0% found this document useful (0 votes)
9 views

Instruction Manual Fieldvue Dvc6000 Hw2 Digital Valve Controller en 123642

The DVC6000 HW2 Digital Valve Controller Instruction Manual provides comprehensive information on the device's specifications, wiring practices, configuration, calibration, and troubleshooting. It is applicable to various instrument levels and includes detailed sections on setup, maintenance, and diagnostics. The manual is intended for users to effectively operate and maintain the digital valve controller.

Uploaded by

Emilio Bernal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views

Instruction Manual Fieldvue Dvc6000 Hw2 Digital Valve Controller en 123642

The DVC6000 HW2 Digital Valve Controller Instruction Manual provides comprehensive information on the device's specifications, wiring practices, configuration, calibration, and troubleshooting. It is applicable to various instrument levels and includes detailed sections on setup, maintenance, and diagnostics. The manual is intended for users to effectively operate and maintain the digital valve controller.

Uploaded by

Emilio Bernal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 124

Instruction Manual DVC6000 HW2 Digital Valve Controller

D103785X012 February 2023

Fisher™ FIELDVUE™ DVC6000 HW2 Digital Valve


Controller
This manual applies to
Instrument Level HC, AD, PD, ODV
Device Type 130b
Hardware Revision 2
Firmware Revision 7
Device Revision 13
DD Revision 71

Contents
Section 1 Introduction . . . . . . . . . . . . . . . . . 3
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Conventions Used in this Manual . . . . . . . . . . . . . . . . 3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Educational Services . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section 2 Wiring Practices . . . . . . . . . . . . . . 9
Control System Requirements . . . . . . . . . . . . . . . . . . 9
HART Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Voltage Available . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Travel/Pressure Control . . . . . . . . . . . . . . . . . . . . . . 23
Compliance Voltage . . . . . . . . . . . . . . . . . . . . . . . . 11 Travel/Pressure Select . . . . . . . . . . . . . . . . . . . 23
Auxiliary Terminal Wiring Length Guidelines . . . . 12 Cutoffs and Limits . . . . . . . . . . . . . . . . . . . . . . . 23
Maximum Cable Capacitance . . . . . . . . . . . . . . . . . 12 Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . 24
Remote Travel Sensor Connections . . . . . . . . . . . . . 13 Pressure Fallback . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation in Conjunction with a Rosemountt Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 24
333 HART Tri‐Loopt HART‐to‐Analog Characterization . . . . . . . . . . . . . . . . . . . . . . . . 25
Signal Converter . . . . . . . . . . . . . . . . . . . . . . . . . 17 Dynamic Response . . . . . . . . . . . . . . . . . . . . . . 27
Section 3 Configuration . . . . . . . . . . . . . . . 19 Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Guided Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Travel Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Manual Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Pressure Tuning . . . . . . . . . . . . . . . . . . . . . . . . 31
Mode and Protection . . . . . . . . . . . . . . . . . . . . . . . . 20 Travel/Pressure Integral Settings . . . . . . . . . . 31
Instrument Mode . . . . . . . . . . . . . . . . . . . . . . . 20 Valve and Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Write Protection . . . . . . . . . . . . . . . . . . . . . . . . 20 Partial Stroke Test . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Output Terminal Configuration . . . . . . . . . . . . 40
Serial Numbers . . . . . . . . . . . . . . . . . . . . . . . . . 21 Switch Configuration . . . . . . . . . . . . . . . . . . . . 40
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 HART Variable Assignments . . . . . . . . . . . . . . 41
Terminal Box . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Transmitter Output . . . . . . . . . . . . . . . . . . . . . 41
Input Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Burst Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Spec Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Alert Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Edit Instrument Time . . . . . . . . . . . . . . . . . . . . 22 Change to HART 5 / HART 7 . . . . . . . . . . . . . . . . . . . . 42

www.Fisher.com
DVC6000 HW2 Digital Valve Controller Instruction Manual
February 2023 D103785X012

Contents (continued) I/P Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Printed Wiring Board (PWB) Assembly . . . . . . . . . .
71
73
Section 4 Calibration . . . . . . . . . . . . . . . . . 43 Pneumatic Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . 43 Gauges, Pipe Plugs or Tire Valves . . . . . . . . . . . . . . 76
Travel Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Terminal Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Auto Calibration . . . . . . . . . . . . . . . . . . . . . . . . 44 Removing the Terminal Box . . . . . . . . . . . . . . . . . . 76
Manual Calibration . . . . . . . . . . . . . . . . . . . . . . 46 Replacing the Terminal Box . . . . . . . . . . . . . . . . . . . 77
Pushbutton Calibration . . . . . . . . . . . . . . . . . . 47 Travel Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sensor Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Pressure Sensors . . . . . . . . . . . . . . . . . . . . . . . . 48 DVC6015 Remote Feedback Unit . . . . . . . . . . 78
Travel Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 DVC6025 Remote Feedback Unit . . . . . . . . . . 79
Analog Input Calibration . . . . . . . . . . . . . . . . . 53 DVC6035 Remote Feedback Unit . . . . . . . . . . 79
Relay Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Double‐Acting Relay . . . . . . . . . . . . . . . . . . . . . 54 DVC6015 Feedback Unit . . . . . . . . . . . . . . . . . 79
Single‐Acting Relays . . . . . . . . . . . . . . . . . . . . . 55 DVC6025 Feedback Unit . . . . . . . . . . . . . . . . . 80
PST Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 DVC6035 Feedback Unit . . . . . . . . . . . . . . . . . 82
Section 5 Device Information, Alerts, Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
and Diagnostics . . . . . . . . . . . . . . . . . . . . . 57 Checking Voltage Available . . . . . . . . . . . . . . . . . . . . 84
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 DVC6000 HW2 Technical Support Checklist . . . . . . 87
Status & Primary Purpose Variables . . . . . . . . . . . . 57 Section 7 Parts . . . . . . . . . . . . . . . . . . . . . . 89
Device Information . . . . . . . . . . . . . . . . . . . . . . . . . 57 Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Service Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Parts Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Alert Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 DVC6005 Base Unit . . . . . . . . . . . . . . . . . . . . . . . . . 90
Alert Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Pressure Gauges, Pipe Plugs, or Tire
Deadband Principle of Operation . . . . . . . . . . . . . . 61 Valve Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . 92
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Remote Travel Sensor Parts . . . . . . . . . . . . . . . . . . 90
Stroke Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 HART Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Partial Stroke Test . . . . . . . . . . . . . . . . . . . . . . . 63 Appendix A Principle of Operation . . . . . . 99
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 HART Communication . . . . . . . . . . . . . . . . . . . . . . . . 99
Section 6 Maintenance and DVC6200 Digital Valve Controller . . . . . . . . . . . . . . . 99
Troubleshooting . . . . . . . . . . . . . . . . . . . . . 67 Appendix B Handheld Communicator
Module Base Maintenance . . . . . . . . . . . . . . . . . . . . . 68 Menu Tree . . . . . . . . . . . . . . . . . . . . . . . 102
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Removing the Module Base . . . . . . . . . . . . . . . . . . 68 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Replacing the Module Base . . . . . . . . . . . . . . . . . . . 70
Submodule Maintenance . . . . . . . . . . . . . . . . . . . . . . 71

2
Instruction Manual Introduction
D103785X012 February 2023

Section 1 Introduction
Installation, Pneumatic and Electrical Connections, and Initial
Configuration
Refer to the DVC6005 Series Remote Mount quick start guide (D103784X012) for DVC6000 HW2 installation,
connection and initial configuration information. If a copy of this quick start guide is needed contact your Emerson
sales office or visit our website at Fisher.com.

Scope of Manual
This instruction manual is a supplement to the DVC6005 Series Remote Mount quick start guide (D103784X012) that
ships with every instrument. This instruction manual includes product specifications, reference materials, custom
setup information, maintenance procedures, and replacement part details.

This instruction manual describes using an Emerson handheld communicator to set up and calibrate the instrument.
You can also use Fisher ValveLink™ software or ValveLink Mobile software to setup, calibrate, and diagnose the valve
and instrument. For information on using ValveLink software with the instrument refer to ValveLink software help or
documentation.

Do not install, operate, or maintain a DVC6000 HW2 digital valve controller without being fully trained
and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid
personal injury or property damage, it is important to carefully read, understand, and follow all of the
contents of this manual, including all safety cautions and warnings. If you have any questions about
these instructions, contact your Emerson sales office before proceeding.

Conventions Used in this Manual


Navigation paths and fast‐key sequences are included for procedures and parameters that can be accessed using a
handheld communicator.

For example, to access Device Setup:


Handheld Communicator Configure > Guided Setup > Device Setup (2‐1‐1)

Refer to Appendix B for the 475 Field Communicator menu trees.

Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex™ Device Communicator.

Description
DVC6000 HW2 digital valve controllers (figures 1‐1) are communicating, microprocessor‐based current‐to‐pneumatic
instruments. In addition to the normal function of converting an input current signal to a pneumatic output pressure,
the DVC6000 HW2 digital valve controller, using the HARTr communications protocol, gives easy access to
information critical to process operation. You can gain information from the principal component of the process, the
control valve itself, using a handheld communicator at the valve, or at a field junction box, or by using a personal
computer or operator's console within the control room.

3
Introduction Instruction Manual
February 2023 D103785X012

Using a personal computer and ValveLink software or Figure 1‐1. DVC6000 HW2 Digital Valve Controller
AMS Suite: Intelligent Device Manager, or a handheld Mounted on Rotary Control Valve/Actuator
communicator, you can perform several operations with
the DVC6000 HW2 digital valve controller. You can
obtain general information concerning software revision
level, messages, tag, descriptor, and date.

Diagnostic information is available to aid you when


troubleshooting. Input and output configuration
parameters can be set, and the digital valve controller can
be calibrated. Refer to table 1‐1 for details on the
capabilities of each diagnostic tier.

Using the HART protocol, information from the field can


be integrated into control systems or be received on a
single loop basis.

The DVC6000 HW2 digital valve controller is designed to


directly replace standard pneumatic and W8373
electro‐pneumatic valve mounted positioners.

Table 1‐1. Instrument Level Capabilities


DIAGNOSTIC LEVEL(2)
CAPABILITY
HC AD PD ODV
Auto Calibration X X X X
Custom Characterization X X X X
Burst Communication X X X X
Alerts X X X X
Step Response, Drive Signal Test & Dynamic Error Band X X X
Advanced Diagnostics (Valve Signature) X X X
Performance Tuner(3) X X X
Travel Control ‐ Pressure Fallback X X X
Supply Pressure Sensor X(4) X X X
Performance Diagnostics X X
Solenoid Valve Testing X X
Lead/Lag Set Point Filter(1) X
1. Refer to brochure part # D351146X012 for information on Fisher optimized digital valves for compressor antisurge applications.
2. HC = HART Communicating ; AD = Advanced Diagnostics ; PD = Performance Diagnostics ; ODV = Optimized Digital Valve.
3. Performance Tuner is only available in ValveLink software.
4. Supply Pressure Sensor available starting with Firmware 7.

Specifications
WARNING
Refer to table 1‐2 for specifications. Incorrect configuration of a positioning instrument could result in the malfunction of
the product, property damage or personal injury.

Specifications for DVC6000 HW2 digital valve controllers are shown in table 1‐2. Specifications for the Trex Device
Communicator can be found in the device communicator quick start guide.

4
Instruction Manual Introduction
D103785X012 February 2023

Table 1‐2. Specifications


Available Mounting Per ISA Standard 7.0.01: A maximum 40 micrometer
DVC6000 HW2 digital valve controllers can be particle size in the air system is acceptable. Further
mounted on Fisher and other manufacturers rotary filtration down to 5 micrometer particle size is
and sliding‐stem actuators(1) recommended. Lubricant content is not to exceed 1
ppm weight (w/w) or volume (v/v) basis.
DVC6005 HW2: Base unit for 2 inch pipestand or wall Condensation in the air supply should be minimized.
mounting
Per ISO 8573-1:
J DVC6015: Remotely mounted feedback unit for Maximum particle density size: Class 7
sliding‐stem applications Oil content: Class 3
J DVC6025: Remotely mounted feedback unit for Pressure Dew Point: Class 3 or at least 10_C less than
rotary or long‐stroke sliding‐stem applications or the lowest ambient temperature expected
J DVC6035: Remotely mounted feedback unit for
quarter‐turn rotary applications Output Signal
Mounting kit required for mounting feedback unit on Pneumatic signal as required by the actuator, up to
actuator full supply pressure.
Mounting the instrument vertically, with the vent at Minimum Span: 0.4 bar (6 psig)
the bottom of the assembly, or horizontally, with the Maximum Span: 9.5 bar (140 psig)
vent pointing down, is recommended to allow Action: J Double, J Single Direct or J Reverse
drainage of moisture that may be introduced via the
instrument air supply. Steady‐State Air Consumption(3)(4)
Standard Relay
Communication Protocol At 1.4 bar (20 psig) supply pressure:
J HART 5 or J HART 7 Less than 0.38 normal m3/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure:
Input Signal Less than 1.3 normal m3/hr (49 scfh)
Point-to-Point Low Bleed Relay
Analog Input Signal: 4-20 mA DC, nominal; split At 1.4 bar (20 psig) supply pressure:
ranging available Average value 0.056 normal m3/hr (2.1 scfh)
Minimum Voltage Available at Instrument Terminals At 5.5 bar (80 psig) supply pressure:
must be 9.5 VDC for analog control, 10 VDC for HART Average value 0.184 normal m3/hr (6.9 scfh)
communication
Minimum Control Current: 4.0 mA Maximum Output Capacity(3)(4)
Minimum Current w/o Microprocessor Restart: 3.5 mA
Maximum Voltage: 30 VDC At 1.4 bar (20 psig) supply pressure:
Overcurrent protected 10.0 normal m3/hr (375 scfh)
Reverse Polarity protected At 5.5 bar (80 psig) supply pressure:
29.5 normal m3/hr (1100 scfh)
Multi-drop
Instrument Power: 11 to 30 VDC at 10 mA Operating Ambient Temperature Limits(2)(5)
Reverse Polarity protected
-40 to 85_C (-40 to 185_F) for base unit
Supply Pressure(2) -52 to 85_C (-62 to 185_F) for base unit utilizing the
Extreme Temperature option (fluorosilicone
Minimum Recommended: 0.3 bar (5 psig) higher elastomers)
than maximum actuator requirements -52 to 125_C (-62 to 257_F) for remote‐mount
Maximum: 10.0 bar (145 psig) or maximum pressure feedback unit
rating of the actuator, whichever is lower
Medium: Air or Natural Gas Independent Linearity(6)
Supply medium must be clean, dry and non-corrosive Typical Value: ±0.50% of output span
-continued-

5
Introduction Instruction Manual
February 2023 D103785X012

Table 1‐2. Specifications (continued)


Electromagnetic Compatibility Other Classifications/Certifications
Meets EN 61326-1:2013 Lloyds Register— Marine Type Approval
Immunity—Industrial locations per Table 2 of CCC— China Compulsory Certification
the EN 61326-1 standard. Performance is CUTR— Customs Union Technical Regulations
shown in table 1‐3 below. (Russia, Kazakhstan and Belarus)
Emissions—Class A
ISM equipment rating: Group 1, Class A ESMA— Emirates Authority for Standardization and
Metrology - ECAS-Ex (UAE)
Lightning and Surge Protection—The degree of
INMETRO— National Institute of Metrology, Quality,
immunity to lightning is specified as Surge immunity
and Technology (Brazil)
in table 1‐3. For additional surge protection
commercially available transient protection devices KTL— Korea Testing Laboratory (South Korea)
can be used. PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
Vibration Testing Method SANS— South Africa National Standards
Tested per ANSI/ISA-S75.13.01 Section 5.3.5. A Contact your Emerson sales office for
resonant frequency search is performed on all three classification/certification specific information.
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance. Connections
Supply Pressure: 1/4 NPT internal and integral pad for
Input Impedance mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
An equivalent impedance of 500 ohms may be used. Tubing: 3/8‐inch recommended
This value corresponds to 10V @ 20 mA. Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal or M20
Humidity Testing Method
Actuator Compatibility
Tested per IEC 61514‐2
Sliding‐Stem Linear
Linear Actuators with rated travel between 6.35 mm
Electrical Classification (0.25 inch) and 606 mm (23.375 inches)
Hazardous Area Approvals Quarter‐Turn Rotary
Rotary Actuators with rated travel between
CSA— Intrinsically Safe, Explosion‐proof,
45 degrees and 180 degrees(7)
Division 2, Dust Ignition-proof
Mounting
FM— Intrinsically Safe, Explosion‐proof,
Dust Ignition-proof, Non-Incendive
Weight
ATEX— Intrinsically Safe, Flameproof, Type n DVC6005 HW2 Base Unit: 4.1 kg (9 lbs)
Dust by intrinsic safety
DVC6015 Remote Feedback Unit: 1.3 kg (2.9 lbs)
IECEx— Intrinsically Safe, Flameproof, Type n DVC6025 Remote Feedback Unit: 1.4 kg (3.1 lbs)
Dust by intrinsic safety and enclosure DVC6035 Remote Feedback Unit: 0.9 kg (2.0 lbs)
Electrical Housing
Construction Materials
CSA— Type 4X, IP66
Housing, module base and terminal box:
FM— Type 4X, IP66 A03600 low copper aluminum alloy
ATEX— IP66 Cover: Thermoplastic polyester
Elastomers: Nitrile (standard)
IECEx— IP66 Fluorosilicone (extreme temperature)
-continued-

6
Instruction Manual Introduction
D103785X012 February 2023

Table 1‐2. Specifications (continued)


Options On State: up to 1 A
J Supply and output pressure gauges or Supply Voltage: 30 VDC maximum
J Tire valves J Integral mounted filter regulator Reference Accuracy: 2% of travel span
J Low‐Bleed Relay(8) J Extreme Temperature Contact your Emerson sales office or go to Fisher.com
J Integral 4‐20 mA Position Transmitter(9): for additional information
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC Declaration of SEP
Reference Accuracy: 1% of travel span Fisher Controls International LLC declares this
The position transmitter meets the requirements of product to be in compliance with Article 4 paragraph
NAMUR NE43; selectable to show failure high 3 of the PED Directive 2014/68/EU. It was designed
( > 22.5 mA) or failure low (< 3.6 mA). Fail high only and manufactured in accordance with Sound
when the positioner is powered. Engineering Practice (SEP) and cannot bear the CE
J Integral Switch(9): marking related to PED compliance.
One isolated switch, configurable throughout the However, the product may bear the CE marking to
calibrated travel range or actuated from a device alert indicate compliance with other applicable European
Off State: 0 mA (nominal) Community Directives.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit. Pneumatic tubing between base
unit output connection and actuator has been tested to 91 meters (300 feet) with minimal pneumatic lag. At 30 meters (100 feet) there was no performance degradation.
2. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
3. Normal m3/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
4. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
5. Temperature limits vary based on hazardous area approval.
6. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long‐stroke applications.
7. Rotary actuators with 180 degree rated travel require a special mounting kit; contact your Emerson sales office for kit availability.
8. The Quad O steady-state consumption requirement of 6 scfh can be met by a DVC6000 HW2 with low bleed relay A option, when used with up to 4.8 bar (70 psi) supply of Natural Gas at 16_C (60_F).
The 6 scfh requirement can be met by low bleed relay B and C when used with up to 5.2 bar (75 psi) supply of Natural Gas at 16_C (60_F).
9. The electronic output is available with either the position transmitter or the switch.

Table 1‐3. EMC Summary Results—Immunity


Performance Criteria(1)
Port Phenomenon Basic Standard Test Level Point-to- Multi-drop
Point Mode Mode
4 kV contact
Electrostatic discharge (ESD) IEC 61000‐4‐2 A(2) A
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
Enclosure Radiated EM field IEC 61000‐4‐3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A A
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Rated power frequency
IEC 61000‐4‐8 30 A/m at 50/60Hz A(2) A
magnetic field
Burst IEC 61000‐4‐4 1 kV A A
I/O signal/control Surge IEC 61000‐4‐5 1 kV B B
Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms A A
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
2. Excluding auxiliary switch function, which meets Performance Criteria B.

7
Introduction Instruction Manual
February 2023 D103785X012

Related Documents
This section lists other documents containing information related to the DVC6000 HW2 digital valve controller. These
documents include:

D Bulletin 62.1:DVC6000 HW2—Fisher FIELDVUE DVC6000 HW2 Digital Valve Controller (D103786X012)

D Bulletin 62.1:DVC6005—Fisher FIELDVUE DVC6005 Series Digital Valve Controller and DVC6015, DVC6025, and
DVC6035 Feedback Unit Dimension (D103308X012)

D DVC6005 Series Remote Mount Digital Valve Controller Quick Start Guide (D103784X012)

D CSA Hazardous Area Approvals—DVC6005 Series Remote Mount Digital Valve Controllers (D104209X012)

D FM Hazardous Area Approvals—DVC6005 Series Remote Mount Digital Valve Controllers (D104210X012)

D ATEX Hazardous Area Approvals—DVC6005 Series Remote Mount Digital Valve Controllers (D104211X012)

D IECEx Hazardous Area Approvals—DVC6005 Series Remote Mount Digital Valve Controllers (D104212X012)

D FIELDVUE Digital Valve Controller Split Ranging (D103262X012)

D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) (D103263X012)

D Using FIELDVUE Instruments with the Smart Wireless THUM Adapter and a HART Interface Module (HIM)
(D103469X012)

D Audio Monitor for HART Communications (D103265X012)

D HART Field Device Specification - Fisher FIELDVUE DVC6000 HW2 Digital Valve Controller (D103782X012)

D Using the HART Tri‐Loop HART‐to‐Analog Signal Converter with FIELDVUE Digital Valve Controllers (D103267X012)

D Implementation of Lock‐in‐Last Strategy (D103261X012)

D Fisher HF340 Filter Instruction Manual (D102796X012)

D AMS Trex Device Communicator User Guide

D ValveLink Software Help or Documentation

All documents are available from your Emerson sales office or at Fisher.com.

Educational Services
Emerson Automation Solutions
Educational Services - Registration
Phone: +1-800‐338‐8158
Email: [email protected]
emerson.com/mytraining

8
Instruction Manual Wiring Practices
D103785X012 February 2023

Section 2 Wiring Practices22


Control System Requirements
There are several parameters that should be checked to ensure the control system is compatible with the
DVC6000 HW2 digital valve controller.

HART Filter
Depending on the control system you are using, a HART filter may be needed to allow HART communication. The
HART filter is a passive device that is inserted in field wiring from the HART loop. The filter is normally installed near the
field wiring terminals of the control system I/O (see figure 2‐1). Its purpose is to effectively isolate the control system
output from modulated HART communication signals and raise the impedance of the control system to allow HART
communication. For more information on the description and use of the HART filter, refer to the appropriate HART
filter instruction manual.

To determine if your system requires a filter contact your Emerson sales office.

Note
A HART filter is typically NOT required for any of the Emerson control systems, including PROVOX™, RS3™, and DeltaV™ systems.

Figure 2‐1. HART Filter Application

NON‐HART BASED DCS

I/O I/O

HART
FILTER

4‐20 mA + HART
DIGITAL VALVE
CONTROLLER

Tx Tx VALVE

A6188‐1

Voltage Available
The voltage available at the DVC6000 HW2 digital valve controller must be at least 10 VDC. The voltage available at
the instrument is not the actual voltage measured at the instrument when the instrument is connected. The voltage
measured at the instrument is limited by the instrument and is typically less than the voltage available.

9
Wiring Practices Instruction Manual
February 2023 D103785X012

As shown in figure 2‐2, the voltage available at the instrument depends upon:
D the control system compliance voltage
D if a filter, wireless THUM adapter, or intrinsic safety barrier is used, and
D the wire type and length.
The control system compliance voltage is the maximum voltage at the control system output terminals at which the
control system can produce maximum loop current.
The voltage available at the instrument may be calculated from the following equation:

Voltage Available = [Control System Compliance Voltage (at maximum current)] - [filter voltage drop (if a HART filter is
used)] - [total cable resistance  maximum current] - [barrier resistance x maximum current].

The calculated voltage available should be greater than or equal to 10 volts DC.
Table 2‐1 lists the resistance of some typical cables.
The following example shows how to calculate the voltage available for a Honeywell™ TDC2000 control system with a
HF340 HART filter, and 1000 feet of Belden™ 9501 cable:
Voltage available = [18.5 volts (at 21.05 mA)] - [2.3 volts] - [48 ohms  0.02105 amps]
Voltage available = [18.5] - [2.3] - [1.01]
Voltage available = 15.19 volts

Figure 2‐2. Determining Voltage Available at the Instrument


TOTAL LOOP THUM ADAPTER
CABLE RESISTANCE (IF USED)
COMPLIANCE VOLTAGE

CONTROL
SYSTEM
VOLTAGE
+ INTRINSIC SAFETY R + AVAILABLE AT THE
HART FILTER
- BARRIER
(if used)
(if used) - INSTRUMENT

Calculate Voltage Available at the Instrument as follows: Example Calculation

Control system compliance voltage 18.5 volts (at 21.05 mA)

– Filter voltage drop (if used) 1 – 2.3 volts (for HF300 filter)

– Intrinsic safety barrier resistance (if used) x maximum loop current – 2.55 volts (121 ohms x 0.02105 amps)
– Smart Wireless THUM adapter voltage drop (if used) 2
– Total loop cable resistance x maximum loop current – 1.01 volts (48 ohms x 0.02105 amps for
1000 feet of Belden 9501 cable)

= Voltage available at the instrument 3 = 15.19 volts, available—if safety barrier (2.55 volts)
is not used
NOTES:
1Obtain filter voltage drop. The measured drop will be different than this value. The measured filter voltage drop
depends upon control system output voltage, the intrinsic safety barrier (if used), and the instrument. See note 3.
2The voltage drop of the THUM adapter is linear from 2.25 volts at 3.5 mA to 1.2 volts at 25 mA.

3The voltage available at the instrument is not the voltage measured at the instrument terminals. Once the
instrument is connected, the instrument limits the measured voltage to approximately 8.0 to 9.5 volts.

10
Instruction Manual Wiring Practices
D103785X012 February 2023

Table 2‐1. Cable Characteristics


Capacitance(1) Capacitance(1) Resistance(2) Resistance(2)
Cable Type
pF/Ft pF/m Ohms/ft Ohms/m
BS5308/1, 0.5 sq mm 61.0 200 0.022 0.074
BS5308/1, 1.0 sq mm 61.0 200 0.012 0.037
BS5308/1, 1.5 sq mm 61.0 200 0.008 0.025
BS5308/2, 0.5 sq mm 121.9 400 0.022 0.074
BS5308/2, 0.75 sq mm 121.9 400 0.016 0.053
BS5308/2, 1.5 sq mm 121.9 400 0.008 0.025
BELDEN 8303, 22 awg 63.0 206.7 0.030 0.098
BELDEN 8441, 22 awg 83.2 273 0.030 0.098
BELDEN 8767, 22 awg 76.8 252 0.030 0.098
BELDEN 8777, 22 awg 54.9 180 0.030 0.098
BELDEN 9501, 24 awg 50.0 164 0.048 0.157
BELDEN 9680, 24 awg 27.5 90.2 0.048 0.157
BELDEN 9729, 24 awg 22.1 72.5 0.048 0.157
BELDEN 9773, 18 awg 54.9 180 0.012 0.042
BELDEN 9829, 24 awg 27.1 88.9 0.048 0.157
BELDEN 9873, 20 awg 54.9 180 0.020 0.069
1. The capacitance values represent capacitance from one conductor to all other conductors and shield. This is the appropriate value to use in the cable length calculations.
2. The resistance values include both wires of the twisted pair.

Compliance Voltage
If the compliance voltage of the control system is not known, perform the following compliance voltage test.
1. Disconnect the field wiring from the control system and connect equipment as shown in figure 2‐3 to the control
system terminals.

Figure 2‐3. Voltage Test Schematic


1 kW POTENTIOMETER
MILLIAMMETER

VOLTMETER

CIRCUIT
UNDER
TEST

A6192‐1

2. Set the control system to provide maximum output current.


3. Increase the resistance of the 1 kW potentiometer, shown in figure 2‐3, until the current observed on the
milliammeter begins to drop quickly.
4. Record the voltage shown on the voltmeter. This is the control system compliance voltage.
For specific parameter information relating to your control system, contact your Emerson sales office.

11
Wiring Practices Instruction Manual
February 2023 D103785X012

Auxiliary Terminal Wiring Length Guidelines


The Auxiliary Input Terminals of a DVC6000 HW2 with instrument level ODV can be used with a locally‐mounted
switch for initiating a partial stroke test. Some applications require that the switch be installed remotely from the
DVC6000 HW2.

The length for wiring connected to the Auxiliary Input Terminals is limited by capacitance. For proper operation of the
Auxiliary Input Terminals capacitance should not exceed 100,000 pF. As with all control signal wiring, good wiring
practices should be observed to minimize adverse effect of electrical noise on the Aux Switch function.

Example Calculation: Capacitance per foot or per meter is required to calculate the length of wire that may be
connected to the Aux switch input. The wire should not exceed the capacitance limit of 100,000 pF. Typically the wire
manufacturer supplies a data sheet which provides all of the electrical properties of the wire. The pertinent parameter
is the highest possible capacitance. If shielded wire is used, the appropriate number is the “Conductor to Other
Conductor & Shield” value.

Example — 18AWG Unshielded Audio, Control and Instrumentation Cable

Manufacturer's specifications include:

Nom. Capacitance Conductor to Conductor @ 1 KHz: 26 pF/ft


Nom. Conductor DC Resistance @ 20 Deg. C: 5.96 Ohms/1000 ft
Max. Operating Voltage - UL 200 V RMS (PLTC, CMG),150 V RMS (ITC)
Allowable Length with this cable = 100,000pF /(26pF/ft) = 3846 ft

Example — 18AWG Shielded Audio, Control and Instrumentation Cable

Manufacturer's specifications include:

Nom. Characteristic Impedance: 29 Ohms


Nom. Inductance: .15 μH/ft
Nom. Capacitance Conductor to Conductor @ 1 KHz: 51 pF/ft
Nom. Cap. Cond. to other Cond. & Shield @ 1 Khz: 97 pF/ft
Allowable Length with this cable = 100,000pF /(97pF/ft) = 1030 ft

The AUX switch input passes less than 1 mA through the switch contacts, and uses less than 5 V, therefore, neither the
resistance nor the voltage rating of the cable are critical. Ensure that switch contact corrosion is prevented. It is
generally advisable that the switch have gold‐plated or sealed contacts.

