EEC Chap.2 Notes
EEC Chap.2 Notes
Total load in the circuit should not exceed 800 watts, and
number of points should not exceed 10 in one circuit.
Lightning and power device should have the different circuits
Minimum size of the conductor in sub circuit should not be
less than 1/8 in case of copper wire and 1/1.4 mm ( 1.5 mm 2)
in case of aluminum wire.
The size of conductor should be such that the voltage drop
should not increase more than 3% of the connected voltage
when full load current is flowing.
All lightning load the fuse wire should not exceed 5 ampere
capacity of power it is 10 ampere.
All D.B. should be marked as power and light.
All the accessories should be fixed on the round block or
board with brass screw.
No inflammable Shades should be used in the installation.
In the domestic wiring three pin plug only should be used.
All the Ironclad appliances, switches etc . Should be Earthed
(e.g. Ceiling fan, bracket,brass holders,etc)
All the switches should be connected through live wire
All the fans should be fitted at the height of 2.5 metres from
the ground.
Neutral should be linked.
Different methods of wiring
a) Looping out from switch and ceiling rose
b) Looping out from switch
c) Looping out from ceiling rose
d) Looping out from junction box
Fan points 1
Plug-points 2
Bed Rooms Light points 2
Fan points 1
Plug-points 1
Fan points 1
Plug-points 1
Fan points 1
Sub circuit 3. -
Full - load current at unity p.f.
= (total load)/(supply voltage)x(power factor)
=
= ______ Ampere
Considering maximum current = 1.5 times full-load current
Therefore , Maximum current = 1.5 x ______ Ampere
Selection of ___ PVC wire in this
3 represent - no. of conductor and
20 represent gauge of each conductor.
Fuse used - ___ A
For reference -
https://www.youtube.com/watch?v=oeWj_yhIuPo&t=713s
selection of wires
single strand 1.4 mm diagram aluminium 250 volt glade wire
capable of 9 ampere current is suitable (TRS type).
other details
Ceiling height 3.5 metres
height of horizontal run from
ground floor level 3 metres
switch board 1.5 metres
from ground level
metre board distance is 0.5
metre
Downward run 1.5 metres
vertical run 0.5 metres
Wastage = 10%
Total length required = 14 + 1.4 = 15.4
= 16m (Approxi.)
Solution -
calculation for total load
Hall : load or of 20 fluorescent lamp = 20x40=800W
load of 10 ceiling fans = 10x60=600W
kitchen: load of 5 fluorescent lamp =5x40=200W
load of 2 exhaust fan = 2x100=200W
load of 5 PowerPoint = 5 x1000 = 5000W
load of Store :
load of two fluorescent lamp = 2x40=80W
load of 15 ampere plug socket = 1x1000=1000W
load of corridor:
load of 4 CFL lamp = 15x4 = 60W
Total load of restaurant = 7940W
the total load is more than three kilowatt, 3 phase 4 wire service
connection will be provide. as having power factor of installation
has 0.8; calculate line current from
W = √3 x Vl xIl x cosΦ
Substituting values Il = 14.325
Considering max. Current = 1.5 x 14.325 A
Hence for mains we will provide PVC wire of 7/20 , having
current rating of 28 Amp.We will divide the load into power and
light loads.
Total light and fan load = 1940W
Total power load = 6000W
Total light and fan points = 43 Nos.
Total light and fan points = 6 Nos.
We will divide 6 power in 3 sub circuit , each of 2000W and will be
connected between one phase and neutral each.
Load current of each power sub circuit = (2000)/(230 x 0.8)
=_____
Considering max. Current = 1.5 times of Load current
Load current = 16.30 A.
Hence Wire provide for power sub circuit 7/20 PVC wire having
current rating of 20 amperes.
