6) The minimum clear distance between vertical legs of shear reinforcement should be largest
of :
• dg + 10 mm
• 40 mm
• 2φ of shear Reinforcement.
(7) The maximum longitudinal spacing sl.max of successive series of stirrups or shear assemblies
should not exceed sl.max , where,
sl.max =0.75d (1+ cot α) Eq, 16.6
(8) The maximum longitudinal spacing of bent-up bars should not exceed sb.max where,
149
IRC:112-2020
Fig. 16.11 Extent of the Inter-Section Zone (in Plan) for the
Connection of Secondary Beams
158
IRC:112-2020
16.14 Anchorage Zones for Post Tensioning Forces
Anchorage zone is defined as the zone within which the concentrated forces of post tensioned anchorages
disperse and spread over the full section of the prestressed structural element.
For the design and amount of reinforcement for the full section and for the local effects, refer Section
13. This reinforcement should be detailed to meet requirements of Clause 13.5 as well as to satisfy the
following rules. Extra reinforcement over and above the calculated amount as per Clause 13.5 shall be
provided, if needed, to satisfy these rules.
(1) Anchorage zones should always be provided with distributed reinforcement near all surfaces
in the form of an orthogonal mesh.
(2) Where groups of post-tensioned cables are located at a certain distance from each other,
suitable links should be arranged at the ends of the members, as a protection against splitting
away of groups.
(3) All reinforcement should be fully anchored.
(4) Where a strut and tie model has been used to determine the transverse tensile force, the
following detailing rules shall be followed:
(a) The steel area actually required to provide the tie force, acting at its design strength,
shall be distributed in accordance with the actual tensile stress distribution, i.e. over
a length of the block approximately equal to its greatest lateral dimension.
(b) Closed stirrups should be used for anchorage of ties.
159
IRC:112-2020
SECTION 17
DUCTILE DETAILING FOR SEISMIC RESISTANCE
17.1 General
(1) Ductile detailing shall be carried out for bridges located in zones III, IV and V of seismic
zone map of IRC:6, if they are designed for Response reduction factor R>1.0
(2) The rules of this Section apply to bridges designed for ductile behaviour for improving
their seismic resistance and aim to ensure a minimum level of curvature/rotation ductility
at the plastic hinges. These are supplementary to the rules given in Sections 15 & 16 which
remain applicable, unless specifically modified in this Section.
(3) In general, plastic hinge formation is not allowed in the superstructure. Therefore there is
no need for application of detailing rules of this Section for the superstructure.
(4) Bridge foundation system shall be designed, as far as practicable, to remain elastic under
design seismic action and foundations shall not be intentionally used as a means of energy
dissipation through phenomenon of hysteresis.
(5) The bridge shall be proportioned and detailed in such a manner that plastic hinges can
occur only at pre-determined locations and not at any other locations.
(6) Where longitudinal reinforcement is curtailed potential of formation of hinge shall be
avoided just beyond the point of curtailment. Not more than 1/3 of longitudinal reinforcement
available at the section shall be curtailed.
17.2.1 Confinement
17.2.1.1 General requirements
(1) Within the potential plastic hinge regions, ductile behaviour of the compression zone of
concrete shall be ensured by providing confinement of concrete.
(2) Confinement is implemented through rectangular hoops and/or cross-ties or through circular
hoops or spirals.
(3) In potential hinge regions where the normalised axial force ηk exceeds the limit,
N ED
nk 0.064, Eq. 17.1
Ac fck
confinement of the compression zone in accordance with Clause 17.2.1.4 shall be provided.
(4) The required quantity of confining reinforcement expressed as ratio ωwd is calculated as per
Eq. 17.2 and shall satisfy the requirements of Clause 17.2.1.2:
w . f yd
wd
fcd Eq. 17.2
where
(a) In rectangular sections:
ρw is the volumetric ratio of transverse reinforcement defined as:
160
IRC:112-2020
A
w sw
S L .b Eq. 17.3
where
A sw = is the area of the stirrups and ties in one direction of confinement.
SL = is the spacing of hoops or ties in the longitudinal direction
b = is the dimension of the concrete core perpendicular to the direction of the
confinement under consideration, measured to the outside of the perimeter hoop.
