2008.12692v1 (1)
2008.12692v1 (1)
*Correspondence: [email protected]
Abstract
Accurate inertia estimates and forecasts are crucial to support the system operation in future low-
inertia power systems. A large literature on inertia estimation methods is available. This paper aims
to provide an overview and classification of inertia estimation methods. The classification considers the
time horizon the methods are applicable to, i.e., offline post mortem, online real time and forecasting
methods, and the scope of the inertia estimation, e.g., system-wide, regional, generation, demand,
individual resource. Shortcomings of the existing inertia estimation methods have been identified and
suggestions for future work have been made.
Keywords: Low-inertia power systems, Inertia estimation, Inertia forecasting, Power system
operation
Date: 21/08/2020
1. Introduction
Sufficient inertia in power systems is crucial to ensure secure and reliable power supply. In tra-
ditional power systems, inertia was provided by the rotating masses of synchronous generation and
motor loads. These days, inertia is decreasing due to the massive introduction of converter-interfaced
generation, consumption and transmission of power, which causes challenges to maintain acceptable
frequency profiles. Inertia has been specifically low during periods of low demand and high renewable
production [1]. To deal with the challenges of reduced inertia levels, system operators would benefit
from accurate estimates or measurements of the inertia available in the system at each point in time as
well as from forecasts of expected inertia levels [2]. System operators currently estimate system inertia
based on part of the resource [2] or based on a simplified empirical relation [3], which are approximate
methods. Considering the evolution of power systems towards lower inertia levels, reliable and more
accurate methods to estimate instantaneous and forecast future inertia are crucial.
1
Although a large literature on inertia estimation methods is available, they have not been surveyed
so far. Existing review papers in the field of low-inertia power systems have focused on (i) the role and
control of technical inertia enhancement techniques involving converter-interfaced energy buffers, also
denoted as virtual inertia or inertia emulation [4, 5, 6, 7, 8], (ii) a general overview of the relevance of
inertia in power systems by looking at the different sources of inertia and their impact on the operation
of power systems [9] and (iii) a broad survey of the issues related to low-inertia power systems as well
as the solutions that have been put forward with a particular focus on transient and frequency stability
and converter control [10].
To give insight in the shortcomings, challenges and opportunities of inertia estimation methods
in the operation of low-inertia power systems, this paper presents an overview and classification of
available inertia estimation methods. We surveyed the literature on inertia estimation methods and
categorized the approaches according to the applicable time horizon and the scope of the inertia esti-
mates. This enables us to discuss the evolution in the development of inertia estimation methods with
relation to the operational practice and to identify shortcomings of the existing methods. Pathways
for future research in the field of inertia estimation methods have been put forward.
Secure and reliable operation of power systems requires a frequency that is nearly constant around
the nominal frequency, which equals 50Hz in most parts of the world and 60Hz in the Americas and
some parts of Asia. Grid codes prescribe acceptable frequency deviations and the system operator
should take adequate actions to satisfy these limits. Inertia is a crucial parameter to satisfy the
frequency limits in today’s power systems.
1 This is the linearised version of the swing equation, which is valid for normal oscillations in power systems [11].
2 The frequency response in Fig. 1 gives the frequency evolution at the centre of inertia (COI). The frequency at the
centre of inertia is a theoretical concept representing the inertia weighted frequency of all generators in the system and
2
Rotor swings
Frequency
Time
f0
∆fss
ROCOF
at COI
fmin =Nadir
Frequency
Power dependent load
PL decrease
PG
∆Ekin
Inertial response and
Secondary
Primary (governor)
control
control
Seconds Minutes
Figure 1: Frequency response after a power imbalance [Figure from [13], used with permission from the author]
d∆f¯
Grid codes put limits on the rate of change of frequency (ROCOF) dt and the frequency nadir
fmin to avoid tripping of protection relays. Generating units’ protection relays are configured to avoid
generating units to be exposed to ROCOF ranges from 1.5 - 2 Hz/s (over a 500-ms rolling window) that
can cause pole slipping and catastrophic failure [14]. Also anti-islanding protection may be designed
based on the detection of ROCOF [15]. Frequency nadir is limited to avoid tripping of underfrequency
load shedding protection relays. Fang et al. provide an overview of the ROCOF and frequency nadir
limits in different power systems around the world [6].
Power system inertia is an important instrument to limit the ROCOF and frequency nadir. In
its elementary form, inertia is defined as the resistance of a physical object to a change in its state
of motion, including changes in speed and direction [13]. In a power system context, inertia can be
understood as the resistance, in the form of any kind of energy exchange, to counteract the changes in
system frequency resulting from power imbalances in generation and demand [13]. In the Great Britain
cannot be measured directly in the system. Calculating this value would require individual frequency measurements for
all generators. Instead of estimating the frequency at the COI online, system operators typically measure the frequency
at a relevant pilot node in the system. However, frequency measurements should be done with care, as they are heavily
influenced by the location of the measurement and neighbouring generators [10].
3
system, the inertial response is defined as the period up to one second immediately following a loss of
generation or demand prior to the activation of primary frequency response services [16]. The inertial
response combined with the droop response of the primary frequency control limits the frequency
nadir after a disturbance. The frequency restoration is further accomplished by the secondary and
tertiary frequency control. Rebours et al. provide an overview of the technical features of the primary,
secondary and tertiary frequency control reserves in different power systems [17].
The nature and size of the available inertial response in the power system has been changing
over the last decade. Originally, rotating masses of synchronous machines, both generation and load,
exchange kinetic energy with the system in the case of a power imbalance by slowing down or speeding
up. This impacts the system frequency as the rotor speed is proportional to the frequency in the
system. The inertial response of the synchronous rotating masses is instantaneous. In today’s power
system, synchronous machines have been gradually replaced by converter-integrated generators and
demand. Moreover, power-electronic-interfaced high voltage dc technology has been increasingly used
for interconnectors between power systems. These technologies can offer inertial response if they have
an adequate energy buffer and control system in place. The control system should regulate the release
and absorption of energy similar to the inertial response of synchronous generation units. Fang et
al. give an overview of the emerging techniques for inertia emulation with different sources of energy
storage [6]. The penetration of inertia emulation in power systems has been limited so far. First of all,
appropriate regulation has not yet been in place. Second, the system’s dynamics characteristics will
be impacted as control characteristics of inertia emulation techniques differ compared to synchronous
generators’ behaviour in case of disturbances [10, 18]. Third, emulated inertial response typically
comes from more variable and uncertain energy buffers, which increases uncertainty and variability in
system operation [19, 20]. This evolution implies that traditional, instantaneous inertial response in
modern power systems has been declining and tends to reduce even further in the future.3
3 In the extreme case of 100% non-synchronous systems, natural response to power imbalances is no longer present
in the system and frequency is no longer a measure of power imbalance [10]. Although the viability of control and
operation of zero-inertia power systems have been proven in simulation studies and practical experiments, their practical
implementation will not be for tomorrow, as many existing grid-connected devices and machines expect frequency to
change relatively slowly and further study is required to integrate new converter technology into existing power system
structures [18]. Milano et al. expect that substituting all conventional power plants with converter-interfaced generation
will take a few decades [10].
