Tornatech - GPX-GPD Presentation Nov 1 2018

The document provides an overview of fire pump controllers, detailing their compliance with NFPA standards and various certifications such as UL and FM Global. It describes the features of the GPx series controllers, including operational capabilities, starting methods, and safety mechanisms. Additionally, it outlines the specifications for automatic power transfer switches and enclosure features.

Uploaded by

mmoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views93 pages

Tornatech - GPX-GPD Presentation Nov 1 2018

The document provides an overview of fire pump controllers, detailing their compliance with NFPA standards and various certifications such as UL and FM Global. It describes the features of the GPx series controllers, including operational capabilities, starting methods, and safety mechanisms. Additionally, it outlines the specifications for automatic power transfer switches and enclosure features.

Uploaded by

mmoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPSX, PDF, TXT or read online on Scribd
You are on page 1/ 93

Fire Pump

Controllers
GPx – GPD Presentation
Fire Pump Controllers
Built to Standard
 National Fire Protection Association (NFPA)
 Pamphlet 20 (NFPA-20)
 Standard for the Installation of Stationary Pumps for Fire
Protection
 Latest Edition

Fire pump controllers 2


Fire Pump Controllers

Listings, Approvals & Certifications


Underwriters Laboratory (UL) CE Marking
 UL218 - Fire pump controllers  Optional
 UL1008 - Transfer Switch  Self-declaration
Equipment  Various EN, IEC & CEE
 CSA C22.2 No. 14 Industrial directives and standards
Control Equipment

FM Global New York City


 Approvals Class 1321/1323
 Accepted for use in the city of New
York by the Department of
Buildings

Fire pump controllers 3


Fire Pump Controllers
Listings, Approvals & Certifications
 Seismic Compliant
 Mounting arrangement: Wall /Rigid Wall Mounted
 Components are tested in accordance with ICC-ES
AC156, IBC 2015 & CBC 2016
 OSHPD Special Seismic Certification Preapproval (OSP)

Fire pump controllers 4


GPx Series
Full Service
Electric Fire Pump Controllers
Fire Pump Controllers
General
 Service entrance rating
 Suitable as service entrance equipment

 Surge suppression
 Surge arrestor rated to suppress surges above line voltage

Fire pump controllers 6


Fire Pump Controllers
General
 Disconnecting means (with or without transfer switch)
 Isolating switch and circuit breaker assembly
 Door interlocked in the ON position
 Isolating switch rated not less than 115% of motor full load
current
 Circuit breaker continuous rating not less than 115% of motor
full load current
 Overcurrent sensing non-thermal type, magnetic only
 Instantaneous trip setting of not more than 20 times the motor

7
full load current
 Common flange mounted operating handle
Fire pump controllers
Fire Pump Controllers
General
 Emergency start handle
 Flange mounted
 Pull and latch activation
 Integrated limit switch
 Across the line start

 Locked rotor protector


 Shunt trip operated
 Factory set at 600% of motor full load current

8
 Trip between 8 and 20 seconds

Fire pump controllers


Fire Pump Controllers
General
 Electrical readings
 Voltage phase to phase
 Amperage of each phase when motor is running

 Pressure readings
 Continuous system pressure display
 Cut-in and Cut-out pressure settings

Fire pump controllers 9


Fire Pump Controllers
General
 Pressure and event recorder
 Pressure readings with date stamp
 Event recording with date stamp
 Stored in memory for lifetime of controller
 Data viewable on operator interface display screen
 Downloadable by USB port to external memory device

Fire pump controllers 10


Fire Pump Controllers
Pressure Sensing
 Pressure transducer and run test solenoid valve
assembly for fresh water application
 Pressure sensing line connection 1/2” FNPT
 Drain connection 3/8”
 Rated for 0-500 PSI working pressure
(standard display at 0-300 PSI)
 Externally mounted with protective cover

Fire pump controllers 11


Fire Pump Controllers
Automatic Power Transfer Switch
 Model GPU
 In addition to main fire pump controller
 Housed in a separate enclosure attached
to main fire pump controller

