COMPUTATION:
I. Typical Load ( C.O.+ Lighting Load + Ref) = ( 9.6 + 1.74 + 3 )A = 14.34A COMPUTATION:
II.Other Loads: I. Typical Load ( C.O.+ Lighting Load + Ref) = ( 9.6 + 1.74 + 3 )A = 14.34A
1 Unit 1 Hp, Electric motor = 8 Amperes II.Other Loads:
1 Units Shower Heater (14.7A)(0.75), (Table 2.20.3.16 Column A) = 11.03 Amperes 1 Unit 1 Hp, Electric motor = 8 Amperes
III.Total Current = ( 14.34 + 8 + 11.03) = 33.37A x (0.8 D.F.) = 26.69 Amperes 1 Units Shower Heater (14.7A)(0.75), (Table 2.20.3.16 Column A) = 11.03 Amperes
IV. Main - Feeder: III.Total Current = ( 14.34 + 8 + 11.03) = 33.37A x (0.8 D.F.) = 26.69 Amperes
= (26.69 + 0.25 x 10A) = 29.19 Amperes IV. Main - Feeder:
For flexibility and voltage drop, use 2 x 22 mm2 THHN wire from the panel board to the = (26.69 + 0.25 x 10A) = 29.19 Amperes
electrical gutter. For flexibility and voltage drop, use 2 x 22 mm2 THHN wire from the panel board to the
V. Main - Protection: electrical gutter.
= (26.69 + 0.25 x 10A) = 29.19 Amperes V. Main - Protection:
Use 100A, 2 pole main circuit breaker. = (26.69 + 0.25 x 10A) = 29.19 Amperes
Use 100A, 2 pole main circuit breaker.
COMPUTATION:
I. Typical Load ( C.O.+ Lighting Load + Ref) = ( 12 + 2.04)A = 14.04A COMPUTATION:
II.Other Loads: I. Typical Load ( C.O.+ Lighting Load + Ref) = ( 12 + 2.04)A = 14.04A
1 Unit 1.5 Hp, ACU = 10 Amperes II.Other Loads:
2 Units 1 Hp, ACU (2x8A) = 16 Amperes 1 Unit 1.5 Hp, ACU = 10 Amperes
2 Units Shower Heater (2 x 14.7A)(0.75), (Table 2.20.3.16 Column A) = 22.05 Amperes 2 Units 1 Hp, ACU (2x8A) = 16 Amperes
III.Total Current = ( 14.04 + 10 + 16 + 22.05) = 62.09A x (0.8 D.F.) = 49.67 Amperes 2 Units Shower Heater (2 x 14.7A)(0.75), (Table 2.20.3.16 Column A) = 22.05 Amperes
IV. Main - Feeder: III.Total Current = ( 14.04 + 10 + 16 + 22.05) = 62.09A x (0.8 D.F.) = 49.67 Amperes
= (49.67 + 0.25 x 10A) = 52.17 Amperes IV. Main - Feeder:
For flexibility and voltage drop, use 2 x 22 mm2 THHN wire from the panel board to the = (49.67 + 0.25 x 10A) = 52.17 Amperes
electrical gutter. For flexibility and voltage drop, use 2 x 22 mm2 THHN wire from the panel board to the
V. Main - Protection: electrical gutter.
= (49.67 + 0.25 x 10A) = 52.17 Amperes V. Main - Protection:
Use 100A, 2 pole main circuit breaker. = (49.67 + 0.25 x 10A) = 52.17 Amperes
Use 100A, 2 pole main circuit breaker.
Logo: Designed by: Approved By: Title: Owner / Location: Sheet Content: Sheet No.:
TIN Number: 165-733-887
REX IVAN R. GRAYCOCHEA Reg. No.: 023456
Future Electrical Engineer PABLO DIAZ GURTIZA, JR. Validity: February 2026 2