4
2.3. Operational measures to limit the risk of ROCOF and underfrequency relay tripping
Reduced instantaneous inertial response increases the risk of tripping loss of main protections of
embedded generators and underfrequency load-shedding relays. Besides changing grid codes in terms
of connection criteria for non-synchronous generation [21] or modifying protection relay settings to
cope with higher ROCOF and larger frequency swings [22], operational measures can be taken to
reduce this risk. Considering the different terms in the swing equation (Eq. (1)), the system operator
can reduce the risk of tripping ROCOF protection relays by reducing the possible largest loss in the
system ∆P max or by increasing the inertial response, represented by the inertia constant H. Fig. 2
gives an overview of the operational practice with respect to inertia for the case of Great Britain.
D-1 11:00 H-1 RT
00:00 12:00 00:00 12:00 00:00
Time
BM
GCT
D-1 electricity
prices available Electricity price per settlement period
Report
physical Expected generator output per settlement pe-
notifications riod
to TSO
Continuous updating of physical notifications
Figure 2: Overview of the operational practice related to inertia for the case of Great Britain
Reducing the possible largest loss requires the system operator to redispatch generation or inter-
connection flows ahead of real time. In Great Britain, the system operator is informed by the expected
output of the balancing mechanism units, which include the largest generating units, from 11:00 day
ahead for each 30-minute settlement period of the next day via the physical notifications. The grid code
of Great Britain defines physical notifications as "a series of MW figures and associated times, making
up a profile of intended input or output of active power at the grid entry point or grid supply point, as
appropriate" [23]. Large generator units, interconnectors and large demand units should provide these
physical notifications. They should update their physical notifications throughout the day if significant
5
changes are to be expected [23]. One hour ahead of real time, the final market settlement is reported
to the system operator and the balancing mechanism starts. During the balancing mechanism, the
system operator can accept bids and offers of the balancing mechanism units and request them to
increase or decrease their power output. System operator’s decisions upon generator redispatch are
not only affected by economic concerns, but should also respect generators’ reported ramp rate limits,
minimum run time and the time taken to synchronize, as well as network constraints while being
practicable for the system operator, e.g., large volumes of energy are preferred to reduce the number
of instructions. Nowadays, reducing the largest loss is typically 10 times cheaper than increasing the
inertial response by bringing additional generators online.4 However, its effectiveness in power systems
with a reduced number of large synchronous generator units and more smaller, distributed generation
units, which are highly variable and uncertain in nature, is questionable.
To increase system inertia, the system operator can replace large amounts of converter-interfaced
generation with synchronous generation ahead of real time. If additional synchronous generators need
to be brought online, the system operator should take into account the time to synchronize the power
plant. To deal with long synchronization time, the system operator has the possibility to start up
balancing mechanism units that are not expected to run according to the physical notifications via the
balancing mechanism start up ancillary service at the price of a start-up and hot-standby payment
[24] or using forward trading. These actions can be initiated before the balancing mechanism starts.
On a time scale of seconds, frequency response can prevent the tripping of underfrequency-load-
shedding relays. The system operator should adequately contract and procure frequency response
services ahead of real time. Moreover, to deal with reduced inertia levels causing increased ROCOF
and larger frequency swings, system operators are developing new, faster-acting frequency response
services to ensure frequency containment within operational limits and avoid underfrequency load
shedding with relaxed ROCOF limits [1].5 Alternatively, markets for inertia, which enable the trade
of virtual inertia from converter-interfaced resources, have been suggested in the literature [25]. It has
been shown that inertia is especially a valuable product if it reduces wind curtailment in the system
[26].
Nowadays, National Grid ESO builds tables representing the five-minute resolution frequency re-
sponse requirement as a function of demand, inertia and largest infeed loss using a frequency simulation
engine [27]. These tables are used in operational systems to optimise the overall frequency response
requirement for 5 minute blocks throughout the day based on the real-time demand, inertia and largest
6
infeed loss. Combining these requirements with the contractual arrangements per settlement period,
gives the control room engineer insight in the residual frequency response requirements that should be
procured from mandatory services in real time.6 Control methods to coordinate the delivery of multi-
ple frequency response services in real time have been investigated in [20]. In power systems operated
by independent system operators, stochastic unit commitment models for simultaneous scheduling of
multiple frequency services and dynamic reduction of the largest loss can support a secure operational
practice [28].
Cost-effective and secure operational decisions require accurate inertia estimates, which enable sys-
tem operators to estimate the characteristics of the frequency response of the system. The frequency
response in power systems is typically estimated based on the swing equation, as introduced in Eq.
(1), which relies upon the inertia in the system. Initial approaches to estimate inertia in power sys-
tems dominated by synchronous generator units assume the system inertia to be nearly constant, with
an inertia constant of generation of approximately 5 seconds and an inertia constant of demand in
the range of 1.6 - 1.8 seconds [29]. To consider the variability in the inertia level in power systems
with reduced synchronous generator units and increased embedded units and uncertain and variable
renewable energy resources, alternative inertia estimation methods have been developed that combine
measurements of system variables, such as frequency and active power, and the physical model of the
frequency profile. The system inertia is considered as a parameter to be estimated in a parameter
estimation or system identification method. Inertia estimation methods in the literature can be cate-
gorized according to the time instant they are estimating the inertia for and according to the scope of
the method. Table 1 classifies the methods row-wise according to the time horizon and column-wise
according to the scope. The following subsections will discuss this classification in more detail.
3.1. Classification of inertia estimation methods according to the time horizon of interest
Inertia estimation methods can be categorized based on the time horizon of interest as offline
post-mortem approaches, online real-time approaches and forecast approaches. Post-mortem inertia
estimation methods are applied, for instance, in an analytical context to make an ex-post assessment
of the inertia level in the system during large disturbance events. Real-time methods aim at making
an instantaneous estimate of the inertia based on readily available measurements of system variables.
Forecast approaches estimate the inertia to be expected in the future.