Fire pump controllers 12


Fire Pump Controllers
Automatic Power Transfer Switch
 Dedicated disconnecting means
 Isolating switch and circuit breaker assembly
 Door interlocked in the ON position
 Isolating switch rated not less than 115% of motor full load current
 Circuit breaker continuous rating not less than 115% of motor full load
current
 Overcurrent sensing non-thermal type, magnetic only
 Instantaneous trip setting of not more than 20 times the motor full load

13
current

Fire pump controllers


Fire Pump Controllers
Automatic Power Transfer Switch
 Time Delays
 Momentary normal power outage override (factory set at 3sec -
field adjustable 1 to 3 sec)
 Alternate (emergency) power available delay (factory set at 3
sec - field adjustable 1 to 3 sec)
 Transfer trouble delay (factory set at 20 sec - field adjustable 1
to 60 sec)
 Retransfer to normal (factory set at 5 min - field adjustable 1 to
20 min)

14
 Generator cooldown (factory set at 5 min - field adjustable 1 to
20 min)
Fire pump controllers
Fire Pump Controllers
Automatic Power Transfer Switch
 Voltage sensing
 Transfer to alternate (normal power dropout) 85% of
nominal - field adjustable 0 to 100%
 Phase reversal transfer to alternate
 Retransfer to normal (normal power pickup) 90% of
nominal - field adjustable 0 to 100%

Fire pump controllers 15


Fire Pump Controllers
Automatic Power Transfer Switch
 Audible Alarm (AIS Open)
 4” alarm bell - 85dB at 10ft.
(3m)

 Generator Start Connection


 SPDT- 8A-250V.AC

Fire pump controllers 16


Fire Pump Controllers
Enclosure Features
 Red RAL3002
 Powder Coating
 Glossy textured finish
 Type 2 (NEMA)
 Bottom entry gland plate
 Lifting Lugs
 Latch system with key lock

Fire pump controllers 17


Fire Pump Controllers
Operational Features
 Automatic Start
 Start on pressure drop
 Remote start signal from automatic device

 Manual Start
 Start pushbutton
 Run test pushbutton
 Deluge valve start

18
 Remote start from manual device

Fire pump controllers


Fire Pump Controllers
Operational Features
 Stopping
 Manual with Stop pushbutton
 Automatic after expiration of minimum run
timer

 Timers
 Field Adjustable & Visual countdown
 Minimum run timer (off delay)
 Sequential start timer (on delay)

19
 Periodic test timer

Fire pump controllers


Fire Pump Controllers
Operational Features
 Actuation
 Visual indication
 Pressure
 Non-pressure

 Mode
 Visual indication
 Automatic

20
 Non-automatic

Fire pump controllers


Fire Pump Controllers
Operational Features
 Transfer switch test pushbutton
 Bypass for re-transfer and generator
shutdown
 Electrically operated and mechanically held
in the normal or alternate position
 Provision for manual operation

Fire pump controllers 21


Fire Pump Controllers
Standard Remote Alarm Contacts
 Power available
 Phase reversal
 Motor run
 Common pump room alarm**
 Common motor trouble**
 Free (field programmable)*

* Tornatech reserves the right to use any of these three alarm points for special
specific application requirements.

22
** Re-assignable
Note: Contacts are DPDT-8A-250VAC

Fire pump controllers


Fire Pump Controllers
Standard Remote Alarm Contacts
 With transfer switch
 Isolating switch in the OFF position
 Transfer switch in normal position
 Transfer switch in alternate (emergency) position

Note: Contacts are SPDT-8A-250VAC


Fire pump controllers 23
Fire Pump Controllers
Starting Methods Summary
WYE-DELTA WYE-DELTA
ACROSS- PART AUTO SOFT START PRIMARY
CLOSED OPEN
THE-LINE WINDING TRANSFORMER SOFT STOP RESISTOR
TRANSITION TRANSITION
MODEL NUMBER GPA GPP GPR GPS GPV GPW GPY (5)
STARTING VOLTAGE PER
WINDING
FULL FULL REDUCED REDUCED REDUCED REDUCED REDUCED
TYPICAL VOLTAGE APPLIED
30% - 50%
AT 100% 100% 65% 70% 100% 100%
MOTOR STARTING (% Vn) (adjustable)
PEAK INRUSH CURRENT
AT STARTING
(10 - 28) x FLA (5 - 14) x FLA (4 - 11) x FLA NEGLIGIBLE (7 - 20) x FLA (3.5 - 9) x FLA (3.5 - 9) x FLA

