This document provides a guide on configuring Event Monitor Service alarms for the Moxa ioLogic E1212 device. It outlines prerequisites, detailed steps for modifying the AlarmConfiguration.XML file, and testing the configuration. The article also includes links to related resources for further assistance.

Uploaded by

xamih31059
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

This document provides a guide on configuring Event Monitor Service alarms for the Moxa ioLogic E1212 device. It outlines prerequisites, detailed steps for modifying the AlarmConfiguration.XML file, and testing the configuration. The article also includes links to related resources for further assistance.

Uploaded by

xamih31059
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

TOOL HUB

Community Libraries Suppor t Par tners Log in

Welcome to Pelco
Support
How can we help?

Search the Community

Current Technical Support Hold Times:


Live Chat: 0 minutes, SMS: 0 minutes, WhatsApp: 0 minutes, Phone: 0 minutes

Support Home > Articles

Follow

Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

Understand how to configure the Event Monitor Service Alarms for the Moxa ioLogic E1212 remote ethernet i/o.

Mar 23, 2023 • Knowledge

Title
Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

Product Portfolio
Pelco

Environment
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 1/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

Moxa ioLogic E1212 remote ethernet i/o.

Platform / Operating System

Browser

Issue
Event Monitor Service alarms are not triggering with Moxa ioLogic E1212 device.

Resolution
Prerequisites:

Event Monitoring Service is installed on machine on your network - See article Installing And Configuring
Event Monitor Service (/s/article/Installing-And-Configuring-Event-Monitor-Service?language=en_US&r=171&ui-
knowledge-components-aura-
actions.KnowledgeArticleVersionCreateDraftFromOnlineAction.createDraftFromOnlineArticle=1)
Event Monitoring has been licensed for your system
Cameras and Monitors in the environment have been numbered
Your Moxa device has been given a static IP address for your network - See article Assigning a static IP
address to Moxa ioLogic E1212 (/s/article/Assigning-a-static-IP-address-to-Moxa-ioLogic-E1212?
language=en_US&r=171&ui-knowledge-components-aura-
actions.KnowledgeArticleVersionCreateDraftFromOnlineAction.createDraftFromOnlineArticle=1)
Verify that you are using the correct build for Moxa E1212 - Version 2.5 Build16091211
This can be found by typing in the IP address of your Moxa Device into a web browser. The
information is displayed on the top of the home screen

Configuring AlarmConfiguration.xml for Moxa E1212

1. Download a new AlarmConfiguration.XML file HERE (https://resources.pelco.com/technical-


support/Video%20Management/VxE/VX%20Integrations/AlarmConfiguration.xml)
2. Press Windows + R and run the services.msc command. Navigate to the VideoXpert Event Monitor
Service, right click it and select Stop

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 2/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

3. Navigate to the install path of Event Monitor Service. The default location is C:\Program Files
(x86)\Pelco\VxEventMonitorService
4. Replace the existing AlarmConfiguration.XML with the new file you downloaded
5. Right click AlarmConfiguration.XML and edit it Notepad as Administrator, or Notepad++
a. This article will reference lines within the XML file. For this reason Notepad++ is recommended.
6. Edit line 4, Device IP, to contain the IP address of your Moxa Device
7. The steps below will be an example of how to configure Alarm 1 to send Camera 5 to Monitor 3, in cell
3 of a 2x2 layout
a. Lines 9-69 will define Alarm 1
b. [Setting Screen layout]
i. Modify line 24 to 3, will select monitor 3
ii. Modify line 32 to 2x2 to set it to a 2x2 layout.
c. [Sending Camera to Monitor/Cell]
i. Modify line 36 to 3 to select monitor 3
ii. Modify line 37 to 3 to select cell 3
iii. Modify line 38 to 5 select camera 5
d. [Inactive Alarm State] - This configuration will remove the camera once the alarm returns to an
inactive state
i. Modify line 67 to 3 to select monitor 3
ii. Modify line 68 to 3 to select cell 3
8. Save the XML file
9. Press Windows + R and run the services.msc command. Navigate to the VideoXpert Event Monitor
Service, right click it and select Start
10. Test the event by connecting contact D10 to the GND.
a. You should see camera 5 on monitor 3, in cell 3 of a 2x2 layout while the connection to the
contact is complete
b. When releasing the contact the camera should be cleared from the cell
c. See below for a diagrams for connecting ALARM 1 contacts

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 3/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 4/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

