Tornatech - GPX-GPD Presentation Nov 1 2018
Tornatech - GPX-GPD Presentation Nov 1 2018
Controllers
GPx – GPD Presentation
Fire Pump Controllers
Built to Standard
National Fire Protection Association (NFPA)
Pamphlet 20 (NFPA-20)
Standard for the Installation of Stationary Pumps for Fire
Protection
Latest Edition
Surge suppression
Surge arrestor rated to suppress surges above line voltage
7
full load current
Common flange mounted operating handle
Fire pump controllers
Fire Pump Controllers
General
Emergency start handle
Flange mounted
Pull and latch activation
Integrated limit switch
Across the line start
8
Trip between 8 and 20 seconds
Pressure readings
Continuous system pressure display
Cut-in and Cut-out pressure settings
13
current
14
Generator cooldown (factory set at 5 min - field adjustable 1 to
20 min)
Fire pump controllers
Fire Pump Controllers
Automatic Power Transfer Switch
Voltage sensing
Transfer to alternate (normal power dropout) 85% of
nominal - field adjustable 0 to 100%
Phase reversal transfer to alternate
Retransfer to normal (normal power pickup) 90% of
nominal - field adjustable 0 to 100%
Manual Start
Start pushbutton
Run test pushbutton
Deluge valve start
18
Remote start from manual device
Timers
Field Adjustable & Visual countdown
Minimum run timer (off delay)
Sequential start timer (on delay)
19
Periodic test timer
Mode
Visual indication
Automatic
20
Non-automatic
* Tornatech reserves the right to use any of these three alarm points for special
specific application requirements.
22
** Re-assignable
Note: Contacts are DPDT-8A-250VAC
STARTING CURRENT (% FLA) 500% -1000% 250% - 500% 210% - 420% 250%-450% 350%-700% 165% - 330% 165% - 330%
TRANSITION CURRENT (%
FLA)
- 250% - 500% 210% - 420% - 350% - 700% 165% - 330% 165% - 330%
10% - 100%
(adjustable on
STARTING TORQUE (% FLT) 50% - 150% 25% - 75% 40% - 85% 50% - 75% 20% - 50% 20% - 50%
Torque Ramp
mode)
STANDARD STANDARD
24
MOTOR TYPE STANDARD 6 WINDINGS STANDARD STANDARD STANDARD
WYE-DELTA WYE-DELTA
NUMBER OF WIRE
CONNECTIONS
3 WIRE 6 WIRE 3 WIRE 3 WIRE 3 WIRE 6 WIRE 6 WIRE
25
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of Full Load Current (FLC)
26
Integrated Limit Switch
28
Min. ampacity of motor conductors: 6 at 125% x 50% of FLC
Transformer
Current Transformers (3)
Motor Contactors
Control Relay
Emergency Start
Mechanism with
29
Integrated Limit Switch
31
Motor Type: Across the line (direct on line)
No. of Contactors: 2 at 42%, 1 at 33% of motor full load
current (FLC)
Min. ampacity of motor conductors: 3 at 125% x 100% of
Fire pump controllers
FLC
Fire Pump Controllers
Starting Methods: Reduced Voltage – Autotransformer
Control Relays
Emergency Start
Mechanism with
32
Integrated Limit Switch
Autotransformer
34
Motor Type: Across the line (direct on line)
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of full load current (FLC)
Fire pump controllers
Fire Pump Controllers
Starting Methods: Reduced Voltage – Electronic Soft Starter
(Soft Start / Soft Stop)
Circuit Breaker / Isolating
Switch Assembly
Surge Arrestor
Control Relays
Emergency Start
35
Mechanism with
Integrated Limit Switch
Soft Starter
37
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor full load current (FLC)
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC
Fire pump controllers
Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Closed
Control Relays
Emergency Start
38
Mechanism with
Integrated Limit Switch
Resistor
40
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor full load current (FLC)
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC
Emergency Start
Mechanism with
41
Integrated Limit Switch
External Components
ViZiTouch V2 Operator
Interface
Externally
mounted
pressure
transducer and
run test
solenoid valve Exterior USB Port
Key
43
with protective
cover. lock
Emergency start
handle
Fire pump controllers
Fire Pump Controllers
Internal Components
Circuit Breaker &
Isolating switch
assembly
Interior
USB Port
Motor Contactor
I/O board with
removable
alarm
contact
terminals
Model GPA Custom designed
emergency start
44
mechanism with
Surge
integrated limit switch
arrestor
4” Alarm
Bell
Custom designed IS/CB
operator handle
Externally ViZiTouch V2
mounted Operator Interface
pressure Transfer
transducer and switch
run test compartmen
solenoid valve Key t
45
with protective lock
cover.
Exterior USB Port
Surge
arrestor
Transfer Switch
46
Model GPU
Gland
Fire pump controllers
plate
Fire Pump Controllers
ViZiTouch V2 Operator Interface
Main features include:
7” color display
On-screen menu with intuitive icons
USB port cover (NEMA 4 rating)
Integrated touch screen protector
Powerful CPU
Multi-language
Upgradable software
66
Glossy textured finish
Automatic Start
Start on pressure drop
Remote start signal from automatic device
69
15s crank from battery 1
15s rest
15s crank
Fire pump controllers from battery 2
Fire Pump Controllers
Operational Features
Stopping
Manual with Stop pushbutton
Automatic after expiration of minimum run timer
(programmable)
Timers
Field Adjustable & Visual countdown
Minimum run timer (off delay)
Sequential start timer (on delay)
Periodic test timer
70
Mode
Visual indication
Automatic
Non-automatic
High Coolant
Alarm only Alarm only Shutdown
Temperature
73
Low Fuel Level Alarm only Alarm only Alarm only
** Re-assignable
4” Alarm Bell
75
Hand-Off-
Auto
selector
Fire pump controllers switch
Fire Pump Controllers
Internal Components
Interior
USB Port
EMI filter
Battery chargers
AC and DC
isolation circuit
breakers
Automotive type
engine connections
76
alarm contact terminals
Gland plate
Fire pump controllers
Fire Pump Controllers
ViZiTouch V2 Operator Interface
Main features include:
7” color display
On-screen menu with intuitive icons
USB port cover (NEMA 4 rating)
Integrated touch screen protector
Powerful CPU
Multi-language
Upgradable software
78
Language
Fire pump controllers
Fire Pump Controllers
On screen menu
85
Pump room temperature (˚F or ˚C)