Sunline Magnum ZF
Sunline Magnum ZF
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Prior Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Component Location
(ZF shown)
HIGH
EFFICIENCY COPPER TUBE/ALUMINUM FIN
20 GAUGE
COMPRESSORS CONDENSER COILS
ALUMINIZED STEEL
TUBULAR HEAT EXCHANGERS
LONG LASTING
POWDER PAINT FINISH
ELECTRICAL
DISCONNECT
MOUNTING
LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL
WIRING ENTRY
KNOCKOUT
FOR SIDE
2" DISPOSABLE
POWER WIRING
FILTERS
ENTRY SIDE
GAS/ELECTRIC
BELT-DRIVE
1" NPTI BLOWER MOTOR UNIT SHOWN
CONDENSATE DRAIN
FULL PERIMETER
14 GAUGE BASE RAILS
WITH LIFTING HOLES
Nomenclature
Refrigeration
Heat Capacity
A = Standard Refrigeration
00 = Cooling Only B = ECC (E-Coat Cond Coil)
C = EEC (E-Coat Evap Coil)
Gas MBH Input
F = ECC,EEC
30 = 300 MBH Input
40 = 400 MBH Input
Controls Option
Sensors
Voltage
A = No Sensors
7 = 380/415-3-50 B = PHM (Phase Monitor)
C = DFS (Dirty Filter Switch)
Outdoor Air Option D = SAD (Supply Air Smoke DET)
E = RSD (Return Air Smoke DET)
A = No Economizer F = PHM,DFS
B = Economizer w/Barometric RLF1 G = PHM,SAD
C = Economizer w/o Barometric RLF H = PHM,RSD
D = Economizer w/Power EXH1 J = DFS,SAD
H = Motorized Damper K = DFS,RSD
J = Motorized Damper w/Baro RLF1 L = SAD,RSD
M = PHM,DFS,SAD
Note: 1. Available Downflow Only N = PHM,DFS,RSD
P = PHM,SAD,RSD
Q = DFS,SAD,RSD
Service Options
R = PHM,DFS,SAD,RSD
1 = No Service Options
2 = DSC (Disconnect Switch)
Prior Nomenclature
Standard Cabinet Hinged Filter Door & Tool Free Access Cabinet
Airflow
AA = None BA = Hinged Filter Door & Tool Free Access Panels
A = Hi Static AB = Phase Monitor BB = Phase Monitor, Hinged Filter Door & Tool Free
B = Hi Static/Economizer AC = Coil Guard Access Panels
C = Hi Static/Economizer/Power Exhaust AD = Dirty Filter Switch BC = Coil Guard, Hinged Filter Door & Tool Free
(Downflow Only) AE = Phase Monitor & Coil Guard Access Panels
D = Hi Static/Motorized Damper AF = Phase Monitor & Dirty Filter Switch BD = Dirty Filter Switch, Hinged Filter Door &
E = Hi Static/Motorized Damper/Barometric Relief AG = Coil Guard & Dirty Filter Switch Tool Free Access Panels
J = Hi Static/Economizer/Barometric Relief AH = Phase Monitor, Coil Guard & Dirty Filter Switch BE = Phase Monitor & Coil Guard, Hinged Filter
RC = Coil Guard & American Flag Door & Tool Free Access Panels
TA = Technicoat Condenser Coil BF = Phase Monitor & Dirty Filter Switch, Hinged
Voltage TJ = Technicoat Evaporator Coil Filter Door & Tool Free Access Panels
TS = Technicoat Evaporator & Condenser Coils BG = Coil Guard & Dirty Filter Switch, Hinged Filter
7 = 380/415-3-50 Door & Tool Free Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
L = Options 1,3 & 4
R = Options 3 & 4
Options
1 = Disconnect
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
• On-board USB Port - The new control comes with a long • Full Perimeter Base Rails - The permanently attached
list of features including data logging, current and base rails provide a solid foundation for the entire unit and
previous system faults and software update capabilities protect the unit during shipment. The rails offer rigging
using the on board USB port and common flash drive. holes so that an overhead crane can be used to place the
Energy use monitoring capabilities allow custom tailoring units on a roof.