(b) In circular sections:
Volumetric ratio ρw of the hoops/spiral reinforcement relative to the concrete core is
given by Eq. 17.4:
4 Asp
w
D .S
sp L Eq. 17.4
where
Asp is the area of the spiral or hoop bar
Dsp is the diameter of the spiral or hoop
SL is the spacing of these bars
Note: Bars inclined at an angle a to the transverse direction shall be assumed to contribute to the
total area Asw or Asp in Eq. 17.3 by their area multiplied by (cos α)
161
IRC:112-2020
(4) For circular sections, the minimum confining reinforcement provided by hoops/spiral is
determined as the higher of two values given in Eq. 17.7
ωwd.c ≥ max (1.4ωw.req; 0.18) Eq. 17.7
(5) When rectangular hoops and cross-ties are used, the minimum reinforcement condition
shall be satisfied in both transverse directions
(1) When the design length Lh of potential plastic hinges shall be estimated as
the larger of the following two values:
- the depth of the pier section within the plane of bending (perpendicular to the axis of
rotation of the hinge);
- the distance from the point of maximum design moment to the point where the design
moment is 80 percent of the value of the maximum moment.
(2) When 0.48 ≥ ηk > 0.24 the design length of the potential plastic hinges as determined in (1)
shall be increased by 50 percent.
(3) The design length of plastic hinges (Lh) estimated above should be used exclusively for
detailing the reinforcement of the plastic hinge. It should not be used for estimating the
162
IRC:112-2020
plastic hinge rotation.
(4) When confinement is required, the reinforcement specified in Clause 17.2.1.2 shall be
provided over the entire length of the plastic hinge. Outside the length of the hinge, the
transverse reinforcement may be gradually reduced to that required by other criteria. The
amount of transverse reinforcement provided over an additional length Lh adjacent to
the theoretical end of the plastic hinge, shall not be less than 50 percent of the confining
reinforcement required in the region of plastic hinge.
163
IRC:112-2020
(5) The confinement shall extend at least upto the length where the value of the compressive
strain exceeds 0.5 εcu2.
164
IRC:112-2020
When Al is at any inclination to the transverse outer tie, then the As shall be divided
by the Sine of the angle between the outer transverse tie and this tie, e.g. in case Al is
inclined at 45 degrees to the outer tie, then As shall be divided by Sin 45, hence As =
√2 x (0.5 As1 + As2 + 0.5 As3)
(3) Along Circular section boundaries, restraining of longitudinal bars should be achieved
through circular ties determined by :
(mm2/m)
Eq. 17.9
where
Al is the area of one circular tie, in mm2.
SL is the spacing of the circular tie along the axis of the member, in m;
ρl is the reinforcement ratio of the longitudinal steel;
D is the Diameter of the Circular section in mm
fyt is the yield strength of the tie; and
fys is the yield strength of the longitudinal reinforcement.
165
IRC:112-2020
17.2.3 Other rules
(1) Due to the possibility of loss of concrete cover in the plastic hinge region, the confining
reinforcement shall be anchored by 135° hooks around a longitudinal bar. Where 90º bend
is used as per Clasue 17.2.2(2), the bar shall extend by minimum 10 diameters into the core
concrete.
(2) Similar anchoring or a full strength weld is required for the lapping of spirals or hoops
within potential plastic hinge regions. In this case laps of successive spirals or hoops, when
located along the perimeter of the member, should be staggered.
(3) Splicing by lapping or welding of longitudinal reinforcement is not allowed within the
plastic hinge region.
(4) The confinement steel and buckling preventing reinforcement shall not be added together.
(5) The buckling prevention and confinement steel may be provided through a set of hoops or
single leg cross ties. The hoops shall engage the longitudinal bars only, while single leg
ties shall engage both the longitudinal bars and the transverse hoops in the manner shown
below at the 135 Degree bent hook. Such ties need not comply with cover requirements at
such engagement locations.
17.3 Foundations
17.3.1 General
Spread foundations (such as footings, rafts), wells, box-type caissons, etc. shall not enter the plastic
range under the design seismic action and hence do not require any special ductile detailing of
reinforcement.
166
IRC:112-2020
17.3.2 Pile foundations
(1) When it is not feasible to avoid localised hinge formation in the piles by designing pier to
form hinges earlier (capacity protection method), integrity and ductile behaviour of piles
shall be ensured as given below.