Phase R = 9 tubes + 3 fans + 1 exhaust = 13 points = 640 W
Phase Y = 9 tubes + 3 fans + 1 exhaust = 13 points = 640 W
Phase B = 9 tubes + 4 fans + 4 CFL = 17 points
= 360+240+60 = 660 W
The light and Fan load on Phase R will be divided into two sub
circuit. One Sub circuit will consist of 6 tubes + 2 ceiling fans =
360 watts. And second will have 3 tubes + 1 ceiling + 1 exhaust
fan = 280W
Similar arrangement will be on Phase Y, wild phase B will have
no to sub circuit consisting of one sub circuit will consist of 5
tubes , 1 fan and two CFL = 290W. And other 4 tubes,3 fan and
two CFL = 370W
Now, we will calculate load current of each sub circuit
Consider load of 370 W = Il =
Load current =
I max =
For standard table of wire, PVC 1/18 copper wire having current
rating of 5 ampere will be used for all light and Fan circuit.
now maximum load for circuit will be = 2646.6 W
Load current on each phase =
I max=
Here 7/20 wire will be used for each phase circuit. now we will be
represent th arrangement of circuit and sub circuit etc. of
installation.
Considering ,
Hence 3/20 PVC copper wire will be used for mains. load will be
divided on all the three phases equally i.e., 1260 W on each
phase i.e, 21 points each of 60 W will be provided on each
phase.21 points will be divided into 3 sub circuit ,each consisting
of 7 points,i.e., 420 watts , with maximum current of 3.4 amp. Will
be provided by ⅛ wire copper.
Form sub circuit from main switch to distribution board, wire of
3/22 PVC copper will be provided , having maximum current of 15
amp . The arrangement of distribution board with their sub circuit
is shown in figure.
Il = total power =
Voltage
Maximum permissible leakage current = Il
5000
Maximum permissible insulation
resistance = supply voltage
maximum permissible leakage current
Rule 58 -
The point of commencement of supply of energy to a
consumer shall be Deemed to be the point at the outgoing
terminals of cutout inserted by the supplier in each conductor
of every service line other than an Earth or Earth neutral
conductor or Earth external conductor of a concentric Cable
at consumer premises.
When the service line is provided with the help of an
overhead line, it must have fixed minimum clearance above
ground of the lowest conductor and definite clearance must
be provided from the adjacent building. This are controlled
by Indian Electricity rules 77 and 79 which are as given
below
Rule 77 -
1) no conductor of an overhead line, including service lines,
erected across a street shall at any part there of be at the height
less than
a) for low and medium voltage line - 5.795m
b) for high voltage line - 6.10m
2)no conductor of an overhead line, including service line, erected
along any street shall at any part there of be at a height less than
a) for low and medium voltage line - 5.490m
b) for high voltage line - 5.795m
3)no conductor of an overhead line, including service line, erected
elsewhere than along or across any street shall be at the height
less than
a) for low medium and high voltage line up to and including 11000
volts, if bare - 4.575m
b) for low medium and high voltage line up to and including 11000
volts, if insulated - 3.965m
c)For high voltage line above 11000 volts - 5.185m
4) for extra High Voltage line the clearance ground shall not be
less than 5.185m + 0.305m for every 33000 volts or part there of
by which the voltage line exceed 33000 volts
provided that the minimum clearance along or across any street
shall not less than 6.10m
Rule 79 -
Where a low or medium voltage overhead line passes above or
adjacent to or terminate on any building ; the following minimum
clearance from any accessible point , on the basis of maximum
sag shall be observed :
a) for any flat roof, open balcony, verandah roof and lean of roof
i)when the line passes above the building a vertical clearance of
2.44m from the highest point
ii) when the line passes adjacent to building a vertical clearance
of 1.22m from the nearest point
b) for pitched roof -
i) when the line above the building, a vertical clearance of 2.44m
immediately under the lines
ii) when the line passes adjacent to the building, a horizontal
clearance of 1.22m
2) any conductor so situated as to have clearance less than that
specified in sub-rule 1) shall be adequately insulated and shall be
attached by means of metal chips at suitable interval to a bear
Earth and wear wire having a breaking strength of not less than
317.52 Kg.
3)the horizontal clearance shall be measure when the line is at
maximum deflection from the vertical due to wind pressure.
Overhead service main
The overhead Service main can be had in a number of ways
depending upon condition prevailing
1) Service main for a Double storey building is as shown in
figure below,
when the connection from overhead bare aluminium
conductor are brought to the buildings side by weatherproof
cable PVC cable.
2) Service mains for single storey house
When an overhead is to be given to a single story house a g i
pipe