MEP Plans

The document outlines specifications for ductwork installation, including compliance with the 2013 California Mechanical Code, duct support requirements, and insulation standards. It emphasizes the importance of proper sealing, temperature control devices, and the coordination of mechanical systems with other trades. Additionally, it includes guidelines for condensate waste sizing and equipment capacity related to air conditioning systems.

Uploaded by

Lukhanyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views41 pages

MEP Plans

The document outlines specifications for ductwork installation, including compliance with the 2013 California Mechanical Code, duct support requirements, and insulation standards. It emphasizes the importance of proper sealing, temperature control devices, and the coordination of mechanical systems with other trades. Additionally, it includes guidelines for condensate waste sizing and equipment capacity related to air conditioning systems.

Uploaded by

Lukhanyo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 41

'HVLJQ&RQVXOWDQW

GENERAL NOTES CONDENSATE WASTE SIZING


EQUIPMENT CAPACITY IN TONS OF REFRIGERATION MINIMUM CONDENSATE PIPE DIAMETER IN INCHES
DUCTWORK: ENERGY:
1. INSTALLATION OF DUCTWORK SHALL BE COORDINATED WITH OTHER TRADES. DUCTS INSTALLED IN LOCATIONS WHERE 1. BACK-DRAFT DAMPERS FOR ALL EXHAUST AND FAN SYSTEMS SHALL BE PROVIDED. EXCEPTION: NO BACK-·ORAFT UP TO 20 3/4"
THEY ARE SUBJECT TO PHYSICAL DAMAGE SHALL BE PROTECTED BY SUITABLE GUARDS. DAMPERS IN GREASE DUCTS.
2. ALL AIR CONDITIONING DUCTS TO COMPLY WITH SMACNA AND CHAPTER 6 OF THE 2013CALIFORNIA MECHANICAL CODE ALL 2. ALL WATER HEATING AND AIR CONDITIONING EQUIPMENT AND FAUCETS SHALL BE C.E.C. CERTIFIED. 21 - 40 1"
TRANSVERSE JOINTS TO BE SUBSTANTIALLY AIRTIGHT WITH TAPE, MASTIC, GASKETING OR OTHER MEANS; ALL LOW 3. AUTOMATIC TEMPERATURE CONTROL DEVICE FOR REGULATION OF SPACE TEMPERATURE SHALL BE EQUIPPED WITH
PRESSURE DUCTWORK SIZED EQUAL TO OR LESS THAN OJ" W.G./100 FT. ALL DUCTS FOR VENTILATION TO COMPLY WITH NIGHT SET BACK AND HAVE THE ABILITY TO OPERATE THE HEATING AND THE COOLING IN SEQUENCE. CONTROL SHALL 41 - 90 1-1/4"
CHARTER 5 OF THE 2013 CALIFORNIA MECHANICAL CODE. BE ADJUSTABLE TO PROVIDE A RANGE OF UP TO 10 DEGREES F BETWEEN FULL HEATING AND FULL COOLING AND HAVE
3. DUCT SUPPORTS AND ANCHORAGE SHALL COMPLY WITH 2013 CMC 604.0 AND TABLE 6-7 AND 6-8 A CAPABILITY OF TERMINATING ALL HEATING AT A TEMPERATURE NO MORE THAN 70 DEGREES F AND COOLING AT A 91 - 125 1-1/2" $5&+,7(&785(
4. MANUAL VOLUME DAMPERS TO BE INSTALLED IN ALL BRANCH TAKE-OFFS. ALL DAMPERS TO HAVE LOCKING QUADRANTS. TEMPERATURE NO LESS THAN 78 DEGREES F.
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