to allow a system to work more efficiently at all times and • Easy Installation - Gas and electric utility knockouts are
occupancy levels. Self test and start-up reports also supplied in the unit underside as well as the side of the
available from the board VIA the USB port. unit. Utility connections can be made quickly and with a
• Embedded LCD Display - The board has a easy to read, minimum amount of field labor. All units are shipped with
built-in LCD display and easy to use navigation joystick 2" throw-away filters installed.
and buttons allowing the user to quickly navigate the • Wide Range of Indoor Airflows - All supply air blowers
menus displaying unit status, options, current function, are equipped with a belt drive that can be adjusted to
supply, return and outdoor temperatures, fault codes and meet the exact requirements of the job.
other information. • Warranty - All models include a 1-year limited warranty
• Safety Monitoring - The control monitors the outdoor, on the complete unit. Compressors each carry a 5-year
supply, and return air temperatures and the high and low warranty. Aluminized steel and stainless steel tubular heat
pressure switch status on the independent refrigerant exchangers carry a 10- year warranty.
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and Factory Installed Options
electric heating units. The control also monitors the YORK® offers several equipment options factory installed, for
voltage supplied to the unit and will protect the unit if low the ZF Series.
voltage due to a brown out, or other electrical issue • Dry Bulb Economizers - All units offer a variety of
occurs. optional factory installed down flow economizers that are
• Low Ambient - An integrated low-ambient control allows shipped, installed and wired with low leak dampers
units to operate in the cooling mode down to 0°F outdoor designed to meet ASHRAE 90.1-2010, AMCA 511 Class
ambient without additional components or intervention. 1A damper, and the International Energy Conservation
Optionally, the control board can be programmed to Code (IECC) certification requirements by achieving
lockout the compressors when the outdoor air leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
temperature is low or when free cooling is available. economizer goes through a rigorous 60,000 cycle test.
• Anti-Short Cycle Protection - To aid compressor life, an Dry bulb, single enthalpy, and dual enthalpy (with field
anti- short cycle delay is incorporated into the standard installed kit) can be selected. All economizer options are
control. Compressor reliability is further ensured by fully integrated into the Simplicity® SE controls. The
programmable minimum run times. For testing, the anti- economizer has spring return, fully modulating damper
short cycle delay can be temporarily overridden with the actuators and is capable of introducing up to 100%
push of a button. outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from
• Fan Delays - Fan on and fan off delays are fully
mechanical refrigeration to economizer operation is
programmable. Furthermore, the heating and cooling fan
regulated by the outdoor air dry bulb temperature or the
delay times are independent of one another. All units are
outdoor air enthalpy input. The dual enthalpy kit provides
programmed with default values based upon their
a second input used to monitor the return air (field
configuration of cooling and/or heating capacity.
installed). The installer needs only to assemble the
• Nuisance Trip Protection and Three Strikes - To outdoor air hood, attach the enthalpy control the hood and
prevent nuisance calls, the control board uses a three mount the hood to the unit (Hood and control are
times, you're out philosophy. The high, low-pressure provided).
switch, anti-freeze protection, low voltage or heating high
• Power Exhaust - Our economizer options are available
limit must trip three times within two hours before the unit
with power exhaust. Whenever the outdoor air intake
control board will lock out the associated compressor.An
dampers are opened for free cooling, the exhaust fan will
alarm message will be displayed on the LCD screen.
be energized to prevent the conditioned space from being
• Lead-Lag - An integrated Lead-Lag option allows equal over-pressurized during economizer operation.
run time hours on all compressors, thereby extending The exhaust fan, motor and controls are installed and
the life of all compressors. This option is selectable on wired at the factory. The rain hood must be assembled
the unit control board. and installed in the field.
• Reliable - From the beginning - All units undergo The power exhaust option can only be used on bottom
computer automated testing before they leave the factory. duct configurations.
