User Manual Easergy P5 Protection Relay_P5_EN_M_33C
User Manual Easergy P5 Protection Relay_P5_EN_M_33C
Protection Relay
User Manual
07/2021
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Protection Relay
Table of Contents
General information ..................................................................................13
Legal notice .............................................................................................13
Purpose ...................................................................................................13
Safety information and password protection................................................14
Abbreviations ...........................................................................................15
Range description .....................................................................................17
Introduction ................................................................................................18
Selection guide by application ...................................................................18
Function table ..........................................................................................20
Technical characteristics ...........................................................................23
Environmental characteristics ....................................................................28
Installation ..................................................................................................32
Safety instructions ....................................................................................32
Transport, handling and storage ................................................................34
Transport ...........................................................................................34
Handling ............................................................................................34
Storage ..............................................................................................34
Unpacking................................................................................................35
Equipment receipt...............................................................................35
Package contents ...............................................................................35
Equipment identification ............................................................................36
Dimensions ..............................................................................................39
Operating environment .............................................................................41
Mounting..................................................................................................42
General mounting operations...............................................................42
Flush mounting with accessory ............................................................44
Flush mounting without accessory........................................................46
Rack mounting ...................................................................................48
Rear panel connectors and application diagrams ........................................50
Easergy P5 rear panel .......................................................................50
Typical application diagrams ................................................................57
Wiring on the real panel ............................................................................64
Slot A: analogue module......................................................................64
Digital input connections......................................................................74
Slot B: power supply + digital 4-input/4-output .......................................75
Slot C, D, E: additional digital input/output modules (6I4O/12I4O/
5I5O) .................................................................................................77
Slots D and E: Arc-flash module (for Easergy P5x30 only)......................78
Installing the digital I/O connectors .......................................................78
Wiring accessories for Slot B, C, D, E ...................................................79
Connecting earth/ground .....................................................................79
Optional rear communication ports and modules.........................................82
Location of the communication ports ....................................................82
Installing the modules..........................................................................83
Slot L: Ethernet communication module with RSTP redundancy
(reference REL51042).........................................................................84
Slot M: Ethernet communication module with RSTP redundancy ............85
Slot N: serial line communication modules ............................................87
P5/EN M/33C 3
Protection Relay
P5/EN M/33C 5
Protection Relay
6 P5/EN M/33C
Protection Relay
Characteristics.................................................................................. 240
Thermal overload protection for feeder (ANSI 49F).................................... 241
Description ....................................................................................... 241
Additional features ............................................................................ 243
Time to trip calculation....................................................................... 243
Block diagram................................................................................... 244
Characteristics.................................................................................. 245
Motor status ........................................................................................... 246
Description ....................................................................................... 246
General settings ............................................................................... 247
Motor speed detection ............................................................................ 248
Description ....................................................................................... 248
Block diagram................................................................................... 249
Characteristics.................................................................................. 249
Motor start time supervision (ANSI 48) ..................................................... 250
Description ....................................................................................... 250
Block diagram................................................................................... 251
Characteristics.................................................................................. 251
Thermal overload protection for machine (ANSI 49M)................................ 252
Description ....................................................................................... 252
Additional features ............................................................................ 255
Time to trip calculation....................................................................... 256
Time left for motor start...................................................................... 256
Block diagram................................................................................... 257
Characteristics.................................................................................. 258
Locked rotor (ANSI 51LR) ....................................................................... 260
Description ....................................................................................... 260
Block diagram................................................................................... 260
Characteristics.................................................................................. 261
Motor restart inhibition (ANSI 66) ............................................................. 262
Description ....................................................................................... 262
Block diagram................................................................................... 264
Characteristics.................................................................................. 265
Motor overspeed (ANSI 12) ..................................................................... 266
Description ....................................................................................... 266
Block diagram................................................................................... 266
Characteristics.................................................................................. 267
Motor underspeed (ANSI 14) ................................................................... 268
Description ....................................................................................... 268
Block diagram................................................................................... 268
Characteristics.................................................................................. 269
Motor Anti-backspin (ABS) protection....................................................... 270
Description ....................................................................................... 270
Block diagram................................................................................... 270
Characteristics.................................................................................. 271
Inrush blocking ....................................................................................... 272
Description ....................................................................................... 272
Block diagram................................................................................... 272
Characteristics.................................................................................. 273
Switch On To Fault (ANSI 50HS).............................................................. 274
Description ....................................................................................... 274
P5/EN M/33C 7
Protection Relay
8 P5/EN M/33C
Protection Relay
P5/EN M/33C 9
Protection Relay
10 P5/EN M/33C
Protection Relay
12 P5/EN M/33C
General information Protection Relay
General information
Legal notice
Copyright
2021 Schneider Electric. All rights reserved.
Disclaimer
No responsibility is assumed by Schneider Electric for any consequences arising
out of the use of this document. This document is not intended as an instruction
manual for untrained persons. This document gives instructions on device
installation, commissioning and operation. However, the manual cannot cover all
conceivable circumstances or include detailed information on all topics. In the
event of questions or specific issues, do not take any action without proper
authorisation. Contact Schneider Electric and request the necessary information.
Contact information
35 rue Joseph Monier
92500 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.se.com
Purpose
This user manual is intended for people who are experts on electrical power
engineering, panel builder, commissioner, and experienced users, communication
specialists or general users of the Easergy P5 protection relays.
The complete manual is arranged as follows:
• Preliminary sections, with the details of the manual (how to use it, glossary)
and technical data.
• Functions of the protection relay.
Explanations, diagrams and settings of the protection, control, monitoring and
maintenance, measurement, recording and programmable logic functions are
detailed in these sections.
• Installation and commissioning.
• Local control panel use, troubleshooting and maintenance instructions.
The following documents complete this manual:
• Quick Start Guide, delivered in the relay package, summarises instructions
for installation.
• Communication Manual, for the understanding and the setup of the
communication protocols with Easergy P5 protection relays.
We welcome your comments about this document. You can reach us by
contacting Customer Care Centre Contact page:
http://www.se.com/CCC
P5/EN M/33C 13
Protection Relay General information
The addition of this symbol to a "Danger" or "Warning" safety label indicates that an
electrical hazard exists which will result in death or serious injury if the instructions
are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury, or equipment damage.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury.
Failure to follow these instructions can result in equipment damage.
14 P5/EN M/33C
General information Protection Relay
Abbreviations
Table 1 - Abbreviations used in the manual
Acronyms Indication
Ø Diameter
CB Circuit Breaker
CID Configured IED Description
CT Current Transformer
CTS Current Transformer Supervision
DI, DO Digital Input, Digital Output: used in connection with the number of inputs and output
contacts within the relay and - when necessary - with the slot letter.
DIN rail Standard metal rail used to mount equipment inside ar rack (DIN for Deutsches
Institut für Normung)
I/O Input/Output (e.g. 6I/4O: 6 inputs, 4 outputs): used in connection with the number of
inputs and output contacts within the relay.
IRIG-B Inter-Range Instrumentation Group time code B: standard for time transfer
max. Maximum
NERC North American Electric Reliability Corporation
NI Network Input
RBAC Role Based Access Control: provides a restricting access to authorised users only
(Cybersecurity).
P5/EN M/33C 15
Protection Relay General information
Acronyms Indication
Ref Reference
RH Relative Humidity
RJ45 Standardised type of connector (eight-wire connector) used for Ethernet networking
(Registered Jack)
RS485 (or Standard defining the electrical characteristics of a serial communication interface.
EIA-485)
VO Virtual Output
VT Voltage Transformer
16 P5/EN M/33C
Range description Protection Relay
Range description
Easergy P5 is a family of digital protection relays for medium voltage
distribution networks dedicated to:
• Buildings and Industry:
◦ Retails
◦ Hotels
◦ Health care
◦ Education and research
◦ Transportation
◦ Industrial buildings
• Utilities: energy distribution
• Large sites:
◦ Oil and Gas
◦ Mining
◦ Mineral and Metals
◦ Water
P5/EN M/33C 17
Protection Relay Introduction
Introduction
Selection guide by application
Table 2 - Easergy P5 protection relay selection guide
Voltage - P5V20 -
Feeder P5F30
Transformer P5U20 - -
Motor P5M30
Characteristics
Phase current 1/5A CT (x3) LPCT (x3) - 1/5A CT (x3) LPCT (x3)
Inputs 4 to 16 4 to 40
Digital
Outputs 3 to 8 + watchdog 3 to 18 + watchdog
Communication
Extension port with
backup memory ■ ■ ■
Serial port ■ ■ ■
Rear ports
Ethernet port ■ ■ ■
IEC 60870-5-101 ■ ■ ■
EtherNet/IP ■ ■ ■
RSTP ■ ■ ■
Redundancy
protocols PRP ■ ■ ■
HSR ■ ■ ■
1. Resistive divider or capacitive divider LPVTs can be connected to the Easergy P5 protection relay.
18 P5/EN M/33C
Introduction Protection Relay
Others
Control 6 controlled + 2 monitored objects Mimic
Matrix ■ ■ ■
Logic
Logic equations ■ ■ ■
Withdrawability ■ ■ ■
P5/EN M/33C 19
Protection Relay Introduction
Function table
Table 3 - Easergy P5 protection relay function selection table
Auto-Recloser P5ARRREC1 79 1 1 - 1 -
Inrush P5IDPHAR1 1 1 - 1 1
Overvoltage P5OVPTOVx 59 - 3 3 3 3
Undervoltage P5UVPTUVx 27 - 3 3 3 3
2. The x at the end of the logical node name in this column corresponds to the number of the stages of protection functions and the number
of the objects for control and monitoring functions.
3. Number of stages depends on the number of residual current inputs.
4. This protection function is only available when 12I4O module is fitted in the Easergy P5 protection relay.
20 P5/EN M/33C
Introduction Protection Relay
Synchro-check P5SCUYMMXU1 25 - - 1 1 -
Lockout relay 86 1 1 1 1 1
Programmable curves 3 3 3 3 3
Monitoring functions
CT supervision P5CTSGGIO1 60 1 1 - 1 1
VT supervision P5VTSGGIO1 60 - 1 1 1 1
Relay monitoring ■ ■ ■ ■ ■
Control functions
Switchgear control and monitoring P5OBJCSWIx 6 6 6 6 6
Local/remote function ■ ■ ■ ■ ■
Function keys 1 1 1 7 7
5. The x at the end of the logical node name in this column corresponds to the number of the stages of protection functions and the number
of the objects for control and monitoring functions.
P5/EN M/33C 21
Protection Relay Introduction
Frequency P5VECAMMXUx ■ ■ ■ ■ ■
6. The x at the end of the logical node name in this column corresponds to the number of the stages of protection functions and the number
of the objects for control and monitoring functions.
22 P5/EN M/33C
Introduction Protection Relay
Technical characteristics
Table 4 - Easergy P5 protection relay technical characteristics
Characteristic Value
Easergy P5x20 Easergy P5x30
Rated frequency 50 Hz or 60 Hz
Power supply
Operating range DC: 24 to 250 V DC, ±20% DC: 48 to 250 V DC, ±20%
AC: 100 to 230 V AC, ±20% AC: 100 to 230 V AC, ±20%
Optional:
DC: 24 to 48 V DC, ±20%
Phase CT inputs
LPCT inputs
Current factor 0.25; 0.50; 1.00; 1.25; 1.33; 2.00; 2.50; 3.20; 4.00; 5.00; 6.30; 6.66; 10; 16; 20; 25; 31.5
CT ratio 1/470
7. This value can be impacted by high temperature exposition during a long time.
P5/EN M/33C 23
Protection Relay Introduction
Characteristic Value
Easergy P5x20 Easergy P5x30
Digital inputs
8. A setting below 10 ms can be used for testing only. It is not recommended during operation.
24 P5/EN M/33C
Introduction Protection Relay
Characteristic Value
Easergy P5x20 Easergy P5x30
Continuous current 8A
Short duration carry current 30 A for 3 s
Other characteristics
Making capacity 2000 operations
5 A DC with L/R = 50 ms
Duty cycle 1 s ON, 9 s OFF
Closing/opening time 7 ms (typical value), 3.5 ms + 3.5 ms for contact bounce, resistive load
P5/EN M/33C 25
Protection Relay Introduction
Characteristic Value
Easergy P5x20 Easergy P5x30
Continuous current 10 A
Short duration carry current 30 A for 3 s
Dielectric withstand across normally None – due to Solid State Devices across normally open contact
open contacts
Dielectric withstand across normally None – due to Solid State Devices across normally open contact
open contacts
Other characteristics
Making capacity 2000 operations
5 A DC with L/R = 50 ms
Breaking capacity 10000 operations
0.25 A DC with L/R = 50 ms
Short duration making capacity 10 A for 1 s;
15 A for 0.3 s;
30 A for 0.2 s;
40 A for 0.03 s
Minimum making current 10 mA with 50 mW minimum
Closing time 1 ms (typical value) for the high-speed contact relay DO1 (Easergy P5x30)
26 P5/EN M/33C
Introduction Protection Relay
Characteristic Value
Easergy P5x20 Easergy P5x30
Continuous current 2A
Short duration carry current 30 A for 200 ms
Other characteristics
Making and breaking capacity 10000 operations
1 A DC with L/R = 20 ms
Minimum making current 10 mA with 50 mW minimum
Closing/opening time 7 ms (typical value) 3.5 ms + 3.5 ms for contact bounce, resistive load
Size (Width x Height x Depth) 102/180/224 mm (4.01/7.08/ 8.82 in) 152.4/180/224 mm (6/7.08/8.82 in)
P5/EN M/33C 27
Protection Relay Introduction
Environmental characteristics
WARNING
HAZARD OF UNEXPECTED OPERATION
Install the Easergy P5 protection relay according to the environmental
characteristics described in the table below.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
According to the informative annex of IEC 60255-1 standard edition 1, all the
environmental tests are performed at the minimum settings which helps to ensure
the robustness of the Easergy P5 protection relay.
All the digital inputs have been tested with 10 ms of debounce filter.
Characteristic Description/Value
Power Supply
Product Safety
None for High Speed, High Break control relay output due to
solid state devices across normally open contact.
Impulse voltage IEC 60255-27 1.2 μs, 50 μs, 5 kV, 0.5 J between all terminals of independent
circuits, and all terminals and case earth/ground.
28 P5/EN M/33C
Introduction Protection Relay
Characteristic Description/Value
Electromagnetic Compatibility
CISPR11
IEC 60255-26
GOST-30805.22
IACS-E10 For equipment installed in the general power distribution zone.
IEC 60255-26
GOST-30805.22
IACS-E10 For equipment installed in the general power distribution zone.
Radiated radio frequency fields IEC 61000-4-3 Level 3 10 V/m, 80 MHz to 6 GHz, 80% AM (1 kHz)
Magnetic field at power IEC 61000-4-8 Level 5 100 A/m continuous; 1000 A/m, 1 to 3 s
frequency
Oscillatory magnetic fields IEC 61000-4-10 Level 5 100 A/m, 100 kHz and 1 MHz
Conducted Radio Frequency IEC 61000-4-6 Level 3 10 V rms common mode, 0.15 MHz to 80 MHz, 80% AM
disturbance (1 kHz)
Fast transient bursts IEC 61000-4-4 Level 4 4 kV common mode, 5 kHz, 100 kHz
Slow damped oscillatory waves IEC 61000-4-18 Level 3 2.5 kV common mode
1 kV differential mode, 100 kHz, 1 MHz
ANSI C37.90.1 2.5 kV, 1 MHz, common mode and transversal mode
IEC 61000-4-12 Level 3 2 kV common mode; 1 kV, differential mode, 100 kHz,
Source impedance: 12 Ω
GOST 30804.4.12
Fast damped oscillatory waves IEC 61000-4-18 Level 3 2 kV common mode, 3 MHz, 10 MHz, 30 MHz
Conducted disturbances 0 to IEC 60255-26 Zone A 150 V rms, differential mode; 300 V rms, common mode.
150 kHz
GOST 51317.4.6 Level 3 Continuous: 30 V rms
Short: 300 V rms
5 Hz – 150 kHz: 30 V rms
Surges 9 IEC 61000-4-5 Level 4 4 kV, common mode; 2 kV, differential mode
9. When protection functions 50N/51N is used and I0 is measured with CSH core balance CT, it is recommended to use operation time of
50 ms at the lowest pickup value setting.
P5/EN M/33C 29
Protection Relay Introduction
Characteristic Description/Value
Climatic
During operation
Exposure to damp heat IEC 60068-2-78 Cab 93% ± 3% RH; 40 ℃ (+104 ℉), 56 days,
without condensation
Temperature variation IEC 60068-2-14 Nc -40℃ to +70℃ (-40℉to +158℉), 10℃/min (18℉/min)
96 hours
Damp heat cyclic test IEC 60068-2-30 Db 55℃/93% ± 3% RH and 25℃/97% -2% +3% RH, with
condensation, 6 cycles (12 h + 12 h)
Variant 1
Storage
Exposure to damp heat IEC 60068-2-78 Cab 93% ± 3% RH; 40 ℃ (+104℉), 56 days, without condensation
Corrosive atmosphere
Salt mist IEC 60068-2-52 Kb/1 4 spraying periods of 2 hours with a storage of 7 days after
each
2 Gas IEC 60068-2-60 Ke +25℃ (+77℉), 75% RH, 21 days,
method 1: 0.5 ppm SO2; 0.1 ppm H2S.
Mechanical Robustness
Characteristics Standard Level Value
In operation (flush mounted case with REL51032: panel mounting kit with flush mounting accessory)
Storage (flush mounted case with REL51032: panel mounting kit with flush mounting accessory)
30 P5/EN M/33C
Introduction Protection Relay
Characteristic Description/Value
Enclosure
Local panel IEC 62262 IK07 Degree of protection against mechanical impacts
NEMA Type 12 -
Rear panel IEC 60529 IP10 Area with ring terminal connection (analogue inputs)
Fire resistance
Fire resistance IEC 60695-2-11 650℃ (1202℉)
Packaging
Cybersecurity
P5/EN M/33C 31
Protection Relay Installation
Installation
Safety instructions
This page contains important safety instructions that must be followed precisely
before attempting to install, repair, service or maintain electrical equipment.
Carefully read and follow the safety instructions described below. Only qualified
personnel, equipped with appropriate individual protection equipment, may work
on or operate the equipment. Qualified personnel are individuals who:
• Are familiar with the installation, commissioning, and operation of the
equipment and of the system to which it is being connected.
• Are able to safely perform switching operations in accordance with accepted
safety engineering practices and are authorised to energise and de-energise
equipment and to isolate, earth/ground, and label it.
• Are trained in the care and use of safety apparatus in accordance with safety
engineering practices.
• Are trained in emergency procedures (first aid).
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Before performing any work on or in this equipment:
• Turn off all power supplying the protection relay and the equipment in which
it is installed before working on it.
• Always use a properly rated voltage sensing device to confirm that power is
off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
• Apply appropriate personal protective equipment and follow safe electrical
work practices. See local regulation.
• Do not install this product in ATEX class 0, 1 and 2 areas.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
Apply proper tightening torque to all wire connections.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF UNEXPECTED OPERATION
Do not energise the primary circuit before this protection relay is properly
configured.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
32 P5/EN M/33C
Installation Protection Relay
DANGER
FIRE HAZARD
If you are authorised to withdraw the relay:
• Disconnect the power supply before removing or replacing a module or the
withdrawable part of the protection relay.
• Never touch electronic parts (electrostatic discharge).
• Before replacing the withdrawable part, clean all debris and contaminants
from the case, the withdrawable part, and the connectors.
Failure to follow these instructions will result in death or serious injury.
P5/EN M/33C 33
Protection Relay Installation
Handling
Protective relays, although generally of robust construction, require careful
handling: handle the Easergy P5 protection relays in their original packing in order
to help protect it against shocks.
If installed in a cubicle: should the protection relay fall out of a cubicle, check its
condition by visual inspection and energising.
Storage
NOTICE
WATER DAMAGE
• Do not expose the products to sustained humidity during storage.
• Electrically energize the products within three months of unpacking.
• Where electrical equipment is being installed, allow sufficient time for
acclimatisation to the ambient temperature of the environment before
powering on.
• Supply power to the protection relay every two years for at least one hour.
Failure to follow these instructions can result in equipment damage.
34 P5/EN M/33C
Installation Protection Relay
Unpacking
Equipment receipt
NOTICE
PRODUCT TAMPERING
Our products leave our factory in closed, sealed original packaging. At delivery,
if the packaging is opened or the seal is broken, Schneider Electric must be
informed.
Failure to follow this instruction can result in compromised confidentiality
and authenticity of the information contained in the products.
Package contents
Each Easergy P5 protection relay is delivered in an independent package
containing:
• An Easergy P5 protection relay
◦ 1a: Easergy P5x20
◦ 1b: Easergy P5x30
• A certificate of conformity ②
• An installation sheet providing main information about installation and use ③
• One plastic bag including a set of labels and stickers, and the cabling kit for
connector A
◦ 4a-1: pack for Easergy P5x20 of CT/VT analogue input type
◦ 4a-2: pack for Easergy P5U20 of LPCT/LPVT analogue input type
◦ 4b-1: pack for Easergy P5x30 of CT/VT analogue input type
◦ 4b-2: pack for Easergy P5x30 of LPCT/LPVT analogue input type
• One plastic bag including one to four rear connectors
◦ 5a: pack for Easergy P5x20
◦ 5b: pack for Easergy P5x30
1a
en
Instruction
Retain
Go to for sheet
future
www.schneid
to download use
reference er-electric.co
the
documents.manual PowerLogic
The
and m QR
IMPORTANT other P5F20 gives code
This websitea direct (front panel
and device NOTE access of
servicedmust
electrical to your the relay)
be installed
by qualified relay’s
Schneider personnel.
responsibleElectric
the
instructions
instruction cannot
for failure
en be held
to follow
sheet.given on
this
Equipme
nt receipt
03/2014
Schneider 1
35 rue Electric
92500 Joseph Industries
en Equipment
Monier
France Rueil-Malmais 2 1
SAS Protection receipt
www.schneide 3 2
on Certificate relay
xxxxxxx
r-electric.com 4 of compliance
Instruction
5
Connector sheet
6
Connector(s) A cabling
© 2014
All rights Schneider kit
reserved. Electric.
4a-2
5
4b-1
4b-2
5a 5b
P533G0A
P5/EN M/33C 35
Protection Relay Installation
Equipment identification
Different kinds of labels and stickers are used on the Easergy P5 protection relay
to identify its model type and its different components.
1 1
2 2 P533G1A
② Reference label
Reference label
The reference label contains the commercial reference, the serial number, the
power supply voltage of the relay and a QR code. The QR code can be used to
access the specific product website through mySchneider App (availabe in App
Store and Google Store) to get basic product documents and product life cycle
documents like Certificate of Conformity and Test.
1
4
2
3 P5
P5U20W211647230001
P533G2A
1 4
2
3 P5
P5F30W211647230001
P533G3A
② Reference
③ Serial number
④ Access to product website
36 P5/EN M/33C
Installation Protection Relay
DANGER
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH RISQUE DE CHOC ELECTRIQUE, D'EXPLOSION OU D'ARC ELECTRIQUE
- This equipment must only be installed and serviced by qualified - Cet équipement doit être installé et entretenu par du personnel
electrical personnel. qualifié.
- Turn off all power supplying this equipment before working on or - Avant toute intervention, couper toutes les alimentations électriques
inside it. de l'équipement.
- Always use a properly rated voltage detection device to confirm that - Toujours utiliser un vérificateur d'absence de tension (VAT) pour
all power is off. confirmer l'absence de tension.
- Apply appropriate personal protection equipment (PPE) and follow - Utiliser les équipements de protection individuelle (EPI) et suivre
safe electrical work pratices. les pratiques de travail sécuritaires.
- Do not install this product in ATEX zone 0 or 1 areas. - Ne pas installer ce produit dans des zones ATEX 0 ou 1.
Le non-respect de ces instructions entraînera la mort ou des blessures
Failure to follow these instructions will result in death or serious injury. graves.
P533G4A
2
P533G5A
P5/EN M/33C 37
Protection Relay Installation
ETH Dual port copper (RJ45) or fibre optic (multi-mode glass fibre) Ethernet ports
EXT Extension port for connection with external module and demodulated IRIG-B input
or back-up memory
P533G6A
38 P5/EN M/33C
Installation Protection Relay
Dimensions
Product dimensions
Dimensions of the Easergy P5 protection relays are shown below:
53.4
51.8 2.10
2.04
98.8
3.89
P533G7A
53.4
103.6
2.10
4.08
150.3
5.92
P533G8A
P5/EN M/33C 39
Protection Relay Installation
158
6.22
43
1.69 P533G9A
Rear clearances
For easy access to the rear panel, the rear clearances illustrated below are
recommended:
60
2.36
2
140
5.51
P533GAA
40 P5/EN M/33C
Installation Protection Relay
Operating environment
Operating temperature and humidity
NOTICE
POTENTIAL DAMAGE FROM ENVIRONMENTAL CONDITIONS
• The Easergy P5 protection relay must be installed in an environment within
the specified operation temperature and humidity.
• The protection relay may not operate correctly if condensation occurs on the
electronic boards inside the device.
Failure to follow these instructions can result in equipment damage.
The Easergy P5 protection relay is intended for indoor installation and use only. If
it is required for use in an outdoor environment, it must be mounted in a specific
cabinet that will enable it to meet the requirements of IEC 60529 with the
classification of protection degree IP54 (dust and splashing water protected).
The temperature/relative humidity factors must be compatible with the
environmental withstand characteristics of the Easergy P5 protection relay:
• Recommended operating range of temperature: -10℃ to +55℃ (+14℉ to
+131℉).
• Maximum operating temperature: -40℃ to +70℃ (-40℉ to +158℉).
• Average humidity: <75% RH over the year.
• Temporary permissible humidity: <93% RH (less than 80 hours per year)
• No condensation.
If the operating conditions are outside the normal range, special arrangements
should be made before commissioning, such as air conditioning of the premises.
P5/EN M/33C 41
Protection Relay Installation
Mounting
General mounting operations
P533GBB
P533GCB
42 P5/EN M/33C
Installation Protection Relay
x3 x4
P533GDA
2
P533GEA
P5/EN M/33C 43
Protection Relay Installation
The handle on the front face of the protection relay is used to separate the
withdrawable part from the fixed outer case. In order to prevent unauthorised
dismantling fix the lock tab on the handle with a wired lead seal to restrict the
rotation of the handle.
P533GFA
CAUTION
HAZARD OF CUTS AND PHYSICAL IMPACT
• Wear gloves and safety shoes.
• Trim the edges of the cut-out plates to remove any jagged edges.
• Carry the assembled relay with withdrawable part locked.
• When cases are mounted on a rack (with withdrawable part not inserted),
stay far enough from the protruding part(s) of the case(s).
Failure to follow these instructions can result in injury or equipment
damage.
The Easergy P5 protection relay can be mounted onto panels with the provided
accessory. It is recommended to use the flush mounting with accessory for
Easergy P5 protection relay.
Mounting Procedure
1. Prepare the cut out in the panel according to the following dimensions.
8.07 ± 0.2
205 ± 0.5
P5x20 P5x30
P533GGA
44 P5/EN M/33C
Installation Protection Relay
2. Insert the flush mounting accessory ① in the panel ② and check that the rear
mounting supports ③ are accessible for panel mounting kits to be inserted.
1 2 1 2
3
REL51032 REL51052
P533GHA
3. Insert the panel mounting kits in the mounting support holes ① and then push
down the front parts (flush panel side) ② to lock the flush mounting accessory
on the panel.
P533GIA
4. Remove the top and bottom seal straps from the rear mounting surface of the
protection relay.
x2 x2
P533GJA
P5/EN M/33C 45
Protection Relay Installation
5. Insert the protection relay ② into the mounting accessory ① and hold it in the
mounting position.
1 2 1 2
P533GKA
6. Fix the protection relay on the accessory with the screws provided in the flush
mounting accessory.
P533GLB
CAUTION
HAZARD OF CUTS AND PHYSICAL IMPACT
• Wear gloves and safety shoes.
• Trim the edges of the cut-out plates to remove any jagged edges.
• Carry the assembled relay with withdrawable part locked.
• When cases are mounted on a rack (with withdrawable part not inserted),
stay far enough from the protruding part(s) of the case(s).
Failure to follow these instructions can result in injury or equipment
damage.
The Easergy P5 protection relay can be directly mounted onto panels without any
accessory.
46 P5/EN M/33C
Installation Protection Relay
Mounting Procedure
1. Prepare the cut-out in the panel for flush mounting according to the following
dimensions.
The thickness of the panel plate should be a minimum of 3 mm (0.12 in.).
P533GNA
P5/EN M/33C 47
Protection Relay Installation
Rack mounting
CAUTION
HAZARD OF FALLING DEVICES
• Wear gloves and safety shoes.
• Carry the assembled relay with withdrawable part locked.
• When cases are mounted on a rack (with withdrawable part not inserted),
stay far enough from the protruding part(s) of the case(s).
Failure to follow these instructions can result in injury or equipment
damage.
Easergy P5 protection relays may be rack mounted using single rack mounting
frames (ref: REL51021), as illustrated in the figure below.
F0187-1
P533GOA
The two horizontal rails of the rack frame have holes drilled at approximately 26
mm (10 in.) intervals. The Easergy P5 protection relays are attached via their
mounting flanges using M4 x 20 mm (0.787 in.) stainless steel self-tapping screws
with stainless steel washers (diameter 4 x 8 mm (0.157 x 0.315 in.) maximum).
Relays can be mechanically grouped into single tier or multi-tier arrangements by
means of the rack frame. This enables schemes using products from the Easergy
P5 product ranges to be pre-wired together prior to mounting (rack mounting with
M4 self-tapping screws, washers and nut).
Mounting Procedure
1. Insert the Easergy P5 protection relay ② into the rack frame ①.
1
2
P533GPA
48 P5/EN M/33C
Installation Protection Relay
2. Fasten the protection relay onto the rack frame using four M4 x 20 mm (0.787
in.) stainless steel self-tapping screws with stainless steel washers (diameter
4 x 8 mm (0.157 x 0.315 in.) maximum).
Figure 27 - Fasten the protection relay onto the rack frame (Easergy
P5x20 shown as an example)
P533GQB
3. Cover up the open section of the rack frame with blank plates if there is still
space left for future installation of protection relays or ancillary components.
P533GRB
Subsequent operation Mount the rack frame on the rack using the mounting flanges on
both sides of the frame.
P5/EN M/33C 49
Protection Relay Installation
P533GSA
✔ ✔ B: Power supply
NOTE: For the slot occupation rules of Easergy P5x30 slot C, D and E, refer
to Slot occupation rules, page 487.
50 P5/EN M/33C
Installation Protection Relay
A B C
1 1
1 2 2 2
3 3
3 4 4 4
5 5
5 6 6 6
7 7
7 8 8 8
9 9
10 10
9 10 11 11
12 12
11 12 13 13
14 14
13 14 15 15
16 16
15 16 17 17
18 18
17 18 19 19
20 20
M N P P533GTA
A B C C C
7 8 DI7 8 8 8
P533GUA
Optional
-S Signalling, 2 A perm.
P5/EN M/33C 51
Protection Relay Installation
A B C
1 1
2 2
L1 1 3 3
4 4
5 5
2 6 6
L2 7 7
8 8
3 9 9
10 10
L3 11 11
4 12 12
13 13
V1 14 14
V2 15 15
V3 16 16
17 17
V4 18 18
19 19
20 20
M N P P533GVA
A B C C C
P533GWB
Optional
-S Signalling, 2 A perm.
52 P5/EN M/33C
Installation Protection Relay
A B C
1 1
1 2 2 2
3 3
3 4 4 4
5 5
5 6 6 6
7 7
7 8 8 8
9 9
10 10
9 10 11 11
12 12
11 12 13 13
14 14
13 14 15 15
16 16
15 16 17 17
18 18
17 18 19 19
20 20
M N P P533GXA
A B C C C
7 8 DI7 8 8 8
V4 DO1 9 DI8 9 DO1 C 9 DI5 9
8 C
10 DI9 10 10 10
9 C
DO2 11 DI10 11 11 DI6 11
C
10 12 DI11 12 DO2 C 12 12
C
11 13 DI12 13 13 DO1 13
C S
12 DO3 C
14 14 14 14
15 DO1 15 DO3 15 DO2 15
S C S
13
Not used WD 16 DO2 S
16 16 16
14 17 17 DO4 17 DO3 17
HS S
15 18 DO3 18 18 18
S
16 19 DO4 19 DO5 19 DO4 19
S HS S
20 20 20 20
17
18
P533GYA
Optional
-S Signalling, 2 A perm.
P5/EN M/33C 53
Protection Relay Installation
D E A B C
1 1 1 1
2 2 1 2 2 2
3 3 3 3
4 4 3 4 4 4
5 5 5 5
6 6 5 6 6 6
7 7 7 7
8 8 7 8 8 8
9 9 9 9
10 10 10 10
11 11 9 10 11 11
12 12 12 12
13 13 11 12 13 13
14 14 14 14
15 15 13 14 15 15
16 16 16 16
17 17 15 16 17 17
18 18 18 18
19 19 17 18 19 19
20 20 20 20
L M N P P533GZA
A B C D E C D E C D E D E
P533H0A
Optional
-S Signalling, 2 A perm.
54 P5/EN M/33C
Installation Protection Relay
D E A B C
1 1 1 1
2 2 2 2
3 3 3 3
1
4 4 L1 4 4
5 5 5 5
6 6 2 6 6
7 7 7 7
8 8 L2 8 8
9 9 3 9 9
10 10 10 10
11 11 L3 11 11
12 12 4 12 12
13 13 13 13
14 14 V1 14 14
15 15 V2 15 15
16 16 V3 16 16
17 17 17 17
18 18 V4 18 18
19 19 19 19
20 20 20 20
L M N P
P533H1A
A B C D E C D E C D E D E
P533H2B
Optional
-S Signalling, 2 A perm.
P5/EN M/33C 55
Protection Relay Installation
DI1 CB open
DI2 CB close
DI3 Free
DI4 Free
DO1 CB trip
DO3 CB close
WD Watchdog (not configurable)
56 P5/EN M/33C
Installation Protection Relay
S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10
IL1
S1 A11 S1 A11
A12 IL2 A12
IL2
S1 A13 S1 A13
A14 IL3 A14
IL3
A15 A15
1/2/5 A A16 I0 (Std) A16 I0 (Std)
S1 A17 A17
1A 1A A18 I0’ (VS)
A18 I0’ (VS)
S1 S1
P533CHA
NOTE: For an application with 2 CTs, only IL1 and IL3 are used by Easergy P5
protection relay (see figure below).
Figure 41 - 3 x 1/5A CTs (with IL2 not connected) and residual current
measured by 1 x 1/2/5A CT and 1 x 1A CT
L1
L2
L3
S1 A9
1/5 A A10 IL1
A11
A12
S1 A13
A14 IL3
A15
1/2/5 A A16 I0 (Std)
S1 A17
1A A18 I0’ (VS)
S1
P533CIA
P5/EN M/33C 57
Protection Relay Installation
S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10 IL1
S1 A11 S1 A11
A12 IL2 A12 IL2
S1 A13 S1 A13
A14 IL3 A14 IL3
A15 A15
CSH
A16 I0 A16
20 A S1 A17 A17
CSH
A18 A18 I0
2A
S1
P533CJA
NOTE: For an application with 2 CTs, only IL1 and IL3 are used by Easergy P5
protection relay( see figure below).
Figure 43 - 3 x 1/5A CTs (with IL2 not connected) and 1 residual current
measured by CSH
L1 L1
L2 L2
L3 L3
S1 A9 S1 A9
1/5 A A10 IL1 1/5 A A10 IL1
A11 A11
A12 A12
S1 A13 S1 A13
A14 IL3 A14 IL3
A15 A15
CSH A16 I0 A16
20 A S1 A17 A17
CSH I0
A18 A18
2A
S1
P533CKA
L1
L2
L3
RJ45 IL1
RJ45 IL2
RJ45 IL3
S1 A1
CSH I0
A2
20 A / 2A
A3
A4 I0
P533CLC
58 P5/EN M/33C
Installation Protection Relay
VT typical application
Voltage input terminals A2 and A4 have been connected internally. For three line-
to-neutral applications, short terminals A4 and A6 together.
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6 V3
A7
A8
P533CMA
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6 V3
A7
A8 V4
P533CNA
P5/EN M/33C 59
Protection Relay Installation
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6 V3
A7
A8 V4
P533COA
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6 V3
A7
A8 V4
P533CPB
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6 V3
A7
A8 V4
P533CQB
60 P5/EN M/33C
Installation Protection Relay
L1
L2
L3
A1
A2 V1
A3
A4 V2
A5
A6
A7
A8 V4
P533CRA
L1
L2
L3
A1
A2 V1
A3
A4
A5
A6 V3
A7
A8
P533CSB
P5/EN M/33C 61
Protection Relay Installation
L1
L2
L3
LPVT L1
LPVT hub
connector
LPVT L2
LPVT L3
P533CTA
L1
L2
L3
LPVT L1
LPVT hub
connector
LPVT L2
LPVT L3
Termination
accessory
NOTE: If one or two LPVT are connected to the LPVT hub connector, the
termination accessory (REL51065) delivered with the protection relay needs
to be plugged on the 2nd and 3rd inputs.
62 P5/EN M/33C
Installation Protection Relay
L1
L2
L3
Cable between
adapter and relay < 10m
LPVT adapter
RJ45
V1, V2, V3
P533CWA
L1
L2
L3
Cable between
adapter and relay < 10m
LPVT adapter
RJ45
V1, V2, V3
LPVT adapter
RJ45 V4
P533CYA
L1
L2
L3
Cable between
adapter and relay < 10m
LPVT adapter
RJ45
V1, V2, V3
LPVT adapter
RJ45 V4
P533D0A
L1
L2
L3
Cable between
adapter and relay < 10m
LPVT adapter
RJ45
V1, V2, V3
LPVT adapter
RJ45 V4
P533D2B
P5/EN M/33C 63
Protection Relay Installation
DANGER
FIRE HAZARD
Apply proper tightening torque to all wire connections.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Use the appropriate (3 or 4-terminal) copper jumper for common
connections.
• After cabling, protect the rear connector A with the two protective caps.
Failure to follow these instructions will result in death or serious injury.
3 5
×10
6
4 ×10
P533D4A
64 P5/EN M/33C
Installation Protection Relay
2
×4
3
×4
4
×2 P533D5A
P533CXA
P5/EN M/33C 65
Protection Relay Installation
2. Fasten the terminal jumper with the provided mounting screws and washers.
P533CZB
3. Connect the bent ring lug end of the cables to the terminal using the provided
mounting screws and washers.
P533D1B
REL51060 1.5 ... 2.5 mm2 (AWG 16 ... 14) Ring lug terminal 4.45 mm (0.18 in)
REL51061 2.5 ... 6 mm2 (AWG 14 ... 10) Ring lug terminal 6.35 mm (0.25 in)
4. After cabling, place and insert the protective caps on the terminal.
66 P5/EN M/33C
Installation Protection Relay
P533D3A
A
V1 1 2 V1 A1
V1
V2 3 4 V2 A2
V3 5 6 V3 A3
V2
V4 7 8 V4 A4
9 10 A5
V3 A6
11 12
A7
13 14 V4
A8
15 16
17 18 P533D6A
P5/EN M/33C 67
Protection Relay Installation
A
IL1
IL2 1
IL3
IL3 IL3 2A VS
Std/20 A Std/20 A
VS/2 A VS/2 A 3
P533D8A
① Current inputs
NOTICE
IMPROPER EQUIPMENT OPERATION
Select the CT size according to the requirement from the electric network.
Failure to follow these instructions can result in equipment damage.
68 P5/EN M/33C
Installation Protection Relay
CT requirement
The CT must be sized to avoid saturation during steady state short circuit currents
where accuracy is required, according to the rules described below for DT or IDMT
operation time.
The condition to be fulfilled by the CT saturation current (Isat) depends on the type
of overcurrent protection operation time:
I
Is Isat
P533DAA
The method for calculating the saturation current depends on the CT accuracy
class as indicated below.