Maximum Cable Capacitance


The maximum cable length for HART communication is limited by the characteristic capacitance of the cable.
Maximum length due to capacitance can be calculated using the following formulas:

Length(ft) = [160,000 - Cmaster(pF)] [Ccable(pF/ft)]


Length(m) = [160,000 - Cmaster(pF)] [Ccable(pF/m)]

where:

160,000 = a constant derived for FIELDVUE instruments to ensure that the HART network RC time constant will be no
greater than 65 μs (per the HART specification).

Cmaster = the capacitance of the control system or HART filter


Ccable = the capacitance of the cable used (see table 2‐1)

12
Instruction Manual Wiring Practices
D103785X012 February 2023

The following example shows how to calculate the cable length for a Foxboro™ I/A control system (1988) with a Cmaster
of 50, 000 pF and a Belden 9501 cable with characteristic capacitance of 50pF/ft.

Length(ft) = [160,000 - 50,000pF] [50pF/ft]

Length = 2200 ft.

The HART communication cable length is limited by the cable characteristic capacitance. To increase cable length,
select a wire with lower capacitance per foot. Contact your Emerson sales office for specific information relating to
your control system.

Remote Travel Sensor Connections


The DVC6005 HW2 base unit is designed to receive travel information via a remote sensor. The remote can be any of
the following:

D Emerson supplied DVC6015, DVC6025 or DVC6035 remote feedback unit; refer to the DVC6005 Series Remote
Mount Digital Valve Controller quick start guide (D103784X012) that ships with the product,

D An under‐traveled 10 kOhm potentiometer used in conjunction with onboard 30 kOhm resistor, or

D A potentiometer used in conjunction with two fixed resistors (potentiometer travel is the same as actuator travel).

WARNING
Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit
with the remote feedback unit shares a conduit with any other power or signal wiring.
Do not place feedback wiring in the same conduit as other power or signal wiring.

Note
3‐conductor shielded cable, 22 AWG minimum wire size, is required for connection between base unit and feedback unit.
Pneumatic tubing between base unit output connection and actuator has been tested to 91 meters (300 feet) with minimal
pneumatic lag. At 30 meters (100 feet) there was no performance degradation.

Using an External 10 kOhm External Potentiometer as a Remote Travel Sensor

Note
Potentiometer travel must be between 1.3 and 1.6 times greater than the actuator travel. For example: if an actuator has a travel
of 9 inches, then a linear potentiometer must be selected with a rated travel between 11.7 and 14.4 inches. The resistive element
must be tapered from 0 kOhm to 10 kOhm over rated travel of the potentiometer. The actuator will only use 63 to 76 % of the
potentiometer rated travel.

13
Wiring Practices Instruction Manual
February 2023 D103785X012

Note
The digital valve controller must be configured using the SStem/Roller selection on the menu of the appropriate setup device.

The DVC6005 HW2 base unit was designed to work with a 40 kOhm potentiometer for travel feedback. However,
there are linear potentiometers that are readily available with a rated resistance of 10 kOhm. Therefore, the feedback
connections terminal box of the DVC6005 HW2 contains an additional 30 kOhm fixed resistor that may be added to
the circuit. This brings the total resistance up to the required 40 kOhm.
1. Mount the external 10 kOhm potentiometer to the actuator such that the mid‐travel position of the potentiometer
(5 kOhm) corresponds to the mid‐travel position of the actuator. This will leave an equal amount of unused resistive
element on both ends of the travel, which is required by the digital valve controller to function properly.
2. On the base unit, remove the feedback connections terminal box cap.
3. If necessary, install conduit between the potentiometer and the base unit following applicable local and national
electrical codes. Route the 3‐conductor shielded cable between the two units (refer to figure 2‐4).

Figure 2‐4. Terminal Details for Connecting a FIELDVUE DVC6005 HW2 Base Unit and a 10k Ohm External
Potentiometer

2
INTERNAL
1 "
10k W
(30k W)

30k

BASE UNIT TERMINATION BOX 3RD PARTY FEEDBACK ELEMENT


(DVC6005 HW2) (WITH 10k W POTENTIOMETER)

4. Connect one wire of the 3‐conductor shielded cable between the terminal labeled “30kW” on the base unit and one
end lead of the potentiometer.
5. Connect the second wire of the 3‐conductor shielded cable between the middle lead (wiper) of the 10 kOhm
potentiometer to Terminal 2 on the base unit.
6. Connect the third wire of the 3‐conductor shielded cable between Terminal 3 on the base unit and the other
end‐lead of the 10 kOhm potentiometer.
7. Connect the cable shield or drain wire to the ground screw in the feedback connections terminal box of the base
unit. Do not connect the shield or drain wire to the external potentiometer.
8. Replace and tighten the base unit cover.

14
Instruction Manual Wiring Practices
D103785X012 February 2023

Using a Potentiometer with Two Fixed Resistors as a Remote Travel Sensor


Perform the following procedure if a potentiometer is used with the same, or slightly longer travel than the actuator's
travel.

Note
The potentiometer must be capable of resistance close to 0 Ohms.

NOTICE

To prevent damage to the potentiometer, ensure that it is free to travel the entire length of the actuator's travel.

Note
The digital valve controller must be configured using the SStem/Roller selection on the menu of the appropriate setup device.

This procedure uses three resistors connected in series, two fixed resistors and one potentiometer. Three conditions
must be met for the resistor combination to correctly operate the digital valve controller:
D The maximum resistance of the potentiometer [Rpot(max)] must be between 3.9 kOhm and 10 kOhm.
D The resistance of R1 is 4.25 times greater than Rpot(max).
D The resistance of R2 is 4 times less than Rpot(max).

WARNING
To avoid personal injury or property damage from an uncontrolled process ensure that the R1 resistor is properly insulated
before installing it in the terminal box.

1. On the base unit, remove the feedback connections terminal box cap.
2. If necessary, install conduit between the two‐resistor series and the base unit following applicable local and national
electrical codes. Route the 3‐conductor shielded cable between the two units (refer to figure 2‐5).

15
Wiring Practices Instruction Manual
February 2023 D103785X012

Figure 2‐5. Terminal Details for Connecting a FIELDVUE DVC6005 HW2 Base Unit and a Three‐Resistor Series

2 (R2)

30kW "
(R1) (Rpot)

BASE UNIT TERMINATION BOX THREE‐RESISTOR SERIES


(DVC6005 HW2)

3. Install the fixed resistor (R1) across the unlabeled bottom Terminal and Terminal #1. The bottom terminal does not
have a screw. The screw on the 30 kOhm terminal can be used. R1 must be properly insulated when installed in the
terminal box to prevent personal injury or property damage.
4. Connect one wire of the 3‐conductor shielded cable between the unlabeled bottom Terminal on the base unit and
an end‐lead of the external potentiometer (Rpot).
5. Connect the second wire of the 3‐conductor shielded cable between the middle lead (wiper) of the external
potentiometer (Rpot) and Terminal 2 on the base unit.
6. Connect the third wire of the 3‐conductor shielded cable between between a lead on fixed resistor (R2) and
terminal #3 of the base unit.
7. Connect the available end‐lead on the potentiometer (Rpot) with the available lead on fixed resistor (R2).
8. Connect the cable shield or drain wire to the ground screw in the feedback connections terminal box of the base
unit. Do not connect the shield or drain wire to the two‐resistor series.
9. Replace and tighten the base unit cover.
Example: Using a linear potentiometer rated at 400 Ohms/inch on an actuator with 16” of travel.
D Rpot(max) is 400 Ohms/in x 16” = 6.4 kOhm
D R1 = 6.4 kOhm x 4.25 = 27.2 kOhm
D R2 = 6.4 kOhm / 4 = 1.6 kOhm

16
Instruction Manual Wiring Practices
D103785X012 February 2023

Installation in Conjunction with a Rosemount 333 HART Tri‐Loop


HART‐to‐Analog Signal Converter
Use the DVC6000 HW2 digital valve controller in operation with a Rosemount 333 HART Tri‐Loop HART‐to‐Analog
Signal Converter to acquire an independent 4‐20 mA analog output signal for the analog input, travel target, pressure,
or travel. The HART Tri‐Loop accepts any three of these digital signals and converts them into three separate 4‐20 mA
analog channels.

Refer to figure 2‐6 for basic installation information. Refer to the Refer to the 333 HART Tri‐Loop HART‐to‐Analog
Signal Converter Product Manual (00809-0100-4754) for complete installation information.

Figure 2‐6. HART Tri‐Loop Installation Flowchart

START HERE

Unpack the
HART Tri‐Loop Install the HART Tri‐
Loop; See HART Tri‐
Loop product manual Configure the HART
Review the HART Tri‐Loop to receive
Tri‐Loop Product digital valve controller
Manual Mount the HART burst commands
Tri‐Loop to the
DIN rail
Check
Digital valve No Wire the digital Pass system No troubleshooting
Install the digital
controller valve controller to test? procedures in
valve controller.
Installed? the HART Tri‐Loop HART Tri‐Loop
product manual
Yes Yes
Install Channel 1
Set the digital wires from HART
valve controller Tri‐Loop to the
Burst Option control room DONE

(Optional) Install
Set the digital Channel 2 and 3 wires
valve controller from HART Tri‐Loop to
Burst Mode the control room

E0365

17
Wiring Practices Instruction Manual
February 2023 D103785X012

Commissioning the Digital Valve Controller for use with the HART
Tri‐Loop Signal Converter
To prepare the digital valve controller for use with a 333 HART Tri‐Loop, you must configure the digital valve controller
to burst mode, and select Burst Command 3. In burst mode, the digital valve controller provides digital information to
the HART Tri‐Loop HART‐to‐Analog Signal Converter. The HART Tri‐Loop converts the digital information to a 4 to 20
mA analog signal. Each burst message contains the latest value of the primary (analog input), secondary (travel
target), tertiary (configured output pressure), and quaternary (travel) variables.
To commission a DVC6000 HW2 for use with a HART Tri‐Loop, perform the following procedures.

Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.

Enable Burst Operation


With I/O Package
Configure > Manual Setup > Outputs > Burst Mode (2‐2‐6‐6) HC, AD, PD or (2-2-7-6) ODV
Handheld Communicator
Without I/O Package
Configure > Manual Setup > Outputs > Burst Mode (2‐2‐6‐2) HC, AD, PD or (2-2-7-2) ODV

Select Burst Enable and follow the prompts to enable burst mode. Then select Burst Command and follow the prompts
to configure Loop Current/PV/SV/TV/QV.

Select the HART Variable Assignments


With I/O Package
Configure > Manual Setup > Outputs > HART Variable Assignments (2-2-6-4) HC, AD, PD or (2-2-7-4) ODV
Handheld Communicator
Without I/O Package
Configure > Manual Setup > Outputs > HART Variable Assignments (2-2-6-1) HC, AD, PD or (2-2-7-1) ODV

Configure the HART Variable Assignments. The Primary Variable (PV) is always Analog Input. The Secondary Variable
(SV), Tertiary Variable (TV) and Quaternary Variable (QV) can be configured to any of the following variables. The
variable assignments in the DVC6000 HW2 must correspond to the variable assignments in the Tri-Loop.
D Setpoint
D Travel (see note below)
D Pressure A
D Pressure B
D Pressure A­B
D Supply Pressure
D Drive Signal
D Analog Input

Note
If the instrument is configured to operate in pressure control mode, or detects an invalid travel sensor reading, the Travel variable
will report pressure in percent of bench set range.

18
Instruction Manual Configuration
D103785X012 February 2023

Section 3 Configuration
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.

Guided Setup
Handheld Communicator Configure > Guided Setup (2‐1)

The following procedures will guide you through the instrument setup process.
Device Setup is used to configure actuator and valve information, calibrate the valve assembly, and assign the tuning
set for the valve assembly.
Auto Calibration is used to establish the limits of physical travel. During this process, the valve will fully stroke from
one travel extreme to the other. There are three calibration options to choose from:
d Autocalibrate – Standard runs the full calibration process (recommended).
d Autocalibrate – Without Biases establishes the travel end points, but does not adjust the Minor Loop Feedback
bias. This is for advanced use when manually setting the biases for large actuators.
d Advanced Settings allows additional custom configuration of calibration parameters. This is for advanced use
when calibrating large actuators.

Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter Default Setting(1)
Control Mode Analog
Restart Control Mode Resume Last
Analog In Range Low 4 mA
Analog In Range High 20 mA
Instrument Analog Input Units mA
Configuration Local AutoCal Button Enabled
Polling Address 0
Burst Mode Enable No
Burst Command 3
Cmd 3 (Trending) Pressure A-B
Input Characterization Linear
Travel Limit High 125%
Travel Limit Low -25%
Travel/Pressure Cutoff High 99.46%
Travel/Pressure Cutoff Low 0.50%
Dynamic Response and
Set Point Rate Open 0%/sec
Tuning
Set Point Rate Close 0%/sec
Set Point Filter Time (Lag Time) 0 sec
Integrator Enable Yes
Integral Gain 9.4 repeats/minute
Integral Deadzone 0.26%
-continued on next page-

19
Configuration Instruction Manual
February 2023 D103785X012

Table 3‐1. Default Detailed Setup Parameters (continued)


Setup Parameter Default Setting(1)
Travel Deviation Alert Enable Yes
Travel Deviation Alert Point 5%
Travel Deviation Time 9.99 sec
Pressure Deviation Alert Enable Yes
Deviation & Other Alerts
Pressure Deviation Alert Point 5 psi(2)
Pressure Deviation Alert Time 5.0 sec
Drive Signal Alert Enable Yes
Supply Pressure Alert Enable Yes
1. The settings listed are for standard factory configuration. DVC6000 HW2 instruments can also be ordered with custom configuration
settings. Refer to the order requisition for custom settings (if specified) .
2. Adjust to bar, kPa, or Kg/cm2 if necessary

Mode and Protection


Handheld Communicator Configure > Manual Setup > Mode and Protection (2‐2‐1)

Instrument Mode
There are two instrument modes for the DVC6000 HW2; In Service or Out of Service. In Service is the normal operating
mode such that the instrument follows the 4­20 mA control signal. Out of Service is required in some cases to modify
configuration parameters or to run diagnostics.

Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In
Service or the instrument is restarted.

Write Protection
There are two Write Protection modes for the DVC6000 HW2: Not Protected or Protected. Protected prevents
configuration and calibration changes to the instrument. The default setting is Not Protected. Write Protection can be
changed to Protected remotely. However, to change Write Protection to Not Protected, you must have physical access
to the instrument. The procedure will require you to press a button ( ) on the terminal box as a security measure.

Instrument
Handheld Communicator Configure > Manual Setup > Instrument (2‐2‐2)

Follow the prompts on the handheld communicator display to configure the following Instrument parameters:

Identification
D HART Tag—A tag name up to 8 characters is available for the instrument. The HART tag is the easiest way to
distinguish between instruments in a multi‐instrument environment. Use the HART tag to label instruments
electronically according to the requirements of your application. The tag you assign is automatically displayed
when the handheld communicator establishes contact with the digital valve controller at power‐up.

D HART Long Tag (HART Universal Revision 7 only)—A tag name up to 32 characters is available for the instrument.

20
Instruction Manual Configuration
D103785X012 February 2023

D Description—Enter a description for the application with up to 16 characters. The description provides a longer
user‐defined electronic label to assist with more specific instrument identification than is available with the HART
tag.

D Message—Enter any message with up to 32 characters. Message provides the most specific user‐defined means for
identifying individual instruments in multi‐instrument environments.

D Polling Address—If the digital valve controller is used in point‐to‐point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique
polling address. The Polling Address is set to a value between 0 and 63 for HART 7 and 0 and 15 for HART 5. To
change the polling address the instrument must be Out Of Service.

For a handheld communicator to be able to communicate with a device whose polling address is not 0, it must be
configured to automatically search for all or specific connected devices.

Serial Numbers
D Instrument Serial Number—Enter the serial number on the instrument nameplate, up to 12 characters.

D Valve Serial Number—Enter the serial number for the valve in the application, up to 12 characters.

Units
D Pressure Units—Defines the output and supply pressure units in either psi, bar, kPa, or kg/cm2.

D Temperature Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the
digital valve controller's printed wiring board.

D Analog Input Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.

Terminal Box
D Calibration (CAL) Button—This button is near the wiring terminals in the terminal box and provides a quick means to
autocalibrate the instrument. The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve
through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write
Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration
button is disabled by default.

D Auxiliary Terminal Action—These wire terminals can be configured to initiate a partial stroke test upon detection of
a short across the (+) and (-) terminals. The terminals must be shorted for 3 to 10 seconds.

Note
Auxiliary Terminal Action is only available for instrument level ODV.

Analog Input Range


D Input Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range
High, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input
Range High corresponds to Travel Range Low. See figure 3‐1.

21
Configuration Instruction Manual
February 2023 D103785X012

D Input Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input
Range Low corresponds to Travel Range High. See figure 3‐1.

Figure 3‐1. Calibrated Travel to Analog Input Relationship

TRAVEL
RANGE
HIGH ZPC = OPEN

ZPC = CLOSED
CALIBRATED TRAVEL, %

THE SHAPE OF THESE LINES


DEPENDS ON THE INPUT
CHARACTERISTICS LINEAR
TRAVEL CHARACTERISTIC SHOWN
RANGE
LOW

ANALOG INPUT
INPUT RANGE mA OR % OF 4‐20 mA INPUT RANGE
LOW HIGH
NOTE:
ZPC = ZERO POWER CONDITION
A6531‐1

Spec Sheet
The Spec Sheet provides a means to store the entire control valve specifications on board the DVC6000 HW2.

Edit Instrument Time


Permits setting the instrument clock. When alerts are stored in the alert record, the record includes the time and date.
The instrument clock uses a 24‐hour format.

22
Instruction Manual Configuration
D103785X012 February 2023

Travel/Pressure Control
Handheld Communicator Configure > Manual Setup > Travel/Pressure Control (2‐2-3)

Travel/Pressure Select
This defines the operating mode of the instrument as well as the behavior of the instrument should the travel sensor
fail. There are four choices:
D Travel Control—The instrument is controlling to a target travel. Fallback is not enabled.
D Pressure Control—The instrument is controlling to a target pressure. Fallback is not enabled.
D Fallback-Sensor Failure—The instrument will fallback to pressure control if a travel sensor failure is detected.
D Fallback-Sensor/Tvl Deviation—The instrument will fallback to pressure control if a travel sensor failure is detected,
or if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time.

Note
Travel / Pressure Select must be set to Travel for double‐acting actuators

Cutoffs and Limits


D Hi Limit/Cutoff Select—When the Hi Cutoff/Limit Select is configured for Cutoff, the Travel Target is set to 123%
when the Travel exceeds the Hi Cutoff Point. When the Hi Cutoff/Limit Select is configured for Limit, the Travel
Target will not exceed the Hi Limit Point.

D Hi Limit/Cutoff Point—This is the point within the calibrated travel range above which the Limit or Cutoff is in effect.
When using cutoffs, a Cutoff Hi of 99.5% is recommended to ensure valve goes fully open. The Hi Cutoff/Limit is
deactivated by setting it to 125%.

D Hi Soft Cutoff Rate—This setting allows the valve to ramp to the high travel extreme when the Cutoff Point is
reached at the configured rate. This provides a controlled ramp into the open travel stop. When set to 0%/sec, the
Hi Soft Cutoff rate is disabled.

D Lo Limit/Cutoff Select—When the Lo Cutoff/Limit Select is configured for Cutoff, the Travel Target is set to ­23%
when the Travel is below the Lo Cutoff Point. When the Hi Cutoff/Limit Select is configured for Limit, the Travel
Target will not fall below the Lo Limit Point.

D Lo Limit/Cutoff Point—This is the point within the calibrated travel range below which the Limit or Cutoff is in effect.
When using cutoffs, a Cutoff Lo of 0.5% is recommended to help ensure maximum shutoff seat loading. The Lo
Limit/Cutoff is deactivated by setting it to ­25%.

D Lo Soft Cutoff Rate—This setting allows the valve to ramp to the low travel extreme when the Cutoff Point is reached
at the configured rate. This provides a controlled ramp into the seat in order to minimize seat damage. When set to
0%/sec, the Lo Soft Cutoff rate is disabled.

23
Configuration Instruction Manual
February 2023 D103785X012

Pressure Control
D Pressure Range High—The high end of output pressure range. Enter the pressure that corresponds with 100% valve
travel when Zero Power Condition is closed, or 0% valve travel when Zero Power Condition is open. This pressure
must be greater than the Pressure Range Lo.

D Pressure Range Lo—The low end of the output pressure range. Enter the pressure that corresponds to 0% valve
travel when Zero Power Condition is closed, or 100% valve travel when Zero Power Condition is open. This pressure
must be less than the Pressure Range Hi.

Pressure Fallback

Note
Pressure Fallback is available for instrument level AD, PD, ODV.

D Tvl Dev Press Fallback—When the difference between the travel target and the actual travel exceeds this value for
more than the Tvl Dev Press Fallback Time, the instrument will disregard the travel feedback and control based on
output pressure.

D Tvl Dev Press Fallback Time—The time, in seconds, that the travel target and the actual travel must be exceeded
before the instrument falls back into pressure control.

D Fallback Recovery—If the instrument has fallen into pressure control and the feedback problem is resolved, recovery
to travel control can occur automatically or with manual intervention. To return to travel control when Manual
Recovery is selected, change the Fallback Recovery to Auto Recovery, and then back to Manual Recovery (if
desired).

Control Mode
D Control Mode—Displays the current control mode of the instrument. This will show Analog if the instrument is in
Point­to­Point mode and is using a 4­20 mA signal for its power and set point. This will show Digital if the
instrument is in Multidrop mode and is using 24 VDC for power and a digital set point for control.

Note
Another mode, Test, may be displayed. Normally the instrument should not be in the Test mode. The digital valve controller
automatically switches to this mode whenever it needs to stroke the valve during calibration or stroke valve, for example.
However, if you abort from a procedure where the instrument is in the test mode, it may remain in this mode. To take the
instrument out of the Test mode, select Change Control Mode and enter Analog or Digital.

D Change Control Mode—Allows you to configure the control mode to Analog or Digital.

D Restart Control Mode—Defines the Control Mode of the instrument after a restart (e.g. power cycle). Available
choices are Resume Last, Analog and Digital.

24
Instruction Manual Configuration
D103785X012 February 2023

Characterization
D Input Characterization

Input Characterization defines the relationship between the travel target and ranged set point. Ranged set point is the
input to the characterization function. If the zero power condition equals closed, then a set point of 0% corresponds to
a ranged input of 0%. If the zero power condition equals open, a set point of 0% corresponds to a ranged input of 100%.
Travel target is the output from the characterization function.

To select an input characterization, select Input Characterization from the Characterization menu. You can select from
the three fixed input characteristics shown in figure 3‐2 or you can select a custom characteristic. Figure 3‐2 shows the
relationship between the travel target and ranged set point for the fixed input characteristics, assuming the Zero
Power Condition is configured as closed.

You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for
a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before
modification, the custom characteristic is linear.

D Custom Characterization

To define a custom input character, select Custom Characterization from the Characterization menu. Select the point
you wish to define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for
the corresponding set point. When finished, select point 0 to return to the Characterization menu.

With input characterization you can modify the overall characteristic of the valve and instrument combination.
Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic
modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the
overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim
(i.e., the plug or cage).

25
Configuration Instruction Manual
February 2023 D103785X012

Figure 3‐2. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)

125 125

100 100
Travel Target, %

Travel Target, %
0 0

-25 -25
Ranged Set Point, % Ranged Set Point, %
-25 0 100 125 -25 0 100 125
Input Characteristic = Linear Input Characteristic = Equal Percentage

125

100
Travel Target, %

-25
-25 0 Ranged Set Point, % 100 125
Input Characteristic = Quick Opening
A6535‐1

26
Instruction Manual Configuration
D103785X012 February 2023

Dynamic Response
D SP Rate Open—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
open position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the
valve to stroke open as fast as possible.

D SP Rate Close—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
close position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the
valve to stroke close as fast as possible.

D Set Point Filter Time (Lag Time)—The Set Point Filter Time (Lag Time) slows the response of the digital valve
controller. A value ranging from 0.2 to 10.0 can be used for noisy or fast processes to improve closed loop process
control. Entering a value of 0.0 will deactivate the lag filter.

Note
Set Point Filter Time (Lag Time) is available for instrument level HC, AD, and PD.

D Lead/Lag Set Point Filter—ODV devices have access to a lead‐lag set point filter that can be used to improve a valve's
dynamic response. The lead‐lag filter is part of the set point processing routine that reshapes the input signal before
it becomes travel set point. Lead‐lag filters are characterized by lead and lag time constants.

Note
Lead/Lag is only available for instrument level ODV.

When the valve is in its active control region (off the seat), the lead‐lag filter improves small amplitude response by
momentarily overdriving the travel set point. This is useful when the actuator is large and equipped with accessories.
As a result, any volume boosters that are present will be activated. The longer the lag time, the more pronounced the
overdrive. Since the lead‐lag input filter is used to enhance the dynamic response of a control valve, filter parameters
should be set after the tuning parameters have been established.

When the valve is at its seat, the lead‐lag filter also has a boost function that sets the initial conditions of the filter
artificially low so that small amplitude signal changes appear to be large signal changes to the filter. The boost
function introduces a large spike that momentarily overdrives the instrument and activates any external volume
boosters that may be present. The lead‐lag boost function is normally disabled except for those cases where the valve
must respond to small command signals off the seat. By setting the lead/lag ratio in the opening and closing directions
to 1.0, the boost function can be enabled without introducing lead‐lag dynamics in the active control region. See table
3‐2 for typical lead‐lag filter settings.

Table 3‐2. Typical Lead/Lag Filter Settings for Instrument Level ODV
Parameter Description Typical Value
Lag Time First order time constant. A value of 0.0 will disable the lead‐lag filter. 0.2 sec
Opening Lead/Lag Ratio Initial response to the filter in the opening direction. 2.0
Closing Lead/Lag Ratio Initial response to the filter in the closing direction. 2.0
Lead‐Lag Boost Initial conditions of the lead‐lag filter when the lower travel cutoff is active. Off

27
Configuration Instruction Manual
February 2023 D103785X012

Tuning
Handheld Communicator Configure > Manual Setup > Tuning (2‐2-4)

Travel Tuning

WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.

D Travel Tuning Set

There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital valve
controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.

Table 3‐3 lists the proportional gain, velocity gain and minor loop feedback gain values for preselected tuning sets.

Table 3‐3. Gain Values for Preselected Travel Tuning Sets


Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback Gain
C 4.4 3.0 35
D 4.8 3.0 35
E 5.5 3.0 35
F 6.2 3.1 35
G 7.2 3.6 34
H 8.4 4.2 31
I 9.7 4.85 27
J 11.3 5.65 23
K 13.1 6.0 18
L 15.5 6.0 12
M 18.0 6.0 12
X (Expert) User Adjusted User Adjusted User Adjusted

In addition, you can specify Expert tuning and individually set the proportional gain, velocity gain, and minor loop
feedback gain. Individually setting or changing any tuning parameter or running Stabilize/Optimize will automatically
change the tuning set to X (expert).

Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize, or Performance Tuner in ValveLink software, may be used to achieve the desired results more rapidly than
manual Expert tuning.

Table 3‐4 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only
recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either
a higher or lower tuning set to get the desired response.

28
Instruction Manual Configuration
D103785X012 February 2023

Table 3‐4. Actuator Information for Initial Setup


Starting
Actuator Actuator Feedback Travel Sensor Motion
Actuator Size Actuator Style Tuning
Manufacturer Model Connection Relay A or C(1)
Set
25 Piston Dbl with or E SStem-Standard
50 w/out Spring. See I for travels up to
Depends upon pneumatic connections.
585C & 585CR 60 actuator instruction J 4 inches.
See description for Travel Sensor Motion
68, 80 manual and L SStem-Roller for
100, 130 nameplate. M longer travels
30 H
34, 40 K
657 45, 50 Spring & Diaphragm L SStem-Standard Clockwise
46, 60, 70, &
80‐100 M
30 H
34, 40 K
667 45, 50 Spring & Diaphragm L SStem-Standard Counterclockwise
46, 60, 70, 76, &
80‐100 M
20, 30 H
33 I
1051 & 1052 Spring & Diaphragm Rotary Clockwise
40 K
60, 70 M

Fisher 30 J
40 K Depends upon pneumatic connections.
1061 Piston Dbl w/o Spring Rotary
60 L See description for Travel Sensor Motion
68, 80, 100, 130 M
Mounting Style Travel Sensor Motion
A Clockwise
20 G
1066SR Piston Sgl w/Spring Rotary B Counterclockwise
27, 75 L
C Clockwise
D Counterclockwise
1 H
2052 2 Spring & Diaphragm J Rotary Clockwise
3 M
For Po operating mode (air opens):
30, 30E E
Counterclockwise
3024C 34, 34E, 40, 40E Spring & Diaphragm H SStem-Standard
For Ps operating mode (air closes):
45, 45E K
Clockwise
225 X(1) Air to Open Air to Close
GX 750 Spring & Diaphragm K SStem-Standard
Counterclockwise Clockwise
1200 M
Air to Extend 16 C Clockwise
32 E SStem-Standard
Air to Retract 54 H Counterclockwise
Baumann Spring & Diaphragm
10 E
Rotary 25 H Rotary Specify
54 J
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Values shown are for Relay A and C. Reverse for Relay B.

29
Configuration Instruction Manual
February 2023 D103785X012

D Proportional Gain—The proportional gain for the travel control tuning set. Changing this parameter will also change
the tuning set to Expert.

D Velocity Gain—The velocity gain for the travel control tuning set. Changing this parameter will also change the
tuning set to Expert.

D MLFB Gain—The minor loop feedback gain for the travel control tuning set. Changing this parameter will also
change the tuning set to Expert.

D Integral Enable—Yes or No. Enable the integral setting to improve static performance by correcting for error that
exists between the travel target and actual travel. Travel Integral Control is enabled by default.

D Integral Gain—Travel Integral Gain is the ratio of the change in output to the change in input, based on the control
action in which the output is proportional to the time integral of the input.

D Stabilize/Optimize

WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.

Stabilize/Optimize permits you to adjust valve response by changing the digital valve controller tuning. During this
routine the instrument must be out of service, however, the instrument will respond to setpoint changes.

If the valve is unstable select decrease response for a more conservative setting. If the valve response is sluggish, select
increase response for a more aggressive saving. When finished select Done.