Units are tested for refrigerant charge and pressure, unit
• Motorized Outdoor Air Intake Damper - Includes a
amperage, and 100% functionality. For the long term - All
slide-in / plug-in damper assembly with a 2- position,
units are painted with a long lasting, powder paint that
spring return motor actuator which opens to a pre-set
stands up over the life of the unit. The paint used has
position whenever the supply air blower is operating and
been proven by a 1000 hour salt spray test.
will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must NOTE: Knobs are shipped separately within the unit to prevent
be field assembled before installing. shipping damage. These must be field installed for tool
• Barometric Relief Damper - This damper option can be free operation.
used to relieve internal building air pressure on units with • Hinged/"Tool Free" Blower, Blower Motor, Filter And
an economizer without power exhaust. This accessory Electric Access Panels - This option allows for complete
includes a rain hood, a bird screen and a fully assembled hinged and tool free access to the unit’s blower, blower
damper. With bottom duct connections, the damper motor, filters and electrical panel sections.
should be mounted over the opening in the return air
panel. With horizontal ductwork, the accessory should be Control Options
mounted on the return air duct.
Simplicity® SE with Communication Option Control -
• E-Coat Condenser Coils - The condenser coils are The York® Simplicity® SE with Communication Option
coated with an epoxy polymer coating to protect against Control is factory installed. It includes all the features of
corrosion. the Simplicity® SE control with an additional gateway to
• E-Coat Evaporator Coils - The evaporator coils are BACnet MS/TP (programmable to Modbus or N2
coated with an epoxy polymer coating to protect against protocols).
corrosion.
Novar® BAS Control - The Novar® building automation
• Filter Options - Standard units are shipped with 2" throw- system controller is factory installed. Incudes supply air
away filters installed. 2" pleated and 4" pleated filters are sensor, return air sensor, dirty filter indicator switch, and
offered as a factory installed option. air proving switch.
• Disconnect Switch - For gas heat units a HACR breaker
CPC BAS Control - The Computer Process Controls
sized to the unit is provided.
Model 810-3060 ARTC Advanced Rooftop building
• Smoke Detectors - (supply air & return air) The smoke automation system controller is factory installed. Includes
detectors stop operation of the unit by interrupting power supply air sensor, return air sensor, dirty filter indicator
to the control board if smoke is detected within the air switch and air proving switch.
compartment.
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Factory installed smoke detectors in the return air, may
Field Installed Accessories
be subjected to freezing temperatures during “off” times
due to out side air infiltration. these smoke detectors have YORK® offers several equipment accessories for field
an operational limit of 32°F to 131°F. smoke detectors installation, for the ZF Series.
installed in areas that could be out side those limitations Dry Bulb Economizers - All units offer a variety of
will have to be moved to prevent having false alarms. optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers
• Coil Guard - Customers can purchase a coil guard kit to designed to meet ASHRAE 90.1-2010, AMCA 511 Class
protect the condenser coil from damage. This is not a hail 1A damper, and the International Energy Conservation
guard kit. Code (IECC) certification requirements by achieving
• Stainless Steel Heat Exchanger - For applications in leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
corrosive environments, this option provides a full economizer goes through a rigorous 60,000 cycle test.
stainless steel heat exchanger assembly. Dry bulb, single enthalpy, and dual enthalpy (with field
• Stainless Steel Drain Pan - An optional rustproof installed kit) can be selected. All economizer options are
stainless steel drain pan is available to provide years of fully integrated into the Simplicity SE controls. The
trouble-free operation in corrosive environments. economizer has spring return, fully modulating damper
• Phase Monitors - Designed to prevent unit damage. The actuators and is capable of introducing up to 100%
phase monitor will shut the unit down in an out-of phase outdoor air. As the outdoor air intake dampers open, the
condition. return air dampers close. The changeover from
• Dirty Filter Switch - This kit includes a differential mechanical refrigeration to economizer operation is
pressure switch that energizes the fault light on the unit regulated by the outdoor air dry bulb temperature or the
thermostat, indicating that there is an abnormally high outdoor air enthalpy input. The dual enthalpy kit provides
pressure drop across the filters. Factory installed option or a second input used to monitor the return air (field
field installed accessory. installed). The installer needs only to assemble the
• Hinged Filter Door/"Tool Free" Blower And Access outdoor air hood, attach the enthalpy control the hood and
Panels (Not Hinged) - This option allows for easy access mount the hood to the unit (Hood and control are
and maintenance. provided).