Practical information
In the absence of any information about the settings, the characteristics below are
suitable for most situations:
P5/EN M/33C 69
Protection Relay Installation
This represents 12 m (39 ft) of wire with cross-section 2.5 mm² (AWG 14) for a
resistance per unit length of 8 Ω/km (2.4 mΩ/ft) approximately.For an installation
with 50 m (164 ft) of wiring with section 2.5 mm² (AWG 14), Rw = 0.4 Ω.
As a result:
Rct ×Ins2 + VAct 0.1 ×25 + 2.5
ActualALF =ALF× = =8
(Rct + Rw)×Ins 2 (0.1 + 0.4)×25 P533DEA
70 P5/EN M/33C
Installation Protection Relay
1
P1 A 3
2
S1 A9
A10 IL1
S2
S1 A11
A12 IL2
S1 A13
A14 IL3
1
S1 A17
A18 2A
S2
2 P533D7A
where:
• ① Terminal P111 (primary current).
• ② Terminal S111 (secondary current).
• ③ Connector A + terminal number.
• Ⓐ Implementation of the cabling between the CTs and the connector:
◦ Conductors contained in the same strand, in a shealth
◦ Conductors run along the metal structures of the MV cubicle
Recommended cable for Schneider Electric's CSH120, CSH200, CSH300 and
GO110 core balance CTs:
• Sheathed cable (to be compliant with electromagnetic compatibility
requirements), shielded by tinned copper braid.
• Resistance per unit length < 100 mΩ/m (30.5 mΩ/ft).
• Minimum dielectric strength: 1000 V (700 Vrms).
• Connect the cable shielding in the shortest manner possible to Easergy P5.
• Flatten the connection cable against the metal frames of the cubicle.
The maximum resistance of the connection wiring must not exceed 4 Ω (i.e. 20 m
maximum for 100 mΩ/m or 66 ft maximum for 30.5 mΩ/ft).
Wiring details
Refer to the table below for the detailed information on wiring the screw-type input
connectors of the analogue module in slot A:
11. Markings of current transformer terminals S1, S2, P1 and P2 according to IEC 60044-1 Standard
P5/EN M/33C 71
Protection Relay Installation
LPCT inputs
NOTICE
IMPROPER EQUIPMENT OPERATION
Use RJ45 cable no longer than 10 m (32.8 ft) for EMC immunity.
Failure to follow these instructions can result in improper operation.
A
1
20A
2
RJ45 IL1 3
2A 4
IL2 RJ45-2
RJ45 IL3
IL3
RJ45-3
V4 RJ45-5
P533D9A
Rated primary current factor 0.25 - 0.50 - 1.00 - 1.25 - 1.33 - This configuration parameter
2.00 - 2.50 - 3.20 - 4.00 - 5.00 - corresponds to the rated
6.30 - 6.66 - 10 - 16 - 20 - 31.5 extended primary current
factor of the LPCT
72 P5/EN M/33C
Installation Protection Relay
LPVT inputs
NOTICE
IMPROPER EQUIPMENT OPERATION
Use CAT6 cable no longer than 10 m (32.8 ft) for EMC immunity.
Failure to follow these instructions can result in improper operation.
A
1
20A
2
3
2A 4
IL1 RJ45-1
IL2 RJ45-2
IL3
RJ45-3
RJ45 V4 V4 RJ45-5
P533DIA
More generally the LPVTs inputs must be compliant with the IEC61869-11
standard.
The table below lists the technical data concerning the ratings and limits of the
LPVT channels:
Parameter Value
Rated secondary voltage 3.25 V / √3
Extended rated voltage 0.25 to 1.5 rated voltage
P5/EN M/33C 73
Protection Relay Installation
DI1 DI3
DI2 DI4
P533DJA
P533DKA
The isolated independent digital inputs are isolated from earth/ground, and each
other. They should be used to acquire data from the following digital sensors:
• Non-isolated sensors (earthed/grounded).
• Remote sensors.
• Sensors from several zones in the installation that do not have equipotential
bonding.
• Sensors from different devices.
To help to ensure that each digital input is isolated, each digital input must be
connected with an independent cable.
The isolated digital inputs with a common connection point are isolated from earth/
ground, but are not isolated in relation to one another (common point). They
should be used to acquire data from the following digital sensors:
• Isolated sensors.
• Sensors that are not isolated but come from the same zone of an installation
with equipotential bonding.
• Sensors that preferably come from the same equipment. The different digital
inputs are contained in the same cable.
The electrical conductors connected to the digital inputs of the Easergy P5
protection relays should run along the metal structures of the cubicle to reduce
earth/ground loops. The conductors are contained in the same strand and, if
possible twisted, to avoid the creation of cabling loops.
NOTICE
IMPROPER EQUIPMENT OPERATION
When connecting the digital inputs:
• Avoid large cabling loops in the various power supplies.
• Do not short-circuit any of the galvanic insulation.
Failure to follow these instructions can result in improper operation or
equipment damage.
When the environmental and installation conditions are highly unfavorable for the
Easergy P5 protection relay, a shielded twisted pair should be used. In such
cases, the cable shielding is connected to the local earth/ground at both ends
(provided that the installation has an equipotential bonding network).
74 P5/EN M/33C
Installation Protection Relay
Power supply
DANGER
FIRE HAZARD
• Protect the power supplying circuit of the Easergy P5 protection relay
against overcurrents.
• For breaking capacity higher than 40W with L/R = 40 ms, protect the digital
output contacts with an additional customer protection (RC or zener diode).
Failure to follow these instructions will result in death or serious injury.
NOTICE
POWER SUPPLY DAMAGE
Before connecting the auxiliary voltage to the Easergy P5 protection relay:
Make sure the nominal value of the auxiliary device voltage corresponds with
the nominal value of the auxiliary system voltage.
Failure to follow these instructions can result in equipment damage.
B19
B20
P533DLA
Digital inputs/outputs
The digital 4-input/4-output module (4I4O) is always mounted in slot B of an
Easergy P5 protection relay. Digital outputs DO1, DO2 and DO3 are specifically
enhanced for circuit breaker (CB) control. Digital output WD is defined as a
Watchdog.
The operating nominal voltage for digital inputs is:
• 24 V DC to 250 V DC
• 100 V AC to 230 V AC
The configuration of the 20-terminal connector of the module is shown in the
following figure:
P5/EN M/33C 75
Protection Relay Installation
B DI1 1
2
3
1 DI1
2 DI2 4
3 5
4 DI2
5 DI3 6
6 DI3 DI4 7
7
8 DI4 8
9
DO1 DO1 9
10 HS
11 10
12 DO2
13 DO2 11
C
14 12
15 DO3 C
16 13
17 WD DO3 14
18 C
19 15
20 Power supply
WD 16
17
18
19
20 P533DMA
Watchdog
The watchdog (self-monitoring) is a changeover contact provided on slot B, digital
output WD, to indicate the health of the device (refer to Watchdog relay, page
435). Schneider Electric strongly recommends that these contacts are hardwired
into the substation's automation system for alarm purposes.
B16
16
17 B17
18
B18
P533DNA
76 P5/EN M/33C
Installation Protection Relay
P533DOA
NOTICE
IMPROPER EQUIPMENT OPERATION
Specific wiring requirements for counting input 12I4O DI1:
• Unshielded twisted pair cable between pin 1 and pin 7
• Section 0.4 to 1.5 mm²
• Example of recommended cable : Belden 9409 or equivalent
• No earth/ground connection on the Easergy P5 side or on the other side to
keep the line symmetrical
• Maximum cable length: 10 m
Failure to follow these instructions can result in equipment damage.
NOTICE
IMPROPER EQUIPMENT OPERATION
If the counting input DI1 on 12I4O is selected, this input cannot be used by any
other protection functions.
Failure to follow these instructions can result in equipment damage.
P5/EN M/33C 77
Protection Relay Installation
D E DI1 1
2
DI2 3
4
DI1 DI3 5
6
DI2
DO1 C
7
DI3
8
DO1 DO2 9
C
10
DO2 C
11
DO3 DO3 S
12
13
Arc1 14
Arc2 Arc1 15
L> 16
Arc3
Arc2 17
L> 18
Arc3 19
L> 20
P533DPA
P533DQA
Subsequent operation After installing the connectors, stick the connector identification labels
included in the package on the rear panel above the connectors.
78 P5/EN M/33C
Installation Protection Relay
Single wire: 0.4 ... 0.5 N.m (—) 2.5 mm (3/32 in.)
0.2 ... 2.5 mm2 (3.5 ... 4.4 lb-in) flat blade screwdriver
(AWG 24 ... 14)
Double wires:
L P533DRA 0.2 ... 1.5 mm2
(AWG 24 ... 16)
Contact tip length
L = 12 mm (0.5 in.)
P533DSA
P533DTA
P533DUA
P533DVA
P533DWA
Connecting earth/ground
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Connect the Easergy P5 protection relay to earth/ground with a nut and
washer using any of the indicated stud terminals (see Fixing the earthing/
grounding cable to the Easergy P5 protection relay, page 80 below).
• Check equipotential earthing/grounding network and test earth/ground
during installation.
Failure to follow these instructions will result in death or serious injury.
The earth/ground connections are accessible on the rear panel of the protection
relays. For Easergy P5x20, there are two connectors located in the bottom left or
right corner of the protection relays; For Easergy P5x30, there are three, one in
the bottom right corner and the other two near Connector A.
P5/EN M/33C 79
Protection Relay Installation
P533DXA
P533DYA
3 P533DZA
Every Easergy P5 must be connected to the local earth/ground bar using one M4
earth/ground stud on the relay case to prevent dangerous voltages being present
in case of a wiring fault or damage to the product. Also, it helps to ensure that the
Easergy P5 protection relay meets EMC claims.
80 P5/EN M/33C
Installation Protection Relay
The minimum recommended wire size is 2.5 mm² (AWG 14) and should have a
ring terminal at the relay end. Due to the limitations of the ring terminal, the
maximum wire size that can be used is 6.0 mm² (AWG 10) per wire.
P5/EN M/33C 81
Protection Relay Installation
NOTICE
IMPROPER EQUIPMENT OPERATION
Use RJ45 cable no longer than 10 m (32.8 ft).
Failure to follow these instructions can result in improper operation.
The Easergy P5 protection relay range includes optional rear communication ports
and modules with RJ45 or fibre optic connections. The ports and modules are
accessible in the lower part of the rear panel. The following figure shows the
location of these single or dual communication ports and modules:
Slot M Dual port Ethernet TP or fibre optic module, configurable to RSTP redundancy
mode or Dual IP mode without redundancy
Slot P Single extension port for connection with external module and demodulated IRIG-
B input and Back-up memory
82 P5/EN M/33C
Installation Protection Relay
NOTICE
IMPROPER EQUIPMENT OPERATION
• Check and make sure the communication modules are locked on the
protection relay.
• Never plug in or draw out the communication modules while the Easergy P5
protection relay is in service, otherwise the Easergy P5 protection relay will
reboot and consequently lose the setting changes made within the last 30
minutes.
Failure to follow these instructions can result in setting change erasure
and consequently mis-operation of the protection relay.
P5/EN M/33C 83
Protection Relay Installation
P533M4A
Characteristics
Location Slot L
Connection 2 x RJ45 connectors with communication indicators
P533M6A
Protocol TP or RSTP
Maximum cable length 10 m (32.8 ft)
84 P5/EN M/33C
Installation Protection Relay
1 2
P533M7A
Characteristics
Location Slot M
Connection 2 x RJ45 connectors with communication
indicators
P533M6A
Protocol TP or RSTP
Maximum cable length 10 m (32.8 ft)
P5/EN M/33C 85
Protection Relay Installation
CAUTION
EYE DAMAGE AND BLINDNESS
Never look into the end of the fibre optic.
Failure to follow these instructions can result in serious injury.
NOTICE
IMPROPER EQUIPMENT OPERATON
• Use only Schneider approved optical transceiver components.
• Never replace the optical transceiver components with unauthorised
manufactured parts.
Failure to follow these instructions can result in equipment damage.
Use optical power meters to determine the operation or signal level of the device.
If electrical-to-optical converters are used, they must have management of
character idle state capability (when the fibre optic cable interface is "Light off").
Specific care should be taken with the bending radius of the fibres, and the use of
optical shunts is not recommended as these can decrease the communication
performance of the transmission path over time.
Characteristics
Location Slot M
Connection 2 LC connectors
P533M9A
Protocol TP or RSTP
Maximum attenuation (fibre optic + connectors) 14 dB (at fibre optic diameter: 62,5/125 μm or
50/125 μm)
86 P5/EN M/33C
Installation Protection Relay
1 2
P533MAA
VW3A8306RC 1 nF 120 Ω
4
1 nF 120 Ω 5
4 1
2
5 1 nF 120 Ω
P533MBA
The internal polarisation resistor 620 Ω can be enabled or disabled with eSetup
Easergy Pro (see parameter "pull line" in the communication manual).
In order to avoid signal reflections on the line, data transmission lines should
always be terminated with a RC terminating impedance (120 Ω/1 nF, reference
VW3A8306RC), or with a 4 line option that includes 2 pairs of 120 Ω/1 nF RC
terminating impedance, fitted at both ends across the signal wires.
P533MCA
P5/EN M/33C 87
Protection Relay Installation
Characteristics
Location Slot N
P533M6A
Protocol TP or RSTP
Line polarisation 620 Ω
EIA-485-2
1 1
1 8 8 8
EIA-485-4
1 1
2 2
4 4
5 5
8 8
P533MDA
88 P5/EN M/33C
Installation Protection Relay
CAUTION
EYE DAMAGE AND BLINDNESS
Never look into the end of the fibre optic.
Failure to follow these instructions can result in serious injury.
Use optical power meters to determine the operation or signal level of the device.
If electrical-to-optical converters are used, they must have management of
character idle state capability (for when the fibre optic cable interface is "Light
off").
Specific care should be taken with the bending radius of the fibres, and the use of
optical shunts is not recommended as these can decrease the performance of the
transmission path over time.
The relay uses 1300 nm multi-mode 100BaseFx ST(BFOC) 2.5 connectors (one
Tx/optical emitter, one Rx/optical receiver).
Characteristics
Location Slot N
Connection 2 x ST (BFOC) connectors
P5/EN M/33C 89
Protection Relay Installation
P533MGA
NOTICE
ETHERNET PORT DAMAGE
Connect only Easergy P5 accessories to the extension module.
Failure to follow these instructions can result in equipment damage.
Characteristics
Location Slot P
Connection RJ45 connector
P533M6A
90 P5/EN M/33C
Installation Protection Relay
Slot M & N: Ethernet communication module with HSR and PRP redundancy (reference
REL51033)
The Ethernet communication module is inserted in both slot M and N of the
device. It can be selected as an option when ordering the device or purchased
later and installed on site. It provides PRP (Parallel Redundancy Protocol) and
HSR (High-availability Seamless Redundancy) and is selectable by configuration.
The module allows instantaneous reconfiguration of the communication system
without communication packet loss.
P533MHA
CAUTION
EYE DAMAGE AND BLINDNESS
Never look into the end of the fibre optic.
Failure to follow these instructions can result in serious injury.
Use optical power meters to determine the operation or signal level of the device.
If electrical-to-optical converters are used, they must have management of
character idle state capability (when the fibre optic cable interface is "Light off").
Specific care should be taken with the bending radius of the fibres, and the use of
optical shunts is not recommended as these can decrease the communication
performance of the transmission path over time.
P5/EN M/33C 91
Protection Relay Installation
Characteristics
Location Both slot M and N
Connection 2 LC connectors
P533M9A
92 P5/EN M/33C
Installation Protection Relay
Other accessories
CSH120 (reference 59635), CSH200 (reference 59636), CSH300 (reference 59637) and
GO110 (reference 50134)
Description
The CSH120, CSH200, CSH300 and GO110 core balance current transformers
(CT) are designed for direct residual current measurement. Due to their low
voltage insulation, they can only be used around insulated cables.
CSH300 ①, CSH200 ② and CSH120 ③ are closed CTs, with different inner
diameters:
• CSH300 ① inner diameter: 291mm (11.46 in.)
• CSH200 ② inner diameter: 196 mm (7.72 in.)
• CSH120 ③ inner diameter: 120 mm (4.72 in.)
GO110 ④ is a split CT, with an inner diameter of 110 mm (4.33 in.).
NOTE: GO110 core balance transformer is not sold anymore. However, for
any refurbishing projects, the Easergy P5 protection relay is compliant with
this core balance transformer and therefore can be connected together as
shown in Typical application diagrams, page 57.
F0550
P533H3A
P5/EN M/33C 93
Protection Relay Installation
Dimensions
Figure 89 - CSH120, CSH 200 and CSH300 dimensions
4 x ØM 4 x ØN
F ØA H K B
J L
E D
P533H4A
A B D E F H J K L M N
CSH120 120 mm 164 mm 44 mm 190 mm 80 mm 40 mm 166 mm 65 mm 35 mm 6 mm 5 mm
(4.72 in.) (6.46 in.) (1.73 in.) (7.48 in.) (3.15 in.) (1.57 in) (6.54 in.) (2.56 in.) (1.38 in.) (0.24 in.) (0.2 in.)
D
T1 T1 M5
E
C
T2
ØB
T2
ØA
G F
P533H5B
A B D E F G
110 mm (4.33 in.) 224 mm (8.82 in.) 92 mm (3.62 in.) 16 mm (0.63 in.) 44 mm (1.73 in.) 8 mm (0.31 in.)
94 P5/EN M/33C
Installation Protection Relay
Assembly
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Only qualified personnel should install this equipment. Such work should be
performed only after reading this entire set of instructions.
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backreading.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Only CSH120, CSH200 and GO110 core balance CTs can be used for direct
residual current measurement.
• Install the core balance CTs on insulated cables.
• Cables with a rated voltage of more than 1000 V must also have an earthed/
grounded shielding.
Failure to follow these instructions will result in death or serious injury.
Select a CT with a diameter at least twice the size of the cable harness going through it
Group the cable(s) in the middle of the CT and use non-conducting binding to hold the CT
in place around the cable harness.
Do not bend the cable(s) close to the CT; install the CT on a straight section of the cable(s)
that is at least twice as long as the CT diameter.
Remember to pass the shielded earthing/grounding braid on the cables back through the
CT. Check that the braid goes the right way through the CT.
When assembling the core balance CTs, group the medium voltage cable (or
cables) in the middle of the core balance CT, use non-conductive binding to hold
the cables, and remember to insert the shielded earthing/grounding braid of the
medium voltage cable through the core balance.
P5/EN M/33C 95
Protection Relay Installation
Connection
Recommended cable:
• Sheathed cable (to be compliant with electromagnetic compatibility
requirements), shielded by tinned copper braid.
• Resistance per unit length < 100 mΩ/m (30.5 mΩ/ft).
• Minimum dielectric strength: 1000 V (700 Vrms).
• Connect the cable shielding in the shortest manner possible to the protection
relay.
• Flatten the connection cable against the metal frames of the cubicle.
The maximum resistance of the connection wiring must not exceed 4 Ω (i.e. 20 m
maximum for 100 mΩ/m or 66 ft maximum for 30.5 mΩ/ft).
15/17
16/18
12 cm max
P5 ground stud
P533H6A
Note that for specific application, it is possible to connect 2 CSH200 core balance
CTs in parallel, for example, when the medium-voltage cables have a large
diameter and the installation uses 2 or 3 conductors per phase.
NOTICE
UNINTENDED AND NUISANCE TRIPPING
The shield of the CSH cable must be connected to the nearest Easergy P5
protection relay earth/ground stud with a cable of less than 12 cm (4.72 in.).
Failure to follow these instructions can result in equipment misoperation.
96 P5/EN M/33C
Installation Protection Relay
Characteristics
Table 16 - Characteristics of the core balance CTs
Transformation 470/1
ratio
Maximum 20 kA - 1s
permissible
current (1CT)
Maximum - 6 kA - 1s 6 kA - 1s -
permissible
current (2 CSHs
in parallel)
P5/EN M/33C 97
Protection Relay Installation
Description
The LPVT hub connector is a simple passive device that combines three LPVT
signals coming from 3 different connectors on one single RJ45 connection.
The output of the LPVT hub connector is directly connected to the LPVT input of
the Easergy P5 protection relay.
The LPVT Hub connector also manages the presence of each LPVT connection
thanks to a daisy chain across the three sensors. If at least one LPVT is missing or
one cable is damaged, an alarm event is logged and displayed on the local panel.
LPVT L3
LPVT L2
LPVT L1
OUT
P533H7A
Connection
The LPVT hub connector is connected to the protection relay through its RJ45
output connector and to the LPVT sensors through the RJ45 input connectors.
LPVT L3 LPVT L3
LPVT L2 LPVT L2
LPVT L1 LPVT L1
OUT OUT
P533H8A
98 P5/EN M/33C
Installation Protection Relay
Characteristics
Table 17 - Characteristics of the LPVT hub connector
Characteristics Values
Electric
Input voltage < 10 V
Form factor
Dimension (L x W x H) 95 mm x 40 mm x 40 mm (3.74 x 1.57 x 1.57 in)
Environment
IP degree of protection IEC 60529 IP30
P5/EN M/33C 99
Protection Relay Installation
Description
The voltage transformer adapter is made with 4 resistor bridges used to interface
conventional voltage transformers (VTs) with the Easergy P5 protection relay
equipped for LPCT/LPVT sensors (please order this accessory separately from
Schneider Electric).
Connection
NOTICE
INCORRECT VOLTAGE MEASUREMENT
• The earth/ground of the connection diagrams below must be the same of the
whole Easergy P5 protection relay. The 0 V of the Easergy P5 power supply
input must be connected to this earth/ground.
• Earth/ground connection point of AC voltage adapter must be connected to
the isolated ground of VT sensor (LV transformer). For other wiring cases,
please consult Schneider Electric.
Failure to follow these instructions can result in measurement error.
RJ45 cable
Brown
Black
Grey
Earth/ground connection
point of voltage adapter
P533H9A
RJ45 cable
Brown
Black
Grey
Earth/ground connection
point of voltage adapter
P533HAA
RJ45 cable
RJ45 cable
Black
Earth/ground connection
point of voltage adapter
P533HCA
RJ45 cable
Brown
Earth/ground connection
point of voltage adapter
P533HDA
Dimensions
Figure 99 - External dimensions of the AC voltage adapter
B C
P533HEA
A B C D E
120 mm (4.72 in.) 38 mm (1.49 in.) 52 mm (2.04 in.) 90 mm (3.54 in.) 25 mm (0.98 in.)
Mounting
Screw
Click!
Screw
P533HFA
P533HHA
Mounting the adapter by its Mounting the adapter using Mounting the adapter on
fixture structure on rail two fastening collars (width: 4 Telequick grid using two
mm/0.16 in) screws (4 mm/0.16 in)
Locked in Locked in
close position open position
P533HGA
Characteristics
Table 18 - Characteristics of the voltage adapter
Humidity IEC 60068-2-30 95% HR; 144 hours (6 cycles of 12 hours at 55°C
(131°F) and another 12 hours at 25°C (77°F))
P533ONA
Its action is to close the loop of the sensor presence detection on pins 3-6 of the
RJ45 and to zeroed the low voltage inputs shorting the 3 others pairs of the RJ45
connector. (1-2, 4-5, 7-8)
8 PIN 5 PIN 1
7
6 PIN 4 PIN 2
5
4
3 PIN 3 PIN 7
2 1
1 1 PIN 6 PIN 8
P533HIA
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Clean the arc sensor periodically as instructed in this user manual and after an
arc-flash fault.
Failure to follow these instructions will result in death or serious injury.
Description
The arc-flash sensors are used by Easergy P5x30 to detect light coming from an
arc-flash incident, they are installed in the protection zone and connected to the
connector terminal on the protection relay.
The arc-flash sensor is activated by strong light caused by an arcing fault. The
sensor transforms light information into a current signal, which is used by the
protection relay to detect an arc-flash and provide the corresponding protection
function.
Dimensions
Figure 103 - Dimensions of the standard arc-flash sensors
mm 22.2
in 0.83 20
14 0.79
0.55
0.39
10
25
1.83
46.4
0.98
8
0.31
4.2
0.17 P533HJA
11 62
0.43 2.44
P533HKA
Characteristics
Table 19 - Characteristics of the standard arc-flash sensors
Shielded - - ■ - - ■
cable
Halogen - ■ - ■ - -
free
Material Plastic
Weight (g/ 1,000/2.2 1,300/2.87 1,300/2.87 300/0.66 400/0.88 400/0.88
lb)
Loop Yes
supervi-
sion
Shielded cable - ■ - ■
Halogen free - - - -
Material Plastic
Weight (g/lb) 1,000/2.2 1,300/2.87 300/0.66 400/0.88
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Never attempt to extend the length of arc-flash sensor cables.
Failure to follow these instructions will result in death or serious injury.
13. To connect the interface in the Easergy P5 protection relay, use REL52883 cable.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS-2011, or
CSAZ462.
• The arc fault detection system is not a substitute for proper PPE when
working on or near equipment being monitored by the system.
• Information on this product is offered as a tool for conducting arc-flash
hazard analysis. It is intended for use only by qualified persons who are
knowledgeable about power system studies, power distribution equipment,
and equipment installation practices. It is not intended as a substitute for the
engineering judgement and adequate review necessary for such activities.
• Only qualified personnel should install and service this equipment. Read this
entire set of instructions and check the technical characteristics of the device
before performing such work.
• Perform wiring according to national standards (NEC) and any requirements
specified by the customer.
• Observe any separately marked notes and warnings.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume all circuits are
live until they are completely de-energized, tested, and tagged. Pay
particular attention to the design of the power system. Consider all sources
of power, including the possibility of back feeding.
• Always use a properly rated voltage sensing relay to ensure that all power is
off.
• The equipment must be properly grounded.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
• Do not open the device. It contains no user-serviceable parts.
• Install all devices, doors and covers before turning on the power to this
device.
Failure to follow these instructions will result in death or serious injury.
Install arc-flash sensors inside the switchgear. There are two options for mounting
the sensors:
• in customer-drilled holes on the switchgear
• on VYX001 Z-shape or VYX002 L-shape mounting plates available from
Schneider Electric or locally fabricated from supplied drawings
59
2.32 2.5
42 0.1
1.65
10
0.39
15
50 0.59
7
1.97
0.28
P533HLA
15 59 15
0.59 2.32 0.59
3
0.12
30
1.18
30
1.18 P533HMA
P533HNA
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Never attempt to extend the length of arc-flash sensor cables.
Failure to follow these instructions will result in death or serious injury.
D 15 +
Sensor 1
D 16 -
D 17 +
Sensor 2
D 18 -
D 19 +
Sensor 3
D 20 -
E 15 +
Sensor 4
E 16 -
E 17 +
Sensor 5
E 18 -
E 19 +
Sensor 6
E 20 -
P533HOA
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Check that the temperature sensors are isolated from dangerous voltages.
Failure to follow these instructions will result in death or serious injury.
Description
The temperature sensor module is an external module used for temperature
measurement with Resistance Temperature Detectors (RTDs). It is connected to
the extension module. It can be selected as an option when ordering the device or
purchased later and installed on site. It provides 8 RTD inputs.
Connection
Figure 110 - Connection of the MET148-2 temperature sensor module
Characteristics
Table 22 - Characteristics of the MET148-2 temperature sensor module
Characteristics Values
Dimensions (L × W × D) 144 mm × 88 mm × 30 mm
(5.67 in × 3.46 in × 1.81 in) 14
Temperature sensors
Current to RTD 4 mA 4 mA
Maximum distance between sensor 1 km (0.62 mi)
and MET148-2
Description
The IRIG-B module is an external module used for accurate time synchronisation.
It is connected to the extension module. It can be selected as an option when
ordering the device or purchased later and installed on site.
The module provides both a modulated (MOD INPUT) and an unmodulated input
(UNMOD INPUT) and can automatically detect which input type is used by the
user. No configuration of input type is needed in the Easergy P5 protection relay.
It does not require any auxiliary supply connection.
MOD
INP
UT
UNM
OD
INPUT
IRIG
0
GN
-B
EXT O
UT
EXT IN
P533HRA
Characteristics
Table 23 - Characteristics of the IRIG-B module
Characteristics Values
Standard
Standard IRIG 200-04
Form factor
Height 95 mm (3.7 in)
Connection
The IRIG-B module is connected to the Easergy P5 protection relay from its EXT
IN port. The cable used for connection must be shielded and of a length not
exceeding 10 m (32.8 ft).
The IRIG-B module provides an additional extension port (EXT OUT) for
connecting other accessories such as the MET148-2 module with CCA77x cords.
The time source is connected to the module through the modulated input, or
through the unmodulated input by connecting signal + to the IRIG-B terminal, and
signal - to the 0+ terminal.
NOTE: If one source is connected on the modulated input and another one on
the unmodulated input, the modulated signal has the priority.
5
8
2
EXT IN
T
EXT OU
3
MOD INPUT UNMOD INPUT 4
8
IRIG-B
0+
GND
P533HSA
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Install IRIG-B module between Easergy P5 protection relay and any other
accessories like MET148-2 temperature module.
• Do not interface any accessories between Easergy P5 protection relay and
IRIG-B module.
Failure to follow these instructions will result in death or serious injury.
Commissioning
Principles
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• NEVER work alone.
• Only qualified personnel should commission this equipment. Such work
should be performed only after reading this entire set of instructions.
• Obey all existing safety instructions when commissioning and maintaining
high-voltage equipment.
• Beware of potential hazardous voltages from open circuited current
transformers, any voltage transformers and any capacitors which could be
charged to hazardous voltages.
• Before energising check that the protection relay and other devices are
connected to a protective earth/ground in accordance with the instructions
provided.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
Apply proper tightening torque to all wire connections.
Failure to follow these instructions will result in death or serious injury.
WARNING
IMPROPER EQUIPMENT OPERATON
Do not energise the primary circuit before this protection relay is properly
configured.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Never open the secondary circuit of a live CT since the high voltage
produced may be lethal to personnel and could damage insulation.
• The secondary of the line CT must be shorted before opening any
connections to it.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
elecrtrical work practices. See NFPA 70E, CSA Z462 or national equivalent.
• Do not choose lower personal protective equipment (PPE) while working on
energised equipment.
Failure to follow these instructions will result in death or serious injury.
Easergy P5 protection relays are tested prior to commissioning, with the dual aim
of maximizing availability and minimizing the risk of malfunctioning of the
assembly being commissioned.
Easergy P5 protection relays are fully numerical in their design, implementing all
protection and non-protection functions in the firmware. The protection relays use
a high degree of self-checking and give an alarm. Therefore, the commissioning
tests do not need to be as extensive as with non-numeric electronic or electro-
mechanical relays.
To commission Easergy P5 protection relays, it is necessary to verify that the
hardware is functioning correctly and the application function settings have been
applied as expected. To confirm that the protection relay is operating correctly
once the settings have been applied, it is necessary to perform basic functional
tests on each active protection element one by one.
The main tasks for the commissioning test are as follow:
• Easergy P5 protection relay check
• Secondary injection test
• Primary injection test
• Final check
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Never open-circuit the secondary circuit of a current transformer because
the high voltage produced may be lethal. It could also damage the insulation.
• Before the test plug is inserted into the test block, make sure the sockets in
the test plug which correspond to the current transformer secondary
windings are linked.
Failure to follow these instructions will result in death or serious injury.
- Vaux + Vaux
1 2
V1
3 4
V2
5 6
7 8 V3
9 10 Output
11 12
+ Vaux
13 14 - Vaux
15 16 Trip
- Trip 17 18
+ Trip 19 20
Input
21 22
IL1
23 24
IL2
25 26
IL3
27 28
I0
Shorting bar
P533I0A
Before inserting the test plug, refer to the scheme diagram. For example, the test
block may be associated with protection current transformer circuits. If an Easergy
P5 protection relay is installed in the switchgear, the test block is not always
provided. In the application case without a test block, it is mandatory to isolate the
voltage transformer supply to the Easergy P5 protection relay using the panel links
or connecting blocks, and to short-circuit and disconnect the line current
transformers from the protection relay terminals. Where means of isolating the
auxiliary power supply and trip circuit (such as isolation links, fuses and MCB) are
provided, these should be used. If this is impossible, the wiring to these circuits
must be disconnected and the exposed ends suitably terminated.
Visual inspection
The visual inspection should include the following aspects:
• Check the rating information on the Easergy P5 protection relay.
• Check that the Easergy P5 protection relay being tested is correct for the
protected objective.
• Check that the circuit reference and system details are entered onto the
setting record sheet (not provided).
• Carefully examine the Easergy P5 protection relay to see that no physical
damage has occurred since installation.
• Check that the case earthing/grounding connections, at the rear of the
protection relay case, are used to connect the protection relay to a local earth/
ground bar using an adequate conductor (see Connecting earth/ground, page
79).
External wiring
• Check that the external wiring is correct to the relevant protection relay
diagram and wiring scheme. Check that the phase rotation appears as
expected.
• Check the connections against the wiring diagram if a test block is provided.
NOTICE
POWER SUPPLY DAMAGE
Before connecting the auxiliary voltage to the Easergy P5 protection relay:
Make sure the nominal value of the auxiliary device voltage corresponds with
the nominal value of the auxiliary system voltage.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The power supply must be turned off for at least 5 s before power supply
module is removed. Otherwise there is the danger of an electric shock.
Failure to follow these instructions will result in death or serious injury.
Watchdog
Using a continuity tester, check that the watchdog contacts (DO4 of slot B) are in
the states shown in the Watchdog contact status table for a de-energised
protection relay.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• The current and voltage transformer connections must remain isolated from
the protection relay for these checks.
• The trip circuit must remain isolated to help prevent accidental operation of
the associated circuit breaker.
Failure to follow these instructions will result in death or serious injury.
Watchdog
Using a continuity tester, check that the watchdog contacts (DO4 of slot B) are in
the states shown in the Watchdog contact status diagram for an energised
protection relay.
On the local panel of Easergy P5 protection relay, press the and then the
key to test the local panel HMI, the protection relay automatically tests all the
LEDs and the screen. The triple color LEDs are lit from green, yellow to red. The
LCD is tested under different colors and contrast values.
Digital inputs
This test checks that all the Easergy P5 protection relay’s digital inputs (opto-
isolated) are functioning correctly. Check the terminal configuration schemes in
Easergy P5 rear panel, page 50 for terminal numbers. Check the polarity and
connect the external 48 V DC supply voltage to the appropriate terminals for the
input being tested. Energise the opto-isolated input one by one.
NOTE: The external power supply is used for this test, but only after
confirming that it is suitably rated, with the variation less than 20%.
The status of each opto-isolated input can be viewed in the Digital inputs view of
the Control menu; a "1" indicating an energised input and a "0" indicating a de-
energised input. When each opto-isolated input is energised, the related DI status
changes to indicate the new state of the inputs.
Digital outputs
This test checks that all the output contact relays are functioning correctly using
the Test mode.
Connect a continuity tester across the terminals corresponding to output relay as
shown in the relevant terminal configuration schemes in Easergy P5 rear panel,
page 50. To operate the output relay DO1 in Slot B, set the field DO1(B) to 1 in the
Digital output Slot X view of the Control menu. Operation is confirmed by the
continuity tester operating for a normally open contact and ceasing to operate for
a normally closed contact. Measure the resistance of the contacts in the closed
state. Reset the output relay by setting the DO1(B) field to 0. Repeat the test for
the rest of the output relays then return the Easergy P5 protection relay to service
by setting the IED mode back to "Normal".
NOTE: Ensure that the thermal ratings of anything connected to the output
relays during the contact test procedure are not exceeded by the over-
operated output contact relays. Keep the time between application and
removal of contact test to a minimum.
Communication ports
The Easergy P5 protection relay supports both serial communication ports and
Ethernet communication ports.
There are five protocols that can be selected and used to communicate through
the serial ports.
• DNP3
• IEC 60870-5-101
• IEC 60870-5-103
• Modbus slave
• Modbus master
If one of these protocols is configured, the Easergy P5 protection relay can
exchange data with protocol master. The serial port parameters, e.g. baud rate,
parity, wire number, can be selected and will take effect after reboot.
There are four protocols that can be selected and used to communicate through
the Ethernet ports.
• IEC 61850
• DNP3
• Modbus
• EtherNet/IP
Three Ethernet protocols can be selected at the same time, and for each protocol
IP address needs to be selected to communicate with clients.
Virtual injections
1. Click on the green button on right-hand side to expand the injector view that
is by default hidden in eSetup Easergy Pro.
3. Select Test mode or Test Block mode for the virtual injection test.
Virtual injections are available only in Test mode or Test Block mode (see Mode
of use for testing purposes, page 176 for more information).
4. Set “Auto read” to On in the menu bar of eSetup Easergy Pro in order to read
the measurements.
Manual injection
In the “Manual” tab of the Virtual injection setting view, set the following
parameters:
• Cycles:
Set the value to the number of signal period to apply for the signal simulation.
• Frequency:
Set the frequency of the signal to inject.
• Scalings:
Set the maximum values and angles.
• Measurements:
Set the injection values for the testing.
Figure 114 - The Virtual injection setting view in eSetup Easergy Pro
The injection time can be set in cycles or in real time. For example, for 50 Hz
nominal frequency, one cycle is 20 ms, so 100 cycles equal to 2 s of injection time.
All the signals are simulated with their fundamental value (no harmonics) and
instantaneously displayed in the Graph section of the view.
Injection
Press on the Start button in the upper section of the view for the injection.
Any protection function that is enabled and of which the threshold setting is below
the injection will activate, with the magnitudes displayed in the measurements
section of the view.
The Easergy P5 protection relay will trip and activate digital outputs physically in
the Test mode and will stay frozen in the Test-block mode.
NOTE: Do not try to manually change the mode while using the injector.
Figure 116 - Secondary injection test connection diagram with test block
L1
L2
L3
Easergy P5
Connector A
Test block + Test plug
A1
A2
A3
A4
A5
A6
A9
A10
A11
A12
A13
A14 V
A15
V
A16
V
A A A A
3-phase
generator A V
P533I1A
In the application case without test block, it is mandatory to remove the voltage
transformer cable. The trip circuit shall be disconnected to avoid the spurious
circuit breaker trip during the secondary injection test. The secondary injection test
can be performed by injecting the current and voltage into the related analogue
connection terminals on the rear panel of the Easergy P5 protection relay via the
test block.
function under test can be enabled. After the completion of the injection tests, all
the protection functions applied must be enabled during the final check stage.
Current inputs
This test verifies that the accuracy of current measurement is within acceptable
tolerances.
• Double check the connection and then start the injection test.
• Apply current equal to the related CT secondary rated current.
• Check its magnitude using a multimeter or reading from the test equipment.
• Check the current magnitude displayed on the local panel of the Easergy P5
protection relay.
• Calculate the current measurement accuracy, it shall be within ±1%.
P5F30 VT ■ ■ ■ ■ ■ ■ ■
LPVT ■ ■
LPVT + VT Adapter ■ ■ ■ ■
P5M30 VT ■ ■ ■
LPVT ■
LPVT + VT Adapter ■ ■
P5V20 VT ■ ■ ■ ■ ■ ■ ■
P5U20 LPVT ■ ■
LPVT + VT Adapter ■ ■ ■ ■
Voltage inputs
This test verifies that the accuracy of voltage measurement is within the
acceptable tolerances.
Seven modes of connection are available on the Easergy P5 protection relay:
Mode U1 U2 U3 U4
3LN VL1 VL2 VL3 -
The following tests will be realised with the VT Connecting Mode set to 3 VT which
is the most used configuration.
• Double check the connection and then start the injection test.
Figure 117 - Connection diagram for testing the LPCT and LPVT
measurement accuracy
L1
L2
L3
Easergy P5
Connector A
S1 A1 1
CSH
A2 2
A3 3
A4 4
Voltage
Generator
IL1 RJ45 1
2
IL2 RJ45 1
LPCTs
2
IL3 RJ45 1
2
LPVT Hub
4
5 VL1, VL2, VL3 RJ45
4
LPVTs
5
4 RJ45
5
P533I2C
LPCT measurement
This test verifies that the accuracy of LPCT measurement is within acceptable
tolerances.
• Disconnect the secondary of LPCTs from the Easergy P5 protection relay.
• Use a generator with low voltage output (30 V max) and connect it directly to
the Easergy P5 protection relay as described inTesting tools and equipment,
page 115.
• Apply current equal to the related LPCT secondary rated current.
• Check its magnitude using a multimeter or reading from the test equipment.
