DM-0601-01 General_DRAFT
DM-0601-01 General_DRAFT
1.0 GENERAL
1.1 APPLICATION
T
1.1.2 See DM-0102, Fire/Life Safety, for associated fire protection requirements, and
DM-0701, Auxiliary Electrical Systems for power and control aspects.
1.1.4 Unless specifically indicated, the requirements of this Section apply to new
construction only.
1.3.1 The design shall generally conform to applicable sections, standards, codes and
documents of the following regulatory and advisory agencies:
T
• Ontario Electrical Safety Code (OESC)
• Ontario Fire Code (OFC)
• Sheet Metal and Air Conditioning Contractors' National Association
•
(SMACNA).
AF
Model National Energy Code for Buildings (MNECB)
1.3.2 Codes referenced herein may include year of issue, so that the designer may
accurately locate the content and intention of the reference. Nonetheless, the
requirements of the most current version of the code shall be applied.
R
1.3.3 Where revisions and updates to references result in conflicts, the designer shall
seek clarification before proceeding with the design.
1.4.1 The analytical design of the ventilation systems serving the tunnels and public
areas of underground rapid transit stations shall be carried out by the use of
applicable computer models. Refer to DM-0607, Fire Ventilation, for additional
requirements.
1.4.4 Heating and cooling loads for station rooms shall be calculated utilizing latest
versions of Carrier HAP software (or equal), and/or design spreadsheets and
forms incorporating recognized formulae and design factors from ASHRAE.
Design conditions shall be appropriate for the station and surrounding natural
environment; details are provided under DM-0601-02, Design Parameters for
Normal Operation.
1.4.5 Piston induced ventilation shall not be used for the following applications:
T
• Rooms with electrical hazard classifications of Class I Div 1 or Class I Div 2.
• Rooms sensitive to brake dust and other contaminants generated by
operation of the transit system.
•
AF
Any other area where the level of induced ventilation is determined to be
insufficient for the requirement.
1.5 COORDINATION
1.5.1 The ventilation concept for the station shall consider various factors that may
impact the design as described by the following items:
R
• If emergency tunnel ventilation will also provide general ventilation to the
tunnel and/or station.
• If platform edge doors are implemented, whether or not there will be a
separate system for station-side ventilation and/or fire ventilation.
D
1.6.1 All ventilation systems shall be formally commissioned in accordance with the
requirements of relevant TTC Master Specifications and ASHRAE Guideline 0 –
The Commissioning Process.
DM–0601-01 MECHANICAL
Page APPROVED Section Subject
Sept-14-2011 VENTILATION General
4 DRAFT
1.6.3 An air balancing report shall be provided for each system, validating that the
design criteria (air flow, air changes, fresh air quantities, pressurization, etc.)
have been achieved within the tolerances indicated within TTC Master
Specifications.
1.6.4 To the extent possible, equipment performance shall be validated under the
following scenarios:
T
• The most onerous or demanding operating condition.
• Validation of equipment interlocks.
• Summer and winter design days.
•
AF
Simulated emergency conditions; fire alarms, fire ventilation.
• Simulated equipment faults; to validate operation of back-up equipment.
• Commercial power failure; recovery after commercial power resumes.
1.7.2 Relevant TTC operating procedures shall be read in conjunction with the Design
D
1.8.2 Sufficient space shall be allowed for component removal and replacement at
the machine without having to disassemble or remove adjacent equipment. A
sufficient lay down area shall also be included in the layout of each room.
MECHANICAL DM-0601-01
Section Subject APRROVED Page
Sep-14-2011
VENTILATION General DRAFT 5
1.8.3 HVAC equipment shall not be located over open stairwells, the track way and
other areas that are difficult or potentially dangerous to access.
T
• Maintenance activities could result in safety hazards to the public and other
TTC employees,
• The public normally has access or public access would be difficult to
control,
AF
• Access for maintenance would be restricted to non-operating hours only.
1.8.5 HVAC equipment, dampers, filters and other accessories shall be arranged in a
systematic manner in places accessible for operation without the use of chain
wheel operators, additional access platforms such as scaffolding, or ladders
requiring fall restraint procedures.
R
1.8.6 To the extent possible HVAC equipment shall be located within rooms
accessible to the trade responsible for their maintenance (i.e. the trade would
normally carry the necessary keys, such as a TTC “BM” key, for access).
D
1.8.9 Ceiling-mounted and wall-mounted HVAC equipment weighing more than [50
kg - TBD] shall not be permitted unless accepted by Plant Maintenance. Such
equipment shall not require frequent maintenance.
1.8.10 All dials of gauges and indicators shall be of sufficient size and arranged so as
to be easily seen, read and operated from floor level.
1.8.11 Systems shall be arranged in a manner such that fall restraint procedures or
confined space access procedures are avoided to the greatest extent possible.
Modifications and deviations from standard design arrangements involving fall
DM–0601-01 MECHANICAL
Page APPROVED Section Subject
Sept-14-2011 VENTILATION General
6 DRAFT
1.8.12 In most cases, HVAC equipment will be replaced in whole (or large pieces) at
one or more times throughout the lifetime of the facility. Provide arrangements
that facilitate removal, delivery and replacement of equipment without
significant impact to the facility operation. The use of tunnels and public areas
for removal and delivery of equipment shall be avoided to the extent practical.
T
1.9.1 Specifications for HVAC equipment and materials shall identify products of the
highest quality consistent with the function and longevity of the facility. Refer
to TTC Master Specifications for standards of acceptance.
1.9.2
AF
Alternatives to products indicated in the TTC Master Specifications shall be
subject to review and acceptance by Plant Maintenance and other TTC
departments.
1.9.3 Ductwork, fittings and associated appurtenances not easily accessible for
replacement: Selected and specified to perform for the service life of the facility
and not less than 50 years.
R
1.9.4 HVAC equipment: Selected and specified to perform for at least 15 years for
unitary equipment, and at least 25 years for built-up air handling systems.
1.9.5 As it is unlikely that HVAC equipment will outlive the facility, provisions to
replace the equipment in whole or part shall be provided. Refer to “Maintenance
D
1.9.7 Service reliability: Products shall have reliable and predictable service. Where
the product is critical to the function of the facility, and the product must be
taken out of service for maintenance and/or repairs, alternatives to maintain the
function must be included in the design. TTC stakeholders shall define the
standard of acceptance in this regard.
1.9.8 Products shall be compliant with green procurement standards. This shall
include:
MECHANICAL DM-0601-01
Section Subject APRROVED Page
Sep-14-2011
VENTILATION General DRAFT 7
END OF SECTION
T
AF
R
D