30
Instruction Manual Configuration
D103785X012 February 2023

Pressure Tuning
D Pressure Tuning Set

There are twelve Pressure Tuning Sets to choose from. Each tuning set provides a preselected value for the digital valve
controller gain settings. Tuning set C provides the slowest response and M provides the fastest response. Tuning set B
is appropriate for controlling a pneumatic positioner. Table 3‐5 lists the proportional gain, pressure integrator gain and
minor loop feedback gain values for preselected tuning sets.

Table 3‐5. Gain Values for Preselected Pressure Tuning Sets


Tuning Set Proportional Gain Integrator Gain Minor Loop Feedback Gain
B 0.5 0.3 35
C 2.2 0.1 35
D 2.4 0.1 35
E 2.8 0.1 35
F 3.1 0.1 35
G 3.6 0.1 34
H 4.2 0.1 31
I 4.8 0.1 27
J 5.6 0.1 23
K 6.6 0.1 18
L 7.8 0.1 12
M 9.0 0.1 12
X (Expert) User Adjusted User Adjusted User Adjusted

In addition, you can specify Expert tuning and individually set the pressure proportional gain, pressure integrator gain,
and pressure minor loop feedback gain. Individually setting or changing any tuning parameter will automatically
change the tuning set to X (expert).

Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize, or Performance Tuner in ValveLink software, may be used to achieve the desired results more rapidly than
Expert tuning.

D Proportional Gain—The proportional gain for the pressure control tuning set. Changing this parameter will also
change the tuning set to Expert.

D MLFB Gain—The minor loop feedback gain for the pressure control tuning set. Changing this parameter will also
change the tuning set to Expert.

D Integral Enable—Yes or No. Enable the pressure integral setting to improve static performance by correcting for
error that exists between the pressure target and actual pressure. Pressure Integral Control is enabled by default.

D Integral Gain—Pressure Integral Gain (also called reset) is the gain factor applied to the time integral of the error
signal between desired and actual pressure. This feature is used during pressure control for greater accuracy during
pressure control/fallback. Changing this parameter will also change the tuning set to Expert.

Travel/Pressure Integral Settings


D Integral Dead Zone—A window around the Primary Setpoint in which integral action is disabled. The Dead Zone is
configurable from 0% to 2%, corresponding to a symmetric window from 0% to +/-2% around the Primary Setpoint.

31
Configuration Instruction Manual
February 2023 D103785X012

Integral Dead Zone is used to eliminate friction induced limit cycles around the Primary Setpoint when the
integrator is active. This dead zone value is used during the Auto Calibration of Travel procedure even if the travel
integral is disabled; in the case of Auto Calibration travel failures with piston actuators, this value should be set to
1%. Default value is 0.26%.

D Integrator Limit—The Integrator Limit provides an upper limit to the integrator output. The high limit is configurable
from 0 to 100% of the I/P drive signal.

Valve and Actuator


Handheld Communicator Configure > Manual Setup > Valve and Actuator (2‐2‐5)

Valve Style—Enter the valve style, rotary or sliding‐stem

Actuator Style—Enter the actuator style, spring and diaphragm, piston double‐acting without spring, piston
single‐acting with spring, or piston double‐acting with spring.

View/Edit Feedback Connection—Select Rotary All, SStem - Roller or SStem - Standard. For rotary valves, enter Rotary -
All, SStem - Roller. For sliding-stem valves, if the feedback linkage consists of a connector arm, adjustment arm, and
feedback arm (similar to figure 3‐3), enter SStem - Standard. If the feedback linkage consists of a roller that follows a
cam (similar to figure 3‐4), enter Rotary All, SStem - Roller.

Figure 3‐3. Feedback Connection for Typical Figure 3‐4. Feedback Connection for Typical
Sliding-Stem Actuator (Up to 4 inch Travel) Long-Stroke Sliding-Stem Actuator (4 to 24 Inches
Travel)
ACTUATOR
STEM TRAVEL SENSOR SHAFT

ROLLER

FEEDBACK
ARM

ADJUSTMENT STEM
ARM CONNECTOR CAM

CONNECTOR X0914

ARM

Relay Type—There are three categories of relays that result in combinations from which to select.
Relay Type: The relay type is printed on the label affixed to the relay body.
A = double‐acting or single‐acting
B = single‐acting, reverse
C= single‐acting, direct
Special App: This is used in single‐acting applications where the “unused” output port is configured to read the
pressure downstream of a solenoid valve.
Lo Bleed: The label affixed to the relay body indicates whether it is a low bleed version.

32
Instruction Manual Configuration
D103785X012 February 2023

Zero Power Condition—The position of the valve (open or closed) when the electrical power to the instrument is
removed. Zero Power Condition (ZPC) is determined by relay type, as shown in figure 3‐5.

Figure 3‐5. Zero Power Condition

Relay Type Loss of Electrical Power


A
Single‐Acting Direct (Relay A or C) Port A pressure to zero.

Port A pressure to zero.


Double‐Acting (Relay A) Port B pressure to full supply.

Single‐Acting Reverse (Relay B) Port B pressure to full supply.


B

X0797

Travel Sensor Motion

WARNING
If you answer YES to the prompt for permission to move the valve when determining travel sensor motion, the instrument
will move the valve through a significant portion of its travel range. To avoid personal injury and property damage caused
by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the
valve or bleed off the process fluid.

Travel Sensor Motion—Select Clockwise, or Counterclockwise. Travel Sensor Motion establishes the proper travel
sensor rotation. Determine the rotation by viewing the end of the travel sensor shaft from the perspective of the
actuator.

D For instruments with Relay A and C: If increasing air pressure at output A causes the shaft to turn clockwise, enter
Clockwise. If it causes the shaft to turn counterclockwise, enter Counterclockwise.

D For instruments with Relay B: If increasing air pressure at output B causes the shaft to turn counterclockwise, enter
Clockwise. If it causes the shaft to turn clockwise, enter Counterclockwise.

Maximum Supply Pressure

Enter the maximum supply pressure that is required to fully stroke the valve.

33
Configuration Instruction Manual
February 2023 D103785X012

Port A Pressure Limit

In single acting direct only applications, the instrument will limit the output pressure to the actuator from Port A.
When this pressure limit is exceeded the device will go to the no air state.

Note
This is a firmware controlled feature that requires loop power to the instrument. If loop power is lost, or there is an electronic or
firmware failure, the protection feature will not remain in effect.

Output Pressure Limit Enable enables/disables the Port A Pressure Limit feature.

Note
There is an associated alert available with this feature. See the Port A Overpressurized alert in the Alert Setup section.

Partial Stroke Test (PST)


Handheld Communicator Configure > Manual Setup > Partial Stroke (2-2-6)

Note
Partial Stroke is only available for instrument level ODV.

Partial Stroke Test Parameters


Test Start Point defines the normal (not tripped) end of valve travel. The valve must be at this end for a PST to be
initiated. Setting this value to Not Configured will disable partial stroke tests.

Travel Hi Hi defines, in percent (%) of calibrated travel, the point above which the valve is considered to have reached
the high end.

Travel Lo Lo defines, in percent (%) of calibrated travel, the point below which the valve is considered to have reached
the low end.

Pause Time is the time between the outgoing and incoming strokes of the test. The default value is 5 seconds. Pause
Time will not be used if Short Duration PST is enabled. The outgoing stroke is from the normal end to the PST target
and the incoming stroke is the return stroke to normal. See figure 3‐6.

34
Instruction Manual Configuration
D103785X012 February 2023

Figure 3‐6. Valve Signature Representation


PST START POINT
1
2
3

INCOMING STROKE
4
5

OUTGOING STROKE
6
PRESSURE

TRIPPED NORMAL
7
TRAVEL
1 SUPPLY PRESSURE
2 END POINT PRESSURE CONTROL
3 INCOMING PRESSURE THRESHOLD
4 LOW FRICTION BREAKOUT PRESSURE THRESHOLD
5 HIGH FRICTION BREAKOUT PRESSURE THRESHOLD
6 OUTGOING PRESSURE THRESHOLD
7 TARGET TRAVEL MOVEMENT  30%

High Friction Breakout Pressure indicates that the breakout required a higher force than configured by the user. Refer
to figure 3‐6.

Low Friction Breakout Pressure indicates that the breakout required a lower force than configured by the user. Refer to
figure 3‐6.

Action On a Failed Test defines if the valve should step or ramp back on a failed stroke test.

Auto Test Interval is the interval of time in days between valve stroke tests that are automatically executed by the
digital valve controller, subject to the device being powered up. A value of 0 disables this feature.

Partial Stroke Parameters


Minimum Travel Movement is the percentage of total span that the valve moves away from its normal operating end
of travel towards its tripped end of travel during the test. The default value is 10%.

Short Duration PST, when enabled the incoming stroke is initiated as soon as the travel reaches the minimum travel
movement. Refer to figure 3‐7 for a time series representation of this parameter.

35
Configuration Instruction Manual
February 2023 D103785X012

Figure 3‐7. Time Series Representation of Short Duration PST

TRAVEL
TRAVEL

NORMAL NORMAL
INCOMING
OUTGOING RAMP RATE
RAMP RATE
REDUCED
PST TIME

RETURN
LEAD
1
1 2 RETURN
2
LEAD
3

TIME BREAKOUT EARLY TIME


PAUSE TIME TIMEOUT TURNAROUND

SHORT DURATION PST SHORT DURATION PST


DISABLED ENABLED

1 MINIMUM TRAVEL MOVEMENT


2 TRAVEL TARGET MOVEMENT
3 MAX. ALLOWABLE TRAVEL

Outgoing Ramp Rate is the rate at which the valve will move during the Outgoing stroke of the Partial Stroke test. The
default value is 0.25%/second.

Incoming Ramp Rate is the rate at which the valve will move during the Incoming stroke of the Partial Stroke test. The
default value is 0.25%/second.

Return Lead defines the percent (%) change in setpoint to overcome the hysteresis in the valve assembly. The error
between setpoint and actual error is added to this percent change. For example, if the Return Lead is set at 0.5% and
there is a 1% error this will be set at 1.5%

Breakout Timeout is the user configured amount of time before which the valve must leave the normal end during a
PST.

Outgoing Pressure Threshold defines the actuator pressure at which a partial stroke test will abort during the outgoing
stroke (see figure 3‐6). This prevents the DVC6200 from exhausting (or building) excessive pressure from/to the
actuator in an attempt to move a stuck valve. During PST Calibration, the Partial Stroke Outgoing Pressure Threshold
will be set automatically as follows:

d Single Acting Actuators - For those actuators that exhaust pressure from the partial test start point, the Outgoing
Pressure Threshold will be a minimum value. For those actuators that build pressure from the partial test start point,
the Outgoing Pressure Threshold will be a maximum value.

d Double Acting Actuators - The Outgoing Pressure Threshold will be set to a negative value for actuators where the
partial stroke start point is opposite of the Zero Power Condition (e.g., Partial Stroke Start Point = Open and Zero
Power Condition = Closed) and to a positive valve for actuators where the partial stroke start point is the same as the
Zero Power Condition.

36
Instruction Manual Configuration
D103785X012 February 2023

The pressure signal used to determine this parameter depends on relay type and is summarized below.
Relay Type Pressure Signal
A or C Port A - Port B
B Port B - Port A
B Special App. Port B
C Special App. Port A
To manually set the partial stroke Outgoing Pressure Threshold, you must examine current partial stroke test results
using ValveLink software. The following steps will guide you through the process:
1. Connect the DVC6200 to a system running ValveLink software.
2. Disable Partial Stroke Outgoing Pressure Limit by ensuring it is not selected as an evaluation criteria for PST
Abnormal.
3. Run a partial stroke test.
4. Select the Press/Time radio button on the partial stroke graph (refer to the example in figure 3‐8). If the actuator
pressure starts high and moves low, find the minimum actuator pressure (Pmin). If the actuator pressure starts low
and moves high, find the maximum actuator pressure (Pmax). Double­acting actuators will display differential
pressure. Use table 3‐6 to estimate the Outgoing Pressure Threshold.
5. Enable the previously disabled Outgoing Pressure Limit - calculate the value using table 3‐6.

Table 3‐6. Estimates for Outgoing Partial Stroke Pressure Limits


Actuator Style Relay Type Zero Power Condition PST Starting Point Partial Stroke Pressure Limit
Open Pmin - 0.25 * (Bench Set High - Bench Set Low)
Closed
Closed Pmax + 0.25 * (Bench Set High - Bench Set Low)
A or C
Open Pmax + 0.25 * (Bench Set High - Bench Set Low)
Open
Spring and Closed Pmin - 0.25 * (Bench Set High - Bench Set Low)
Diaphragm Open Pmax + 0.25 * (Bench Set High - Bench Set Low)
Closed
Closed Pmin - 0.25 * (Bench Set High - Bench Set Low)
B
Open Pmin - 0.25 * (Bench Set High - Bench Set Low)
Open
Closed Pmax + 0.25 * (Bench Set High - Bench Set Low)

Open 0.5 * Pmin


Closed
Closed Pmax + 0.5 * (Psupply - Pmax)
A or C
Open Pmax + 0.5 * (Psupply - Pmax)
Open
Closed 0.5 * Pmin
Single Acting Piston
Open Pmax + 0.5 * (Psupply - Pmax)
Closed
Closed 0.5 * Pmin
B
Open 0.5 * Pmin
Open
Closed Pmax + 0.5 * (Psupply - Pmax)

Open Pmin - 0.5 * (Psupply + Pmin)


Closed
Closed Pmax + 0.5 * (Psupply - Pmax)
Double Acting Piston A
Open Pmax + 0.5 * (Psupply - Pmax)
Open
Closed Pmin - 0.5 * (Psupply + Pmin)

37
Configuration Instruction Manual
February 2023 D103785X012

Figure 3‐8. Example Time Series Plot; Actuator Pressure

ACTUAL TRACE FROM TEST (TYPICAL)


MINIMUM PRESSURE
PRESSURE (%)

(Pmin)

OUTGOING PRESSURE LIMIT

TIME (SEC)

Incoming Pressure Threshold defines the actuator pressure at which a partial stroke test will abort during the incoming
stroke (see figure 3‐6). This prevents the DVC6200 from exhausting (or building) excessive pressure from / to the
actuator in an attempt to move a stuck valve.

PST Abnormal Criteria


A partial stroke test is marked as abnormal if it fails any of the following user-selected criteria.
1. Stroking Pressure (includes outgoing and incoming)
2. Hi friction breakout pressure
3. Low friction breakout pressure
4. Max travel
5. Insufficient travel
6. Not seated (either at the start or end of the test)
7. SOV Test preceded PST and failed
8. Travel deviation

PST Abort Criteria


The PST is terminated and the valve is returned to the normal end. The return to the normal end will be per the user
configuration for an aborted test. The abort criteria will only be active if it is added as a criteria to be evaluated during
PST by adding it to the PST Abnormal Criteria.

The user can select any of the following to abort a Partial Stroke Test:
1. Stroking Pressure (includes outgoing and incoming)
2. Hi friction breakout pressure
3. Low friction breakout pressure
4. Max travel
5. Insufficient travel
6. Not seated (either at the start or end of the test)
7. SOV Test preceded PST and failed
8. Travel deviation

38
Instruction Manual Configuration
D103785X012 February 2023

PST Prohibited
A partial stroke test will not be initiated if any of the following user-configurable conditions are active:
1. Flash Integrity Failure
2. Minor Loop Sensor Failure
3. Reference Voltage Failure
4. Drive Current Failure
5. Critical NVM Failure
6. Temperature Sensor Failure
7. Pressure Sensor Failure
8. Travel Sensor Failure
9. Supply Pressure Low
10. Travel Deviation
11. Pressure Fallback active

39
Configuration Instruction Manual
February 2023 D103785X012

Outputs
Handheld Communicator Configure > Manual Setup > Outputs (2-2-6) HC, AD, PD or (2-2-7) ODV

Output Terminal Configuration

Note
Output Terminal Configuration is only available on units that have the optional 4­20 mA position transmitter or switch hardware
installed. For information on position transmitter/discrete switch wiring and configuration refer to the DVC6005 Series Remote
Mount Digital Valve Controller Quick Start Guide (D103784X012).

D Output Terminal Enable—If using the optional output terminal for a Position Transmitter or Switch output, this must
be enabled with a user interface tool such as ValveLink software.

D Function—The output terminals can be configured as one of the following:


Transmitter - 4­20 mA output that represents 0­100% of the calibrated valve travel.
Limit Switch - Discrete switch (1 A max) that trips at a configurable point within 0­100% of calibrated valve travel.
Alert Switch - Discrete switch (1 A max) that trips based on a configurable device alert.
D Fail Signal—Should the output circuit fail to operate properly, the output will attempt to drive to a known state.
Depending on the nature of the failure, the circuit may or may not be able to achieve this fail state. When
configured as a position transmitter, the output can be configured to fail low (< 3.6 mA). The output can be
configured to fail high (> 22.5 mA) when the digital valve controller is powered. When configured as a switch, the
output can be configured to drive Closed or Open.

Note
On loss of digital valve controller power, the switch circuit will always go to the open state.

Switch Configuration

Note
Switch Configuration is only available on units that have the optional 4­20 mA position transmitter or switch hardware installed.

D Limit Switch Trip Point—When the function is configured as a Limit Switch, the Limit Switch Trip Point defines the
threshold for the limit switch in percent of calibrated travel.

D Alert Switch Source—When the function is configured as an Alert Switch, the Alert Switch Source determines which
alert will activate the switch. The alert choices are: Travel Deviation or Pressure Fallback.

40
Instruction Manual Configuration
D103785X012 February 2023

D Switch Closed—Configures the action of the switch. The choices are: Below Trip Point / Alert Not Active or Above
Trip Point / Alert Active.

HART Variable Assignments


Instrument variables can be reported via four different HART variable assignments. The Primary Variable is always
configured as Analog Input. However, the remaining three variables have additional options as listed below.
Primary Variable (PV) Analog Input
Secondary Variable (SV) Travel, Travel Setpoint, Pressure A, Pressure B, Pressure A­B, Supply Pressure,
Drive Signal, or Analog Input; default value is Travel Setpoint
Tertiary Variable (TV) Travel, Travel Setpoint, Pressure A, Pressure B, Pressure A­B, Supply Pressure,
Drive Signal, or Analog Input; default value is Pressure A.
Quaternary Variable (QV) Travel, Travel Setpoint, Pressure A, Pressure B, Pressure A­B, Supply Pressure,
Drive Signal, or Analog Input; default value is Travel.

Transmitter Output

Note
Transmitter Output is only available on units that have the optional 4­20 mA position transmitter or switch hardware installed.

This configures the relationship between the valve travel and the position transmitter output signal. There are two
choices; 4mA = Valve Closed or 4mA = Valve Open.

Burst Mode
Burst mode provides continuous communication from the digital valve controller. Burst mode applies only to the
transmission of burst mode data (HART Variable Assignments) and does not affect the way other data is accessed.

D Burst Enable—Turns on or off the burst mode.

D Burst Command—Defines which HART command is configured for burst reporting. When using a Tri­Loop, select
Command 3.
HART 5
- Analog Input (Command 1)
- Loop Current / Travel (Command 2)
- Loop Current / PV / SV / TV / QV (Command 3)
HART 7 -
- Analog Input (Command 1)
- Loop Current / Travel (Command 2)
- Loop Current / PV / SV / TV / QV (Command 3)
- Read Device Variable with Status (Command 9)
- Read Device Variables (Command 33)
- Read Additional Status (Command 48)

41
Configuration Instruction Manual
February 2023 D103785X012

Note
Access to information in the instrument is normally obtained through the poll/response of HART communication. A handheld
communicator or the control system may request any of the information that is normally available, even while the instrument is in
burst mode. Between each burst mode transmission sent by the instrument, a short pause allows the handheld communicator or
control system to initiate a request. The instrument receives the request, processes the response message, and then continues
“bursting” the burst mode data.
Burst mode will be disabled by ValveLink software during diagnostics tests such as Valve Signature.
HART 7 allows three burst commands to be reported. When using a Tri-Loop, do not enable the 2nd or 3rd burst commands. These
additional commands will result in missed messages, thus taking the Tri-Loop's output to the fault state.

Note
If the instrument is configured to operate in pressure control mode, or detects an invalid travel sensor reading, the Travel variable
will report pressure in percent of bench set range.

Alert Setup
Handheld Communicator Configure > Alert Setup (2‐3)

An alert is a notification that the instrument has detected a problem. Alerts that are enabled and active will be
recorded in the instrument memory within the Alert Record (see Section 5). Some alerts are also defined in the HART
Command 48 response structure which is can be read by any HART communicating host system (refer to the HART
Field Device Specification, D103782X012).

Certain critical alerts can be configured to shut down the device when active (i.e. latch in the Zero Power Condition).
This can be enabled or disabled for each applicable alert. The default shutdown setting is disabled. To clear the
shutdown, correct the problem and then cycle power to the instrument (or disable the alert).

Alerts may be enabled or disabled with the instrument In Service, Out of Service, Protection On, or Protection Off.
However, shutdown alerts can only be enabled or disabled while Protection is off.

For a detailed explanation of the alerts and the recommended actions, refer to Section 5.

Change to HART 5 / Change to HART 7


Handheld Communicator Service Tool > Maintenance > Change to HART 5 / Change to HART 7 (3-5-3) HC or (3-5-4) AD, PD or (3-5-5) ODV

Note
This procedure must never be done while the valve is in service and controlling the process. Depending on the control system or
asset management system attached, complete system reset may be required to reestablish HART communication. Consult the
system documentation for further information.

This procedure changes the instrument from HART Universal Revision 5 to HART Universal Revision 7 (or vice versa).
Before proceeding, verify that your systems are prepared to support HART Universal Revision 7 devices. Follow the
prompts on the handheld communicator display.

42
Instruction Manual Calibration
D103785X012 February 2023

Section 4 Calibration 44
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.

Calibration Overview
When a DVC6000 HW2 digital valve controller is ordered as part of a control valve assembly, the factory mounts the
remote feedback unit on the actuator and connects the necessary tubing, then sets up and calibrates the controller.

For digital valve controllers that are ordered separately, recalibration of the analog input or pressure sensors generally
is unnecessary. However, after mounting on an actuator, perform the initial setup then calibrate travel by selecting
Configure > Calibration > Travel Calibration > Auto Calibration. For more detailed calibration information, refer to the
following calibration procedures.

Handheld Communicator Configure > Calibration (2-4)

Auto Travel Calibration - see page 44

Manual Travel Calibration - see page 46

Pushbutton Calibration - see page 47

Pressure Sensor Calibration - see page 48

Travel Sensor Calibration - see page 49

Analog Input Calibration - see page 53

Relay Adjustment - see page 54

PST Calibration (ODV Instrument Level only) - see page 56

Note
The Instrument Mode must be Out Of Service and the Protection set to None before the instrument can be calibrated.
If you are operating in burst mode, we recommend that you disable burst before continuing with calibration. Once calibration is
complete, burst mode may then be turned back on.

WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.

43
Calibration Instruction Manual
February 2023 D103785X012

Travel Calibration
If a double‐acting relay is used, you will be prompted to run the relay adjustment when auto or manual calibration is
selected. Select Yes to adjust the relay, select No to proceed with calibration. For additional information, refer to Relay
Adjustment on page 54.

Auto Calibration
User interaction is only required with Auto Calibrate Travel when the feedback connection is SStem ‐ Standard (Sliding
Stem ‐ Standard). A feedback connection of Rotary ‐ All, SStem ‐ Roller (Sliding Stem ‐ Roller) requires no user
interaction and you can start with step 6.

For a SStem ‐ Standard feedback connection, interaction provides a more accurate crossover adjustment. Setting
crossover establishes the zero degree point for the geometric correction used to translate the rotary motion observed
by the travel sensor into the linear motion of the sliding‐stem valve.

1. Select the method of crossover adjustment: manual, last value, or default. Manual is the recommended choice. If
you select Manual, the handheld communicator will prompt you to adjust the crossover in step 3.
If you select Last Value, the crossover setting currently stored in the instrument is used and there are no further user
interactions with the auto‐calibration routine (go to step 6). Use this selection if you cannot use manual, such as
when you cannot see the valve.
If you select Default, an approximate value for the crossover is written to the instrument and there are no further
user interactions with the auto‐calibration routine (go to step 6). Use this selection only as a last resort. Default
assumes a midrange position on the travel sensor as the crossover point, however, this may not be an appropriate
value to use for crossover because of variations in mounting and travel sensor calibration.
2. The instrument seeks the high and low drive points and the minor loop feedback (MLFB) and output bias. No user
interaction is required in this step. For a description of these actions see step 6.
3. If you select Manual in step 1, you are asked to select an adjustment source, either analog or digital. If you use a
current source to adjust the crossover, select Analog and go to step 4. If you wish to adjust the current source
digitally, select Digital and go to step 5.
4. If you selected Analog as the crossover adjustment source, the handheld communicator prompts you to adjust the
current source until the feedback arm is 90° to the actuator stem, as shown in figure 4‐1. After you have made the
adjustment, press OK and go to step 6.
5. If you selected Digital as the crossover adjustment source, the handheld communicator displays a menu to allow
you to adjust the crossover.
Select the direction and size of change required to set the feedback arm so it is 90° to the actuator stem, as shown
in figure 4‐1. Selecting large, medium, and small adjustments to the crossover causes changes of approximately
10.0°, 1.0°, and 0.1°, respectively, to the rotation of the feedback arm.
If another adjustment is required, repeat step 5. Otherwise, select Done and go to step 6.
6. The remainder of the auto calibration procedure is automatic. It is completed when the Calibration menu appears.
During calibration, the instrument seeks the high and low end points and the minor loop feedback (MLFB) and
output bias. By searching for the end points, the instrument establishes the limits of physical travel, i.e. the actual
travel 0 and 100% positions. This also determines how far the relay beam swings to calibrate the sensitivity of the
MLFB sensor.

44
Instruction Manual Calibration
D103785X012 February 2023

Figure 4‐1. Crossover Point

ACTUATOR
STEM

90_

FEEDBACK
ARM

A6536-3

7. Place the instrument In Service and verify that the travel properly tracks the current source.

If the unit does not calibrate, refer to table 4‐1 for error messages and possible remedies.

Table 4‐1. Auto Calibrate Travel Error Messages


Error Message Possible Problem and Remedy
The analog input signal to the instrument must be greater than 3.8 mA. Adjust the current output
Power failure occurred during Auto Calib
from the control system or the current source to provide at least 4.0 mA.
The problem may be one or the other of the following:
1. The tuning set selected is too low and the valve does not reach an end point in the allotted time.
Select Manual Setup > Tuning > Travel Tuning > Stabilize/Optimize then Increase Response (selects next
Auto Calib did not complete within the time limit. higher tuning set).
2. The tuning set selected is too high, valve operation is unstable and does not stay at an end point
for the allotted time. Select Manual Setup > Tuning > Travel Tuning > Stabilize/Optimize then Decrease
Response (selects next lower tuning set).
Prior to receiving this message, did the instrument output go from zero to full supply? If not, verify
instrument supply pressure by referring to the specifications in the appropriate actuator instruction
manual. If supply pressure is correct, check instrument pneumatic components (I/P converter and
relay).

Insufficient travel If the instrument output did go from zero to full supply prior to receiving this message, then verify
proper mounting by referring to the appropriate mounting procedure in the Installation section.

Verify travel sensor adjustment by performing the appropriate Travel Sensor Adjust procedure in the
Calibration section. Making the crossover adjustment with the valve positioned at either end of its
travel will also cause this message to appear.
Drive signal exceed low limit; check supply 1. Check supply pressure (reverse‐acting relay)
pressure 2. Friction is too high.
Drive signal exceed high limit; check supply 1. Check supply pressure (direct‐acting relay)
pressure 2. Friction is too high

45
Calibration Instruction Manual
February 2023 D103785X012

Manual Calibration
Two procedures are available to manually calibrate travel:
D Analog Adjust— This procedure is used when you can manually change the 4-20 mA current source to move the
valve.
D Digital Adjust— This procedure is used when the 4-20 mA current source cannot be manually changed.

Analog Calibration Adjust


Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be
capable of generating 4 to 20 mA.
Follow the prompts on the handheld communicator display to calibrate the instrument's travel in percent.

Note
0% Travel = Valve Closed
100% Travel = Valve Open

1. Adjust the input current until the valve is near mid‐travel. Press OK.

Note
In steps 2 through 7 the accuracy of the current source adjustment affects the position accuracy.

2. Adjust the current source until the valve is at 0% travel, then press OK.
3. Adjust the current source until the valve is at 100% travel, then press OK.
4. Adjust the current source until the valve is at 0% travel, then press OK.
5. Adjust the current source until the valve is at 100% travel, then press OK.
6. Adjust the current source until the valve is at 5% travel, then press OK.
7. Adjust the current source until the valve is at 95% travel, then press OK.
8. Place the instrument In Service and verify that the travel properly tracks the current source.
Digital Calibration Adjust
Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be set
between 4 and 20 mA.
Follow the prompts on the handheld communicator display to calibrate the instrument's travel in percent.
1. Adjust the input current until the valve is near mid‐travel. Press OK.

Note
0% Travel = Valve Closed
100% Travel = Valve Open

46
Instruction Manual Calibration
D103785X012 February 2023

2. From the adjustment menu, select the direction and size of change required to set the travel at 0%.
Selecting large, medium, and small adjustments causes changes of approximately 10.0%, 1.0%, and 0.1%,
respectively. If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3.
3. From the adjustment menu, select the direction and size of change required to set the travel to 100%.
If another adjustment is required, repeat step 3. Otherwise, select Done and go to step 4.
4. From the adjustment menu, select the direction and size of change required to set the travel at 0%.
If another adjustment is required, repeat step 4. Otherwise, select Done and go to step 5.
5. From the adjustment menu, select the direction and size of change required to set the travel to 100%.
If another adjustment is required, repeat step 5. Otherwise, select Done and go to step 6.
6. From the adjustment menu, select the direction and size of change required to set the travel to 5%.
If another adjustment is required, repeat step 6. Otherwise, select Done and go to step 7.
7. From the adjustment menu, select the direction and size of change required to set the travel to 95%.
If another adjustment is required, repeat step 7. Otherwise, select Done and go to step 8.
8. Place the instrument In Service and verify that the travel properly tracks the current source.