• Check the current magnitude displayed on the local panel of the Easergy P5
protection relay.
• Calculate the LPCT measurement accuracy, it shall be within ±1%.
NOTE: To be sure everything is well reconnected after test, it is recommended
to perform a primary injection, at low level.
LPVT measurement
This test verifies that the accuracy of LPVT measurement is within acceptable
tolerances.
• Disconnect the secondary of LPVTs from the LPVT hub.
If the LPVT hub is not accessible inside the cubicle, disconnect the secondary
of the LPVT hub from the Easergy P5 protection relay, and connect another
one to replace it during the tests.
• Use a generator with low voltage output (10 V max) and connect it directly to
the LPVT hub as described in Testing tools and equipment, page 115.
• Apply voltage equal to the related LPVT secondary rated voltage.
• Check its magnitude using a multimeter or reading from the test equipment.
• Check the voltage magnitude on the local panel of the Easergy P5 protection
relay.
• Calculate the LPVT measurement accuracy, it shall be within ±1%.
NOTE: To be sure everything is well reconnected after test, it is recommended
to perform a primary injection, at low level.
Current protection
This test, performed on stage 1 of the overcurrent protection function in setting
group 1, is to check that the protection relay is operating correctly at the
application-specific settings.
1. Determine which output relay has been selected to operate when an I> trip
occurs.
2. Connect the output relay so that its operation will trip the test set and stop the
timer of the injection box.
3. Connect the current outputs of test set (current injection source) to the
protection relay current input terminals.
4. Apply a current of 120% of the current setting to the protection relay and the
relay shall trip according to the operation time setting.
5. Check the tripping time from the test set and compare with the operation time
setting.
6. Check the related fault recorder, events, and the related LEDs for trip
indications.
A similar test procedure can be applied for the secondary injection test to check
the other protection functions with the application-specific settings.
Voltage protection
This test, performed on stage 1 of the under-voltage protection function in setting
group 1, is to check that the protection relay is operating correctly at the
application-specific settings.
1. Determine which output relay has been selected to operate when a U< trip
occurs.
2. Connect the output relay so that its operation will trip the test set and stop the
timer.
3. Connect the voltage outputs of the test set (voltage injection source) to the
protection relay voltage input terminals.
4. Apply normal voltage first and then a voltage of 80% of the voltage setting to
the protection relay. The relay shall trip according to the operation time
setting.
5. Check the tripping time from the test set and compare with the operation time
setting.
6. Check the related fault recorder, events, and the related LEDs for trip
indications.
A similar test procedure can be applied for the secondary injection test to check
the other protection functions with the application-specific settings. P5/
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The primary injection test shall be performed by the qualified electrical
engineers and strictly follow the related primary injection testing instructions
from the utility.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
If any of the external wiring was disconnected from the protection relay to run
any tests, make sure that all connections are restored according to the external
connection or scheme diagram.
Failure to follow these instructions will result in death or serious injury.
Voltage connections
NOTICE
CIRCUIT OVERLOAD
• Using a multi-meter, measure the voltage transformer secondary voltages to
ensure they are compliant with the Easergy P5 protection relay’s input
ratings.
• Check that the system phase rotation is correct using a phase rotation meter.
Failure to follow these instructions can result in equipment damage.
Thus, the VT ratio, polarity, phase sequence and the external wiring from the
primary system to the protection relay can be verified by the primary voltage
injection.
Current connections
NOTICE
CIRCUIT OVERLOAD
Measure the current transformer secondary values for each input using a
multimeter connected in series with corresponding protection relay current
input.
Failure to follow these instructions can result in equipment damage.
LPCT connections
NOTICE
MEASUREMENT LOSS
Make sure that LPCTs are connected to all 3 phases with low power sensors or
with RJ45 plug.
Failure to follow these instructions can result in no current measured.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS-2011, or
CSAZ462.
• The arc fault detection system is not a substitute for proper PPE when
working on or near equipment being monitored by the system.
• Information on this product is offered as a tool for conducting arc-flash
hazard analysis. It is intended for use only by qualified persons who are
knowledgeable about power system studies, power distribution equipment,
and equipment installation practices. It is not intended as a substitute for the
engineering judgement and adequate review necessary for such activities.
• Only qualified personnel should install and service this equipment. Read this
entire set of instructions and check the technical characteristics of the device
before performing such work.
• Perform wiring according to national standards (NEC) and any requirements
specified by the customer.
• Observe any separately marked notes and warnings.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume all circuits are
live until they are completely de-energized, tested, and tagged. Pay
particular attention to the design of the power system. Consider all sources
of power, including the possibility of back feeding.
• Always use a properly rated voltage sensing relay to ensure that all power is
off.
• The equipment must be properly grounded.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
• Do not open the device. It contains no user-serviceable parts.
• Install all devices, doors and covers before turning on the power to this
device.
Failure to follow these instructions will result in death or serious injury.
Checking zones
End
P533I3A
Checking zones
• Check the protected zones where sensors have been installed and compare
them against the drawings.
• Consult the customer if the configuration does not match with the drawings.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Removing trip wires may cause loss of protection. Review system drawings and
diagrams before disconnecting trip circuits.
Failure to follow these instructions will result in death or serious injury.
• Disconnect the trip signals to the circuit breakers that may disturb other parts
of the system during the test.
• Also disconnect trip signals routed to other parts of the system, such as the
breaker failure (ANSI 50BF) backup trip to upstream breakers and the
transfer trip signals.
• Test the disconnected trip signals with a multimeter.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS-2011, or
CSAZ462.
• The arc fault detection system is not a substitute for proper PPE when
working on or near equipment being monitored by the system.
• Information on this product is offered as a tool for conducting arc-flash
hazard analysis. It is intended for use only by qualified persons who are
knowledgeable about power system studies, power distribution equipment,
and equipment installation practices. It is not intended as a substitute for the
engineering judgement and adequate review necessary for such activities.
• Only qualified personnel should install and service this equipment. Read this
entire set of instructions and check the technical characteristics of the device
before performing such work.
• Perform wiring according to national standards (NEC) and any requirements
specified by the customer.
• Observe any separately marked notes and warnings.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume all circuits are
live until they are completely de-energized, tested, and tagged. Pay
particular attention to the design of the power system. Consider all sources
of power, including the possibility of back feeding.
• Always use a properly rated voltage sensing relay to ensure that all power is
off.
• The equipment must be properly grounded.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
• Do not open the device. It contains no user-serviceable parts.
• Install all devices, doors and covers before turning on the power to this
device.
Failure to follow these instructions will result in death or serious injury.
Testing the arc flash sensors with the light-only criteria operates the trip outputs of
the device.
Testing the arc flash sensors with the light and current criteria, without an injected
current, only generates an indication on Easergy P5 that protects the zone.
NOTE:
Testing the arc-flash sensors using a light source can trip the neighboring
zones.
Because of their placement, some sensors cannot be tested without
dismantling parts of the system. After completing the testing, reassemble the
parts and validate the compliance with original mounting. Consult the
equipment manufacturer before dismantling any parts.
NOTE:
Because of their placement, some sensors cannot be tested without
dismantling parts of the system. After completing the testing, reassemble the
parts and validate the compliance with original mounting. Consult the
equipment manufacturer before dismantling any parts.
P533I4A
1. Point a powerful light source such as a flashlight or camera flash unit to each
arc-flash sensors until the sensor is activated.
2. Check the arc-flash sensor indication from the Easergy P5 protection relay.
3. Check the address of the activated arc-flash sensor from the Easergy P5
protection relay.
4. Compare the arc-flash sensor address information from the protection relay
with that on the sensor location map.
5. Fill in the test result in the test report.
6. Reset the protection relay.
7. Repeat the procedure with the next arc-flash sensor.
CAUTION
CIRCUIT OVERLOAD
Do not open a loaded current measuring circuit before the secondary circuit of
the current transformer is reliably short-circuited.
Failure to follow these instructions can result in injury or equipment
damage.
1. Short circuit the secondary circuit of the current transformer and disconnect
the Easergy P5 protection relay from the measuring circuit.
2. Connect a current injection device, one phase at a time, to the Easergy P5
protection relay of the current measuring circuit.
3. For a current injection device with time measurement, connect the injection
device either to inject the current continuously or when triggered by the time
measuring circuit:
a. Use the digital input of the current injection device for the stop trigger in
the time measurement circuit.
b. Connect the trip output of the tested unit to the digital input of the current
injection device for the stop trigger. For measuring the total operating
time, use the circuit breaker’s NO contact, which indicates that status of
circuit breaker is open, for the stop trigger.
c. Connect the time measuring start signal output to the flashlight.
Configure the time measuring start signal to either trigger only the
flashlight or both the flashlight and the current injection.
Preferably, the current injection should be triggered before the flashlight.
d. Measure the operate time between the start trigger and stop trigger.
Verify that the technical characteristics of the channels are not exceeded
2. Position a flashlight to each of the light sensors in sequence. Start the time
measurement to trigger the flash.
3. Check that the arc-flash protection function operates.
4. Check the operation time from the time measuring device.
5. Generate at least one trip with current.
6. Reset the protection relay and repeat for other light sensors.
Test report
• Check the protected zones where sensors have been installed and compare
them against the drawings.
• Consult the customer if the configuration does not match with the drawings.
Supervisor
Date
P533I5A
Final check
NOTICE
CIRCUIT OVERLOAD
• Remove all test or temporary shorting leads.
• If it has been necessary to disconnect any of the external wiring from the
protection relay to perform the wiring verification tests, make sure that all
connections are replaced according to the relevant external connection or
scheme diagram.
Failure to follow these instructions can result in equipment damage.
The commissioning is now complete, but before putting the protection relay into
normal operation, check the following items:
• Ensure that the protection relay is restored to service.
• CB maintenance and current counters should be zero. These counters can be
reset.
• Double check the application-specific settings, to help ensure that all the
desired protection and control functions are enabled with the correct settings.
Extract the final setting file from the protection relay.
• Check the Date and Time of the protection relay, to ensure the date and time
are exactly synchronised.
• Reset all event records, fault records, and disturbance records. Make sure
that alarms and LEDs have been reset before leaving the protection relay.
The device is now ready for operation.
Use
Introduction
The local panel can be used for both entering all the data required for operation of
the Easergy P5 protection relay and accessing the data for equipment
management.
The following tasks can be handled from the local panel:
• Controlling switchgear units:
◦ View equipment status on an animated mimic diagram
◦ Local opening and closing of up to 6 devices controlled by Easergy P5
• Read out the list of enabled protections
• Readout and modification of settings
• Readout of live operating data including waveforms
• Read out logic status signals
• Readout of operating data logs and of monitoring signal logs
• Readout of event logs after overload situations, ground faults, or short circuits
in the power system
• Read out the Easergy P5 protection relay's module versions
• Device resetting and triggering of additional control functions used in testing
and commissioning
• Test the protection relay with dedicated IED modes (contact outputs forced or
not)
• Entering a password according to different access rights for settings and
operations (see Cybersecurity, page 459)
Control is also possible through the PC interface. This requires a suitable PC
installed with a specific operating program called eSetup Easergy Pro (see eSetup
Easergy Pro, page 160).
Local panel
Presentation
The Easergy P5 protection relay is equipped with a user friendly local panel.
1 2 3 4
5
ON !
Bay
6
Easergy
0 A
0 A
0 A
0.00 A 7
22
9
21
20 10
19 11
18 12
Open
is perfect is a Queen
Jean-Marc Linda
Close
is perfect is a Queen
Jean-Marc Linda
13
14
17
16 15 P533MSA
1 2 3 4
5
ON !
Bay
Easergy
6
0 A
0 V
0 VA
0 kW
0 kVAr 7
0 Hz
22
9
21
20 F1 F2 F3 10
19 F4 F5 F6 F7
11
18
Open
is perfect is a Queen
12
Jean-Marc Linda
Close
is perfect is a Queen
Jean-Marc Linda
13
14
17
16 15 P533MTA
Push buttons
Symbol Function
to
This push button allows the user to set the Easergy P5 protection relay to
remote control mode or local control mode.
LED indicators
Status indicators
This includes the 4 LEDs located on top of the LCD representing the different
status of the Easergy P5 protection relay regarding power, alarm, trip, and
operation mode (refer to item 1 to 4 in Local panel of Easergy P5x20, page 140
and Local panel of Easergy P5x30, page 141) and the LED associated with the
"Local/Remote" push button (refer to item 19 in Local panel of Easergy P5x20,
page 140 and Local panel of Easergy P5x30, page 141).
Indicators States
OFF ON Flash
Power OFF Power ON -
No trip Trip -
Configurable LEDs
These LEDs can be configured in three different colors: green, red and yellow, and
be individually latched or unlatched (see LED matrix, page 379).
These LEDs are configured by default according to LED1 to LED6 on Easergy P5
x20, page 143 and LED1 to LED10 on Easergy P5 x30, page 143.
Green CB Open
Easergy P5V20
Green CB Open
Color LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10
Green CB Open
BAY
IL1 100 A
IL3 100 A
P 944 kW
Q -1632 kVar
If it is, the Easergy P5 protection relay proceeds to the default screen; If it isn't, a
message is displayed, prompting the user to either keep or discard the content of
the extension module. If the user selects the “Block new backup” option, the
content is kept, the Easergy P5 protection relay will block the backup operation; If
the user selects the “Discard” option, the protection relay directly reconfigures
from the extension module.
When the Easergy P5 protection relay is in operation mode, it is possible to switch
to the main menu screen by pressing key. Depending on the user role, the user
can also change the device settings at any time.
If an event or alarm occurs during operation, a popup message is permanently
displayed on the LCD screen until it is acknowledged using the key.
If there is an alarm message displayed and no action on the keypad for 5 minutes,
the Easergy P5 protection relay will jump to the default screen and then display
the alarm message again automatically.
If there is no alarm message displayed, the default screen is displayed
automatically.
Menu structure
The Easergy P5 protection relay has two levels of menus: the main menu (home
menu) and sub-menus.
NOTE: The hierarchy and navigation of the menu structure are the same on
Easergy P5x20 and Easergy P5x30, but due to a larger resolution, the
Easergy P5x30 LCD color screens can display data and graphics in greater
detail.
The Easergy P5 device is delivered with auto-login feature. It will be disabled
when the passwords for all three levels are changed from the default ones. For the
default passwords for all the levels, refer to Factory default configuration, page
479.
1 2 3 4
P533MUA
The main menu screen has 2 widgets: the top title bar, and the main display area.
The top title bar shows the following items:
• Menu name: full name of the menu item that is being selected (the names
next to the menu icons use their short forms)
• Home icon: located on the left side of the top title bar, indicates that the
current screen is the home screen of the LCD display
• Padlock icon ( ): located on the right side of the top title bar, indicating that
no user has logged in to the device; the icon disappears when any user has
logged in.
• Remote/Local control icon: located on the right end of the top title bar,
indicates the protection relay's current control mode
P533MVA
The main display area lists all the menu items (sub-menus) of the Easergy P5
protection relay.
In the main menu, pressing the navigation keys on the local panel moves the
focus onto a main menu item (sub-menu). The sub-menu title is displayed in the
top title bar of the main menu screen. Pressing allows the user to enter the
highlighted sub-menu.
Sub menus
Figure 127 - The Measurement sub-menu
P533MWA
In the sub-menu, pressing or key moves the focus onto a sub-menu item
and pressing selects the item and allows the user to enter the setting page of
the item.
NOTE: There could be more menu items than is able to be displayed in the
view. The user needs to scroll to these items using the key.
Data/setting page
Some sub-menu items may have more than one data/setting pages, which is
indicated by an arrow on either the left or right end, or by arrows on both ends of
the title bar:
• Arrow on the right end
Pressing the key scrolls the screen to the next data/setting page.
• Arrow on the left end
Pressing the key scrolls the screen to the previous data/setting page.
• Arrows on both the left and right ends
Pressing the or key scrolls the screen to the previous or next data/
setting page, respectively.
Upon seeing the desired data/setting page, pressing allows the user to enter
the data/setting page, and after that, pressing the or key moves the focus
onto each parameter field.
NOTE: There could be more parameters than is able to be displayed in the
view. The user needs to scroll to these parameters using the key.
When an editable parameter is in focus, pressing opens the parameter
setting view and enables the user to change the value or option by pressing the
navigation arrow keys. When a non-editable parameter is in focus, pressing
key pops up a message, indicating that the parameter is not editable. When the
user is not fully authorised to edit the setting, pressing key pops up a
"Permission denied" message.
When changing the settings, use the navigation keys according to the following
instructions to get the result quickly:
• For selecting options, use the and keys;
• For changing the value of integer numbers, use either the and keys, or
the and keys;
• For changing the value of float numbers, first use the and keys to
quickly approach the integer part of the number in steps of 1 and then use the
and keys to adjust the decimal part in steps of 0.01.
In the protection menu, some protection stage items have a first setting page with
more than one view. These views belong to different setting groups of the
protection stage. In this case, upon selecting the menu item, an additional text line
"Press OK to edit groups" is displayed at the top of the main display area to
indicate that here the user can edit the settings of different setting groups.
Pressing the key to enter the group editing status. Pressing the and
keys to scroll to the setting view for the desired setting group.
OK
P533MXA
Figure 129 - Moving in the menu structure of the Easergy P5 protection relay
OK OK OK OK
1 2 3 4 5
OK P533MYA
Pressing and keys, and/or and keys moves the focus to the desired
position or view.
Pressing key allows the user to enter the sub menu (2), the data/setting page
selecting view (3), the parameter selecting view (4), or the parameter editing view
(5), depending on where the user is situated in the structure at the time.
Pressing key is also required to confirm and finalise the editing in the
parameter editing view.
Pressing the key once returns the screen to the previous view;
Pressing the key longer for about 3 seconds returns the screen to the default
screen.
Login
The user may need to log in before changing settings or accessing the data
protected by password. The Easergy P5 device is delivered with auto-login
feature. It will be disabled when the passwords for all three levels are changed
from the default ones. For the default passwords for all there levels, refer to
Factory default configuration, page 479.
The Login screen can be accessed from the main menu or through the key on
the local panel. The following login procedure starts from the main menu.
1. Press the navigation keys and then the key to enter the User Login menu
from the main menu screen.
The screen displays the Login view with the focus on the "UserName" field.
Login
Name
Password
EngineerLevel
OperatorLevel
InstallerLevel
Input user name
3. Press or key to select a user name from the user list and then press
to confirm your choice.
4. Enter the password by first pressing or key to select the code position,
and then pressing or key to select different letter or digits and pressing
to confirm.
Login
Name EngineerLevel
Password
NOTE: After a correct password is entered, the LCD display returns to the
home screen and the padlock icon disappears from the screen title bar,
indicating that the user is now able to view/edit the settings, depending on the
access right level of the user type.
NOTE: To access the User Login screen using the key on the local panel,
press and then press the key. This feature enables the user to directly
access the User Login screen from wherever in the menu structure rather than
has to go back to the home screen.
Logout
By default, the user is automatically logged out if there is no action on the keypad
for 3 minutes.
The user can also logout manually by first going to the User Login screen from the
local panel and then pressing the key.
NOTE: To access the User Login screen using the key on the local panel,
press and then press the key. This feature enables the user to directly
access the User Login screen from wherever in the menu structure rather than
has to go back to the home screen.
6. Press key once to go to previous view or press the key for 3 seconds to go
to the default screen.
NOTE: The LCD contrast can alternatively be adjusted by pressing the key
and then pressing the and key. The contrast changes incrementally
with every step but the screen does not display the values.
Changing language
The interface language can be changed on the local panel according to the
following steps:
1. Press the navigation keys and then the key to enter the General settings
menu from the main menu screen. The screen displays the General settings
menu with the focus on the "Lang" option.
2. Press the key to enter the Language setting page.
3. Press the key to focus on the setting item.
4. Press the key again to bring up the language list.
5. Press the or key to select the desired language and then press the
key to confirm the selection.
NOTE: The interface language can alternatively be changed through eSetup
Easergy Pro in the System info view of the General menu.
WARNING
INOPERABLE PROTECTION RELAY
Make sure that the reboot of the protection relay has no impact on people and
equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
After changing some settings, the protection relay needs to reboot. During this
time, the device is not operational.
Parameters can be changed on the setting pages of certain sub-menus:
1. In the main menu, enter the menu item that relates to the function you need to
access.
Refer to Main menu (home menu), page 146 for how to access the menu
items.
2. In the sub-menu, select the sub-menu item that includes the parameter you
want to change.
Refer to Sub menus, page 147 for how to access the sub-menu items.
3. With the related sub-menu item selected, press or key to scroll to the
specific setting page on which you can find the parameter and then press
to enter the setting page.
4. Press the or key to move the focus onto the parameter field and then
press the key to start editing the parameter.
5. Use the navigation keys to change the value of the parameter and then press
the key to confirm your change.
Refer to Data/setting page, page 148 for how to use the navigation keys
tactically.
6. Press the key once to go back to the previous view in the menu, or press it
for 3 seconds to return to the default screen.
5. Press the key once to go back to the previous view in the menu, or press it
for about 3 seconds to return the default screen.
NOTE: For viewing the alarm list, press key once to go to the Alarm list
page after Step 2.
Matrix operations
The matrix mapping operation can be performed on the local panel of the Easergy
P5 protection relay, in the eSetup Easergy Pro software tool, or through the web
HMI.
The following procedure describes the mapping operation on the local panel of the
Easergy P5 protection relay. The operation is much easier in eSetup Easergy Pro
and the web HMI due to their intuitive interfaces.
1. Select the Control function from the main menu, press to enter the sub-
menu.
2. Press or key to scroll to the menu item (e.g. DI) that needs matrix
mapping operation.
3. Press or key to scroll to the matrix mapping page and start the
mapping operation.
NOTE: The local panel LCD screen only shows the first line of mapping
relations already existing in the configuration. If no mapping relation is
available for the first line of the matrix, the screen only shows the digital
input or internal signal on the left side of the screen.
4. Press or key to scroll to the digital input or internal signal type and
then press to confirm. The first crossing point on the matrix line starts to
blinck.
5. Press or key to scroll to the crossing point for which you want to set
the mapping status.
NOTE: Some crossing points may not be visible in the screen but the user
can view all the crosssing points by pressing key.
6. Press or key to select the mapping status (enabled or diabled;
connected or unconnected; latched or unlatched, depending on which matrix
mapping operation is being performed) and then press to confirm.
The screen shows the current line of mapping relations, leaving the empty
crossing points invisible on the screen.
7. Press key to leave the matrix setting page and then key to return to the
preview level in the menu structure.
Controlling objects
The local panel provides buttons for directly controlling objects like circuit breaker
and earth/ground switch. The user do not need to go through the menu to find out
the options for closing/opening the objects.
The USB key status changes from “Off” to “On” automatically in the USB file
copy view of the Device/Test sub menu.
Copy files to USB 1/1
USB key Off
2. Select “Copy to USB key” and then select “All” to copy all the files from the
protection relay to the USB key.
Copy files to USB 1/1
Copy Easergy P5 to USB
USB key On
Copy to USB key -
3. A progress bar is displayed on the screen and after a short while a “Success”
message appears on the screen when the transfer is completed.
WARNING
INOPERABLE PROTECTION RELAY
Make sure that the reboot of the protection relay has no impact on people and
equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
After changing some settings, the protection relay needs to reboot. During this
time, the device is not operational.
eSetup Easergy Pro is a setting and operating software tool for configuring
Easergy P5 devices, local operation and customisation functions.
The eSetup Easergy Pro software is supplied directly through the Schneider
Electric website www.se.com, along with the eSetup Easergy Pro program for
recovering disturbance recording files, and all the Easergy P5 documentation in
PDF format.
Figure 133 - eSetup Easergy Pro menu bar and tool bar
The eSetup Easergy Pro software has a graphical interface where the protection
relay settings and parameters are grouped under nine menu tabs:
• General
• Measurements
• Control
• Protection
• Matrix
• Logs
• Communication
• Device/Test
• Documentation
The contents of the tabs depend on the device type and the selected application
mode. Refer to the User Manual of eSetup Easergy Pro for detailed information on
the setting views of each menu.
The eSetup Easergy Pro stores the device configuration in a setting file. The
configuration of one physical device is saved in one setting file. The configurations
can be printed out and saved for later use.
When starting to work with eSetup Easergy Pro, there are three options:
• Create a new setting file without connecting to a protection relay
• Open an existing (previously saved) setting file without connecting to a
protection relay
• Connect to a relay and read the settings from the protection relay .
eSetup Easergy Pro can be connected to a single relay via the mini-USB port in
the protection relay's local panel or to a group of protection relays via Ethernet.
Operation modes
The eSetup Easergy Pro software can be used in three operation modes:
• Disconnected mode
• Single unit connecting mode
• Network connecting mode
NOTICE
UNINTENDED EQUIPMENT OPERATION AND NUISANCE TRIPPING
After writing new settings, configurations or firmware to a protection relay,
perform a test to verify that the protection relay operates correctly with the new
settings.
Failure to follow these instructions can result in unwanted shutdown of
the electrical installation.
P533N5A
1. Connect the USB cable (reference 59700) to the front port of the Easergy
P5 protection relay and the PC (see Connecting a PC to the Easergy P5 using
a USB cable, page 161), after that look for a new COM port under COM & LPT
in the Device Manager window of the PC.
If you are unsure which is the right port, detach the USB cable and insert it
again when you are in this menu.
2. Right-click on the port and select Update Driver Software from the
contextual menu.
3. Select the option Browse my computer for driver software and locate the
driver in the P5 driver_files folder under the eSetup Easergy Pro directory.
4. Click the Install button in the prompt window to start installing the driver.
5. If the driver has been installed successfully, the connection now appears
under Network adapters in the Device Manager window each time you
connect the PC to a Easergy P5 protection relay.
Web HMI
Overview
The web HMI is used for operation and settings. It has the same functions as
eSetup Easergy Pro except the logic and mimic customisation.
The web HMI can be accessed using the following browsers 15, 16, 17:
pre-installed certification ■ ■ -
pre-installed certification ■ ■ ■
Reminder messsage
about device reboot
P533NBA
Firefox
4. Close the certificate viewing window and then click the "Confirm
Security Exception" button.
The web HMI "Login" page opens.
5. Now the certificate file is already imported into the Firefox browser
and we can see it in the Certificate Manager of the Firefox browser.
5. Click "Next" and then, on the "Certificate store" page, select the
Certificate Store "Trusted Root Certification Authorities".
Edge in Windows 10
The following procedure for accessing the Easergy P5 web HMI uses the IE
browser for illustration. The screen shots for the Edge browser are identical.
3. On the computer screen, click the "Start" button and then type in
"mmc" in the "search bar".
The "Console" interface opens on the screen.
5. Click "Certificates" in the left box and then click the "Add" button.
The "Certificates Snap-in" window appears.
7. Select "Local computer" and then click "Finish" to close the "Select
computer" window.
11. Click "Browse" and then, in the pop-up dialog box, select the path
of the certificate followed by the certificate name "192.168.1.21.p12"
(the suffix of the certificate is "p12").
Note that the file type should be "All Files".
14. Type in the password "secbrick", check the "Mark this key as
exportable..." option, and then click "Next".
The "Certificate Store" window appears.
.
15. Check the "Place all certificates in the following store" option,
browse to the certificate store folder "Trusted Root Certification
Authorities", and then click "Next".
The certificate import settings page appears.
17. After the certificate has been imported successfully, set up the
Edge browser by checking the "Use TLS 1.0", "Use TLS 1.1", and
"Use TLS 1.2" options under the "Advanced" tab of the "Internet
options".
Protection functions
General features of protection stages
Enable/disable protection functions
The different stages of the protection function can be enabled/disabled
individually.
If a protection function stage is disabled, it is not shown in the protection menu in
the local panel.
To enable or disable a protection function stage:
• With eSetup Easergy Pro or Web HMI
Enter the Valid protection stages view in the Protection menu or directly go to
each protection stage view in the same menu.
For the motor protection, there is a dedicated Motor status view in the protection
menu where it is possible to enable or disable the following protection functions:
• Thermal overload protection for machine (ANSI code 49M)
• Motor start-up supervision (ANSI code 48)
• Motor restart inhibition (ANSI code 66)
• Locked rotor (ANSI code 51LR)
• Motor Anti-backspin (ABS) protection
• Motor speed detection
NOTE: The Motor status view is comprised of settings (e.g. nominal motor
start current) common to these functions.
Setting groups
Setting groups are controlled by using controlling inputs like digital inputs, function
keys, virtual inputs, HMI or custom logic.
When none of the assigned inputs are active, the active setting group is defined by
parameter 'SetGrp no control state' (see Settings related to setting groups in the
Valid Protection Stages view, page 175).
When one controlling input activates, the corresponding setting group is activated
as well. If multiple inputs are active at the same time, the active setting group
follows the definition by 'SetGrp priority' (see Settings related to setting groups in
the Valid Protection Stages view, page 175).
By using virtual I/O the active setting group can be controlled using the local panel
display, any communication protocol, or in-built programmable logic functions.
When a controlling input is configured, the SetGrp common change parameter (in
the Valid protection stages view of the Protection menu in eSetup Easergy Pro) or
the Set. group parameter in the same menu on the local panel) is not operational.
Setting group changes are applied simultaneously to all protection functions.
Figure 140 - Settings related to setting groups in the Valid Protection Stages
view
Figure 141 - Set the Mode of use in System info view of the General menu
Blocking
Any protection function, except arc-flash protection (see Arc-flash (ANSI 50ARC),
page 280), can be blocked with internal and external signals using the block
matrix. Internal signals are, for example, logic outputs, start and trip signals from
other stages and external signals are for example digital and virtual inputs.
Some protection stages have also inbuilt blocking functions. For examples, phase
overcurrent has an input for inrush detection.
When a protection stage is blocked, it won't start in case of a fault condition. If
blocking is activated during the operation delay, the delay counting is frozen until
the blocking condition is off or the start resets, that is, the fault condition
disappears. If the stage is already tripping, the blocking has no effect. See
Blocking matrix, page 378 for more information.
Overshoot time
Overshoot time is the time the protection relay needs to notice that a fault has
been cleared during the operate time. This characteristic is important when
grading the operate time settings between relays.
t FAULT
t OVERSHOOT ≤ 50 ms
For example, when there is a heavy fault in an outgoing feeder, it will start both the
incoming and outgoing feeder relay. However, the fault must be cleared by the
outgoing feeder protection relay and the incoming feeder relay must not trip.
Although the operating delay setting of the incoming feeder is more than that of
the outgoing feeder, the incoming feeder might still trip if the operate time
difference is not big enough. The difference must be more than the overshoot time
of the incoming feeder relay plus the operate time of the outgoing feeder circuit
breaker.
Definition for overshoot time, page 178 shows an overvoltage fault seen by the
incoming feeder when the outgoing feeder clears the fault. If the operation delay
setting would be slightly shorter or if the fault duration would be slightly longer than
in the figure, an unselective trip might happen (the dashed 40 ms pulse in the
figure). In devices, the overshoot time is less than 50 ms.
Figure 143 - Disengaging time and adjustable reset time according to IEC
60255-151 standard
Energising
quantity
Start (pick-up)
signal
Disengaging time
Operate
signal
Value of
internal time
delay counter
The adjustable reset time is a definite or inverse time hold used mainly to detect
restriking faults (DT) or allow coordination with electromechanical protection
relays (Inverse). It can be used also for coordination with electromechanical
relays.
It is implemented in the following protection functions:
• Phase overcurrent (ANSI 50/51)
• Directional phase overcurrent (ANSI 67)
• Earth/ground fault overcurrent (ANSI 50N/51N)
The adjustable reset time may be inhibited if necessary.
Start level
Reset level
The reset ratio is the ratio between the reset level and the start level. To avoid any
chattering of the protection for low settings of thresholds, a reset ratio can be
claimed with a minimum value of hysteresis. For example: <93% with a minimum
of hysteresis of 0.005In.
Hysteresis
Reset level
Start level
Is I P533A4A
t (s)
It (A) P533A5A
The operate time in the definite time mode is fixed by the operation delay setting.
The timer starts when the protection stage starts and counts until the set time has
elapsed. After that, the stage issues a trip command. If the protection stage reset
before the definite time operation has elapsed, then the stage resets.
By default, the definite time delay cannot be set to zero because the value
contains processing time of the function and operate time of the output contact.
This means that the time indicated in the Definite time setting view is the actual
operate time of the function.
Use the Accept zero delay setting in the protection stage setting view to accept
the zero setting for definite time function. In this case, the minimum operate time
of the function must be tested separately.
NOTE: The start time and the operate time values include the fault detection
time and operation time of the contact.
Operation modes
There are two operation modes to use the dependent time characteristics:
• Standard delays
Using standard delay characteristics by selecting a curve family (IEC, IEEE,
IEEE2, RI) and a delay type (Normal inverse, Very inverse, etc.). See
Standard dependent operation delay, page 183.
• Fully programmable dependent delay characteristics
Building the characteristics by setting 16 [current, time] points. The relay
interpolates the values between given points with second degree
polynomials. This mode is activated by the setting curve family to "PrgN",
where N = 1, 2, 3, corresponding to the three different programmable curves
available. Each programmed curve can be used independently by any
number of protection stages. See Programmable dependent time curves,
page 194.
Limitations
The minimum definite operation time starts at the latest when the measured value
is twenty times the setting. However, there are limitations at high setting values
due to the measurement range. The maximum measured secondary phase
current and the maximum directly measured earth/ground fault current depends
on the type of sensor used (see Maximum measured secondary currents and
settings for phase and earth/ground fault overcurrent inputs, page 183 below).
The full scope of dependent delay curves go up to 20 times the setting or the
maximum of the dynamic measurement, whichever is smaller. At a high setting,
the maximum measurement capability limits the scope of dependent curves
according to Maximum measured secondary currents and settings for phase and
earth/ground fault overcurrent inputs, page 183.
The protection function starts when the current reaches 1.05 times of the setting
(Iset).
Table 28 - Available standard delay families and the available delay types
within each family
NI Normal inverse ■ ■
VI Very inverse ■ ■ ■
EI Extremely inverse ■ ■ ■
CT 60In
Standard earth/ground fault 20In0
CSH 20In0
Very sensitive earth/ground fault 20In0
kA
t= B
I
− 1
I set P533A6A Equation 7.1
0.50 ⋅ 0.14
t= 0.02
= 5.0
4
−1
2 P533A7A
The operate time in this example is five seconds. The same result can be read
from IEC normal inverse delay, page 185.
IEC tripping characteristics (limit value*, please refer to Minimum definite operation time, page 184)
Figure 148 - IEC normal inverse delay Figure 149 - IEC extremely inverse delay
limit value*
limit value*
Figure 150 - IEC very inverse delay Figure 151 - IEC long time inverse delay
1
Delay (s)
k = 1.25
k=1
k = 0.5
0.1
k = 0.2
0.01 k = 0.025
0.001
1 10 limit value* 100
I/Iset
A
t=k C
+ B
I − 1
I set
P533A8A Equation 7.2
0.0515
t = 0.50 ⋅ + 0.1140 = 1.9
4 0.02
−1
2 P533A9A
The operate time in this example is 1.9 seconds. The same result can be read
from IEEE/ANSI moderately inverse delay, page 188.
IEEE/ANSI tripping characteristics (limit value*, please refer to Minimum definite operation time, page 184)
Figure 153 - IEEE/ANSI long time inverse delay Figure 154 - IEEE/ANSI long time very inverse
delay
limit value*
limit value*
Figure 155 - IEEE/ANSI long time extremely Figure 156 - IEEE/ANSI moderately inverse delay
inverse delay
limit value*
limit value*
Figure 157 - IEEE/ANSI short time inverse delay Figure 158 - IEEE/ANSI short time extremely
inverse delay
limit value*
limit value*
10 K = 1.25
K=1
K = 0.5
K = 0.2
1
Delay (s)
K = 1.25
K = 0.025 K=1
0.1 K = 0.5
K = 0.2
0.01
K = 0.025
0.001
0.01 0.1 1 10 limit value* 100
I/Iset
B D E
t = k A + + 2
+ 3
I I I
− C − C − C
I set I set I set P533AAA Equation 7.3
0.6791 − 0.08 0.127
t = 0.5 ⋅ 0.1735 + + + = 0.38
4 4
2
4
3
− 0.8 − 0.8 − 0.8
2 2 2 P533ABA
The operate time in this example is 0.38 seconds. The same result can be read
from IEEE2 moderately inverse delay, page 191.
IEEE2 tripping characteristics (limit value*, please refer to Minimum definite operation time, page 184)
Figure 160 - IEEE2 moderately inverse delay Figure 161 - IEEE2 normal inverse delay
Figure 162 - IEEE2 very inverse delay Figure 163 - IEEE2 extremely inverse delay
k I
t RI = t RXIDG = 5.8 − 1.35 ln
0.339 0.236 k I set P533ADA
I
I set P533ACA
0.5
t RI = = 2.3
0.236
0.339 −
4
2 P533AEA
The operate time in this example is 2.3 seconds. The same result can be read
from RI dependent delay, page 193.
Example of the delay type RXIDG
k = 0.50
I = 4 In
Iset = 2 In
4
t RXIDG = 5.8 − 1.35 ln = 3.9
0.5 ⋅ 2 P533AFA
The operate time in this example is 3.9 seconds. The same result can be read
from RXIDG dependent delay, page 193.
RI and RXIDG tripping characteristics (limit value*, please refer to Minimum definite operation time, page 184)
A
treset =k×
I
B
1−
Iset P533AGA
The reset time characteristic is defined by a setting in the protection stage. The
allowed settings are dependent on the operate curve as shown in the table.
The TMS (inverse time coefficient) of the IDMT reset timer is the one defined for
the operate curve.
For all operate curves not listed in the table above, the reset timer is of DT type.
1 1.00 10.00 s
2 2.00 6.50 s
3 5.00 4.00 s
4 10.00 3.00 s
5 20.00 2.00 s
6 40.00 1.00 s
7 1.00 0.00 s
8 1.00 0.00 s
9 1.00 0.00 s
10 1.00 0.00 s
11 1.00 0.00 s
12 1.00 0.00 s
13 1.00 0.00 s
14 1.00 0.00 s
15 1.00 0.00 s
16 1.00 0.00 s
The minimum definite operation time starts at the latest when the measured value
is twenty times the setting. However, there are limitations at high setting values
due to the measurement range.
Example
Figure 166 - Functionality of cold load current feature
1 3 4
Pick-up
Idle
Cold
load P533AHA
1. No activation because the current has not been under the set IDLE current.
2. Current dropped under the IDLE current level but now it stays between the IDLE
current and the start current for over 80 ms.
3. No activation because the phase two lasted longer than 80 ms.
4. Now we have a cold load activation which lasts as long as the operate time was
set or as long as the current stays above the start setting.
Characteristics
Table 35 - Settings and characteristics of cold load pick-up function
Settings/characteristics Value
(description/label)
Idle current/Idle
Range 0.01In – 0.50In
Resolution 0.01In
Pickup current/Pickup
Resolution 0.01In
CLPU dead time/DeadTime
Setting range 0.10 - 14400.00 s
Resolution 0.01 s
Maximum time/MaxTime
Setting range 0.01 - 300.00 s 19
Resolution 0.01 s
Accuracy 1% or ±20 ms
19. This is the instantaneous time, i.e. the minimum total operational time including the fault detection time and operate time of the trip
contacts.
Operation
To implement the SOL function:
• Set the upstream protection
• Set the upstream protection and activate the SOL. Set the SOL operation
delay with a value higher than the Operation delay value
• In the downstream relay output matrix, connect the start signals of the
different protections involved in the logic discrimination, on the SOLxStr then
connect the SOLx trip on a dedicated contact relay
• In the upstream relay output matrix, connect the dedicated logic input for SOL
to the SOL status signal.
Up to two signals can be provided by the SOL function.
A CB trip clearing time can be set to erase the SOL signal after trip. The SOL
operation time of the upstream protection usually takes into account of the
breaking device operating time and the protection reset time.
Downstream
Relay Prot. Start
CB Failure!
Matrix = Operation delay T
Prot. Trip
SOLx Start
Wire connection
or GOOSE message
Upstream
Relay
Digital Inputx
Matrix
“Prot.SOLt>” is selected
for Operation delay
SOL Status comparison
Prot. Start
= Operation delay T
Example 1
Figure 167 - Example 1: Radial distribution with use of time-based
discrimination
0.9
0.6
0.3
The upstream protection units are typically delayed by 0.3 s to give the
downstream protection units time to trip. When there are many levels of
discrimination, the fault clearing time at the source is long. In this example, if the
fault clearing time for the protection unit furthest downstream is Xs = 0.2 s, the
fault clearing time at the source is T = Xs + 0.9 s = 1.1 s.
