Understand how to configure the Event Monitor Service Alarms for the Moxa ioLogic E1212 remote ethernet i/o.
Title
Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
Product Portfolio
Pelco
Environment
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 1/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
Browser
Issue
Event Monitor Service alarms are not triggering with Moxa ioLogic E1212 device.
Resolution
Prerequisites:
Event Monitoring Service is installed on machine on your network - See article Installing And Configuring
Event Monitor Service (/s/article/Installing-And-Configuring-Event-Monitor-Service?language=en_US&r=171&ui-
knowledge-components-aura-
actions.KnowledgeArticleVersionCreateDraftFromOnlineAction.createDraftFromOnlineArticle=1)
Event Monitoring has been licensed for your system
Cameras and Monitors in the environment have been numbered
Your Moxa device has been given a static IP address for your network - See article Assigning a static IP
address to Moxa ioLogic E1212 (/s/article/Assigning-a-static-IP-address-to-Moxa-ioLogic-E1212?
language=en_US&r=171&ui-knowledge-components-aura-
actions.KnowledgeArticleVersionCreateDraftFromOnlineAction.createDraftFromOnlineArticle=1)
Verify that you are using the correct build for Moxa E1212 - Version 2.5 Build16091211
This can be found by typing in the IP address of your Moxa Device into a web browser. The
information is displayed on the top of the home screen
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 2/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
3. Navigate to the install path of Event Monitor Service. The default location is C:\Program Files
(x86)\Pelco\VxEventMonitorService
4. Replace the existing AlarmConfiguration.XML with the new file you downloaded
5. Right click AlarmConfiguration.XML and edit it Notepad as Administrator, or Notepad++
a. This article will reference lines within the XML file. For this reason Notepad++ is recommended.
6. Edit line 4, Device IP, to contain the IP address of your Moxa Device
7. The steps below will be an example of how to configure Alarm 1 to send Camera 5 to Monitor 3, in cell
3 of a 2x2 layout
a. Lines 9-69 will define Alarm 1
b. [Setting Screen layout]
i. Modify line 24 to 3, will select monitor 3
ii. Modify line 32 to 2x2 to set it to a 2x2 layout.
c. [Sending Camera to Monitor/Cell]
i. Modify line 36 to 3 to select monitor 3
ii. Modify line 37 to 3 to select cell 3
iii. Modify line 38 to 5 select camera 5
d. [Inactive Alarm State] - This configuration will remove the camera once the alarm returns to an
inactive state
i. Modify line 67 to 3 to select monitor 3
ii. Modify line 68 to 3 to select cell 3
8. Save the XML file
9. Press Windows + R and run the services.msc command. Navigate to the VideoXpert Event Monitor
Service, right click it and select Start
10. Test the event by connecting contact D10 to the GND.
a. You should see camera 5 on monitor 3, in cell 3 of a 2x2 layout while the connection to the
contact is complete
b. When releasing the contact the camera should be cleared from the cell
c. See below for a diagrams for connecting ALARM 1 contacts
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 3/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 4/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
Cause
The AlarmConfiguration.XML is not configured to work with the Moxa Device
Additional Notes
A GUI method of setting up the System is to use the Event Monitor Tool:
https://www.pelco.com/partners/technical-partners/videoxpert-integrations/pelco-event-monitor-service/
(https://www.pelco.com/partners/technical-partners/videoxpert-integrations/pelco-event-monitor-service/)
Keywords
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 5/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
URL Name
Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212
Article Number
000139898
Article Visible To
Public, End Customer, Partner
Terms of Use Disclaimer - The information provided in this article is intended to help guide customers on how to
address situations that they may encounter with their products. Care has been taken to ensure the accuracy of the
information on this site. Motorola Solutions Inc. and its affiliates and subsidiaries, including but not limited to Avigilon
Corporation and Pelco Inc., assume no responsibility or liability for any errors or omissions in the content of this
article, or any data or configuration loss that may result by employing this information, which is provided “as is” and
“as available”, with no guarantees of completeness, accuracy, usefulness or timeliness. By using this article, you agree
to these terms and conditions.
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 6/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
Display the sensing camera in the external monitor when a motion or alarm event is de-
tected (/s/article/Display-the-sensing-camera-in-the-external-monitor-when-a-motion-or-alarm-event-is-de- 361
tected-1538586661030)
Products Solutions
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 7/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
(https://www.facebook.com/pelcovideo) (https://www.instagram.com/PelcoVideo)
(https://www.linkedin.com/company/pelco/) (https://www.youtube.com/pelcovideo)
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 8/9
11/27/23, 10:47 AM Configuring Event Monitor Service Alarms for Moxa ioLogic E1212
(https://twitter.com/pelcovideo)
https://support.pelco.com/s/article/Configuring-Event-Monitor-Service-Alarms-for-Moxa-ioLogic-E1212?language=en_US 9/9