Cause
The AlarmConfiguration.XML is not configured to work with the Moxa Device

Additional Notes
A GUI method of setting up the System is to use the Event Monitor Tool:
https://www.pelco.com/partners/technical-partners/videoxpert-integrations/pelco-event-monitor-service/
(https://www.pelco.com/partners/technical-partners/videoxpert-integrations/pelco-event-monitor-service/)

A configuration manual exists for configuring using the Tool:


https://assets.pelco.com/media/62645d6d-c375-41a9-8259-b7f295fddf49/C6682M-
A_EventMonitorConfigTool_InstallAndOpsMan_103020.pdf (https://assets.pelco.com/media/62645d6d-c375-41a9-8259-
b7f295fddf49/C6682M-A_EventMonitorConfigTool_InstallAndOpsMan_103020.pdf)

Keywords

Knowledge Article Total View Count


1,229

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 5/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

URL Name
Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212

Article Number
000139898

Article Visible To
Public, End Customer, Partner

Discontinued Product? Electrical Shock Hazard?

Potential Data Loss? Electrostatic Discharge Required?

Complex Procedure Required?

Pelco - Video Managemen… Pelco - Cameras & Access…


(/s/topic/0TODo000000b… (/s/topic/0TODo000000b…

Was this article helpful?

Terms of Use Disclaimer - The information provided in this article is intended to help guide customers on how to
address situations that they may encounter with their products. Care has been taken to ensure the accuracy of the
information on this site. Motorola Solutions Inc. and its affiliates and subsidiaries, including but not limited to Avigilon
Corporation and Pelco Inc., assume no responsibility or liability for any errors or omissions in the content of this
article, or any data or configuration loss that may result by employing this information, which is provided “as is” and
“as available”, with no guarantees of completeness, accuracy, usefulness or timeliness. By using this article, you agree
to these terms and conditions.

Related Helpful Articles


Installing And Configuring Event Monitor Service (/s/article/Installing-And-Configuring-Event-
1.18K
Monitor-Service)

Assigning a static IP address to Moxa ioLogic E1212 (/s/article/Assigning-a-static-IP-address-to-


140
Moxa-ioLogic-E1212)

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 6/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

VideoXpert - Event Monitor Configuration Tool appears not to accept settings


401
(/s/article/VideoXpert-Event-Monitor-Configuration-Tool)

Creating an Alarm on a Camera through the Event Monitor Configuration Tool


456
(/s/article/How-do-I-create-an-Alarm-for-a-Camera-on)

Display the sensing camera in the external monitor when a motion or alarm event is de-
tected (/s/article/Display-the-sensing-camera-in-the-external-monitor-when-a-motion-or-alarm-event-is-de- 361
tected-1538586661030)

Still Need Help?

Ask The Community

Submit A Support Case

Products Solutions

VideoXpert Enterprise Industries


(https://www.pelco.com/products/video- (https://www.pelco.com/solutions/#expl
management-solution- ore)
videoxpert/videoxpert-enterprise/) Capabilities
VideoXpert Professional (https://www.pelco.com/solutions/capab
(https://www.pelco.com/products/video- ilities/)
management-solution-videoxpert/vxpro/)
Cameras
(https://www.pelco.com/products/camer
as/)
Accessories
(https://www.pelco.com/products/acces
sories/)

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 7/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

Special Modification Requests


(https://www.pelco.com/products/specia
l-modification-requests/)
Professional Services Partners

Field Services Global Distribution Partners


(https://www.pelco.com/professional- (https://www.pelco.com/partners/global-
services/field-services/) distribution-partners/)
Remote Services
(https://www.pelco.com/professional-
services/remote-services/)
VxCare Packages
(https://www.pelco.com/professional-
services/vxcare-packages/)
Blog Legal

Pelco Blog End User License Agreement - Camera


(https://www.pelco.com/pelco-blog/) Firmware EULA
(https://www.pelco.com/about/legal/end
-user-license-agreement-eula/)
Preference Center
(https://www.pelco.com/about/legal/pelc
o-communication-preference-center/)
Regulatory Notices
(https://www.pelco.com/about/legal/reg
ulatory-notices/)
Do Not Sell My Personal Information
(https://www.motorolasolutions.com/en_
us/about/privacy-
policy.html#californiaresidents)
Terms of Use
(https://www.motorolasolutions.com/en_
us/about/terms-use.html)
Privacy and Cookie Policy
(https://www.pelco.com/about/legal/pelco-
privacy-policy/)

(https://www.facebook.com/pelcovideo) (https://www.instagram.com/PelcoVideo)

(https://www.linkedin.com/company/pelco/) (https://www.youtube.com/pelcovideo)

https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 8/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212

(https://twitter.com/pelcovideo)

© 2022 Pelco, Inc.