Example 2
Figure 168 - Example 2: Radial distribution with use of logic discrimination
Bay
0
0
0
0
0
0
A
V
VA
kW
kVAr
Hz
0.10
Bay
A
0 V
0 VA
0 kW
0 kVAr
0 Hz
0
Bay
A
0 V
0 VA
0 kW
0 kVAr
0 Hz
0
SOL signal
Bay
A
0 V
0 VA
0 kW
0 kVAr
0 Hz
0
Characteristics
Settings and characteristics Values
SOL1 status
Options -; Trip;
SOL2 status
Options -; Trip;
SOL OpNb
Range 1-2
Easergy P5
P533AJA
Z12 = V L1 − V L2
I L1 − I L2 − I pre-fault P533AKA
The reference current setting is used to start the calculation of the fault locator
based on the pre-fault current magnitude. The calculation can be activated also
based on a digital or logic input.
Example
An application example where the fault location algorithm is used at the incomer
side is presented below.
Figure 170 - Illustration of the fault location algorithm used at the incomer
side
Voltage
Current
Characteristics
Table 36 - Setting parameters of incomer short-circuit fault locator
Line reactance 0.010 – 10.000 Ohms/ 0.389 Line reactance of the line.
km This is used only to convert
the fault reactance to
kilometers.
dItrig 10 – 800 50 Trig current (sudden
increase of phase current)
−
Z12 = V L1 V L2
I L1 − I L2 P533ANA
When the feeder fault locator is calculating ground fault impedance, the following
formula is used:
Z12 = V L1
I L1+ k x I0 P533APA
Triggering of the fault reactance calculation happens when the start value is
exceeded or both “Start setting” and “Triggering digital input” terms are fulfilled.
When used, “Triggering digital input” can be either digital or virtual input.
Example
An application example where the fault location algorithm is used at the feeder
side is presented below.
Figure 173 - Illustration of the fault location algorithm used at the feeder side
Voltage
Current
Characteristics
Table 38 - Settings and characteristics of the fault locator function (ANSI
21FL)
Pick-up setting 0.10 – 5.00 xIn 1.2 Current limit for triggering.
Line reactance 0.010 – 10.000 Ohms/ 0.491 Line reactance of the line. This is
km used only to convert the fault
reactance to kilometer.
Earth/ground 0.010 – 10.000 - 0.678 Calculated earth/ground factor from
factor line specifications.
Very sensitive E/F CT (VL1 + VL2 + VL3) SEF CT primary / (√3*VT primary)
CSH core balance CT (VL1+ VL2 + VL3) CSH CT primary / (√3*VT primary)
(IL1 + IL2+ IL3) (VL1 + VL2 + VL3) Phase CT primary / (√3*VT primary)
Operation
Ys
operate
* Y = G + jB Y > Ys
Admittance:
Non-directional
P533AUA
B B B
operate operate operate operate
G > Gs G < -Gs G < -Gs G > Gs
Gs G -Gs G -Gs Gs G
NOTE:
Center of the characteristic area for forward direction occurs when I0 is in
phase with -U0.
Assuming that the direction of the G axis is 0°. If the correction angle is set to
+30°, this rotates the boundary from 90° - 270° to 60° - 240°.
+30° operate
G > Gs
Gs G
P533AWA
B B B
operate operate
B > Bs B > Bs
Bs Bs
G G G
-Bs -Bs
operate operate
B < -Bs B < -Bs
NOTE:
Center of characteristic area for forward direction occurs when I0 leads -U0 by
90°.
Assuming that the direction of the G axis indicates 0°. If the correction angle is
set to +30°, this rotates the boundary from 0° - 180° to 330° - 150°.
operate
B > Bs
+30°
P533AYA
Block diagram
> Start
& Register
event
& Register
event
Drop off
& Register
event
Admittance Calculation
Start
& Register
event
U0 >
& Gn > & Trip
I0 >
& Register
event
Drop off
& Register
event
Start
& Register
event
& Register
event
Drop off
Direction Determination
Inhibit
Ctrl
Block
Enable events
Bn
Direction t> Reset time
Correction U0> Yn> Gn> Bn> Gn mode SOL Mode SOLt >
U0 Min I0 Min
(fixed) (fixed) Angle Direction
mode P533AZA
Characteristics
Table 41 - Settings and characteristics of the neutral admittance protection
Settings/ Values
characteristics
(description/label)
U0 setting/U0>
Resolution 0.001
Accuracy ±5%
I0 minimum
Value 0.1 A primary (fixed), for current measured by CSH core balance CT
(2A);
1 A primary (fixed), for current measured by CSH core balance CT
(20A);
0.005In (fixed) for current measured by very sensitive EF CT;
0.02In (fixed) for current measured by standard EF CT;
0.05In (fixed) for derived EF current value.
Yn pick-up value/Yn>
Setting range (1% - 200%) In/Un for current measured by very sensitive earth/ground
fault CTs;
(5% - 1000%) In/Un for current measured by standard earth/ground fault
CTs;
(25% - 5000%) In/Un for current measured by 2A CSH, 20A CSH, and for
current value that is vector sum of 3CTs
Resolution 1% In/Un for current measured by very sensitive earth/ground fault CTs;
5% In/Un for current measured by standard earth/ground fault CTs;
25% In/Un for current measured by 2A CSH, 20A CSH, and for current
value that is vector sum of 3CTs
Accuracy ±5%
Gn pick-up value/Gn>
Setting range (1% - 100%) In/Un for current measured by very sensitive earth/ground
fault CTs;
(5% - 500%) In/Un for current measured by standard earth/ground fault
CTs;
(25% - 2500%) In/Un for current measured by 2A CSH, 20A CSH, and for
current value that is vector sum of 3CTs
Resolution 1% In/Un for current measured by very sensitive earth/ground fault CTs;
5% In/Un for current measured by standard earth/ground fault CTs;
25% In/Un for current measured by 2A CSH, 20A CSH, and for current
value that is vector sum of 3CTs
Accuracy ±5%
Settings/ Values
characteristics
(description/label)
Bn pick-up value/Bn>
Setting range (1% - 100%) In/Un for current measured by very sensitive earth/ground
fault CTs;
(5% - 500%) In/Un for current measured by standard earth/ground fault
CTs;
(25% - 2500%) In/Un for current measured by 2A CSH, 20A CSH, and for
current value that is vector sum of 3CTs
Resolution 1% In/Un for current measured by very sensitive earth/ground fault CTs;
5% In/Un for current measured by standard earth/ground fault CTs;
25% In/Un for current measured by 2A CSH, 20A CSH, and for current
value that is vector sum of 3CTs
Accuracy ±5%
Direction mode/mode
Options Non dir; Forward; Backward
Operation time/t>
Resolution 0.01 s
Accuracy ±5% or ±50 ms
SOL mode
Options Disable/Enable
Resolution 0.01 s
Accuracy ±5% or ±20 ms
Reset time
Setting range 0 - 100 s
Resolution 0.01 s
Accuracy ±5% or ±20 ms
Characteristic time
Start time ≤ 65 ms at 2Yn>;
100 ms at maximum
Overshoot time ≤ 40 ms at 2Yn>
Setting group
Number 4
condition
to operate
synchro
request
request timeout
sync OK
OK pulse length
sync fail
P533ALA
NOTE: The CB close time setting can be used to anticipate the closing of the
CB and meet all the conditions to operate.
Voltage checking
When one of the two voltage is absent, coupling may be authorised according to
one of the seven checking modes.
• U12 and U12y absent (DD)
• U12 absent and U12y present (DL)
• U12 present and U12y absent (LD)
• U12 absent regardless of U12y state (present or absent) (DD/DL)
• U12y absent regardless of U12 state (present or absent) (DD/LD)
• One voltage is present while the other one is absent (DL/LD)
• At least one voltage is absent (DD/DL/LD)
The presence of each voltage is detected by comparing the voltage to the Ulive
limit setting. The absence of each voltage is detected by comparing the voltage to
Udead limit setting.
Block diagram
Figure 181 - Block diagram of the synchro-check protection function (ANSI
25)
F |ΔF| < df
Fy
U12
U12y |ΔU| < du
sync ok
|Δφ| < dφ
=0
sync ok
Async
Sync
< Udead
DD ≥1 close enable
< Udead
DD/DL/LD
≥1
>1 DD/DL
LD no voltage
≥1 DL/LD
DL
>1 DD/DL
no U12
no U12y
Characteristics
Table 42 - Setting and characteristics of the synchro-check function Δf, ΔU,
Δφ (ANSI 25)
Settings/characteristics Values
(description/label)
Sync mode/SMode
CB close time/CBtime
Setting range 0.04 - 0.6 s
Resolution 0.01 s
Udead limit setting/Udead
Resolution 1%Un
Accuracy ±3%Un
Resolution 1%Un
Accuracy 3%Un or 3% of the setting
Settings/characteristics Values
(description/label)
Frequency difference/df
Resolution 0.01 Hz
Accuracy ±20 mHz
Voltage difference/dU
Resolution 1%Un
Accuracy ±3%Un
Resolution 1°
Accuracy ±2° when Δf < 0.2 Hz; else ±5°
Request timeout/ReqTime
Resolution 0.1 s
Accuracy ±1% or ±20 ms
Frequency range 46 - 64 Hz
Setting groups/SetGrp
Number 4
H
D
B F
10%Un
J
A G
time
U<
undervoltage
P533AQA
state
A The maximum of the three line-to-line G The voltage ULLmax is under block limit
voltages ULLmax is below 10%Un. This is not and this is not regarded as an
regarded as an undervoltage situation. undervoltage situation.
Block diagram
Figure 183 - Block diagram of the undervoltage protection function (ANSI
27)
U12
U23 Min < & Start
U31
& Register
event
Max < 10%Un
Trip
Block
Register
&
event
Characteristics
Table 43 - Settings and characteristics of the undervoltage protection (ANSI
27)
Pick-up value/U<
Resolution 1%Un
Accuracy ±2%
Operation delay/t<
Resolution 0.01 s
Accuracy ±1% or ±25 ms
Resolution 0.01 s -
Hysteresis/Hyster
Resolution 0.1%
Resolution 1V
Accuracy ±2%
Characteristic times
Start time < 50 ms/45 ms 23
Disengaging time < 60 ms/75 ms 23
Number 4
H
D
B F
block limit
J
A G
time
A The maximum of the three line-to-line voltage G The voltage ULLmax is below the block
ULLmax is below the block limit. This is not limit and this is not regarded as an
regarded as an undervoltage situation. undervoltage situation.
Block diagram
Figure 185 - Block diagram for the positive sequence undervoltage
protection
Start
& Register
event
U12
U23 MAX > 0 t
& Trip
U31
&
CB
not closed
U1 <
& Register
event
Characteristic
Table 44 - Settings and characteristics of the positive sequence
undervoltage protection stage U1< and U1<<
Settings/characteristics Value
(description/label)
Pick-up value/U1<
Resolution 1%
Operation delay/t>
Resolution 0.01 s
Accuracy ±1% or ±30 ms
Resolution 1%
Accuracy ±2%
Characteristic times
Start time < 70 ms/65 ms 25
Disengaging time < 85 ms/100 ms 25
Number 4
P
P
Reverse zone Forward zone
P533B2A
Reverse zone Forward zone
P533B3A
The start setting range is from -200% to +200% of the nominal apparent power Sn.
The nominal apparent power is determined by the configured voltage and current
transformer values according to equation below.
Sn = 3 Un In P533B4A
There are two identical stages available with independent setting parameters.
Each stage is deactivated if the maximum voltage of all phases drops below 5% of
the rated voltage value.
Block diagram
Figure 188 - Block diagram of the directional power protection
Start
P >0
< 0 t
U12 Trip
U23 Max < 5%Un
U31
& Register
event
>
<0
& Register
event
Characteristics
Table 45 - Settings and characteristics of the directional power protection
stages P< and P<<
Settings/characteristics Value
(description/label)
Pick-up value/P<
Resolution 0.5%
Operation delay/t<
Resolution 0.1 s
Accuracy ±1% or ± 150 ms
Characteristic times
Start time < 250 ms
Disengaging time < 500 ms
Setting group
Number 4
I0 = IL1 + IL2+ I L3
P533B6A
U0 = VL1 + VL2+ V L3
P533B7A
Q0
Forward Backward
Zone Zone
Pick-up Pick-up
sector size sector size
P0
Pick-up Pick-up
sector size sector size
-U0I0>
+U0I0>
P533B8A
The protection is deactivated if the residual voltage is lower than U0> setting.
The protection is a definite time protection function, where t> is the operation time
setting of the protection.
Operation
With a Petersen coil system, the current in a faulty feeder is usually inductive and
in a healthy feeder, capacitive.
For the forward output, a confirmation is applied on the start signal, because the
wattmetric is based on active power and when a restriking fault occurs with a
Petersen coil system, the following phenomenon needs to be considered:
For the backward output, the wattmetric protection is able to detect the capacitive
current circulation in healthy feeders, to see that the fault is on upstream side:
• In steady state, this capacitive current has a phase-shift of 90° with the
residual voltage. So this capacitive current is not detected because it is
outside the backward characteristic, symmetrical to forward area.
• During the transient, the capacitive current goes first in the backward area,
before to go outside with at the end a phase-shift of 90°. This transient signal
is not used to detect a backward fault with capacitive current, but mainly to
block other protection functions of healthy feeders. This can be the case
when a HV/MV transformer supplies two incomers at the same time (see
Faulty feeder vs. healthy feeder, page 228).
U0
I0
I0r I0
I0 I0v
I0a U0 U0
Tripping direction
The normal operate area, in Easergy P5 protection relay could be set to forward or
reverse area, because sometimes it is not possible to modify CT or VT
connections when there is a mistake in the wirings. In that case, to avoid a
modification of wirings, you can set the operate area to forward (default setting) or
reverse. So if you change the operate area, the confirmation must be applied to
the operate area (which could be forward or backward).
Block diagram
Figure 191 - Block diagram of the wattmetric earth/ground fault protection function (ANSI 32N)
I0 > Alarm
P0 & & non-operate
U0
& Register event
> Alarm
operate
& Register event
-Sector < φ0 < +Sector
Start
Backward
& 0 t
180 - Sector < φ0 < 180 + Sector
Forward
Confirmation & Register event
t t
1 &
0 0
Trip
& Register event
Block
&
S
> &
R
Inh
Mem time
U0> I0U0> Sector Mode U0> Mem Mode: Mem mode: t> Reset Enable
voltage time time events P533BAA
Characteristics
Table 46 - Settings and characteristics of the wattmetric earth/ground fault
protection stages I0U0> and I0U0>>
Settings/characteristics Value
(description/label)
I0 input/Input
Direction mode/Mode
Options Forward; Backward
Inhibit ctrl./InhCtrl
Options Selection of one digital input (DI) or one virtual
input (VI)
Pick-up value/I0U0>
Accuracy ±10%
Settings/characteristics Value
(description/label)
Uₒ> setting/Uₒ>
Resolution 0.1%
Accuracy ±5%
Pick up sector/Sector
Resolution 1°
Accuracy ±1° with I0 and U0 measured
±3° with I0 and U0 calculated
Hysteresis 1° with I0 measured
3° with I0 calculated
Operation delay/t> (DT)
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 50 ms/45 ms at 2 I0U0> 27
< 55 ms/50 ms at 1.2 I0U0> 27
< 60 ms/55 ms at 1.05 I0U0> 27
Overshoot time < 40 ms at 2 I0U0>
Disengaging time < 60 ms/75 ms 27
Setting group
Number 4
Block diagram
Figure 192 - Block diagram of the phase undercurrent protection function
(ANSI 37)
IL1
IL2 Min < & Start
IL3
Trip
Block
& Register event
Characteristics
Table 47 - Settings and characteristics of the phase undercurrent protection
function (ANSI 37)
Settings/characteristics Value
(description/label)
Pick-up value/I<
Resolution 1%
Operation delay/t<
Resolution 0.1 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 60 ms/55 ms 28
Disengaging time < 65ms/80 ms 28
Setting group68
Number 4
28. The 2nd value is only for high speed high break digital outputs.
Block diagram
Figure 193 - Block diagram of the temperature monitoring function (ANSI 38)
T < +200˚C
& > Alarm
Characteristics
Table 48 - Setting and characteristics of the temperature monitoring function
(ANSI 38)
Settings/characteristics Value
(description/label)
Unit °C
Accuracy ±1°C (±1.8°F)
Alarm delay/AlmDly
Accuracy 1% ± 20 ms
Operation delay/OperDly
Accuracy 1% ± 20 ms
Characteristic times
Start time <3s
Setting group
Number 1
1
I2 = ( IL1 + a2 IL2 + a IL3 )
3 P533BDA
with
2π
j ------
a = e 3 P533BEA
Block diagram
Figure 194 - Block diagram of the negative sequence overcurrent protection
function (ANSI 46)
IL1
IL2 I2 >
& Start
IL3
& Register
event
Block
≥1 Trip
& Register
event
k>
I2> t> DT/ IDMT Enable
IDMT characteristics events P533BFA
Characteristics
Table 49 - Settings and characteristics of the negative sequence overcurrent
protection stage I2>
Settings/characteristics Value
(description/label)
Pick-up value/I2>
Resolution 0.01In
Accuracy ±3% or ±0.005In
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Accuracy ±5% or ±30 ms
Reset type
Reset time
Setting range 0.03 - 100 s
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 50 ms/45 ms at 2xI2> 29
< 60 ms/55 ms at 1.2xI2> 29
< 65 ms/60 ms at 1.05xI2> 29
Disengaging time < 75 ms/90 ms 29
Setting group
Number 4
29. The 2nd value is only for high speed high break digital outputs.
1
I1 = ( IL1 + a IL2 + a2 IL3 )
3 P533BGA
1
I2 = ( I + a2 IL2 + a IL3 )
3 L1 P533BHA
NOTE: The broken conductor function is inhibited if the current value flowing
in each one of the three phases is less than 20% of the nominal current.
Block diagram
Figure 195 - Block diagram of the unbalance overcurrent broken conductor
protection function (ANSI 46BC)
Register
Block & event
Trip
& Register
event
Characteristics
Table 50 - Settings and characteristics of the unbalance overcurrent broken
conductor protection stage I2/I1>
Settings/characteristics Value
Pick-up value/I2/I1>
Resolution 1%
Accuracy ±3%
Hysteresis
Value 95%
Operation delay/t>
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 50 ms/45 ms at 2xI2/I1> 30
< 60 ms/55 ms at 1.2xI2/I1> 30
< 75 ms/70 ms at 1.05xI2/I1> 30
Disengaging time < 75 ms/90 ms 30
Setting group
Number 4
30. The 2nd value is only for high speed high break digital outputs.
T
t=
U2
Us 1 P533BKA
where:
t is the theoretical operate time in seconds
T is the time setting (theoretical operate time for U2 = 2 × Us)
U2 is the calculated value of negative sequence voltage
Us is the pick-up setting value of the negative sequence overvoltage protection (
U2> or U2>>)
The U2> stage has a settable reset delay that enables the detection of intermittent
faults. This means that the time counter of the protection function does not reset
immediately after the fault is cleared, but resets after the release delay has
elapsed. If the fault appears again before the release delay time has elapsed, the
delay counter continues from the previous value. This means that the function
eventually trips if faults are occurring often enough. This function is blocked by
VTS operation if the setting “VTSOpMod” is set to “BLOCKING”.
Block diagram
Figure 196 - Block diagram of the negative sequence overvoltage protection
(ANSI 47)
U2 U2/Un >
& Start
Register
VTSInh Blk & event
No
blk
t
≥1
Block ≥1 Trip
& Register
event
Characteristics
Table 51 - Settings and characteristics of the negative sequence overvoltage
protection function (ANSI 47)
Resolution 1%Un
Accuracy ±2%
Delay type/DelayType
Options DT;
INV (the characteristic follows the equation provided in
Description, page 239)
Resolution 0.01 s
Accuracy DT: ±2% or ±20 ms;
IDMT: ±5% or ±20 ms
Resolution 0.01 s
Accuracy ±2% or ±20 ms
Hysteresis/Hyster
Value 98% ± 1%
Characteristic times
Start time < 40 ms/35 ms for 0.9 - 1.1U2>31
Overshoot time < 40 ms for 0.9 - 1.1U2>
Setting group
Number 4
31. The 2nd value is only for high speed high break digital outputs.
l eq (t)
( ) x Δtτ Δt
2
H(t) = H(t - Δt) + - H(t - Δt) x
k x lb τ P533BMA
where:
• H(t) is the thermal level computed at time t ("Thermal level").
• H(t - Δt) is the thermal level computed at time t - Δt.
• Ieq(t) is the equivalent heating phase current at time t computed from the
maximum of the 3 phase RMS currents.
• Ib is the continuous rated level ("Basic current setting" or "Ib").
• k is the "k" factor applied to the basic current to define the maximum
continuous current ("Factor k").
• is the heating/cooling thermal time constant of the feeder ("Heating time
constant" or "Time constant "), where is assumed to be much greater than
Δt.
"[Ieq(t) / (k x Ib)]2x Δt / " expresses the heat transfer due to the phase current Ieq(t)
and "H(t - Δt) x Δt / " expresses the natural cooling of the feeder conductors.
The thermal overload protection operates when the thermal level is greater than
100%. This thermal level of 100% can be reached with a permanent current above
the basic current value Ib multiplied by the k factor.
With a continuous load current "Ieq", the thermal level "H" is equal to:
l eq
(K lb )
2
H (l eq ) =
x P533BNA
The table below indicates the thermal level with different values of continuous load
current:
1 100% (operation)
0.9 81%
0.8 64%
0.7 49%
0.6 36%
0.5 25%
0.4 16%
0.3 9%
Generally, the basic current Ib is set to the continuous thermal withstand current of
the feeder conductors, and k factor could be set to take into account the accuracy
of the global current measuring chain (phase CTs and the protection relay). The k
factor is set to 1.0 by default.
An thermal alarm ("AlmThm" output) is provided which operates when the thermal
level is greater than or equal to the "Thermal Alarm Value" setting (expressed in
%) and is usually set to be lower than 100 %, the operate level. This threshold,
expressed in %, is available only in the current based setting mode.
The thermal level in % is accessible as an output measurement.
When thermal overload is managed in the several setting groups, the thermal level
is kept after the setting group change (no thermal level reset), and the thermal
level is computed according to the new settings.
l eq (t)
( ) x Δtτ Δt
2
H(t) = H(t - Δt) + Fa x - H(t - Δt) x
k x lb τ P533BQA
Where common values are identical to the thermal level H(t) calculation formula,
and the additional "Fa" ambient temperature factor is defined with the following
equation:
Tmax - T nom
Fa =
Tmax - T a P533BRA
where:
• Tmax is the maximum temperature of the equipment ("Max object
temperature").
• Tnom is the limit of the ambient temperature designed for the feeder
conductors to operate at rated loads without causing thermal degradation of
insulation ("Nominal ambient temp", typically equal to 40 ℃).
Where H(t), Tmax and Ta are defined according to the previous equations.
The thermal overload protection operates when the computed temperature
"Tobject" is above or equals the maximum temperature Tmax.
An thermal alarm is provided ("AlmThm" output). This output operates when the
temperature level is greater than or equal to the alarm temperature threshold
("Talm" setting, expressed in ℃).
The ambient temperature (Ta) and object temperature (Tobject) are accessible as
output measurements in ℃ (Ta = "Ambient temperature" output and Tobject =
"Object temperature" output). The value of the ambient temperature is equal to the
default value set as "TmpAmbDft".
Additional features
The thermal level computation expressed in % is always available with the feeder
thermal level output. The current thermal level is saved in a non volatile memory
when the Easergy P5 protection relay is powered off. If the current thermal level is
above 90%, a value of 90% is memorised to prevent possible nuisance tripping on
supply restoration.
A measurement output where the remaining time to trip is provided, based on the
hypothesis that the load current present remains constant until thermal overload
operation occurs ("Time" Output).
An time remaining alarm ("RsvAlm" output) is provided. It operates when the
calculated remaining time is less than or equal to the "Reserve value" time setting.
There is a digital input (“FThLevRst” signal) to reset the thermal level value, when
the digital input is asserted, the value of Thermal level is set to Zero.
It is possible to block the protection function using the block matrix.
Typical values of thermal time constant:
Air-core reactors 40
Capacitor banks 10
Overhead lines 10 ( Cu: cross section greater than or equal to 100 mm2 (0.15 in2);
or AI: 150 mm2 (0.23 in2) )
Busbars 60
Fa x H(leq ) - H 0
t = τ x Ln (
Fa x H(Ieq ) - 100% ) P533BOA
where:
• is the thermal time constant for the protected equipment.
• Ln( ) is natural logarithm function.
• Fa is the ongoing temperature compensation. In current based setting mode,
Fa = 1.
• H(Ieq) is the thermal level calculated with the continuous load current (Ieq) and
the basic current setting (Ib) (see Current based setting mode).
• H0 is the current thermal state corresponding to the last calculation.
In the same way, for a continuous current higher than the current threshold (k x Ib),
the time for the alarm to operate is:
Fa x H(leq ) - H 0
t = τ x Ln ( )
Fa x H(leq ) - H alarm P533BTA
where:
Halarm is "Alarm" (alarm threshold setting, in %). In temperature based setting
mode, the threshold alarm threshold is expressed in ℃ with "Talm" setting. The
corresponding thermal level in % (Halarm) is defined by the following equation:
Talm - T a
H alarm = x 100%
Tmax - T a P533BUA
Block diagram
Figure 197 - Block diagram of the thermal overload protection function (ANSI 49F)
Block Blocked
& Register
Current based mode event
calculation ≥1 &
>100% Trip
%
IL1 RMS
IL2 RMS MAX >
IL3 RMS
>
& RsvAlm
< & Register
RTD #8 event
< TmpAlm
& Register
event
> TmpAlm
& Register
event
Characteristics
Table 52 - Settings and characteristics of the thermal overload protection
stage 49F>
Settings/characteristics Values
(description/label)
Resolution 0.01In
Max permissive factor/Factor k
Resolution 0.01
Heating time constant/Time constant τ 1
Resolution 1%
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Alarm temperature/T°alm
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Resolution 0.1%
Characteristics
Tripping time accuracy ±5% or ±500 ms (with the applicable factor
according to IEC 60255-149)
Setting group
Number 4
Motor status
Description
There are three possible status for a motor: stopped, starting or running.
The Easergy P5 detects motor start by CB position, motor current, or both CB
position and motor current using “Motor start detection mode”.
• CB Position: The CB position changes from open to closed.
• Current: Three phase currents have been less than 5% In (phase CT primary
value). Then any of the three phase currents increases and exceeds the
motor start detection current.
• CB Position and Current: Any of the three phase currents exceeds the motor
start detection current in 90 ms after CB position changes from open to close.
Stopped
2 4
1 1
Starting Running
3
P533BWA
Istart
90 ms
CB Closed
Motor Running
Status 100 ms
Starting
Stopped
P533BXA
Istart
90 ms
CB Closed
Motor
Status
Running
Stopped
P533BYA
General settings
Settings Value
(description/label)
Resolution 0.01In
Motor start detection current/Istart>
Setting range 0.1In - 10.00In
Resolution 0.01In
Reset ratio 95% ± 2%
1 2
P533BZA
Characteristics Values
Pass-band (in Hz) > 2Ωn* R/60
The proximity detector output pulses are at a voltage level which is compatible
with the logic inputs (24 – 240 V DC), which means that a logic input must be
mapped to a given proximity detector to perform the speed measurement. The
12I4O module contains a specific digital input (DI1) to detect the motor speed. It
can recognise the high voltage signal as status 1 with > 200 us pulse width and
the low voltage signal as status 0 with > 120 us pulse width.
Easergy P5 protection relay can only use one speed detection input. If several
12I4O modules (such as Slot C, Slot D, Slot E) are fitted in the Easergy P5
protection relay, the user can select the dedicated digital input from any of the
12I4O modules for motor speed detection. If there is no 12I4O module fitted in the
relay, the motor speed detection and motor overspeed / underspeed protection will
be invisible.
NOTICE
IMPROPER EQUIPMENT OPERATION
If the counting input DI1 on 12I4O is selected for motor speed detection, this
input cannot be used by any other protection functions.
Failure to follow this instruction can result in equipment damage.
When the motor speed detection function is Enabled and one specific digital input
is selected as motor speed input, the settings, such as “Delay”, “On Event”, “OFF
Event” and “Debounce” settings in “Control/Digital inputs” are automatically
noneffective for this selected digital input.
This function provides an output signal “Zero Speed”. If the Easergy P5 protection
relay does not detect the pulse from the proximity sensor for motor speed
measurement for a settable duration, the zero speed output signal is ON.
Block diagram
Figure 202 - Block diagram of zero speed detection
New pulse
Tzero 0
Absence Zero Speed
of pulses
& Register
event
Characteristics
Table 54 - Settings and characteristics of motor speed detection protection
Settings/characteristics Values
(description/label)
Resolution 1 rpm
Resolution 1
Zero speed delay
Resolution 1s
Accuracy ±2% or ±150 ms
Motor speed
Resolution 1 rpm
Accuracy ±1 rpm
Refresh interval 1s
Measurement time 100 ms
Setting group
Number 1
2
I
T = motNomSt Tstart
I P533C1A Equation 7.7
Where:
T = Dependent operate time
ImotNomSt = Nominal motor start current
I = Maximum of IL1, IL2, IL3
Tstart = Motor start time
Figure 203 - Example of an dependent operation time of the motor start time
supervision protection function
250
200
Istart = 6xIn, rated start current
Tstart = 15 s, maximum allowed start time
Time (s)
150
100
50
Tstart
1 2 3 4 5 6 7 8
Current (xIn) Istart P533C2A
The pick-up current setting Istart> is the start detection level of the start current.
While the motor status is starting and the current exceeds the pick-up setting
Istart>, the motor start-up supervision stage starts to count the operate time.
When current drops below the setting Istart>, the motor start-up supervision stage
releases. Motor start-up supervision is active only during the starting of the motor.
Block diagram
Figure 204 - Block diagram of the motor start time supervision function
(ANSI 48)
IL1
IL2 MAX >
& & Start
IL3
& Register
event
Motor status
= starting
Block ≥1 Trip
& Register
event
Characteristics
Table 55 - Settings and characteristics of the motor start time supervision
protection stage Ist>
Settings/characteristics Value
(description/label)
Delay type
Resolution 0.1 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 70 ms/65 ms 32
Disengaging time < 85 ms/100 ms 32
Setting groups
Number 1
NOTE: For motor start detection current and nominal start current settings,
see Motor status, page 246.
32. The 2nd value is only for high speed high break digital outputs.
where:
where:
◦ IL1, IL2, IL3 are the RMS phase currents.
◦ q is a user setting to define the unbalance factor ("Unbalance factor" or
"Factor q").
For an asynchronous motor, q is determined as follows:
q = 2 x TLR I LR - 1
2
Sn P533C6A
Where 2 is the heating time constant during starting sequence or the phase
currents is greater than the motor start threshold ("Time constant for motor starting
" or "Time constant 2").
The digital output Motor TC2 active is asserted in this state.
Motor is stopped
When the motor is stopped, the cooling effect is dominant since there is no
heating contribution, so a cooling time constant must be taken into account in the
stopped state. In that state, the thermal level H(t) is computed according to the
following equation:
Δt
H(t) = H(t - Δt) - H(t - Δt) x
τ 3 P533C8A
With a continuous load current "Ieq", the thermal level "H" is equal to:
l eq
(K )
2
H (l eq ) =
x lb
P533C9A
The table below indicates the thermal level with different values of continuous load
current:
1 100% (operation)
0.9 81%
0.8 64%
0.7 49%
0.6 36%
0.5 25%
0.4 16%
0.3 9%
Generally, the basic current Ib is set to the continuous thermal withstand current of
the protected equipment, and k factor could be set to take into account the
accuracy of the global current measuring chain (phase CTs and the protection
relay). The k factor is set to 1.0 by default.
An thermal alarm ("AlmThm" output) is provided which operates when the thermal
level is greater than or equal to the "Thermal alarm value" setting (expressed in %)
and is usually set to be lower than 100%, the operate level. This signal can be
used to lock the CB reclosing until thermal state is back under the alarm level.
The thermal level in % is accessible as an output measurement.
When thermal overload is managed in the several setting groups, the thermal level
is kept after the setting group change (no thermal level reset), and the thermal
level is computed according to the new settings.
Where common values are identical to the thermal level H(t) calculation formula,
and the additional "Fa" ambient temperature factor is defined with the following
equation:
Tmax - T nom
Fa =
Tmax - T a P533CBA
where:
• Tmax is the maximum temperature of the equipment ("Max object temperature"
setting).
• Tnom is the limit of the ambient temperature designed for the protected
equipment to operate at rated loads without causing thermal degradation of
insulation ("Nominal ambient temperature" setting, typically equal to 40 ℃).
Where H(t), Tmax and Ta are defined according to the previous equations.
The thermal overload protection operates when the computed temperature
"Tobject" is above or equals the maximum temperature Tmax.
An thermal alarm is provided ("AlmThm" output). This output operates when the
temperature level is greater than or equal to the alarm temperature threshold
("Talm" setting, expressed in ℃).
The ambient temperature (Ta) and object temperature (Tobject) are accessible as
output measurements in ℃ (Ta = "Ambient temperature" output and Tobject =
"Object temperature" output).
Additional features
The thermal level computation expressed in % is always available with the motor
thermal level output. The current thermal level is saved in a non volatile memory
when the Easergy P5 protection relay is powered off. If the current thermal level is
above 90%, a value of 90% is memorised to prevent possible nuisance tripping on
supply restoration.
A measurement output about the remaining time to trip ("Estimated time to trip" or
" TimeToTrip") is provided, based on the hypothesis that the load current present
remains constant until thermal overload operation occurs.
A time remaining alarm ("RsvAlm" output) is provided. It operates when the
calculated remaining time is less than or equal to the "Reserve value" time setting.
A remote command can be used to reset the thermal level (e.g. after
commissioning tests). This reset can be also performed from the local panel.
It is possible to block the protection function using the block matrix.
After each motor start sequence, the function is able to compute the thermal level
consumed by the latest start. This measurement is accessible with the
measurement output "Motor start thermal level/MStrThelev". When the thermal
level calculation is above (100% - MStrThmlev), the output signal "Block motor
start" is asserted to inhibit CB Closing from taking place. The output time
measurement output "Time left for motor start" provides the remaining time until
the motor can be started.
There is a digital input (“MThLevRst” signal) to reset the thermal level value, when
the digital input is asserted, the value of Thermal level H(t) shall be set to Zero.
where:
• is the thermal time constant for the protected equipment.
◦ When the motor is in starting state, the time constant for motor starting is
used;
◦ When the motor is in running state, the heating time constant is used;
◦ When motor is in stopped state, the cooling time constant is used.
• Ln( ) is natural logarithm function.
• Fa is the ongoing temperature compensation. In current based setting mode,
Fa = 1.
• H(Ieq) is the thermal level calculated with the continuous load current and the
basic current setting (see Motor is stopped).
• H0 is the current thermal state corresponding to the last calculation.
In the same way, for a continuous current higher than the current threshold (k x Ib),
the time for the alarm to operate is:
Fa x H(leq ) - H 0
t = τ x Ln ( )
Fa x H(leq ) - H alarm P533CEA
where:
Halarm is "Alarm", the alarm threshold setting in %. In temperature based setting
mode, the threshold alarm threshold is expressed in ℃ with "Talm" setting. The
corresponding thermal level in % (Halarm) is defined by the following equation:
Talm - T a
H alarm = x 100%
Tmax - T a P533CFA
( KI x I ) x t start
2
H start = Fa x start
τstart
b P533Q1A
where:
• Fa is ambient temperature factor calculated by:
Tmax - Tnom
Fa =
Tmax - Ta P533Q4A
t = τcooling x Ln ( H (t)
100% - H start ) P533Q2A
where:
• H(t) is the thermal level calculated at the moment.
• cooling is the cooling time constant when motor is stopped.
Block diagram
Figure 205 - Block diagram of thermal overload protection function (ANSI 49M)
Block Blocked
Register
& event
> 100% &
Current based mode Trip
Calculation ≥1
I2
%
Therm Register
level & event
add > 100%
IL1 RMS
& Blk Motor start
IL2 RMS %
MAX Motor str
IL3 RMS level
>
Heating H(t)
init
& AlmThm
Mot. Start H(t)
init ≥1
MThLevRst > & Register
event
Temperature based ºC
mode calculation
>
& RsvAlm
< & Register
RTD #8 event
& Register
event
& Register
event
< TmpAlm
& Register
event
> TmpAlm
& Register
event
Characteristics
Table 56 - Settings and characteristics of the thermal overload protection
stage 49M>
Settings/characteristics Values
(description/label)
Resolution 0.01In
Factor k
Setting range 0.1 - 1.5
Resolution 0.01
Heating time constant/Time constant τ 1
Setting range 0 - 10
Resolution 0.1
Thermal alarm value/Alarm
Setting range 50% - 100%
Resolution 1%
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Settings/characteristics Values
(description/label)
Resolution 1 ℃ (1.8 ℉)
Resolution 1 ℃ (1.8 ℉)
Characteristics
Tripping time accuracy ±5% or ±500 ms (with the applicable factor
according to IEC 60255-149)
Setting group
Number 4
NOTE: To test the thermal overload protection more easily and faster, it is
possible to set a Thermal level init. value and a motor start level init. value
from 0% to 90%. After test, it is possible to reset the values to 0%.
2
I
T = motNomSt Tstart
I P533FNA Equation 7.8
Block diagram
Figure 206 - Block diagram of the locked rotor protection stage Ilr>
IL1
& Register
event
Characteristics
Table 57 - Settings and characteristics of the locked rotor protection stage
Ilr>
Settings/characteristics Values
(description/label)
Pick-up value/Ilr>
Resolution 0.1%
Accuracy ±3%
Delay type/DelayType
Operation delay/t>
Resolution 0.1 s
Accuracy ±1% or ±20 ms (DT)
±5% or ±20 ms (INV)
Characteristic times
Start time < 60 ms/55 ms at 2xIlr 33
< 70 ms/65 ms maximum 33
Disengaging time < 85 ms/100 ms 33
Setting group
Number 1
33. The 2nd value is only for high speed high break digital outputs.
ON
OFF
Time
Start Inhibition Reference period = 60 min
ON
OFF
tn = 8 min Time
P533F9A
ON
OFF
Time
Start Inhibition
Min time between motor starts
ON
OFF
Time
P533FAA
So, the motor restart inhibition function is active if any one of the following
conditions is satisfied:
• Blocking due to number of starts limitation
• Blocking due to minimum time between 2 starts
M
+
Output matrix
DO1 DOx
I> start
I> trip
N> alarm
N> motor start inhibit
P533FBA
Block diagram
Figure 210 - Block diagram of the motor restart inhibition function (ANSI 66)
Motor
starting & Count num. during
reference period ≥
≥1 N> motor
start inhibition
≥ Hot starts/t -1
≥1 Alarm
Characteristics
Table 58 - Settings and characteristics of the motor restart inhibition
function (ANSI 66)
Settings/characteristics Values
(description/label)
Resolution 0.1%
Max motor hot starts
Setting range 1 - 20
Resolution 1
Max motor cold starts
Setting range 1 – 20
Resolution 1
Min time between motor starts/Interval
Setting range 0.0 min - 100.0 min
Setting groups
Number 1
Block diagram
Figure 211 - Block diagram of the motor overspeed stages Motor speed> and
Motor speed>>
Motor speed
& Start
Block
Register
& event
Trip
& Register
event
Characteristics
Table 59 - Settings and characteristics of the motor overspeed protection
function (ANSI 12)
Resolution 1%Ωn
Resolution 1s
Accuracy ±1% or ±25 ms
Characteristic times
Start time < 250 ms + 2*(60000 ms/(Ω*R))
Setting group
Number 1
0.05Ωn
Start
t
Trip
P533FEA
Block diagram
Figure 213 - Block diagram of the motor underspeed stages Motor speed<
and Motor speed<<
Register
& event
<
Trip
<0.05Ωn
≥1
Block
& Register
event
Characteristics
Table 60 - Settings and characteristics of the motor underspeed protection
function (ANSI 14)
Resolution 1%Ωn
Accuracy ±2%*(5%Ωn)
Resolution 1s
Accuracy ±1% or ±25 ms
Characteristic times
Start time < 250 ms + 2*(60000 ms/(Ω*R))
Setting group
Number 1
Block diagram
Figure 214 - Block diagram of Motor Anti-backspin (ABS)
Zero Speed
ABSAllowRestart
&
Speed
measured mode
Zero Speed DI
AntiBkSpin
& ≥1 & Alarm
Ex. zero
speed mode
& Register
event
Motor Status
Stopped
Time to restart
Characteristics
Table 61 - Settings and characteristics of Motor Anti-backspin (ABS)
protection
Settings/characteristics Values
(description/label)
Resolution 1s
Accuracy ±1% or ±25 ms
Setting group
Number 1
Inrush blocking
Description
Second harmonic inrush blocking detects high inrush current flows that occur
when transformers or machines are connected and helps to prevent tripping for
this normal occurrence.