Pushbutton Calibration
A pushbutton near the wiring terminals in the terminal box provides a quick means to autocalibrate the instrument.
The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve through the full range of travel
whether the Instrument Mode is In Service or Out of Service. However, if the Write Protection is Protected, this button
will not be active. To abort, press the button again for 1 second. The calibration button is enabled by default.

Note
Pressure range (used for Pressure Fallback) is not recalibrated during this procedure.

This calibration procedure is recommended whenever the I/P converter or pneumatic relay is replaced. Do not use the
pushbutton calibration for initial calibration when mounting the instrument on an actuator, or if the printed wiring
board assembly was replaced.

If you suspect calibration has changed due to drift, first perform a Valve Signature diagnostic test using ValveLink
software to capture the as­found data for future root cause analysis.

47
Calibration Instruction Manual
February 2023 D103785X012

Sensor Calibration

Pressure Sensors

Note
The pressure sensor is calibrated at the factory and should not require calibration.

Output Pressure Sensor


To calibrate the output pressure sensor, connect an external reference gauge to the output being calibrated. The
gauge should be capable of measuring maximum instrument supply pressure. Depending upon the sensor you wish to
calibrate, select either Output A Sensor or Output B Sensor. Follow the prompts on the handheld communicator display
to calibrate the instrument's output pressure sensor.
1. Adjust the supply pressure regulator to the maximum instrument supply pressure. Press OK.
2. The instrument reduces the output pressure to 0. The following message appears.

Use the Increase and Decrease


selections until the displayed
pressure matches the output x
pressure.

Press OK when you have read the message.


3. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value.
Selecting large, medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30
psi/0.0207 bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively.

If the displayed value does not match the output pressure, press OK, then repeat this step (step 4) to further adjust
the displayed value. When the displayed value matches the output pressure, select Done and go to step 5.
5. The instrument sets the output pressure to full supply. The following message appears.

Use the Increase and Decrease


selections until the displayed
pressure matches the output x
pressure.

Press OK when you have read the message.


6. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
7. From the adjustment menu, select the direction and size of adjustment to the displayed value. If the displayed value
does not match the output pressure, press OK, then repeat this step (step 7) to further adjust the displayed value.
When the displayed value matches the output pressure, select Done and go to step 8.
8. Place the instrument In Service and verify that the displayed pressure matches the measured output pressure.

48
Instruction Manual Calibration
D103785X012 February 2023

Supply Pressure Sensor


To calibrate the supply pressure sensor, connect an external reference gauge to the output side of the supply
regulator. The gauge should be capable of measuring maximum instrument supply pressure. Follow the prompts on
the handheld communicator display to calibrate the instrument's supply pressure sensor.
1. Select a) Zero Only, or b) Zero and Span (gauge required).
a. If Zero Only calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Once calibration is complete, go to step 5.

b. If Zero and Span calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Adjust the supply regulator to the maximum instrument supply pressure. Press OK.
Proceed with step 2.
2. The following message appears:

Use the Increase and Decrease


selections until the displayed
pressure matches the supply
pressure.

Press OK when you have read this message.


3. The value of the pressure appears on the display.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value.
Selecting large, medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30
psi/0.0207 bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively.

Adjust the displayed value until it matches the supply pressure, select Done and go to step 5.
5. Place the instrument In Service and verify that the displayed pressure matches the measured supply pressure.

Travel Sensor
The travel sensor is normally adjusted at the factory and should not require adjustment. However, if the travel sensor
has been replaced, adjust the travel sensor by performing the appropriate procedure. See the Maintenance section for
travel sensor assembly replacement procedures.

DVC6015 and DVC6035 Remote Feedback Units

WARNING
Failure to remove air pressure may cause personal injury or property damage from bursting parts.

1. Remove supply air and remove the instrument from the actuator.

49
Calibration Instruction Manual
February 2023 D103785X012

2. As shown in figure 4‐2, align the feedback arm (key 79) with the housing by inserting the alignment pin (key 46)
through the hole marked “A” on the feedback arm. Fully engage the alignment pin into the tapped hole in the
housing.

Note
The alignment pin (key 46) is stored inside the remote feedback unit housing.

Figure 4‐2. FIELDVUE DVC6015 Remote Feedback Unit Showing Feedback Arm in Position for Travel Sensor
Adjustment

ALIGNMENT PIN
FEEDBACK ARM (KEY 46)
(KEY 79)

TRAVEL
SENSOR
SHAFT

X0918

3. Loosen the screw that secures the feedback arm to the travel sensor shaft. Position the feedback arm so that the
surface of the feedback arm is flush with the end of the travel sensor shaft.
4. Connect a current source to the instrument LOOP - and LOOP + terminals. Set the current source to any value
between 4 and 20 mA. Connect the handheld communicator to the TALK terminals.
5. Before beginning the travel sensor adjustment, set the instrument mode to Out Of Service and the protection to
None.
6. From the Calibrate menu select Sensor Calibration, Travel Sensor. Follow the prompts on the handheld communicator
display to adjust the travel sensor counts to the value listed in table 4‐2.

Table 4‐2. Travel Sensor Counts


Remote Feedback Unit Travel Sensor Counts
DVC6015 700 ±200
DVC6025 2100 ±200
DVC6035
600 ±200
Counterclockwise shaft rotation(1)
DVC6035
3400 ±200
Clockwise shaft rotation(1)
1. Refer to figure 4‐3 to determine the desired starting position for the DVC6035 based on potentiometer shaft; counterclockwise or clockwise.

50
Instruction Manual Calibration
D103785X012 February 2023

Figure 4‐3. Travel Indicator Assembly Starting Position; Counterclockwise or Clockwise

DVC6035 FEEDBACK
ARM MOVEMENT
DVC6035 FEEDBACK
ARM MOVEMENT

ACTUATOR SHAFT MOVEMENT ACTUATOR SHAFT MOVEMENT


STARTING POSITION OF THE TRAVEL INDICATOR ASSEMBLY IF STARTING POSITION OF THE TRAVEL INDICATOR ASSEMBLY
INCREASING PRESSURE FROM OUTPUT A DRIVES THE INDICATOR IF INCREASING PRESSURE FROM OUTPUT A DRIVES THE
CLOCKWISE. THE POTENTIOMETER SHAFT WILL ROTATE INDICATOR COUNTERCLOCKWISE. THE POTENTIOMETER
COUNTERCLOCKWISE AS VIEWED FROM THE BACK OF THE SHAFT WILL ROTATE CLOCKWISE AS VIEWED FROM THE
INSTRUMENT. BACK OF THE INSTRUMENT.

Note
In the next step, be sure the feedback arm surface remains flush with the end of the travel sensor shaft.

7. While observing the travel sensor counts, tighten the screw that secures the feedback arm to the travel sensor
shaft. Be sure the travel sensor counts remain within the tolerances listed in table 4‐2. Paint the screw to discourage
tampering with the connection.
8. Disconnect the handheld communicator and current source from the instrument.
9. Remove the alignment pin and store it in the instrument housing.
10. Install the remote feedback unit on the actuator.

DVC6025 Remote Feedback Unit

WARNING
Failure to remove air pressure may cause personal injury or property damage from bursting parts.

1. Remove supply air and remove the instrument from the actuator.
2. See figure 4‐4 for parts identification. Disconnect the bias spring (key 82) from the feedback arm assembly (key 84)
and the arm assembly (key 91). Remove the mounting bracket (key 74) from the back of the feedback unit. Hold
the arm assembly (key 91) so that the arm assembly points toward the terminal box and the arm is parallel to the
back of the housing, as shown in figure 4‐5.

51
Calibration Instruction Manual
February 2023 D103785X012

Figure 4‐4. FIELDVUE DVC6025 Digital Valve Controller Mounted on Fisher 2052, Size 33 Actuator

CAP SCREW, HEX SOCKET


MOUNTING (KEY 116)
ADAPTER
(KEY 117)

MOUNTING BRACKET
(KEY 74)

BIAS SPRING
(KEY 82)
FEEDBACK ARM ASSEMBLY
(KEY 84)

ARM ASSEMBLY
(KEY 91)
FEEDBACK ARM
TORSION SPRING
(KEY 93)

X0919

3. Loosen the screw that secures the arm assembly to the travel sensor shaft. Position the arm assembly so that the
outer surface is flush with the end of the travel sensor shaft.
4. Connect a current source to the instrument LOOP - and LOOP + terminals. Set the current source to any value
between 4 and 20 mA. Connect the handheld communicator to the TALK terminals.
5. Before beginning the travel sensor adjustment, set the instrument mode to Out Of Service and the protection to
None.
6. From the Calibrate menu, select Sensor Calibration, Travel Sensor. Follow the prompts on the handheld
communicator display to adjust the travel sensor counts to the value listed in table 4‐2.

52
Instruction Manual Calibration
D103785X012 February 2023

Note
In the next step, be sure the arm assembly outer surface remains flush with the end of the travel sensor shaft.

7. While observing the travel sensor counts, tighten the screw that secures the arm assembly to the travel sensor
shaft. Be sure the travel sensor counts remain within the tolerances listed in table 4‐2. Paint the screw to discourage
tampering with the connection.
8. Disconnect the handheld communicator and current source from the instrument.
9. Apply lubricant (key 63) to the pin portion of the arm assembly (key 91).
10. Replace the mounting bracket on the back of the instrument and reconnect the bias spring between the feedback
arm assembly and the arm assembly on the travel sensor shaft.
11. Install the remote feedback unit on the actuator.

Figure 4‐5. FIELDVUE DVC6025 Travel Sensor Arm/Housing Back Plane Alignment

BACK EDGE OF ARM


PARALLEL W/BACK
OF HOUSING

ARM ASSEMBLY

ARM ASSEMBLY PIN

TRAVEL
SENSOR SHAFT

BACK OF HOUSING
A7025

Analog Input Calibration


To calibrate the analog input sensor, connect a variable current source to the instrument LOOP+ and LOOP- terminals.
The current source should be capable of generating an output of 4 to 20 mA. Follow the prompts on the handheld
communicator display to calibrate the analog input sensor.
1. Set the current source to the target value shown on the display. The target value is the Input Range Low value. Press
OK.
2. The following message appears:

Use the Increase and Decrease


selections until the displayed
current matches the target.

Press OK when you have read this message.

53
Calibration Instruction Manual
February 2023 D103785X012

3. The value of the Analog Input appears on the display. Press OK to display the adjustment menu.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value.
Selecting large, medium, and small adjustments causes changes of approximately 0.4 mA, 0.04 mA, and 0.004 mA,
respectively.

If the displayed value does not match the current source, press OK, then repeat this step (step 4) to further adjust
the displayed value. When the displayed value matches the current source, select Done and go to step 5.
5. Set the current source to the target value shown on the display. The target value is the Input Range High value.
Press OK.
6. The following message appears:

Use the Increase and Decrease


selections until the displayed
current matches the target.

Press OK when you have read this message.


7. The value of the Analog Input appears on the display. Press OK to display the adjustment menu.
8. From the adjustment menu, select the direction and size of adjustment to the displayed value. If the displayed value
does not match the current source, press OK, then repeat this step (step 8) to further adjust the displayed value.
When the displayed value matches the current source, select Done and go to step 9.
9. Place the instrument In Service and verify that the analog input displayed matches the current source.

Relay Adjustment
Before beginning travel calibration, check the relay adjustment. Replace the instrument cover when finished.

Note
Relay B and C are not user‐adjustable.

Double‐Acting Relay
The double‐acting relay is designated by “Relay A” on a label affixed to the relay itself. For double‐acting actuators, the
valve must be near mid‐travel to properly adjust the relay. The handheld communicator will automatically position the
valve when Relay Adjust is selected.

Note
Care should be taken during relay adjustment as the adjustment disc may disengage if rotated too far.

Rotate the adjustment disc, shown in figure 4‐6, until the output pressure displayed on the handheld communicator is
between 50 and 70% of supply pressure. This adjustment is very sensitive. Be sure to allow the pressure reading to
stabilize before making another adjustment (stabilization may take up to 30 seconds or more for large actuators).

54
Instruction Manual Calibration
D103785X012 February 2023

If the low bleed relay option has been ordered stabilization may take approximately two minutes longer than the
standard relay.

Relay A may also be adjusted for use in single‐acting‐ direct applications. Rotate the adjustment disc as shown in figure
4‐6 for single‐acting direct operation.

Figure 4‐6. Relay A Adjustment (Shroud Removed for Clarity)

FOR SINGLE‐ACTING DIRECT


RELAYS: ROTATE ADJUSTMENT
DISC IN THIS DIRECTION UNTIL IT
CONTACTS THE BEAM
FOR DOUBLE‐ACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO DECREASE
OUTPUT PRESSURE

ADJUSTMENT DISC
FOR DOUBLE‐ACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO INCREASE
OUTPUT PRESSURE

W9034

Single‐Acting Relays

WARNING
For Instrument Level ODV only:
If the unused port is monitoring pressure, ensure that the pressure source conforms to ISA Standard 7.0.01 and does not
exceed the pressure supplied to the instrument.
Failure to do so could result in personal injury or property damage caused by loss of process control.

Single‐Acting Direct Relay

The single‐acting direct relay is designated by “Relay C” on a label affixed to the relay itself. Relay C requires no
adjustment.

Single‐Acting Reverse Relay

The single‐acting reverse relay is designated by “Relay B” on a label affixed to the relay itself. Relay B is calibrated at the
factory and requires no further adjustment.

55
Calibration Instruction Manual
February 2023 D103785X012

PST Calibration (ODV Instrument Level only)


This procedure permits you to run the Partial Stroke Calibration, which enables the Partial Stroke Test. It establishes
values for Partial Stroke Pressure Limit, Pressure Set Point and Pressure Saturation Time for End Point Pressure Control,
Travel Deviation Alert Point and Travel Deviation Time. The Partial Stroke Calibration also sets default values for max
travel movement, test speed, and test pause time.

Note
You must take the instrument out of service before running Partial Stroke Calibration.
Ensure that the instrument is put back in service after the completing the calibration procedure.

56
Instruction Manual Device Information, Alerts, and Diagnostics
D103785X012 February 2023

Section 5 Device Information, Alerts, and Diagnostics55


Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.

Overview
Handheld Communicator Overview (1)

Status & Primary Purpose Variables


The overview section provides basic information about the current state of the instrument and gives you access to the
current values of:
D Alert Status
D Communication Status
D Instrument Mode (In/Out of Service)
D Analog Input
D Setpoint
D Travel
D Supply Pressure
D Actuator Pressure(s)
D Travel/Pressure Control Configuration

Device Information
Device Information provides details about the instrument construction including:
D Tag Name
D Instrument Model Number
D Instrument Level (see table 5‐1)
D Device ID (unique number used to prevent the instrument from accepting commands intended for other
instruments)
D Serial Numbers
D Firmware, DD, and Hardware Revisions
D HART Universal Revision
D Write Protection (provides a procedure to enable/disable)
Table 5‐1. Functions Available for Instrument Level
Instrument Level Functions Available
HART Communicating: Communicates with a handheld communicator and ValveLink software. In addition,
HC provides: travel cutoffs and limits, minimum opening and closing times, input characterization (linear, equal
HC
percentage, quick opening, and custom), trending with ValveLink Solo, and the following alerts: travel deviation;
travel alert high, low, high high, and low low; drive signal; cycle counter; and travel accumulation.
Advanced Diagnostics: Includes all functions listed above plus (with ValveLink software) all offline diagnostic tests
AD
(dynamic error band, drive signal, step response, and valve signature) plus online trending
Performance Diagnostics: Includes all functions listed above plus all Performance Diagnostics online/in‐service
PD
valve testing (valve friction, electronics, and mechanical condition)
ODV Optimized Digital Valve: Includes all functions listed above plus partial stroke test and lead/lag set point filter

57
Device Information, Alerts, and Diagnostics Instruction Manual
February 2023 D103785X012

Service Tools
Handheld Communicator Service Tools (3)

Device Status
Instrument alerts, when enabled, detect many operational and performance issues that may be of interest. If there are
no alerts currently active, this display will be empty.

Alert Record
The DVC6000 HW2 will store 20 alerts. Once the alert record is full, no additional alerts will be stored until the record is
cleared.

Alert Reporting
In addition to on-board storage of alerts, the DVC6000 HW2 can report active alerts via HART Command 48 - Read
Additional Status. Refer to table 5‐2 for a summary of the default alert settings from the factory. Following is a detailed
description of the meaning of each alert.

Table 5‐2. Default Alert Settings


Name Alert Shutdown NE107 Category
Flash Integrity Failure Enabled(1) Disabled Failure
Minor Loop Sensor Failure Enabled(1) Disabled Failure
Reference Voltage Failure Enabled(1) Disabled Failure
Drive Current Failure Enabled(1) Disabled Failure
Critical NVM Failure Enabled(1) Disabled Failure
Temperature Sensor Failure Enabled(1) Disabled Failure
Pressure Sensor Failure Enabled(1) Disabled Failure
Travel Sensor Failure Enabled(1) Disabled Failure

Alert Record Not Empty Disabled Not Available Maintenance


Calibration in Progress Disabled Not Available Function Check
Diagnostics in Progress Disabled Not Available Function Check
Pressure Fallback Active Enabled Not Available Out of Specification
Autocal in Progress Disabled Not Available Function Check

Non-Critical NVM Enabled(1) Disabled Failure


Cycle Counter High Disabled Not Available Maintenance
Travel Accumulator High Disabled Not Available Maintenance
Instrument Time is Approximate Disabled Not Available Not Available
Alert Record Full Disabled Not Available Maintenance
Offline / Failed Enabled Not Available Failure
Diagnostic Data Available Disabled Not Available Not Available
Supply Pressure Low Enabled Not Available Out of Specification
End Point Pressure Deviation Enabled Not Available Out of Specification
Supply Pressure High Enabled Not Available Maintenance
1. These default alert configurations cannot be changed.
-continued-

58
Instruction Manual Device Information, Alerts, and Diagnostics
D103785X012 February 2023

Table 5‐2. Default Alert Settings (continued)


Name Alert Shutdown NE107 Category
Integrator Saturated High Disabled Not Available Out of Specification
Integrator Saturated Low Disabled Not Available Out of Specification

Travel Alert Low Disabled Not Available Not Available


Travel Alert Low-Low Disabled Not Available Not Available
Travel Alert High Disabled Not Available Not Available
Travel Alert High-High Disabled Not Available Not Available
Travel Deviation Enabled Not Available Out of Specification
Travel Limit/Cutoff High Disabled Not Available Not Available
Travel Limit/Cutoff Low Disabled Not Available Not Available
Drive Signal Alert Enabled Not Available Out of Specification

Output Circuit Error Enabled Not Available Failure


Port A Overpressurized Enabled Disabled Failure

Alert Record Full is active when the alert record is full. Additional alerts that are detected will not be saved to the alert
record until the alert record is cleared.

Alert Record Not Empty is active when there are one or more alerts stored in the alert record.

Autocal in Progress is active when auto calibration is in progress.

Calibration in Progress is active when calibration is in progress.

Critical NVM Failure is active if there is a failure associated with NVM that is critical for instrument operation. To clear
the alert, restart the instrument. If the alert persists, replace the printed wiring board assembly.

Cycle Counter High is active if the Cycle Counter exceeds the Cycle Count Alert Point. The Cycle Count records the
number of times the travel changes direction when it is outside of the deadband. To clear the alert, set the Cycle
Counter to a value less than the alert point. See figure 5‐2.

Diagnostic Data Available is active when diagnostic data has been collected and is being stored in the instrument.

Diagnostics in Progress is active when a diagnostic test is in progress.

Drive Current Failure is active when the drive current to the I/P converter is not flowing as expected. If this alert occurs,
check the connection between the I/P converter and the printed wiring board assembly. Try removing the I/P
converter and reinstalling it. If the alert does not clear, replace the I/P converter or the printed wiring board assembly.

Drive Signal Alert monitors the drive signal and calibrated travel. If one of the following conditions exists for more than
20 seconds, the alert is set.

For the case where Zero Power Condition is defined as closed:


Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%

For the case where Zero Power Condition is defined as open:


Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%

59
Device Information, Alerts, and Diagnostics Instruction Manual
February 2023 D103785X012

End Point Pressure Deviation is active if the instrument is in pressure control and the pressure is not tracking the set
point within the configured deviation allowance.

Field Device Malfunction is active if the pressure, position, or temperature sensors are providing invalid readings.

Flash Integrity Failure is active if there is a failure associated with flash ROM (read only memory). To clear the alert,
restart the instrument. If the alert persists, replace the printed wiring board assembly.

Instrument Time is Approximate is active if the instrument has been powered down since the last time the instrument
clock was set. To clear the alert, reset the instrument time.

Integrator Saturated High is active if the instrument integrator is saturated at the high extreme.

Integrator Saturated Low is active if the instrument integrator is saturated at the low extreme.

Internal Sensor Out of Limits is active if there is a problem with either the pressure sensor or the printed wiring board
assembly.

Loop Current Validation Alert is active if the loop current is significantly out of range, or if there is a problem with the
analog circuit electronics. To clear the alert, restart the instrument with the loop current verified to be in the 4-20 mA
range. If the alert persists, replace the printed wiring board.

Note
If the control system is known to output current 24 mA or above, Shutdown on Loop Current Validation should not be enabled.

Minor Loop Sensor Failure is active if the pneumatic relay position reading is outside the valid range. If the alert
persists, replace the printed wiring board.

Non-Critical NVM is active if there is a failure associated with NVM (nonvolatile memory) that is not critical for
instrument operation. To clear the alert, restart the instrument. If the alert persists, replace the printed wiring board
assembly.

Offline / Failed is active if a shutdown alert has put the device in a failed state and is therefore not controlling the input.
Examine the alert(s) that caused the shutdown.

Output Circuit Error is active if the output circuit is not responding. Verify that the DIP switch on the main electronics
matches the configuration of the OUT terminals. If the DIP switch setting is correct and the alert is still active, replace
the main electronics.

Port A Overpressurized requires that both the Port A Overpressurized Alert and the Port A Output Pressure Limit are
enabled and applies to single acting direct applications only. The alert is active if the output pressure from Port A of the
DVC6000 HW2 exceeds the configured pressure limit setting. Check the supply pressure regulator for damage and
verify its pressure set point.

Pressure Fallback Active is active when the instrument has detected a problem with the travel feedback and is now
controlling the output like an I/P transducer.

Pressure Sensor Failure is active if any of the 3 pressure sensor readings (output A, output B, supply) are outside the
range of 24.0 to 125.0% of the calibrated pressure for more than 60 seconds. If this alert is active, check the
instrument supply pressure, ensure the printed wiring board assembly is properly mounted onto the module base
assembly, and ensure the pressure sensor o-rings are properly installed. If the alert persists after restarting the
instrument, replace the printed wiring board assembly.

60
Instruction Manual Device Information, Alerts, and Diagnostics
D103785X012 February 2023

Reference Voltage Failure is active if there is a failure associated with the internal voltage reference. If this alert is
active, replace the printed wiring board assembly.
Supply Pressure High is active if the supply pressure falls above the supply pressure high alert point.
Supply Pressure Low is active if the supply pressure falls below the supply pressure low alert point.
Temperature Sensor Failure is active when the instrument temperature sensor fails, or the sensor reading is outside of
the range of -60 to 100°C (-76 to 212°F). The temperature reading is used internally for temperature compensation of
inputs. If this alert is active, restart the instrument. If the alert persists, replace the printed wiring board assembly.
Travel Accumulator High is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point. The Travel
Accumulator totalizes the travel of the valve when the deadband is exceeded. To clear the alert, set the Travel
Accumulator to a value less than the alert point. See figure 5‐2.
Travel Alert Hi is active when the Travel exceeds the Travel Alert Hi Point. Once the alert is active, the alert will clear
when the Travel falls below the Travel Alert Hi Point minus the Travel Alert Deadband. See figure 5‐1.

Note
The Travel Alert Hi Hi and Travel Alert Lo Lo points are used to calculate the stroke time in the event of a demand. The values are
typically set to 99% and 1% respectively, however it is not necessary to enable the alert. Stroke time can be read from the device
with ValveLink software.

Travel Alert Hi-Hi is active when the Travel exceeds the Travel Alert Hi Hi Point. Once the alert is active, the alert will
clear when the Travel falls below the Travel Alert Hi Hi Point minus the Travel Alert Deadband. See figure 5‐1.
Travel Alert Lo is active when the Travel is below the Travel Alert Lo Point. Once the alert is active, the alert will clear
when the Travel exceeds the Travel Alert Lo Point plus the Travel Alert Deadband. See figure 5‐1.
Travel Alert Lo-Lo is active when the Travel is below the Travel Alert Lo Point. Once the alert is active, the alert will clear
when the Travel exceeds the Travel Alert Lo Point plus the Travel Alert Deadband. See figure 5‐1.
Travel Limit/Cutoff Hi is active when the Travel exceeds the Hi Limit/Cutoff Point.
Travel Limit/Cutoff Lo is active when the Travel falls below the Lo Limit/Cutoff Point.
Travel Deviation— If the difference between the Travel Target and the Travel exceeds the Travel Deviation Alert Point
for more than the Travel Deviation Time, the Travel Deviation Alert is active. It remains active until the difference
between the travel target and the Travel is less than the Travel Deviation Alert Point minus the Travel Alert Deadband.
See figure 5‐1.
Travel Sensor Failure is active if the sensed travel is outside the range of 25.0 to 125.0% of calibrated travel. If this alert
is active, check the instrument mounting. Also, check that the electrical connection from the travel sensor is properly
plugged into the printed wiring board assembly. After restarting the instrument, if the alert persists, troubleshoot the
printed wiring board assembly or travel sensor.
Variable out of Range is active if one or more of the measured analog sensor readings (loop current, pressure,
temperature, or travel) is saturated or reading out of its configured range. The condition may be due to improper
configuration or physical setup and not be due to a sensor malfunction.

Deadband Principle of Operation


The deadband is the percent (%) of ranged travel around a travel reference point where no change in alert status will
occur. This prevents the alert from toggling on and off when operating near the alert point.

61
Device Information, Alerts, and Diagnostics Instruction Manual
February 2023 D103785X012

The Travel Alert Deadband applies to the Travel Deviation Alert as well as the Travel Alert Hi, Lo, Hi Hi, and Lo Lo.
Figure 5‐1 illustrates the principle behind setting and clearing a Travel Alert Hi. The alert is set when the travel exceeds
the alert point, and is cleared when it falls below the deadband.

Figure 5‐1. Travel Alert Deadband

ALERT IS SET

TRAVEL ALERT
HIGH POINT
VALVE POSITION

TRAVEL ALERT
DEADBAND

ALERT IS CLEARED

TIME
A6532

The Cycle Counter and Travel Accumulator Deadband applies to both the Cycle Count High Alert and the Travel
Accumulator High Alert. The deadband establishes a zone around a travel reference point. The travel reference point
gets reestablished to the point of travel reversal that occurs outside of the deadband. The deadband must be
exceeded before a change in travel direction will be counted as a cycle and the accumulated travel (up to the point of
travel reversal) is added to the total accumulation. See figure 5‐2.

Figure 5‐2. Cycle Counter and Travel Accumulator Deadband Example (set at 10%)

DEADBAND EXCEEDED, NEW


REFERENCE POINT ESTABLISHED

DEADBAND
REFERENCE POINT DEADBAND (+/- 5%)
VALVE POSITION

TIME
DEADBAND

DARK SEGMENTS REPRESENT THE AMOUNT OF TRAVEL


THAT WILL BE ADDED TO THE TRAVEL ACCUMULATOR
E1473
CYCLE COUNTER INCREMENTS

62
Instruction Manual Device Information, Alerts, and Diagnostics
D103785X012 February 2023

Diagnostics
Stroke Valve
Follow the prompts on the handheld communicator display to select from the following:

D Done—Select this if you are done. All ramping is stopped when DONE is selected.

D Ramp Open—ramps the travel toward open at the rate of 1.0% per second of the ranged travel.

D Ramp Closed—ramps the travel toward closed at the rate of 1.0% per second of the ranged travel.

D Ramp to Target—ramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.

D Step to Target—steps the travel to the specified target.

Partial Stroke Test

Note
Partial Stroke Test is only available for instrument level ODV.

The Partial Stroke Test allows DVC6000 HW2 digital valve controllers with instrument level ODV to perform a Valve
Signature type of test while the instrument is in service and operational. In some applications, it is important to be able
to exercise and test the valve to verify that it will operate when commanded. This feature allows the user to partially
stroke the valve while continually monitoring the input signal. If a demand arises, the test is aborted and the valve
moves to its commanded position. The partial stroke valve travel is configurable between 1 and 30% maximum travel,
in 0.1% increments. Data from the last partial stroke test is stored in the instrument memory for retrieval by ValveLink
software.

The Partial Stroke Test allows you to perform a partial, 10%, stroke test (standard) or a custom stroke test. With the
custom stroke test, the stroke may be extended up to 30%. Be sure to check plant guidelines before performing a
custom stroke test. The purpose of this test is to ensure that the valve assembly moves upon demand.

A partial stroke test can be initiated when the valve is operating at either 4 or 20 mA (point‐to‐point mode).

When enabled, a partial stroke test may be initiated by the device (as a scheduled, auto partial stroke test), a remote
pushbutton located in the field or at the valve, a handheld communicator, or ValveLink software.

For information on configuring the Partial Stroke Test, see Partial Stroke Variables in the Detailed Setup section.

D Automatic (Scheduled)

The Auto Partial Stroke Test allows the partial stroke test to be scheduled by the DVC6000 HW2. The test is scheduled
in number of hours between tests. Any power cycle will reset the test clock timer.

D Local Pushbutton

A partial stroke test command may be sent to the digital valve controller using a set of contacts wired to the auxiliary
+/- terminals. To perform a test, the contacts must be closed for 3 to 5 seconds and then opened. To abort the test,

63
Device Information, Alerts, and Diagnostics Instruction Manual
February 2023 D103785X012

close the contacts for 1 second. The last set of diagnostic data is stored in the instrument memory for later retrieval via
ValveLink software.

D Handheld Communicator
1. Connect the handheld communicator to the LOOP terminals on the DVC6005 HW2 base unit and turn on.
2. From the Online menu, select Service Tools > Diagnostics > Partial Stroke Test.
3. Select either Standard (10%) or Custom. With the Custom Stroke Test, the stroke may be entered up to 30% with
configurable stroking speed and pause time.
4. The currently configured Stroke, Stroking Speed, and Pause Time is displayed. Choose “Yes” to run the test using
these values. Choose “No” to modify the values. The default value for Stroke Speed is 0.25%/second.
5. The valve begins to move and the actual travel reported by the digital valve controller is displayed on the handheld
communicator.
6. Once the valve has reached the endpoint, check that the valve has reached the desired set point. The valve should
return to its original position.
D ValveLink Software

Run the Partial Stroke diagnostic.