7
Table 1: Overview and classification of inertia estimation methods according to time horizon and scope
Scope
Synchronous Embedded Clustered
System Zone Demand
generation generation generators/Node
Online, discrete [40, 41, 42] [3, 43, 44] [45, 46, 47, 48, 49] [50] [51]
References that present a method that is able to estimate the inertia for different scopes are only mentioned once in the table, i.e., in the column of the smallest
scope it is applicable to.
3.1.1. Offline, post-mortem inertia estimation
Post-mortem, disturbance-based approaches to estimate total system inertia were the first attempts
to improve the modelling-intensive approach in [29] to estimate the frequency response profile. Post-
mortem approaches estimate the inertia after large frequency disturbing events have taken place for
which the power imbalance related to the rate of change of frequency is accurately known. Inoue et
al. were the first to introduce such a disturbance-based approach for inertia estimation that combines
the swing equation with processed PMU measurements7 of the frequency and the known size of the
disturbance to estimate the total system inertia [30]. They estimate the inertia constant as:
−∆P
H= i (2)
d(∆f /f0 )
dt t=0
i
d(∆f /f0 )
with ∆P the size of the loss and dt the rate of change of frequency at the starting time
t=0
of the disturbance.8 This approach estimates the combined contribution of synchronous generators,
embedded units and demand. Most post-mortem, disturbance-based approaches ignore the damping
and the short-term frequency response services in the imbalance ∆P applied in the swing equation, by
assuming it to be zero in the short time period immediately after the disturbance [31, 38]. Especially
with the introduction of new, fast frequency response services, which reduce the time window of pure
inertial response, this assumption may become challenging. Including activated frequency response
services, such as governor response, and frequency and voltage dependent characteristics of the load
in the modelling of the power imbalance is a way to deal with this issue, such as in [32] and [34]. This
approach also facilitates the simultaneous estimation of the system inertia constant and the size of the
disturbance considering the frequency- and voltage-dependent dynamics using parameter estimation
that relies upon solving a system of linear equations in [32] or an optimization in [34].
Three aspects are specifically affecting the accuracy of post-mortem approaches. First of all, the
size of the loss should be accurately known. For this reason, not all events may be suitable for use
in post-mortem inertia estimation. Ashton et al. mention the difficulty of estimating the inertia
after events with multiple sequential outages of generators and suggest to focus on instantaneous
events, which may be detected by their modified detrended fluctuation analysis [33]. Second, the
on-set of the event, i.e., t = 0, should be accurately determined. A recently suggested technique in
7 PMUs can measure voltage and currents phasors in the system, as well as frequency, rate of frequency change, active
power output of generators and power flows on transmission lines with measurement rates of 30 - 60 measurements per
second [60, 61]. PMUs have the capability to directly monitor load feeders, but this is typically not the priority. The
capability of PMUs to support inertia estimation depends on the noise and response delay on a step change [62]. Also
the locations of the PMUs impact the frequency measurement. Some methods use averaged frequency measurements of
the PMUs to circumvent location specific frequency swings [63].
8 ∆f = f (t = 0) − f with f the nominal system frequency and t=0 the onset time of the disturbance.
0 0
9
the literature estimates the event on-set based on the second derivative of the ROCOF [64]. Third,
the accuracy of the ROCOF calculation is affecting the accuracy of the inertia estimate. ROCOF
has to be estimated on the relevant time interval, i.e., between the on-set of the event and the on-
set of primary frequency response. The latter is determined by the time constant of the governors
in traditional frequency response and is typically between 1-2 seconds following an infeed loss [16].9
The oscillatory component in the frequency signal produced by the synchronizing power between the
generators may cause erroneous results for the ROCOF calculation. To overcome this issue, Inoue et al.
fitted a polynomial to the frequency signal to extract the frequency signal and smooth the transients
[30, 31, 36], whereas Ashton et al. used a 0.5Hz low-pass filter to filter the frequency signal after finding
the fitting of a polynomial to the signal insufficient [16]. Besides the oscillations, ROCOF calculations
may be corrupted by noise, which is filtered using moving average filters [30] or modified detrended
fluctuation analysis [33, 16] in the state-of-the-art techniques. Also the location of the frequency
measurements relative to the in-feed loss is affecting the ROCOF calculation. For an identical event,
a measurement from a weakly interconnected part of the system with low localized inertia results in
a higher estimated value of the ROCOF compared to an estimate based on a measurement from an
electrically strong part of the network with a relatively high inertia [16].
Important disadvantages of the post-mortem approaches are that increasing dynamic behaviour
(small signal and transient) due to reduced inertia levels may hamper the accuracy of the inertia esti-
mation and that the inertia can only be determined at discrete time instants, after a large disturbance
event has occurred. As large disturbance events do not occur frequently, post-mortem approaches do
not result in continuous inertia estimates. Inertia estimation methods with low temporal resolution
are expected to become less reliable in the future due to the increasing variability of inertia in the
system. Keeping a data base of accurate inertia estimates during large frequency events can support
inertia estimation with higher temporal resolution.
9 This time constant may change in future power systems due to the integration of very fast frequency response
services, such as the fast frequency response in Great Britain. These services do not react instantaneously, such as the
inertia response, but within one second of a -0.5Hz change in frequency [65, 20].
10
control and data acquisition (SCADA) system or energy management system (lower-bound methods)
[59, 66], (ii) close-to-real-time inertia estimation during disturbances based on PMU measurements
(discrete methods) [3, 45, 42, 49, 47], (iii) continuous inertia estimation based on PMU measurements
or measurements with even higher sampling rates (continuous methods) [53, 52, 56]. Table 2 classifies
the real-time approaches according to these three types of methods. The approaches are also classified
according to the domain in which the inertia is estimated, i.e., using a time series model, a model in
the Laplace domain or a model in the modal domain based on inter-area oscillations.
Table 2: Categorization of real-time inertia estimation methods in lower bound, discrete and
continuous methods that apply parameter estimation in time series, Laplace and modal domain
models.
Domain
Time series Laplace Modal
1
Temporal resolution of the inertia estimates depends on the resolution of the estimation
of the inter-area oscillations [55].
Total inertia from transmission-system-connected synchronous generation units. Total inertia may
be approximated by summing the inertia contribution of transmission-system-connected synchronous
generators based on their online capacity and inertia constant. The inertia constant of a synchronous
generator equals the kinetic energy in the rotating mass at rated speed of the generator expressed
proportional to the power rating of the generator and represents the time in seconds a generator can
provide rated power solely using the kinetic energy stored in the rotating mass [68]. Accurate inertia
constants of individual generators are typically not available to the transmission system operator [69].
Also the equivalent inertia constant of virtual inertia resources is not readily available and variable
over time. Research efforts have been focussing on estimating these equivalent inertia constants.10 On
top of the inertia constant, this approach requires knowledge of the online status and the generation
capacity of the generators. The online status of large transmission-system-connected generators can
be monitored in the SCADA or EMS system, while their capacity is known to the system operator.