In the Easergy P5 protection relay, the inrush detection function can block the
following protection functions.
• Phase overcurrent (with or without directional element)
• Standard earth/ground fault overcurrent (without directional element)
• Very sensitive earth/ground fault overcurrent (without directional element)
When the corresponding inrush blocking is enabled in the setting group and the
inrush blocking signal is detected.
During transformer inrush conditions, the second harmonic level may not be the
same for all phases. So Easergy P5 protection relay calculates the ratio between
the second harmonic component and the fundamental frequency component for
each phase. When the ratio of the second harmonic component of any phase is
higher than the ratio setting, the inrush blocking signal is detected.
To avoid mis-operation, the inrush detection is only active when the phase current
is greater than 10%In. Otherwise, the output of the inrush detection is reset. For
additional protection a maximum threshold current is settable. Currents above this
threshold will bypass any inrush blocking. The threshold is set based on the
transformer reactance. This reactance will limit any inrush current , therefore
currents greater than this are treated as short circuits.
The inrush blocking signal requires the presence of second harmonic current for 1
period (20 ms at 50 Hz). Similarly the reset of this condition requires the absence
of second harmonic component for 30 ms.
This difference in time provides hysteresis to the inrush blocking and avoids the
signal oscillating during low harmonic conditions such as occur towards the end of
an inrush condition.
The other protection functions which need the inrush blocking function can be
configured in the block matrix via eSetup Easergy Pro.
Block diagram
Figure 215 - Block diagram of inrush blocking
<
Inrush
IL2H2 20ms 30ms
detection
>IL2H2 / IL2 &
IL2
& Register
>0.1In
& ≥1 event
<
Characteristics
Table 62 - Settings and characteristics of the inrush blocking function
Settings/characteristics Values
(description/label)
Pick-up value/Pickup H2
Resolution 1%
Accuracy ±1%
Hysteresis 1%
Resolution 0.01In
Accuracy ±3% or ±0.005In
Characteristic times
Start time < 40 ms
Setting group
Number 1
Operation
Switch-on-to-fault function operates within the SOTF active operation time, page
274 and Switch-on-to-fault function does not operate after the SOTF active
operation time elapses, page 275 illustrate the operation of the SOTF function:
1. Switch-onto-fault does not activate if the CB has not been in open position
before the fault. Open CB detection is noticed from the highest phase current
value which has to be under a fixed low-limit threshold (0.02 x In). Opening of
the CB can be detected also with digital inputs (Dead line detection input =
DI1 – DIx, Fx, VI1 – VIx). The default detection input is based on the current
threshold, so the dead line detection input parameter has value “–“.
2. Dead line detection delay defines how long the CB has to be open so that the
SOTF function is active. If the set operation time is not fulfilled and the highest
phase current value (maximum of IL1, IL2, IL3) rises over the start setting, the
SOTF does not operate.
3. If the highest phase current value of IL1, IL2, IL3 goes successfully under the
low limit and rises to a value between the low limit and the start value, then if
the highest phase current value rises over the start setting value before the
SOTF active operation time expires, the SOTF trips. If this SOTF active
operation time is exceeded, the SOTF does not trip even if the start setting
value is exceeded.
Start setting
Dead
delay
SOTF active timer
SOTF trip
P533FIA
Figure 217 - Switch-on-to-fault function does not operate after the SOTF
active operation time elapses
1
Start setting
Dead
delay
SOTF active timer
SOTF trip
P533FJA
Block diagram
Figure 218 - Block diagram of the Switch On To Fault protection function
(ANSI 50HS)
0 T
Dead line
input
Characteristics
Table 63 - Settings and characteristics of the switch-on-to-fault protection
function (ANSI 50HS)
Settings/characteristics Values
(description/label)
Pick-up value/SOTF
Resolution 0.01In
Accuracy ±3%
Resolution 0.01 s
SOTF active after CB closure/Act time
Setting range 0.10 s - 60.00 s
Resolution 0.01 s
Dead line detection input
Characteristic times
Start time < 30 ms/25 ms when I/Iset < 1.5 34
< 40 ms/35 ms maximum 34
Disengaging time < 60 ms/75 ms 34
Setting group
Number 1
34. The 2nd value is only for high speed high break digital outputs.
Block diagram
Figure 219 - Block diagram of the three-phase overcurrent stages I> and I>>
IL1
IL2 MAX
& Start
IL3
Register
& event
Block
Trip
& Register
InrushStat event
&
& Select
CLPStat & setting
NOTE:
The Reset time setting in the above figure only applies to the protection stage
I>.
IL1
IL2 MAX
& Start
IL3
Register
& event
Block
InrushStat Trip
&
& Register
SOLStat event
& Select setting
Select setting
CLPStat &
&
Characteristics
Table 64 - Setting and characteristics of the phase overcurrent protection
(ANSI 50/51)
Pick-up value
Setting range 0.05In - 20In (DT) 0.1In - 20In (DT) 0.1In - 40In
0.05In - 5In (IDMT) 0.1In - 5In (IDMT)
Resolution 0.01In
Accuracy ±3% or ± 0.005In
Resolution 0.01 s
Accuracy ±1% or ± 20 ms
Accuracy ±5% or ± 20 ms -
Reset type
Resolution 0.01 s -
Accuracy ±1% or ± 20 ms -
Resolution 0.01 s
SOL Inv. time 0.05 to 20.0 for DT, IEC and RI -
coefficient 0.50 to 20.0 for RXIDG, IEEE and IEEE2
K/SOLK>
Accuracy ±1% or ±20 ms, definite time ±1% or ±20 ms
±5% or ±20 ms, IDMT time
Setting range 0.05In - 20In (DT) 0.1In - 20In (DT) 0.1In - 20In
0.05In - 5In (IDMT) 0.1In - 5In (IDMT)
Resolution 0.01In
Accuracy ±3% or ± 0.005In
Resolution 0.01 s
CLP Inv. time 0.05 - 20.0 for DT, IEC and RI; -
coefficient 0.50 - 20.0 for RXIDG, IEEE and IEEE2
K/CLPK>
Accuracy ±1% or ±20 ms, definite time ±1% or ±20 ms
±5% or ±20 ms, IDMT time
Include harmonics/IncHarm35
Options Enable (for the use of rms current values);
Disable (for the use of fundamental current values);
Characteristic times
Start time < 35 ms/30 ms < 30 ms/25 ms < 25 ms/20 ms
at 2 x I> 36 at 2 x I>> 36 at 2 x I>>> 36
< 40 ms < 40 ms < 35 ms/30 ms
at 1.2 x I> at 1.2 x I>> at 1.2 x I>>> 36
Disengaging time < 55 ms/70 ms 36
Number 4
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Information on this product is offered as a tool for conducting arc flash hazard
analysis. It is intended for use only by qualified persons who are knowledgeable
about power system studies, power distribution equipment, and equipment
installation practices. It is not intended as a substitute for the engineering
judgement and adequate review necessary for such activities.
Failure to follow these instructions will result in death or serious injury.
Description
The arc-flash protection function (ANSI code 50ARC) is a high speed protection
function able to detect arcing events on busbar in a few millisecond, to minimise
equipment damages.
The arc-flash protection contains 8 arc stages that can be used to trip for example
the circuit breakers. Arc stages are activated with overcurrent and light signals (or
light signals alone). The allocation of light and/or different current signals to arc
stages is defined in arc-flash protection matrices: current, light and output matrix.
The matrices are programmed via the dedicated arc-flash matrix menus. Available
matrix signals depend on the order code (see Order information, page 486).
Available signal inputs for arc-flash protection depend on the Easergy P5
protection relay's configuration with 3 or 6 light inputs.
With 3 to 6 arc-flash input options, the Easergy P5 x30 protection relay allows to
build a multi-zone arc-flash protection system.
Information like arc detection or current detection can be exchanged across the
system using two communication ways:
• GOOSE messages using the IEC 61850 protocol (preferred solution)
• Virtual outputs and outputs
ZONE 1
=Arc sensor
Device 3
ZONE 2
ZONE 3
T T
Device 1 Device 2
P533E0A
In this application example, the arc-flash sensor for zone 4.1 is connected to
Device 1. If the arc-flash sensor detects the fault and simultaneously Device 3
sends a current signal, the zone 4.1 is isolated by the outgoing feeder breaker.
The arc-flash sensor for zone 4.2 is connected to the Device 2 and operates the
same way.
The arc-flash sensors for zone 3 are connected to Device 1, 2 or 3. If a sensor
detects the fault in zone 3, the light-only signal is transferred to Device 3 which
also detects overcurrent and then trips the main circuit breaker.
An eventual arc-flash fault in zone 1 or 2 does not necessarily activate the current
element in Device 2. However, arc detection can be achieved by using the light-
only principle. If an arc-flash occurs in cable termination, zone 1 or zone 2, the
fault is cleared by the upstream circuit breaker.
Each arc-flash protection stage provides:
• One arc detection function, which can be connected either to one of the
available arc sensors (for local detection) or to a digital input or GOOSE
information (for remote detection).
• One current detection function, which can be connected either to phase or
earth/ground fault high-speed overcurrent (for local detection) or to a virtual
input or GOOSE information (for remote detection).
• One trip input to other relays
The trip signal of arc-flash protection is not a part of the global trip. In this
case it is convenient to use Goose which provides a fast signal to the other
relay.
Earth/ground fault current can be only measured and detected, according to the
Easergy P5 protection relay, from:
• 1/5A residual CT input
• CSH residual current input
Each stage of the arc-flash protection can be blocked individually by a control
inputs such as digital input, virtual inputs and function keys.
Block diagram
Figure 222 - Block diagram of the arc-flash protection function
IL1/IL2/IL3 > ≥1
pulse Trip
t
Light
Operation
Before configuring the arc flash protection, the arc sensors need to be installed
through eSetup Easergy Pro.
The installation process is as follows:
1. In eSetup Easergy Pro, select ARC protection in the Protection menu.
2. Under Settings, click the Install arc sensors drop-down list and select Install.
Digital ouptut On, Off D01 to D03 (slot B) or D01 to D04 (slots C, D, E)
according to the Easergy P5 configuration
Characteristics
Table 68 - Setting and characteristics of the arc-flash protection function
(ANSI 50ARC)
Setting/characteristics Values
(description/label)
Stage Mode/Mode
Resolution 0.01In
Accuracy ±2.5%
Resolution 0.01In
Accuracy ±2.5%
DI to block stage
Options Selection of one digital input (DI), one virtual input (VI), or one
function key (Fx).
Operation delay/Delay
Accuracy ±1% or 20 ms
Resolution 1 ms
Accuracy ±1% or 20 ms
Characteristic time
Start time 37
Light only 2 ms minimum 4 ms maximum
37. With high speed high break contact relay (Easergy P5x30) only.
Setting/characteristics Values
(description/label)
The arc operation delay is intended, with the separate arc stage, for the circuit
breaker failure scheme only.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not use the arc operation delay for primary trip.
Failure to follow these instructions will result in death or serious injury.
Current based protection [IL1<] & [IL2<] & [IL3<] & [I0<] or [I0'<] according to Easergy
P5 model
Non-current based protection Three options are available:
• Current protection reset
• Pole dead
• Reset of the non-current protection
Similarly, if both the line current and voltage fall below a pre-set threshold the
protection relay will also initiate a pole dead condition.
This is necessary so that a pole dead indication is still given even when an
upstream circuit breaker is opened. The under-voltage (U<) and under-current (I<)
thresholds have the following, fixed, pickup and drop-off levels as shown in Pole
dead logic, page 288.
If the VT fails a signal is taken from the VTS logic to block the pole dead
indications that would be generated by the under-voltage and under-current
thresholds. However, the VTS logic will not block the pole dead indications if they
are initiated by a "CB Open" signal. The object for used CB is directly set in the
Objects view of the Control menu in eSetup Easergy Pro.
< 0.05In
IL1 Dropff: 0.055In
&
UL1 < 0.1Un ≥1
Dropff: 0.3Un
< 0.05In
IL2 Dropff: 0.055In All Pole Dead
&
< 0.1Un ≥1 &
UL2 Dropff: 0.3Un
< 0.05In
IL3 Dropff: 0.055In
&
< 0.1Un ≥1
UL3 Dropff: 0.3Un
VTSBlk
CB Pos
(Open) P533E2A
NOTE: For Easergy P5U20, under voltage detection logic is ignored. For
Easergy P5V20, only CB position is used to check pole dead, under current
and under voltage logic are disabled.
Matrix use
To activate the circuit breaker failure function with current protection trip or with
non-current protection trip, it is recommended to connect the relevant signals.
These are the CBF-ITrp signal or CBF-nITrp signal respectively.
The digital input used for the external trip signal is directly set in the breaker failure
function.
Block diagram
Figure 227 - Block diagram of the circuit breaker failure protection function
CBF 2 Trip
Register
IL1, IL2, IL3 < & event
I0 <
Current protection
trip (CB-I-trip) S t 0 S
&
Digital input for ≥1 R R
external reset signal
I0’ trip S
&
I0’ < ≥1 R
≥1 CBF 1 Trip
VL1, VL2, VL3 Pole Dead
≥1
t 0
Detection
CB open & & Register
position event
Non-current S
protection trip &
(CB-N-trip) & R
& ≥1
&
Digital input for
external trip signal S
& &
R
& ≥1
I<
I0< Enable CBF T1> Enable Enable CBF T2> Enable
I0’< timer 1 events timer 2 events
NonCurRstMod = PoleDead ExtRstMod = I<
NonCurRstMod = ProRst ExtRstMod = ProRst
NonCurRstMod = I< ExtRstMod = PoleDead P533E3A
Characteristics
Table 70 - Settings and characteristics of the breaker failure protection
function (ANSI 50BF)
Settings/characteristics Values
(description/label)
Resolution 0.01In
I0< Current Set/I0<
Setting range 0.05In0 - 4In0 for I0 measured by CSH;
0.02In0 to 4In0 for I0 measured by standard earth/ground fault CT
Resolution 0.001
I0'< Current Set/I0'<
Setting range 0.002In0 to 0.8In0 for very sensitive earth/ground fault
Resolution 0.001
Time1 Operation Delay/T1>
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Options Selection of one digital input DI, one virtual input VI, or one
function key
Options Selection of one digital input DI, one virtual input VI, or one
function key
Characteristic times
Reset time 38 < 35 ms for any trip initiate, reset by I<;
< 35 ms for any trip initiate, reset by I0<;
< 50 ms for non-current protection initiate, reset by Pole Dead 39
Setting group
Number 1
Figure 228 - Typical capacitor bank protection application with the Easergy
P5 protection relay
Easergy P5
A9
IL1
A10
A11
IL2
A12
A13
IL3
A14
A15
I0 Std
A16
A17
I0 VS
A18
P533E4A
Two stages are available. Stage 1 is based on the earth/ground fault overcurrent
stage I0>>> and stage 2 is based on the earth/ground fault overcurrent stage
I0>>>>. Normally, stage 1 is applied as the trip stage and stage 2 is applied as the
alarm stage. As well as current input I0, the phase current IL1 is used to polarise
the capacitor bank unbalance current for the standing unbalance current
compensation and the faulty phase location.
Compensation method
The unbalance current under normal conditions can be compensated to get better
protection sensitivity. There are two compensation modes, Normal mode and
Location mode. Stage 1 can only select Normal mode. Stage 2 can select Normal
mode or Location mode.
Normal mode
The compensation is performed manually during commissioning. Using eSetup
Easergy Pro (as shown in Get the standing unbalance current via eSetup Easergy
Pro, page 292) or relay HMI, the relay can get the standing unbalance current
vector (here, IL1 is the angle reference) and record the magnitude and angle. For
flexible compensation purpose, the magnitude of the standing unbalance current
to be compensated is user settable under Normal Mode (setting SetBal), while the
angle of the standing unbalance current is not settable, fixed as the recorded
angle during commissioning.
Figure 229 - Get the standing unbalance current via eSetup Easergy Pro
Mag(I 0compensated)
IL1 Compensation value: > Start
&
I0 I0compensate = I0 - I0cmp Angle(I 0 ) - Angle(IL1 ) Register
Recorded & event
I0 angle
I0csh
Trip
Location mode
As in the Normal mode, the initial standing unbalance current vector (magnitude,
angle referred to IL1) can be recorded during commissioning. The magnitude of the
standing unbalance current to be compensated is not user settable, but the
automatic compensation feature is provided. In Location Mode the branch of each
faulty element can be estimated and thus improve the fault finding and
maintainability of the capacitor bank.
Sensitive Setting
The stage I0>>>> Pick up value should be set based on the calculated unbalance
current change of one faulty element. The calculation can use the following
formula:
UL-N UL-N
-1 -1
(2· π·f·C1) (2·π·f·C2)
3I0 = 3 P533E6A
Figure 231 - How a failure in different branches of the bank affects the I0
measurement
Easergy P5 H I
A B G C
F D
E
P533E7A
Automatic Compensation
The operation time setting for stage I0>>>> specifies how long the relay must wait
until it is certain that there is a faulty element in the bank. After this time has
elapsed, the corresponding counter will contain the number of faults. If none of the
six counters reach the setting Max Allowed Faults, the stage I0>>>> makes a new
compensation automatically, and the compensated unbalance current for this
stage is now zero. The I0>>>> stage will reset and be sensitive to a new faulty
element. Note the counters are not reset by this action and will continue to
accumulate any further faulty elements. As shown in Automatic compensation
under location mode, page 294, the current vector A is the initial recorded
standing unbalance current and the current vector B is the unbalance current with
the faulty capacitor elements. The new compensation current is “vector B – vector
A”. If one of the six counters reach the setting Max Allowed Faults, stage I0>>>>
will operate and the compensation current vector is recovered to the initial
recorded standing unbalance current vector A.
Note, the automatic compensation does not affect the measured unbalance
current of stage I0>>>.
90
I0
A
180 0
B
270 P533E8A
Mag(I0compensated)
IL1 > Start
I0 - “I0cmp” &
I0 Recorded I0 Register
& event
I0csh
Counter > Trip
calculation
Block Register
& event
Characteristics
Table 71 - Settings and characteristics of the capacitor bank unbalance
protection stage (ANSI 51C)
Settings/characteristics Values
(description/label)
I0 input/Input
Options I0 , I0Calc
Pick-up setting/I0>>>>
Resolution 0.01In
Accuracy ±3% or ±0.002In for I0 measured with standard EF CT;
±3% or ±0.005In for I0 measured with CSH;
Operation delay/t>>>>
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Compensation Mode
Resolution 0.01In
Max Allowed Faults (only available under Location Compensation Mode)
Setting range 1 - 10
Characteristic times
Start time < 40 ms/35 ms 40
Overshoot time < 40 ms
Disengaging time < 95 ms/110 ms 40
Setting group
Number 4
40. The 2nd value is only for high speed high break digital outputs.
Operations
Standard dependent operation delay, page 183). The other stages have definite
time operation characteristic. By using the definite delay type and setting the delay
to its minimum, an instantaneous (ANSI 50N) operation is obtained.
Using the directional earth/ground fault overcurrent stages in undirectional mode,
three more stages with dependent operate time are available for undirectional
earth/ground fault overcurrent protection.
For the very sensitive earth/ground fault overcurrent protection function (ANSI
50G/51G), there are three protection stages: I0’>, I0’>>, I0’>>>.
Block diagram
Figure 235 - Block diagram of the earth/ground fault overcurrent protection
stages I0>, I0>> and I0’>, I0’>>
I0 / I0’ >
I0calc & Start
Register
& event
Block
Trip
& Register
InrushStat & event
NOTE:
The Reset time setting in the above figure (with * mark) is only used in the
protection stage I0> or I0’>.
I0 / I0’ >
& Start
I0calc
Register
& event
Block
InrushStat Trip
&
I0 >
& Start
& Register
event
Block
Trip
t
& Register
event
Characteristics
Table 72 - Settings and characteristics of the earth/ground fault overcurrent protection functions (ANSI
50N/51N and ANSI 50G/51G)
I0 input/Input
Setting range (I0> ...) For delay type DT: 0.02In0 - 10.00In0 for I0 0.05In0 - 10.00In0
0.02In0 - 10.00In0 for I0 measured with standard EF measured with standard
CT; EF CT;
0.05In0 - 10.00In0 for I0 measured with CSH; 0.05In0 - 10.00In0 for I0
0.05In - 20.00In for I0 calculated measured with CSH;
0.05In - 20.00In for I0
For delay type IDMT: calculated
0.02In0 - 5.00In0 for I0 measured with standard EF CT;
0.05In0 - 5.00In0 for I0 measured with CSH;
0.05In - 5.00In for I0 calculated
Setting range (I0'> ...) 0.002In0 - 1.000In0 for I0' measured with very sensitive EF CT -
Resolution 0.01 s
Accuracy ± 1% or ± 20 ms
Inv. time coefficient k/k> 0.05 - 20.0 for DT, IEC, RI; -
0.50 - 20.0 for RXIDG, IEEE and IEEE2;
Accuracy ± 5% or ± 20 ms -
Reset type -
Reset time -
Resolution 0.01 s -
Table 72 - Settings and characteristics of the earth/ground fault overcurrent protection functions (ANSI
50N/51N and ANSI 50G/51G) (Continued)
Resolution 0.01 s -
SOL Inv. time coefficient 0.05 - 20.0 for DT, IEC, RI; -
K/SOLK> 0.50 - 20.0 for RXIDG, IEEE and IEEE2.
Resolution 0.01 s -
CLP Inv. time coefficient 0.05 - 20.0 for IEC and RI; -
K/CLPk> 0.50 - 20.0 for RXIDG, IEEE and IEEE2.
Network grounding -
Resolution 1% -
42. Common settings for setting group 1, 2, 3, 4 (see “Faulty phase detection during earth/ground fault”).
Table 72 - Settings and characteristics of the earth/ground fault overcurrent protection functions (ANSI
50N/51N and ANSI 50G/51G) (Continued)
Characteristic times
Start time < 30 ms/25 ms at 2 x I0 pick-up value 43
Number 4
NOTE: For the earth/ground fault overcurrent stage I0>>>>>, the Selective
Overcurrent Logic (SOL), Cold Load Pickup (CLP), and Inrush detection
features are not provided.
Phase recognition
A neutral voltage displacement has been detected.
A faulted phase or phases are detected in the two-stage system.
1. Use delta principle to detect the faulty phase/phases.
2. Configuration of the faulty phase with neutral current angle comparison to the
suspected faulted phase.
For an ideal, grounded network, when there is a forward earth/ground fault in
phase L1, its current increases, creating a calculated or measured zero sequence
current with a phase angle of 0 degrees. If there is a reverse earth/ground fault in
phase L1, its current decreases creating a calculated or measured zero sequence
current with a phase angle of 180 degrees.
When there is a forward earth/ground fault in phase L2, its current increases
creating a calculated or measured zero sequence current with a phase angle of
-120 degrees. If there is a reverse earth/ground fault in phase L2, its current
decreases creating a calculated or measured zero sequence current with a phase
angle of 60 degrees. When there is a forward earth/ground fault in phase L3, its
current increases creating a calculated or measured zero sequence current with a
phase angle of 120 degrees. If there is a reverse earth/ground fault in phase L3 its
current degreases creating a calculated or measured zero sequence current with
a phase angle of -60 degrees.
For a compensated network, the stability of the protection depends on the network
compensation degree. So for compensated networks, this feature can be turned
off to avoid confusion.
For high-impedance earthed/grounded networks, there is a drop-down menu in all
setting groups to choose between RES/CAP. RES is the default and it is for
earthed/grounded networks. When CAP is chosen, the I0 angle is corrected to an
inductive direction of 90 degrees.
43. The 2nd value is only for high speed high break digital outputs.
• FDW IL2
Phase L2 increases above the set limit and two other phases remain inside
the set (delta) limit. I0 current angle is +/- 60 degrees from phase L2’s phase
angle.
• FDW IL3
Phase L3 increases above the set limit and two other phases remain inside
the set (delta) limit. I0 current angle is +/- 60 degrees from phase L3’s phase
angle.
• FWD IL1 - IL2
Phase L1 and L2 increase above the set limit and phase L3 remains inside
the set (delta) limit. I0 current angle is between phase L1’s and phase L2’s
phase angles.
• FWD IL2 - IL3
Phase L2 and L3 increase above the set limit and phase L1 remains inside
the set (delta) limit. I0 current angle is between phase L2’s and phase L3’s
phase angles.
• FWD IL3 - IL1
Phase L3 and L1 increase above the set limit and phase L2 remains inside
the set (delta) limit. I0 current angle is between phase L3’s and phase L1’s
phase angles.
• FWD IL1 - IL2 - IL3
All three phase currents increase above the set delta limit.
• REV 1 (any one phase)
One phase decreases below the set delta limit and other two phases remain
inside the delta limit.
• REV 2 (any two phase)
Two phases decrease below the set delta limit and third phase remains inside
the delta limit.
• REV 3 (all three phases)
All three phase currents decrease below the set delta limit.
I L3 I L3
I L1
0° 0° 0° 0°
I0
I L2 I L2
I L1 I0
P533EEA
I L3 I L3 I0
IL 2
IL 1
0° 0° 0° 0°
IL 1
I0
IL 2
P533EFA
I L3
I L3 I0
I L1
0° 0° 0° 0°
I L1
I0
I L2 I L2
P533EGA
Fault recording
When a faulty phase is recognised, it is recorded in the earth/ground fault current
protection fault log (also in the event list and alarm screen). This faulted phase
and direction recording function have a tick box in eSetup Easergy Pro for
enabling/disabling in the protection stage settings.
Reset delay
The U> stage has a settable reset delay that enables the detection of intermittent
faults. This means that the time counter of the protection function does not reset
immediately after the fault is cleared, but resets after the release delay has
elapsed. If the fault appears again before the release delay time has elapsed, the
delay counter continues from the previous value. This means that the function
eventually trips if faults are occurring often enough.
Configurable hysteresis
The dead band is 3% by default. This means that an overvoltage fault is regarded
as a fault until the voltage drops below 97% of the start setting. In a sensitive
alarm application, a smaller hysteresis is needed. For example, if the start setting
is about only 2% above the normal voltage level, the hysteresis must be less than
2%. Otherwise, the stage does not release after fault.
Block diagram
Figure 241 - Block diagram of the three-phase overvoltage stages U>, U>>
and U>>>
U12
U23 MAX
U31
& Start
& Register
event
Blocking
Trip
t
& Register
event
Characteristics
Table 73 - Settings and characteristics of the overvoltage protection
function (ANSI 59)
Resolution 1%Un
Accuracy ±3%
Resolution 0.01 s
Accuracy ±1% or ±30 ms ±1% or ±20 ms
Resolution 0.01 s -
Hysteresis/Hyster 44
Resolution 0.1%
Accuracy ± 2%
Characteristic times
Start time < 50 ms/45 ms 45 < 40 ms/35 ms 45
Disengaging time < 60 ms/75 ms 45
Number 4
where:
Uns is the rated secondary phase voltage.
• When the voltage measurement mode contains "+U0": The neutral
displacement voltage is measured only with voltage transformer(s), for
example using a broken delta connection. The setting values are relative to
the configured VT0 secondary voltage (line-to-line voltage).
where:
Unos is the rated secondary residual voltage.
V4 is the fourth voltage input channel of Easergy P5 protection relay.
NOTE: When the voltage measuring mode is LL/LLy, U0 is zero and therefore
the neutral voltage displacement protection function of all stages will not
operate.
Block diagram
Figure 242 - Block diagram of the neutral voltage displacement protection
function
Start
U0
Register
event
Blocking
Trip
Register
event
Characteristics
Table 74 - Settings and characteristics of the neutral voltage displacement
protection function
Pick-up value/U0>
Resolution 1%
Operation delay/t>
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Characteristic times
Start time < 50 ms/45 ms 46 < 40 ms/35 ms 46
Overshoot time < 45 ms
Disengaging time < 50 ms/65 ms 46 < 55 ms/40 ms 46
Setting groups
Number 4
46. The 2nd value is only for high speed high break digital outputs.
15
Uc = X c
UcLN ∑ In
n =1
h
Xc = 1
2π f C set
P533EJA where P533EKA
Uc = Amplitude of a pure fundamental frequency sine wave voltage, whose peak value is
equal to the maximum possible peak value of the actual voltage (including harmonics)
over a
Y-coupled capacitor.
n= Order number of harmonic. n = 1 for the fundamental frequency component. n = 2 for 2nd
harmonic etc.
Ih = nth harmonic of the measured phase current. h = 1 - 15.
Above equation gives the maximum possible voltage, while the actual voltage
depends on the phase angles of the involved harmonics. The protection is
sensitive to the highest voltage of the three line-to-neutral voltages. Whenever this
value exceeds the start setting of a particular stage, this stage starts and issues a
start signal. If the fault situation is present longer than the definite operation delay
setting, a trip signal is issued.
2
Q n = 2π fn UcLN Cset
P533ELA
n n n
set
Mvar P533EMA
12
12
P533ENA
Xc = 1
2π f C set P533EKA
The pure fundamental voltage Uc having a peak value equal to the highest
possible voltage with similar harmonic content as the measured reactive capacitor
currents is: Ucp1 = 31.806*(181/1 + 3.62/2 + 12.67/3 + 9.05/5) = 6006 V
and in per-unit values: Ucp1 = 6006/8000 = 0.75Un
15
Uc = X c
UcLN ∑ In
n =1
h
P533EJA
The same calculation is executed for phases L2 and L3. The highest of the three
values is compared to the start setting.
Block diagram
Figure 245 - Block diagram of the capacitor overvoltage protection function
(ANSI 59C)
IL1
Uc
IL2
Uc
MAX > & Start
IL3
Uc
f
& Register
event
Blocking
Trip
t
& Register
event
Characteristics
Table 75 - Settings and characteristics of the capacitor overvoltage
protection Uc>
Settings/characteristics Values
(description/label)
Pick-up value/Uc>
Resolution 0.01
Accuracy ±3%
Resolution 0.01 μF
Resolution 1V
Operation delay/t> (DT)
Resolution 0.5 s
Accuracy < 1.5 s
Characteristic times
Start time < 1.5 s
Disengaging time < 1.5 s
Setting group
Number 4
Block diagram
Figure 246 - Block diagram of the directional phase overcurrent protection function (stage Iφ> and
Iφ>>)
DirMode
Block Trip
& Register
event
InrushStat &
& Select
CLPStat setting
&
Mode Enable Enable Enable Iφ> CLPIφ> t> CLPt> SOLt> DT/IDMT Reset IDMT k> CLPk> SOLk> Enable
Inrush SOL CLP time characteristics events
P533OOA
Figure 247 - Block diagram of the directional phase overcurrent protection function (stage Iφ>>> and
Iφ>>>>)
DirMode
Block Trip
& Register
event
InrushStat &
& Select
CLPStat
& setting
Operation
Operate time
Stages Iφ>and Iφ>> can be configured for definite time or dependent time
characteristic. Stages Iφ>>> and Iφ>>>> have definite time (DT) operation delay.
The device shows a scalable graph of the configured delay on the local panel
display.
Examples
Figure 248 - Example of the directional overcurrent function characteristic
Im +90°
2°
ind. +cap.
SET
VA LUE
0° +res.
res. I LOAD Re
TRIP AREA
BASE ANGLE = °
I FAULT
cap. +ind.
90° P533ERA
Figure 249 - Bi-directional application with two stages Iφ> and Iφ>>
+90°
ind. +cap.
4°
I φ >> TRIP AREA
SET SET
VA LUE VA LUE 0°
res. +res.
BASE ANGLE = °
BASE ANGLE = 18 °
cap. +ind.
P533ESA
When any of the three phase currents exceeds the setting value and, in directional
mode, the phase angle including the base angle is within the active ±88° wide
sector, this stage starts and issues a start signal. If the fault situation is present
longer than the operate time setting, a trip signal is issued.
NOTE: When using directional overcurrent protection in low impedance
earthed/grounded networks, the device has to be connected to line-to- neutral
voltages instead of line-to-line voltages, therefore the voltage measurement
mode has to be "3LN".
Characteristics
Table 76 - Setting and characteristics of directional phase overcurrent
protection function (ANSI 67)
Resolution 0.01In
Accuracy ±3% or ±0.005In
Direction mode/Mode
Options Dir; Nodir; Dir + Backup
Angle offset/Offset
Resolution 1°
Accuracy ±2° (U > 5 V) or ±10° (U = 0.1 - 5.0 V)
Resolution 0.01 s
Reset type -
Resolution 0.01 s -
Resolution 0.01s
SOL Inv. time coefficient/ 0.05 - 20.0 for DT, IEC, RI; -
SOLk> 0.50 - 20.0 for RXIDG, IEEE
and IEEE2.
Accuracy ±1% or ±20 ms, definite time; ±1% or ±20 ms
±5% or ±30 ms, IDMT time
Resolution 0.01In
Accuracy ±3% or ± 0.005In
Resolution 0.01 s
CLP Inv. time coefficient/ 0.05 - 20.0 for DT, IEC, RI; -
CLPk> 0.50 - 20.0 for RXIDG, IEEE
and IEEE2.
Accuracy ±1% or ±20 ms, definite time; ±1% or ±20 ms
±5% or ±30 ms, IDMT time.
Characteristic times
Start time < 45 ms/40 ms at 2 x Iφ pick-up value 47
< 60 ms/55 ms at 1.2 x Iφ pick-up value 47
Number 4
47. The 2nd value is only for high speed high break digital outputs.
Polarisation
The neutral displacement voltage used for polarisation is either directly measured
by VT input U0 of the Easergy P5 protection relay or, alternatively, internally
calculated from the three phase voltages depending on the selected voltage
measurement mode.
• 3LN, 3LN/LLy and 3LN/LNy:
The residual voltage is calculated from the phase voltages and therefore no
separate residual voltage transformers are needed. The setting values are
relative to the configured voltage transformer (VT).
• 3LN+U0, 2LL+U0, and 2LL+Uₒ+LLy:
The residual voltage is measured with dedicated voltage transformer for
example using a broken delta connection. The setting values are relative to
the VT0 secondary voltage defined in the configuration.
Block diagram
Figure 250 - Block diagram of the directional earth/ground fault overcurrent protection function
operating in ResCap mode (ANSI 67N)
I0
I0calc
I0 ’ I0 cos(AngleDiff)
*
I0csh DirMode
& ≥1
OR
> Start
&
Res
Cap & ≥1 I0 sin(AngleDiff)
*
DI
& Register
event
&
DI
≥ Trip
U0
>
U0calc
Block
& Register
event
Figure 251 - Block diagram of the directional earth/ground fault overcurrent protection function
operating in Sector mode (ANSI 67N)
DirMode
&
I0
& Start
I0calc
I0’
I0csh -AngSec < AngleDiff < AngSector
U0 & Register
event
U0calc
≥ Trip
>
>
& Register
event
Block
NOTE: The AngleDiff in the two figures above is calculated using this formula:
AngleDiff = (Angle(I0) - Angle(U0)) - AngleOffset
Figure 252 - Block diagram of the directional earth/ground fault overcurrent protection function
operating in Undir mode (ANSI 67N)
DirMode
& Start
I0
I0calc
I 0’ >
& Register
I0csh event
Block
≥ Trip
& Register
event
k>
I0φ> Mode = Undir DT / IDMT t> IDMT Enable events
characteristics P533EVA
+90°
I0sin ᵠ >
CAP
I0 ᵠ >
I0
RES
ᵠ
0°
I0cos ᵠ >
-U0
I0 ᵠ >
P533EWA
TRIP AREA
I0
+152° +32°
70°
I0ᵠ > 120°
0° 0°
70° -U0 120° I0ᵠ > -U0
-15°
I0 TRIP AREA
-85° -88°
P533EXA
The drawn I0 phasor in both figures is inside the trip area. The angle offset and
half sector size are user’s parameters.
Characteristics
Table 77 - Setting and characteristics of the directional earth/ground fault
overcurrent protection function (ANSI 67N)
I0 input/Input
Direction mode/Mode
Options ResCap, Sector, NoDir
Options Selecting Res, Cap, one digital input (DI), or one virtual input (VI).
Resolution 1%Un0
Angle offset/Offset
Resolution 0.02
Accuracy ±1% or ±50 ms
Reset type
Resolution 0.02 s
Characteristic times
Start time < 65 ms/60 ms < 55 ms/50 ms
at 2 x I0φ pick-up value 50 at 2 x I0φ pick-up value 50
Number 4
t (ms)
P533EYA
Block diagram
Figure 256 - Block diagram of the directional transient intermittent earth/ground fault stage I0INT>
I0 samples
I0 Start
I0 peak
TRANSIENT
P ALGORITHM & Register
event
I0 fundamental DIV
freq. amplitude R
U0 U0 samples COUNTER
U0 n Trip
CLEAR
U0
& Trig & Register
event
Block TOF
Operation
Direction calculation
The function is sensitive to the instantaneous sampled values of the earth/ground
fault overcurrent and neutral voltage displacement voltage. The selected voltage
measurement mode has to include a direct U0 measurement with a voltage
transformer.
NOTE: Connect the U0 signal according to the connection diagram to achieve
correct polarisation.
Auto reclosing
The start signal of any I0φ> stage initiating auto reclosing (AR) can be used to
block the I0INT> stage to avoid the I0INT> stage with a long intermittent setting to
interfere with the AR cycle in the middle of discrimination time.
Usually the I0INT> stage itself is not used to initiate any AR. For transient faults, the
AR does not help because the fault phenomena itself already includes a repetitive
unsuccessful self-extinguishing.
Figure 257 - Set peak amount condition is satisfied and operate time elapses
within intermittent time setting. Stage issues a trip.
U0
I0
TRIP
Setting for minimum number of peaks = 2
Time (s)
P533F0A
Figure 258 - Peak amount condition is not satisfied when operation delay
elapses but last required peak occurs during intermittent time. Stage then
issues instant trip.
U0
I0
Time (s)
P533F2A
Figure 259 - Peak amount condition is satisfied but intermittent time elapses
before operate time. Stage is reset.
U0
I0
Time (s)
P533F1A
Characteristics
Table 78 - Settings and characteristics of the transient intermittent earth/
ground fault protection stage I0INT>
Settings/characteristics Values
(description/label)
I0 input/Input
Direction mode/Mode
Options Forward; Reverse
I0 peak value/I0Peak
U0 Pick-up/U0>
Resolution 1%Un0
Accuracy ±3%
Setting range 1 – 20
Resolution 1
Operation delay/t>
Resolution 0.02 s
Accuracy ±1% or ±20 ms
Resolution 0.01 s
Intermittent time/Intmt time 51
Resolution 0.01 s
Characteristic times
Start time < 50 ms/45 ms maximum 52
Disengaging time < 65 ms
Setting group
Number 4
Block diagram
Figure 260 - Block diagram of the magnetising inrush detection stage Ih5>
I L1 H5
I L2
I L3
H5 MAX > & Start
H5
Block
& Register
event
Trip
t
& Register
event
Characteristics
Table 79 - Setting and characteristics of the over excitation detection
function (ANSI 68H5)
Setting/characteristics Values
(description/label)
Pick-up value/Ih5>
Resolution 1%
Operation delay/t>
Resolution 0.01 s
Accuracy ±1% or 30 ms
Characteristic times
Start time < 55 ms/50 ms 53
Disengaging time < 85 ms/70 ms 53
Setting group
Number 1
53. The 2nd value is only for high speed high break digital outputs.
Purpose
Typically protection functions detect the fault and trigger the AR function. After
tripping the circuit breaker, the AR function can reclose the CB. Normally, the first
reclose (or shot) is so short in time that users cannot notice anything. However,
the fault is cleared and the feeder will continue in normal service.