(2) The following locations along the pile should be treated as potential plastic hinges.
(a) At the pile heads adjacent to the pile cap, when the rotation of the pile cap about a
horizontal axis transverse to the seismic action is restrained by the large stiffness of
the pile group.
(b) At location of maximum bending moment in piles taking into account soil-pile
interaction, using appropriate stiffnesses of both pile, pile cap and soil.
(c) At the interfaces of soil layers with markedly different shear deformability (e.g.
change of strata).
(3) At location of type 2(a), confining reinforcement of the amount specified in Clause 17.2.1.1
along a vertical length equal to 3 times the pile diameter, shall be provided.
(4) Unless a more accurate analysis is made, longitudinal as well as confining reinforcement
of the same amount as that required at the pile head, shall be provided over a length of two
pile diameters on each side of the point of maximum moment at location of type 2(b) and
of each side of the interface at locations of type 2(c).
167
IRC:112-2020
SECTION 18
18.1 General
This Section gives specifications of materials to be used in construction of new concrete bridges and
standards to which they should conform. For new construction, the Indian Standards, referred below or
any specific international standards governing these materials, shall be the latest revisions thereof. The
tables and notes below table given in this Section are reproduced for ready reference from the relevant
IS Codes listed in Annexure A-3.
For assessment of properties of materials in existing bridges, the standards in force at the time of their
construction or the actual standards used for procurement, shall be referred to. The time dependency of
properties shall also be taken into account in such cases.
168
IRC:112-2020
Table 18.1 Reinforcing Steel
Relevant BIS
Type of Steel
Yield Stress/
proof stress/
0.2% proof-
actual 0.2%
Designation
yield stress
Minimum
elongation
Minimum
stress ƒyk
Standard
Strength,
Min. %
Grade /
Tensile
than
Bars upto & including
IS:432 410 MPa 23
20mm dia. = 250 MPa
Mild Steel Grade-I (Part-1)-
1982 20mm ≤dia 50mm
410 MPa 23
240 Mpa
110% (not less than
Fe 415 14.5
485MPa)
IS:1786 415 MPa 112% (not less than
Fe 415D 18.0
500MPa)
Fe 415S ≥ 125% 20.0
108% (not less than
Fe 500 12.0
545MPa)
High Strength
IS:1786 500 MPa 110% (not less than
Deformed Steel Fe 500D 16.0
565MPa)
(HSD Steel)
Fe 500S ≥ 125% 18.0
106% (not less than
Fe 550 10.0
585MPa)
IS:1786 550 MPa
108% (not less than
Fe 550D 14.5
600MPa)
106% (not less than
Fe 600 IS:1786 600 MPa 10.0
660MPa)
Note:
1. Elongation on a gauge length of 5.65√A, where A is the cross-sectional area of the test
piece, when tested in accordance with IS:1608.
2. For seismic zones III, IV & V, HSD steel bars having minimum elongation of 14.5% and
conforming to other requirements of IS:1786 shall be used.
3. For seismic zones III, IV and V, HSD steel bars shall possess following properties:
a. The actual 0.2% proof strength of steel bars based on tensile test must not exceed
their characteristic 0.2% proof strength by more than 20 percent.
b. The ratio of the actual ultimate strength to the actual 0.2 percent proof strength/yield
strength shall be at least 1.15.
169
IRC:112-2020
layer, to a minimum 72-79 percent of zinc as the innermost layer above the base steel. These layers
increase the corrosion resistance of steel.
The strength as well as elongation and bond properties are not adversely affected by galvanising.
170
IRC:112-2020
18.3.2 Nomenclature, grade designation, strength, elongation and relaxation
The following grades of steel having characteristics as mentioned in Table 18.3 to 18.5, are permitted
for use in bridges designed for normal life.
For other bridges mentioned in Clause 5.8.1 wires/strands having smaller diameters than those given in
the Tables, but otherwise meeting the requirements of Indian Standards mentioned therein, can be used.
171
IRC:112-2020
(3) For acceptance, all samples tested from a batch shall meet requirement of minimum breaking load and
proof load as per IS 6006 and IS 14268.
10, 12, 16, 20, 22, 25, 28, 32. 980 MPa 80% of specified tensile
strength
Notes:
(1) Elongation at failure shall not be less than 10 percent measured on gauge length of 5.65 √A where A is the
area of cross-section of steel bar.