Solenoid Valve Health Monitoring


Solenoid valve health monitoring requires the following setup:

D Single-acting actuator

D Solenoid valve installed between the DVC6000 HW2 pressure output and the actuator

D Unused output pressure port of the DVC6000 HW2 connected between the solenoid and the actuator, close to the
actuator

D Relay configured as “special application”

D Triggered profile enabled and the “Pressure Differential” trigger event selected.

If the solenoid valve is wired directly to the logic solver, the following steps can be used to test the solenoid valve.
1. Momentarily interrupt the power to the solenoid valve through the Logic Solver (typically 100 to 200 milliseconds).
The duration of the interruption should be short enough so that the safety valve travel does not move, but long
enough to so that a pressure drop across the solenoid valve is detected.
2. Properly configured, data collection will occur automatically and will be stored onboard the DVC6000 HW2.
3. With ValveLink software, upload the diagnostic data from the triggered profile menu.
4. Examine the graph and observe that there was a change in the pressure reading downstream of the solenoid.

64
Instruction Manual Device Information, Alerts, and Diagnostics
D103785X012 February 2023

Variables
Handheld Communicator Service Tools > Variables (3-4)

The Variables section provides current values of the instrument variables. Below is a list of the variables available for
viewing:
D Write Protection (also provides a procedure to enable/disable)
D Instrument Mode (also provides a procedure to place in/out of service)
D Analog Input
D Setpoint
D Travel
D Drive Signal
D Input Characterization (also provides a procedure to modify)
D Cycle Counter
D Travel Accumulator
D Supply Pressure
D Actuator Pressure(s)
D Travel/Pressure Control Configuration (also provides a procedure to modify)
D Control Mode (also provides a procedure to modify)
D Instrument Temperature
D Travel Counts (this is the raw travel sensor reading used for advanced adjustments)
D Maximum Recorded Temperature
D Minimum Recorded Temperature
D Number of Power Ups
D Days Powered Up

65
Device Information, Alerts, and Diagnostics Instruction Manual
February 2023 D103785X012

66
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Section 6 Maintenance and Troubleshooting66


The DVC6000 HW2 digital valve controller enclosure is rated Type 4X and IP66, therefore periodic cleaning of internal
components is not required. If the DVC6000 HW2 is installed in an area where the exterior surfaces tend to get heavily
coated or layered with industrial or atmospheric contaminants, it is recommended that the vent (key 52) be
periodically removed and inspected to ensure there is no partial or full obstruction. If the vent appears to be partially or
fully obstructed, it must be cleaned or replaced. Lightly brush the exterior of the vent to remove contaminants and run
a mild water/detergent solution through the vent to ensure it is free of any obstruction. Allow the vent to dry before
reinstalling.

WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.

WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.

WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing
any maintenance procedures on the DVC6000 HW2 digital valve controller:
D Always wear protective clothing, gloves, and eyewear.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
from both sides of the valve.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not
applying force to the valve stem; this will allow for the safe removal of the stem connector.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply:
D Remove electrical power before removing the housing cap. Personal injury or property damage from fire or explosion
may result if power is not disconnected before removing the cap.
D Remove electrical power before disconnecting any of the pneumatic connections.
D When disconnecting any of the pneumatic connections or any pressure retaining part, natural gas will seep from the
unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result
from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken.
Preventive measures may include, but are not limited to, one or more of the following: Remote venting of the unit,
re‐evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources.
D Ensure that all caps and covers are correctly installed before putting this unit back into service. Failure to do so could
result in personal injury or property damage from fire or explosion.

67
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

WARNING
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 1‐2. It may also impair operations and the intended function of the device,
and could cause personal injury and property damage.

Note
If the feedback arm (key 79) or feedback arm assembly (key 84) is removed from the digital valve controller, the travel sensor must
be recalibrated.

Because of the diagnostic capability of the DVC6000 HW2, predictive maintenance is available through the use of
ValveLink software. Using the digital valve controller, valve and instrument maintenance can be enhanced, thus
avoiding unnecessary maintenance. For information on using the ValveLink software, refer to the ValveLink software
online help.

Module Base Maintenance


The digital valve controller contains a module base consisting of the I/P converter, printed wiring board assembly, and
pneumatic relay. The module base may be easily replaced in the field without disconnecting field wiring or tubing.

Tools Required
Table 6‐1 lists the tools required for maintaining the DVC6000 HW2 digital valve controller.

Table 6‐1. Tools Required


Tool Size Component
Phillips Screwdriver Relay, printed wiring board assembly, and cover screws
Hex key 5 mm Terminal box screw
Hex key 1.5 mm Terminal box cover screw
Hex key 2.5 mm I/P converter screws
Hex key 5 mm Travel sensor screws
Hex key 6 mm Module base screws
Open‐end wrench 1/2‐inch Connector Arm screw (DVC6015)
Hex key 9/64‐inch Feedback arm screw
Open‐end wrench 7/16‐inch DVC6015 mounting bolts
Hex key 3/16‐inch DVC6025 mounting bolts

Removing the Module Base


To remove the DVC6005 HW2 module base, perform the following steps. Refer to figure 7‐2 for key number locations.

WARNING
To avoid personal injury or equipment damage from bursting of parts, turn off the supply pressure to the digital valve
controller and bleed off any excess supply pressure before attempting to remove the module base assembly from the
housing.

68
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

1. For sliding‐stem applications only, a protective shield for the feedback linkage is attached to the side of the module
base assembly as shown in figure 6‐1. Remove this shield and keep for reuse on the replacement module. The
replacement module will not have this protective shield.

Figure 6‐1. Protective Shield for Feedback Linkage


FEEDBACK ARM EXTENSION,
BIAS SPRING

SHIELD

X0908

2. Unscrew the four captive screws in the cover (key 43) and remove the cover from the module base (key 2).
3. Using a 6 mm hex socket wrench, loosen the three‐socket head screws (key 38). These screws are captive in the
module base by retaining rings (key 154).

Note
The module base is linked to the housing by two cable assemblies. Disconnect these cable assemblies after you pull the module
base out of the housing.

4. Pull the module base straight out of the housing (key 1). Once clear of the housing, swing the module base to the
side of the housing to gain access to the cable assemblies.
5. The base unit has two cable assemblies, shown in figure 6‐2, which connect the module base, via the printed wiring
board assembly, to the travel sensor and the terminal box. Disconnect these cable assemblies from the printed
wiring board assembly on the back of the module base.

69
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

Figure 6‐2. Printed Wiring Board Cable Connections

TERMINAL BOX

REMOTE MODULE BASE


TERMINAL BOX ASSEMBLY

HOUSING CABLE TO REMOTE PRINTED WIRING


CABLE TO TERMINAL BOX BOARD ASSEMBLY
X0921
TERMINAL BOX

Replacing the Module Base


To replace the DVC6005 HW2 module base perform the following steps. Refer to figure 7‐2 for key number locations.

NOTICE

To avoid affecting performance of the instrument, take care not to damage the module base seal or guide surface. Do not
bump or damage the bare connector pins on the PWB assembly. Damaging either the module base or guide surface may
result in material damage, which could compromise the instruments ability to maintain a pressure seal.

Note
To avoid affecting performance of the instrument, inspect the guide surface on the module and the corresponding seating area in
the housing before installing the module base assembly. These surfaces must be free of dust, dirt, scratches, and contamination.
Ensure the module base seal is in good condition. Do not reuse a damaged or worn seal.

1. Ensure the module base seal (key 237) is properly installed in the housing (key 1). Ensure the O‐ring (key 12) is in
place on the module base assembly.
2. Connect the terminal box connector to the PWB assembly (key 50). Orientation of the connector is required.
3. Connect the travel sensor connector to the PWB assembly. Orientation of the connector is required.
4. Insert the module base (key 2) into the housing (key 1).
5. Install three socket head screws (key 38) in the module base into the housing. If not already installed, press three
retaining rings (key 154) into the module base. Evenly tighten the screws in a crisscross pattern to a final torque of
16 NSm (138 lbfSin).

70
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

NOTICE

Disruption of process control can result if the cable assemblies/wiring are damaged when attaching the cover to the
module base assembly.
Ensure that the cable assemblies/ wiring are positioned in the cavity of the module base so they do not get compressed or
damaged when attaching the cover to the module base assembly in step 6.

6. Attach the cover (key 43) to the module base assembly.


7. For sliding‐stem applications only, install the protective shield onto the side of the replacement module base
assembly (refer to figure 6‐1).

Submodule Maintenance
The base unit's module base contains the following submodules: I/P converter, PWB assembly, and pneumatic relay. If
problems occur, these submodules may be removed from the module base and replaced with new submodules. After
replacing a submodule, the module base may be put back into service.

NOTICE

Exercise care when performing maintenance on the module base. Reinstall the cover to protect the I/P converter and
gauges when servicing other submodules.
In order to maintain accuracy specifications, do not strike or drop the I/P converter during submodule maintenance.

I/P Converter
Refer to figure 7‐2 for key number locations. The I/P converter (key 41) is located on the front of the module base.

Note
After I/P converter submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.

Replacing the I/P Filter


A screen in the supply port beneath the I/P converter serves as a secondary filter for the supply medium. To replace this
filter, perform the following procedure:
1. Remove the I/P converter (key 41) and shroud (key 169) as described in the Removing the I/P Converter procedure.
2. Remove the screen (key 231) from the supply port.

71
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

3. Install a new screen in the supply port as shown in figure 6‐3.


4. Inspect the O‐ring (key 39) in the I/P output port; if necessary, replace it.
5. Reinstall the I/P converter (key 41) and shroud (key 169) as described in the Replacing the I/P Converter procedure.

Figure 6‐3. I/P Filter Location

O‐RING LOCATED W8072

IN I/P CONVERTER SCREEN (FILTER) LOCATED IN I/P


OUTPUT PORT CONVERTER SUPPLY PORT

Removing the I/P Converter


1. Remove the front cover (key 43), if not already removed.
2. Refer to figure 6‐4. Using a 2.5 mm hex socket wrench, remove the four socket‐head screws (key 23) that attach the
shroud (key 169) and I/P converter (key 41) to the module base (key 2).
3. Remove the shroud (key 169); then pull the I/P converter (key 41) straight out of the module base (key 2). Be
careful not to damage the two electrical leads that come out of the base of the I/P converter.
4. Ensure that the O‐ring (key 39) and screen (key 231) stay in the module base and do not come out with the I/P
converter (key 41).

Replacing the I/P Converter


1. Refer to figure 6‐3. Inspect the condition of the O‐ring (key 39) and screen (key 231) in the module base (key 2).
Replace them, if necessary. Apply silicone lubricant to the O‐rings.
2. Ensure the two boots (key 210) shown in figure 6‐4 are properly installed on the electrical leads.
3. Install the I/P converter (key 41) straight into the module base (key 2), taking care that the two electrical leads feed
into the guides in the module base. These guides route the leads to the printed wiring board assembly submodule.
4. Install the shroud (key 169) over the I/P converter (key 41).
5. Install the four socket‐head screws (key 23) and evenly tighten them in a crisscross pattern to a final torque of
1.6 NSm (14 lbfSin).
6. After replacing the I/P converter, calibrate travel or perform touch‐up calibration to maintain accuracy
specifications.

72
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Figure 6‐4. I/P Converter

SHROUD
(KEY 169)

I/P CONVERTER SOCKET‐HEAD


(KEY 41) SCREWS (4)
(KEY 23)

BOOTS
(KEY 210)
W9328

PWB (Printed Wiring Board) Assembly


Refer to figure 7‐2 for key number locations. The PWB assembly (key 50) is located on the back of the module base
assembly (key 2).

Note
If the PWB assembly submodule is replaced, calibrate and configure the digital valve controller to maintain accuracy specifications.

Removing the Printed Wiring Board Assembly


1. Separate the module base from the housing by performing the Removing the Module Base procedure.
2. Remove three screws (key 33).
3. Lift the PWB assembly (key 50) straight out of the module base (key 2).
4. Ensure that the O‐rings (key 40) remain in the pressure sensor bosses on the module base assembly (key 2) after the
PWB assembly (key 50) has been removed.

Replacing the PWB Assembly and Setting the DIP Switch


1. Apply silicone lubricant to the pressure sensor O‐rings (key 40) and install them on the pressure sensor bosses in the
module base assembly.
2. Properly orient the PWB assembly (key 50) as you install it into the module base. The two electrical leads from the
I/P converter (key 41) must guide into their receptacles in the PWB assembly and the pressure sensor bosses on the
module base must fit into their receptacles in the PWB assembly.
3. Push the PWB assembly (key 50) into its cavity in the module base.
4. Install and tighten three screws (key 33) to a torque of 1 NSm (10.1 lbfSin).

73
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

5. Set the DIP switch on the PWB assembly according to table 6‐2. On units that have the optional 4-20 mA position
transmitter or switch hardware installed, set the Transmitter or Switch option according to table 6‐3.

Table 6‐2. DIP Switch Configuration(1)


Switch Label Operational Mode DIP Switch Position
PT-PT 4­20 mA Point­to­Point Loop LEFT
Multi 24 VDC Multi­Drop Loop RIGHT
1. Refer to figure 6‐5 for switch location.

Table 6‐3. Output Switch Configuration(1)


Switch Label/Function DIP Switch Position
Transmitter LEFT
Switch RIGHT
1. Refer to figure 6‐5 for switch location.

Figure 6‐5. Printed Wiring Board (PWB) Connections and Settings

TRANSMITTER/SWITCH
SELECTION

TRAVEL SENSOR TRAVEL SENSOR


CONNECTOR CONNECTOR

TERMINAL BOX
TERMINAL BOX CONNECTOR
CONNECTOR

OPERATIONAL
OPERATIONAL
MODE SELECTION
MODE SELECTION

X0463 X0432

Note
For the digital valve controller to operate with a 4 to 20 mA control signal, be sure the DIP switch is in the point‐to‐point loop
position.

6. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
7. Setup and calibrate the DVC6005 HW2 base unit.

74
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Pneumatic Relay
Refer to figure 7‐2 for key number locations. The pneumatic relay (key 24) is located on the front of the module base.

Note
After relay submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.

Removing the Pneumatic Relay


1. Loosen the four screws that attach the relay (key 24) to the module base. These screws are captive in the relay.
2. Remove the relay.

Replacing the Pneumatic Relay


1. Visually inspect the holes in the module base to ensure they are clean and free of obstructions. If cleaning is
necessary, do not enlarge the holes.
2. Apply silicone lubricant to the relay seal and position it in the grooves on the bottom of the relay as shown in
figure 6‐6. Press small seal retaining tabs into retaining slots to hold relay seal in place.
3. Position the relay (with shroud) on the module base. Tighten the four screws, in a crisscross pattern, to a final
torque of 2 NSm (20.7 lbfSin).
4. Using the handheld communicator, verify that the value for the parameter Relay matches the relay type installed.
5. After replacing the relay and verifying the relay type, calibrate travel or perform touch‐up calibration to maintain
accuracy specifications

Figure 6‐6. Pneumatic Relay Assembly

RELAY SEAL
W8074

75
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

Gauges, Pipe Plugs, or Tire Valves


Depending on the options ordered, the DVC6000 HW2 will be equipped with either gauges (key 47), pipe plugs (key
66), or tire valves (key 67). Single‐acting instruments will also have a screen (key 236, figure 7‐3). These are located on
the top of the module base next to the relay.

Perform the following procedure to replace the gauges, tire valves, or pipe plugs. Refer to figure 7‐2 for key number
locations.
1. Remove the front cover (key 43).
2. Remove the gauge, pipe plug, or tire valve as follows:
For gauges (key 47), the flats are on the gauge case. Use a wrench on the flats of the gauge to remove the gauge from
the module base. For double‐acting instruments, to remove the supply gauge remove one of the output gauges.

For pipe plugs (key 66) and tire valves (key 67), use a wrench to remove these from the module base.
3. Apply pipe thread sealant (key 64) to the threads of the replacement gauges, pipe plugs, or tire valves.
4. Using a wrench, screw the gauges, pipe plugs, or tire valves into the module base.

Terminal Box
WARNING
Refer to the Maintenance WARNING at the beginning of this section.

Refer to figure 7‐2 for key number locations.

The terminal box is located on the housing and contains the terminal strip assembly for field wiring connections.

Removing the Terminal Box


WARNING
To avoid personal injury or property damage caused by fire or explosion, remove power to the instrument before removing
the terminal box cover in an area which contains a potentially explosive atmosphere or has been classified as hazardous.

1. Loosen the set screw (key 58) in the cap (key 4) so that the cap can be unscrewed from the terminal box.
2. After removing the cap (key 4), note the location of field wiring connections and disconnect the field wiring from
the terminal box.
3. Separate the module base from the housing by performing the Removing the Module Base procedure.
4. Remove the screw (key 72). Pull the terminal box assembly straight out of the housing.
5. Remove two wire retainers (key 44), internal and external to the terminal box.

76
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Replacing the Terminal Box

Note
Inspect all O‐rings for wear and replace as necessary.

1. Install two wire retainers (key 44), internal and external to the terminal box.
2. Apply silicone lubricant to the O‐ring (key 34) and install the O‐ring over the stem of the terminal box.
3. Insert the terminal box assembly stem into the housing until it bottoms out. Position the terminal box assembly so
that the hole for the screw (key 72) in the terminal box aligns with the threaded hole in the housing. Install the
screw (key 72).
4. Connect the terminal box connector to the PWB assembly (key 50). Orientation of the connector is required.
5. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
6. Reconnect the field wiring as noted in step 2 in the Removing the Terminal Box procedure.
7. Apply silicone lubricant to the O‐ring (key 36) and install the O‐ring over the 2‐5/8 inch threads of the terminal box.
Use of a tool is recommended to prevent cutting the O‐ring while installing it over the threads.
8. Apply lubricant (key 63) to the 2‐5/8 inch threads on the terminal box to prevent seizing or galling when the cap is
installed.
9. Screw the cap (key 4) onto the terminal box until no gap remains.
10. Install the set screw (key 58) into the cap (key 4). Secure the cap by engaging the set screw.
11. Apply sealant (key 64) to the conduit entrance plug (key 62) and install it into the unused conduit entry of the
terminal box.

Travel Sensor
WARNING
Refer to the Maintenance WARNING at the beginning of this section.

Replacing the travel sensor requires removing the remote feedback unit from the actuator.

WARNING
To avoid personal injury or property damage caused by fire or explosion, remove power to the instrument before removing
the travel sensor assembly in an area which contains a potentially explosive atmosphere or has been classified as
hazardous.

77
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

Disassembly

Note
If the feedback arm (key 79) or feedback arm assembly (key 84) is removed from the digital valve controller, the travel sensor
assembly [i.e. potentiometer/bushing assembly (key 223)] must be recalibrated.

DVC6015 Remote Feedback Unit


Refer to figure 7‐4 for key number locations.
1. Remove piping and fittings from the instrument.
2. Disconnect the adjustment arm from the connector arm and the feedback arm, see figure 6‐7.
3. Remove the instrument from the actuator.
4. Loosen the screw (key 80) that secures the feedback arm (key 79) to the travel sensor shaft.
5. Remove the feedback arm (key 79) from the travel sensor shaft.
6. Disconnect the three travel sensor assembly wires from the terminals.
7. Remove the screw (key 72) that fastens the travel sensor assembly to the housing.
8. Pull the travel sensor assembly (key 223) straight out of the housing.

Figure 6‐7. FIELDVUE DVC6015 Adjustment Arm

FEEDBACK ARM (KEY 79)

ADJUSTMENT ARM
CONNECTOR ARM

X0910

78
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

DVC6025 Remote Feedback Unit


Refer to figure 7‐5 for key number locations.
1. Remove piping and fittings from the instrument.
2. Remove the instrument from the actuator.
3. Disconnect the bias spring (key 82) from the feedback arm assembly (key 84) and the arm assembly (key 91).
Remove the mounting bracket (key 74) from the back of the digital controller. If the torsion spring (key 93) needs to
be replaced, ensure that the shaft on which it is installed is smooth and free of rough spots. Replace the entire
feedback arm assembly if necessary.
4. Loosen the screw (key 80) that secures the arm assembly to the travel sensor assembly shaft.
5. Remove the arm assembly (key 91) from the travel sensor assembly shaft.
6. Disconnect the three travel assembly wires from the terminals.
7. Remove the screw (key 72) that fastens the travel sensor assembly to the housing.
8. Pull the travel sensor assembly (key 223) straight out of the housing.

DVC6035 Remote Feedback Unit


Refer to figure 7‐6 for key number locations.
1. Remove piping and fittings from the instrument.
2. Remove the instrument from the actuator. Loosen the screw (key 80) that secures the feedback arm (key 79) to the
travel sensor shaft. Remove the feedback arm from the travel sensor assembly shaft.
3. Disconnect the three travel sensor assembly wires from the terminals.
4. From within the housing, unscrew the travel sensor assembly (key 223) from the housing.

Assembly

Note
If the feedback arm (key 79) or feedback arm assembly (key 84) is removed from the digital valve controller, the travel sensor
assembly must be recalibrated.

DVC6015 Remote Feedback Unit


Refer to figure 7‐4 for key number locations.
1. Insert the travel sensor assembly (key 223) into the housing (key 1). Secure the assembly with screw (key 72).
2. Connect the travel sensor assembly wires to the terminals as follows:
red  terminal 1
white  terminal 2
black  terminal 3
3. Loosely assemble the bias spring (key 78), screw (key 80), plain washer (key 163), and nut (key 81) to the feedback
arm (key 79), if not already installed.
4. Attach the feedback arm (key 79) to the travel sensor assembly shaft.

79
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

5. Using a handheld communicator, perform the appropriate Travel Sensor Adjust procedure in the Calibration
section. Install the remote feedback unit on the actuator when the travel sensor adjustment is complete.

Note
If a handheld communicator is not available, perform the Travel Sensor Adjustment with Multimeter procedure below.

Travel Sensor Adjustment with a Multimeter (DVC6015)

1. Align the feedback arm (key 79) to the housing (key 1) by inserting the alignment pin (key 46) through the hole
marked “A” on the feedback arm. Fully engage the alignment pin into the tapped hole in the side of the housing.
Position the feedback arm so that the surface is flush with the end of the travel sensor shaft.
2. Connect a multimeter set to a resistance range of 50,000 ohms. Measure the resistance between terminals 1 and 3
of the remote feedback unit. Refer to figure 6‐8 for terminal location. The resistance should be between 40,000 and
50,000 ohms.
3. Multiply the result in step 2 by 0.046 to get a calculated resistance. The calculated resistance should be in the range
of 1840 to 2300 ohms.
4. Re‐range the multimeter to a resistance of 3000 ohms between terminals 2 and 3 of the remote feedback unit.
Refer to figure 6‐8 for terminal location.
5. Adjust the travel sensor shaft to obtain the calculated resistance determined in step 3, $100 ohms.

Note
In the next step, be sure the feedback arm surface remains flush with the end of the travel sensor shaft.

6. While observing the resistance, tighten the screw (key 80) to secure the feedback arm to the travel sensor shaft. Be
sure the resistance reading remains at the calculated resistance determined in step 3, $100 ohms. Paint the screw
to discourage tampering with the connection.
7. Disconnect the multimeter from the travel sensor connector.
8. Travel sensor adjustment is complete. Install the remote feedback unit on the actuator.

DVC6025 Feedback Unit


Refer to figure 7‐5 for DVC6025 key number locations.

1. Insert the travel sensor assembly (key 223) into the housing. Secure the assembly with screw (key 72).
2. Connect the travel sensor assembly wires to the terminals as follows:
red  terminal 1
white  terminal 2
black  terminal 3
3. Loosely assemble the screw (key 80), plain washer (key 163), and nut (key 81) to the arm assembly (key 91), if not
already installed.
4. Attach the arm assembly (key 91) to the travel sensor assembly (key 223) shaft.

80
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Figure 6‐8. Remote Feedback Terminals; Potentiometer Resistance Measurement

TERMINAL 2
TERMINAL 3

TERMINAL 1

5. Using a handheld communicator, perform the appropriate Travel Sensor Adjust procedure in the Calibration
section. Install the remote feedback unit on the actuator when travel sensor adjustment is complete.

Note
If a handheld communicator is not available, perform the Travel Sensor Adjustment with Multimeter procedure below.

Travel Sensor Adjustment with a Multimeter (DVC6025)


1. Connect a multimeter set to a resistance range of 50,000 ohms. Measure the resistance between terminals 1 and 3
of the remote feedback unit. Refer to figure 6‐8 for terminal location. The resistance should be between 40,000 and
50,000 ohms.
2. Multiply the result in step 1 by 0.142 to get a calculated resistance. The calculated resistance should be in the range
of 5680 to 7100 ohms.
3. Re‐range the multimeter to a resistance of 7000 ohms between terminals 2 and 3 of the remote feedback unit.
Refer to figure 6‐8 for terminal location.
4. Hold the arm assembly (key 91) in a fixed position so that the arm is parallel to the housing back plane and pointing
toward the terminal box. Position the arm assembly so that the outer surface is flush with the end of the travel
sensor shaft.
5. Adjust the travel sensor shaft to obtain the calculated resistance determined in step 2, $100 ohms.

Note
In the next step, be sure the arm assembly outer surface remains flush with the end of the travel sensor shaft.

81
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

6. While observing the resistance, tighten the screw (key 80) to secure the feedback arm to the travel sensor shaft. Be
sure the resistance reading remains at the calculated resistance determined in step 2, $100 ohms. Paint the screw
to discourage tampering with the connection.
7. Disconnect the multimeter from the travel sensor connector.
8. Apply anti‐seize (key 64) to the pin portion of the arm assembly (key 91).
9. Position the mounting bracket over the back of the digital valve controller. Push the feedback arm assembly
(key 84) toward the housing and engage the pin of the arm assembly into the slot in the feedback arm.
10. Install the mounting bracket (key 74).
11. Install the bias spring (key 82) as shown in figure 6‐9.
12. Travel sensor adjustment is complete. Install the remote feedback unit on the actuator.

Figure 6‐9. FIELDVUE DVC6025 digital Valve Controller, Bias Spring (key 82) Installation

BIAS SPRING
(KEY 82)

FEEDBACK ARM
ASSEMBLY
(KEY 84)

ARM ASSEMBLY
(KEY 91)

NOTE:
INSTALL BIAS SPRING WITH SMALLER DIAMETER HOOK CONNECTED TO ARM ASSEMBLY (KEY 91)
AND WITH BOTH HOOK OPENINGS TOWARD CENTER OF BRACKET.

DVC6035 Remote Feedback Unit


Refer to figure 7‐6 for DVC6035 key number locations.
1. Apply lubricant (key 63) to the travel sensor assembly threads.
2. Screw the travel sensor assembly (key 223) into the housing until it is tight.
3. Connect the travel sensor wires to the terminals as follows:
red  terminal 1
white  terminal 2
black  terminal 3

82
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

4. Loosely assemble the bias spring (key 78), screw (key 80), plain washer (key 163), and nut (key 81) to the feedback
arm (key 79), if not already installed.
5. Attach the feedback arm (key 79) to the travel sensor shaft.
6. Using a handheld communicator, perform the appropriate Travel Sensor Adjust procedure in the Calibration
section. Install the remote feedback unit on the actuator when travel sensor adjustment is complete.

Note
If a handheld communicator is not available, perform the Travel Sensor Adjustment with a Multimeter procedure below.

Travel Sensor Adjustment with a Multimeter (DVC6035)


1. Align the feedback arm (key 79) to the housing (key 1) by inserting the alignment pin (key 46) through the hole
marked “A” on the feedback arm. Fully engage the alignment pin into the tapped hole in the housing. Position the
feedback arm so that the outer surface is flush with the end of the travel sensor shaft.
2. Connect a multimeter set to a resistance range of 50,000 ohms. Measure the resistance between terminals 1 and 3
of the remote feedback unit. Refer to figure 6‐8 for terminal location. The resistance should be between 40,000 and
50,000 ohms.
3. Multiply the result in step 2 by 0.042 to get a calculated resistance. The calculated resistance should be in the range
of 1680 to 2100 ohms.
4. Re‐range the multimeter to a resistance of 3000 ohms between terminals 2 and 3 of the remote feedback unit.
Refer to figure 6‐8 for terminal location.
5. Adjust the travel sensor shaft to obtain the calculated resistance determined in step 3, $100 ohms.

Note
In the next step, be sure the feedback arm outer surface remains flush with the end of the travel sensor shaft.

6. While observing the resistance, tighten the screw (key 80) to secure the feedback arm to the travel sensor shaft. Be
sure the resistance reading remains at the calculated resistance determined in step 3, $100 ohms. Paint the screw
to discourage tampering with the connection.
7. Disconnect the multimeter from the travel sensor connector.
8. Travel sensor adjustment is complete. Install the remote feedback unit on the actuator as described in the
Installation section.

83
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

Troubleshooting
If communication or output difficulties are experienced with the instrument, refer to the troubleshooting chart in
table 6‐4. Also see the DVC6000 HW2 Troubleshooting Checklist on page 87.

Checking Voltage Available


WARNING
Personal injury or property damage caused by fire or explosion may occur if this test is attempted in an area which contains
a potentially explosive atmosphere or has been classified as hazardous.

To check the Voltage Available at the instrument, perform the following:


1. Connect the equipment in figure 2‐3 to the field wiring in place of the FIELDVUE instrument.
2. Set the control system to provide maximum output current.
3. Set the resistance of the 1 kilohm potentiometer shown in figure 2‐3 to zero.
4. Record the current shown on the milliammeter.
5. Adjust the resistance of the 1 kilohm potentiometer until the voltage read on the voltmeter is 10.0 volts.
6. Record the current shown on the milliammeter.
7. If the current recorded in step 6 is the same as that recorded in step 4 (± 0.08 mA), the voltage available is
adequate.
8. If the voltage available is inadequate, refer to Section 2, Wiring Practices.

Restart Processor
This is a “soft” reset of the device. This procedure can only be performed while the instrument is out of service. A soft
reset will immediately put into effect changes that have been sent to the instrument. Also, if the device is configured
to shutdown on an alert, the soft reset will clear the shutdown.

