GINLONG TECHNOLOGIES CO.,LTD.
S6-EH1P(12-16)K03-NV-YD-L
Solis Single Phase Low Voltage Energy Storage Inverters
Features:
• Generator-compatible to extend backup duration during grid power outage
• Multiple inverters can operate together to form a microgrid
• Supports dual backup ports for intelligent control of critical and non-critical loads
• 10 seconds of 200% overload capability
• Automatic switchover time is < 4ms, providing seamless transitions from grid to backup
• Supports a maximum input current of 20A, making it ideal for all high-power PV modules of any brand
• Ensures excellent power supply stability, keeping the load unaffected by a weak grid or generator
supply fluctuations
• The battery's DC side can handle a maximum charge/discharge current of up to 290A, allowing it to
store more surplus energy generated by PV systems 英语
NEW
Models:
S6-EH1P12K03-NV-YD-L
S6-EH1P14K03-NV-YD-L
S6-EH1P16K03-NV-YD-L
www.solisinverters.com
DATASHEET S6-EH1P(12-16)K03-NV-YD-L
Models 12K 14K 16K
Input DC (PV side)
Recommended max. PV array size 24 kW 28 kW 32 kW
Max. usable PV input power 19.2 kW 22.4 kW 22.4 kW
Max. input voltage 550 V
Rated voltage 380 V
Start-up voltage 100 V
MPPT voltage range 80 - 520 V
Max. input current 40 A / 40 A / 40 A
Max. short circuit current 50 A / 50 A / 50 A
MPPT number / Max. input strings number 3/6
Battery
Battery type Li-ion / Lead-acid
Battery voltage range 40 - 60 V
Max. charge / discharge current 250 A 290 A 290 A
Communication CAN / RS485
Output AC (Grid side)
Rated output power 12 kW 14 kW 16 kW
Operation phase L/N/PE
Rated grid voltage 220 V / 230 V
Rated grid frequency 50 Hz / 60 Hz
Rated grid output current 54.5 A / 52.2 A 63.6 A / 60.9 A 72.7 A / 69.6 A
Power factor > 0.99 (0.8 leading - 0.8 lagging)
THDi < 3%
Input AC (Grid side)
y
Input voltage range 187 - 253 V
r
Max. input current 81.8 A / 78.3 A 95.5 A / 91.3 A 109.1 A / 104.3 A
a
Frequency range 45 - 55 Hz / 55 - 65 Hz
Output AC (Back-up)
n
Rated output power 12 kW 14 kW 16 kW
i
Max. apparent output power 2 times of rated power, 10 s
Back-up switch time < 4 ms
im
Rated output voltage L/N/PE, 220 V / 230 V
l
Rated frequency 50 Hz / 60 Hz
Rated output current 54.5 A / 52.2 A 63.6 A / 60.9 A 72.7 A / 69.6 A
re
THDv (@linear load) < 3%
Input Generator
P
Max. input power 12 kW 14 kW 16 kW
Max. input current 54.5 A / 52.2 A 63.6 A / 60.9 A 72.7 A / 69.6 A
Rated input frequency 50 Hz / 60 Hz
Efficiency
Max. efficiency 97.6%
EU efficiency 97.2%
BAT charged by PV max. efficiency > 94.9%
BAT charged / discharged to AC max. efficiency > 94.33% / 93.51%
Protection
Surge protection Yes
DC reverse-polarity protection Yes (PV only)
Ground fault monitoring Yes
Integrated AFCI 2.0 Optional
Protection class / Over voltage category I / II (PV and BAT), III (MAINS and BACKUP and GEN)
General Data
Dimensions (W × H × D) 464 × 763 × 282 mm
Weight 48.5 kg
Topology Transformerless
Operating ambient temperature range -25 ~ +60°C
Ingress protection IP66
Noise emission (typical) < 65 dB(A)
Cooling concept Intelligent fan-cooling
Max. operation altitude 4000 m
Grid connection standard NRS 097-2-1, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530
Safety / EMC standard IEC/EN 62109-1/-2, EN 61000-6-2/-3
Features
DC connection MC4 plug (PV port) / Terminal Block (BAT port)
AC connection Terminal Block
Display 7.0" LCD display & Bluetooth + APP
Communication RS485, Optional: Cellular, Wi-Fi, LAN