PEAK INRUSH CURRENT


AT TRANSITION
- (2 - 5) x FLA (4 - 11) x FLA NEGLIGIBLE (7 - 20) x FLA NEGLIGIBLE (3.5 - 9) x FLA

STARTING CURRENT (% FLA) 500% -1000% 250% - 500% 210% - 420% 250%-450% 350%-700% 165% - 330% 165% - 330%

TRANSITION CURRENT (%
FLA)
- 250% - 500% 210% - 420% - 350% - 700% 165% - 330% 165% - 330%
10% - 100%
(adjustable on
STARTING TORQUE (% FLT) 50% - 150% 25% - 75% 40% - 85% 50% - 75% 20% - 50% 20% - 50%
Torque Ramp
mode)
STANDARD STANDARD

24
MOTOR TYPE STANDARD 6 WINDINGS STANDARD STANDARD STANDARD
WYE-DELTA WYE-DELTA
NUMBER OF WIRE
CONNECTIONS
3 WIRE 6 WIRE 3 WIRE 3 WIRE 3 WIRE 6 WIRE 6 WIRE

Fire pump controllers


Fire Pump Controllers
Starting Methods: Full Voltage - Across the Line (Direct on Line)

Starting Method: Full Voltage Across the line (Direct on line)


Typical Voltage Applied at Start: 100%
Inrush Current: 6x normal load current
Starting Torque: 100% Motor
Type: Across the line (Direct on line)

25
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of Full Load Current (FLC)

Fire pump controllers


Fire Pump Controllers
Starting Methods: Full Voltage - Across the Line (Direct on Line)

Circuit Breaker / Isolating


Switch Assembly

Isolating Switch / Circuit


Breaker Operator Handle
I/O Board

Current Transformers (3)


Surge Arrestor
Motor Contactor

Control Relay Emergency Start


Mechanism with

26
Integrated Limit Switch

Fire pump controllers


Fire Pump Controllers
Starting Methods: Full Voltage - Across the Line (Direct on Line)

Fire pump controllers 27


Fire Pump Controllers
Starting Methods: Reduced Voltage – Part Winding

Starting Method: Reduced Voltage - Part winding


Typical Voltage Applied at Start: 100%
Inrush Current: 65% of normal with first winding
Starting Torque: 48%
Motor Type: Part winding
No. of Contactors: 2 at 50% of motor full load current (FLC)

28
Min. ampacity of motor conductors: 6 at 125% x 50% of FLC

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Part Winding

Circuit Breaker / Isolating


Switch Assembly
Surge Arrestor

Isolating Switch / Circuit


I/O Board Breaker Operator Handle

Transformer
Current Transformers (3)

Motor Contactors

Control Relay
Emergency Start
Mechanism with

29
Integrated Limit Switch

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Part Winding

Fire pump controllers 30


Fire Pump Controllers
Starting Methods: Reduced Voltage – Autotransformer

Starting Method: Reduced Voltage - Autotransformer


Typical Voltage Applied at Start: 65%
Inrush Current: 42% of normal load current
Starting Torque: 42%

31
Motor Type: Across the line (direct on line)
No. of Contactors: 2 at 42%, 1 at 33% of motor full load
current (FLC)
Min. ampacity of motor conductors: 3 at 125% x 100% of
Fire pump controllers
FLC
Fire Pump Controllers
Starting Methods: Reduced Voltage – Autotransformer

Circuit Breaker / Isolating


Switch Assembly
Surge Arrestor

Isolating Switch / Circuit


Breaker Operator Handle
I/O Board

Control Relays

Current Transformers (3)


Transformer
Motor Contactors

Emergency Start
Mechanism with

32
Integrated Limit Switch
Autotransformer

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Autotransformer

Fire pump controllers 33


Fire Pump Controllers
Starting Methods: Reduced Voltage – Electronic Soft Starter
(Soft Start / Soft Stop)

Starting Method: Reduced Voltage - Soft start / soft stop


Typical Voltage Applied at Start: 30%
Inrush Current: 30% (adjustable)
Starting Torque: 30%