• Motorized Outdoor Air Intake Damper - Includes a
slide-in / plug-in damper assembly with a 2-position,
spring return motor actuator which opens to some pre-set Guide Specifications
position whenever the supply air blower is operating and
will drive fully closed when the blower unit shuts down. General
The rain hood is painted to match the basic unit and must
be field assembled before installing. Units shall be manufactured by Johnson Controls Unitary
• Roof Curbs - Fourteen-inch high roof curbs provide a Products in an ISO 9001 certified facility.
water-tight seal between the unit and the finished roof. ZF models have 2 condenser fan motors and compressors. All
These full perimeter curbs meet the requirements of the compressors include crankcase heat and internal discharge
National Roofing Contractors Association (NRCA) and are temperature protection. Every refrigerant circuit includes an
shipped knocked-down for field assembly. expansion valve, a liquid line filter-drier, a discharge line high
They're designed to fit inside the base rails of the unit and pressure switch and a suction line with a freezestat and low
include both a wood nailing strip and duct hanger supports. pressure/loss of charge switch. The unit control circuit includes
• High Altitude Natural Gas - Burner orifices and pilot 75 VA and 150 VA transformers, a 24-volt circuit breaker and a
orifices are provided for proper furnace operation at relay board with two compressor lockout circuits, a terminal
altitudes up to 6,000 feet. strip for thermostat wiring, plus an additional set of pin
• Propane - Burner orifices, pilot orifices and gas valve parts connectors to simplify the interface of additional field controls.
are provided to convert a natural gas furnace to propane. All units have long lasting powder paint cabinets with 1000 hour
• High Altitude Propane - Burner orifices and pilot orifices salt spray test approval under ASTM-B117 procedures. All
are provided for proper furnace operation at altitudes up models include a 1-year limited warranty on the complete unit.
to 6,000 feet. This accessory supplements the basic Compressors and electric heater elements carry an additional
propane conversion kit. 4-year warranty. Aluminized steel tubular heat exchangers
carry an additional 9-year warranty.
• Side Duct Flanges - One-inch flanges replace the supply
and return air panels on the rear of the unit to accommodate
Description
horizontal duct connections. These flanges can also be used
individually for bottom supply / horizontal return or horizontal ZF units shall be factory-assembled, single packaged, ZF***N
supply/bottom return. They cannot be used on units with Electric Cooling/Gas Heat, ZF***C Cooling designed for outdoor
power exhaust. mounted installation.
• Barometric Relief Damper - This damper accessory can
be used to relieve internal building air pressure on units They shall have built-in field convertible duct connections for
with an economizer without power exhaust. This down discharge supply/return or horizontal discharge supply/
accessory includes a rain hood, a bird screen and a fully return, and be available with factory installed options or field
assembled damper. With bottom duct connections, the installed accessories. The units shall be factory wired, piped,
damper should be mounted over the opening in the return charged with R-410A refrigerant and factory tested prior to
air panel. With horizontal ductwork, the accessory should shipment. All unit wiring shall be both numbered and color
be mounted on the return air duct. coded. All units shall be manufactured in a facility certified to
• Enthalpy Accessory Control Kit - This kit contains the ISO 9001 standards and the cooling performance shall be rated
required components to convert a single enthalpy in accordance with DOE and AHRI test procedures. Units shall
economizer to dual enthalpy. be classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No.