Although the complexity of inertia estimation based on the online capacity of generators is very low,
10 These research efforts are indicated in the fourth column of Table 1 and are discussed in more detail in Section
3.2.2.
11
the resulting inertia estimate is not very accurate. First of all, the approach underestimates the total
system inertia that is available, as only synchronous generators that are monitored by the transmission
system operator are considered in the estimate, whereas small embedded units, such as combined heat
and power plants, or small motor loads are not considered. Therefore, this result can be considered
as a lower bound on the inertia, defining an upper limit on the ROCOF. Second, the inertia estimates
resulting from lower bound inertia estimation are only available at discrete time instants. They rely
upon the monitoring of energy management or SCADA systems. Although the SCADA system usually
samples data at a relatively high frequency of typically 1 Hz, the standard practice is to store 10-minutes
averaged values of the parameters characterising the operating and environmental conditions [70]. To
estimate the inertia between two monitoring instants of the generators, a statistical model to estimate
the change in inertia from synchronous generators based on measurements of frequency deviation with
a higher temporal resolution can be applied [63].
Discrete inertia estimation. Inertia estimation methods are available that are able to estimate inertia
close to real time during disturbances based on PMU measurements of frequency and estimates of
power imbalance. Two main approaches can be distinguished in this group of methods: (i) Methods
that directly work with the time series data and (ii) methods that work in the modal domain and
estimate the inertia based on inter-area oscillations, as indicated in Table 2. Similar to the offline
disturbance-based approaches, the underlying model of these parameter estimation methods is the
linearised swing equation, typically ignoring damping and primary and secondary frequency response.
The methods assume to estimate the inertia within the very short period after the disturbance before
these slower dynamics are in place. Schiffer et al. have included a generator governor model to
capture the impact of primary frequency control [40]. Alternatively, applying more detailed system
models, including dynamic generator models and power flow equations, enable the estimation of the
inertia based on voltage measurements [50]. However, this comes at an increased computational cost.
Bayesian approaches for parameter estimation enable the quantification of the uncertainty on the point
estimates of inertia caused amongst others by measurement noise [50].
Real-time disturbance-based inertia estimation is challenging for two reasons. First of all, the online
detection of an appropriate disturbance requires attention. Detection based on signals filtered using a
moving-average filter is a frequently used technique [45, 42]. Second, accurate estimation of the size of
the disturbance based on available PMU measurements is challenging. Approaches to deal with this
challenge differ with the scope of the inertia estimation method. In methods that estimate the inertia
constant of individual generators based on time series of PMU measurements it is frequently assumed
that the mechanical power output of a generator equals the electrical power output at the previous
time instant [45, 42]. This assumption is based on the slow response of a generators mechanical
12
power output compared to the electrical power output and the fact that frequency control balances
the mechanical and electrical power within the generator making them approximately equal before a
disturbance [46]. Methods to estimate regional, on the contrary, approximate the power imbalance per
independent frequency region as the change in power flow on the interconnecting lines during small
disturbances [3]. The latter assumption originates from the inter-area power flow oscillations between
independent frequency regions resulting from power imbalances.
The performance of disturbance-based inertia estimation methods depends on the size of the distur-
bance [3]. Originally, only outage events were considered as appropriate frequency events [42]. However,
also generator rescheduling at the hour causing frequent, recurring, and scheduled frequency variations
have proven to be suitable for real-time inertia estimation [40]. Nevertheless, the temporal resolution
of the estimates is still limited to 30-60 minutes in these cases. At intermediate time instants, values
for inertia have to be extrapolated based on the latest estimation [63].
Continuous inertia estimation. (Near-)continuous inertia estimation methods rely upon PMU measure-
ments of the frequency or measurements with even higher sampling rates and continuous estimates of
the power imbalance in the system. Based on these two sources of information they estimate inertia in
the time domain, Laplace domain or modal domain, as indicated in Table 2. (Near-)continuous meth-
ods have an increased temporal resolution compared to discrete inertia estimation methods. However,
continuously estimating the power imbalance during normal system operation is hard, as power imbal-
ances in normal operation are small compared to measurement noise and cannot be measured directly
with state-of-the-art measurement equipment. Two approaches have been used in the literature to
continuously determine the power imbalances in power systems during normal operation. A first ap-
proach estimates the power imbalances on a near-continuous basis (in a time scale of minutes or tens of
minutes) based on PMU measurements. This method involves strong assumptions and is only valid if
generator settings do not change [53]. Second, inertia estimation methods based on microdisturbances
may overcome the issue of poor estimation of power imbalance by injecting a known microdisturbance
in the system. These microdisturbance may be optimized to maximize the signal to noise ratio [56] or
the impact on the frequency measurements can be filtered with advanced signal processing [52].11
The accuracy and reliability of continuous inertia estimation methods have not been proven so far.
Guo et al have shown that the accuracy of their estimates reduce with larger errors in the measure-
ments and that accurate initial guesses of the inertia constants are required to ensure the convergence
of the algorithm, which are not straightforward to obtain [55]. Also the method of Tuttelberg et al.
has shown deficiencies [53]. The results of a case study indicate incorrect inertia estimates at some
11 The latter approach has been commercialized by Reactive Technologies and requires high-speed measurement units
for very fast frequency measurements (no PMUs) [52].
13
time instants. One of the reasons for the poor performance may be related to the approximation
of the power imbalance in the system. The output of generators and interconnectors are considered
to be constant over the measurement period and the measured changes in generation and intercon-
nection flows compared to the start of the measurement period are attributed to power imbalances.
Also microdisturbance methods have not been thoroughly validated. Validation of the method in [52]
is performed based on one week of inertia data provided by the British system operator, which are
based on an empirical formula. Although the measurements swing around the empirical results, the
empirical results do not correspond with the ground truth inertia. It is hard to attribute the swings
of the measurements to the stochastic behaviour of inertia or to measurement noise, as values for the
ground truth are not available and a reference case for calibration has not been presented. Moreover,
it is important to verify the applicability of inertia estimation based on microdisturbances for large
and not densely meshed systems with high levels of inertia for which the single-centre-of-inertia ap-
proximation is not valid and where it is hard to distinguish small load disturbances from noise and
natural attenuation of the perturbation [71]. Also potential power quality issues due to the inserted
microdisturbances should be investigated [71].