(2) The 1000 hour relaxation when tested at 70 percent of UTS shall not be more than 49 N/mm2.
(3) For acceptance of test results from a lot, a value calculated as arithmetic mean minus 0.6 of the range of test
results shall be more than the minimum strength and elongation specified as per IS 2090.
(4) 0.2 percent proof stress shall not be less than 85 percent of minimum tensile strength.
18.3.3.1 Ductility
The requirements of ductility at fracture are deemed to be satisfied by use of steel having the minimum
elongations specified in Clause 18.3.2.
The wires/strands shall pass the bendability test (reverse bending test) as specified in relevant Indian
Standards.
172
IRC:112-2020
18.4.1 Cement
The cement shall be any of the following. The selected type should be appropriate for the intended use.
If any other cement conforming to other International Standards is used, it shall be corresponding to
one of the types listed above and shall meet the minimum specifications of the Indian Standards.
173
IRC:112-2020
18.4.4 Aggregates
18.4.4.1 General
All coarse and fine aggregates shall conform to IS:383 and shall be tested to conform to IS:2386 Parts
I to VIII.
18.4.5 Water
Water used for mixing and curing shall be clean and free from injurious amounts of oils, acids, alkalis,
salts, sugar, organic materials or other substances that may be deleterious to concrete or steel.
(1) In case of doubt regarding development of strength, the suitability of water for producing
concrete shall be ascertained by the compressive strength and initial setting time tests
specified in (3) & (4).
(2) The sample of water taken for testing shall represent the water proposed to be used for
concreting, due account being paid to seasonal variation. The sample shall not receive any
treatment before testing other than that envisaged in the regular supply of water proposed
for use in concrete. The sample shall be stored in a clean container previously rinsed out
with similar water.
174
IRC:112-2020
(3) Average 28 days compressive strength of at least three 150 mm concrete cubes prepared with
water proposed to be used, shall not be less than 90 percent of the average strength of three
similar concrete cubes prepared with distilled water. The cubes shall be prepared, cured and
tested in accordance with the requirements of IS:5l6.
(4) The initial setting time of test block made with the appropriate cement and the water
proposed to be used, shall not be less than 30 minutes and shall not be more than 30
minutes from the initial setting time of control test block prepared with the same cement
and distilled water. The test blocks shall be prepared and tested in accordance with the
requirements of IS 4031 (Part 5).
(5) The pH value of water shall not be less than 6. Potable water is generally considered
satisfactory for mixing concrete. As a guide the following concentrations represent the
maximum permissible values:
(a) To neutralise 100 ml sample of water, using phenolphthalein as an indicator, it should
not require more than 5 ml of 0.02 normal NaOH. The details of test are given in
Clause 8.1 of IS 3025 (Part 22).
(b) To neutralise 100 ml sample of water, using mixed indicator, it should not require
more than 25 ml of 0.02 normal H2SO4. The details of test shall be as given in Clause
8 of IS 3025 (Part 23).
(c) Permissible limits for solids shall be as given in Table 18.6.
Table 18.6 Permissible Limit for Solids
175
IRC:112-2020
Except ordinary concrete with strength designations of M-15 & M-20, the design mix of standard
concrete and high performance concrete shall be established by laboratory / field testing and controlled
at site by conducting tests to confirm suitability of constituent materials, as per the relevant codes
mentioned in Clause 18.4. The concrete shall meet the acceptance criteria as per Clause 18.6. Mix
design shall be modified if it does not meet the acceptance criteria.
Concrete Total Quantity of dry aggregate by mass Proportion of fine Maximum quantity
Grade per 50 kg of cement to be taken as the sum aggregate to coarse of water per 50kg
of individual masses of fine and coarse aggregate (by mass) of cement (litres)
aggregate (Kg) P.C.C. R.C.C.
M15 350 Generally 1:2, subject 25 -
M20 250 to upper limit 1:1.5 25 22
and lower limit 1:2.5
176
IRC:112-2020
(3) Mix Design for High Performance Concrete
General: Choice of materials, concrete mix design and field practices are quite critical, so that optimum
performance can be extracted of each of the ingredients. The procedure of mix proportioning of normal
grades of concrete may not be adequate. Relationships between the compressive strength of concrete
and water/cement ratio (or water-cement + cementitious materials ratio, when part of the cement is
replaced by mineral admixtures) and between water content and workability will have to be established
by laboratory trials for the grade of concrete, the materials to be used, and the water-reducing efficiency
of the superplasticiser.