34
Motor Type: Across the line (direct on line)
No. of Contactors: 1 at 100% of horsepower
Min. ampacity of motor conductors: 3 at 125% x 100% of full load current (FLC)
Fire pump controllers
Fire Pump Controllers
Starting Methods: Reduced Voltage – Electronic Soft Starter
(Soft Start / Soft Stop)
Circuit Breaker / Isolating
Switch Assembly
Surge Arrestor

Isolating Switch / Circuit


Breaker Operator Handle
I/O Board

Control Relays

Current Transformers (3)


Transformer
Motor Contactors

Emergency Start

35
Mechanism with
Integrated Limit Switch
Soft Starter

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Electronic Soft Starter
(Soft Start / Soft Stop)

Fire pump controllers 36


Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Closed

Starting Method: Reduced Voltage - Wye-delta closed


Typical Voltage Applied at Start: 100%
Inrush Current: 33% of normal load current
Starting Torque: 33%

37
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor full load current (FLC)
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC
Fire pump controllers
Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Closed

Circuit Breaker / Isolating


Switch Assembly
Surge Arrestor

Isolating Switch / Circuit


Breaker Operator Handle
I/O Board

Control Relays

Current Transformers (3)


Transformer
Motor Contactors

Emergency Start

38
Mechanism with
Integrated Limit Switch
Resistor

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Closed

Fire pump controllers 39


Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Open

Starting Method: Reduced Voltage - Wye-delta open


Typical Voltage Applied at Start: 100%
Inrush Current: 33% of normal load current
Starting Torque: 33%

40
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor full load current (FLC)
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Open

Circuit Breaker / Isolating


Switch Assembly
Surge Arrestor

Isolating Switch / Circuit


Breaker Operator Handle
I/O Board

Current Transformers (3)


Transformer
Motor Contactors
Control Relays

Emergency Start
Mechanism with

41
Integrated Limit Switch

Fire pump controllers


Fire Pump Controllers
Starting Methods: Reduced Voltage – Wye Delta Open

Fire pump controllers 42


Fire Pump Controllers
Lifting Lugs

External Components
ViZiTouch V2 Operator
Interface

4” Alarm Custom Designed IS/CB


Bell operator handle

Externally
mounted
pressure
transducer and
run test
solenoid valve Exterior USB Port
Key

43
with protective
cover. lock
Emergency start
handle
Fire pump controllers
Fire Pump Controllers
Internal Components
Circuit Breaker &
Isolating switch
assembly
Interior
USB Port

Motor Contactor
I/O board with
removable
alarm
contact
terminals
Model GPA Custom designed
emergency start

44
mechanism with
Surge
integrated limit switch
arrestor

Fire pump controllers


Gland
plate
Fire Pump Controllers
External Components Lifting Lugs

4” Alarm
Bell
Custom designed IS/CB
operator handle

Externally ViZiTouch V2
mounted Operator Interface
pressure Transfer
transducer and switch
run test compartmen
solenoid valve Key t

45
with protective lock
cover.
Exterior USB Port

Fire pump controllers


Fire Pump Controllers
Internal Components

I/O board with


removable alarm
contact terminals
Circuit Breaker
& Isolating
switch
assembly

Surge
arrestor

Transfer Switch

46
Model GPU

Gland
Fire pump controllers
plate
Fire Pump Controllers
ViZiTouch V2 Operator Interface
Main features include:
 7” color display
 On-screen menu with intuitive icons
 USB port cover (NEMA 4 rating)
 Integrated touch screen protector
 Powerful CPU
 Multi-language
 Upgradable software

Fire pump controllers 47


Fire Pump Controllers
Home Screen

Fire pump controllers 48


Fire Pump Controllers
Home Screen with Automatic Transfer switch

Fire pump controllers 49


Fire Pump Controllers
On screen menu
Home
Alarms
Configuration
History
Service
Manuals
Language
Fire pump controllers 50
Fire Pump Controllers
Alarms / Events

Fire pump controllers 51


Fire Pump Controllers
Configuration

Fire pump controllers 52


Fire Pump Controllers
History

Fire pump controllers 53


Fire Pump Controllers
Service

Fire pump controllers 54


Fire Pump Controllers
Languages

Fire pump controllers 55


Fire Pump Controllers
Visual Indications
 Power available (Normal /Alternate) Remote automatic start
 Motor run  Remote manual start
 Periodic test  Pump on demand/Automatic start
 Manual start  Low discharge pressure
 Deluge valve start  Pump room temperature (˚F or ˚C)
 Emergency start  Lockout