5. DUCT SIZES SHOWN ARE NET SIZES REQUIRED. LINED DUCTS SHALL BE INCREASED IN SIZE TO ACCOMMODATE LINING 4. AT LEAST ONE AUTOMATIC SPACE TEMPERATURE CONTROL DEVICE (THERMOSTAT) SHALL BE PROVIDED FOR EACH ZONE 126 - 250 2" û‚¹¼ċ™‚ċĖû™‹&Ђí
WITHOUT LOSS OF AREA, AND/OR EACH SEPARATE HVAC SYSTEM. (NOT MORE THAN ONE FLOOR OF BUILDING SHALL BE INCLUDED). 7KH3URPHQDGH1RUWK
6. PROVIDE MASTIC OR DUCT TAPE JOINT SEALANT TO SEAL TRANSVERSE JOINTS ON AIR SUPPLY DUCTS INSTALLED IN 5. ALL AIR CONDITIONING UNITS TO BE FURNISHED WITH MAINTENANCE MANUALS, SCHEDULES AND TAGS. /RQJ%HDFK&$
THE SIZE OF CONDENSATE WASTE PIPES MAY BE FOR ONE UNIT OR A COMBINATION OF UNITS, OR AS RECOMMENDED BY THE MANUFACTURER.
LOCATIONS WHERE AIR LEAKAGE THROUGH THE JOINTS WOULD BE NON-BENEFICIAL TO THE OCCUPIED AREA 6. ALL AIR CONDITIONING UNITS TO BE EQUIPPED WITH A READILY ACCESSIBLE MANUALLY ADJUSTABLE AUTOMATIC MEANS THE CAPACITY OF WASTE PIPES ASSUMES A 1/8 INCH PER FOOT OR ONE PERCENT SLOPE, WITH THE PIPE RUNNING THREE-QUARTERS FULL:
ZZZLGDH[SHULHQFHQHW
TEMPERATURE REQUIREMENTS. AND, SEAL LONGITUDINAL JOINTS ON LOW-PRESSURE SUPPLY DUCTS WHERE INTERNAL OF REDUCING THE ENERGY USED FOR HVAC DURING PERIOD OF NON USE OR ALTERNATE USE OF THE BUILDING SPACE
STATIC PRESSURE EXCEED 0.75" OF WATER PRESSURE. OR ZONES SERVED BY THE SYSTEM, SUCH AS A TIME CLOCK OR TIME SWITCH. Outside Air - 20% Room Air - 80% $UFKLWHFW
7. FLEX DUCT SHALL BE ATTACHED TO ALL REGISTERS, GRILLES, COLLARS AND FITTINGS ACCORDING TO ITS LISTINGS. I.E. A 7. EACH MECHANICAL OR GRAVITY VENTILATING UNIT, EXCEPT ATTIC VENTILATORS SHALL BE EQUIPPED WITH AN DB WB DB WB
MINIMUM OF TWO WRAPS OF UL 181 TAPE AND A PANDUIT STRAP ON THE INSIDE LINER AND A MINIMUM OF TWO WRAP OF AUTOMATIC TYPE NORMALLY CLOSED OUTSIDE AIR DAMPER TO SERVE AS A MEANS OF PROVIDING AIR VOLUME 90°F 73°F 75°F 62.5°F
UL 181 TAPE OR A PANDUIT STRAP OR BOTH ON THE OUTSIDE COVER. REDUCTION ANO/OR SHUT-OFF WHEN VENTILATION IS NOT REQUIRED. (DOES NOT APPLY TO COMBUSTION AIR *(2))5(<%/,0
8. ALL FLEX DUCT SPLICES SHALL BE SLEEVED. OPENINGS).
$,$1&$5%/(('$3
9. ALL AFD SPLICES SHALL BE SLEEVED.
10. MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A QUALITY CONTROL: Plans, maps, specifications, studies, and reports not
SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 PER CBC 602.0 1. PROVIDE AS BUILT DRAWINGS AND SUBMIT COPIES TO THE OWNER. containing a red ink seal imprint accompanied by an
11. FLEXIBLE DUCTS 10 BE GLASS-FLEX FOR STRAIGHT RUNS ONLY 8'-0', MAXIMUM IN LENGTH. ALL ELBOWS AND TURNS SHALL original
2. CONTRACTOR SHOULD SUBMIT SHOP DRAWINGS. EQUIPMENT HANGERS, ANCHOR BOLTS AND METHODS OF TABLE NO. 6-7 DUCT SUPPORT signature by the licensed professional may have been
BE SHEET METAL GALVANIZED. fraudulently altered and shall not be considered an original
INSTALLATION MUST HAVE CITY APPROVAL AND MAY BE SUPPLIED BY HILTI OR EQUAL. copy. All information should be disregarded unless verified