236-M90 conditions.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work. Unit Cabinet
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper Unit cabinet shall be constructed of galvanized steel, with
exhausting of furnace combustion products, this kit can be exterior surfaces coated with a non-chalking, powdered paint
installed to prevent the flue exhaust from entering nearby finish, certified at 1000 hours salt spray test per ASTM-B117
fresh air intakes. standards. Indoor blower section shall be insulated with a
• Wood Skid - Allows unit to be handled with 90" forks. minimum 1/2" thick insulation, coated on the airside. Aluminum
• CO2 Sensor - Senses CO2 levels and automatically foil faced insulation shall be used in the furnace compartment
overrides the economizer when levels rise above the and be fastened with rigid fasteners to prevent insulation from
present limits. entering the air stream. Cabinet panels shall be easily
• Coil Guard - Customers can purchase a coil guard kit to removable for servicing and maintenance. Full perimeter base
protect the condenser coil from damage. This is not a hail rails shall be provided to assure reliable transit of equipment,
guard kit. overhead rigging and proper sealing on roof curb applications.
Disposable 2" filters shall be furnished and be accessible
• Phase Monitors - Designed to prevent unit damage. The
through a removable access door, sealed airtight. Units filter
phase monitor will shut the unit down in an out-of phase
track shall be designed to accommodate either 2" or 4" filters.
condition.
Fan performance measuring ports shall be provided on the
outside of the cabinet to allow accurate air measurements of
evaporator fan performance without removing panels or
creating air by-pass of the coils. Condensate pan shall be d. The refrigeration system shall provide at least 10° F of
internally sloped and conform to ASHRAE 62-89 self-draining sub-cooling at design conditions.
standards. Condensate connection shall be a minimum of 1"
e. All models shall have two independent circuits.
I.D. female and be a ridged mount connection. Unit shall
incorporate a fixed outdoor air damper with an outdoor air Unit Controls
intake opening covered with a bird screen and a rain hood
painted to match the exterior of the unit. a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
Indoor (Evaporator) Fan Assembly the 24-volt transformer side.
Fan shall be a belt drive assembly and include an adjustable- b. Unit shall incorporate a lockout circuit which provides
pitch motor pulley. Job site selected (B.H.P.) brake horsepower reset capability at the space thermostat or base unit,
shall not exceed the motors nameplate horsepower rating, plus should any of the following standard safety devices trip
the service factor. Units shall be designed not to operate above and shut off compressor.
service factor. Fan wheel shall be double-inlet type with c. Loss-of-charge/Low-pressure switch.
forward-curved blades, dynamically balanced to operate
1. High-pressure switch.
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. 2. Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, a LED (light-emitting
Outdoor (Condenser) Fan Assembly diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
The outdoor fans shall be of the direct-driven propeller type,
d. Unit shall incorporate "AUTO RESET" compressor over
discharge air vertically, have aluminum blades riveted to
temperature, over current protection.
corrosion resistant steel spider brackets and shall be
dynamically balanced for smooth operation. The 2 outdoor fan e. Unit shall operate with conventional thermostat designs
motors shall be totally enclosed with permanently lubricated and have a low voltage terminal strip for easy hook-up.
bearings, internally protected against overload conditions and
f. Unit control board shall have on-board diagnostics and
staged independently.
fault code display.
Refrigerant Components g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
Compressors: 25°F.
a. Shall be Scroll compressors internally protected with
h. Control board shall monitor each refrigerant safety switch
internal discharge temperature protection over
independently.
temperature protection.
i. Control board shall retain last 5 fault codes in non volatile
b. Shall have internal spring isolation and sound muffling to
memory, which will not be lost in the event of a power
minimize vibration and noise, and be externally isolated
loss.
on a dedicated, independent mounting.
