Product Report_30XB0800

The document provides performance specifications for a 720 kW air-cooled chiller with a fixed-speed screw compressor, including cooling efficiency, sound levels, and operating conditions. It details the unit's cooling capacity, refrigerant type, and electrical information. Additionally, it includes documentation references such as PSD, IOM, and technical drawings.

Uploaded by

Sajin Sivadasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views

Product Report_30XB0800

The document provides performance specifications for a 720 kW air-cooled chiller with a fixed-speed screw compressor, including cooling efficiency, sound levels, and operating conditions. It details the unit's cooling capacity, refrigerant type, and electrical information. Additionally, it includes documentation references such as PSD, IOM, and technical drawings.

Uploaded by

Sajin Sivadasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Standard Report Project

Selection for CLYDE Consultant


Tag
Brain Kumaran (9/26/2023 10:12:11 AM) CH-1

30XB 0800
Air-cooled chiller with xed-speed screw compressor

Performance Information
Mode Cooling
Cooling Capacity (1) kW 720
Cooling E ciency (COPR) (1) kW/kW 2.409
Unit Power Input (1) kW 298.7
Sound power level (LwA) (1) dB(A) 98.0
Sound Pressure Level at 10.0m
dB(A) 65.4
(LpA) (1)
Minimum Capacity (2) kW 78.3
Maximum Capacity kW 720
(1) All performances are compliant with AHRI Standard 551/591 (SI). Sound Power level according to
ISO9614-1.
(2) Due to the minimum flow rate allowable a lower inlet water temperature might have to be specified to
achieve this performance.
Non contractual picture

Operating Conditions
System element Cooling
Seasonal E ciency
Water heat exchanger IPLV.SI kW/kW 4.494
NPLV.SI kW/kW 4.163
Fluid Type Fresh Water
Fouling Factor(3) (sqm-K)/kW 0.0176
Leaving Temperature °C 7.20 Unit Information
Fluid

Entering Temperature °C 12.70 Refrigerant type R-134a


Fluid Flow l/s 31.19 Refrigerant Weight kg 130
Total pressure drop kPa 25.9 Tonnes CO2 Equivalent Tonnes 186
Air heat exchanger Category PED CAT IV
Number of Refrigerant Circuit 2
Air Entering Air Temperature °C 46.0
Number of Passes (Evaporator) 2
Altitude m 0
Number of Compressor 2
Distance from coast > 3km
Number of Fan 12
(3) The impact of fouling factor is calculated as per AHRI 550/590-551/591 method Fan Power Input kW 19.59
Operating / Shipping Weight kg 5767/5648
Unit Dimensions (LxWxH) mm 7186x2253x2322
Unit Con guration
149 Bacnet over IP
15 Low noise level Electric Information
281 Evaporator with aluminum jacket Unit Voltage V-Ph-Hz 400-3-50
93A Compressor discharge valves Standby Power W 200
Power Factor 0.87
Electrical Circuit Supply 1
Maximum Current A 544
Startup Current A 813
Current at AHRI Conditions A 419

Documentation
PSD
IOM
Technical drawing
Revit le

Package Chiller Builder-EMEA v5.08.0.0 (date 9/27/2023) Page 1/1