The minimum cement content of concrete, inclusive of any mineral admixtures, shall be not less than
380 kg/m3.
The ratio of water/(all cementitious materials including cement) should generally not exceed 0.33, but
in no case more than 0.40.
Field Trial Mixes: Mix proportions arrived at by laboratory trials shall, in addition, be verified to be
satisfactory under field conditions and necessary adjustments made. Field trial mixes shall be prepared
for all grades of concrete, using samples of approved materials.
The concreting plant and means of transportation employed to make trial mixes and to transport them
to representative distances shall be similar to the corresponding plant and transport to be used in the
works. The optimum sequence of mixing of ingredients shall be established by trials. Mixing time may
be longer than in normal grade concrete mixes.
The temperature of concrete at the time of placement shall not exceed 25°C. The temperature of
concrete at the mixing stage should be lower, to allow for rise in temperature during transport. When
considerable distance of transport is involved, particular attention should be paid to ensure retention of
slump as targeted for placement.
Use of Mock-up Testing: Further mock-up testing may be carried out to ensure that the concrete can
be satisfactorily placed and compacted, taking into account the location of placement and provision
of reinforcement, and adjustments made in concrete mix design and/or detailing of reinforcement
accordingly.
177
IRC:112-2020
adjustments at batching plants so that properties of concrete at placement are as per the
requirements.
(c) In order to get a relatively quicker idea of the quality of concrete, optional tests on beams
for modulus of rupture at 72 ± 2 h or at 7 days, or compressive strength tests at 7 days
may be carried out in addition to 28 days compressive strength test. For this purpose,
the acceptable values should be arrived at, based on actual testing. In all the cases, the
equivalent 28 days compressive strength shall be the criterion for the acceptance/rejection
of the concrete.
(d) Additional samples may be required for various purposes such as to determine the strength
of concrete at 7 days or at the time of transfer of prestress or striking the formwork, or to
determine the duration of curing, or to check the testing error. Additional samples may also
be required for testing samples cured by accelerated methods as described in IS 9013. The
specimen shall be tested as described in IS 516.
(2) Test Specimen and Sample Strength
Three test specimens constitute one sample for any type of test at specified age of testing. The average
of these results of three samples constitute the test result of sample provided that the individual variation
is within ±15 percent of average. If variation is larger, the sample shall be discarded.
(3) Frequency of Sampling
The minimum frequency of sampling of concrete of each grade shall be in accordance with Table 18.8.
At least one sample shall be taken from each batch of work. For the purpose of acceptance as per Table
18.8, quantity of concrete represented by a group of four consecutive samples shall include all batches
and single sample shall represent the batch from which it is taken.
Where concrete is provided continuously at site from a batching plant or RMC plant, groups
of four consecutive samples, shall not have overlapping common samples. Irrespective of other
methods of controlling production used at the batching/RMC plant the requirements of this Clause
shall be met.
178
IRC:112-2020
18.6 Acceptance Criteria
18.6.1 General
Acceptance or rejection of concrete is mostly based on compressive strength. However, other properties
of the concrete in fresh and hardened states including durability are also important.
Apart from meeting the acceptance criteria given below, concrete is liable to be rejected if it is porous
or honey-combed, its placing has been interrupted without providing a proper construction joint, the
reinforcement has been displaced beyond the tolerances specified, or construction tolerances have
not been met. However, the hardened concrete may be accepted after carrying out suitable remedial
measures.
179
IRC:112-2020
18.6.6 Chloride content
The chloride content in the concrete can be measured as described in IS 14959 – Part I (for fresh
concrete) or Part II (for hardened concrete). Alternatively it can be calculated, in which case, the
method of calculation shall be based upon the measured chloride-ion contents of all constituents and
the mix proportion of concrete. The chloride-ion content so measured or calculated and expressed
as the percentage of chloride-ion by mass of cement, shall not exceed the value specified in Clause
14.3.2.3.
180
IRC:112-2020
18.7.2 Properties in the Fresh State
The filling ability and stability of self-compacting concrete in the fresh state can be defined by four key
characteristics. Each characteristic can be assessed by one or more test methods (Table 18.9).