Coils: Gas Heating Section (ZF***N Models)
a. Evaporator and condenser coils shall have aluminum Shall be designed with induced draft combustion with post purge
plate fins mechanically bonded to seamless internally logic and energy saving direct spark ignition, redundant main gas
enhanced copper tubes with all joints brazed. Special valve. Ventor wheel shall be constructed of stainless steel for
Phenolic coating shall be available as a factory option. corrosion resistance. The heat exchanger shall be of the tubular
b. Evaporator and Condenser coils shall be of the direct type, constructed of T1-40 aluminized steel for corrosion
expansion, draw-thru, design. resistance and allowing minimum mixed air entering temperature
of 25 °F. Burners shall be of the in-shot type, constructed of
Refrigerant Circuit and Refrigerant Safety Components shall
aluminum coated steel and contain air mixture adjustments. All
include:
gas piping shall enter the unit cabinet at a single location through
a. Balance-port thermostatic expansion valve with either the side or curb, without any field modifications. An
independent circuit feed system. integrated control board shall provide timed control of evaporator
b. Filter drier/strainer to eliminate any moisture or foreign fan functioning and burner ignition. Heating section shall be
matter. provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure b. Induced draft motor speed sensor.
refrigerant pressure during any necessary servicing or
c. Flame roll out switch (automatic reset).
troubleshooting, without losing charge.
d. Flame proving controls. Unit shall have two independent
stages of capacity.
Unit shall be capable of starting and running at 125° F outdoor • Roof Curb - 14" high, full perimeter curb with wood nailer
temperature, exceeding maximum load criteria of AHRI (shipped knocked-down).
Standard 340/360. The compressor, with standard controls, • 100% Barometric Relief Damper - Contains a rain hood,
shall be capable of operation down to 25° F outdoor air inlet screen, exhaust damper and mounting hardware.
temperature. Unit shall be provided with fan time delay to Used to relieve internal air pressure through the unit.
prevent cold air delivery before heat exchanger warms up (Gas • Propane Conversion Kit - Contains new orifices and gas
heat only). valve parts to convert from natural to L.P. gas. One per
unit required.
Electrical Requirements
• High Altitude - Natural Gas - Contains orifices required
All unit power wiring shall enter unit cabinet at a single factory for applications between 2000 and 6000 feet altitude.
provided location and be capable of side or bottom entry, to
• High Altitude - Propane Gas - Contains orifices required
minimize roof penetrations and avoid unit field modifications.
for applications between 2000 and 6000 feet altitude.
Separate side and bottom openings shall be provided for the
Must be used with propane conversion kit.
control wiring.
• Burglar Bars - Designed to work with above roof curbs,
Standard Limited Warranties depending on unit model. Fits duct openings of curb
supply and return air openings.
• Compressor 5 Years
• Side Duct Flange - Supply and return air duct flanges for
• Heat Exchanger 10 Years
side duct applications. Do not use on units with power
• Other Parts 1 Year exhaust.
Optional Outdoor Air (Shall be made available by either/or): • Wood Skid - Allows unit to be handled with 90" forks.
• Economizer/motorized Damper Rain Hood
• Dry Bulb Economizer - Outdoor and return air dampers (ZFN/E/C240 only) - Contains all hood panels and the
that are interlocked and positioned by a fully-modulating, hardware for assembling.
spring-return damper actuator. The maximum leakage
• Anti-Recycle Timer - Assures 5-minute off time between
rate for the outdoor air intake dampers shall be designed
compressor cycles.
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A
damper, and the International Energy Conservation Code • Coil Guard Kit - Guard for cooling coil.
(IECC) certification requirements by achieving leakage
OTHER FACTORY INSTALLED OPTIONS
rates of 3 cfm/sq. ft. at 1" of static pressure. During
economizer operation, a mixed-air temperature control • Power Exhaust Option - To work in conjunction with
shall modulate the outdoor and return air damper economizers.
assembly to prevent the supply air temperature from • Stainless Steel Heat Exchanger
dropping below 55°F. Changeover from compressor to
• Stainless Steel Drain Pan
economizer operation shall be provided by an integral
electronic enthalpy control that feeds input into the basic • E-Coat Epoxy Polymer Coated Condenser and
module. The outdoor intake opening shall be covered with Evaporator Coil
a rain hood that matches the exterior of the unit. Water • Electronic Single Enthalpy Economizer
eliminator/filters shall be provided. • Dirty Filter Switch
Simultaneous economizer/compressor operation is also • Phase Monitor
possible. Dampers shall fully close on power loss.
