220 KV Switchgear Tcc-All Devices - Brief & Sort (Ac, DC)

The document outlines protective device settings for relays, specifically focusing on overcurrent relay settings for various bus configurations. It includes details such as manufacturer, model, current settings, time delays, and trip elements for different phases and neutral configurations. The settings are categorized by bus type and include specific parameters for each relay ID.

Uploaded by

reltecempmails
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views1 page

220 KV Switchgear Tcc-All Devices - Brief & Sort (Ac, DC)

The document outlines protective device settings for relays, specifically focusing on overcurrent relay settings for various bus configurations. It includes details such as manufacturer, model, current settings, time delays, and trip elements for different phases and neutral configurations. The settings are categorized by bus type and include specific parameters for each relay ID.

Uploaded by

reltecempmails
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Protective Device Settings - Relay

K
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam) Direct. (67) Preload.
PT / Multip.

Manufacturer Base Block


CT Settings Device Level Prim. Time Prim. Time
Designated Bus Relay ID & Trip Element Current Curve Pickup Pickup TOC by Direction Setting Setting
Ratio Group Function /Stage Amps Delay Amps Delay
Model Setting IOC

Schneider
220 KV O/G TO
Bus7 Electric 600:1 Group 1 Overcurrent Phase OC1 IEC Extremely Inverse 0.770 462.000 0.880 10.000 6000.00 0.01 s Enabled
160 MVA TRF
P141

Schneider
220 KV O/G TO
Bus7 Electric 600:1 Group 1 Overcurrent Neutral OC1 IEC Standard Inverse 0.150 90.000 0.190
160 MVA TRF
P141

Schneider
220 KV O/G TO
Bus20 Electric 3000:1 Group 1 Overcurrent Ground OC1 IEC Standard Inverse 0.200 600.000 0.120
160 MVA TRF
P141

Schneider
220 KV O/G TO 80
Bus5 Electric 600:1 Group 1 Overcurrent Phase OC1 IEC Extremely Inverse 0.390 234.000 0.935 5.000 3000.00 0.01 s Enabled
MVA TRF
P141

Schneider
220 KV O/G TO 80
Bus5 Electric 600:1 Group 1 Overcurrent Neutral OC1 IEC Standard Inverse 0.080 48.000 0.250
MVA TRF
P141

Schneider
220 KV O/G TO 80
Bus17 Electric 1600:1 Group 1 Overcurrent Ground OC1 IEC Standard Inverse 0.180 288.000 0.215
MVA TRF
P141

Schneider
220 KV
Bus6 Electric 600:1 Group 1 Overcurrent Phase OC1 IEC Extremely Inverse 0.950 570.000 1.200
TRANSFER BUS
P141

Schneider
220 KV
Bus6 Electric 600:1 Group 1 Overcurrent Neutral OC1 IEC Standard Inverse 0.200 120.000 0.305
TRANSFER BUS
P141

Schneider
MAIN BUS-1 220 KV BUS TIE Electric 600:1 Group 1 Overcurrent Phase OC1 IEC Extremely Inverse 0.950 570.000 0.850
P141

Schneider
MAIN BUS-1 220 KV BUS TIE Electric 600:1 Group 1 Overcurrent Neutral OC1 IEC Standard Inverse 0.200 120.000 0.400
P141

Schneider
Bus14 220 KV INCOMER Electric 600:1 Group 1 Overcurrent Phase OC1 IEC Extremely Inverse 0.950 570.000 1.200
P141

Schneider
Bus14 220 KV INCOMER Electric 600:1 Group 1 Overcurrent Phase OC2 IEC Standard Inverse 0.080 48.000 0.025 Reverse
P141

Schneider
Bus14 220 KV INCOMER Electric 600:1 Group 1 Overcurrent Neutral OC1 IEC Standard Inverse 0.200 120.000 0.500
P141