02- FAQ AutoLink Electronic Sectionalizer
02- FAQ AutoLink Electronic Sectionalizer
AutoLink
Frequently Asked Questions
October 2013
1
ABB AutoLink FAQ Document: 1YSA160036-en
Table of Contents
1 Background ......................................................................................................................... 4
1.6 What are the available pickup levels in the AutoLink? ...................................................... 4
2.2 What is the maximum pass-through current for the AutoLink? ........................................ 5
2.7 When does the AutoLink know that the line is open?........................................................ 6
2.8 Does the AutoLink detect transformer energization inrush currents? ............................. 6
3.1 Which cutout bodies are suitable for AutoLink installation? ............................................ 6
3.2 What is the minimum load current required for the AutoLink to be operational? ............ 6
2
ABB AutoLink FAQ Document: 1YSA160036-en
3.3 Are there spare parts available for the AutoLink? ............................................................. 6
3.6 What are the recommendations for setting the AutoLink? ................................................ 7
4 General ................................................................................................................................. 8
3
ABB AutoLink FAQ Document: 1YSA160036-en
1 Background
4
ABB AutoLink FAQ Document: 1YSA160036-en
2 Technical features
2.1 What standard does the AutoLink comply with?
The AutoLink complies with ANSI C37.63 standard (IEEE Standard Requirements for Overhead, Pad-
Mounted, Dry-Vault, and Submersible Automatic Line Sectionalizers for AC Systems up to 38kV).
5
ABB AutoLink FAQ Document: 1YSA160036-en
2.7 When does the AutoLink know that the line is open?
The AutoLink detects a dead line when it measures 200mA or less. If more than 200mA are present
when the current is interrupted, the AutoLink will not advance its counter.
3.2 What is the minimum load current required for the AutoLink to be
operational?
The AutoLink requires 6A for at least 30 sec to charge up. A larger current will shorten the charge up
time.
6
ABB AutoLink FAQ Document: 1YSA160036-en
7
ABB AutoLink FAQ Document: 1YSA160036-en
4 General