• Coil Guard
• Motorized Outdoor Air Dampers - Outdoor and return
• Bas Controls - Simplicity ® SE, CPC, HONEYWELL,
air dampers that are interlocked and positioned by a 2-
NOVAR
position, spring-return damper actuator. The maximum
leakage rate for the outdoor air intake dampers shall not • BAS Ready Economizer (2-10 V.D.C. Actuator Without a
exceed 2% when dampers are fully closed and operating Controller)
against a pressure differential of 0.5 IWG. A unit-mounted • Hinged Filter Door Access And Tool Free Access
potentiometer shall be provided to adjust the outdoor and Panels
return air damper assembly to take in the design CFM of • Hinged Tool Free Blower, Blower Motor, Filter And
outdoor air to meet the ventilation requirements of the Electrical Access Panels
conditioned space during normal operation. Whenever the
indoor fan motor is energized, the dampers open up to • 2" Pleated Filters, MERV 8
one of two pre-selected positions - regardless of the • 4" Pleated Filters, MERV 13
outdoor air enthalpy. Dampers return to the fully closed • Disconnect Switch
position when the indoor fan motor is de-energized.
• Supply Air Smoke Detector
Dampers shall fully close on power loss.
• Return Air Smoke Detector
Physical Data
Capacity Performance
ZF180-240 Cooling Capacities
1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
WC.
1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
WC.
1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
WC.
1. These capacities are gross ratings. For net capacity, deduct air blower motor heat, MBh = 3.415 x kW.
2. Capacity ratings are based on 80°F (26.7°C) Entering Air Dry Bulb Temperature.
3. These ratings are total input kW, thus include the two condenser fan motors, compressor motors, and the supply air blower motor at 0.40"
WC.
Airflow Performance
ZF180-240 Side Duct Application
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
RPM Selection
Size Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Model HP Max BHP
(Tons) Sheave Sheave Open Open Open Open Open Open Closed
180
ZF 4.0 4.72 1VP62 BK75 925 967 1009 1051 1093 1135 N/A
(15)
240
ZF 6.3 7.13 1VP75 BK100 895 926 956 987 1018 1049 N/A
(20)
* Maximum blower speed is 1400 RPM for ZF180 and 1200 RPM for ZF240
Drive Selection
1. 6800 CFM
2. 2.0 iwg
3. Using the supply air blower performance table below, the following data point was located: 1020 RPM & 5.92 BHP.
4. Using the RPM selection table below, Size X and Model Y is found.
5. 5.92 BHP exceeds the maximum continuous BHP rating of the 5.0 HP motor. The 7.5 HP motor is required.
6. 1020 RPM is within the range of the 7.5 HP drives.
7. Using the 7.5 HP motor and drive, 3.5 turns open will achieve 1020 RPM.
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
305 Meter
0.900 610 Meter
914 Meter
0.850
1219 Meter
0.800 1524 Meter
1829 Meter
0.750 2134 Meter
2430 Meter
0.700
2743 Meter
3048 Meter
0.650
0.600
4.4 10 15.5 21 26.6 32 38
Air Temperature (ºC)
Sound Performance
ZF Indoor Sound Power Levels
Sound Power, dB (10-12) Watts
Size ESP Blower 1
CFM Sound Rating Octave Band Centerline Frequency (Hz)
(Tons) (IWG)
RPM BHP dB (A) 63 125 250 500 1000 2000 4000 8000
180 (15) 6000 1.0 1,080 4.6 91 88 90 90 87 85 81 81 76
240 (20) 8000 1.0 1,020 6.6 86 85 85 83 82 82 78 75 70
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Electrical Data
ZF180 - 240
Compressors
OD Fan Supply Pwr
(each) Max Fuse2/
Motors Blower Conv Electric Heat Option
Size MCA1 Breaker3
Volt (each) Motor Outlet
(Tons) (Amps) Size
RLA LRA MCC (Amps)