12 Abundant literature is available on load forecasting in power systems. An overview can be found in [72, 73].
14
their expected status and has been reported by the independent system operator ERCOT [57]. However,
the expected status of the generators is not generally available to all transmission system operators in
day ahead. Moreover, a drawback of this model is that only considering transmission-system-connected
synchronous generators’ contribution results in an underestimation of the total system inertia as the
contribution from demand has not been considered. Other system operators estimate the future
inertia contribution from embedded units and demand based on the demand forecast multiplied with
I
an empirical constant [3]. The resulting structure of the forecast model for the inertial energy Êt+k|t
can be represented as:
K̂t+k|t,i · Hi · PiG,C + a · P̂t+k|t
X
I D
Êt+k|t = (3)
i
with K̂t+k|t,i the reported status of the synchronous generator unit i at time t for time t + k, Hi its
inertia constant [s], PiG,C its generating capacity [MW] and P̂t+k|t
D
the forecast of the system demand
at time t for time t + k [MW]. While originally a single constant regression constant a has been used
for the system as a whole, linear regression analysis on regional inertia estimates has been applied to
derive spatially differentiated empirical constants [3]. To build these regression models, historical data
of the inertia in the system and the corresponding system state are required. The accuracy of the
forecasts will be determined by the accuracy and resolution of the historical inertia estimates.
Point forecast models relying upon the reported status of synchronous generator units are expected
to decrease in accuracy. Due to the increased penetration of variable and uncertain renewable energy
sources with zero marginal cost, the market dynamics are expected to increase and the day-ahead
reported statuses are expected to be less accurate and more uncertain, which hampers the forecasting
of the available inertia. This effect has been shown in the ERCOT system, where inertia forecasts
based on week-ahead generator reports typically overestimate the real-time inertia during periods
with low energy prices [57]. Two measures can be taken to deal with this challenge. First of all, an
improved point forecast model of the status of the synchronous generators may reduce the point forecast
error. A first approach is to model the energy trading to estimate the generators’ statuses. However,
modelling energy trading is not straightforward, especially not if quantitative results are required [74].
Moreover, transmission system operators in power systems with independent market operators do not
have access to the bids and offers in the energy markets and are only informed by the outcome of the
market at gate-closure time close to real time, e.g., one hour ahead of real time in Great Britain [23].
Therefore, it might be more beneficial from a system operator’s perspective to identify relationships
between the generators’ online capacity and other system variables impacting the energy trading that
are directly available to the system operator, such as historical data of the status of the different
generators, historical data and forecasts of total transmission system demand, forecasts of wind and
solar generation, interconnector flows, electricity prices, etc. Second, while current practice focuses on
15
point forecasts, modelling the uncertainty on the forecasts enables the system operator to assess the
risk of ROCOF and underfrequency relay tripping. Probabilistic forecast models are a useful tool in
this respect, as they represent the conditional distribution of the future inertial energy for different
forecast horizons conditional upon the system state, for a variety of system states. The system state is
characterized by a set of exogenous variables, such as demand, wind production, day-ahead electricity
price and forecasts of the respective system variables. The linear regression model in state-of-the-art
approaches provides a framework to estimate or predictive distribution of the inertia forecasts, but this
is based on a set of strict assumptions, i.e., (i) the errors are statistically independent, (ii) the errors
have a constant variance and (iii) follow a normal distribution. Alternative parametric, semi-parametric
and non-parametric probabilistic forecast models should be developed for inertia forecasting.13 The
development of accurate probabilistic forecast models requires a large data set. However, current
inertia estimation methods provide accurate estimates during discrete events resulting in a data set
too small for accurate forecast modelling or near-continuous estimates that are inaccurate or of which
the accuracy has not been proven.
Traditional explanatory inertia forecasting models as the one introduced in Eq. (3) rely upon
the assumptions that a linear, additive and stationary relation holds between system inertia and
the exogenous variables, i.e., total system demand and the inertia contribution from synchronous
generators. To avoid the assumption of linearity and additivity, the feasibility of non-linear, artificial
neural network (ANN) models as explanatory models for inertia forecasting has been tested in [59].
The presented ANN models use total system demand, total generation from power-electronic interfaced
generation and total generation from synchronous generators as input features to model the system
inertia. General statements about the accuracy of the method cannot be made as the report only
mentions the application of the approach in a simplified simulation context, which does not capture
the actual stochastic behaviour of the inertia in the system [59].
Inertia estimation methods may also be categorized based on their spatial resolution. Some methods
are able to estimate the total system inertia or regional inertia, which makes them different in terms
of their geographical scope. Other methods focus on the estimation of different contributors to the
inertia, such as synchronous generators, demand or virtual inertia resources.
13 Probabilistic forecasting models have already been applied extensively in other energy forecasting contexts, such as
load forecast, price forecasting and wind forecasting [72, 75, 76].
16
3.2.1. Geographical scope
Historical approaches to estimate the system inertia focussed on calculating a single value for the
total system inertia based on the concept of centre of inertia, which is determined by the average system
frequency [30, 31, 32, 34]. This value of system inertia captures the contribution from generation,
demand and virtual inertia resources, when present. Assuming a single value for inertia in the system
is acceptable in strong transmission systems with limited variations of the frequency between locations.
Lower inertia levels will, however, increase the risk for angle swings and oscillations between areas [68].
To improve the inertia estimates, recent efforts have been focussing on providing zonal estimates
of the inertia or spatial inertia profiles. Zonal inertia estimates are more flexible than system inertia
estimates, as aggregating the zonal inertia contributions gives the total system inertia, while the zonal
or individual contributions cannot be derived from the system estimate. These zonal inertia estimates
may be used by the system operator in procuring very fast frequency response services and in enhanced
and coordinated frequency control methods [20]. Different approaches to divide the system in zones
have been used in the literature: (i) division around the constraint boundaries of the network under
analysis [16] or (ii) in zones in which angles and frequency are closely coupled [3, 35, 43]. The latter
is preferable from a physical perspective.
17
capacity14 and their individual inertia constants. Originally, synchronous generators’ inertia constants
were estimated using the load ramp test, the probing test and the transient test [79, 80, 81, 82]. Alter-
natively, dynamic online estimation based on PMU measurements has been proposed to estimate the
inertia constants of synchronous generator units or virtual inertia resources, as indicated in the third
and fourth column of Table 1. In these methods, inertia is estimated as a parameter in a dynamic
frequency responsive model, matching the power output of the model with the power output from
the measurements during the disturbance event. The comparison to derive the inertia constants can
be done manually [37] or using a grey-box identification method that optimizes the parameters of a
dynamic model of the frequency response of a generator unit by minimizing a weighted mean squared
error between the power output from the dynamic model for the given frequency measurements related
to the disturbance with the measured power output of the generator unit [36].15 Alternatively, a two
stage validation and calibration process has been suggested to validate the dynamic model accuracy
of a generator based on PMU measurements and update the model parameters using an extended
Kalman filter in case of model deficiencies [47]. One of the dynamic model parameters to be estimated
in this approach is the inertia constant of the generator.