Fire pump controllers 56


Fire Pump Controllers
Visual Indications (Transfer Switch)
 Alternate (emergency) isolating switch in the OFF
position
 Alternate (emergency) voltage phase to phase
 Transfer switch in normal position
 Transition timers

Fire pump controllers 57


Fire Pump Controllers
Visual Alarms
 Control Voltage not Healthy  Low Water Level
 Fail to Start  Motor Trouble
 Invalid Cut-In  Normal Power Phase Reversal
 Lock Rotor Current  Overcurrent
 Loss of Power  Overvoltage
 Low Ambient Temperature

Fire pump controllers 58


Fire Pump Controllers
Visual Alarms
 Phase Loss L1  Pump Room Alarm
 Phase Loss L2  Service Required
 Phase Loss L3  Undercurrent
 Phase Unbalanced  Undervoltage
 Pressure Transducer fault detected  Check Weekly Test Solenoid
 Pump on Demand  Weekly Test Cut-In Not Reached

Fire pump controllers 59


Fire Pump Controllers
Visual Alarms (Transfer Switch)
 Automatic Transfer switch trouble
 Alternate power phase reversal
 Alternate locked rotor current

Fire pump controllers 60


Fire Pump Controllers
Visual & Audible Alarms (Transfer Switch)
 Alternate isolating switch open/tripped
 Alternate circuit breaker in Off or tripped

Fire pump controllers 61


Model GPD
Diesel Engine
Fire Pump Controllers
Fire Pump Controllers
General

 AC power supply  Grounding system


 120V/1ph/60hz  Negative
 208V to 240V/1ph/50-60hz
 Battery chargers
 Engine starting voltage  Two independent fully
 12VDC automatic
 24VDC  10A continuous charge
 500mA trickle charge

Fire pump controllers 63


Fire Pump Controllers
Pressure Sensing
 Pressure transducer and run test
solenoid valve assembly for fresh water
application
 Pressure sensing line connection 1/2”
FNPT
 Rated for 0-500 PSI working pressure
(standard display at 0-300 PSI)
 Externally mounted with protective
Firecover
pump controllers 64
Fire Pump Controllers
Audible Alarm

4” alarm bell


85dB at 10ft. (3m)

Fire pump controllers 65


Fire Pump Controllers
Enclosure Features
 Type 2 (NEMA)
 Bottom entry gland plate
 Wall mounting lugs
 Latch system with key lock
 Red RAL3002
 Powder Coating

66
 Glossy textured finish

Fire pump controllers


Fire Pump Controllers
Enclosure Features
 Dimensions:
 Wall Mount: 27-1/2"h x 27w x 9-5/8"d
 Floor Mount: 48"h x 27"w x 9-5/8"d
 Mounting stand (Option D25)

Fire pump controllers 67


Fire Pump Controllers
Operational Features
 Selector switch
 HAND-OFF-AUTO
 Behind lockable and breakable cover

 Automatic Start
 Start on pressure drop
 Remote start signal from automatic device

Fire pump controllers 68


Fire Pump Controllers
Operational Features
 Manual Start
 Crank 1 and Crank 2 start pushbutton
 Run test pushbutton
 Deluge valve start
 Remote start from manual device
 Crank cycle
 3 consecutive cycle attempts

69
 15s crank from battery 1
 15s rest
 15s crank
Fire pump controllers from battery 2
Fire Pump Controllers
Operational Features
 Stopping
 Manual with Stop pushbutton
 Automatic after expiration of minimum run timer
(programmable)

 Timers
 Field Adjustable & Visual countdown
 Minimum run timer (off delay)
 Sequential start timer (on delay)
Periodic test timer

70

Fire pump controllers


Fire Pump Controllers
Operational Features
 Actuation
 Visual indication
 Pressure
 Non-pressure

 Mode
 Visual indication
 Automatic
 Non-automatic

Fire pump controllers 71


Fire Pump Controllers
Run Test Push Button
 Operational in the AUTO position only
 Energizes run test solenoid valve to
create artificial pressure drop and
start the engine

