0% found this document useful (0 votes)
15 views

MFM Meter

The document contains test certificates for various electrical components at the Diamond 30MW Solar Power Plant in Karnataka, including multifunction meters, vacuum circuit breakers, current transformers, and potential transformers. Each section details the specifications, general checks, operational checks, and test results, confirming that all equipment tested is within acceptable limits and deemed fit for operation. The testing was conducted by Super Grade Electrical Contractor and verified by Greenko O & M.

Uploaded by

reltecempmails
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views

MFM Meter

The document contains test certificates for various electrical components at the Diamond 30MW Solar Power Plant in Karnataka, including multifunction meters, vacuum circuit breakers, current transformers, and potential transformers. Each section details the specifications, general checks, operational checks, and test results, confirming that all equipment tested is within acceptable limits and deemed fit for operation. The testing was conducted by Super Grade Electrical Contractor and verified by Greenko O & M.

Uploaded by

reltecempmails
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 12

Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Calibration date Calibration due date


Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel
TEST CERTIFICATE FOR MULTIFUNCTION METER

1.0. Name plate details :


Make SECURE
Type Elite 440
Class 0.5S
CTR 100/1A
PTR 33KV/110V.AC
Sl. No. D0300310
Import Initial Reading 65.1Mwh
Final Reading 65.3Mwh
Export Initial Reading 26985.2Mwh
Final Reading 26985.4Mwh
2.0. General check :
Item Description Result
1 Physical inspection of the Meter  Yes  N/A PASS
2 AC/DC Voltage Checks  Yes  N/A PASS
3 Panel Earthling Checks  Yes  N/A PASS
4 Inspect for physical damage / defects.  Yes  N/A PASS
3.0.Test Parameter :
A) Energy Measurement :
Load Applied Units Meter Reading In Watt hours
In (%) Taken
To be Found Left As
10% 0.10 100 100.02 100.02
50% 0.20 200 200.03 200.03
100% 0.40 400 400.04 400.04
B) Power Measurement
Active Power :
Phase Voltage applied Current applied Measured Power Calculated Power % Error
In(V.AC) In(A.AC) In(MW) In(MW)
R 63.51∟0° 1∟0° 5.70 5.71 0.175
Y 63.51∟240° 1∟240° 5.70 5.71 0.175
B 63.51∟120° 1∟120° 5.70 5.71 0.175

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Reactive Power :
Phase Voltage applied Current applied Measured Power Calculated Power % Error
In(V.AC) In(A.AC) In(Mvar) In(Mvar)
R 63.51∟90° 1∟0° 5.70 5.71 0.175
Y 63.51∟-30° 1∟240° 5.70 5.71 0.175
B 63.51∟210° 1∟120° 5.70 5.71 0.175
B) Voltage Measurement :
Voltage applied In (V.AC) Voltage Measured In (Kv.AC)
Phase
50 % 100 % 50 % 100 %
R 31.75 63.51 9.524 19.05
Y 31.75 63.51 9.525 19.03
B 31.75 63.51 9.529 19.03
C) Current Measurement.
Current Applied In (%) Current Measured In (A.AC)
Phase
25% 50% 75% 100% 25% 50% 75% 100%
R 25 50 75 100 24.99 49.99 75.13 99.97
Y 25 50 75 100 25.04 50.05 74.99 100.09
B 25 50 75 100 24.89 50.00 74.98 100.05
D) Power Factor Measurement :
Applied Power Factor Measured Power Factor
0.80 Lag 0.802 Lag
0.80 Lead 0.803 Lead
1.00 Unity 1.02 Unity
E) Frequency Measurement :
Phase Applied Frequency Measured Frequency Calculated Frequency % Error
In(Hz) In(Hz) In(Hz)
R 50 50 50 0.0
Y 50 50 50 0.0
B 50 50 50 0.0

4.0. Accuracy and Status :


Accuracy Status
With In The Limit Tested Good
5.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Certificate No Page No
Calibration date Calibration due date
Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel

TEST CERTIFICATE FOR VACCUM CIRCUIT BREAKER

1.0. Name plate details :


Make ABB
Type OVB-VBF 36.9.5225
Rated Voltage 36 KV
Rated Current 1250A
Short Time Current 25 KA For 3 Sec
Operating Sequence 0-0.3S-Co-3min-Co
Opening Coil 24 V.DC
Closing Coil 24 V.DC
Sl.No. 1VYN020216003518