84
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

Table 6‐4. Instrument Troubleshooting


Symptom Possible Cause Action
1. Analog input reading at 1a. Control mode not Analog. 1a. Check the control mode using a handheld communicator. If
instrument does not match in the Digital or Test mode, the instrument receives its set point
actual current provided. as a digital signal. Control is not based on input current. Change
Control Mode to Analog.
1b. Low control system compliance voltage. 1b. Check system compliance voltage (see Wiring Practices in
the Installation section.
1c. Instrument shutdown due to self test failure. 1c. Check instrument status using a handheld communicator
(see Viewing Instrument Status in the Viewing Device
Information section).
1d. Analog input sensor not calibrated. 1d. Calibrate the analog input sensor (see Analog Input
Calibration in the Calibration section).
1e. Current leakage. 1e. Excessive moisture in the terminal box can cause current
leakage. Typically the current will vary randomly if this is the
case. Allow the inside of the terminal box to dry, then retest.
2. Instrument will not 2a. Insufficient Voltage Available. 2a. Calculate Voltage Available (see Wiring Practices in the
communicate. Installation section). Voltage Available should be greater than or
equal to 10 VDC.
2b. Controller output Impedance too low. 2b. Install a HART filter after reviewing Control System
Compliance Voltage requirements (see Wiring Practices in the
Installation section).
2c. Cable capacitance too high. 2c. Review maximum cable capacitance limits (see Wiring
Practices in the Installation section).
2d. HART filter improperly adjusted. 2d. Check filter adjustment (see the appropriate HART filter
instruction manual).
2e. Improper field wiring. 2e. Check polarity of wiring and integrity of connections. Make
sure cable shield is grounded only at the control system.
2f. Controller output providing less than 4 mA to loop. 2f. Check control system minimum output setting, which should
not be less than 3.8 mA.
2g. Disconnected loop wiring cable at PWB. 2g. Verify connectors are plugged in correctly.
2h. PWB DIP switch not set properly. 2h. Check for incorrect setting or broken DIP switch on the back
of the PWB. Reset switch or replace PWB, if switch is broken. See
table 6‐2 for switch setting information
2j. PWB failure. 2j. Use a 4-20 mA current source to apply power to the
instrument. Terminal voltage across the LOOP+ and LOOP-
terminals should be 8 to 9.5 VDC. If the terminal voltage is not 8
to 9.5 VDC, replace the PWB.
2k. Polling address incorrect. 2k. Use a handheld communicator to set the polling address
(refer to the Detailed Setup section). From the Utility menu,
select Configure Communicator and Polling. Select Always Poll. Set
the instrument polling address to 0.
2l. Defective terminal box. 2l. Check continuity from each screw terminal to the
corresponding PWB connector pin. If necessary, replace the
terminal box assembly.
2m. Defective handheld communicator or ValveLink 2m. If necessary, repair or replace cable.
modem cable.
2n. ValveLink modem defective or not compatible 2n. Replace ValveLink modem.
with PC.
2p. ValveLink hardlock defective or not programmed. 2p. Replace if defective or return to factory for programming.
3. Instrument will not 3a. Travel sensor seized, will not turn. 3a. Rotate feedback arm to ensure it moves freely. If not, replace
calibrate, has sluggish the travel sensor (pot/bushing) assembly.
performance or oscillates. 3b. Broken travel sensor wire(s). 3b. Inspect wires for broken solder joint at potentiometer or
broken wire. Replace travel sensor (pot/bushing) assembly.
3c. Travel sensor misadjusted. 3c. Perform Travel Sensor Adjust procedure in the Calibration
section.
3d. Open travel sensor. 3d. Check for continuity in electrical travel range. If necessary,
replace pot/bushing assembly.
3e. Cables not plugged into PWB correctly. 3e. Inspect connections and correct.
3f. Feedback arm loose on potentiometer. 3f. Perform Travel Sensor Adjust procedure in the Calibration
section.

85
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

Table 6‐4. Instrument Troubleshooting (Continued)


Symptom Possible Cause Action
3. Instrument will not 3g. Feedback arm bent/damaged or bias spring 3g. Replace feedback arm and bias spring.
calibrate, has sluggish missing/damaged.
performance or oscillates. 3h. Configuration errors. 3h. Verify configuration:
If necessary, set protection to None.
If Out of Service, place In Service.
Check:
Travel Sensor Motion
Tuning set
Zero control signal
Feedback Connection
Control mode (should be Analog)
Restart control mode (should be Analog)
3j. Restricted pneumatic passages in I/P converter. 3j. Check screen in I/P converter supply port of the module base.
Replace if necessary. If passages in I/P converter restricted,
replace I/P converter.
3k. O‐ring(s) between I/P converter ass'y missing or hard 3k. Replace O‐ring(s).
and flattened losing seal.
3l. I/P converter ass'y damaged/corroded/clogged. 3l. Check for bent flapper, open coil (continuity), contamination,
staining, or dirty air supply. Coil resistance should be between
1680 ‐ 1860 ohms. Replace I/P assembly if damaged, corroded,
clogged, or open coil.
3m. I/P converter ass'y out of spec. 3m. I/P converter assembly nozzle may have been adjusted.
Verify drive signal (55 to 80% for double‐acting; 60 to 85% for
single‐acting) with the valve off the stops. Replace I/P converter
ass'y if drive signal is continuously high or low.
3n. Defective module base seal. 3n. Check module base seal for condition and position. If
necessary, replace seal.
3p. Defective relay. 3p. Depress relay beam at adjustment location in shroud, look
for increase in output pressure. Remove relay, inspect relay seal.
Replace relay seal or relay if I/P converter ass'y good and air
passages not blocked. Check relay adjustment.
3q. Defective 67CFR regulator, supply pressure gauge 3q. Replace 67CFR regulator.
jumps around.
4. ValveLink diagnostic tests 4a. Bent or defective pressure sensor. 4a. Replace PWB.
provide erroneous results. 4b. Pressure sensor O‐ring missing. 4b. Replace O‐ring.
5. Handheld communicator 5a. Battery pack not charged. 5a. Charge battery pack.
does not turn on. Note: Battery pack can be charged while attached to the
handheld communicator or separately. The handheld
communicator is fully operable while the battery pack is
charging. Do not attempt to charge the battery pack in a
hazardous area.

86
Instruction Manual Maintenance and Troubleshooting
D103785X012 February 2023

DVC6000 HW2 Troubleshooting Checklist


1. Instrument serial number as read from nameplate ________________________________________________
2. Is the digital valve controller responding to the control signal? Yes _________ No _________

If not, describe ___________________________________________________________________________


3. Measure the voltage across the “Loop -” and Loop +” terminal box screws when the commanded current is 4.0 mA
and 20.0 mA: __________V @ 4.0 mA __________V @ 20.0 mA.
(These values should be around 8.6 V @ 4.0 mA and 8.8 V @ 20 mA.)
4. Is it possible to communicate via HART to the digital valve controller? Yes _________ No _________
5. What is the Diagnostic Tier of the digital valve controller? AC ____ HC ____ AD ____ PD ____ ODV____
6. What is the firmware version of the digital valve controller? ______________
7. What is the hardware version of the digital valve controller? ______________
8. Is the digital valve controller's Instrument Mode “In Service”? Yes _________ No _________
9. Is the digital valve controller's Control Mode set to “Analog”? Yes _________ No _________
10. Is it on Travel or Pressure control?
11. What are the following parameter readings?

Input Signal _________ Drive Signal _________%

Supply Pressure _________ Pressure A _________ Pressure B _________

Travel Target _________% Travel _________%


12. What are the following alert readings?

Fail alerts _______________________________________________________________________________

Valve alerts _____________________________________________________________________________

Operational status ________________________________________________________________________

Alert event record entries __________________________________________________________________


13. Export ValveLink data (if available) for the device (Status Monitor, Detailed Setup, etc.).

Mounting
1. Which DVC6000 HW2 do you have? DVC6005 HW2 w/ DVC6015 ____ DVC6025 ____ DVC6035 ____
2. What Make, Brand, Style, Size, etc. actuator is the DVC6000 HW2 mounted on? ________________________
3. What is the full travel of the valve? ____________________________________________________________
4. What is the Mounting Kit part number? _________________________________________________________
5. If mounting kits are made by Impact Partner/customer, please provide pictures of installation.
6. Is the Mounting kit installed per the instructions? Yes _________ No _________
7. What is the safe position of the valve? Fail closed _________ Fail open _________

87
Maintenance and Troubleshooting Instruction Manual
February 2023 D103785X012

88
Instruction Manual Parts
D103785X012 February 2023

Section 7 Parts77
Parts Ordering
Whenever corresponding with your Emerson sales office about this equipment, always mention the controller serial
number.

WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson should not, under any
circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson may void your warranty,
might adversely affect the performance of the instrument, and could cause personal injury and property damage.

Parts Kits Kit Description Part Number

6* Seal Screen Kit


[kit contains 25 seal screens (key 231)
and 25 O-rings (key 39)] 14B5072X182
Note
All Standard kits with elastomers include nitrile elastomers. Extreme
temperature kits include fluorosilicone elastomers.
Note
The following terminal boxes are only compatible with PWB Assembly
electronics hardware revision 2 (HW2) (key 50), as shown in figure 7‐1.
Kit Description Part Number Use only with replace in-kind.

1* Elastomer Spare Parts Kit (kit contains parts to


service one digital valve controller) 7 Terminal Box Kit
Standard 19B5402X012
Extreme Temperature 19B5402X022 Without I/O Package
Standard 19B5401X142
2* Small Hardware Spare Parts Kit (kit contains parts Extreme Temperature 19B5401X152
to service one digital valve controller) 19B5403X012
Without I/O Package, Natural Gas Approved
3 Conversion Kit, DVC6015 to DVC6025 19B5405X012 Standard 19B5401X742
Extreme Temperature 19B5401X752
4 Conversion Kit, DVC6025 to DVC6015 14B5072X112
With I/O Package
5 Alignment Pin Kit Standard Temperature 19B5401X182
[kit contains 15 alignment pins (key 46)] 14B5072X092 Extreme Temperature 19B5401X192

*Recommended spare 89
Parts Instruction Manual
February 2023 D103785X012

Kit Description Part Number Key Description Part Number

8* I/P Converter Kit


Standard 38B6041X152 DVC6005 HW2 Base Unit
Extreme Temperature 38B6041X132
(see figure 7‐2)
9 Adjustment Arm Kit
(includes washer, nut and adjustment arm) 14B5072X132
Housing
10* Spare Module Base Assembly Kit 1 Housing
[kit contains module base (key 2); drive screws, qty. 2, 11 Drive Screw (2 req'd)
(key 11); shield/label (key 19); hex socket cap screw, qty. 3, 20 Shield
(key 38); self tapping screw, qty. 2 (key 49); pipe plug, qty. 3 52 Vent(2)
(key 61); retaining ring, qty. 3 (key 154); screen (key 236); 74 Mounting Bracket(17)
and flame arrestors, qty. 3 (key 243)] 248 Screw, hex head(17) (4 req'd)
GE18654X012 249 Screw, hex head(17) (4 req'd)
250 Spacer(17) (4 req'd)
11* Spare Shroud Kit GE29183X012 267 Standoff(17) (2 req'd)
271 Screen
12 Travel Sensor with Feedback Arm Assembly
and PTFE Sleeve Kit Common Parts
DVC6015 GG09948X012 16* O-ring(1) (3 req'd)
DVC6025 GG09950X012 29 Warning label, for use only with LCIE hazardous area
classifications
13 Remote Travel Sensor Assembly 33 Mach Screw, pan hd(2) (3 req'd)
38 Cap Screw, hex socket(2,10) (3 req'd)

Note 43* Cover Assembly (includes cover screws)


Contact your Emerson sales office for Remote Travel Sensor Assembly Standard GG53748X012
ordering information. Extreme temperature GG53748X022

48 Nameplate
49 Screw, self tapping (2 req'd)(10)
63 Lithium grease (not furnished with the instrument)
64 Pipe thread sealant (not furnished with the instrument)
14 Remote Terminal Box Kit GE00418X012 65 Lubricant, silicone sealant (not furnished with the instrument)
154 Retaining Ring(2) (3 req'd)
15 Feedback Unit 237 Module Base Seal(1)
DVC6015 49B7986X012
DVC6025 long arm 49B7987X012
DVC6025 Short Arm 49B7987X022 Module Base
DVC6035 49B7988X012 2 Module Base(10)
DVC6035 (for GX actuator) 49B7988X022 11 Drive Screw(10) (2 req'd)
12 O-ring(1)
16 Feedback Unit Termination Strip Kit GE00419X012 19 Shield Assembly(10)
17 Pipestand/Wall Mounting Kit GE00420X012 61 Pipe Plug, hex socket(10) (3 req'd)
236 Screen, for single-acting units only(10)
243 Flame Arrestor Assembly(10) (3 req'd)

I/P Converter Assembly


Parts List 23
39*
Cap Screw, hex socket(2,11) (4 req'd)
O-ring (1,8)
41 I/P Converter(8)
169 Shroud(8,11)
210* Boot(1,8) (2 req'd) (also see figure 6‐4)
Notes 231* Seal Screen(1,6,8)
Contact your Emerson sales office for Part Ordering information.
Standard parts with elastomers include nitrile elastomers. Extreme
temperature parts include fluorosilicone elastomers. *Recommended spare
1. Available in the Elastomer Spare Parts Kit
Parts with footnote numbers shown are available in parts kits; see 2. Available in the Small Hardware Spare Parts Kit
footnote information at the bottom of the page. 6. Available in the Seal Screen Kit
8. Available in the I/P Converter Kit
10. Available in the Spare Module Base Assembly Kit
11. Available in the Spare Shroud Kit
17. Available in the Pipestand/Wall Mounting Kit

90
Instruction Manual Parts
D103785X012 February 2023

Key Description Part Number Figure 7‐1. Terminal Box

Relay
24* Relay Assembly, (includes shroud, relay seal, mounting screws)
Standard
Single-acting direct (relay C) 38B5786X132
Double-acting (relay A) 38B5786X052
Single-acting reverse (relay B) 38B5786X092
Low Bleed
Single-acting direct (relay C) 38B5786X152
Double-acting (relay A) 38B5786X072
Single-acting reverse (relay B) 38B5786X112
Extreme Temperature
Standard Bleed
Single-acting direct (relay C) 38B5786X142 WITHOUT I/O PACKAGE WITH I/O PACKAGE
Double-acting (relay A) 38B5786X032
Single-acting reverse (relay B) 38B5786X102
Low Bleed
Single-acting direct (relay C) 38B5786X162 Key Description
Double-acting (relay A) 38B5786X082
Single-acting reverse (relay B) 38B5786X122

PWB Assembly
Terminal Box 50* PWB Assembly for DVC6005 HW2
4 Terminal Box Cap(14)
34* O-ring(1,7,14)
36* O-ring(1,7,14)
44 Wire Retainer(2) (6 req'd) (not shown) Note
58 Set Screw, hex socket(2,14) The following PWB Assemblies are only compatible with the terminal
72 Cap Screw, hex socket(2,14) boxes shown in figure 7‐1.
164 Terminal Box Assembly(7)

Feedback Connections Terminal Box Hardware Revision 2 (HW2), without I/O Package
4 Terminal Box Cap(14) For instrument level HC
34* O-ring(1,7,14) For instrument level AD
36* O-ring(1,7,14) For instrument level PD
44 Wire Retainer(2,15) (5 req'd) (not shown) For instrument level ODV
58 Set Screw, hex socket(2,14)
62 Pipe Plug, hex hd(14) Hardware Revision 2 (HW2), with I/O Package
72 Cap Screw, hex socket(2,14) (3 req'd) For instrument level HC
262 Adapter(14) For instrument level AD
263* O-ring(14) For instrument level PD
264 Terminal Box Assembly, remote(14) For instrument level ODV

*Recommended spare
1. Available in the Elastomer Spare Parts Kit
2. Available in the Small Hardware Spare Parts Kit
7. Available in the Terminal Box Kit
14. Available in the Remote Terminal Box Kit

91
Parts Instruction Manual
February 2023 D103785X012

Key Description Part Number Key Description


107 Mounting Bracket(15), DVC6015 only
Not for mounting on 1250 and 1250R actuators.
Mounting parts for 1250 and 1250R actuators are
included in the mounting kit for these actuators.
Pressure Gauges, Pipe Plugs, or --- Feedback Linkage Shield

Tire Valve Assemblies Up to 50.4 mm (2 inch) travel


All sliding-stem actuators except 585C size 60
(see figure 7‐3) 50.4 mm (2 inch) to 104mm (4 inch) travel
All sliding-stem actuators except 585C size 60
585C size 60, 19 mm (0.75 inch) to
47* Pressure Gauge 104 mm (4 inch) travel
Double-acting (3 req'd); Single-acting (2 req'd)
PSI/MPA Gauge Scale 131 Retainer Wire
To 60 PSI, 0.4 MPa 18B7713X042 163 Plain Washer(2,15)
To 160 PSI, 1.1 MPa 18B7713X022
PSI/bar Gauge Scale 223* Potentiometer/Bushing Assembly (Travel Sensor Assembly)(15)
To 60 PSI, 4 bar 18B7713X032 DVC6015 and DVC6025
To 160 PSI, 11 bar 18B7713X012 DVC6035
PSI/KG/CM2 Gauge Scale
To 60 PSI, 4 KG/CM2 18B7713X072 251 Feedback housing(15)
To 160 PSI, 11 KG/CM2 18B7713X082 252 Assembly Plate Shield(15) (DVC6015 only)
253 Terminal bracket(15,16)
66 Pipe Plug, hex hd 254 Terminal Strip(15,16)
For units w/o gauges 255 Terminal Cap(15)
256 O-ring(15)
67 Tire Valve Assembly (3 req'd) 257 Machine Screw, pan head(15) (2 req'd) (DVC6015 only)
Not for mounting on 1250 and 1250R actuators. 258 Label, cover(15)
260 Hex Nut (2 req'd)
261 Nameplate
265 Plug(15) (DVC6015 and DVC6035 only)
DVC6025 (see figure 7‐5)
74 Mounting Bracket
Remote Feedback Units 82 Bias Spring
83 Bearing Flange (2 req'd)
84 Feedback Arm Assembly
Common Parts 85 E-ring (2 req'd)
DVC6015, DVC6025, and DVC6035 86 Plain Washer (2 req'd)
(see figures 7‐4, 7‐5, and 7‐6) 87 Follower Post
88 Roller
89 Spring Lock Washer
23 Cap Screw, hex socket(15,16) (2 req'd) 90 Hex Nut
44 Wire Retainer(15,16) (9 req'd) 91 Arm Assembly
46 Alignment Pin(5,15) 92 Cap Screw, hex socket (4 req'd)
for DVC6015 and DVC6035 93 Torsion Spring, Feedback Arm
49 Screw, self tapping (2 req'd)
58 Set Screw, hex socket(15)
62 Pipe Plug, hex hd(15)
64 Anti-seize compound (not furnished with the instrument) HART Filters
65 Lubricant, silicone sealant (not furnished with the instrument) HF340, DIN rail mount
72 Cap Screw, hex socket(2,15) (2 req'd) HF341, DIN rail Mount, pass through (no filter)
for DVC6015, and DVC6025
78 Bias Spring(2,15)
for DVC6015 and DVC6035
79 Feedback Arm
for DVC6015 and DVC6035
80 Cap Screw, hex socket(2,15)
81 Square Nut(2,15)
104 Cap Screw, hex hd(15) (4 req'd), DVC6015 only
Not for mounting on 1250 and 1250R actuators.
Mounting parts for 1250 and 1250R actuators are
included in the mounting kit for these actuators. *Recommended spare
2. Available in the Small Hardware Spare Parts Kit
5. Available in Alignment Pin Kit
15. Available in Feedback Unit Kit
16. Available in Feedback Unit Termination Strip Kit

92
Instruction Manual Parts
D103785X012 February 2023

Figure 7‐2. FIELDVUE DVC6005 HW2 Base Unit Assembly

SECTION A-A

SECTION C-C

SECTION B-B

APPLY LUB, SEALANT


NOTES:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
49B3261-C SHT 1 & 2

93
Parts Instruction Manual
February 2023 D103785X012

Figure 7‐2. FIELDVUE DVC6005 HW2 Base Unit Assembly (continued)

E E

SECTION E-E

OUTPUT A

OUTPUT A

OUTPUT B OUTPUT B
SUPPLY SUPPLY

WALL MOUNTING PIPESTAND MOUNTING


APPLY LUB, SEALANT
NOTES:
1SEE FIGURE 7‐3 FOR GAUGE CONFIGURATIONS
2. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
49B3261-C SHT 2 & 3

94
Instruction Manual Parts
D103785X012 February 2023

Figure 7‐3. Typical FIELDVUE DVC6005 HW2 Digital Valve Controller Gauge Configuration

DOUBLE-ACTING
SINGLE-ACTING DIRECT SINGLE-ACTING REVERSE
APPLY LUB, SEALANT
NOTE:
1FOR SINGLE-ACTING DIRECT, OUTPUT B IS PLUGGED.
2FOR SINGLE-ACTING REVERSE, OUTPUT A IS PLUGGED.
49B3261-C SHT 2

95
Parts Instruction Manual
February 2023 D103785X012

Figure 7‐4. FIELDVUE DVC6015 Remote Feedback Unit Assembly

SECTION C-C

SECTION B-B

APPLY LUB, SEALANT SECTION A-A SECTION D-D


NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
49B7986-A

96
Instruction Manual Parts
D103785X012 February 2023

Figure 7‐5. FIELDVUE DVC6025 Remote Feedback Unit Assembly

SECTION B-B

SECTION A-A

APPLY LUB, SEALANT, THREAD LOCK


NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
49B7987-A

97
Parts Instruction Manual
February 2023 D103785X012

Figure 7‐6. FIELDVUE DVC6035 Remote Feedback Unit Assembly

SECTION C-C

SECTION B-B

SECTION A-A
APPLY LUB, SEALANT, THREAD LOCK
NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED

49B7988-A

98
Instruction Manual Principle of Operation
D103785X012 February 2023

Appendix A Principle of OperationAA−A


HART Communication
The HART (Highway Addressable Remote Transducer) protocol gives field devices the capability of communicating
instrument and process data digitally. This digital communication occurs over the same two‐wire loop that provides
the 4‐20 mA process control signal, without disrupting the process signal. In this way, the analog process signal, with
its faster update rate, can be used for control. At the same time, the HART protocol allows access to digital diagnostic,
maintenance, and additional process data. The protocol provides total system integration via a host device.

The HART protocol uses frequency shift keying (FSK). Two individual frequencies of 1200 and 2200 Hz are
superimposed over the 4‐20 mA current signal. These frequencies represent the digits 1 and 0 (see figure A‐1). By
superimposing a frequency signal over the 4-20 mA current, digital communication is attained. The average value of
the HART signal is zero, therefore no DC value is added to the 4‐20 mA signal. Thus, true simultaneous communication
is achieved without interrupting the process signal.

Figure A‐1. HART Frequency Shift Keying Technique

+0.5V

0 ANALOG
SIGNAL
-0.5V
1200 Hz 2200 Hz
“1” “0”

AVERAGE CURRENT CHANGE DURING COMMUNICATION = 0


A6174

The HART protocol allows the capability of multidropping, i.e., networking several devices to a single communications
line. This process is well suited for monitoring remote applications such as pipelines, custody transfer sites, and tank
farms. See table 6‐2 for instructions on changing the printed wiring board DIP switch configuration to multidrop.

DVC6000 HW2 Digital Valve Controller


The DVC6000 HW2 digital valve controller housing contains the travel sensor, terminal box, pneumatic input and
output connections and a module base that may be easily replaced in the field without disconnecting field wiring or
tubing. The module base contains the following submodules: I/P converter, printed wiring board (pwb) assembly, and
pneumatic relay. The relay position is detected by sensing the magnet on the relay beam via a detector on the printed
wiring board. This sensor is used for the minor loop feedback (MLFB) reading. The module base can be rebuilt by
replacing the submodules. See figures A‐3.

99
Principle of Operation Instruction Manual
February 2023 D103785X012

Figure A‐2. Typical FIELDVUE Instrument to Personal Computer Connections for ValveLink Software

CONTROL SYSTEM

HART MODEM

FIELD TERM.

E1568

DVC6000 HW2 digital valve controllers are loop‐powered instruments that provide a control valve position
proportional to an input signal from the control room. The following describes a double‐acting digital valve controller
mounted on a piston actuator.

The input signal is routed into the terminal box through a single twisted pair of wires and then to the printed wiring
board assembly submodule where it is read by the microprocessor, processed by a digital algorithm, and converted
into an analog I/P drive signal.

As the input signal increases, the drive signal to the I/P converter increases, increasing the I/P output pressure. The I/P
output pressure is routed to the pneumatic relay submodule. The relay is also connected to supply pressure and
amplifies the small pneumatic signal from the I/P converter. The relay accepts the amplified pneumatic signal and
provides two output pressures. With increasing input (4 to 20 mA signal), the output A pressure always increases and
the output B pressure decreases. The output A pressure is used for double‐acting and single‐acting direct applications.
The output B pressure is used for double‐acting and single‐acting reverse applications. As shown in figure A‐3 the
increased output A pressure causes the actuator stem to move downward. Stem position is sensed through the
feedback linkage by the travel sensor which is electrically connected to the printed wiring board assembly submodule.
The stem continues to move downward until the correct stem position is attained. At this point the printed wiring
board assembly stabilizes the I/P drive signal. This positions the flapper to prevent any further increase in nozzle
pressure.

As the input signal decreases, the drive signal to the I/P converter submodule decreases, decreasing the I/P output
pressure. The pneumatic relay decreases the output A pressure and increases the output B pressure. The stem moves
upward until the correct position is attained. At this point the printed wiring board assembly stabilizes the I/P drive
signal. This positions the flapper to prevent any further decrease in nozzle pressure.

100
Instruction Manual Principle of Operation
D103785X012 February 2023

Figure A‐3. FIELDVUE DVC6000 HW2 Digital Valve Controller Block Diagram

4-20 mA

INPUT SIGNAL
+
HART
AUXILIARY
TERMINALS
TERMINAL BOX

PRINTED
WIRING BOARD
DRIVE REMOTE
FEEDBACK CONNECTION SIGNAL
TERMINAL BOX FEEDBACK
UNIT
OUTPUT A

I/P
CONVERTER PNEUMATIC
RELAY SUPPLY PRESSURE

OUTPUT B

VENT
VALVE AND
ACTUATOR

VALVE TRAVEL FEEDBACK

E1569

101
Handheld Communicator Menu Trees Instruction Manual
February 2023 D103785X012

Appendix B Handheld Communicator Menu Trees


This section contains handheld communicator menu trees for instrument level HC, AD, PD, and ODV. It also contains
an alphabetized function/variable list to help locate the function/variable on the appropriate menu tree. All Fast Key
Sequences referenced in the menu trees assume the Online menu (see figure B-2) as the starting point.

Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.