Fire pump controllers 72


Fire Pump Controllers
Operational Features

Manual Start or Run Test or


Automatic Start
Remote Start Periodic Test

High Coolant
Alarm only Alarm only Shutdown
Temperature

Low Oil Pressure Alarm only Alarm only Shutdown


Alarm &
Shutdown Overspeed Shutdown Shutdown Shutdown
Schedule Pump Room
Low/High Ambient Alarm only Alarm only Alarm only
Temperature

73
Low Fuel Level Alarm only Alarm only Alarm only

Fire pump controllers


Fire Pump Controllers
Standard Remote Alarm Contacts
 Controller trouble
 Engine run / Louver activation circuit
 Main switch in HAND or OFF
 Engine trouble**
 Pump room alarm**
 Field Programmable

** Re-assignable

Fire pump controllers 74


Fire Pump Controllers ViZiTouch V2
Operator Interface
External Components
Key Lock

4” Alarm Bell

Externally mounted pressure


transducer and run test solenoid
valve with protective cover
Exterior USB Port

75
Hand-Off-
Auto
selector
Fire pump controllers switch
Fire Pump Controllers
Internal Components
Interior
USB Port

EMI filter
Battery chargers

AC and DC
isolation circuit
breakers
Automotive type
engine connections

I/O board with removable

76
alarm contact terminals

Gland plate
Fire pump controllers
Fire Pump Controllers
ViZiTouch V2 Operator Interface
Main features include:
 7” color display
 On-screen menu with intuitive icons
 USB port cover (NEMA 4 rating)
 Integrated touch screen protector
 Powerful CPU
 Multi-language
 Upgradable software

Fire pump controllers 77


Fire Pump Controllers
Home Screen
Home
Alarms
Configuration
History
Service
Manuals

78
Language
Fire pump controllers
Fire Pump Controllers
On screen menu

Fire pump controllers 79


Fire Pump Controllers
Alarms / Events

Fire pump controllers 80


Fire Pump Controllers
Configuration

Fire pump controllers 81


Fire Pump Controllers
History

Fire pump controllers 82


Fire Pump Controllers
Service

Fire pump controllers 83


Fire Pump Controllers
Languages

Fire pump controllers 84


Fire Pump Controllers
Visual Indications
 Engine run
 Main switch AUTO
 Main switch in OFF
 Main switch in HAND
 Periodic test
 Cranking Cycle
 AC Power available

85
 Pump room temperature (˚F or ˚C)

Fire pump controllers


Fire Pump Controllers
Visual Alarms
• Pump room trouble • Weak battery 2
• Pump on demand • Battery 1 overvoltage
• AC Failure • Battery 2 overvoltage
• Charger 1 Failure • Loss of continuity 1
• Charger 2 Failure • Loss of continuity 2
• Weak battery 1 • High fuel level

Fire pump controllers 86


Fire Pump Controllers
Visual Alarms
• Fuel tank leak • ECM warning
• Low suction pressure • Weekly test cut-in not reached
• High raw water temperature • Check weekly test solenoid
• Water reservoir low • Pressure transducer fault
• Low pump room temperature • Invalid Cut-In
• High pump room temperature • Service required

Fire pump controllers 87


Fire Pump Controllers
Visual and Audible Alarms
• Engine trouble • Battery 1 Failure
• Controller trouble • Battery 2 Failure
• Engine low oil pressure • Engine fail to start
• Engine high temperature • Low fuel level
• Engine low temperature • ECM fault
• Engine overspeed • ECM SS in Alternate Position
• DC Failure • Fuel injection malfunction

Fire pump controllers 88


Fire Pump Controllers
Visual and Audible Alarms
 Low fuel level  Engine high temperature
 High fuel level  Engine low temperature
 Engine ECM in alternate position  Engine ECM fault
 Engine fuel injection malfunction  Engine low oil pressure

Fire pump controllers 89


Fire Pump Controllers
Field Connections

Fire pump controllers 90


Fire Pump Controllers
Engine Connections

Fire pump controllers 91


Fire Pump Controllers
Engine Connections

Fire pump controllers 92


Thank you!
Americas Europe Middle East Asia