Based on the limited data set of estimates of the inertia contribution from embedded units and
demand during large disturbance events, research efforts have developed explanatory models that relate
the inertia contribution from demand and embedded units to the total system demand [39, 36]. These
models have predictive capabilities. However, due to the limited size of the data set, only simple model
structures with a limited number of parameters to be trained, such as linear regression models, have
been used to avoid overfitting [39]. The temporal resolution of the estimates of the inertia contribution
of demand and embedded units, and therefore the size of the available data set, can be increased by
using an estimation method with higher temporal resolution to estimate the total system or zonal
inertia.16
Secure and cost-effective operation of low-inertia power systems requires accurate and reliable
estimates and forecasts of inertia in the system on a close-to-continuous and regional basis, considering
contributions from generation, demand and virtual inertia resources. The state of the art in inertia
estimation methods has evolved from delivering post-mortem, total system inertia estimates after
14 If information about the generators’ online capacity is not available, Bian et al. have proposed a method to estimate
the generator contribution based on the produced power by fuel type [39].
15 Different simulation models should be built for different types of generator units.
16 An overview of different methods for total system or zonal inertia estimates with different temporal resolution with
18
discrete large power imbalance events towards close-to-continuous real-time inertia estimates with
the possibility to make regional estimates, which is crucial in power systems consisting of strong
regions interconnected by long links. These near-continuous inertia estimates enable monitoring of
the system’s frequency response profiles with a high temporal resolution, which is crucial to deal
with the operational challenges induced in power systems with decreasing inertia levels. Although
important steps have been taken towards near-continuous inertia estimates, the accuracy and reliability
of continuous inertia estimation techniques have not been adequately proven yet due to limited ground
truth knowledge about the inertia in the system. Recommended directions for further work and future
research are (i) the testing and validation of near-continuous inertia estimation methods to ensure that
the techniques do not impact the stability of the system and to obtain more accurate estimates, (ii)
getting more insight in the contributors to the system inertia in different operating states, especially
the contribution of embedded units that are not observable and uncontrollable for the system operator,
and (iii) the development of models to forecast future levels of total system inertia, zonal inertia or
the inertia contribution from individual resources, such as demand and unmonitored embedded units.
First of all, the proposed near-continuous inertia estimation methods and technologies should be
validated and calibrated against situations during which the inertia is accurately known, such as
the testing of a single generator or a large frequency event. Moreover, further work is needed to
verify the impact on the stability and security of the power system of the small power injections in
microdisturbance methods. Based on the results of these analyses the presented methods may be
further improved.
Second, having insight in the contribution of demand and embedded units to inertia and its relation
to other system variables is important in power systems with decreasing inertia levels to inform power
system operators’ decision making process about the unmonitored inertia in the system in real time
and in the future. Estimates of the inertia contribution of demand and embedded units rely upon
accurate estimates of the total inertia from which the inertia contribution of monitored, transmission-
system-connected generators is subtracted. Due to the limited availability of reliable and accurate
total system inertia estimates with high temporal resolution, estimation of the contribution of demand
and embedded units currently relies upon inertia estimates during large disturbance events.
Third, the field of inertia forecasting has ample opportunities for progression. The state of the art
on inertia forecasting models is limited to explanatory, linear regression models with a limited number
of exogenous variables and focuses on providing point forecasts. However, the system operator would
benefit from probabilistic inertia forecasting models to assess the risk of ROCOF and underfrequency
relay tripping and to inform decision making. Once reliable and accurate inertia estimates of the total
system or a zone as well as of the different contributors are available with a high temporal resolution,
these data can be used to develop probabilistic forecasting models. The resulting probabilistic forecasts
19
of inertia may inform system operator’s decisions on the modification of the inertia in the system or
the potential largest loss, frequency response procurement or the volume of inertia to buy on a market
for inertia. Alternatively, one can look into the benefits of direct forecasts of predictive distributions of
system variables, such as rate of change of frequency and frequency deviation, rather than the system
parameter of inertia to estimate the probability of potential issues in the frequency response. Similar
approaches of integrated forecasting have been suggested in the context of determining market bids of
power plants with uncertain production [83].
Acknowledgments
This work has been funded by Electricity Network Innovation Allowance project on Short-term
System Inertia Forecast NIA_NGSO0020.
References
[1] National Grid ESO, “Response and reserve roadmap,” 2019, Accessed 21/07/2020. [Online].
Available: https://www.nationalgrideso.com/document/157791/download
[3] D. Wilson, J. Yu, N. Al-Ashwal, B. Heimisson, and V. Terzija, “Measuring effective area inertia to
determine fast-acting frequency response requirements,” International Journal of Electrical Power
& Energy Systems, vol. 113, pp. 1–8, Dec. 2019.
[5] M. Dreidy, H. Mokhlis, and S. Mekhilef, “Inertia response and frequency control techniques for
renewable energy sources: A review,” Renewable and Sustainable Energy Reviews, vol. 69, pp.
144–155, Mar. 2017.
[6] J. Fang, H. Li, Y. Tang, and F. Blaabjerg, “On the Inertia of Future More-Electronics Power
Systems,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 7, no. 4, pp.
2130–2146, 2019.
20
[8] K. S. Ratnam, K. Palanisamy, and G. Yang, “Future low-inertia power systems: Requirements,
issues, and solutions - A review,” Renewable and Sustainable Energy Reviews, vol. 124, p. 109773,
2020.
[9] P. Tielens and D. Van Hertem, “The relevance of inertia in power systems,” Renewable and
Sustainable Energy Reviews, vol. 55, pp. 999–1009, 2016.
[10] F. Milano, F. Dörfler, G. Hug, D. J. Hill, and G. Verbič, “Foundations and Challenges of Low-
Inertia Systems (Invited Paper),” in 2018 Power Systems Computation Conference (PSCC), Jun.
2018, pp. 1–25.
[13] P. Tielens, “Operation and control of power systems with low synchronous inertia,” PhD Thesis,
KU Leuven, 2017.
[15] Australian Energy Market Operator, “International review of frequency control adap-
tation,” Tech. rep, Tech. Rep., 2016, Accessed: 06/03/2020. [Online]. Available:
https://www.aemo.com.au/-/media/Files/Electricity/NEM/Security_and_Reliability/Reports/2016/FPSS---Intern
[18] T. Ackermann, T. Prevost, V. Vittal, A. J. Roscoe, J. Matevosyan, and N. Miller, “Paving the
Way: A Future Without Inertia Is Closer Than You Think,” IEEE Power and Energy Magazine,
vol. 15, no. 6, pp. 61–69, 2017.