180 380-3-50 16.7 13 111 101 26 20.3 2.1 6.3 0 NONE - - - 44.4 60
(15) 415-3-50 16.7 13 111 101 26 20.3 2.1 6.7 0 NONE - - - 44.8 60
240 380-3-50 18.6 17.9 118 118 29 28 2.1 8.2 0 NONE - - - 53.6 70
(20) 415-3-50 18.6 17.9 118 118 29 28 2.1 9.1 0 NONE - - - 54.5 70
CONTROL
THERMOSTAT TERMINAL
TERMINALS BLOCK
W1
W1
W2
W2
1 Y1
Y1 G
Y2 Y2
OCC
G
X
R R
3
C SD-24
C
Smoke
RC Detector
4
OCC C
5
X 24V 24 VAC
Class 2
R
1 Second stageŚĞĂƟŶŐŶot required on single stage heĂƟŶg units.
2 Jumper is required if there is no Smoke Detector circuit.
3 Jumper is required for any coŵďŝŶĂƟŽŶ of R, RC, or RH.
4 OCC is an output from the thermostat to indicate the Occupied ĐŽŶĚŝƟon.
5 X is an input to the thermostat to display Error Status condiƟons.
Y
X
FRONT
LEFT
B C
B
C D
A A E
FRONT 0)
FRONT ( 18 0)
)
4” 24
4 (6 9”) (
2 6
D F 16 58 (
17
ZF180-240 Unit Weights Imperial
Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
180 (15) ZF 1685 1680 66.5 45.7 391 443 449 397 256 277 302 306 281 259
240 (20) ZF 2405 2400 70 44 558 590 643 609 369 382 397 433 417 402
ZF180-240 Unit Accessory Weights Imperial ZF180-240 Unit Accessory Weights Metric
Weight (lbs.) Weight (kg.)
Unit Accessory Unit Accessory
Shipping Operating Shipping Operating
Economizer 165 160 Economizer 74.8 72.6
Power Exhaust 90 85 Power Exhaust 40.8 40.8
Gas Heat1 240 240 Gas Heat1 108.9 108.9
Motorized Damper 150 150 Motorized Damper 68 68
Barometric Damper 50 45 Barometric Damper 22.7 22.7
Econ./Motorized Damper Rain Hood 60 55 Econ./Motorized Damper Rain Hood 27.2 27.2
Econ./Power Exhaust Rain Hood 95 90 Econ./Power Exhaust Rain Hood 43.1 43.1
Wood Skid 220 220 Wood Skid 99.8 99.8
Roof Curb 190 185 Roof Curb 86.2 86.2
1. Weight given is for the maximum number of tube heat 1. Weight given is for the maximum number of tube heat
exchangers available (8 tube). exchangers available (8 tube).
Unit Dimensions
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
(Discharge)
OUTDOOR AIR
(Economizer)
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
(Discharge)
OUTDOOR AIR
(Economizer)
EVAPORATOR
SECTION
DOT PLUG
1026 (For pressure
(40-3/8") drop reading)
FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR
COMPRESSOR
OUTDOOR
ACCESS
AIR
1029
SUPPLY AIR
(40-1/2")
ACCESS 474
(18-5/8")
1" NPT FEMALE
Dimensions listed are for side 130 COND. DRAIN
RETURN AIR (5-1/8") CONNECTION
duct flange openings; see ACCESS
705
(27-3/4")
OUTDOOR AIR
Field Accessories for Side ZF180 727 (28-5/8”) COMPARTMENT
Duct Flange Kit. REAR ZF240 1006 (39-5/8") ACCESS
VIEW
NOTE: Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts.
ECONOMIZER
MOTORIZED
SUPPLY AIR POWER EXHAUST DAMPER
COMPARTMENT RAIN HOOD RAIN HOOD
(on Return Air Compartment) (on Outdoor Air Compartment) ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
930 Compartment)
(36-5/8”)
25 (1“) CONDENSATE
410 DRAIN
(16-1/8”) (Must be trapped)
127 (5”)
716 2337
(28-3/16”) (92”)
DETAIL “Y”
UNIT WITH RAIN HOODS
Unit Clearances And Rain hood Dimensions (15 & 20 Ton)