Auto-recloser principle
Even though the basic principle of AR is very simple, there are a lot of different
timers and parameters that have to be set.
The Easergy P5 protection relays provide auto-reclosing with up to five shots. A
shot consists of open time (so called “dead” time) and closed time (so called
“burning” time or discrimination time). A high-speed shot means that the dead time
is less than one second. The time-delayed shot means longer dead times up to
two to three minutes.
There are four AR lines. A line means an initialisation signal for AR. Normally, start
or trip signals of protection functions are used to initiate an AR sequence. Each
AR line has a priority. AR1 has the highest and AR4 has the lowest priority. This
means that if two lines are initiated at the same time, AR follows only the highest
priority line. A very typical configuration of the lines is that the instantaneous
overcurrent stage initiates the AR1 line, time-delayed overcurrent stage the AR2
line and earth/ground fault protection will use lines AR3 and AR4.
I>t AR-request) CB CB
I>>s I>s
DirectTrip 0...300 s Reclaim time
0...300 s
Shot 1 AR1 In use succeeded
0...300 s 0...300 s 0...300 s 0...300 s
AR2 In use Move back
to shot 1
Shot
3...5
P533F4A
The AR matrix above defines which signals (the start and trip signals from
protection stages or digital input) are forwarded to the AR function. In the AR
function, the AR signals can be configured to initiate the reclose sequence. Each
shot from 1 to 5 has its own enabled/disabled flag. If more than one AR signal
activates at the same time, AR1 has highest priority and AR2 the lowest. Each AR
signal has an independent start delay for the shot 1. If a higher priority AR signal
activates during the start delay, the start delay setting will be changed to that of
the highest priority AR signal.
After the start delay, the CB is opened if it is still closed (i.e. if no trip has been
issued from another protection function in the mean time). When the CB opens, a
dead time timer is started. Each shot from 1 to 5 has its own dead time setting. If
the reclaim time elapses with no further starting or tripping, the AR sequence is
successfully executed and the AR function moves to ready state and waits for a
new AR request in shot 1.
It is recommended to configure the protection stage’s start signal to initiate the AR
function. A trip signal from the protection stage can be used as a backup. If AR
does not issue the open command, the protection trip signal still operates the CB.
The delay setting of the protection stage should be longer than the AR start delay,
CB operation time and protection reset time.
Operation
Manual closing
When CB is closed manually with the local panel, by remote, or with digital inputs,
the reclaim state is activated. Within the reclaim time, all AR requests are rejected.
The protection stages take care of tripping when they are connected to a trip relay
in the output matrix.
Manual opening
Manual CB open command during AR sequence stops the sequence and leaves
the CB open.
AR shots blocking
Each AR shot can be blocked with a digital input, virtual input or virtual output. The
blocking input is selected with the Block setting. When the selected input is active,
the shot is blocked. A blocked shot is treated like it does not exist and AR
sequence skips it. If the last shot in use is blocked, any AR request during
reclaiming of the previous shot causes the final tripping.
Starting AR sequence
Each AR request line has its own start delay timer. That AR line that is selected
depends on which starting delay elapses first. If more than one delay elapses at
the same time, the AR request of the highest priority is selected. AR1 has the
highest priority and AR4 has the lowest priority. First shot is selected according to
the AR request. Next AR opens the CB and starts counting dead time.
DI to block AR setting
This setting is useful with an external synchro-check device. This setting only
affects re-closing the CB. Re-closing can be blocked with a digital input, virtual
input or virtual output. When the blocking input is active, CB is not closed until the
blocking input becomes inactive again. When blocking becomes inactive, the CB
is immediately closed providing the close command is still active.
Figure 262 - Example sequence of two shots (after shot 2 the fault is cleared)
I> setting
Current
Open command
CB
Close command
CB
CBclose
state
CBopen
state
P533F5A
1. The current exceeds the I> setting; the start delay from shot 1 starts.
2. After the start delay, an OpenCB relay output is operated.
3. The CB opens. The dead time from shot 1 starts, and the OpenCB relay
output resets.
4. The dead time from shot 1 elapses; a CloseCB output is operated.
5. The CB closes. The CloseCB output resets, and the discrimination time
from shot 1 starts. The current is again above the I> setting.
6. The discrimination time from the shot 1 elapses; the OpenCB relay output
is operated.
7. The CB opens. The dead time from shot 2 starts, and the OpenCB relay
output resets.
8. The dead time from shot 2 runs out; the CloseCB output is operated.
9. The CB closes. The CloseCB output resets, and the discrimination time
from shot 2 starts. The current is now below I> setting.
10. Reclaim time starts. After the reclaim time elapsed the AR sequence is
successfully executed. The AR function moves to wait for a new AR
request in shot 1.
Characteristics
Table 80 - Setting and characteristics of the auto-recloser protection
function (ANSI 79)
Setting/characteristics Values
(description/label)
Enable Auto-Recloser/AR
Options On; Off
DI for ARon/ARoff/AR DI
Options Selection of one digital input (DI), one virtual input (VI), one virtual
output (VO), or one function key.
Breaker 1 object/CB1
Breaker 2 object/CB2
Auto CB selection/AutoCBSel
Options Disable; Enable
Options Selection of one digital input (DI), one virtual input (VI), one virtual
output (VO), or one function key.
Dead time
Setting range 0.01 s – 1,200 s
Resolution 0.01 s
Discrimination time
Setting range 0.02 s – 300 s
Resolution 0.01 s
Reclaim time/ReclT
Setting range 0.02 s - 3000 s
Resolution 0.01
Block by external synchro-check/ExtSync
Options Selection of one digital input (DI), one virtual input (VI), one virtual
output (VO), or one function key.
Block diagram
Figure 263 - Block diagram of the over and under frequency protection
(ANSI 81)
f >
& Start
& Register
event
>
< Trip
< t
Block &
& Register
event
U12
U23 MAX <
U31
Characteristics
Table 81 - Setting and characteristics of the over and under frequency
protection stages f>< and f><><
Setting/characteristics Values
(description/label)
Pick-up value/f><
Operation delay/t><
Resolution 0.02 s
Accuracy ±1% or ±20 ms
Accuracy ±2%
Characteristic times
Start time < 100 ms / 95 ms 55, typically 80 ms
Number 4
Block diagram
Figure 264 - Block diagram of the underfrequency protection function (ANSI
81U)
f <
& Start
& Register
event
Block
t Trip
U12
U23 MAX < Register
&
U31 event
Characteristics
Table 82 - Setting and characteristics of the underfrequency protection
stages f<, f<<
Setting/characteristics Values
(description/label)
Pick-up value/f<
Resolution 0.01 Hz
Accuracy ±0.01 Hz
Operation delay/t<
Resolution 0.01 s
Accuracy ±1% or ±20 ms
Resolution 1%
Accuracy ±2%
Characteristic times
Start time < 100ms / 95 ms 57, typically 80 ms
Number 4
Block diagram
Figure 265 - ROCOF function structure overview
df/dt >
≥1
<
Start
& Register
event
U12
U23 MAX < &
t
Operate
U31
& Register
Block event
Characteristics
Table 83 - Setting and characteristics of the rate of change of frequency
protection stages df/dt> and df/dt>>
Settings/characteristics Values
(description/label)
Direction of change/Mode
Pick-up value/df/dt>
Accuracy ±2%
Operation delay/t>
Resolution 0.01 s
Accuracy ±2% ± 30 ms
Characteristic times
Start time < 135 ms / 130 ms 59 for df/dt > 0.1 Hz/s
< 170 ms / 165 ms 59 for df/dt = 0.1 Hz/s
Disengaging time < 210 ms / 225 ms 59
Number 4
Latch function
This feature can also be programmed for outputs in the Output Matrix setting view.
Any protection stage start or trip, digital input, logic output, alarm and GOOSE
signal connected to the following outputs can be latched when required:
• Output contacts DOs
• LEDs on the local panel
• Virtual outputs VO1- VO20
Figure 267 - I> trip and I>> trip signals locked out with DO (B) and DO (C),
respectively
NOTE: The latched signal is identified with a dot and circle in the matrix signal
line crossing.
The lockout can be released through the local panel with the key, or via the
eSetup Easergy Pro. See Releasing latches, page 381.
Available signals
Table 84 - Available signals to be supervised by the programmable stages
Signals Description
U12y Line-to-line reference voltage taken from other side of the CB for
synchro-check scheme
Measurement functions
Primary, secondary and per unit scaling
All measurement values are shown as primary values although the Easergy P5
protection relay is connected with its analogue voltage and current inputs to
secondary signals. Some measurement values are shown as relative values in per
unit or percent. Almost all pick-up setting values are using relative scaling.
The scaling is done using the rated values of VTs and CTs, or LPVTs and LPCTs
depending on the selected model order option.
Scaling settings
The scaling settings define the characteristics of measurement transformers
connected to the Easergy P5 protection relay and determine the correct
adaptation and performance of the metering and protection functions.
They are accessed via:
• eSetup Easergy Pro or web HMI Scaling view in General menu
• on local panel in the CT- VT view of the General menu
The scaling parameters are listed in List of scaling parameters, page 344.
Un0p Rated primary residual voltage of VT Same setting as the rated primary
transformer voltage of transformer
Voltage Usage of voltage inputs for phase VT 3LN + U0, 3LN, 2LL + U0, 3LN /
measurement mode voltage, residual voltage or other LNy, 3LN / LLy, 2LL + U0 + LLy,
additional voltage LL / LLy
Current values
Secondary
-> Primary I np I nop Vsec
I pri = Isec ⋅ I0pri = I0sec ⋅ I pri = x Ipr
I ns I nos k x 22.5 mV
Primary
I ns I0sec = I0pri ⋅ I nos
-> Secondary
I pri
Isec = I pri ⋅ Vsec = I × k × 22.5 mV
I np Inop pr
For residual current measured by CSH core balance CTs, only primary values are
considered. CTpri is equal at 2A or 20A according to the connection on the
protection relay.
Examples
1. Secondary to primary (CT)
CT = 500 A / 5 A
If the current on Easergy P5 input is 4 A, then the corresponding primary
current is Ipri = 4 x 500 / 5 = 400 A.
2. Secondary to primary (LPCT)
LPCT = 100 A / 22.5 mV
If the voltage on the LPCT input is 30 mV, then the corresponding primary
current is Ipri = 30 / 22.5 x 100 = 136 A, whatever is K.
With K = 0.25, Vsec corresponds to 136 / (100 x 0.25) = 5.44 In.
3. Primary to secondary (CT)
CT = 500 A / 5 A
If Easergy P5 displays Ipri = 100 A, then the injected current is
Isec = 100 x 5 / 500 = 1 A.
4. Primary to secondary (LPCT)
LPCT = 100 A / 22.5 mV
If Easergy P5 displays Ipri = 640 A, then the injected current is
Vsec = 640 / 100 x 22.5 = 144 mV, whatever is K.
With K = 3.2, Vsec corresponds to 640 / (100 x 3.2) = 2 In.
I sec I sec
I pu = Ipu = Vsec / ( k x 22.5) I pu = -
Ins Ins
Amp -> Per unit
Ipri = Ipu . Inp Ipri = Ipu x k x Ipr Ipri = Ipu . Inp Ipri = Ipu . Inp
Examples
1. Secondary to per unit for phase current (CT)
CT = 750 A / 5 A
If the current injected is 7 A, then the per unit current is
Ipu = 7 / 5 = 1.4 In = 140%.
2. Per unit to secondary for phase current (CT)
CT = 750 A / 5 A
If the protection setting is 2In = 200%, then the corresponding secondary
current is Isec = 2 x 5 = 10 A.
3. Secondary to per unit for phase current (LPCT)
LPCT = 100 A / 22.5 mV with K = 3.2
If the Easergy P5 protection relay displays Ipri = 640 A, then the injected
voltage is
Vsec corresponds to 640 / (100 x 3.2) = 2 In.
4. Primary to per unit for phase current (LPCT)
LPCT rated current = 100 A with LPCT Current factor k = 2 (45 mV at the
secondary)
If the primary current is 150 A (33.75 mV at the secondary), then the per unit
current (voltage) is Ipu = 150/200 = 33.75/45 = 0.75 In.
5. Per unit to primary and secondary value (LPCT)
LPCT rated current = 100 A with LPCT Current factor = 10
If protection setting is 1.5 In, the corresponding secondary voltage is
Vsec = 1.5 x 10 x 22.5 = 337.5 mV,
and the corresponding primary current is
Ipri = 1.5 x 100 x 10 = 1.5 kA.
6. Secondary to per unit for earth/ground fault current (CT)
CT0 = 750 A / 1 A
If for standard and very sensitive earth/ground fault inputs or phase current
input (3 CT calculation) the current is 30 mA, then the per unit current is
Ipu = 0.03 / 1 = 0.03In0.
7. Per unit to secondary for earth/ground fault current (CT)
CT0 = 50 A / 1 A
If for standard and very sensitive earth/ground fault inputs or phase current
input (3 CT calculation) the protection setting is 10%In0, then the
corresponding Isec = 0.1 x 1 = 100 mA.
Voltage values
NOTE: U1 and U2 are respectively the positive and the negative sequence
voltages. U0 is the residual voltage (zero-sequence voltage x3).
LL LN U1 U2 U0
3LN Upr/√3 3.25V/√3 Unp/√3 Unp Unp/√3 Unp/√3 Unp/√3 Unp/√3
Examples
1. Secondary to primary
Line-to-line voltage measurement mode (VT)
VT = 12000 V / 110 V
If voltage connected to the Easergy P5 input V1, V2 or V3 = 100 V, then
primary voltage is Upri = 100 x 12000 / 110 = 10909 V.
Line-to-neutral voltage measurement mode (VT)
VT = 12000 V / 110 V
If the three phase symmetric voltage magnitude is 60 V, then the primary
voltage is Upri = √3 x 60 x 12000 / 110 = 11336 V.
2. Primary to secondary
Line-to-line voltage measurement mode (VT)
VT = 12000 V / 110 V
If the Easergy P5 protection relay displays Upri = 10910 V, then the secondary
voltage is Usec = 10910 x 110 / 12000 = 100 V.
Line-to-neutral voltage measurement mode (VT)
VT = 12000 V / 110 V
If the Easergy P5 protection relay displays
U12 = U23 = U31 = 10910 V for a symmetric voltage system, then the
secondary voltages at V1, V2 and V3 are
Usec = 10910 / √3 x 110 / 12000 = 57.7 V.
3. Line-to-neutral voltage measurement mode (LPVT)
LPVT = 20 kV/3.25 V with k = 0.5
If the Easergy P5 protection relay displays
U12 = U23 = U31 = 11 kV for a symmetric voltage system, then the secondary
voltages V1, V2, and V3 are
Vsec = 11000 / 20000 x 3.25 / √3 = 1.032 V.
Upri
Upu =
k x Upr
Usec U U sec U
Voltage –> Per unit
Upu = = pri Upu = 3 ⋅ = 3 ⋅ pri
VTsec VTpri VTsec VTpri
Usec
Upu = x 3
k 3.25
x
VTpri
Upri = Upu ⋅ VTpri Upri = Upu ⋅ Upri = Upu x k x Upr
3
Examples
1. Secondary to per unit
Line-to-line voltage measurement mode
VT = 12000 V / 110 V
If the voltage input of V1 or V2 is 100 V, then the per unit voltage is
Upu = 100 / 110 = 1.00 pu = 91%.
Line-to-neutral voltage measurement mode
VT = 12000 V / 110 V
If the three symmetric line-to-neutral injected to the voltage inputs are 63.5 V,
then the per unit voltage is Upu = √3 x 63.5 / 110 = 1.00 pu = 100%.
2. Per unit to secondary
Line-to-line voltage measurement mode
VT = 12000 V /110 V
If the Easergy P5 protection relay displays 1.00 pu = 100%, then the
secondary voltage is Usec = 1.00 x 110 = 110 V.
Line-to-neutral voltage measurement mode
VT = 12000 V / 110 V
If the Easergy P5 protection relay displays 1.00 pu = 80%, then the three
symmetric line-to-neutral voltages injected to the inputs are
Usec = 0.8 x 110 / √3 = 50.8 V.
3. Per unit to secondary for voltage measurement with LPVT
LPVT = 20 kV / 3.25 V with k = 0.8
If the line-to-neutral voltage displayed is 0.5xUn, the secondary value injected
to the Easergy P5 protection relay is 0.5 x 0.8 x 3.25 / √3 = 0.75 V.
Upri 1
Upu = Upu = V1 + V2 + V3
Unop k Upr sec
Per unit
-> voltage
Usec = Upu ⋅ Unos V1 + V2 + V3 sec = Upu ⋅ Uns V1 + V2 + V3 sec
= Upr x k x 3.25
Examples
1. Secondary to per unit
Residual voltage measurement (VT)
U0sec = 110 V (this is a configuration value corresponding to U0 at full ground
fault.)
If the voltage connected to the device's input V3 is 22 V, then the per unit
voltage is Upu = 22 / 110 = 0.20 pu = 20%.
Residual voltage calculated (VT)
VT = 12000 V / 110 V
If the voltage connected to the relay's input V1 is 38.1 V, while V2 = V3 = 0,
then the per unit voltage is
Upu= (38.1 + 0 + 0) / ( √3 x 110) = 0.20 pu = 20%.
2. Per unit to secondary
Voltage measurement mode is "2LL + U0" (VT)
U0sec = 110 V (this is a configuration value corresponding to U0 at full earth/
ground fault.)
If the relay displays U0 = 20%, then the secondary voltage at input V3 is
Usec = 0.20 x 110 = 22 V.
3. Per unit to secondary
Residual voltage calculated (VT)
VT = 20 kV /110 V
If the Easergy P5 protection relay displays U0 = 20% and if V2 = V3 = 0, then
the secondary voltage at V1 is Usec = √3 x 0.2 x 110 = 38.1 V.
Residual voltage calculated (LPVT)
LPVT = 20 kV / √3 / 3.25 V / √3 with k = 1.5
If Easergy P5 protection relay displays 30% and V1 = V3 = 0, then the
secondary voltage of V2 is Usec = 0.3 x 1.5 x 3.25 / 1.732 = 0.844 V.
Reading of measurements
All measurement values can be read out via:
• Local panel: Measurements menu ( ) and on the Mimic screen if they were
configured with eSetup Easergy Pro
• eSetup Easergy Pro: Measurements menu
• Communication interface (if the used protocol provide this)
• EcoStruxure Power Device application
The refresh interval, on automatic cyclic updates, is less than 1 second typically.
Phase currents
Easergy P5 measures the fundamental and RMS values of phase current inputs
using 1A CTs, 5A CTs, or LPCTs:
Value Description
Fundamental value
IL1 Fundamental value of phase 1 current IL1
RMS value
IL1rms RMS value of phase 1 current IL1
The RMS current measurement takes into account harmonics up to the 15th. The
calculation is done as follows:
2 2 2
IRMS = If 1 + If 2 + ... +If 15 P533Z1A
Value Description
Magnitude
Units A
Resolution 1A
Accuracy ± 0.5% for measurement value of 1.0In;
± 1% for range 0.3In to 1.5In;
± 2% for range 0.1In to 0.3In
Phase angle 65
Resolution 0.1°
Accuracy 0.5° with IL > 0.1In
65. Phase angle can only be detected when current is over 100 mA.
Residual current
Easergy P5 protection relay measures the fundamental value of the residual
current connected to the standard earth/ground fault input (I0) or alternatively to
the very sensitive earth/ground fault input (I0').
The residual current is calculated by the vector sum of the 3 phase currents or
directly measured with a conventional CT or CSH core balance CT.
Characteristics Range
Units A
Resolution CSH: 0.01 A
1 A CT: 0.001 A
1A/5A CT: 0.01 A
Accuracy, I0 < 0.02In0: ± 2%
0.02In0 to 0.05In0: ± 1%
> 0.05In0: ± 0.5%
Accuracy, I0' < 0.002In0: ± 2%
0.002In0 to 0.005In0: ± 1%
> 0.005In0: ± 0.5%
Frequency
Easergy P5 protection relay determines the frequency based on the samples of an
available voltage or current signal. The frequency determination will be
automatically adapted to the availability and quality of the related signal inputs:
• Based on positive sequence voltage U1 or
• Based on any single line-to-line voltage or line-to-neutral voltage
• Based on currents when the voltage is not measured or under 15%Un.
The frequency is not measured if:
• The max of three line-to-line or line-to neutral voltage or positive sequence
voltage U1 is less than 15% of Un.
• The max of three currents or positive sequence current (I1) is less than
10%In
The following table provides an overview of the characteristics for frequency
measurement:
Table 96 - Characteristics for frequency measurement
Characteristics Range
Measurement range 10 Hz - 72 Hz
Units Hz
Resolution 0.001 Hz
Accuracy ± 0.01 Hz
Voltages
The Easergy P5 measures the fundamental and RMS values of line-to-line
voltages and line-to-neutral voltages.
Value Description
U12 Fundamental value of the line-to-line voltage between phase 1 and phase 2
U23 Fundamental value of the line-to-line voltage between phase 2 and phase 3
U31 Fundamental value of the line-to-line voltage between phase 3 and phase 1
U12rms RMS value of the line-to-line voltage between phase 1 and phase 2
U23rms RMS value of the line-to-line voltage between phase 2 and phase 3
U31rms RMS value of the line-to-line voltage between phase 3 and phase 1
These voltages are measured with the three analogue voltage inputs VL1, VL2 and
VL3.
A 4th analogue voltage input V4 is used to measure an additional line-to-line
voltage or line-to-neutral voltage, which is usually used as a reference voltage for
the synchronisation checking function.
Uy : fundamental value of the additional line-to-line voltage
Uyrms : RMS value of the additional line-to-line voltage calculated as follows:
2 2 2
VRMS = Vf 1 + Vf 2 + ... +Vf 15 P533Z2A
For LL connections, the three line-to-line voltages are directly measured and the
line-to-neutral voltages are calculated taking into account the residual voltage
measurement when it is measured. Otherwise, the calculation considers a
balanced power system.
For LN connections, the three line-to-neutral voltages are directly measured and
the three line-to-line voltages are calculated.
3LN/LNy VT, LPVT VL1, VL2, VL3, U12, U23, U31, VL1'
VL1y 66 U12y
3LN/LLy VT, LPVT VL1, VL2, VL3, U12, U23, U31 U12'
U12y 66
Depending on the phase rotation, the line-to-line values are defined according to
1-2-3 network: line-to-neutral and line-to-line voltages, page 355 and 1-3-2
network: line-to-neutral and line-to-line voltages, page 355:
• For voltage between phases 1 and 2:
Figure 268 - 1-2-3 network: line-to- Figure 269 - 1-3-2 network: line-to-
neutral and line-to-line voltages neutral and line-to-line voltages
VL3 VL2
U31 U12
VL1 VL1
U23 U23
U12 U31
VL3
VL2 P533MLA
P533MMA
Characteristics Range
Magnitude
Units V
Resolution 1V
Accuracy ± 5% from 1%Un to 10%Un
± 2% from 10%Un to 20%Un
± 1% from 20%Un to 50%Un
± 0.5% at 50%Un and above
Phase angle
Resolution 0.1°
Accuracy 0.5° with VL > 0.1Un and IL > 0.1In
Residual voltage
The Easergy P5 protection relay measures the fundamental value of a residual
voltage U0 by an open star/delta voltage transformer. If such a VT is not available,
the protection relay is able to calculate U0 by taking the internal sum of the three
line-to-neutral voltages:
3LN+U0 VT U0 measured
3LN/LLy VT, LPVT U0 calculated 69
2LL+U0 VT U0 measured
2LL+U0+LLy VT U0 measured
The following table lists the characteristics for measuring residual voltage:
Characteristics Range
Units V; kV
Resolution 1V
Accuracy 1 V to 10 V secondary: ± 5%;
10 V to 20 V secondary: ± 2%;
20 V to 50 V secondary: ± 1%;
> 50 V secondary: ± 0.5%
3LN VT, LPVT VL1, VL2, VL3 IL1, IL2, IL3 3 wattmeter Available
3LN + U0 with U0/V4
3LN/LLy (optional) IL1, IL3 2 wattmeter Not available
3LN/LNy 70
Power calculation
The power values are calculated in detail as follows:
• By 3 wattmeter method:
P = VL1 IL1 cos (VL1 IL1) + VL2 IL2 cos (VL2 IL2) + VL3 IL3 cos (VL3 IL3)
P533Z6A
Q = VL1 IL1 sin (VL1 IL1) + VL2 IL2 sin (VL2 IL2) + VL3 IL3 sin (VL3 IL3)
P533Z7A
• By 2 wattmeter method:
P = U12 IL1 cos (U12 IL1) + U32 IL3 cos (U32 IL3)
P533Z8A
Q = U12 IL1 sin (U12 IL1) + U32 IL3 sin (U32 IL3)
P533Z9A
•
2 2
S= P +Q P533ZAA
P533MNA
+direction
of flow
P533MOA
cos = cos = +
PF = ind PF= cap
VREF 0°
III I IV
cos = cos = +
PF= cap PF = ind P533MPA
Q
+90°
II I
cos = cos = +
PF= cap PF = ind
S
P 0°
III IV
cos = cos = +
PF = ind PF = cap P533MQA
Characteristics
The following tables summarise the characteristics for power measuring:
Measurement 0 to 1 IND/CAP -1 to +1
range
72. Sn = 3UnpIn
73. For measurements at In, Un, cosφ > 0.8.
Accuracy ± 1% typical 74
where
h1 = Fundamental value
h2 - h15 = Harmonics
Example
h1 = 100A, h3 = 10 A, h7 = 3 A, h11 = 8 A
102 + 32 + 82
THD = = 13.15%
100 P533ZDA
Demand values
The Easergy P5 protection relay calculates average demand values of phase
currents IL1, IL2, IL3 and power values S, P and Q. They are calculated over an
adjustable demand time in a range from 10 to 60 minutes.
Figure 273 - The Demand values view in the Measurements menu in eSetup
Easergy Pro
RMS values
IL1RMSda A Demand of RMS phase current IL1
Characteristics Range
f Frequency
PF Power factor
The clearing parameter "ClrMax" is a common reset for all min. and max. values.
Setting/characteristics Values
Measurement mode
Options Default (same as the scaling setting); L-L; L-N
Resolution 1%Un
Resolution 1%Un
DT delay time
Resolution 0.02 s
Accuracy ±1% or ±30 ms
Resolution 1%Un
Maximum time
Setting range 10 s to 1000 s
Resolution 1s
Gap time
Resolution 0.01 s
Characteristic time
Disengaging time < 60 ms
Temperature
Operation
This function gives the temperature value measured by resistance temperature
detectors (RTDs):
• Platinum Pt100 (100 Ω at 0°C or 32°F) in accordance with the IEC 60751 and
DIN 43760 standards
• Nickel 100 Ω or 120 Ω (at 0°C or 32°F).
Each RTD channel gives one measurement: tx = RTD x temperature.
The function also indicates RTD faults:
• RTD disconnected (t > 205°C or t > 401°F)
• RTD shorted (t < -35°C or t < -31°F).
In the event of a fault, the display of the value is inhibited.
The associated monitoring function generates a maintenance alarm.
Readout
The measurements may be accessed via:
• RTD view of the Measurements menu on the local panel of the Easergy P5
protection relay
• Temperature view of the Measurements menu in eSetup Easergy Pro
• the communication link
Characteristics
Table 110 - Characteristics of temperature measuring
Characteristics Values
Range -30°C to +200°C (-22°F to +392°F)
L (km)
Δt () = 2 X 2
S (mm ) P533ZFA
Control functions
Digital outputs
Description
Digital outputs are available for control and signalling purposes.
The number of available outputs depends on the number and type of board
options ordered.
The following digital output contact relays are available:
• Slot B
The digital output DO1 is normally opened (NO) contact (and high speed high
break contact for P5x30 only) used for control. The digital output DO2
(Change Over contact) is usually used for control.
The digital output DO3 (Normal Open) is usually used for control.
The digital output DO4 (change over contact) is dedicated to the watchdog
(signalling).
Both the tripping DO2 relay and the watchdog relay have normally open (NO)
or normally closed (NC) contacts. Refer to Selecting the trip command and
examples of use, page 398.
• Slot C, D, E (6I4O option)
The digital outputs DO1 to DO4 (Normal Open single pole single throw) are
for signalling only.
Slot C, D, E (5I5O option)
The digital outputs DO1 and DO2 (Change Over contact single pole double
throw) are usually used for control.
The digital outputs DO3 (Normal Open single pole single throw) are for
control.
The digital outputs DO4 and DO5 are normally opened (NO) contact and high
speed high break contact used for control.
Slot C, D, E (12I4O option)
The digital outputs DO1 to DO4 are independently controlled normally open
signalling contacts with DO1 & DO2 and DO3 & DO4 having a common
connection point.
• Slot D, E (Arc-flash option)
The digital output DO1 (Normal Open) is usually used for control.
The digital output DO2 (Change Over contact single pole double throw) is
usually used for control.
The digital output DO3 (Normal Open single pole single throw) is usually used
for signalling.
The contacts are (SPST) normal open (NO) type, except signal relay DO2
and DO4 (watchdog) which has a changeover contact (SPDT).
The digital outputs can be set in Normal Open or Normal Close position with
eSetup Easergy Pro and Web HMI in the Relays polarity view of the Control
menu.
The status of the digital outputs can be read:
• with eSetup Easergy Pro in the Relays view of the Device/Test menu
• by the local panel in the Digital output Slot x view under the menu option
DO of the Device/Test sub-menu
• EcoStruxure Power Device application
• Web HMI
Label and description texts can be edited with eSetup Easergy Pro or the Web
HMI in Names for output relays view according to the demand. Labels are the
short parameter names used on the local panel display and descriptions are the
longer names used by eSetup Easergy Pro (the Names of the output relays view
in the Control menu).
Any internal signal can be connected to the output relays using the output matrix.
An output relay can be configured as latched or non-latched. (see Output Matrix
view in the Matrix menu of eSetup Easergy Pro and Web HMI).
D E A B C
1 1 1 1
2 2 1 2 2 2
3 3 3 3
4 4 3 4 4 4
5 5 5 5
6 6 5 6 6 6
7 7 7 7
8 8 7 8 8 8
9 9 9 9
10 10 10 10
11 11 9 10 11 11
12 12 12 12
13 13 11 12 13 13
14 14 14 14
15 15 13 14 15 15
16 16 16 16
17 17 15 16 17 17
18 18 18 18
19 19 17 18 19 19
20 20 20 20
L M N P
P533NCA
Characteristics
Table 112 - Characteristics of the digital outputs
Label String of max. Short name for digital outputs on the Editable parameter
10 characters local display. (password needed)
Default is "DO1 - DOx". x is the
maximum number of the digital outputs.
Description String of max. Long name for digital outputs. Editable parameter
32 characters Default is "Digital output 1 - Digital (password needed)
output x". x is the maximum number of
the digital outputs.
Digital inputs
CAUTION
FIRE HAZARD
Do not connect power greater than 0.5 W to each digital input for ambient
temperature lower than 70℃ (158℉), or 0.8 W for lower than 45℃ (113℉).
Failure to follow these instructions can result in injury or equipment
damage.
Digital inputs are available for control purposes. For example, the digital inputs
can provide the position of the circuit breaker and make it possible to change
setting group, block/enable/disable functions, program logic, and indicate object
status.
The number of available inputs depends on the number and type of option boards.
The digital inputs require an external control voltage (AC or DC) and are activated
after the voltage exceeds the pick-up threshold. Deactivation follows when the
voltage drops below the drop-off threshold limit.
Figure 275 - The Digital inputs setting section in the Digital inputs view
1s 1s
Voltage
0
Digital input
0 P533NDA
Digital inputs on/off events and alarm pop-up message display can be enabled
and disabled in Digital inputs setting view of eSetup Easergy Pro or Web HMI.
Individual operation counters are located in the same view as well. The maximum
value of the counters is settable and is the same for all counters.
The status of the digital inputs can be read:
• with eSetup Easergy Pro and Web HMI in the Digital Inputs view of the
Control menu
• by local panel in the Digital inputs view of the DI menu option in the Control
menu
• EcoStruxure Power Device application
• Communication according to the protocol
The configuration of the digital inputs in eSetup Easergy Pro is common for all
digital inputs on the same board.
The digital inputs can be set for the following voltage values with pre-defined
setting values or settable values:
• Universal (by default)
• Standard AC or DC voltages (24 V DC, 48 V DC, 110 V DC, 220 V DC and
220 V AC)
• Customisable AC (settable from 24 to 220 V AC), customisable DC (settable
from 24 to 220 V DC)
Timing diagram of a digital input during pick-up, page 372 and Timing diagram of a
digital input during a drop-off, page 373 below illustrate the timing diagrams of a
digital input during pick-up and drop-off:
Nominal voltage
Pick-up ratio (%)
Inrush time
P533NEA
Debounce time
Nominal voltage
Holding current
DI high
DI low P533NFA
Label and description texts can be edited with eSetup Easergy Pro according to
the demand. Labels are the short parameter names used on the local panel and
descriptions are the longer names used by eSetup Easergy Pro.
The digital input signals can be connected to the different outputs of the Output
Matrix, Block Matrix, Auto-reclosing Matrix, Object block Matrix views in the Matrix
menu of eSetup Easergy Pro and Web HMI or used in the custom logic function.
D E A B C
1 1 1 1
2 2 1 2 2 2
3 3 3 3
4 4 3 4 4 4
5 5 5 5
6 6 5 6 6 6
7 7 7 7
8 8 7 8 8 8
9 9 9 9
10 10 10 10
11 11 9 10 11 11
12 12 12 12
13 13 11 12 13 13
14 14 14 14
15 15 13 14 15 15
16 16 16 16
17 17 15 16 17 17
18 18 18 18
19 19 17 18 19 19
20 20 20 20
L M N P
P533NGA
Characteristics
Table 114 - Characteristics of the digital inputs
Parameter Value
Universal Standard voltage Customisable voltage
Power maximum 0.5 W for ambient temperature less than 70℃ (158 ℉);
0.8 W for ambient temperature less than 45℃ (113 ℉);
Counters 0 to 255 - 511 - 1023 - 2047 - 4095 - 8191 - 16383 - 32767 - 65535
Reset automatically to 0 if the limit is exceeded.
Name of digital inputs Label: short name for display on the local panel.
String of max. 10 characters. Default is "DI1 – DIx".
NOTE: Digital inputs can be assigned to a signal with normal state or inverted
state.
Number of 20
Virtual Inputs
Number of 20
Virtual Outputs
Label String of Short name for virtual inputs and virtual Editable parameter
max. 10 outputs on the local display. (password needed)
characters Default is "VI1 - VIn" and "VO1 - VOn".
n is the maximum number of the digital
inputs or outputs.
Description String of Long name for virtual inputs and virtual Editable parameter
max. 32 outputs. Default is "Virtual input 1 (or (password needed)
characters Virtual output 1) -Virtual input n (or
Virtual output n)".
n is the maximum number of the virtual
inputs or virtual outputs.
Matrix
General information
The Easergy P5 protection relay has several matrices that are used for linking the
hardware and software elements together to create a protection chain:
• Output matrix
Used to link various inputs, outputs, statuses and signals to send a command
to the contact relays and virtual outputs, to activate disturbance recording,
and to provide SOL status.
• Block matrix
Used to block protection stages
• LED matrix
Used to control LEDs on the local panel
• Object block matrix
Used to inhibit object control
• Auto-recloser matrix
Used to control auto-recloser
• Arc-flash matrix
Used for Arc-flash detection functions
• Event matrix
See Logging and recording functions, page 402.
• Goose matrix
Used in association with IEC61850 (see the Goose matrix view in the
communication menu).
It allows to associate up to 128 Goose messages (NIx) to a virtual input or a
Goose message (NI).
Protection stages
Directly
measured Block matrix Output matrix User’s logic
I n
n values START I
TRIP N
V START
n Calculate TRIP P
START U
S, P, Q, n BLOCK TRIP T
cosφ, tanφ, INPUT
symmetric BLOCK S
components INPUT
etc. BLOCK
INPUT OUTPUTS
... n
Digital
inputs
n Output relays Virtual
DI and indicators outputs
n Optional
delay
and
inversion n
Output matrix
The output matrix is used for connecting signals issued by different functions to
the output relays (DO), virtual outputs (VO) and disturbance record trigger (DR).
The connecting signals to the outputs are the following:
• Protection signals from the different stages including setting changes
• Auto-recloser information
• Digital inputs
• Virtual inputs and outputs
• Object control command
• Function keys
• Goose
• Voltage sag/swell and interrupt
• Timers
The Output matrix setting view of eSetup Easergy Pro and Web HMI represents
the state (de-energised/energised) of the digital output's coil. For example, an
orange vertical line in the Output matrix and a logical "1" in the Relays view
represent the energised state of the coil. The same principle applies for both NO
and NC type digital outputs. The actual position (open/closed) of the digital
outputs' contacts in coil's de-energised and energised state depends on the type
(NO/NC) of the digital outputs. De-energised state of the coil corresponds to the
normal state of the contacts.
A digital output can be configured as latched or non-latched. The releasing latches
procedure is described in Releasing latches, page 381.
Programming matrix
NOTE: Logic outputs (see Logic functions, page 391) are also assigned
automatically in the output matrix when defined in any user programmable
logic scheme.
Blocking matrix
The operation of any protection stage can be blocked using the blocking matrix.
The blocking signal can originate from the digital inputs or it can be a start or trip
signal from a protection stage or an output signal from the user's programmable
logic. In All protection stages can be blocked in block matrix, page 378, an active
blocking is indicated with a black dot (●) at the crossing point of a blocking signal
and the signal to be blocked.
The Blocked status becomes visible only when the stage is about to activate.
Figure 284 - A view from the setting tool showing a DI input blocking
connection (left picture) and the result for the I> stage when the DI is active
and the stage exceeds its current start value
NOTICE
UNINTENDED AND NUISANCE TRIPPING
• In the online mode, the blocking matrix is dynamically controlled by selecting
and deselecting protection stages.
• Activate the protection stages first, then store the settings in the protection
relay. After that, refresh the blocking matrix before configuring it.
Failure to follow these instructions can result in unwanted shutdown of
the electrical installation.
LED matrix
The LED matrix defines the use of the Alarm LED , the trip LED , and the
configurable LEDs on the local panel of Easergy P5 protection relay. A lot of
functions can be assigned to eachLED.
Protection, arc and green or red Normal/ Different type of protection Set
programmable stages Latched/ stages can be assigned to
BlinkLatch LEDs
Digital/virtual inputs and green or red Normal/ All different type of inputs Set
function buttons Latched/ can be assigned to LEDs
BlinkLatch
Object open/close, object green or red Normal/ Information related to Set
final trip and object failure Latched/ objects and object control
information BlinkLatch
Local control enabled green or red Normal/ While remote/local state is Set
Latched/ selected as local the "local
BlinkLatch control enabled" is active
Logic output 1-20 green or red Normal/ All logic outputs can be Set
Latched/ assigned to LEDs at the
BlinkLatch LED matrix
Manual control indication green or red Normal/ When the user has Set
Latched/ controlled the objectives
BlinkLatch
Setting error, self green or red Normal/ Self diagnostic signal Set
diagnostic alarm, pwd open Latched/
and setting change BlinkLatch
All the LEDs (6 for Easergy P5x20; 10 for Easergy P5x30) can be assigned as
green or red. The selection of green and red at the same time will result in yellow.
The connection can be normal, latched or blink-latched (flashing).
Figure 285 - LEDs are assigned in the LED matrix view of the Matrix menu in
eSetup Easergy Pro
Normal connection
When the connection is normal, the assigned LED is active when the control
signal is active. After deactivation, the LED turns off. LED activation and
deactivation delay when controlled is approximately 10 ms.
Latched connection
A latched LED activates when the control signal activates but remains lit even
when the control signal deactivates. Latched LEDs can be released by pressing
the key on the local panel.