21
[19] L. Ruttledge, N. W. Miller, J. O’Sullivan, and D. Flynn, “Frequency Response of Power Systems
With Variable Speed Wind Turbines,” IEEE Transactions on Sustainable Energy, vol. 3, no. 4,
pp. 683–691, Oct. 2012.
[20] “The Enhanced Frequency Control Capability (EFCC) project closing down
report,” Tech. Rep., 2019, Accessed 21/07/2020. [Online]. Available:
https://www.nationalgrideso.com/document/144566/download
[21] J. Brisebois and N. Aubut, “Wind farm inertia emulation to fulfill Hydro-Québec’s specific need,”
in 2011 IEEE Power and Energy Society General Meeting, Jul. 2011, pp. 1–7.
[22] J. Bradley, “DC0079 Frequency Changes during Large Disturbances and their
Impact on the Total System,” 2017, Accessed 21/07/2020. [Online]. Available:
http://www.dcode.org.uk/assets/files/RTA/DCRP_MP_18_08_DC0079%20Retrospective%20Application%20RTA
[23] Balancing code no. 1 Pre gate closure process, Accessed 21/07/2020. [Online]. Available:
https://www.ofgem.gov.uk/ofgem-publications/54725/9753-5505gcbc1.pdf
[24] National Grid ESO, “Proposed BM startup service,” Tech. Rep., 2006, Accessed 2020-12-02.
[Online]. Available: https://www.nationalgrideso.com/document/90771/download
[25] E. Ela, V. Gevorgian, A. Tuohy, B. Kirby, M. Milligan, and M. O’Malley, “Market Designs
for the Primary Frequency Response Ancillary Service—Part I: Motivation and Design,” IEEE
Transactions on Power Systems, vol. 29, no. 1, pp. 421–431, Jan. 2014.
[26] L. Badesa, F. Teng, and G. Strbac, “Economic value of inertia in low-carbon power systems,”
in 2017 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT-Europe), Sep.
2017, pp. 1–6.
[28] L. Badesa, F. Teng, and G. Strbac, “Simultaneous Scheduling of Multiple Frequency Services in
Stochastic Unit Commitment,” IEEE Transactions on Power Systems, vol. 34 (5), pp. 3858–3868,
2019.
[29] M. Kelly, F. McNamara, A. Cooke, and T. Canning, “Modelling of post generation loss frequency
behaviour in power systems,” in International Conference on Large High Voltage Electric Systems,
vol. 2, 1994, pp. 38–307.
22
[30] T. Inoue, H. Taniguchi, Y. Ikeguchi, and K. Yoshida, “Estimation of power system inertia constant
and capacity of spinning-reserve support generators using measured frequency transients,” IEEE
Transactions on Power Systems, vol. 12, no. 1, pp. 136–143, 1997.
[32] D. Zografos, M. Ghandhari, and R. Eriksson, “Power system inertia estimation: Utilization of
frequency and voltage response after a disturbance,” Electric Power Systems Research, vol. 161,
pp. 52–60, 2018.
[34] D. Zografos, M. Ghandhari, and K. Paridari, “Estimation of power system inertia using particle
swarm optimization,” in 2017 19th International Conference on Intelligent System Application to
Power Systems (ISAP), 2017, pp. 1–6.
[35] G. Chavan, M. Weiss, A. Chakrabortty, S. Bhattacharya, A. Salazar, and F.-H. Ashrafi, “Identifica-
tion and Predictive Analysis of a Multi-Area WECC Power System Model Using Synchrophasors,”
IEEE Transactions on Smart Grid, vol. 8, no. 4, pp. 1977–1986, 2017.
[36] M. R. Bank Tavakoli, M. Power, L. Ruttledge, and D. Flynn, “Load Inertia Estimation Using
White and Grey-Box Estimators for Power Systems with High Wind Penetration,” IFAC Proceed-
ings Volumes, vol. 45, no. 21, pp. 399–404, 2012.
[37] T. Littler, B. Fox, and D. Flynn, “Measurement-based Estimation of Wind Farm Inertia,” in 2005
IEEE Russia Power Tech, 2005.
[39] Y. Bian, H. Wyman-Pain, F. Li, R. Bhakar, S. Mishra, and N. P. Padhy, “Demand Side Contribu-
tions for System Inertia in the GB Power System,” IEEE Transactions on Power Systems, vol. 33,
no. 4, pp. 3521–3530, 2018.
23
[40] J. Schiffer, P. Aristidou, and R. Ortega, “Online Estimation of Power System Inertia Using Dy-
namic Regressor Extension and Mixing,” IEEE Transactions on Power Systems, vol. 34 (6), pp.
4993–5001, 2019.
[41] G. Cai, B. Wang, D. Yang, Z. L. Sun, and L. Wang, “Inertia Estimation based on Observed Elec-
tromechanical Oscillation Response for Power Systems,” IEEE Transactions on Power Systems,
vol. 34 (6), pp. 4291–4299, 2019.
[42] P. Wall and V. Terzija, “Simultaneous Estimation of the Time of Disturbance and Inertia in Power
Systems,” IEEE Transactions on Power Delivery, vol. 29, no. 4, pp. 2018–2031, 2014.
[44] J. H. Chow, A. Chakrabortty, L. Vanfretti, and M. Arcak, “Estimation of radial power system
transfer path dynamic parameters using synchronized phasor data,” IEEE Transactions on Power
Systems, vol. 23, no. 2, pp. 564–571, 2008.
[45] P. Wall, F. Gonzalez-Longatt, and V. Terzija, “Estimation of generator inertia available during a
disturbance,” in 2012 IEEE Power and Energy Society General Meeting, 2012, pp. 1–8.
[46] M. Sun, Y. Feng, P. Wall, S. Azizi, J. Yu, and V. Terzija, “On-line power system inertia calculation
using wide area measurements,” International Journal of Electrical Power & Energy Systems, vol.
109, pp. 325–331, 2019.
[47] Z. Huang, P. Du, D. Kosterev, and S. Yang, “Generator dynamic model validation and parameter
calibration using phasor measurements at the point of connection,” IEEE Transactions on Power
Systems, vol. 28, no. 2, pp. 1939–1949, 2013.
[48] K. Kalsi, Y. Sun, Z. Huang, P. Du, R. Diao, K. K. Anderson, Y. Li, and B. Lee, “Calibrating
multi-machine power system parameters with the extended kalman filter,” in 2011 IEEE Power
and Energy Society General Meeting. IEEE, 2011, pp. 1–8.