2.0. General check :


Item Description Result
1 Physical inspection of the Breaker  Yes  N/A PASS
2 AC/DC Voltage Checks  Yes  N/A PASS
3 Panel Earthling Checks  Yes  N/A PASS
4 Inspect for physical damage / defects.  Yes  N/A PASS

3.0. Operational Checks :


Rack IN/OUT Mechanism Checked and found “OK”
Manual/Electrical Spring Charge Operation Checked and found “OK”
Manual/Electrical Close/Open Operation Checked and found “OK”
Operating Mechanism Checked and found “OK”
HT Isolating contacts Checked and found “OK”
Auxiliary Contacts (BB1BB2) Checked and found “OK”
Vacuum interrupters Checked and found “OK”
OC Coil Resistance Checked and found “OK”
CC Coil Resistance Checked and found “OK”
Operation Counter Checked and found “OK”

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

4.0.Insulation Resistance Test :


Breaker "OFF" Breaker "ON"
R - R' 6.74GΩ R–Y 7.49GΩ R–E 2.43GΩ R - R' 0
Y - Y' 8.97GΩ Y–B 5.21GΩ Y–E 4.24GΩ Y - Y' 0
B - B' 7.87GΩ B–R 4.23GΩ B–E 2.31GΩ B - B' 0

5.0. Contact Resistance Test :


Phase R Y B
Current Applied 101.1 A 101.1 A 101.2 A
Resistance Measured 30.80 µΩ 28.2 µΩ 25.3 µΩ

6.0. Timing Test :


Phase Close time In(mS) Open time In(mS) Close - Open time(mS)
TC1 TC2
R 75.3 26.0 26.0 37.3
Y 73.1 26.0 26.0 38.9
B 73.4 25.0 26.0 37.0

7.0. Status :
Breaker Tested Good, Fit for Operation.

8.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Certificate No Page No
Calibration date Calibration due date
Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel

TEST CERTIFICATE FOR CURRENT TRANSFORMER

1.0. Name plate details :


Make Pragathi Electricals
Cores Core-1 Core-2
Class 0.5 5P
Burden 2.5VA 2.5VA
CT Ratio 100/1A 100/1A
S. No. R-Phase 16/370891
Y-Phase 16/370865
. B-Phase 16/370892

2.0. General check :


Item Description Result
1 Physical inspection of the CT  Yes  N/A PASS
2 Panel Earthling Checks  Yes  N/A PASS
3 Inspect for physical damage / defects.  Yes  N/A PASS

3.0.Winding Resistance Test : (Measured In Ω)


Phase R Y B
Core-1 1.2 1.2 1.2
Core-2 2.2 2.2 2.2

4.0.Insulation Resistance Test :


Voltage applied (Primary to Earth, Primary to Secondary 5KV) and (Secondary to Earth 500V)
Phase Primary-Earth Primary to Secondary Secondary to Earth
(Applied 5KV) P-C1 P-C2 C1-E C2-E
R 31.9 GΏ 21.5 GΏ 15.5 GΏ 25.5 GΏ 31.6 GΏ
Y 38.9 GΏ 25.6 GΏ 16.1 GΏ 31.5 GΏ 36.1 GΏ
B 40.1 GΏ 30.1 GΏ 17.1 GΏ 40.1 GΏ 39.9 GΏ
5.0.Ratio Test :
Phase CT Ratio Primary current Secondary current measured In(A.AC)
injected In (A.AC) Core-1 Core-2
25 0.26 0.25
R 100/1-1A 50 0.51 0.51
75 0.76 0.74
100 1.00 1.01

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

25 0.25 0.26
Y 100/1-1A 50 0.49 0.51
75 0.74 0.75
100 0.99 1.01
25 0.25 0.24
B 100/1-1A 50 0.50 0.50
75 0.76 0.74
100 0.99 1.01

6.0.Polarity,Accuracy & Status :


Polarity Accuracy Status
Tested OK With In The Limit Tested Good

7.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Certificate No Page No
Calibration date Calibration due date
Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel

TEST CERTIFICATE FOR POTENTIAL TRANSFORMER

1.0. Name plate details :


Make Lamco Industries Pvt Ltd
Core 1 2 3
Ratio 33KV/√3/110V//√3 33KV/√3/110V//√3 33KV/√3/110V//√3

Class 0.5/3P 3P 3P
Burden 50VA 50VA 50VA
S.no R-Phase 16/370924
Y-Phase 16/370931
B-Phase 16/371952

2.0. General check :


Item Description Result
1 Physical inspection of the PT  Yes  N/A PASS
2 Panel Earthling Checks  Yes  N/A PASS
3 Inspect for physical damage / defects.  Yes  N/A PASS

3.0.Winding Resistance Test : (Measured In Ω)


Phase R Y B
Core-1 0.2 0.2 0.2
Core-2 0.4 0.4 0.4
Core -3 0.3 0.3 0.3

4.0.Insulation Resistance Test : (Measured In GΩ)


Voltage applied (Primary to Earth, Primary to Secondary 5KV) and (Secondary to Earth 500V)
Phase R Y B
Primary 31.9 38.9 40.1
to Earth
Primary C1 C2 C3 C1 C2 C3 C1 C2 C3
to Sec 21.5 15.5 15.5 25.6 16.1 15.5 30.1 17.1 15.5
Sec to C1 C2 C3 C1 C2 C3 C1 C2 C3
Earth 25.5 31.6 15.5 31.5 36.1 15.5 40.1 39.0 15.5
Between C1-C2 C2-C3 C1-C3 C1-C2 C2-C3 C1-C3 C1-C2 C2-C3 C1-C3
core 25.5 31.6 23.0 31.5 36.1 24.3 40.1 39.0 25.5

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

5.0.Ratio Test :
Phase Primary voltage Secondary voltage measured In(V.AC)
applied In(V.AC) Phase Core-1 Core-2 Core-3
RY 415 ry 1.38 1,39
YB 415 yb 1.39 1.39
BR 415 br 1.39 1.39 0.462
415 rn 0.80 0.80
415 yn 0.80 0.80
415 bn 0.80 0.80

6.0.Polarity,Accuracy & Status :


Polarity Accuracy Status
Tested OK With In The Limit Tested Good

7.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Certificate No Page No
Calibration date Calibration due date
Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel

TEST CERTIFICATE FOR LIGHTNING ARRESTER

1.0. Name plate details :


Make Lamco Industries Pvt Ltd
Type LSM
Rated Voltage 30KV,10KA
S.no R-Phase 72
Y-Phase 55
B-Phase 59
Y-Phase 16/370931
B-Phase 16/371952

2.0. General check :


Item Description Result
1 Physical inspection of the LA  Yes  N/A PASS
2 Earthling Checks  Yes  N/A PASS
3 Inspect for physical damage / defects.  Yes  N/A PASS

3.0.Insulation Resistance Test : (Measured In MΩ)


Voltage applied (5KV)
Circuit Ref R Y B
Primary-Earth 7.44 7.34 6.98

4.0. Accuracy & Status :


Accuracy Status
With In The Limit Tested Good

5.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M


Certificate No Page No

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

Calibration date Calibration due date


Customer details M/s. Diamond 30MW Solar Power Plant,
Voravoo Kavala,Challakere.
Chitradurga (Dist)
Karnataka.
Location Diamond Block-3
System 33KV ICOG Panel

TEST CERTIFICATE FOR INVERTER DUTY TRANSFORMER

1.0. Name plate details :


Make Danish Pvt.Ltd
Output (KVA) 4500
Type of Cooling ONAN
Rated Voltage HV 33000V.AC
Rated Voltage LV 405x4
Rated Current HV 78.73
Rated Current LV 1603.80
Vector Group Dy11y11y11y11
% Imp.Voltage 5.451-5.764
SL.No. 16084001

2.0. General check :


Item Description Result
1 Physical inspection of the Transformer  Yes  N/A PASS
2 Earthling Checks  Yes  N/A PASS
3 Inspect for physical damage / defects.  Yes  N/A PASS

3.0.Insulation Resistance Test : (Measured In GΩ)


Voltage applied (5KV)
Circuit Ref Measured Value
LV 1 2.65
LV 2 Earth 2.05
LV 3 1.98
LV 4 2.28