Blink-latched connection
When the connection is "BlinkLatch", the assigned LED is active and blinking as
long as the control signal is active. After deactivation, the LED remains latched
and blinking. The latch can be released by pressing the key on the local panel.
Auto-recloser matrix
The auto-recloser matrix is used to link digital inputs, virtual inputs, protection
stage outputs, object statuses, logic outputs, alarm signals and GOOSE signals to
control the auto-recloser. For more information, see Auto-recloser function (ANSI
79), page 330.
Arc-flash matrix
The arc-flash detection matrix uses three types of matrix:
• Arc-flash light matrix
The arc-flash light matrix is used for connecting light signals detected by
sensors or Goose or any virtual inputs to the different stages of the Arc-flash
detection function.
• Arc-flash current matrix
The arc-flash current matrix is used for connecting current signals and any
virtual inputs to the different stages of the Arc-flash detection function.
• Arc-flash output matrix
The arc-flash output matrix is used for connecting the different arc stage
signals to the digital outputs.
See Arc-flash (ANSI 50ARC), page 280 for more information on the arc-flash
protection function of the Easergy P5 protection relay.
Releasing latches
According to the matrix configurations different outputs and indicators can be
latched or non-latched. A non-latched output or indicator follows the controlling
signal. A latched output or indicator remains active after the controlling signal
releases.
There is a common "release all latches" signal to release all the latched relays.
This release signal resets all the latched digital outputs and indicators.
Each digital output can be latched or not independently through the output matrix.
The release of the latches can be done:
• Directly with the key on the local panel
• With a digital input/output or virtual input/output set in the Release latches
view of the Control menu of eSetup Easergy Pro or Web HMI
• With eSetup Easergy Pro clicking Device button in the menu bar and
selecting Release all latches
Figure 287 - Release latches using the Device button in the menu bar of
eSetup Easergy Pro
Mimic display
The Easergy P5 protection relay can display a mimic screen on the local panel.
The mimic screen can be entered from the main menu.
A single-line diagram, to be shown on the Mimic screen, can be created in eSetup
Easergy Pro through the Mimic view of the General menu.
B Draw line: used to draw lines in the view. I Some predefined drawings for use in the
To draw a line, select the tool, click the left view.
mouse button at the start point and then
move the cursor to the second point and
click again.
E Zoom in: used to increase the size of the L Auto reclosing check box
view. To show or hide the Auto-reclosing state
To zoom in, click the tool until the view in the view.
reaches the desired size.
F Zoom out: used to decrease the size of M Virtual input x check boxes
the view. To show or hide the specified virtual
To zoom out, click the tool until the view inputs states in the view.
reaches the desired size.
G Clear view: used to remove all objects N Up to 8 freely selectable measurements
from the view. To select the measurements to be shown
To clear the view, click the tool and select in the view.
OK to confirm.
Virtual input 1–4 0 Change the status of virtual inputs while the
1 password is enabled. Position can be changed.
Figure 289 - The Local panel conf view in eSetup Easergy Pro
Clear events -
Clear
Default screen Used to set the default home
screen of the local panel.
Controllable objects
The Easergy P5 protection relay allows the control of six objects, that is, circuit-
breakers, disconnectors and earthing/grounding switches by the "select before
operate" or "direct control" principle.
The object block matrix and logic functions can be used to configure interlocking
to help ensure the control before the output pulse is issued. The objects 1 - 6 are
controllable whilst the additional objects 7 - 8 are only able to show the status.
Controlling of objects 1–6 is possible in the following ways:
• through the object control buttons (I/O)
• through the local panel and display using single line diagram
• through the function key
• through a digital input
• through a remote communication
• through eSetup Easergy Pro setting tool
• through Web HMI
• through the EcoStruxure Power Device application
The connection of an object to specific controlling outputs is done via an output
matrix (object 1 – 6 open output, object 1 – 6 close output). There is also an output
signal "Object failed" that is activated if the control of an object is not completed.
Object states
Each object has the following states:
Open
Close
Undefined (11)
DI for "obj open" None, any digital input, virtual input Open information
or virtual output
DI for "obj close" Close information
Max ctrl pulse 0.02 – 600 s Pulse length for open and close
length commands. Control pulse stops
once object changes its state
If changing the states takes longer than the time defined by the "Max ctrl pulse
length" setting, the object is inoperative and the "Object failure" matrix signal is
set. Also, an undefined event is generated. "Completion timeout" is only used for
the ready indication. If the "DI for 'obj ready'" is not set, the completion timeout has
no meaning.
NOTE: The Object can only be controlled when its position is in a known state.
Output signals of controllable objects
Each controllable object has two control signals in the matrix:
DI for "obj open" None, any digital input, virtual input Open information
or virtual output
DI for "obj close" Close information
If changing states takes longer than the time defined by "Object timeout" setting,
an "Object failure" matrix signal is set, and an undefined-event is generated.
Setting Active
If the protection relay is in a local control state, the remote control inputs are
ignored and vice versa. An object is controlled when a rising edge is detected from
the selected input. The length of digital input pulse should be at least 60 ms.
The function keys are configured to control objects in the Function buttons view
of the Control menu.
This view shows the selected objects and controls for all the function keys of the
Easergy P5 protection relay.
Status 0 Disabled
1 Enabled
Selected control V1 - V20 Virtual input
Fn Function key n
Object for control - Disabled: the control buttons do not control Set
buttons any object.
Timers
Description
The Easergy P5 protection platform includes four settable timers that can be used
together with the user's programmable logic or to control setting groups and other
applications that require actions based on calendar time. Each timer has its own
settings. After setting the selected on-time and off-time you can then select
whether the timer is activated every day or just selected days of the week (See the
setting parameters for details). The timer outputs are available for logic functions
and for the block and output matrices.
P533NIA
You can force any timer, which is in use to on or off. The forcing is done by writing
a new status value. Unlike the digital inputs no forcing flag is needed.
The forced timer status remains as forced until the next forced change or the next
time the timer automatically changes status.
The status of each timer is stored in the non-volatile memory when the auxiliary
power is switched off. At startup, the status of each timer is recovered.
Setting parameters
Table 121 - Setting parameters of timers
MTWTF The timer switches on and off every day except Saturdays and
Sundays
MTWTFS The timer switches on and off every day except Sundays.
SatSun The timer switches on and off every Saturday and Sunday.
Logic functions
Easergy P5 protection relay supports user-defined programmable logic for
boolean signals. User-configurable logic can be used to create functionality that is
not provided by the protection relay as a default. You can see and modify the logic
in the Programmable Logic setting view of the Control menu in the eSetup
Easergy Pro or Web HMI.
AND 1
OR 1
XOR 1
AND+OR 2
CT 2
(count + reset)
128
INVAND 2 (An input gate can include 20
any number of signals.)
INVOR 2
OR + AND 80 2
RS 2
(set + reset)
RS_D 4
(set + D + load +
reset)
&
Virtual input 1
Logic output 1 Virtual output 1
Virtual input 3
≥1
Digital input 1
Logic output 1 Digital output 1
Digital input 2
P533P7A
Logic timer
Easergy P5 protection relay logic function can be used to manage accurate
breaker control and alarms with flexibility thanks to the logic timers included. Logic
timers offer the possibility of assigning a freely configurable time characteristic to
the output signal of each Boolean equation.
Settings/characteristics Value
Timer mode
Setting range Oper./rel. delay; Oper.del./pulse; Op/rel.del,
retrg; Minimum time; Op.d/pulse, retrg
t1
Setting range 0 - 60,000.00 s
Resolution 0.01 s
Accuracy ±1% or ±20 ms
t2
Setting range 0 - 60,000.00 s
Resolution 0.01 s
Accuracy ±1% or ±20 ms
The following figures show the time characteristics for the various timer stage
operating modes.
Logic output n
t1 = 0 s
Logic output n
t1, t2 > 0 s
Logic output n
Logic output n
t1 = 0 s
Logic output n
t1, t2 > 0 s
Logic output n
t2 = 0 s
Logic output n
Retrigger pulse
t1 = 0 s
Logic output n
t2
Retrigger pulse
t1, t2 > 0 s
Logic output n
Logic output n
P533NOA
Logic output n
t1 = 0 s
Logic output n
Retrigger pulse
t1, t2 > 0 s
Logic output n
AND
In Out
A Y
0 0
1 1
In Out
A Y
0 1
1 0
In Out
A B Y
0 0 0
1 1 1
1 0 0
0 1 0
In Out
A B Y
0 0 1
1 1 0
1 0 1
0 1 1
AND+OR
In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
CT
(count+reset)
In Out
A B Y Y
Cont Reset Setting New
1 3 0
1 3 0
1 3 1
1 3 0
OR
In Out
A B Y
0 0 0
1 1 1
1 0 1
0 1 1
In Out
A B Y
0 0 1
1 1 0
1 0 0
0 1 0
In Out
A B C Y
0 0 0 0
1 0 0 1
1 1 0 1
0 1 0 1
1 1 1 1
In Out
A B C Y
0 0 0 1
1 0 0 0
1 1 0 0
0 1 0 0
1 1 1 0
INVAND
In Out
A B Y
0 0 0
1 0 1
1 1 0
0 1 0
INVOR
In Out
A B Y
0 0 1
1 1 1
1 0 1
0 1 0
OR+AND
(AND+OR
reversed) In Out
A B Y
0 0 0
1 1 1
1 0 0
0 1 0
RS
(set+reset)
A B Y
Set Reset Y
1 0 1
1 1 0
0 0 0
0 1 0
RS_D
(set+D+load+reset)
A B C D Y
Set D-input Load Reset Y
0 0 0 0 0
1 x x 0 1
0 1 0 0 0
0 1 1 0 1
x x x 1 0
XOR
In Out
A B C Y
0 0 0 0
0 0 1 1
0 1 0 1
0 1 1 0
1 0 0 1
1 0 1 0
1 1 0 0
1 1 1 0
Circuit Breaker with Shunt Trip Coil Circuit Breaker with Undervoltage Trip
Coil
The circuit breaker stays closed if Easergy The circuit breaker opens automatically if
P5 protection relay goes into the fail-safe Easergy P5 protection relay goes into the fail-
position. safe position.
Monitoring is required to detect whether the The circuit breaker opens if the substation
protection is no longer operational. auxiliary voltage disappears.
NOTICE
RISK OF UNPROTECTED ELECTRICAL INSTALLATION
Always connect the watchdog output to a monitoring device to mitigate and take
appropriate action when the selected trip command does not result in the
installation tripping or when the Easergy P5 protection relay fails.
Failure to follow these instructions can result in unprotected electrical
installation.
Trip
Breaker closed Breaker open
B B
11 9 5 B 7 B
Inhibit closing DO1 DI3 DI4
DO2 12 10 6 8
13
Closing DO3 15
Figure 302 - Example of use with undervoltage trip coil with fail-safe
condition (diagram 2)
Trip
Breaker closed Breaker open
B B
11 9 5 B 7 B
Inhibit closing DO1 DI3 DI4
DO2 12 10 6 8
13
Closing DO3 15
P533NQA
Figure 303 - Example of use with undervoltage trip coil without fail-safe
condition (diagram 3)
Trip
Breaker closed Breaker open
B B
11 9 5 B 7 B
Inhibit closing DO1 DI3 DI4
DO2 12 10 6 8
13
Closing DO3 15
Closing Trip
Contactor
1 C 3 C
2 4
(1) (1)
DI5 DI6
Shunt
trip coil (1) Standard assignments;
can be modified.
P5F30_6N
00001
IL1 300 A
IL2 300 A
IL3 300 A
lovs 0.000 A
U12 11559 V
U23 11542 V
U31 11579 V
P 4594 kW
P5F30_6N
00001
Open
Close
Event buffer
The Easergy P5 protection relay provides a logging and recording of all important
events that happen during operations. All “operationally relevant” signals, each
fully tagged with date and time at signal start and signal end, are registered and
stored in chronological order. For example, an event can be, start-on, start-off,
trip-on or trip-off of any protection stage, alarm-on or alarm-off, a digital input
change, etc. Each event is associated with a unique code. The selection of signals
to be considered in the event logging and recording can be configured by the user.
As an example, a typical trip event is shown in Example of I> trip on event and its
visibility in local panel and communication protocols, page 402.
Table 126 - Example of I> trip on event and its visibility in local panel and
communication protocols
Event desc: I> trip on 2In Event text and fault value Yes No
Event configuration
To configure which events are recorded the event enabling matrices are used (see
the Event enabling views in the Logs menu of eSetup Easergy Pro). This allows
the optimisation of reporting by selecting the most useful events and deselecting
the ones of no interest. This prevents them from being written to the event buffer.
• Event enabling - stages 1
This matrix is used to activate an event when there is a change to the Start
and Trip status of a protection feature. Select On, Off or both.
• Event enabling - stages 2
This matrix is similar to the Event enabling -stages 1 matrix but more
dedicated to functions which provide more information than start and trip
signals (e.g. thermal image protection).
• Event enabling - objects
This matrix is dedicated to generate events associated to the defined objects
such as circuit breaker status and controls.
• Event enabling - AR
This matrix is dedicated to the auto recloser function and is used to generate
an event associated with auto reclose states and status.
• Event enabling - logic
This matrix is used to generate an event when one of the logic equations (up
to 20) is true or false.
• Event enabling - other
This matrix is dedicated to system monitoring including setting group change.
The maximum size of the buffer is 2000 events and can be exported a a PDF file
via eSetup Easergy Pro Print menu. 300 events can be displayed by eSetup
Easergy Pro. Only the latest 300 events, or the oldest 300 events, can be read on
the local panel according to the scroll order parameter.
All events are stored in non-volatile memory inside the Easergy P5 protection
relay and can be saved every 150 ms in the backup memory if available
(Extension board option).
When the buffer is filled the oldest event will be overwritten when a new event
occurs. The shown resolution of a time stamp for an event is one millisecond, but
the actual resolution depends on the particular function creating the event. For
example, most protection stages create events with a 5 ms, 10 ms or 20 ms
resolution. The absolute accuracy of all time stamps also depends on the
protection relay's time synchronisation.
Characteristics
Table 127 - Setting parameters for events
Clear events/ClrEv -
Display event time not in On (check mark) Event time shown normally if relay is
sync/Sync synchronised
Disturbance recording
Description
The Easergy P5 protection relay provides for fault events a disturbance recording
with the sampled analogue values of pre-selected analogue currents and voltages
before, during and after a fault event. Additionally, the calculated frequency, the
states of digital inputs (DI) and output (DO) signals are provided for detailed fault
analysis. The complete list of provided signals is shown in Disturbance recording
parameters (measurements and monitored values), page 406.
Triggering the recording
The recording can be triggered by any start or trip signal from any protection
stage, by a digital input, logic output or GOOSE signals. The triggering signal is
selected in the output matrix (vertical signal DR). The recording can also be
triggered manually. All recordings are time-stamped.
Reading recordings
The recordings can be uploaded with eSetup Easergy Pro (see Disturbance
recorder view of the GENERAL menu). The recording is in COMTRADE format.
This also means that other programs can be used to view and analyse the
recordings made by the Easergy P5 protection relay.
Number of channels
A maximum of 30 records can be stored with a mix of analogue and digital signals:
• 14 Analogue signals
• 124 Digital Signals (40 Digital inputs; 20 Digital outputs; 32 Start signals; 32
Trip signals)
A pre-selection of the channels and their order in the fault recording is made per
default and can be changed by the user with the parameters shown in Disturbance
recording parameters (measurements and monitored values), page 406.
NOTE: eSetup Easergy Pro provides directly the max record duration when
the signals to record are selected (see the bottom section of the Disturbance
recording view in the General menu).
81. Digital input signal means digital inputs (DI), virtual inputs (VI), etc.
82. Digital output signal means digital outputs (DO), virtual output (VO), etc.
Parameters
Table 130 - Disturbance recording parameters (measurements and
monitored values)
Parameter
Value Description
(description/label)
Status of recording
- Not active
Status/Status
Run Waiting a triggering
Trig Recording
Parameter
Value Description
(description/label)
Pre trig time/PreTrig 0% - 100% Amount of recording data before the trig
moment
Disturbance recording event On The event log is created or not when
(checkmark); Disturbance recording is triggered.
Off
Recording memory events On The event log is created or not when
(checkmark); Disturbance recording is reset
Off (clear the recording, reset the time and so on).
The selection of signals depends on the model of Easergy P5 protection relay and
also on the voltage measurement mode.
Characteristics
Table 132 - Disturbance recording characteristics
The recording time and the number of records depend on the time setting and the
number of selected channels.
Table 133 - Example of I> LOG [50/51] and its visibility in local panel and
communication protocols
Elapsed delay/EDly 100% Elapsed time of the operating time setting. 100% = trip
Table 134 - Example of VT supervisor and its visibility in local panel and
communication protocols
Settings / characteristics
Table 135 - Running hour counter settings/characteristics
Resolution 10 s
Start counter/Starts
Setting range 0 - 65535
Voltage interruptions
Description
The Easergy P5 protection relay includes a simple function to detect voltage
interruptions. The function calculates the number of voltage interruptions and the
total time of the voltage-off time within a given calendar period. The period is
based on the relay's real-time clock. The available periods are:
• 8 hours, 00:00 - 08:00, 08:00 - 16:00, 16:00 - 24:00
• one day, 00:00 - 24:00
• one week, Monday 00:00 - Sunday 24:00
• one month, the first day 00:00 - the last day 24:00
• one year, 1st January 00:00 - 31st December 24:00
After each period, the number of interruptions and the total interruption time are
stored as previous values. The interruption counter and the total time are cleared
for a new period. Previous values are overwritten.
Voltage interruption is based on the value of the positive sequence voltage U1 and
a limit value you can define. Whenever the measured U1 goes below the limit, the
values of the interruption counter and the total time counter starts are
incremented.
The shortest recognised interruption time is 40 ms. If the voltage-off time is
shorter, it may be recognised depending on the relative depth of the voltage dip.
If the voltage has been significantly over the limit U1< and then there is a small
and short under-swing, it is not recognised .
t
P533K1A
On the other hand, if the limit U1< is high and the voltage has been near this limit,
and then there is a short but very deep dip, it is recognised.
t
P533K2A
Parameter Value
Voltage low limit/U1<
Resolution 1%
Characteristic time
Start time < 60 ms
Disengaging time < 60 ms
S ■ Apparent power ■ ■
P ■ ■ Active power ■ ■
Q ■ ■ Reactive power ■ ■
The timebase can be a value from one cycle to one minute. Also a demand value
can be used as the timebase and its value can be set between 10 and 60 minutes.
Table 139 - Parameters of the day and month registers
Daylight time standards vary widely throughout the world. Traditional daylight/
summer time is configured as one (1) hour positive bias. The new US/Canada
DST standard, adopted in the spring of 2007 is one (1) hour positive bias, starting
at 2:00am on the second Sunday in March, and ending at 2:00am on the first
Sunday in November. In the European Union, daylight change times are defined
relative to the UTC time of day instead of local time of day (as in U.S.), so
European customers need to carefully check the local country rules for DST.
The daylight saving rules are by default UTC +2:00 (24-hour clock):
• Daylight saving time start: Last Sunday of March at 03.00
• Daylight saving time end: Last Sunday of October at 04.00
To ensure proper hands-free year-around operation, automatic daylight time
adjustments must be configured using the “Enable DST” setting and not with the
time zone offset option.
604.8
AAIntv =
DriftInOneWeek
P533K3A
If the auto-adjust interval "AAIntv" has not been zero, but further trimming is still
needed, the following equation can be used to calculate a new auto-adjust
interval.
1
AAIntvNEW =
1 DriftInOneWeek
+
AAIntvPREVIOUS 604.8 P533K4A
The term DriftInOneWeek/604.8 may be replaced with the relative drift multiplied
by 1000 if some other period than one week has been used. For example, if the
drift has been 37 seconds in 14 days, the relative drift is 37*1000/(14*24*3600) =
0.0306 ms/s.
Example 1
If there has been no external sync and the protection relay's clock is leading sixty-
one seconds a week and the parameter AAIntv has been zero, the parameters are
set as:
AvDrft = Lead
604.8
AAIntv = = 9.9s
61 P533K5A
With these parameter values, the system clock corrects itself with –1 ms every 9.9
seconds which equals –61.091 s/week.
Example 2
If there is no external sync and the protection relay's clock has been lagging five
seconds in nine days and the AAIntv has been 9.9 s, leading, then the parameters
are set as:
1
AAIntv NEW = = 10.6
1 5000
−
9.9 9 ⋅ 24 ⋅ 3600
When the internal time is roughly correct – the deviation is less than four seconds
– no synchronising or auto-adjust turns the clock backwards. Instead, if the clock
is leading, it is softly slowed down to maintain causality.
synchronisation with DI
The clock can be recognised by reading minute pulses from digital inputs, virtual
inputs or virtual outputs. The sync source is selected with the SyncDI setting.
When a rising edge is detected from the selected input, the system clock is
adjusted to the nearest minute. The length of the digital input pulse should be at
least 50 ms. The delay of the selected digital input should be set to zero.
synchronisation correction
If the sync source has a known offset delay, it can be compensated with the SyOS
setting. This is useful for compensating hardware delays or transfer delays of
communication protocols. A positive value compensates a lagging external sync
and communication delays. A negative value compensates any leading offset of
the external synch source.
Sync source
When the protection relay receives new sync message, the sync source display is
updated. If no new sync messages are received within the next 1.5 minutes, the
protection relay switches over to internal sync mode.
Deviation
The time deviation means how much the system clock time differs from the sync
source time. The time deviation is calculated after receiving a new sync message.
The filtered deviation means how much the system clock was really adjusted.
Filtering takes care of small deviation in sync messages.
Auto-lag/lead
The protection relay synchronises to the sync source, meaning that it starts
automatically leading or lagging to stay in sync with the master. The learning
process takes a few days.
DI Digital input
Minute sync pulse DI/ The digital input used for clock synchronisation.
SyncDI 85 Possible value depends on the type of I/O card
installed.
- DI not used for synchronising.
Auto adjust interval/ 0.0 - 1000.0 s Adapted auto-adjust interval for 1 ms correction
AAIntv 86
Average drift/AvDrft lead; lag Adapted average clock drift sign
Latest time deviation/ ± 32767 ms Latest time deviation between the system clock and
Dev the received synchronisation
85. Set the DI delay to its minimum and the polarity so that the leading edge is the synchronising edge.
86. If external synchronisation is used, this parameter is set automatically.
dd-mm-yyyy
mm-dd-yyyy
Time zone/Time zone -15.00 - +15.00 87 UTC time zone for SNTP synchronisation. 88
87. A range of -11 h - +12 h would cover the whole Earth but because the International Date Line does not follow the 180° meridian, a wider
range is needed.
88. Decimal numbers are used, e.g. the time zone of 5:45 is expressed as 5.75.
Monitoring functions
Trip circuit supervision (ANSI 74)
Description
Trip circuit supervision monitors the wiring from the protective device to the circuit
breaker trip coil. This function monitors the availability of the circuit when it is
requested to trip and reports an issue if needed.
By default, this user-configurable supervision function uses the Easergy P5
programmable logic to monitor the circuit continuity, loss of auxiliary supply
voltage or mismatching of the CB position indication contacts. Depending on user
settings, the function inhibits closing of the circuit breaker.
wire 1
Trip
relay(s) CB open DI1 CB closed DI2 Easergy P5
wire 2a
wire 2b
Circuit breaker
Trip
coil
wire 3
P533JAA
In the normal condition, when the trip circuit is OK, the status of inputs is opposite
(0,1) or (1,0). When the trip circuit is not OK (coil, wires, auxiliary contact state or
auxiliary voltage failure), both logic inputs are in the same state and an alarm is
issued after a delay. This delay is needed to prevent false signaling during breaker
opening events. The timing is set based on breaker operating time and trip pulse
length.
The following table summarizes the TCS alarm output depending on the CB and
its auxiliary contact positions as well as possible wiring failure conditions.
89. "failure" indicates that one or more of the components are permanently open circuit or short circuit.
CB open DI1
T 0
=1 TCS alarm
CB closed DI2
T=2s
P533JDA
Figure 316 - TCS with two digital inputs when the CB is in closed position
TCS alarm
=1
2s
52b 52a
P533JBA
90. "failure" indicates that one or more of the components are permanently open circuit or short circuit.
Figure 317 - TCS two digital inputs when the CB is in open position
TCS alarm
=1
2s
52b 52a
P533JCA
The figure below shows the default logic configuration of TCS in Easergy P5. In
this example the TCS is latched when an error condition is encountered and reset
using a virtual input.
Electrical wear
Breaker curve
The permitted CB operation number is defined by a CB permissible operation
curve. This curve is usually available in the documentation of the CB
manufacturer. The curve specifies the permissible number of operations for every
level of broken current.
10000
1000
100
50
20
10
100 200 500 1000 10000 100000
Breaken current (A) P533JEA
As shown in the figure below, in the Easergy P5 protection relay, this curve is
parameterised in the CB monitoring function with a maximum of eight points in the
form of [CurveIx, CurvNx]. If fewer than eight points are needed, the unused
points are set to [IBIG, 1], where IBIG is more than the maximum breaking capacity.
Table 142 - Values of the above circuit breaker wear characteristic graph
4-8 100 1
The values are taken from the figure above. The table (circuit breaker curve) is
edited with eSetup Easergy Pro or Web HMI in the CB Monitoring view of the
protection menu.
Two alarms on “Operations left” limit
The CB monitoring function is designed with two alarms, each with two
parameters:
• Current
This parameter can be set to the CB's nominal current or any typical
application current for the first alarm, and to a typical fault current for the
second alarm.
• Operations left
This parameter determines when an alarm is activated. When the “operations
left” at the given current level drops below this limit, the alarm is started.
The permitted operations at these two alarm levels can be calculated
automatically according to the breaker curve and logarithmic interpolation (see
next section). Any actual interrupted current is logarithmically weighted for the two
given alarm current levels and the number of operations left at the alarm points is
decreased accordingly. As shown in the figure below, the Easergy P5 protection
relay shows the allowed “operations left” based on the breaker curve, logarithmic
interpolation and actual interrupted current.
Logarithmic interpolation
The permitted number of operations for the currents between the defined points is
logarithmically interpolated using this equation:
a
C=
In P533JFA
where
C = permitted operations
I = broken current
a, n = constant according to the following two equations, where ln represents the
natural logarithm function, Ck/Ck+1 is the permitted number of operations defined
by CurveN, Curve(N+1) in the breaker curve table, and Ik/Ik+1 is the corresponding
broken current defined by CurveIk, CurveI(k+1) in the breaker curve table.
n
a = Ck I k P533JJA
Ck
ln
C k +1
n=
I
ln k +1
Ik P533JGA
Each time a trip signal is detected, the corresponding permitted operations shall
be calculated based on the broken current Ibrk:
a
Cbrk = n
Ibrk P533JHA
ln 10000
80
n= = 1.5038
ln 31000
1250 P533JKA
6
a 454 x 10
Calarm2 = n = 1.5038
= 945
Ibrk 6000 P533JMA
Calarm 945
∆1,2 = = =3
Cbrk 313 P533JOA
In phase L3, the current is less than the alarm limit current 6 kA. For such
currents, the decrement is one.
Five ranges of cumulative current
Each time the CB opens, the broken current is added to the corresponding total
cumulative broken current, phase by phase. The cumulative broken current is
given in (kA)2.
In addition to the total cumulative broken current, there are five cumulative broken
current ranges to assess the breaking device pole condition. Each range’s high
limit value is configurable and the low limit value equals to the high limit of its
previous range. Each range has three different counters, one for each phase, to
record how many times the broken current falls into the range. see figure below.
The cumulative broken current is also computed by phase. When the Easergy P5
protection relay is in test mode or the CB has been withdrawn, the cumulative
broken current is not updated.
An alarm signal will be generated when the cumulative broken current of any
phase exceeds the "broken I alarm setting".
Mechanical wear
CB Open counter, Protection Trip counter and Rack out counter
The “CB Open” counter is to record the number of CB close to open operation. It is
incremented even if the Easergy P5 protection relay is in test mode.
The “Protection Trip” counter is to record CB open times issued from Global trip.
This counter can also be set to a custom value but it does not increment during
test mode.
If, for whatever reason the circuit breaker does not open successfully after the
pulse setting time out ( configured in object), the trip counters are not
incremented.
The “Rack out” counter is to record the number of racking in/out operations of the
CB truck. It is incremented in test mode.
Open time, close time and charging time
If two different digital signals are used to indicate the 52a and 52b status of the CB
position, the open time is measured from the moment when the “52b” status
becomes false to the moment when the “52a” status becomes true; the close time
is measured from the moment when the “52a” status becomes false to the
moment when the “52b” status becomes true.
However, if the CB position is only configured as 52a or 52b, the open time and
close time will be recorded as 0 each time when its related status changes.
The charging time is computed from the moment when the CB position changes to
close to the moment when the spring status changes to ready. The spring status is
configured through "DI for object ready" setting in Objects.
Open/close times and charging times are recorded for 8 latest operations in the
Easergy P5, each with a timestamp. If the time recorded exceeds the range, the
time will be tagged as a "dummy" value (65535) which allows the customer to
easily detect something is wrong with the CB.
These CB open times, close times and charging times are also recorded when the
Easergy P5 is in test mode.
52b
52a
P533JPA
CB monitoring status
Alarm 2
Current 0.00 - 100.00 kA Alarm2 current level Editable
Cycles 100,000 - 1 Alarm2 limit for operations left Editable
Current points (CurveIx, 0.00 - 100.00 kA 8 current points of the CB wear Editable
x = 1, 2, … 8) characteristic
High limit / Iprim 0.0 - 100.0 kA High limit setting for each bin Editable
Parameter Accuracy
Charging time ±1 s
Block diagram
LPCTlost
T 0 Alarm
IL1 < 1%In
& Register
IL2 > 5%In event
Loss of phase
< 1.2In 20ms 0
L1 OR Fast Alarm
&
IL3 > 5%In Register
&
Loss of phase L2
event
< 1.2In ≥1 S
Angle R
IL2 Loss of phase L3
110° - 130° ≥1
IL3
I0 > & ≥1
U0 <
Reset
DI input
Characteristics
Table 145 - Settings and characteristics of the current transformer
supervision function (ANSI 60)
Settings/characteristics Values
(description/label)
Resolution 0.01In
Accuracy ±3%
Resolution 1%
Accuracy ±3%
Resolution 0.01 s
Accuracy ±1% or ±30 ms at 3I0 and 3U0
Characteristic times
Disengaging time < 60 ms
Settings/characteristics Values
(description/label)
Block diagram
I2 <
& Register
IL1 event
IL2 max(I) >
IL3 &
<
VTS alarm
U12 t
U23 max(V) < 0.3Un
U31
& Register
event
MCB open
≥1
LPVT loss
Inhibit Ctrl
P533JRB
U2> I2< I< (max) I> (min) t> Reset time Enable events
Characteristics
Table 147 - Settings and characteristics of the voltage transformer
supervision function (ANSI 60)
Settings/characteristics Values
(description/label)
U2> setting/U2>
Resolution 0.1
Accuracy ±2% or ± 0.2 V (secondary), whichever is bigger
I2< setting/I2<
Resolution 0.01
Accuracy ±2% or 0.02 In, whichever is bigger
Operation delay/t>
Resolution 0.02 s
Accuracy ±1% or ±30 ms, whichever is bigger
Inhibit ctrl/InhCtrl
Options Selection of one input (DI; VI)
I>(min) setting/I>(min)
Resolution 0.01 In
Accuracy ±1% or 0.02 In
I<(max) setting/I<(max)
Resolution 0.01 In
Accuracy ±1% or 0.02 In, whichever is bigger
V<
Value 30% Vn, fixed
Value 10 s
Accuracy 30 ms
Characteristic times
Reset time < 30 ms
Setting group/SetGrp
Number 1
Maintenance
The Easergy P5 protection relays together with their extension units,
communication accessories, arc-flash detection sensors and cabling, require
maintenance in work according to their specification. Keep a record of the
maintenance actions. The maintenance can include, but is not limited to, the
following actions.
Safety instructions
This page contains important safety instructions that must be followed precisely
before attempting to install, repair, service or maintain electrical equipment.
Carefully read and follow the safety instructions described below.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• NEVER work alone.
• Turn off all power supplying this equipment before working on or inside it.
Consider all sources of power, including the possibility of backfeeding.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Do not power a withdrawn mobile part of the Easergy P5 protection relay
with voltage > 24 V. Put back the withdrawable part in the fixed part before
powering it on.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
Apply proper tightening torque to all wire connections.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
If you are authorised to withdraw the relay:
• Disconnect the power supply before removing or replacing a module or the
withdrawable part of the protection relay.
• Never touch electronics parts (risk of damage due to electrostatic
discharge).
• Before replacing the withdrawable part, clean all debris and contaminants
from the case, the withdrawable part, and the connectors.
• In case of module or withdrawable part replacement, perform the
commissioning operations before using the protection relay.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF SETTING CHANGES ERASED
Never plug in or draw out the communication modules while the Easergy P5
protection relay is in service.
Failure to follow these instructions can result in injury or equipment
damage.
Self-monitoring
Watchdog relay
The Easergy P5 protection relays are equipped as standard with a watchdog relay
(digital output 4 in slot B). This is a changeover relay which is kept permanently in
the on-position by the Easergy P5 protection relay. In the event of protection relay
failure, or if the auxiliary power supply fails, the watchdog relay reverts to the off-
position.
Maintenance/Test LED
The Easergy P5 protection relay has gone into the fall-back position following
detection by the embedded self-tests of the failure of one of its internal
components. In this case, the Easergy P5 protection relay is no longer
operational. This LED may light up when the protection relay is energised
during all the start phase of the Easergy P5 protection relay (for about 60
seconds). This is normal and does not indicate any internal failure. When the start
phase of the protection relay is completed, the LED is off if no internal failure is
detected.
Press the key to remove the message (the alarm message is logged in
the Alarm message list).
◦ The communication is still operational depending on the type of the
internal failure
◦ The communication with eSetup Easergy Pro, on the local panel is active
depending on the type of internal failure
List of self-tests
The self-tests are described in the table below.
Table 148 - List of self-tests
Power supply
EEPROM boards
NOR Flash memory
DDRAM memory
On energisation and during
Back up memory
operation
Internal bus
Display and graphic libraries
Micro processor
Digital inputs
Digital outputs
Backup memory
The Easergy P5 protection relay has an optional feature of a removable back up
memory. This feature provides a mechanism for storing the product settings and
other related information separately to the removable part of Easergy P5.
The memory allows quick, restoration of settings should there be a need to
exchange the withdrawable part. As a result, the mobile part can be replaced and
back in service in a matter of minutes.
The optional back up memory is included in the extension module that can be
installed in Slot P. This extension module also includes connectivity to support
IRIG-B and thermal sensors.
Figure 326 - The optional extension module (slot P) that includes the back-
up memory
Automatic storage
The Easergy P5 automatically stores all settings, events and disturbance
recordings at 2AM local time every day.
As indicated above the secured process means that the memory can not be
corrupted as the save is verified before previous data is overwritten.
NOTE: Due to this unique feature the important data and settings are always
secured locally and not based on any remote storage on a control system.
1. Press the key to enter the main menu and then select the Device/Test icon
using the arrow keys.
2. Press the key to enter the Device/Test sub menu.
3. Select the Back-up option using the key and press .
4. Press , select Man. Trig and then press .
Backup Memory 1/2
Trigger backup memory
Status Idle
Man. Trig -
Ignore Restore
Press the key to keep the information in the back up memory or the button
to discard and prevent the pop up occurring again.
NOTE: This action does not restore the settings. Follow the ‘Restore from
Backup memory’ process described below.
1. Press the key to access the main menu and then select Device/Test by
using the arrow keys.
2. Press the key to enter the Device/Test sub menu.
3. Press the key to select the Back-up option and then press .
4. Press the key to enter the second setting page “Restore Memory” and
then press .
5. Press the key to select the “Trig restore memory” parameter and then
press .
6. Press the key to select On.
The Easergy P5 shows the following notification window:
CAUTION
All the settings, events,
records will be replaced
by backup. Don’t apply an
unverified backup against
unpredictable risks.
Recheck relay after restore.
Restore Cancel
Preventive maintenance
The Easergy P5 protection relay requires maintenance in order for it to work
according to the specification.
WARNING
HAZARD OF UNEXPECTED SYSTEM OPERATION
Carry out periodic system testing as per the testing recommendation in this
manual or if the protection system scheme has been changed.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Introduction
To obtain the maximum availability of the installation, it is essential to ensure that
the Easergy P5 protection relay is operational at any times.
The Easergy P5 protection relay's internal self-tests, the watchdog relay, and the
LED alert the user in the event of internal protection relay failure.
Nevertheless, elements outside the Easergy P5 protection relay are not subject to
these self-tests and it is therefore necessary to carry out regular preventive
maintenance.
Check the Easergy P5 protection relay visually and pay attention to dirty
components, loose wire connections, damaged wiring, user interface screen and
LEDs, and other mechanical connections.
Then, to perform maintenance, carry out all the recommended commissioning
tests.
First test all the digital inputs and outputs involved in tripping the circuit breaker. A
test of the complete chain including the circuit breaker is also recommended.
The software setting tool, eSetup Easergy Pro, is especially useful during
maintenance tests and procedures.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS-2011, or
CSAZ462.
• The arc fault detection system is not a substitute for proper PPE when
working on or near equipment being monitored by the system.
• Information on this product is offered as a tool for conducting arc-flash
hazard analysis. It is intended for use only by qualified persons who are
knowledgeable about power system studies, power distribution equipment,
and equipment installation practices. It is not intended as a substitute for the
engineering judgement and adequate review necessary for such activities.
• Only qualified personnel should install and service this equipment. Read this
entire set of instructions and check the technical characteristics of the device
before performing such work.
• Perform wiring according to national standards (NEC) and any requirements
specified by the customer.
• Observe any separately marked notes and warnings.
• NEVER work alone.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume all circuits are
live until they are completely de-energized, tested, and tagged. Pay
particular attention to the design of the power system. Consider all sources
of power, including the possibility of back feeding.
• Always use a properly rated voltage sensing relay to ensure that all power is
off.
• The equipment must be properly grounded.
• Connect the device's protective ground to functional earth according to the
connection diagrams presented in this document.
• Do not open the device. It contains no user-serviceable parts.
• Install all devices, doors and covers before turning on the power to this
device.
Failure to follow these instructions will result in death or serious injury.
Intervention frequency
Test the Easergy P5 protection relay periodically according to the end user's
safety instructions and national safety instructions or law.
The necessary time between visual inspections and functional checks depends on
the installation operating conditions. Generally, we recommend to carry out
periodic checks or tests every four (4) years. In corrosive or harsh offshore
environments, functional testing should be carried out more often; we recommend
every three (3) years.
For the testing procedures, see Commissioning, page 114.
The table below summarises the recommended frequency of interventions.
Test Periodicity
Test Periodicity
CAUTION
RISK OF DEVICE MIS-OPERATION AND PROTECTION INTERRUPTION
To avoid irregularity during service of the Easergy P5 protection relay, the health
condition must be checked on a timely basis according to the site maintenance
plan.
Failure to follow these instructions can result in injury or equipment
damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Turn off all power supply to the equipment before working.
• Protect the rear connector A with the two protective caps.
Failure to follow these instructions will result in death or serious injury.
Check the wiring connections in the rear panel: for the type of screws, screwdriver
to be used, and torque (see Installation, page 32).
In addition to the periodic wiring and connections check, a thermal measurement
with thermal camera is recommended to make visible any warm points of the
installation so that loose connections could be detected and corrected before a
real issue occurs.
Check the earth/ground connections (two ends).
Place back the two protective caps (connector A) before powering on the Easergy
P5 protection relay.
DANGER
HAZARD OF UNEXPECTED SYSTEM OPERATION
• If the arc-flash detection unit is no longer supplied with power or is in
permanent non-operational state, the protection functions are no longer
active and all the output contacts are dropped out.
• To detect a power-off or a permanent fault state, connect the watchdog (SF)
output contact to a monitoring device such as SCADA or DCS.
Failure to follow these instructions will result in death or serious injury.
Hardware cleaning
Pay special attention to ensure that the device, its extension units and sensors do
not become dirty.
DANGER
HAZARD OF UNEXPECTED SYSTEM OPERATION
• Do not use any type of solvents or gasoline to clean the device, sensors or
cables.