Function/Variable See Figure Function/Variable See Figure


Actual Travel B-5 Change Instrument Mode B-1, B-5
Actuator Manufacturer B-5 Change to HART 5 / Change to HART 7 B-11
Actuator Model B-5 Change Travel/Pressure Select B-6, B-11
Actuator Selection B-5 Change Write Protection B-1, B-3, B-5
Actuator Size B-5 Clear Records B-9, B-11
Actuator Style B-7 Control Mode B-6, B-11
Air B-5 Critical NVM Failure
B-9
Alert Record Full (PST Prohibited Electronics Alerts)
B-9
(Alert Record/Status Alerts Enable) Critical NVM Failure (Electronics Alerts NE107) B-8
Alert Record Full Critical NVM Failure Shutdown B-8
B-9
(Alert Record/Status Alerts NE107) Custom Characterization B-6, B-11
Alert Record Not Empty Cycle Count B-8, B-11
B-9
(Alert Record/Status Alerts Enable) Cycle Count Hi (Travel History Alerts Enable) B-8
Alert Record Not Empty
B-9 Cycle Count High (Travel History Alerts NE107) B-8
(Alert Record/Status Alerts NE107)
Cycle Count High Alert Point B-8
Alert Switch Source B-7
Cycle Count/Travel Accum Deadband B-8
Analog Input B-3, B-11
Days Powered Up B-11
Analog Input (Calibration) B-10
DD Information B-3
Analog Input Units B-5
Description B-3, B-5
Area Units B-5
Device ID B-3
Auto Calibration B-4, B-10
Device Revision B-3
Autocal in Progress
B-9 Device Setup B-4
(Alert Record/Status Alerts Enable)
Autocal in Progress Device Status B-3, B-11
B-9 Diagnostic Data Available
(Alert Record/Status Alerts NE107) B-9
Auxiliary Terminal Action B-5 (Alert Record/Status Alerts Enable)
Auxiliary Terminal Action, Edit B-5 Diagnostic Data Available
B-9
(Alert Record/Status Alerts NE107)
Breakout Timeout B-7
Diagnostic in Progress
Breakout Torque B-5 B-9
(Alert Record/Status Alerts Enable)
Burst Command B-7
Diagnostic in Progress
Burst Enable B-7 B-9
(Alert Record/Status Alerts NE107)
Calibration Button B-5 Drive Current Failure (Electronics Alerts NE107) B-8
Calibration in Progress Drive Current Failure
B-9 B-9
(Alert Record/Status Alerts Enable) (PST Prohibited Electronics Alerts)
Calibration in Progress Drive Current Failure Shutdown B-8
B-9
(Alert Record/Status Alerts NE107) Drive Signal B-3, B-11
Calibration Record B-10
Drive Signal (Electronics Alerts Enable) B-8
Calibration Time B-10
Drive Signal (Electronics Alerts NE107) B-8
Calibration Type B-10
Dynamic Torque B-5
Calibrator B-10
Edit Cycle Counts B-8
Change Control Mode B-6, B-11
Edit Instrument Time B-5, B-9

102
Instruction Manual Handheld Communicator Menu Trees
D103785X012 February 2023

Function/Variable See Figure Function/Variable See Figure


Edit Travel Accumulator B-8 Lo Limit/Cutoff Point B-6, B-8
Effective Area B-5 Lo Limit/Cutoff Select B-6
Fail Signal B-7 Lo Soft Cutoff Range B-6
Fallback Recovery B-6, B-9, B-11 Low Friction Breakout Pressure B-7
Fallback-Sensor Failure B-9 Lower Bench Set B-5
Fallback-Sensor/Travel Deviation B-9 Manual Calibration B-10
Feedback Connection B-5, B-7 Manufacturer (Device) B-3
Firmware Revision B-3 Maximum Allowable Travel Movement B-7
Flash Integrity Failure (Electronics Alerts NE107) B-8 Maximum Recorded Temperature B-11
Flash Integrity Failure Maximum Supply Pressure B-7
B-9
(PST Prohibited Electronics Alerts) Message B-3, B-5
Flash Integrity Failure Shutdown B-8 Minimum Recorded Temperature B-11
Flow Direction B-5 Minimum Required Travel Movement B-7
Flow Tends to B-5 Minor Loop Sensor Failure
B-9
Function B-7 (PST Prohibited Electronics Alerts)
Hardware Revision (Device) B-3 Minor Loop Sensor Failure
B-9
HART Long Tag B-3, B-5 (PST Prohibited Electronic Alerts)
Minor Loop Sensor Failure (Sensor Alert NE107) B-9
HART Tag B-3, B-5
Minor Loop Sensor Failure Shutdown B-9
HART Universal Revision B-3
MLFB Gain (Travel & Pressure Tuning) B-7
HART Variable Assignments B-7
Model (Device) B-3
High Friction Breakout Pressure B-7
Nominal Supply B-5
Hi Limit/Cutoff Point B-6, B-8
Non-Critical NVM Failure
Hi Limit/Cutoff Select B-6 B-8
(Electronics Alerts NE107)
Hi Soft Cutoff Rate B-6
Non-Critical NVM Failure Shutdown B-8
Incoming Pressure Threshold B-7
Number of Power Ups B-11
Inlet Pressure B-5
Outgoing Pressure Threshold B-7
Input Characterization B-6, B-11
Outlet Pressure B-5
Input Range Hi B-5
Output Circuit Error (Electronics Alerts Enable) B-8
Input Range Lo B-5
Output Circuit Error (Electronics Alerts NE107) B-8
Instrument Alert Record B-9
Output Pressure Limit Enable B-8
Instrument Level B-3
Output Terminal Enable B-7
Instrument Mode B-1, B-5
Packing Type B-5
Instrument Serial Number B-3, B-5
Partial Stroke Test B-11
Instrument Time is Approximate
B-9 Polling Address B-5
(Alert Record/Status Alerts Enable)
Port A Overpressurized (Pressure Alerts Enable) B-8
Instrument Time is Approximate
B-9 Port A Overpressurized (Pressure Alerts NE107) B-8
(Alert Record/Status Alerts NE107)
Integral Enable (Travel & Pressure Tuning) B-7 Port A Pressure Limit B-8
Integral Gain (Travel & Pressure Tuning) B-7 Port Diameter B-5
Integrator Limit B-7 Port Type B-5
Integrator Saturated Hi Position Transmitter B-5
B-9
(Alert Record/Status Alerts Enable) Pressure A B-3, B-11
Integrator Saturated Hi Pressure A-B B-3, B-11
B-9
(Alert Record/Status Alerts NE107) Pressure B B-3, B-11
Integrator Saturated Lo Pressure Control B-9
B-9
(Alert Record/Status Alerts Enable) Pressure Deviation Alert Point B-8
Integrator Saturated Lo
B-9 Pressure Deviation (Pressure Alerts Enable) B-8
(Alert Record/Status Alerts NE107)
Pressure Deviation (Pressure Alerts NE107) B-8
Integral Dead Zone B-7
Pressure Deviation Time B-8
Last AutoCal Status B-10
Pressure Fallback Active
Last PST Results B-7 B-9
(PST Prohibited Alerts Enable)
Leak Class B-5
Pressure Fallback Active (Sensor Alerts Enable) B-9
Length Units B-5
Pressure Fallback Active (Sensor Alerts NE107) B-9
Lever Arm Length B-5
Pressure Range High B-6
Lever Style B-5
Pressure Range Low B-6
Limit Switch Trip Point B-7
Pressure Sensor Failure
Limit Switch Valve Close B-5 B-9
(PST Prohibited Alerts Enable)
Limit Switch Valve Open B-5

103
Handheld Communicator Menu Trees Instruction Manual
February 2023 D103785X012

Function/Variable See Figure Function/Variable See Figure


Pressure Sensor Failure Supply Pressure Lo Alert Point B-6, B-8
B-9
(Sensor Alerts NE107) Switch Closed B-7
Pressure Sensor Failure Shutdown B-9 Temperature B-11
Pressure Sensors (Calibration) B-10 Temperature Units B-5
Pressure Tuning Set B-7 Temp Sensor Failure
B-9
Pressure Units B-5 (PST Prohibited Alerts Enable)
Program Flow Failure (Partial Stroke Alerts NE107) B-9 Temp Sensor Failure (Sensor Alerts NE107) B-9
Program Flow Failure Shutdown B-9 Temp Sensor Failure Shutdown B-9
Proportional Gain (Travel & Pressure Tuning) B-7 Torque Units B-5
PST Abnormal (Partial Stroke Alerts Enable) B-9 Transmitter Output B-7
PST Abnormal (Partial Stroke Alerts NE107) B-9 Travel B-3, B-8, B-11
PST Abnormal Criteria B-7 Travel Accumulator (Alert Setup) B-8
PST Abort Criteria B-7 Travel Accumulator (Travel History) B-11
PST Enable B-7 Travel Accumulator Alert Point B-8
PST Calibration B-10 Travel Accumulator High
B-8
PST Deferral Reason B-7 (Travel History Alerts Enable)
PST Pass (Partial Stroke Alerts Enable) B-9 Travel Accumulator High
B-8
PST Pass (Partial Stroke Alerts NE107) B-9 (Travel History Alerts NE107)
Travel Alert Deadband B-8
PST Prohibited (Partial Stroke Alerts Enable) B-9
Travel Control B-9
PST Prohibited (Partial Stroke Alerts NE107) B-9
Travel Counts B-11
PST Result Criticality B-7
Travel Deviation B-8
PST Start Point B-7
Travel Deviation (PST Prohibited Alerts Enable) B-9
PST Variables B-7
Travel Deviation (Travel Alerts Enable) B-8
Push Down To B-5
Travel Deviation (Travel Alerts NE107) B-8
PWB Serial Number B-3
Travel Deviation Alert Point B-8
Quick Release B-5
Travel Deviation Pressure Fallback B-6
Rated Travel B-5
Travel Deviation Pressure Fallback Time B-6
Relay Adjust B-10
Travel Deviation Time B-8
Relay Type B-7
Travel Hi (Travel Alerts Enable) B-8
Reference Voltage Failure
B-8 Travel Hi (Travel Alerts NE107) B-8
(Electronics Alerts NE107)
Reference Voltage Failure Travel Hi Hi (Travel Alerts Enable) B-8
B-9
(PST Prohibited Electronics Alerts) Travel Hi Hi (Travel Alerts NE107) B-8
Reference Voltage Failure Shutdown B-8 Travel Hi Alert Point B-8
Reset PST Abnormal Alert B-11 Travel Hi Hi Alert Point B-8
Restart Control Mode B-6, B-11 Travel Lo (Travel Alerts Enable) B-8
Restart Processor B-11 Travel Lo (Travel Alerts NE107) B-8
Return Lead B-7 Travel Lo Lo (Travel Alerts Enable) B-8
Seat Type (Trim) B-5 Travel Lo Lo (Travel Alerts NE107) B-8
Setpoint B-3, B-8, B-11 Travel Lo Alert Point B-8
Short Duration PST B-7 Travel Lo Lo Alert Point B-8
Shutdown Activated (Electronics Alerts Enable) B-8 Travel Limit/Cutoff Hi (Travel Alerts Enable) B-8
Shutdown Activated (Electronics Alerts NE107) B-8 Travel Limit/Cutoff Hi (Travel Alerts NE107) B-8
Simulate B-11 Travel Limit/Cutoff Lo (Travel Alerts Enable) B-8
Solenoid Valve B-5 Travel Limit/Cutoff Lo (Travel Alerts NE107) B-8
SP Rate Close B-6 Travel/Pressure Select B-6, B-9, B-11
SP Rate Open B-6 Travel Sensor Adjust B-10
Spring Rate B-5 Travel Sensor Failure (Sensor Alerts NE107) B-9
Spring Rate Units B-5 Travel Sensor Failure
B-9
Stabilize/Optimize B-7, B-11 (PST Prohibited Alerts Enable)
Stem Diameter B-5 Travel Sensor Failure Shutdown B-9
Stroke Valve B-11 Travel Sensor Motion B-5, B-7
Supply Pressure B-3, B-8, B-11 Travel Tuning Set B-7
Supply Pressure Hi (Pressure Alerts Enable) B-8 Travel Units B-5
Supply Pressure Hi (Pressure Alerts NE107) B-8 Unbalanced Area B-5
Supply Pressure Hi Alert Point B-8 Upper Bench Set B-5
Supply Pressure Lo (PST Prohibited Alerts Enable) B-8 Valve Class B-5
Supply Pressure Lo (Pressure Alerts Enable) B-8 Valve Manufacturer B-5

104
Instruction Manual Handheld Communicator Menu Trees
D103785X012 February 2023

Function/Variable See Figure Function/Variable See Figure


Valve Model B-5 View Alert Records B-9, B-11
Valve Serial Number B-3, B-5 View/Edit Burst Messages B-7
Valve Size B-5 View/Edit Lag Time B-6
Valve Style B-5, B-7 Volume Booster B-5
Velocity Gain B-7 Write Protection B-1, B-3, B-5
Zero Power Condition B-7

Figure B-1. Hot Key Figure B-2. Online

Favorites HART Application


Hot Key 1 Offline
1 Instrument Mode 2 Online Online
2 Change Instrument Mode 3 Utility 1 Overview
3 Write Protection 4 HART Diagnostics 2 Configure
4 Change Write Protection 3 Service Tools

Figure B-3. Overview


1-7-1
1-6 Identification
Pressure Variables
1 HART Tag
1 Supply Pressure 1 2 HART Long Tag 2
2 Pressure A 3 Manufacturer
3 Pressure B 4 Model
4 Pressure A-B 5 Instrument Level 1-7-1-6
6 Device ID and Serial Numbers Device ID and Serial Numbers
7 Message
1 1 Device ID
8 Description
Overview 1-7 2 Valve Serial Number
3 Instrument Serial Number
1 Device Status Device Information 4 PWB Serial Number
2 Analog Input 1-7-2
3 Setpoint 1 Identification
2 Revisions Revisions
4 Travel
5 Drive Signal 3 Security 1 HART Universal Revision
6 Pressure Variables 2 Device Revision
7 Device Information 1-7-3 3 Hardware Revision
Security 4 Firmware Revision
1 Write Protection 5 DD Information
2 Change Write Protection

NOTES:
1 SUPPLY PRESSURE IS AVAILABLE FOR INSTRUMENT LEVEL AD, PD, AND ODV.
2 HART LONG TAG IS AVAILABLE WITH HART 7 ONLY.

Figure B-4. Guided Setup


2
Configure 2-1
1 Guided Setup Guided Setup
2 Manual Setup
1 Device Setup
3 Alert Setup
2 Auto Calibration
4 Calibration

105
Handheld Communicator Menu Trees Instruction Manual
February 2023 D103785X012

Figure B-5. Manual Setup > Mode Protection & Manual Setup > Instrument

2-2-1 2-2-2-1
2 Identification
Mode and Protection
Configure 1 HART Tag
1 Instrument Mode
1 Guided Setup 2 HART Long Tag 1
2 Change Instrument Mode
2 Manual Setup 3 Description
3 Write Protection
3 Alert Setup 4 Message
4 Change Write Protection
4 Calibration 5 Polling Address

2-2 2-2-2
Instrument 2-2-2-2
Manual Setup 1 Identification Serial Numbers
1 Mode and Protection 2 Serial Numbers 1 Instrument Serial Number
2 Instrument 3 Units 2 Valve Serial Number
3 Travel/Pressure Control 4 Terminal Box
4 Tuning 5 Analog Input Range 2-2-2-3
5 Valve and Actuator 6 Spec Sheet Units
6 Partial Stroke Test (PST) 7 Edit Instrument Time
1 Pressure Units
7 Outputs
2-2-2-6 2 Temperature Units
Spec Sheet 3 Analog Input Units
1 Units 2-2-2-4
2 Valve Terminal Box
3 Trim 1 Calibration Button
4 Actuator 2-2-2-6-3
2 Auxiliary Terminal Action 2
5 Accessories Trim 3 Edit Auxiliary Terminal Action 2

2-2-2-6-5 1 Seat Type


Accessories 2 Leak Class 2-2-2-5
3 Port Diameter Analog Input Range
1 Volume Booster
2 Quick Release 4 Port Type 1 Input Range Hi
3 Solenoid Valve 5 Flow Direction 2 Input Range Lo
4 Position Transmitter 6 Push Down To
5 Limit Switch Valve Open 7 Flow Tends To 2-2-2-6-1
8 Unbalanced Area Units
6 Limit Switch Valve Close
1 Travel Units
2-2-2-6-4 2 Length Units
Actuator 2-2-2-6-2 3 Area Units
Valve 4 Spring Rate Units
1 Actuator Manufacturer 5 Torque Units
2 Actuator Model 1 Valve Manufacturer
3 Actuator Size 2 Valve Model
4 Actuator Selection 3 Valve Serial Number 2-2-2-6-2-4
2-2-2-6-4-6 3 5 Travel 4 Valve Style Valve Style
6 Lever Style 5 Stem Diameter
Lever Style 3 1 Valve Style
7 Effective Area 6 Packing Type
1 Lever Style 2 Valve Size
8 Spring Rate 7 Valve Travel
2 Lever Arm Length 3 Valve Class
9 Air 8 Inlet/Outlet Pressures
9 Torque 3
2-2-2-6-2-7
2-2-2-6-4-9
Air Valve Travel
2-2-2-6-4-5
1 Air 1 Rated Travel
Travel 2 Actual Travel
2 Upper Bench Set
3 Lower Bench Set 1 Feedback Connection
4 Nominal Supply 2 Travel Sensor Motion
2-2-2-6-2-8
Inlet/Outlet Pressures
1 Inlet Pressure
2-2-2-6-2-9 2 Outlet Pressure
Torque 3

1 Dynamic Torque
NOTES:
2 Breakout Torque
1 HART LONG TAG IS AVAILABLE WITH HART 7.
2 AUXILIARY TERMINAL ACTION AND EDIT AUXILIARY TERMINAL ACTION ARE AVAILABLE WITH INSTRUMENT LEVEL ODV.
3 AVAILABLE WHEN VALVE IS ROTARY.

106
Instruction Manual Handheld Communicator Menu Trees
D103785X012 February 2023

Figure B-6. Manual Setup > Travel/Pressure Control

2-2-3
Travel/Pressure Control 2-2-3-3
Cutoffs and Limits
1 Travel/Pressure Select
2 Change Travel/Pressure Select 1 Hi Limit/Cutoff Select
3 Cutoffs/Limits 2 Hi Limit/Cutoff Point
4 Pressure Control 3 Hi Soft Cutoff Rate
5 Pressure Fallback 1 4 Lo Limit/Cutoff Select
2-2 6 Control Mode 5 Lo Limit/Cutoff Point
Manual Setup 7 Characterization 6 Lo Soft Cutoff Rate
8 Dynamic Response
1 Mode and Protection 2-2-3-4
2 Instrument 2-2-3-7 (HC)
2-2-3-8 (AD, PD, ODV) Pressure Control
3 Travel/Pressure Control
4 Tuning Dynamic Response 1 Pressure Range High
5 Valve and Actuator 1 SP Rate Open 2 Pressure Range Low
6 Partial Stroke Test (PST) 2 SP Rate Close
7 Outputs 3 View/Edit Lag Time 2-2-3-5 (AD, PD, ODV)
Pressure Fallback 1
2-2-3-6 (HC)
1 Tvl Dev Press Fallback
2-2-3-7 (AD, PD, ODV)
2 Tvl Dev Press Fallback Time
Characterization
3 Fallback Recovery
1 Input Characterization 4 Supply Pressure Lo Alert Point
2 Custom Characterization
2-2-3-5 (HC)
2-2-3-6 (AD, PD, ODV)
Control Mode
1 Control Mode
2 Change Control Mode
NOTE: 3 Restart Control Mode
1 PRESSURE FALLBACK IS AVAILABLE FOR INSTRUMENT LEVEL AD, PD, AND ODV.

107
Handheld Communicator Menu Trees Instruction Manual
February 2023 D103785X012

Figure B-7. Manual Setup > Tuning through Manual Setup > Outputs

2-2-4-1
Travel Tuning
2-2-4
1 Travel Tuning Set
Tuning 2 Proportional Gain
1 Travel Tuning 3 Velocity Gain
2 Pressure Tuning 4 MLFB Gain
2-2 3 Travel/Pressure Integral Settings 5 Integral Enable
Manual Setup 6 Integral Gain
2-2-4-3 7 Stabilize/Optimize
1 Mode and Protection Travel/Pressure Integral Settings
2 Instrument 1 Integral Dead Zone 2-2-4-2
3 Travel/Pressure Control Pressure Tuning
2 Integrator Limit
4 Tuning 1 Pressure Tuning Set
5 Valve and Actuator 2 Proportional Gain
2-2-5
6 Partial Stroke 1 3 MLFB Gain
7 Outputs Valve and Actuator
4 Integral Enable
1 Valve Style
WITHOUT I/O PACKAGE

5 Integral Gain
WITH I/O PACKAGE

2 Actuator Style
2-2-6-1
3 Feedback Connection
4 Relay Type Test Configuration
5 Zero Power Condition 1 PST Enable
6 Travel Sensor Motion 2 PST Start Point
7 Max Supply Pressure 3 PST Variables
2-2-6 4 Return Lead
WITH I/O PACKAGE
Partial Stroke 1 5 Short Duration PST
1 Test Configuration 6 Max Allowable Travel Movement
2-2-6 (HC, AD, PD)
2 Test Acceptance Criteria 7 Min Required Travel Movement
2-2-7 (ODV)
Outputs 3 PST Alert Behavior
4 PST Deferral Reason
1 Output Terminal Config 2-2-6-2
5 Last PST results
2 Limit Switch Configuration
Test Acceptance Criteria
3 Alert Switch Configuration 2-2-6-3
4 HART Var Assignments 2-2-6-1 (HC, AD, PD) 1 Outgoing Pressure Threshold
Partial Alert Behavior
5 Transmitter Output 2 Incoming Pressure Threshold
2-2-7-1 (ODV)
6 Burst Mode 1 PST Abnormal Criteria 3 High Friction Breakout Press
Output Terminal Config 2 PST Abort Criteria 4 Low Friction Breakout Press
2-2-6-6 (HC, AD, PD) 1 Output Terminal Enable 3 PST Result Criticality 5 Breakout Timeout
2-2-7-6 (ODV) 2 Function
Burst Mode
3 Fail Signal
1 Burst Enable
2 View/Edit Burst Messages 2
2-2-6-2 (HC, AD, PD)
2-2-7-2 (ODV) WITHOUT I/O PACKAGE 2-2-6-1 (HC, AD, PD)
2-2-6-4 (HC, AD, PD) 2-2-6 (HC, AD, PD) 2-2-7-1 (ODV)
2-2-7-4 (ODV) Limit Switch Configuration 2-2-7 (ODV)
HART Var Assignments Outputs HART Var Assignments
1 Limit Switch Trip Point
1 Primary Variable (PV) 2 Switch Closed 1 HART Var Assignments 1 Primary Variable (PV)
2 Secondary Variable (SV) 2 Burst Mode 2 Secondary Variable (SV)
3 Tertiary Variable (TV) 3 Tertiary Variable (TV)
4 Quaternary Variable (QV) 2-2-6-3 (HC, AD, PD) 4 Quaternary Variable (QV)
2-2-7-3 (ODV) 2-2-6-2 (HC, AD, PD)
Alert Switch Configuration 2-2-7-2 (ODV)
1 Alert Switch Source Burst Mode
1 Burst Enable
2 View/Edit Burst Messages 2

NOTES:
1 PARTIAL STROKE IS AVAILABLE FOR INSTRUMENT LEVEL ODV.
2 LABEL IS 'BURST COMMAND' FOR HART 5.

108
Instruction Manual Handheld Communicator Menu Trees
D103785X012 February 2023

Figure B-8. Alert Setup > Electronics through Travel History

2-3-1-1
2-3-1 Electronics Alerts Enable
Electronics 1 Drive Signal
2
Configure 1 Electronics Alerts Enable 2 Shutdown Activated
2 Electronic Alerts NE107 2 3 Output Circuit Error 4
1 Guided Setup 3 Electronics Alerts Shutdown
2 Manual Setup 2-3-1-2
3 Alert Setup 2-3-1-3
Electronics Alerts Shutdown Electronics Alerts NE107
4 Calibration
1 Drive Current Failure Shutdown 1 Drive Current Failure
2-3 2 Critical NVM Failure Shutdown 2 Drive Signal
Alert Setup 3 Non-Critical NVM Failure Shutdown 3 Critical NVM Failure
4 Flash Integrity Failure Shutdown 4 Non-Critical NVM Failure
1 Electronics
5 Reference Voltage Failure Shutdown 5 Flash Integrity Failure
2 Pressure
6 Reference Voltage Failure
3 Travel
7 Shutdown Activated
4 Travel History 2-3-2 8 Output Circuit Error 4
5 Partial Stroke 1 Pressure 2-3-2-1
6 Sensors
7 Alert Record/Status 1 Pressure Alerts Enable Pressure Alerts Enable
2 Pressure Alert NE107 2 1 Supply Pressure Hi
3 Supply Pressure 2 Supply Pressure Lo 3
4 Supply Pressure Hi Alert Point 3 Pressure Deviation
5 Supply Pressure Lo Alert Point 4 Port A Overpressurized
6 Pressure Deviation Alert Point
7 Pressure Deviation Time
8 Port A Pressure Limit 2-3-2-2
9 Output Pressure Limit Enable Pressure Alerts NE107
2-3-4-1
Travel History Alerts Enable 1 Supply Pressure Hi
2 Supply Pressure Lo 3
1 Cycle Count Hi 3 Pressure Deviation
2 Tvl Accum Hi 4 Port A Overpressurized
2-3-3
2-3-4 Travel
2-3-3-1
Travel History 1 Travel Alerts Enable Travel Alerts Enable
1 Travel History Alerts Enable 2 Travel Alerts NE107 2
3 Travel 1 Tvl Deviation
2 Travel History Alerts NE107 2 2 Tvl Hi Hi
3 Cycle Count/Travel Accum Deadband 4 Setpoint
5 Travel Alert DB 3 Tvl Lo Lo
4 Cycle Counter 4 Tvl Hi
5 Travel Accumulator 6 Travel Deviation
7 Travel Limit 5 Tvl Lo
8 Travel Limit/Cutoff 6 Tvl Limit/Cutoff Hi
2-3-4-5 7 Tvl Limit/Cutoff Lo
Travel Accumulator
2-3-4-2
1 Travel Accumulator 2-3-3-8 2-3-3-2
Travel History Alerts NE107 Travel Limit/Cutoff
2 Edit Travel Accumulator Travel Alerts NE107
3 Travel Accumulator Alert Point 1 Cycle Count High 1 Hi Limit/Cutoff Point 1 Travel Deviation
2 Travel Accumulator High 2 Lo Limit/Cutoff Point 2 Travel Hi Hi
3 Travel Lo Lo
2-3-4-4 4 Travel Hi
2-3-3-7
Cycle Counter Travel Limit 5 Travel Lo
6 Travel Limit/Cutoff Hi
1 Cycle Count 1 Travel Hi Hi Alert Point 7 Travel Limit/Cutoff Lo
2 Edit Cycle Counts 2 Travel Lo Lo Alert Point 2-3-3-6
3 Cycle Count High Alert Point 3 Travel Hi Alert Point Travel Deviation
4 Travel Lo Alert Point
1 Travel Deviation
2 Travel Deviation Alert Point
NOTES: 3 Travel Deviation Time
1 PARTIAL STROKE IS AVAILABLE FOR INSTRUMENT LEVEL ODV.
2 NE107 ALERTS ARE AVAILABLE FOR HART 7. ALL HART 5 FAST-KEY SEQUENCES WILL DECREASE BY ONE NUMBER AFTER THE NE107 ALERT CONFIGURATION ENTRY.
3 SUPPLY PRESSURE LO ALERT IS AVAILABLE FOR INSTRUMENT LEVEL AD, PD, AND ODV.
4 OUTPUT CIRCUIT ERROR IS AVAILABLE WHEN THE TRANSMITTER FUNCTION IS CONFIGURED.

109
Handheld Communicator Menu Trees Instruction Manual
February 2023 D103785X012

Figure B-9. Alert Setup > Partial Stroke through Alert Record/Status

2-3-5-1 (ODV)
Partial Stroke Alerts Enable
1 PST Abnormal
2-3-5 (ODV) 2 PST Pass
3 PST Prohibited
Partial Stroke
2-3
1 Partial Stroke Alerts Enable 2-3-5-2 (ODV)
Alert Setup
2 Partial Stroke Alerts NE107 2 Partial Stroke Alerts NE107
1 Electronics 3 Partial Stroke Alerts Shutdown
2 Pressure 4 PST Prohibited Alerts Enable 1 PST Abnormal
3 Travel 2 PST Pass
4 Travel History 3 PST Prohibited
5 Partial Stroke 1 2-3-5-4 (ODV) 4 Program Flow Failure
6 Sensors PST Prohibited Alerts Enable
7 Alert Record/Status 2-3-5-3 (ODV)
1 PST Prohibited Electronic Alerts Partial Stroke Alerts Shutdown
2 Travel Sensor Failure
2-3-6 (HC, AD, PD) 1 Program Flow Failure Shutdown
3 Pressure Sensor Failure
2-3-7 (ODV) 4 Temp Sensor Failure
Alert Record/Status 5 Pressure Fallback Active 2-3-5-4-1 (ODV)
1 Alert Record/Status Alerts Enable 6 Supply Pressure Lo
PST Prohibited Electronic Alerts
2 Alert Record/Status Alerts NE107 2 7 Travel Deviation
3 View Alert Records 1 Critical NVM Failure
4 Clear Records 2 Drive Current Failure
5 Instrument Alert Record 3 Reference Voltage Failure
6 Edit Instrument Time 4 Minor Loop Sensor Failure
5 Flash Integrity Failure

2-3-6-2 (HC, AD, PD)


2-3-7-2 (ODV)
Alert Record/Status Alerts NE107 2-3-5 (HC, AD, PD)
2-3-6 (ODV) 2-3-5-1 (HC, AD, PD)
1 Alert Record Not Empty
2 Alert Record Full Sensors 2-3-6-1 (ODV)
3 Instrument Time is Approximate 1 Sensor Alerts Enable Sensor Alerts Enable
4 Calibration in Progress 2 Sensor Alerts NE107 2 1 Pressure Fallback Active 3
5 Autocal in Progress 3 Sensor Alerts Shutdown
6 Diagnostic in Progress 4 Change Travel/Pressure Select 3
7 Diagnostic Data Avail 5 Travel/Pressure Select 3
8 Integrator Sat Hi 6 Fallback Recovery 3 2-3-5-2 (HC, AD, PD)
9 Integrator Sat Lo 2-3-6-2 (ODV)
Sensor Alerts NE107
3 2-3-5-4 (HC, AD, PD)
2-3-6 -1 (HC, AD, PD) 1 Travel Sensor Failure
2-3-6-4 (ODV)
2-3-7-1 (ODV) 2 Pressure Sensor Failure
Change Travel/Pressure Select
3 Temp Sensor Failure
Alert Record/Status Alerts Enable
1 Travel Control 4 Minor Loop Sensor Failure
1 Alert Record Not Empty 2 Pressure Control 5 Pressure Fallback Active 3
2 Alert Record Full 3 Fallback-Sensor Failure
3 Instrument Time is Approximate 4 Fallback-Sensor/Tvl Deviation 2-3-5-3 (HC, AD, PD)
4 Calibration in Progress 2-3-6-3 (ODV)
5 Autocal in Progress Sensor Alerts Shutdown
6 Diagnostic in Progress 1 Travel Sensor Failure Shutdown
7 Diagnostic Data Avail 2 Pressure Sensor Failure Shutdown
8 Integrator Sat Hi 3 Temp Sensor Failure Shutdown
9 Integrator Sat Lo 4 Minor Loop Sensor Failure Shutdown

NOTES:
1 PARTIAL STROKE IS AVAILABLE FOR INSTRUMENT LEVEL ODV.
2 NE107 ALERTS ARE AVAILABLE FOR HART 7. ALL HART 5 FAST-KEY SEQUENCES WILL DECREASE BY ONE NUMBER AFTER THE NE107 ALERT CONFIGURATION ENTRY.
3 PRESSURE FALLBACK MENU ITEMS ARE AVAILABLE FOR INSTRUMENT LEVEL AD, PD, AND ODV.

110
Instruction Manual Handheld Communicator Menu Trees
D103785X012 February 2023

Figure B-10. Calibration

2
Configure HART 5
2-4-1
1 Guided Setup Travel Calibration
2 Manual Setup
3 Alert Setup 1 Auto Calibration
4 Calibration 2 Last AutoCal Status
3 Manual Calibration
4 Calibration Record

HART 5
2-4
Calibration HART 7
HART 7 2-4-1
1 Travel Calibration Travel Calibration
2 Relay Adjust
3 Sensor Calibration 1 Auto Calibration
4 PST Calibration 1 2 Last AutoCal Status
3 Manual Calibration
2-4-3 4 Calibration Type
Sensor Calibration 5 Calibration Time
1 Travel Sensor Adjust 6 Calibrator
2 Pressures Sensors
3 Analog Input 2
NOTES:
1 PST CALIBRATION IS AVAILABLE FOR INSTRUMENT LEVEL ODV.
2 ANALOG INPUT IS NOT AVAILABLE WHEN THE DIP SWITCH IS SET TO MULTI-DROP.

