Navodila Za Uporabo 197498 Enda Et2411 230 08 Regulator Temperature NTC 60 Do 150 C Rele 8 A D X S X V 71 X 77 X 35 MM

The ENDA ET2411 ON/OFF Heat Controller is designed for temperature control with a scale range of -60.0 to 150.0 °C and an accuracy of ± 1%. It features selectable heating or cooling control, adjustable setpoint limits, and a single NTC sensor input, with various electrical characteristics depending on the model. The device must be installed according to safety regulations and is protected against humidity and vibrations.

Uploaded by

mohamedziat555
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views2 pages

Navodila Za Uporabo 197498 Enda Et2411 230 08 Regulator Temperature NTC 60 Do 150 C Rele 8 A D X S X V 71 X 77 X 35 MM

The ENDA ET2411 ON/OFF Heat Controller is designed for temperature control with a scale range of -60.0 to 150.0 °C and an accuracy of ± 1%. It features selectable heating or cooling control, adjustable setpoint limits, and a single NTC sensor input, with various electrical characteristics depending on the model. The device must be installed according to safety regulations and is protected against humidity and vibrations.

Uploaded by

mohamedziat555
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

english TECHNICAL SPECIFICATIONS

Read this document carefully before using this device. The guarantee will be expired by device INPUT
demages if you don't attend to the directions in the user manual. Also we don't accept any Input Type Scale Range Accuracy
compensations for personal injury, material damage or capital disadvantages. NTC Sensor Typ 103AT-2 EN 60751 -60.0...150.0 °C -76.0...302.0°F ± 1% (for full scale) ± 1 Digit
at 25 °C - 10 kOhm
ENVIRONMENTAL CONDITIONS
ENDA ET2411 ON/OFF HEAT CONTROLLER Ambient/Storage temperature 0 ... +50 / °C -25... +70 °C(without icing)
Relative Humidity Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
Thank you for choosing ENDA ET2411 ON/OFF Heat Controller. Protection Class According to EN60529; Front panel: IP65 Rear panel : IP20
Height Max. 2000m

- 77 x 35mm sized. Do not use the device in locations subject to corrosive and flammable gasses.
- Single NTC sensor input. °F C1 ELECTRICAL CHARACTERISTICS
Supply 230V AC +10% -20%, 50/60Hz or 12/24V AC/DC 10%
-
-
Zero point input shift.
Selectable heating or cooling control for C1 relay output.
°C Power Consumption Max. 3VA
- Selectable heating or cooling control. SET Wiring Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
- In the case of sensor failure, relay state can be set to ON or OFF. Line Resistance Max. 100ohm
Data Retention EEPROM (Min. 10 years)
- Upper and lower setpoint limits can be adjusted.
- Temperature unit can be selected as °C or °F. ENDA ET2411 EMC EN 61326-1 : 2013 (Performance criterion B is satisfied for EN 61000-4-3)
Safety Requirements EN 61010-1 : 2010 (Pollution degree 2, overvoltage category II)
- CE marked according to European Norms.
4 digits, 12.5mm, 7 segment red LED
R HS Indicator
OUTPUT
Konform C1 Output For 5A Models : 250V AC, 5A (resistive load), NO control output.
For 8A Models : 250V AC, 8A (resistive load), NO and NC control output.
1 - Supply Voltage 2 - Relay Current Selection For 16A Models : 250V AC, 16A (resistive load), NO control output.
Life Expectancy for Relay For 5A Models : 5. Mio. Switching for no-load operation; 100.000 switching for 5A resistive load at 250VAC.
230........230V AC 05.....5A Relay Output For 8A Models : 30. Mio. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC.
Order Code : ET2411 - - 024........24V AC/DC 08.....8A Relay Output For 16A Models : 30. Mio. Switching for no-load operation; 100.000 switching for 16A resistive load at 250VAC.
1 2 012........12V AC/DC 16...16A Relay Output
SM.........7-24VAC/9-30VDC CONTROL
Control Type Single-setpoint and alarm control.
Control Algorithm
A/D Converter 12 bit resolution, 100ms sampling time.
ENDA ET2411 is intended for installation within control panels. Make sure that the device is used only for Hysteresis Adjustable between 0.1 and 20.0°C/F.
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against HOUSING
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded. Housing Type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W77xH35xD61mm
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
Weight Approx. 215g (After packing)
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualified staff and must be according to the relevant locally applicable regulations. Enclosure Materials Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX
ET2411-230-08
DIGITAL THERMOSTAT
ET2411-230-16
DIGITAL THERMOSTAT
ET2411-SM-05
DIGITAL THERMOSTAT Dimensions
Made in Turkey 8 680407 715299 Made in Turkey 8 680407 715367 Made in Turkey 8 680407 715350 77mm Depth 5mm
250V AC 8A
RESISTIVE LOAD
250V AC 16A
RESISTIVE LOAD
250V AC 5A
RESISTIVE LOAD
61mm
C1
NTC C1
NTC C1
NTC
°F C1
For removing mounting clamps:

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 °C - Push the flush-mounting clamp


SET
in direction 1 as shown in the
Equipment is protected throughout Holding screw figure below.Then,pull
by DOUBLE INSULATION 0.4-0.5Nm. out the clamp in direction 2 .
ENDA ET2411

NOTE: Fuse
Note:
Connection
SUPPLY: F 100 mA Cable Flush mounting
Switch 1) Mains supply cords shall meet the requirements of Panel
184-253V AC 5 Line
250V AC
230V AC
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
Flush mounting 2 clamp Rubber
Packing
50/60Hz 3VA
11 12 10 9 8 7 6 5 4 3 2 1
6 Neutral Supply clamp
supply switch shall bring the identification of the Panel cut-out
Fuse should Note:1) Panel thickness should
C1

relevant instrument and it should be easily


NTC

be connected Cable size: 1,5mm² 71,5mm


RESISTIVE LOAD

1
250V AC 8A

accessible by the operator. be maximum 7mm.


2) If there is not 60mm free
Made in Turkey

992517 704086 8 DIGITAL THERMOSTAT


ET2411-230-08
SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS space at the back side of
up to date: 25.03.2019, modification reserved and can be change any time previous notice ! the device,it would be
difficult to remove it from
the panel.
SURAN Industrieelektronik
Dettinger Str. 9 Tel.: +49 (0)7451 / 625 617 E-mail : [email protected]
D-72160 Horb a.N. Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
1. / 2 ET2411-E-25032019
Programming Diagram

Running Mode
Measured temperature Default value C1 Set value
SET

105 C1.SE. 100 100 101 102 101 If no key is pressed within 3 seconds, Running Mode is entered.

When this button is pressed


C.SEt message is appeared Temperature setpoint value is adjusted with buttons then, Entering Running Mode in Programming Mode :
and temperature setpoint
when one of these buttons are pressed for the first time, blinking setpoint value appears. In Programmin Mode, if no keys are pressed for 20 seconds information is
adjustment mode is entered.
saved automatically and Running Mode is entered.
SET
SET
Alternatively, if and keys are pressed together, Programming Menu
If key is pressed while holding down key,
is entered. In the Programming Menu, if key is pressed while holding
then Programming Menu is entered. SET
down key, then Running Mode is entered.

Programming Menu
SET SET SET

C1.Cn. ConF. SECu.


Default Default
Value Value S.Cod = Access code for security menu.
C1..L.L.= Control set point lower limit for C1
0 This parameter should be 411 .
output. HEAt C.tyP. C.typ. = Control type selection. S.Cod.
C1..L.L. It can be adjusted between -60.0 and C1.H.L. C.typ. = HEAt Heating control is selected.
parameter value. C.typ. = CooL Cooling control is selected. When s.co. = 0 , if key is
pressed for 4 seconds while holding
C1H.L.= Control set point upper limit for C1 °C Unit. Unit = Temperature unit selection. SET

C1..H.L. output. Unit. = Can be selected as °C or °F


down key, then d.PAr. is seen
It can be adjusted between 150.0 and C1.L.L. on display and the device is returned
parameter value. to factory settings.
no d.P. d.P. = Decimal point display selection.
If d.P. = no , decimal value is not dotted.
C1.Hy. = Output hysteresis value. If d.P. = YES , decimal value is dotted.
C1.Hy.
It can be adjusted between 0.1 and 20.0 °C. oFFS. = Offset value.
P.YES C1.sc. C1..sc. = C1,Cn. Security menu access level.
0 oFFs. nonE = Invisible.
Zero point shift value is added to the measured P.yEs = Can be modified.
value. This feature is used for eliminating the
measuring probe distance errors. It can be P. no = Visible but can’t be modified.
adjusted between -20.0 and 20.0°C.
P.YES Co.sc. . Co.sc. = ConF. Configuration menu access level.
C1.E.S. C1.E.S. = C1 Output state in case of sensor failure. nonE = Invisible.
Modification Of Parameter Diagram
SET SET SET on = Output is ON in case of sensor failure. P.yEs = Can be modified.
off = Output is OFF in case of sensor failure. P. no = Visible but can’t be modified.

C.S. sc. C.S.sc. = C1 set value security access level.


SET
While holding down key, parameter value blinks and by ERROR MESSAGES P.YES
P.yEs = Can be modified.
using keys, the requested value can be adjusted.
P. no = Visible but can’t be modified.
pfa Sensor is broken
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the ---- Temperature value is
higher than the scale
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is Temperature value is
returned. The same procedure is valid for the decrementing. ____ lower than the scale

2. / 2 ET2411-E-25032019