4.0.PI Value Test : (Measured In GΩ)


Circuit Reference 1 Minute 10 Minute PI
HV-E 3.11 5.76 1.85
LV 1 4.90 6.99 1.42
HV-LV LV 2 3.89 6.09 1.56
LV 3 3.20 5.26 1.64
LV 4 3.90 5.19 1.33

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

5.0.Ratio Test :
Primary voltage applied Secondary voltage measured
Tap In(V.A.C) In(V.A.C)
No LV-1 LV-2
RY YB BR ry yb Br rn yn bn
1 418 416 419 4.65 4.63 4.65 4.65 4.63 4.65
2 417 416 417 4.76 4.74 4.77 4.76 4.74 4.76
3 416 417 418 4.87 4.85 4.87 4.87 4.85 4.87
4 418 418 417 4.99 4.96 4.99 4.99 4.96 4.99
5 418 417 418 5.12 5.09 5.12 5.11 5.08 5.12
6 417 416 419 5.25 5.21 5.24 5.24 5.22 5.25
7 416 417 418 5.40 5.35 5.40 5.40 5.37 5.40
8 419 418 417 5.54 5.50 5.54 5.55 5.50 5.55
9 420 419 418 5.70 5.65 5.70 5.69 5.66 5.69
Primary voltage applied Secondary voltage measured
Tap In(V.A.C) In(V.A.C)
No LV-3 LV-4
RY YB BR ry yb br rn Yn bn
1 418 416 419 4.65 4.63 4.65 4.64 4.63 4.65
2 417 416 417 4.77 4.74 4.76 4.76 4.74 4.76
3 416 417 418 4.87 4.85 4.87 4.87 4.85 4.87
4 418 418 417 5.00 4.97 5.00 5.00 4.97 5.00
5 418 417 418 5.12 5.09 5.13 5.12 5.09 5.15
6 417 416 419 5.26 5.23 5.26 5.26 5.23 5.26
7 416 417 418 5.41 5.36 5.41 5.40 5.35 5.41
8 419 418 417 5.56 5.52 5.54 5.56 5.51 5.55
9 420 419 418 5.70 5.66 5.70 5.69 5.67 5.70
6.0. Magnetizing Current.(Measured in mA)
Tap.no R Y B
1 2.8 1.5 2.4
2 2.7 1.6 2.3
3 3.0 1.9 2.6
4 3.1 2.0 2.5
5(N) 3.3 2.1 2.8
6 3.2 2.0 2.9
7 3.8 2.3 3.2
8 3.7 2.4 3.1
9 4.5 2.9 3.9

TESTED BY VERIFIED BY Greenko O & M

No.254/5,3rd Main Road, Mahalakshmi Layout, Bangalore - 560086,


Super Grade Electrical Contractor, CEIG Testing Licence Holder & Consultants

7.0. Core Balance : For Tap no-5


Circuit Ref Voltage measured(V.AC)
YB RY BR
R-Open
417 253 164.5
BR RY YB
Y-Open
420 339.5 76.8
RY YB BR
B-Open
420 321.9 101.4
8.0.Vector Group: Dy11y11y11y11
Circuit Ref 1V2W = 1V2V 1W2W < 2V1W
LV-1 413=413 415<420
LV-2 413=413 414<420
LV-3 413=413 414<420
LV-4 413=413 414<420
9.0.Winding Resistance Test :
Tap no For HV Measured in (Ω) at 25°C
1U1V 1V1W 1W1U
1 1.256 1.251 1.254
2 1.247 1.243 1.244
3 1.223 1.228 1.225
4 1.201 1.205 1.204
5(N) 1.198 1.192 1.196
6 1.165 1.166 1.161
7 1.136 1.138 1.132
8 1.117 1.110 1.115
9 1.056 1.050 1.052
For LV Measured In (mΩ) at 25°C
2U2V 2V2W 2W2U
0.85 0.82 0.86
0.85 0.86 0.89
0.89 0.90 0.91
0.94 0.96 0.93
10.0. Accuracy & Status :
Accuracy Status
With In The Limit Tested Good

11.0. Standard Used :

TESTED BY VERIFIED BY Greenko O & M