• When cleaning the sensor, make sure that the cleaning solution does not
contact anything other than the sensor.
Failure to follow these instructions will result in death or serious injury.
Troubleshooting
Troubleshooting assistance
The Easergy P5 is a withdrawable protection relay. The faulty protection relay can
be removed from its outer case without disconnecting the wires from the terminals.
This allows to quickly replace a protection relay, provided that the spare part is
available.
The replacement of a protection relay is done with the following steps:
1. Perform a diagnostic check on the protection relay:
• The status of the watchdog relay (DO4 contact relay on slot B)
• The status of the " " and " " LEDs as well as the configurable LEDs
• The LED and the " " LED on the local panel
• The messages displayed on the local panel
• The alarm list and maintenance file downloaded with eSetup Easergy
Pro
2. Check the compatibility of the spare part: the labels on the fixed and the
withdrawable parts are the same.
3. Recover the configuration from the backup memory (optional) and restart of
the new protection relay, following the instructions displayed on the local
panel.
The Easergy P5 is a modular protection relay. The modules that can be replaced
individually are:
• The communication modules
• The extension modules with back-up memory
Identification of the modules can be accessed:
• From the local panel of the Easergy P5 protection relay ( in the Device/Test
menu)
• From eSetup Easergy Pro (Boards view of the Device/test menu)
• From the web server and the EcoStruxure Power Device application
Maintenance message with: Mismatch between hardware Check the model number on
Module ID = 3 configuration and product fixed part with model number
Error type = -7 model number. on the withdrawable.
1st five characters after the
application reference should
be the same:
P5xx0-AAAA-Axxxx-xxxx
Maintenance message with: Hardware failure detected on Change the fix part of the
Module ID = 3 the fixed part (slot A) when the Easergy P5 protection relay
Error type = -5 Easergy P5 protection relay is with the equivalent one.
Completed by one of these powered on.
references: The message specifies the
• 3CT-CSH board impacted by the defect.
• 3CT-4VT-CSH
• 5CT
• 5CT-4VT
• 4VT
• LPCT-LPVT
Maintenance message with: Hardware failure detected on Change the withdrawable part
Module ID = 3 the withdrawable part when the of the Easergy P5 protection
Error type = -5 Easergy P5 protection relay is relay with the same model
Completed by one of these powered on. number.
references: The message specifies the
• 6DI-4DO board impacted by the defect.
• ARC-FLASH
• CPU P5x20
• CPU P5x30
• PSU30H-DI-DO
• PSU30L-DI-DO
• PSU20-DI-DO
Alarm message completed by Hardware failure detected on Check that the hardware
one of these references: the optional boards when the resources are equivalent or
• EXTENSION-BKUP Easergy P5 protection relay is exceeds those used in the
• COM SRL RS485 powered on. configuration file.
• COM SRL FO
• COM ETH 2TP-M (on
slot M)
• COM ETH 2FO-M (on
slot M)
• COM ETH 2TP-L (on slot
L)
• COM ETH HSR/PRP
Message appears during a Major issue on the CPU board Change the withdrawable part
reboot of the Easergy P5 of the Easergy P5 protection of the Easergy P5 protection
protection relay. The boot is not relay. relay with the same model
complete and the following number.
message is displayed:
- Firmware not complete (in
English only)
Alarm message completed by MET148-2 loose connection Check the MET148-2 module
the reference: is well connected to the
MET148-2 Extension and backup memory
board.
See Troubleshooting the
MET148-2 module, page 450
for more information.
CT supervision Alarm message Connection issue from CT/ Check the connection from MV
LPCT transformer to the transformer to the analogue
Easergy P5 protection relay input of the Easergy P5
protection relay.
Alarm message completed by The RTD number x on the As the message is common to
“RTD x Open Circuit Fault On” MET148-2 module is the RTD channels of the
or by: “RTD x Short Circuit disconnected or short- MET148-2 module, go to the
Fault On”, circuited. temperature measurement
display screen to determine
where x is the number of the which RTD is affected by the
RTD defect.
Measurement displayed:
• Tx.x = -**** = RTD
disconnected (T > 205 °C
(401 °F))
• Tx.x = **** = RTD short-
circuited (T < -35 °C (-31
°F))
Then check the connection of
RTDs.
The user did not log in using Use the InstallerLevel to log
the InstallerLevel user type and into the device.
was not allowed to proceed
with the firmware upgrade
operation.
The trip signal does Faulty trip circuit wiring. Check that the wiring of the trip circuit is
not reach the circuit not faulty.
breaker.
The protection does The protection needs both Check the dip switch configuration. The
not trip even when a light and current information protection may be configured to require
sufficient light signal to trip. both the light and current condition to trip.
is provided.
Faulty sensor wiring Loose sensor wire. Check the sensor wiring. The sensor wire
detected by the self- may have loosened in the terminal blocks.
supervision.
Error message Light pulse to the arc-flash Check that the light pulse to the arc-flash
indicating blocked sensor is too long. sensor is not too long.
sensor channel.
If light is supplied to the arc-flash sensor for
more than three seconds, the self-
supervision function activates and switches
the light sensor channel to daylight
blocking mode, and the sensor channel is
blocked.
MET148-2 green LED on. No response from the Check the position of the
MET148-2 red LED off. MET148-2 module. module number selection
jumper:
• MET1 for first MET148-2
module (temperatures T1
to T8)
• MET2 for second
MET148- 2 module
(temperatures T9 to T16).
• If the jumper position
needs to be changed,
reboot the MET148-2
module (by disconnecting
and reconnecting the
interconnection cord).
• Change the extension
module.
MET148-2 red LED flashing. Faulty wiring, MET148-2 Check module connections:
powered but loss of dialogue • RJ45 plugs of CCA77x
with base unit. cords clipped correctly
into sockets.
• If the MET148-2 module
is the last in the chain,
check that the line
terminating jumper is in
the Rc position. In all
other cases, check that
the jumper is in the
position marked
.
MET148-2 red LED on. More than 3 remote modules Remove a remote module.
connected.
MET148-2 module internal Change MET148-2 module.
failure.
Firmware upgrade
NOTE: This section applies to firmware upgrade operation only. For firmware
downgrade, please contact Schneider Electric Customer Care Center.
From time to time it may be necessary to upgrade the firmware of your Easergy
P5. There could be a number of reasons for this, new functionality, security
patches or correction of product behaviour.
The firmware upgrade feature of the Easergy P5 protection relay provides the
possibility for the user to upgrade the application firmware themselves through
eSetup Easergy Pro.
Upgrading the firmware requires the eSetup Easergy Pro software to be
connected to the device to be upgraded. This can be done either through the mini-
USB port on the local panel or one of the rear Ethernet ports.
You must also have access to the zip file containing the firmware version you wish
to upgrade to. This file typically has the format Easergy-P5-firmware-Vxx.xxx.xxx.
zip. Please contact Schneider Electric Customer Care Center to get the package.
Please be aware that the contents of this file must come from Schneider Electric
and the firmware signature will be checked to ensure that it has come from a
genuine source before the product is updated.
NOTICE
RISK OF DATA LOSS
• Please save your configuration files, disturbance records and events before
starting the firmware upgrade.
• After the firmware upgrade is done, the operator needs to first connect to the
device and retrieve all configurations through eSetup Easergy Pro, open the
saved file, and then select the “Copy all to DEVICE” option from the “File”
menu.
• The operator needs to rebuild the logics and matrix.
• The operator needs to reload the second language package.
Failure to follow these instructions will result in loss of all configurations,
disturbance records and events.
The process for upgrading the firmware on the Easergy P5 protection relay is as
follows:
1. Connect the laptop that runs eSetup Easergy Pro to the Easergy P5
protection relay and log in with “InstallerLevel”.
2. Open the main menu from the top-left corner of the application, select the
"Update firmware..." option, and then select the new firmware package from
the folder where you saved the package.
3. The application performs the following operations before starting the upgrade:
a. Check the user's rights
b. Check the available memory size
c. Copy the firmware to the device
d. Check firmware/hardware version compliance
4. If every check is passed, the application gets ready to upgrade the firmware
and prompts the user to confirm. Click OK to confirm and the application will
reboot the device, and after that the new firmware will take effect.
Figure 327 - The fixed and withdrawable parts of the Easergy P5 protection
relay
2
P533JUA
① Fixed rack
② Withdrawable part
To limit the time of interventions for maintenance reasons, the faulty protection
relay can be removed without disconnecting the wires or the connections. This
allows to quickly replace a Easergy P5 protection relay, provided that the spare
part is available.
The spare withdrawable part must be compatible with the one which is replaced.
The compatibility rules are as follows:
• The spare part must have the same hardware resources
• The spare part must have the same product model number
• The spare part must have the same major software version
To avoid any unintended withdrawing, and for security reasons, the removable
part is fixed to the rack by 3 screws for Easergy P5 x20 and 4 screws for Easergy
P5 x30 protection relays.
The procedure for replacing the Easergy P5 protection relay is as follows:
Preliminary operations
NOTE: If the Easergy P5 protection relay is still working, do not hesitate to
save configuration, settings and parameters to the back-up memory of the
extension module (optional) if it is available in the protection relay. For saving
(backup), go to the backup view of the Device/Test menu on the local panel.
1. Power off the Easergy P5 protection relay.
2. Unscrew the 3 screws on Easergy P5 x20 (or 4 for Easergy P5 x30) that fix
the local panel to the relay outer case. Refer to Unscrewing the front face
locking screws, page 43.
Tools (-) 6.5 mm (1/4 in.) or (+) PZ2 screwdriver (Digital torque
screwdriver for installing)
3. Push upward the handle lock that locks the device handle.
4. Close the shutter of the local panel if it is open.
Removal
1. Using the device handle, pull the withdrawable part of the protection relay to
detach it from the outer case (pull the device handle from the top and bottom
when side access is difficult).
P533JSA
2. Extract the withdrawable part of the protection relay, using your both hands to
ensure a secure grip.
3. Check the model numbers on both the withdrawable part and the outer case.
Installation
1. Before replacing the module:
• For compatibility of the spare part, check that the identification on the
labels on the fixed and the withdrawable parts are the same.
• Visually check the cleanliness and state of the rear connectors (rear part
and lower part).
2. With the device handle fully open, insert the withdrawable (spare) part gently
into the fixed part.
3. Push down the handle to lock the withdrawable part. The lock tab on the
handle locks the handle to the local panel automatically.
P533JTA
4. For highly vibrating environment, put in place the screws (3 for Easergy P5
x20 and 4 for Easergy P5 x30) for locking the local panel to the relay case.
NOTE: The screws are not mandatory for the installation of the spare part, but
recommended for security reasons.
Subsequent operations
After installing the Easergy P5 protection relay, perform the following operations if
necessary:
1. Switch on the Easergy P5 protection relay and check the relay operation.
Check the model number (from the Device/Test menu on the local panel) and
compare it with the associated model number displayed in eSetup Easergy
Pro.
2. If an extension module with backup memory is available on the Easergy P5
protection relay, update the device configuration.
3. For recovery of the configuration from the backup memory (optional) and
restart of the new protection relay, follow the instructions displayed on the
local panel.
CAUTION
RISK OF SETTING CHANGES ERASED
• Never plug in or draw out the communication modules while the Easergy P5
protection relay is in service.
• Check and make sure that the communication module is locked.
Failure to follow these instructions can result in injury or equipment
damage.
Preliminary operation
Before changing a communication module:
1. Power off the Easergy P5 protection relay.
2. Check if it there is enough space (> 15 cm or 6 in.) in the rear and lower part
of the case to extract the modules. If not possible, remove the case from its
support.
Removal
The module can be easily removed from the Easergy P5 protection relay:
1. Push down the locking tab ①.
2. Gently pull the communication module forward ②.
2
1
P533JVA
Installation
Install the module according to the following steps:
1. Before replacing the module, check visually the front plate ① and the
connector ②.
1 2
P533JWA
Subsequent operation
After installing the module:
1. Check that the module is locked (visual check).
2. Switch on the Easergy P5 protection relay and verify that the module has
been detected:
• On the local panel, enter the Device/Test sub-menu from the main menu
and check this in the Board view.
• With eSetup Easergy Pro see the Device Info view in the Device/Test
menu.
End of life
At end of life, Easergy P5 protection relays must be dismantled to facilitate the
recovery of the various constituent materials.
The proportion of recyclable material is higher than 65%. This percentage
includes the metallic materials and marked thermoplastics conforming to the
current legislation, as well as the subassemblies that must be sent to specialised
treatment systems: 3 to 5 electronic cards, and an LCD screen that can easily be
disassembled.
It is calculated according to "ECO’DEEE recyclability and recoverability calculation
method" (version V1.20, September 2008, presented to ADEME, the French
Agency for Environment and Energy Management).
Cybersecurity
Cybersecurity overview
This chapter contains up-to-date information about your product’s cybersecurity.
Network administrators, system integrators and personnel that commission,
maintain or dispose of a device should:
• Apply and maintain the device’s security capabilities. See Device security
capabilities, page 462 for details.
• Review assumptions about protected environments. See Protected
environment assumptions, page 463 for details.
• Address potential risks and mitigation strategies. See Potential risks and
compensating controls, page 464 for details.
• Follow recommendations to optimise cybersecurity.
To communicate a security topic affecting a Schneider Electric product or solution,
go to https://www.se.com/ww/en/work/support/cybersecurity/vulnerability-policy.
jsp.
The Easergy P5 device is delivered with auto-login feature. It will be disabled
when the passwords for all three levels are changed from the default ones.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords to help prevent unauthorised access to device
settings and information.
• Disable unused ports/services and default accounts, where possible, to
minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example: least rights, separation of
duties) to help prevent unauthorised exposure, loss, modification of data and
logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Security policy
NOTICE
HAZARD OF ACCESSIBILITY LOSS
• Setup a security policy and procedure to back up the security administrator
user account.
• Do not share a single user account with multiple users. Set one user account
associated to roles and rights per user.
• Do not excessively decrease "user parameters" values.
Failure to follow these instructions can result in loss of access to the
protection relay.
NOTICE
CYBER SECURITY HAZARD
• Except for private GetSet protocol via secured communication (SSH), the
device does not have the capability to transmit data encrypted using the
following protocols: IEC 61850, DNP3 over Ethernet, Modbus slave over
Ethernet, EtherNet/IP, IEC 60870-5-103 serial, IEC 60870-5-101 serial,
DNP3 serial, Modbus slave serial, Modbus master serial, IEEE 1588 and
SNTP.
• If other users gained access to your network, transmitted information can be
disclosed or subject to tampering.
• For transmitting data over an internal network, physically or logically
segment the network. The access to the internal network needs to be
restricted by using standard controls, such as firewalls, and other relevant
features supported by your device, such as IPTable whitelisting.
• For transmitting data over an external network, encrypt protocol
transmissions over all external connections using an encrypted tunnel, TLS
wrapper or a similar solution.
Failure to follow these instructions can increase the risk of unauthorised
access.
Product defense-in-depth
Use a layered network approach with multiple security and defense controls in
your IT and control system to minimize data protection gaps, reduce single-
pointsof- failure and create a strong cybersecurity posture. The more layers of
security in your network, the harder it is to breach defenses, take digital assets or
cause disruption.
Information confidentiality
These security capabilities help protect the confidentiality of information through
secure protocols that employ cryptographic algorithms, key sizes and
mechanisms used to help prevent unauthorised users from reading information in
transit, i.e. SSH, SFTP and HTTPS.
Physical security
In order to prevent unauthorised access, lock the shutter on the local panel of the
Easergy P5 protection relay with a wired lead seal. See Lock the shutter and
handle, page 43 for details.
Cybersecurity configuration
These security capabilities support the analysis of security events, help protect the
device from unauthorised alteration and records configuration changes and user
account events:
• Internal time synchronization.
• Time source integrity protection and the Easergy P5 protection relay
configuration event logging.
• Timestamps, including date and time, match the Easergy P5 protection relay
clock.
• SSH server hosts an internal SFTP site and stores files in the Easergy P5
protection relay’s flash memory, such as: COMTRADE records and firmware
files.
• Embeds user information with changes.
• Offload information to syslog or a protected storage or retention location.
Port hardening
The communication port of Easergy P5 protection relay can be disabled. Each
logical port can be independently disabled. Port hardening configuration can be
set from the local panel of Easergy P5 protection relay, from eSetup Easergy Pro,
or from the web HMI, with the ENGINEER access right.
Firmware upgrades
This security capability helps protect the authenticity of the firmware running on
the Easergy P5 protection relay and facilitates protected file transfer: digitally
signed firmware is used to help protect the authenticity of the firmware running on
the Easergy P5 protection relay and only allows firmware generated and signed by
Schneider Electric.
User Default account If you do not Change the default password for all
accounts settings are often change the accounts to help reduce unauthorised
the source of default password, access. See Passwords, page 475.
unauthorised unauthorised
access by access can occur.
malicious users.
Secure IEC 61850, DNP3 If a malicious user For transmitting data over an internal
protocols over Ethernet, gained access to network, physically or logically segment
Modbus slave your network, they the network.
over Ethernet, could to intercept
EtherNet/IP, IEC communications. For transmitting data over an external
60870-5-103 network, encrypt protocol transmissions
serial, IEC 60870- over all external connections using an
5-101 serial, encrypted tunnel, TLS wrapper or a similar
DNP3 serial, solution.
Modbus slave
serial, Modbus See Protected environment assumptions,
master serial, page 463.
IEEE 1588 and
SNTP protocols
are unsecure.
Cybersecurity configuration
Cybersecurity in the scope of energy management is a set of rules, methods, and
technical features improving the quality of services and interrupt the deliveries
resulting from accidental or intentional actions.
The Easergy P5 protection relay has one of the two following cybersecurity levels:
• Basic CS: basic cybersecurity rules as default configuration
• Advanced CS: cybersecurity option, proposed as a firmware option to be
selected at the ordering
To know which cybersecurity level is adopted in the Easergy P5 protection relay,
check the 17th field of the reference number of the Easergy P5 protection relay as
shown in the examples below, where A stands for basic and B for advanced level.
P 5 x 2 0 - _ _ _ _ - _ _ _ _ _ - _ _ A _
P 5 x 3 0 - _ _ _ _ - _ _ _ _ _ - _ _ B _
NOTE: Only the firmware with Advanced CS level configuration fulfills the
requirements of IEC 62443-4 Security Level 1 (SL 1).
The table below lists the differences between the two cybersecurity levels:
Communication encryption ■ ■
Security logs - ■
Manual mode
When the CAE is connected to the Easergy P5 protection relays, the security
administrator can manually push the user database and RBAC (Role Based
Access Control) directly to a group of protection relays that are located inside a
substation and to manually download and concentrate the security logs from
protection relays.
Since the bonus will be on the security administrator to ensure all devices are
synchronised when a change is made, it is not recommended for manual mode to
be used on groups of more than 32 Easergy P5 protection relays or other devices.
CAE
RBAC
Ethernet
Security logs
P533JXA
Automatic mode
In this mode the security administrator is responsible for the configuration of the
RBAC and user database with the CAE. The CAE communicates with a central
server and the protection relays.
User authentication is done both at a centralised level (user password control) and
at the relay level (user vs. role and role vs. right). The security protocol used is
RADIUS.
The security logs are automatically and permanently concentrated by a central
server. The CAE is used by the security administrator to visualise them.
Authentication Roles
Ethernet - RADIUS protocol
Security logs
P533JYA
Corporate active
directory
Central server or
CAE
3rd party
Authentication Roles
Ethernet - RADIUS protocol
Security logs
P533JZA
GENERAL SETTINGS
Cybersecurity reset -
RBAC Reset to factory
Firmware upgrade
Config Access
Via F1 Key Enabled
Via SCADA Enabled
NOTICE
IMPROPER EQUIPMENT OPERATION
If F1 key is configured as the quick access of the Easergy P5 lock/unlock
functionality, F1 key cannot be used by any other functions.
Failure to follow this instruction can result in improper operation.
Via F1 Key
Disabled Enabled
Locked Unlocked
Access via HMI Read/Write Read Read/Write
In locked state, when there is no alarm pop-up message on the screen, pressing
key will pop up a "Permission denied" message.
Via SCADA
Disabled Enabled
Access via rear comms Read Read/Write
SCADA (IEC 61850)
List of roles
The Easergy P5 menus and screens are accessible according to the Role Based
Access Control concept (RBAC) to help prevent unauthorised operation. RBAC is
essentially a collection of permissions. Users are assigned particular roles, and
through those role assignments acquire the permissions to perform particular
functions. Since users are not assigned permissions directly, but only acquire
them through their role (or roles), management of individual user rights becomes a
matter of simply assigning appropriate roles to the user's account; this simplifies
common operations, such as adding a user, or changing user's account.
VIEWER DefaultViewer Can view all information except security logs which are present
within the Easergy P5 protection relay and read their value. A
viewer cannot modify settings and files.
OPERATOR DefaultOperator Has the same rights as Viewer and can perform control actions
and change setting groups.
ENGINEER DefaultEngineer Has the same rights as Operator and can configure and set
Easergy P5 protection relay. He can retrieve and analyze
process data and records, perform control actions and change
setting groups.
INSTALLER DefaultInstaller Has the same rights as Engineer plus the right to upgrade
firmware91; to be used during the engineering phase for
external users. Retrieve Easergy P5 protection relay and
process data during commissioning and change the
configuration and / or setting groups during installation.
SECAUD DefaultSecAud Can read security logs. A security auditor can view equipment
logs and access user authentication logs.
SECADM SecurityAdmin Can change the security policy (user, roles and rights) of
Easergy P5 protection relay.
NOTE: In the security policy, the security administrator account of role type
SecAdm is assigned at least to two security administrators.
The Easergy P5 protection relay's RBAC is compliant with IEC 62351 part 8 and,
with CAE, can be extended further depending on the organisation.
All the roles are password protected and granted up to 256 sessions in one time.
List of rights
The list of rights is defined at:
• Operation level
• Engineering level
• Installation level
• Product manufacturer level
91. For this feature, please contact Schneider Electric for more information.
For customer use, the Easergy P5 protection relays have been designed in order
to allow and control the following usages:
• Read the information provided by the Easergy P5 protection relay:
measurements, status of the controlled and monitored switchgears, settings,
alarms, tripping context
• Open and close the switchgears
• Upload from the protection relay the log files and disturbance record files
• Configure the Easergy P5 protection relay for integration into the cubicle,
protection and control
• Configure the Easergy P5 protection relay for integration into a SCADA
system
These usages are realised by assigning specific right(s) to the users of the
Easergy P5 protection relay based on their role in the protection relay's RBAC.
The followed table shows roles and their rights granted by default for the Easergy
P5 protection relay.
Security ■ ■ ■
Configuration change ■ ■
Control ■ ■ ■
Internal data ■ ■ ■ ■
Configuration read ■ ■ ■ ■
Settings read ■ ■ ■ ■
Read data ■ ■ ■ ■
Debug system ■
Debug application ■
Secure communication ■ ■ ■ ■
Configuration change P5_RightConfigMgt Permission to modify the configuration, it means we can change
any settings which need a reboot of the device, for example,
scaling values like CT ratio or voltage connection mode.
Configuration read P5_RightConfigDft Permission to read the configuration which need a reboot of the
device, for example, scaling values like CT ratio or voltage
connection mode.
Setting change P5_RightSettingMgt Permission to modify any setting which does not need a reboot of
the device, for example, protection or communication settings.
Includes also logic and Mimic configuration in eSetup Easergy
Pro, switching device mode (normal use or tests mode) and
allowing test execution.
Setting read P5_RightSettingDft Permission to read any setting which do not need a reboot of the
device, for example, protection threshold or operation time.
Control P5_RightCtrlObjMgt Permission to perform all kind of operations (select, open and
close all switches, reset and clear alarms), except setting group
change.
Read data P5_RightDataDft Permission to read all the data (i.e., measurements, fixed
parameters (i.e. model number, ….), logs, …
Debug system P5_RightSystemDebug Permission to execute firmware (low level) debug command
(internal manufacturer user)
Secure communication P5_RightSecureComm Permission to connect eSetup Easergy Pro to the Easergy P5
Device user data file read P5_RightUserRootDirDefaultAccess Permission to read through SFTP or eSetup Easergy Pro, user
data in /usr/ directory of file system embedded in the device like
disturbance records, …
Device user data file full P5_RightUserRootDirFullAccess Permission to read, write, delete, transfer through SFTP or eSetup
access Easergy Pro, user data in /usr/ directory of file system embedded
in the device like disturbance records, … except security logs.
Device system data file P5_RightSysRootDirFullAccess Permission to read, write, delete, transfer through SFTP, system
full access data in /sys/ directory of file system embedded in the device
(internal manufacturer user); permission to update, through
eSetup Easergy Pro and the device firmware.
Device cybersecurity data P5_RightCybSecRootDirDefaultAccess Permission to read, write, delete, transfer through CAE,
full access cybersecurity data in /cyb_sec/ directory of file system embedded
in the device.
Backup memory copy P5_RightBackupRootDirDefaultAccess Permission to read, write, delete, transfer through SFTP, back up
memory data in /backup/ directory of file system embedded in the
device.
Function key control P5_RightFnkey0x Permission to operate with the function keys.
with 0x = 01 to 07 There is one permission per function key Fx (x = 1 to 7)
Clear statistics data P5_RightStatMgt Permission to read and clear statistics data like counters, demand,
max, min., thermal level, …
Read statistics data P5_RightStatDft Permission to read only statistics data like counters, demand,
max, min., thermal capacity, …
Internal data P5_RightDescMgt Permission to read and write internal data (internal manufacturer
user)
Login
For login by local panel, go to the User Login menu from the main menu, and then
select the name or role and enter the password. Refer to Login, page 150 for more
information.
For login by eSetup Easergy Pro, Refer to Connecting to a single protection relay
using USB cable, page 163 or Connecting to protection relays via Ethernet, page
163 for more information.
Access lockout
The first invalid password entry sets the counter of failed authorisation and
initiates an attempt timer.
If the user reaches the maximum number of retry, a message with the similar
meaning is displayed and the user is blocked. In this case, only the viewer's
access rights are granted and any other access are blocked.
The maximum failed authorisation is set by CAE. The default is defined at 5 and
can be set until 99. If the value is set to 0, it means there is no limitation.
When the maximum number of failed authorisation is reached, a lockout period is
activated. This lockout period is by default 240 seconds with a maximum of 9999
seconds. It is set by CAE.
If the attempt timer expires, or the correct password is entered before the attempts
counter reaches the maximum number, then the attempts counter is reset to zero.
If a user is blocked out, the block is applied to that named user of all the Easergy
P5 protection relay interfaces. The blocking of one user does not result in blocks
to the others.
If the user entry is blocked, recovering the RBAC or pushing a new RBAC will not
reset the blocked user entry, but an Easergy P5 protection relay reboot will reset
the blocking time and attempts counter, so the user entry will be unblocked.
Logout
For security reasons, it is recommended to logout after any operation on the
Easergy P5 protection relay.
In the main menu screen, Login screen and Mimic screen, a padlock icon is
present in the top-right corner of the title bar to signify that there is no user logged
in to the Easergy P5 protection relay. The padlock icon disappears when any user
logs in.
NOTE: It is recommended to set "Minimum inactivity period" to 10 minutes at
minimum in order to download or upload files during installation, operation and
maintenance.
Number of accounts
The maximum number of user accounts which can be memorised in Easergy P5
protection relay is 32.
A central server is required if more user accounts are required.
Passwords
Changing password
For basic cybersecurity level, the password can be changed from both the local
panel and eSetup Easergy Pro:
• Local panel
Using the ChPwd (Change Password) option in the General Settings menu
• eSetup Easergy Pro
Using the "Change password" option in the (Tools) drop down list in the
tool bar.
The following is an example procedure of changing the password from the local
panel:
1. Log into the device by entering the password.
2. Enter the General Settings menu and select the ChPwd option.
GENERAL SETTINGS
MdbsS
DNP3
I-101
I-103
PortH
IpFilter
ChPwd
CSRst
4. Enter the new password and then enter the password once again for
confirmation.
Change Password
UserName EngineerLevel
NOTE: In step 3 the user can select another user with a lower access right in
order to change the password for that user. This is useful and convenient for
changing password for other users when they have lost their passwords. This
function can also serve as a complement to the password recovery options
described in Factory reset using a reset code, page 477.
NOTE: In step 3 the user can not select another user with a higher access
right in order to change the password for that user. A “Permission denied”
message will appear on the screen.
For advanced cybersecurity level, the change is done exclusively through the CAE
tool in the User Authentication section of the User Accounts menu.
Password complexity
The Easergy P5 protection relay accepts the default user name, "EngineerLevel"
and the default password, "AAAA".
The following password complexity rule is available for both the basic and
advanced security levels.
• Password length must be 1 to 8 characters
• Passwords can contain the following ASCII [33 to 122] characters:
◦ Latin capital letters from A to Z
◦ Latin lowercase characters from a to z
◦ Figures from 0 to 9
◦ Non-alphabetic characters: [ \ ] ^ _ ’ ! “ # $ %` & ‘ ( ) * + , - . / : ; < = > ? @
NOTE: Passwords cannot contain the user account name or parts (no more
than two consecutive characters) of the user's full name. To help to secure
Easergy P5 protection relay, the password should be as longer as possible,
mixing lowercase and uppercase characters, figures and non-alphabetic
characters.
With CAE it is possible to configure the password according to NERC and
IEEE 1686 standard recommendations.
Standard Configuration
provides enough time for the Customer Care Center to manually generate and
send a reset code. The Service Level Agreement (SLA) for reset code generation
is one working day.
To prevent accidental reading of the Easergy P5 reset request code the cell
displays a warning message.
The reset request code will be displayed on confirmation, whereupon the validity
timer will be started.
Note that the reset request code can only be read from the local panel.
Once a new reset request code is generated on the Easergy P5, the reset code
will become invalid, so please make sure the Easergy P5 protection relay is
always powered on before you get the reset code.
Reset code
The reset code can only be obtained from the Schneider Electric Customer Care
Center.
The reset code is intended for password recovery only. It is not a replacement
password that can be used continually. It can only be used once - for password
recovery.
Entry of the reset code causes the Easergy P5 protection relay to reset all
passwords back to factory default.
The "passwords set to default" message is displayed.
The reset code can be applied through any interface, local or remote. It will
achieve the same result irrespective of which interface it is applied through.
Charge is to the user to enter the new appropriate passwords.
NOTICE
RISK OF PASSWORD RECOVERY PROCESS FAILURE
• The reset code is only valid for its corresponding reset request code. Once a
new reset request code is generated on the Easergy P5 protection relay, the
reset code provided by the Customer Care Center becomes invalid.
• Avoid the circumstances that will cause a new reset request code to be
generated by the protection relay before entering the reset code.
Failure to follow these instructions will result in interruption of the
password recovery process.
The passwords can be reset to factory defaults through the following procedure:
1. Get the reset request code from the “RBAC Reset to factory” view of the
General settings menu as illustrated in the following figure.
2 Select “Get request code” from the “RBAC Reset to factory” view
3 Select “on”
4 Reset request code generated and displayed on the screen
7. Enter the reset code obtained in Step 3 above to start the reset.
RBAC recovery
When the withdrawable part of a Easergy P5 protection relay is replaced, the new
one comes with the security policy previously introduced into the protection relay.
Unless the Easergy P5 protection relay has been previously enrolled into the
security system, the factory default RBAC is active. Engineer role is requested in
order to recover the data stored from the back-up memory of the extension
module (option).
Once the new Easergy P5 protection relay is restarted, its security policy is
updated either automatically if a security server is connected or manually with
CAE.
NOTICE
UNAUTHORISED EQUIPMENT TAMPERING
At the first use of the Easergy P5 protection relay, it is recommended to change
the different default passwords according to the rules defined in Password
complexity, page 476.
Failure to follow this instruction can result in unauthorised product use
and setting changes, and compromised security of the information
contained in the product.
When delivered from factory, the Easergy P5 protection relay's RBAC has the
following configuration:
SECAUD – – – – – –
Port hardening
It is possible to disable a communication port from the local panel of Easergy P5
protection relay, from eSetup Easergy Pro, or from the web HMI, with the
ENGINEER access right.
Physical ports which can be disabled:
• Front mini-USB port (for eSetup Easergy Pro connection)
• Rear serial port
• Rear Ethernet port
Each logical port can be independently disabled on each rear Ethernet port and on
the front USB port, which also supports Ethernet.
These logical ports are listed below with Ethernet port number in brackets:
• Communication protocol with eSetup Easergy Pro (Port 22)
• IEC 61850 (Port 102)
• DNP3 over Ethernet (Default on port 20000, configurable by the user)
• Modbus TCP/IP (Default on port 502, configurable by the user)
• EtherNet/IP (Port 44818)
• FTPs (Port 22)
NOTE: The default status of the ports mentioned above are enabled. It is
strongly recommended to disable the ports when they are no longer needed,
to reduce the attack surface to the Easergy P5.
The figure below shows the Port Hardening Configuration settings in the Protocol
Configuration view of the Communication menu in eSetup Easergy Pro:
The port hardening can also be set from the local panel through the Port
hardening config. view of the General menu.
When the ports or the protocols on Ethernet module are disabled or enabled,
reboot of the Easergy P5 protection relay is needed.
NOTE: In addition to port hardening configuration, and in order to prevent
access to the communication ports on the local panel, it is possible to put a
physical seal (See Lock the shutter and handle, page 43).
Upgrades management
When the Easergy P5 protection relay firmware is upgraded – security
configuration remains the same until changed, including usernames and
passwords. It is recommended security configuration is reviewed after an upgrade
to analyze rights for new or changed device features and revoke or apply them
according to your company’s policies and standards.
Revision history
Document version Description
P5/EN M/11A First edition for initial product release
2019-05 Firmware version V01
Release / Build 001.029
Configuration tool eSetup Easergy Pro V2.0.0 or later
CET850 V3.1.2 or later
P5/EN M/22A Firmware version V01
2019-11 Release / Build 200.008
Configuration tool eSetup Easergy Pro V2.2.0 or later
CET850 V3.2.0 or later
Hardware LPCT/LPVT available for P5U20
Ethernet communication module with RSTP redundancy
(reference REL51042)
Local panel Local panel layout enhanced
U2>, U2>> Negative sequence overvoltage protection (ANSI 47)
I0/U0>, I0/U0>> Neutral admittance protection (ANSI 21YN)
N> Motor restart inhibition function (ANSI 66) enhanced
CB monitoring CB monitoring function enhanced
Firmware upgrade Firmware upgrade feature
USB data transfer USB data transfer function available
I2> The following features are available:
I>, I>>
• STI and CO8 curves to the IEC and IEEE curve types,
I0>,
respectively
I0’>, I0’>>
Iφ>, Iφ>> • IDMT reset curve
I0φ>, I0φ>>, I0φ>>>
Logic gate Logic gate number increased to 250
P5/EN M/33A Firmware version V01
2020-07 Release / Build 300.103
Configuration tool eSetup Easergy Pro V3.0.0 or later
CET850 V3.3.0 or later
Hardware 12I4O and 5I5O modules available
24 to 48 V DC voltage power supply module available for
P5x30
Motor speed detection Motor speed detection available
Motor speed>, Motor Motor overspeed (ANSI 12) protection available
speed>>
Motor speed<,Motor Motor underspeed (ANSI 14) protection available
speed<<
ABS Motor Anti-backspin (ABS) protection available
Inrush Inrush detection enhaned
68H2 2nd harmonic detection removed
Order information
Protection relay
The order information can be configured using the procedure provided on
Schneider Electric website www.se.com.
When ordering, please state:
• Type designation;
• Quantity;
• Options (see respective ordering code).
Order information Model Withdrawable HW Fixed HW Version
1 2 3 4 5 6 7 8 9 10 11 12 13
Application P5V20 - - -
Universal current protection P5U20
Voltage protection relay P5V20
Feeder protection with directional P5F30
Motor Protection P5M30
Slot D - Additional I/O
Without (fixed selection for P5U20 and P5V20) A
6DI + 4DO B
3 Arc sensors + 3DI + 3DO C
5DI + 5DO D
12DI + 4DO E
Slot E - Additional I/O
Without (fixed selection for P5U20 and P5V20) A
6DI + 4DO B
3 Arc sensors + 3DI + 3DO C
5DI + 5DO D
12DI + 4DO E
Slot B - Power supply
24 - 250 V DC / 100 - 230 V AC + 4DI + 3DO + WD (P5X20) B
48 - 250 V DC / 100 - 230 V AC + 4DI + 3DO + WD (P5X30) C
24 - 48 V DC + 4DI + 3DO + WD (P5X30) D
Slot C - Additional I/O
without A
6DI + 4DO B
5DI + 5DO D
12DI + 4DO E
Slot A - CT/VT
3 phase CT + 2 residual CT (P5U20) B
3 phase CT + 1 residual CSH (P5U20) C
4 VT (P5V20) D
3 phase CT + 2 residual CT + 4 VT (P5X30) G
3 phase CT + 1 residual CSH + 4 VT (P5X30) H
3 LPCT + 1 residual CSH + 4 LPVT (P5X30 and P5U20) I
Slot L - 2nd Ethernet communicaiton port
Without (fixed selection for P5U20 and P5V20) A
Ethernet TP module with RSTP (2*RJ45) (*) B
Model version
Latest A
Firmware version
Latest A
Cyber Security
Basic A
Advanced B
Languages
English A
English - Chinese B
English - French C
English - Italian E
English - Polish F
English - Portuguese G
English - Russian EAC H
English - Spanish I
English - Trad. Chinese L
NOTE: For the applicable slot occupation rules for your Easergy P5 protection
relay ordered, refer to Slot occupation rules, page 487 to get more details.
Accessories
Order accessories for your Easergy P5 protection relay according to the table
below:
Order code Descrip�on
Communica�on Modules
REL51038 Ethernet TP module - slot M
REL51039 Ethernet FO module - slot M
REL51042 Ethernet TP module - slot L
REL51033 Ethernet HSR/PRP FO module - slots M-N
REL51036 RS485 serial line module - slot N
VW3A8306RC RS485 line termina�on accessory
REL51040 Fiber op�c serial line module - slot N
REL51034 Extension module - slot P
External modules
59641 8 temperature sensor module (MET148-2)
REL51045 IRIG-B module
59660 0.6m remote module connec�on cord
59661 2m remote module connec�on cord
59662 4m remote module connec�on cord
Sensors
59635 Core balance CT, Ø=120mm (CSH120)
59636 Core balance CT, Ø=200mm (CSH200)
59637 Core balance CT, Ø=300mm (CSH300)
EMS59572 VT adapter
EMS59573 LPVT sensor hub
REL52801 Arc accessory VA1DA-20 Arc sensor 20m
REL52802 Arc accessory VA1DA-20S-HF Arc sensor 20m shielded halogen free
REL52803 Arc accessory VA1DA-20S Arc sensor 20m shielded
REL52804 Arc accessory VA1DA-6 Arc sensor 6m connect cable
REL52805 Arc accessory VA1DA-6S-HF Arc sensor 6m shielded halogen free
REL52806 Arc accessory VA1DA-6S Arc sensor 6m shielded
REL52807 Arc accessory VA1EH-20 Arc sensor 20m pipe sensor
REL52808 Arc accessory VA1EH-20S Arc sensor 20m pipe sensor shielded
REL52809 Arc accessory VA1EH-6 Arc sensor 6m pipe sensor
REL52810 Arc accessory VA1EH-6S Arc sensor 6m pipe sensor shielded
Moun�ng accessories
REL51032 20TE flush moun�ng accessory
REL51052 30TE flush moun�ng accessory
REL51021 19inch rack moun�ng accessory
REL51018 30TE blanking plate for rack moun�ng
REL51019 20TE blanking plate for rack moun�ng
REL51020 10TE blanking plate for rack moun�ng
Wiring accessories
REL51054 2-pin comb-busbar for I/O - 100 pcs
REL51055 3-pin comb-busbar for I/O - 100 pcs
REL51056 4-pin comb-busbar for I/O - 50 pcs
REL51057 5-pin comb-busbar for I/O - 50 pcs
REL51058 6-pin comb-busbar for I/O - 50 pcs
REL51059 90° ring wiring terminal red -250 pcs
REL51060 90° ring wiring terminal blue -250 pcs
REL51061 90° ring wiring terminal yellow -250 pcs
Easergy Pro connec�on cable
59700 PC cord USB