[49] S. Guo and J. Bialek, “Synchronous machine inertia constants updating using Wide Area Mea-
surements,” in 2012 3rd IEEE PES Innovative Smart Grid Technologies Europe (ISGT Europe),
2012, pp. 1–7.
24
[51] R. K. Panda, A. Mohapatra, and S. C. Srivastava, “Online Estimation of System Inertia in a
Power Network utilizing Synchrophasor Measurements,” IEEE Transactions on Power Systems,
p. [Early access], 2019.
[53] K. Tuttelberg, J. Kilter, D. Wilson, and K. Uhlen, “Estimation of Power System Inertia From
Ambient Wide Area Measurements,” IEEE Transactions on Power Systems, vol. 33, no. 6, pp.
7249–7257, 2018.
[55] S. Guo, S. Norris, and J. Bialek, “Adaptive Parameter Estimation of Power System Dynamic
Model Using Modal Information,” IEEE Transactions on Power Systems, vol. 29, no. 6, pp. 2854–
2861, 2014.
[56] J. Zhang and H. Xu, “Online Identification of Power System Equivalent Inertia Constant,” IEEE
Transactions on Industrial Electronics, vol. 64, no. 10, pp. 8098–8107, 2017.
[57] P. Du and J. Matevosyan, “Forecast System Inertia Condition and Its Impact to Integrate More
Renewables,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 1531–1533, 2018.
[60] A. G. Phadke, “Synchronized phasor measurements in power systems,” IEEE Computer Applica-
tions in Power, vol. 6, no. 2, pp. 10–15, 1993.
[61] N. Shams, P. Wall, and V. Terzija, “Active Power Imbalance Detection, Size and Location Estima-
tion Using Limited PMU Measurements,” IEEE Transactions on Power Systems, vol. 34, no. 2,
pp. 1362–1372, 2019.
25
[62] P. Wall, P. Regulski, Z. Rusidovic, and V. Terzija, “Inertia estimation using PMUs in a laboratory,”
in IEEE PES Innovative Smart Grid Technologies, Europe, 2014, pp. 1–6.
[63] X. Cao, B. Stephen, I. F. Abdulhadi, C. D. Booth, and G. M. Burt, “Switching Markov Gaussian
Models for Dynamic Power System Inertia Estimation,” IEEE Transactions on Power Systems,
vol. 31, no. 5, pp. 3394–3403, Sep. 2016.
[64] W. Wang, W. Yao, C. Chen, X. Deng, and Y. Liu, “Fast and Accurate Frequency Response
Estimation for Large Power System Disturbances using Second Derivative of Frequency Data,”
IEEE Transactions on Power Systems, pp. 1–1, 2020.
[67] Y. Zhang, J. Bank, E. Muljadi, Y.-H. Wan, and D. Corbus, “Angle Instability Detection in Power
Systems With High-Wind Penetration Using Synchrophasor Measurements,” IEEE Journal of
Emerging and Selected Topics in Power Electronics, vol. 1, no. 4, pp. 306–314, 2013.
[68] P. Kundur, N. J. Balu, and M. G. Lauby, Power system stability and control. McGraw-hill New
York, 1994, vol. 7.
[69] W. Winter, K. Elkington, G. Bareux, and J. Kostevc, “Pushing the Limits: Europe’s New Grid:
Innovative Tools to Combat Transmission Bottlenecks and Reduced Inertia,” IEEE Power and
Energy Magazine, vol. 13, no. 1, pp. 60–74, 2015.
[70] E. Gonzalez, B. Stephen, D. Infield, and J. J. Melero, “Using high-frequency SCADA data for wind
turbine performance monitoring: A sensitivity study,” Renewable Energy, vol. 131, pp. 841–853,
2019.
[71] J. Yu, V. Terzija, D. Wilson, A. Nechifor, and M. Eves, “D2.1 Requirements for Monitoring
& Forecasting PE-based KPIs (2018),” Tech. Rep., Accessed 06/03/2020. [Online]. Available:
https://www.h2020-migrate.eu/_Resources/Persistent/7c5fc3e4d17b17ca2e3ea78815bfd35998cf2ae0/D2.1%20-%20R
[72] T. Hong and S. Fan, “Probabilistic electric load forecasting: A tutorial review,” International
Journal of Forecasting, vol. 32, no. 3, pp. 914–938, 2016.
26
[73] C. Kuster, Y. Rezgui, and M. Mourshed, “Electrical load forecasting models: A critical systematic
review,” Sustainable Cities and Society, vol. 35, pp. 257–270, 2017.
[74] R. Weron, “Electricity price forecasting: A review of the state-of-the-art with a look into the
future,” International Journal of Forecasting, vol. 30, no. 4, pp. 1030–1081, 2014.
[75] J. Nowotarski and R. Weron, “Recent advances in electricity price forecasting: A review of prob-
abilistic forecasting,” Renewable and Sustainable Energy Reviews, vol. 81, pp. 1548–1568, 2018.
[76] Y. Zhang, J. Wang, and X. Wang, “Review on probabilistic forecasting of wind power generation,”
Renewable and Sustainable Energy Reviews, vol. 32, pp. 255–270, 2014.
[78] C. Concordia and S. Ihara, “Load representation in power system stability studies,” IEEE trans-
actions on power apparatus and systems, no. 4, pp. 969–977, 1982.
[79] M. Ariff, B. Pal, and A. K. Singh, “Estimating dynamic model parameters for adaptive protection
and control in power system,” IEEE Transactions on Power Systems, vol. 30, no. 2, pp. 829–839,
2014.
[80] H. Tsai, A. Keyhani, J. Demcko, and R. Farmer, “On-line synchronous machine parameter estima-
tion from small disturbance operating data,” IEEE Transactions on Energy Conversion, vol. 10,
no. 1, pp. 25–36, 1995.
[81] M. Karrari and O. Malik, “Identification of physical parameters of a synchronous generator from
online measurements,” IEEE transactions on energy conversion, vol. 19, no. 2, pp. 407–415, 2004.
[82] “IEEE Guide for Test Procedures for Synchronous Machines Part I: Acceptance and Performance
Testing Part II: Test Procedures and Parameter Determination for Dynamic Analysis, IEEE Std
115-2009 (Revision of IEEE Std 115-1995),” Tech. Rep., 2010.
[83] T. Carriere and G. Kariniotakis, “An Integrated Approach for Value-oriented Energy Forecasting
and Data-driven Decision-making. Application to Renewable Energy Trading,” IEEE Transactions
on Smart Grid, vol. 10, no. 6, pp. 6933–6944, 2019.
27