Figure B-11. Service Tools 3-4-1-4


3-2 Pressure Variables
Alert Record 1 Supply Pressure 2
3 2 Pressure A
1 View Alert Records
Service Tools 2 Clear Records 3 Pressure B
1 Device Status 4 Pressure A-B
2 Alert Record 3-3 3-4-1
3 Diagnostics Travel/Pressure
Diagnostics
4 Variables 1 Setpoint
5 Maintenance 1 Stroke Valve
2 Travel
6 Simulate 5 2 Partial Stroke Test 1
3 Drive Signal
4 Pressure Variables
3-4 5 Change Travel/Pressure Select
3-5
Maintenance Variables 6 Travel/Pressure Select
1 Stabilize/Optimize 1 Travel/Pressure 7 Fallback Recovery 2
2 Restart Processor 2 Control Mode
3 Reset PST Abnormal Alert 3 3 Analog Input
4 Change to HART 5 4 4 Temperature 3-4-2
5 Travel Counts Control Mode
6 Characterization
7 Travel History 1 Control Mode
8 Run Time Extremes 2 Change Control Mode
3 Restart Control Mode
3-4-8
Run Time Extremes 3-4-6
3-4-7 Characterization
1 Maximum Recorded Temperature
Travel History 1 Input Characterization
2 Minimum Recorded Temperature
2 Custom Characterization
3 Days Powered Up 1 Cycle Count
4 Number of Power Ups 2 Travel Accumulator

NOTES:
1 PARTIAL STROKE TEST IS AVAILABLE IN INSTRUMENT LEVEL ODV.
2 SUPPLY PRESSURE AND FALLBACK RECOVERY ARE AVAILABLE FOR AD, PD, ODV.
3 RESET PST ABNORMAL ALERT IS AVAILABLE IN INSTRUMENT LEVEL ODV.
4 LABEL IS 'CHANGE TO HART 7' FOR HART 5.
5 HART 7 ONLY.

111
Glossary Instruction Manual
February 2023 D103785X012

Glossary
Alert Point Control Loop
An adjustable value that, when exceeded, An arrangement of physical and electronic
activates an alert. components for process control. The electronic
components of the loop continuously measure
one or more aspects of the process, then alter
Algorithm those aspects as necessary to achieve a desired
A set of logical steps to solve a problem or process condition. A simple control loop
accomplish a task. A computer program contains measures only one variable. More sophisticated
one or more algorithms. control loops measure many variables and
maintain specified relationships among those
variables.
Alphanumeric
Consisting of letters and numbers. Control Mode
Defines where the instrument reads its set point.
The following control modes are available for a
Analog Input Units FIELDVUE Instrument:
Units in which the analog input is displayed and Analog The instrument receives its travel set
maintained in the instrument. point over the 4‐20 mA loop.
Digital The instrument receives its set point
digitally, via the HART communications link.
ANSI (acronym) Test This is not a user‐selectable mode. A
The acronym ANSI stands for the American handheld communicator or ValveLink software
National Standards Institute places the instrument in this mode whenever it
needs to move the valve, such as for calibration or
diagnostic tests.
ANSI Class
Valve pressure/temperature rating.
Control Mode, Restart
Determines the instrument control mode after a
restart. See Control Mode for the available restart
Bench Set control modes.
Pressure, supplied to an actuator, required to
drive the actuator through rated valve travel.
Expressed in pounds per square inch. Controller
A device that operates automatically to regulate a
controlled variable.
Byte
A unit of binary digits (bits). A byte consists of
eight bits.
Current‐to‐Pressure (I/P) Converter
An electronic component or device that converts
a milliamp signal to a proportional pneumatic
pressure output signal.
Calibration Location
Where the instrument was last calibrated; either
in the factory or in the field. Cycle Counter
The capability of a FIELDVUE instrument to record
the number of times the travel changes direction.
Configuration The change in direction must occur after the
Stored instructions and operating parameters for deadband has been exceeded before it can be
a FIELDVUE Instrument. counted as a cycle.

112
Instruction Manual Glossary
D103785X012 February 2023

Cycle Counter Alert Drive Signal Alert


Checks the difference between the Cycle Counter Checks the drive signal and calibrated travel. If
and the Cycle Counter Alert Point. Cycle Counter one of the following conditions exists for more
Alert is active when the cycle counter value than 20 seconds, the Drive Signal Alert is active. If
exceeds the Cycle Counter Alert Point. It clears none of the conditions exist, the alert is cleared.
after you reset the Cycle Counter to a value less If Zero Power Condition = Closed
than the alert point. The alert is active when:
drive signal <10% and calibrated travel >3%
drive signal >90% and calibrated travel <97%
Cycle Counter Alert Point If Zero Power Condition = Open
An adjustable value which, when exceeded, The alert is active when:
activates the Cycle Counter Alert. Valid entries drive signal <10% and calibrated travel <97%
are 0 to 4 billion cycles.
drive signal >90% and calibrated travel >3%

Equal Percentage
A valve flow characteristic where equal
Cycle Counter Deadband increments of valve stem travel produce equal
Region around the travel reference point, in percentage changes in existing flow. One of the
percent of ranged travel, established at the last input characteristics available for a FIELDVUE
increment of the Cycle Counter. The deadband Instrument. See also, Linear and Quick Opening.
must be exceeded before a change in travel can
be counted as a cycle. Valid entries are 0% to Feedback Signal
100%. Typical value is between 2% and 5%. Indicates to the instrument the actual position of
the valve. The travel sensor provides the feedback
signal to the instrument printed wiring board
assembly.
Deviation
Usually, the difference between set point and Firmware Revision
process variable. More generally, any departure The revision number of the instrument firmware.
from a desired or expected value or pattern. Firmware is a program that is entered into the
instrument at time of manufacture and cannot be
changed by the user.

Device ID Free Time


Unique identifier embedded in the instrument at Percent of time that the microprocessor is idle. A
the factory. typical value is 25%. The actual value depends on
the number of functions in the instrument that
are enabled and on the amount of
communication currently in progress.
Device Revision Full Ranged Travel
Revision number of the interface software that Current, in mA, that corresponds with the point
permits communication between a handheld where ranged travel is maximum, i.e., limited by
communicator and the instrument. the mechanical travel stops.

Gain
The ratio of output change to input change.
Drive Signal
The signal to the I/P converter from the printed Hardware Revision
wiring board. It is the percentage of the total Revision number of the Fisher instrument
microprocessor effort needed to drive the valve hardware. The physical components of the
fully open. instrument are defined as the hardware.

113
Glossary Instruction Manual
February 2023 D103785X012

HART (acronym) Instrument Protection


The acronym HART stands for Highway Determines if commands from a HART device can
Addressable Remote Transducer. calibrate and/or configure certain parameters in
the instrument. There are two types of
instrument protection:
HART Universal Revision Configuration and Calibration: Prohibits changing
Revision number of the HART Universal protected setup parameters; prohibits
Commands which are the communications calibration.
protocol for the instrument. None: Permits both configuration and calibration.
The instrument is ”unprotected.”

Input Characteristic Instrument Serial Number


The relationship between the ranged travel and
The serial number assigned to the printed wiring
ranged input. Possible values include: linear,
board by the factory but can be changed during
equal percentage, and quick opening.
setup. The instrument serial number should
match the serial number on the instrument
nameplate.
Input Current
The current signal from the control system that
serves as the analog input to the instrument. See Leak Class
also Input Signal. Defines the allowable leakage by a valve when it is
closed. Leak class numbers are listed in two
standards: ANSI/FCI 70‐2 and IEC 534‐4.
Input Range
The analog input signal range that corresponds to
the travel range. Linear
A valve flow characteristic where changes in flow
rate are directly proportional to changes in valve
Input Signal stem travel. One of the input characteristics
The current signal from the control system. The available for a FIELDVUE instrument. See also,
input signal can be displayed in milliamperes or in Equal Percentage and Quick Opening.
percent of ranged input.
Linearity, dynamic
Linearity (independent) is the maximum
Instrument Level deviation from a straight line best fit to the
Determines the functions available for the
opening and closing curves and a line
instrument. See table 5‐1. representing the average value of those curves.

Instrument Mode Memory


Determines if the instrument responds to its A type of semiconductor used for storing
analog input signal. There are two instrument programs or data. FIELDVUE instruments use
modes: three types of memory: Random Access Memory
In Service: For a fully functioning instrument, the (RAM), Read Only Memory (ROM), and
instrument output changes in response to analog Non‐Volatile Memory (NVM). See also these
input changes. Typically changes to setup or listings in this glossary.
calibration cannot be made when the instrument
mode is In Service.
Out of Service: The instrument output does not Menu
change in response to analog input changes A list of programs, commands, or other activities
when the instrument mode is Out of Service. that you select by using the arrow keys to
Some setup parameters can be changed only highlight the item then pressing ENTER, or by
when the instrument mode is Out of Service. entering the numeric value of the menu item.

114
Instruction Manual Glossary
D103785X012 February 2023

Minimum Closing Time Primary Master


Minimum time, in seconds, for the travel to Masters are communicating devices. A primary
decrease through the entire ranged travel. This master is a communicating device permanently
rate is applied to any travel decrease. Valid entries wired to a field instrument. Typically, a
are 0 to 400 seconds. Deactivate by entering a HART‐compatible control system or a computer
value of 0 seconds. running ValveLink software is the primary master.
In contrast, a secondary master is not often
permanently wired to a field instrument. A
handheld communicator or a computer running
Minimum Opening Time ValveLink software communicating through a
Minimum time, in seconds, for the travel to HART modem could be considered a secondary
increase through the entire ranged travel. This master.
rate is applied to any travel increase. Because of Note: If one type of master takes an instrument
friction, actual valve travel may not respond in Out Of Service, the same type must put it In
exactly the same time frame. Valid entries are 0 Service. For example, if a device set up as a
to 400 seconds. Deactivate by entering a value of primary master takes an instrument Out Of
0 seconds. Service, a device set up as a primary master must
be used to place the instrument In Service.

Quick Opening
Non‐Volatile Memory (NVM) A valve flow characteristic where most of the
A type of semiconductor memory that retains its change in flow rate takes place for small amounts
contents even though power is disconnected. of stem travel from the closed position. The flow
NVM contents can be changed during characteristic curve is basically linear through the
configuration unlike ROM which can be changed first 40 percent of stem travel. One of the input
only at time of instrument manufacture. NVM characteristics available for a FIELDVUE
stores configuration restart data. Instrument. See also, Equal Percentage and
Linear.

Random Access Memory (RAM)


Parallel A type of semiconductor memory that is normally
Simultaneous: said of data transmission on two or used by the microprocessor during normal
more channels at the same time. operation that permits rapid retrieval and storage
of programs and data. See also Read Only
Memory (ROM) and Non‐Volatile Memory (NVM).

Polling Address Rate


Address of the instrument. If the digital valve Amount of change in output proportional to the
controller is used in a point‐to‐point rate of change in input.
configuration, set the polling address to 0. If it is
used in a multidrop configuration, or split range
application, set the polling address to a value Read‐Only Memory (ROM)
from 0 to 15 for HART 5 and 0 to 63 for HART 7. A memory in which information is stored at the
time of instrument manufacture. You can
examine but not change ROM contents.

Pressure Sensor Seat Load


A FIELDVUE instrument internal device that Force exerted on the valve seat, typically
senses pneumatic pressure. The DVC6000 HW2 expressed in pounds force per lineal inch of port
has three pressure sensors: one to sense supply circumference. Seat load is determined by shutoff
pressure and two to sense the output pressures. requirements.

115
Glossary Instruction Manual
February 2023 D103785X012

Set Point Filter Time (Lag Time) Travel Accumulator Deadband


The time constant, in seconds, for the first‐order Region around the travel reference point
input filter. The default of 0 seconds will bypass established at the last increment of the
the filter. accumulator. This region must be exceeded
before a change in travel can be accumulated.
Valid entries are 0% to 100%.
Software
Microprocessor or computer programs and Travel Alert
routines that reside in alterable memory (usually Checks the ranged travel against the travel high
RAM), as opposed to firmware, which consists of and low alert points. The travel alert is active if
programs and routines that are programmed into either the high or low point is exceeded. Once a
memory (usually ROM) when the instrument is high or low point is exceeded, the ranged travel
manufactured. Software can be manipulated must clear that point by the Travel Alert
during normal operation, firmware cannot. Deadband before the alert clears. Four travel
alerts are available: Travel Alert Hi, Travel Alert Lo,
Travel Alert Hi Hi, and Travel Alert Lo Lo.
Stroking Time
The time, in seconds, required to move the valve
from its fully open position to fully closed, or vice
Travel Alert Deadband
versa. Travel, in percent of ranged travel, required to
clear a travel alert, once it is active. Valid entries
are -25% to 125%.
Temperature Sensor
A device within the FIELDVUE instrument that Travel Alert High Point
measures the instrument's internal temperature. Value of the travel, in percent of ranged travel,
which, when exceeded, sets the Travel Alert Hi
alert. Valid entries are -25% to 125%.
Travel
Movement of the valve stem or shaft which Travel Alert High High Point
changes the amount the valve is open or closed. Value of the travel, in percent of ranged travel,
which, when exceeded, sets the Travel Alert Hi Hi
alert. Valid entries are -25% to 125%.
Travel Accumulator
The capability of a FIELDVUE instrument to record Travel Alert Low Point
total change in travel. The value of the Travel Value of the travel, in percent of ranged travel,
Accumulator increments when the magnitude of which, when exceeded, sets the Travel Alert Lo
the change exceeds the Travel Accumulator alert. Valid entries are -25% to 125%.
Deadband. To reset the Travel Accumulator, set it
to zero.
Travel Alert Low Low Point
Value of the travel, in percent of ranged travel,
Travel Accumulator Alert which, when exceeded, sets the Travel Alert Lo Lo
Checks the difference between the Travel alert. Valid entries are -25% to 125%.
Accumulator value and the Travel Accumulator
Alert Point. The Travel Accumulator Alert is active Travel Cutoff
when the Travel Accumulator value exceeds the Defines the cutoff point for the travel, in percent
Travel Accumulator Alert Point. It clears after you of ranged travel. There are two travel cutoffs:
reset the Travel Accumulator to a value less than high and low. Once travel exceeds the cutoff, the
the alert point. drive signal is set to either maximum or
minimum, depending on the Zero Control Signal
and if the cutoff is high or low. Minimum opening
Travel Accumulator Alert Point time or minimum closing time are not in effect
An adjustable value which, when exceeded, while the travel is beyond the cutoff. Use the
activates the Travel Accumulator Alert. Valid travel cutoff to obtain the desired seat load or to
entries are 0% to 4 billion %. be sure the valve is fully open.

116
Instruction Manual Glossary
D103785X012 February 2023

Travel Deviation Travel Sensor


The difference between the analog input signal A device within the FIELDVUE instrument that
(in percent of ranged input), the “target” travel, senses valve stem or shaft movement. The travel
and the actual “ranged” travel. sensor in the DVC6000 HW2 is mechanically
connected to the valve stem or shaft.

Travel Deviation Alert Travel Sensor Motion


Checks the difference between the target and the Increasing or decreasing air pressure causes the
ranged travel. If the difference exceeds the Travel shaft to rotate clockwise or counterclockwise.
Deviation Alert Point for more than the Travel Device Setup asks if it can move the valve to
Deviation Time, the Travel Deviation Alert is determine travel.
active. It remains active until the difference is less
than the Travel Deviation Alert Point. Tuning
The adjustment of control terms or parameter
values to produce a desired control effect.
Travel Deviation Alert Point
An adjustable value for the target travel and the Tuning Set
ranged travel difference, expressed in percent, Preset values that identify gain settings for a
When this value is exceeded by the travel FIELDVUE instrument. The tuning set and supply
deviation for more than the Travel Deviation pressure together determine an instrument's
Time, the Travel Deviation Alert is active. Valid response to input signal changes.
entries are 0% to 100%. Typically this is set to 5%.
Watch Dog Timer
A timer that the microprocessor must rearm
Travel Deviation Time periodically. If the microprocessor is unable to
The time, in seconds. that the travel deviation rearm the timer, the instrument goes through
must exceed the Travel Deviation Alert Point reset.
before the alert is active. Valid entries are 1 to 60
seconds.
Zero Power Condition
The position of the valve (open or closed) when
the electrical power to the instrument is
Travel Limit removed. Zero Power Condition (ZPC) is
A setup parameter that defines the maximum determined by relay and actuator action as
allowable travel (in percent of ranged travel) for follows:
the valve. During operation, the travel target will
not exceed this limit. There are two travel limits: Single Acting Direct (Relay C) Upon loss of
high and low. Typically the travel limit low will be electrical power instrument goes to zero air
used to keep the valve from going completely output at port A.
closed. Double Acting (Relay A) Upon loss of electrical
power instrument goes to full supply air output at
port B. A goes to zero air output.
Travel Range Single Acting Reverse (Relay B) Upon loss of
Travel, in percent of calibrated travel, that electrical power instrument goes to full supply air
corresponds to the input range. output at Port B.

117
Index Instruction Manual
February 2023 D103785X012

Index Analog Input, 53


Pressure Sensors, 48
PST, 56
Pushbutton, 47
A Relay Adjustment, 54
Actuator Compatibility, 6 Sensor, 48
Travel, 44
Actuator Style, 32 Auto, 44
Alert Record, 58 Manual, 46
Travel Sensor, 49
Alert Record Full, 59 Travel Sensor Adjust, 49
Alert Record Not Empty, 59 Calibration (CAL) Button, 21
Alert Reporting, 58 Calibration in Progress, 59
Alert Settings, Default, 58 Certifications
Alert Setup, 42 Brazil, INMETRO, 6
China, CCC, 6
Alert Switch, Function, Output Terminal India, PESO CCOE, 6
Configuration, 40 Lloyds Register, 6
Alert Switch Source, 40 Russia, Kazakhstan and Belarus, CUTR, 6
South Africa, SANS, 6
AMS Suite: Intelligent Device Manager, 4
South Korea, KTL, 6
Analog Calibration Adjust, 46 United Arab Emirates, ESMA, 6
Analog Input Range, 21 Change Control Mode, 24
Input Range Hi, 21 Characterization, 25
Input Range Lo, 22 Custom Characterization, 25
Analog Input Units, 21 Input Characterization, 25
ATEX, Hazardous Area Approvals, 6 China Compulsory Certification (CCC), China,
Certifications, 6
Auto Calibration, 19, 44
Error Messages, 45 Communication Protocol, HART 7 or HART 5, 5
Compliance Voltage, 11
Auto Partial Stroke Test, 63
Configuration, Initial, 3
Autocal in Progress, 59
Connections, 6
Autocalibrate Electrical, 3
Advanced Settings, 19 Pneumatic, 3
Standard, 19
Without Biases, 19 Construction Materials, 6

Auxiliary Terminal, Wiring Length Guidelines, 12 Control Mode, 24


Change Control Mode, 24
Auxiliary Terminal Action, 21 Control Mode, 24
Restart Control Mode, 24
B Critical NVM Failure, 59
crossover adjustment, 44
Breakout Timeout, 36
CSA, Hazardous Area Approvals, 6
Burst Mode, 41
Custom Characterization, Defining, 25
Burst Operation, setting for Tri-Loop, 18 Customs Union Technical Regulations (CUTR), Russia,
Kazakhstan and Belarus, Certifications, 6
C Cutoffs and Limits, 23
Hi Limit/Cutoff Point, 23
Calibration, 43 Hi Limit/Cutoff Select, 23

118
Instruction Manual Index
D103785X012 February 2023

Lo Limit/Cutoff Point, 23 Fallback Recovery, 24


Lo Limit/Cutoff Select, 23 Fallback-Sensor Failure, Travel/Pressure Select, 23
Cycle Counter High, 59 Fallback-Sensor/Tvl Deviation, Travel/Pressure Select,
23
D Fast Key Sequences, handheld communicator, 102
Field Device Malfunction, 60
Deadband, Principle of Operation, 61
Filter Settings, Typical Lead/Lag, 27
Declaration of SEP, 7
Flash Integrity Failure, 60
Default Parameters, Detailed Setup, 19
FM, Hazardous Area Approvals, 6
Descriptor, 21
frequency shift keying (FSK), 99
Device Diagnostics, 58
Function, Output Terminal Configuration
Device Information, 57
Alert Switch, 40
Device Status, 58 Limit Switch, 40
Diagnostic Data Available, 59 Transmitter, 40

Diagnostics, 63
Diagnostics in Progress, 59 G
Digital Calibration Adjust, 46 Gain Values
Pressure Tuning Sets, 31
DIP Switch, Setting, 73
Travel Tuning Sets, 28
Drive Current Failure, 59
Gauges, Tire Valves, & Pipe Plugs
Drive Signal Alert, 59 Parts List, 92
Dynamic Response, 27 Replacing, 76
Lag Time, 27 Guided Setup, 19
SP Rate Close, 27
SP Rate Open, 27
H
E Handheld Communicator Menu Trees, 102
HART Command 48, 58
Edit Instrument Time, 22
HART Communication, principle of operation, 99
Educational Services, 8
HART Filter, 9
Electrical Classification, 6
Part Numbers, 92
Electrical Connections, 3
HART Long Tag, 20
Electrical Housing, 6 HART Tag, 20
Electromagnetic Compatibility, 6 HART Tri‐Loop, 17
EMC Summary Results, Immunity, 7 Installation Flowchart, 17
Emirates Authority for Standardization and Metrology HART Universal Revision, Change, 42
(ESMA), United Arab Emirates, Certifications, 6
HART Variable Assignments, 41
End Point Pressure Deviation, 60 HART communications protocol, 3
Expert tuning, travel tuning, 28, 31 Hazardous Area Approvals , CSA, FM, ATEX, IECEx, 6
Hi Limit/Cutoff Point, 23
F Hi Limit/Cutoff Select, 23
Fail Signal, Output Terminal Configuration, 40 Hi Soft Cutoff Rate, 23

119
Index Instruction Manual
February 2023 D103785X012

Humidity Testing Method, 6


K
Korea Testing Laboratory (KTL), South Korea,
I Certifications, 6

I/P Converter
Parts List, 90 L
Removing, 72
Lag Time, 27
Replacing, 72
Replacing Filter, 71 Lead/Lag, 27
typical filter settings, 27
IECEx, Hazardous Area Approvals, 6
Lead/Lag Time, 27
Incoming Pressure Threshold, 38
Lightning and Surge Protection, 6
Incoming Ramp Rate, 36 Limit Switch, Function, Output Terminal
Independent Linearity, 5 Configuration, 40
Limit Switch Trip Point, 40
Input Characterization, 25
Lloyds Register, Marine Type Approval, 6
Input Impedance, 6
Lo Limit/Cutoff Point, 23
Input Range, 21
Lo Limit/Cutoff Select, 23
Input Range Hi, 21
Lo Soft Cutoff Rate, 23
Input Range Lo, 22 Loop Current Validation Alert, 60
Input Signal, 5
Installation, 3 M
Instrument Level, Capabilities, 4 Maintenance and Troubleshooting, 67
Instrument Mode, 20 Manual Calibration, 46
Instrument Time, Edit, 22 Manual Setup, 19

Instrument Time is Approximate, 60 Maximum Cable Capacitance, 12


Maximum Output Capacity, 5
Instument Serial Number, 21
maximum supply pressure, 33
Integral Dead Zone, Travel/Pressure Integral Settings,
31 Menu Trees, Handheld Communicator, 102

Integral Enable Message, 21


Pressure Tuning, 31 Minimum Travel Movement, 35
Travel Tuning, 30
Minor Loop Sensor Failure, 60
Integral Gain MLFB Gain
Pressure Tuning, 31 Pressure Tuning, 31
Travel Tuning, 30 Travel Tuning, 30
Integral Setting, 31 Module Base
Removal, 68
Integrator Limit, Travel/Pressure Integral Settings, 32
Replacing, 70
Integrator Saturated High, 60 Module Base, Parts List, 90
Integrator Saturated Low, 60 Module Base Maintenance, 68
Internal Sensor Out of Limits, 60 Mountings, 5

120
Instruction Manual Index
D103785X012 February 2023

N Prohibited, 39
ValveLink software, 64
National Institute of Metrology, Quality, and Parts
Technology (INMETRO), Brazil, Certifications, 6 Common Parts, 90
natural gas, as supply medium, 67 Feedback Parts, 92
Gauges, Tire Valves, & Pipe Plugs, 92
NE107 Category, Alert Settings, 58 HART Filters, 92
Non-Critical NVM, 60 I/P Converter Assembly, 90
Kits, 89
Module Base, 90
O ordering, 89
Printed Wiring Board Assembly, 91
Offline / Failed , 60 Relay, 91
Options, 7 Terminal Box, 91

Outgoing Pressure Threshold, 36 Petroleum and Explosives Safety Organisation - Chief


Controller of Explosives (PESO CCOE), India,
Outgoing Ramp Rate, 36 Certifications, 6
Output Circuit Error , 60 Pneumatic Connections, 3
Output Pressure Limit Enable, 34 Pneumatic Relay
Parts List, 91
Output Pressure Sensor, Calibration, 48
Removing, 75
Output Signal, 5 Replacing, 75
Output Terminal Configuration, 40 Polling Address, 21
Output Terminal Enable, 40 Port A Overpressurized, 60
Outputs, 40 Position Transmitter, 40
HART Variable Assignments, 41 Pressure Control, 24
Output Terminal Configuration, 40 Pressure Range High, 24
Switch Configuration, 40 Pressure Range Lo, 24
Transmitter Output, 41 Travel/Pressure Select, 23
Overview, 57 Pressure Fallback Active, 60
Pressure Range High, 24
P Pressure Range Lo, 24
Partial Stroke Parameters, 35 Pressure Sensor Failure , 60
Breakout Timeout, 36 Pressure Sensors, Calibration, 48
Incoming Pressure Threshold, 38
Pressure Tuning, 31
Incoming Ramp Rate, 36
Minimum Travel Movement, 35 Pressure Tuning Set, 31
Outgoing Pressure Threshold, 36 Pressure Tuning Sets, Gain Values, 31
Outgoing Ramp Rate, 36
Return Lead, 36 Pressure Units, 21
Short Duration PST, 35 Principle of Operation
Partial Stroke Test (PST) DVC6200, 99
Abnormal Criteria, 38 HART Communication, 99
Abort Criteria, 38 Printed Wiring Board Assembly
Automatic (scheduled), 63 Parts List, 91
Auxiliary Terminal, Local Pushbutton, 63 Removing, 73
handheld communicator, 64 Replacing, 73
Parameters, 34 Setting DIP Switch, 73

121
Index Instruction Manual
February 2023 D103785X012

Proportional Gain Steady‐State Air Consumption, 5


Pressure Tuning, 31 Stroke Valve, 63
Travel Tuning, 30
Supply Pressure, 5
PST Calibration, 56
Supply Pressure High, 61
Pushbutton Calibration, 47
Supply Pressure Low, 61
Supply Pressure Sensor, Calibration, 49
R Switch, 40
Reference Voltage Failure, 61 Switch Closed, 41
Related Documents, 8 Switch Configuration, 40
Relay Adjustment, 54 Alert Switch Source, 40
Limit Switch Trip Point, 40
Relay Type, 32 Switch Closed, 41
Remote Travel Sensor Connections
Using a 10 kOhm External Potentiometer as, 13
Using a Two-Resistor Series as, 15 T
Restart Control Mode, 24 Temperature Limits, Operating Ambient, 5
Restart Processor, 84 Temperature Sensor Failure, 61
Return Lead, 36 Temperature Units, 21
Terminal Box, 21
S Auxiliary Terminal Action, 21
Calibration (CAL) Button, 21
Sensor Calibration, 48 Parts List, 91
Removing, 76
Serial Number Replacing, 77
Instrument, 21
Valve, 21 Transmitter, 40
Function, Output Terminal Configuration, 40
Service Tools, 58
Alert Record, 58 Transmitter Output, 41
Device Status, 58 Travel Accumulator High, 61
Variables, 65
Travel Alert Hi, 61
Set Point Filter Lag Time, 27
Travel Alert Hi-Hi, 61
Set Point Filter Lead/Lag Time, 27 Travel Alert Lo, 61
Short Duration PST, 35 Travel Alert Lo-Lo, 61
Solenoid Valve, Health Monitoring, 64 Travel Calibration, 44
South Africa National Standards (SANS), Certifications, Travel Control, Travel/Pressure Select, 23
6
Travel Cutoff Hi, 61
SP Rate Close, 27
Travel Cutoff Lo, 61
SP Rate Open, 27
Travel Deviation, 61
Spec Sheet, 22
Travel Sensor
Special App, Relay, 32 Adjusting
Specifications, 4 DVC6015, 49
DVC6025, 51
Stabilize/Optimize, 30
DVC6035, 49
Status & Primary Purpose Variables, 57 Parts List, 92

122
Instruction Manual Index
D103785X012 February 2023

Removing
DVC6015, 78
U
DVC6025, 79 Units
DVC6030, 79 Analog Input, 21
Replacing Pressure, 21
DVC6015, 79 Temperature, 21
DVC6025, 80
DVC6035, 82
Travel Sensor Adjust, 49 V
Travel Sensor Failure, 61 Valve Serial Number, 21
Travel Sensor Motion, 33 Valve Style, 32
Travel Tuning, 28 ValveLink software, 4
Stabilize/Optimize, 30
Variable out of Range, 61
Travel Tuning Set, 28
Variables, 65
Travel Tuning Sets, Gain Values, 28 Status & Primary Purpose, 57
Travel/Pressure Control, 23 Velocity Gain, Travel Tuning, 30
Control Mode, 24
Cutoffs and Limits, 23 Vibration Testing Method, 6
Fallback Recovery, 24 Voltage Available, 9
Pressure Control, 24 Checking, 84
Pressure Fallback, 24
Travel/Pressure Select, 23
Tvl Dev Press Fallback, 24 W
Tvl Dev Press Fallback Time, 24
Weight
Travel/Pressure Select, 23
DVC6005 HW2 base unit, 6
Fallback-Sensor/Tvl Deviation, 23
DVC6015 feedback unit, 6
Pressure Control, 23
DVC6025 feedback unit, 6
Pressure-Sensor Failure, 23
DVC6035 feedback unit, 6
Travel Control, 23
Wiring Practices, 9
Troubleshooting, Instrument, 84
Control System Requirements, 9
Tuning, 28 Compliance Voltage, 11
Integral Settings, 31 HART Filter, 9
Pressure, 31 Voltage Available, 9
Travel, 28 Maximum Cable Capacitance, 12
Tuning Set Write Protection, 20
Pressure, 31
Travel, 28
Tvl Dev Press Fallback, 24 Z
Tvl Dev Press Fallback Time, 24 Zero Power Condition, 33

123
DVC6000 HW2 Digital Valve Controller Instruction Manual
February 2023 D103785X012

Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, PROVOX, Rosemount, Tri-Loop, DeltaV, RS3, and THUM are marks owned by one of the companies in the Emerson Automation
Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of
Emerson Electric Co. HART is a registered trademark of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com

124
E 2014, 2023 Fisher Controls International LLC. All rights reserved.

You might also like