181
IRC:112-2020
18.8 Grouting
18.8.1 General
Grout is a homogenous mixture of cement and water. It may contain chemical admixtures which
modify the properties of grout in its fluid state. These recommendations cover the cement grouting of
post tensioned tendons of prestressed concrete members of bridges.
The purpose of grouting is to provide permanent protection to the post tensioned steel against corrosion
and to develop bond between the prestressing steel and the surrounding structural concrete. The grout
ensures encasement of steel in an alkaline environment for corrosion protection and by filling the duct
space it prevents water collection and freezing.
A critical feature of grout is that it should remain pumpable for the time required to fully inject the
tendon.
182
IRC:112-2020
18.8.2 Materials
(1) Water
Only clean potable water free from impurities conforming to Clause 18.4.5 shall be used. No sea or
creek water is to be used at all.
(2) Cement
The same type of cement as used in construction of prestressed elements, should be used for preparation
of the grout. It should be as fresh as possible and free from any lumps.
(3) Sand
(4) Admixtures
Acceptable admixtures conforming to IS 9103 may be used if tests have shown that their use improves
the properties of grout, i.e. increasing fluidity, reducing bleeding, entraining air or expanding the grout.
Admixtures must not contain chlorides, nitrates, sulphides, sulphites or any other products which are
likely to damage the steel or grout. When an expanding agent is used, the total unrestrained expansion
should not exceed 10 percent. Aluminium powder as an expanding agent is not recommended as doubts
exist about its long term effects.
Alternatively, the dry materials may be batched in a factory for pre-mixed grout and mixed with the
liquid materials on site as per instructions of the manufacturers.
It is essential that the grout is maintained in a homogenous state and of uniform consistency so that
there is no separation of cement during the entire grouting process. It is, therefore, necessary that the
grout be continuously mixed in a colloidal mixer with a minimum speed of 1000 RPM and travel of
discharge not exceeding 15 m per second.
Before grouting, the properties of the grout mix should be tested. Tests should be conducted for each
job periodically.
Water/cement ratio should be as low as possible, consistent with workability and should not exceed
0.40.
183
IRC:112-2020
(2) Deleterious Materials
No chloride, sulphates shall be separately added to the grout. The constituent may contain chlorides/
sulphates. However, its net effect should not exceed the following limits in the grout:
- Chlorides (Cl-) not more than 0.1 percent by weight of cement.
- Sulphate (SO3) not more than 4 percent by weight of cement.
- Sulphide-ions (S2-) not more than 0.01 percent by weight of cement.
(3) Temperature
The temperature of the grout after accounting for the ambient temperature of the structure, shall not
exceed 25°C.
(4) Compressive Strength
The compressive strength of 100 mm cube of the grout shall not be less than 27 MPa at 7 days or 30
MPa at 28 days. Cubes shall be cured in a moist atmosphere for the first 24 hours and subsequently in
water. These tests shall be conducted in advance to ascertain the suitability of the grout mix. The 7 day
strength is not mandatory if the 28 day strength requirement is met.
(5) Setting Time
Initial setting time of grout shall be more than three hours and less than 12 hours. The final setting time
shall not be less than 24 hours.
(6) Bleeding
Bleeding is the separation of free water from the grout mix. It includes the filtering effect of strands
where the cavities between the wires constituting the strand, block cement particles and permit water
under pressure to move ahead of the grout in the direction of general flow of grout. The bleeding shall
be sufficiently low to prevent excessive segregation and sediment of the grout material. The bleeding
shall not exceed 0.3 percent of volume of the initial volume of grout after three hours kept at rest.
(7) Volume Change
Volume change of the grout at rest for 24 h shall be within the range of - 1 % and + 5 % of the original
volume when tested as per EN 445. It should not be more than +0.2 percent at 28 days.
(8) Fluidity
Fluidity is tested as per EN 445 by a) cone test and b) grout spread test. The time for cone test (as per
Fig 18.2a) shall be less than or equal to 25 seconds. The spread of the grout as per grout spread test (as
per Fig 18.2b) shall be greater than or equal to 140 mm.
For retention of fluidity there shall not be more than 20% reduction in fluidity at 30 minutes when
tested as per EN 445.
184
IRC:112-2020
185