12. PROVIDE DUCT LINING TO SUPPLY DUCT OF EACH AC UNIT FOR MINIMUM Of 10 FT. DUCT LINING TO BE EQUAL TO 3. IT IS THE SPECIFIC INTENT OF THIS DESIGN CONDITIONS THAT THE ENTIRE SYSTEM INCLUDING EQUIPMENT, DUCTWORK, by the professional whose signature appears above.
A - VERTICAL DUCTS Copyright Protected 2016.
JOHNS-MANVILLE, 1" THICK x 1-1/2 PCF DENSITY DUCT LINER. DUCTWORK TO BE INCREASED IN EACH DIMENSION TO AIR OUTLETS/INLETS AND ALL OTHER PARTS BE NOISELESS AND FREE OF VIBRATION TRANSMISSION. PROVIDE AND
INCORPORATE THICKNESS OF LINING. INSTALL VIBRATION ISOLATORS OR DAMPERS, SOUND INSULATION PADS, FLEXIBLE CONNECTORS AND SIMILAR MAXIMUM SIDE OF METAL STRAP MAXIMUM DIAMETER
STRAP
13. VOLUME DAMPERS IN ALL BRANCH DUCTS. RECTANGULAR DUCT ANGLE BRACKET OF ROUND DUCTS
MATERIAL AS REQUIRED. INSTALL VOLUME DAMPERS ON ALL DUCTS AS FAR AS POSSIBLE FROM AIR INLET/OUTLET. (QJLQHHULQJ&RQVXOWDQW
14. PROVIDE GALVANIZED SHEET METAL DUCTS FABRICATED AND INSTALLED TO CMC 2013 EDITION. 0.047" (NO. 18 GAGE)
MAKE THE NECESSARY NOISE OR VIBRATION CORRECTIONS BY INSTALLING THESE ITEMS AT NO COST TO THE OWNER. 24" 1" X 1 /8" (STRAP) 1 10" GALVANIZED STEEL 2" WIDE
4. THE DRAWINGS ARE IN PART DIAGRAMMATIC AND ARE INTENDED TO CONVEY THE SCOPE OF THE WORK; THEY INDICATE
0.058" (NO. 16 GAGE)
AIR DEVICES: THE GENERAL ARRANGEMENT AND APPROXIMATE SIZES OF EQUIPMENT, DUCTWORK, PIPING, OUTLETS, ETC. FOLLOW 36" 1" X 1" X 1/8" (ANGLE) 1 20"
GALVANIZED STEEL 2" WIDE 1
1. ARROWS AT CEILING DIFFUSERS INDICATE THE AIR THROW PATTERN. THE DRAWINGS AS CLOSELY AS PRACTICAL IN LAYING OUT THE WORK, BE GUIDED BY THE CONDITIONS AT THE JOB AND
2. COORDINATE WITH ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CONSULT THE CONSTRUCTION DRAWINGS OF THE OTHER TRADES TO BECOME FAMILIAR WITH ALL CONDITIONS 48" 1 1/8" x 1 1/8" x 1/8" (ANGLE) 1 40" 1/8" STEEL x 1 1/2" 1
DIFFUSERS, REGISTERS, AND LOUVERS. AFFECTING THE WORK.
3. ALL REGISTERS AND GRILLS INSTALLED IN T-BAR CEILINGS SHALL BE ATTACHED AT EACH CORNER TO THE MAIN RUNNERS 5. UPON COMPLETION OF AND AFTER CLEANING OF SYSTEM AND EQUIPMENT, CAREFULLY ADJUST FOR NORMAL OPERATION 60" 1 1/2" x 1 1/2" x 1/8" (ANGLE) 1 60" 1/8" STEEL x 2" 1
WITH APPROVED CLIPS OR SM SCREWS. OF THE AUTOMATIC PARTS OF HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS.
6. EQUIPMENT AND DUCTWORK EXPOSED TO WEATHER MUST BE WEATHERPROOFED, OVER 60" 2" x 2" x 1/8" (ANGLE) 1 OVER 60" 3/16" STEEL x 2" 1
INSULATION: 7. ROOF MOUNTED EQUIPMENT SHALL BE LABELED AS TO THE SPACE IT SERVES, (WHEN MORE 1HAN ONE HEATING OR
1. MINERAL FIBER INSULATION SHALL BE INSTALLED IN JOINT SPACES WHENEVER A PLUMBING PIPE OR DUCT PENETRATES A COOLING UNIT SERVES DIFFERENT OCCUPANTS.)
FLOOR-CEILING ASSEMBLY OR WHERE SUCH PIPE OR DUCT PASSES THROUGH THE PLANE OF FLOOR-CEILING 8. CONTRACTOR SHALL BALANCE AIR SYSTEM TO THE CFM CAPACITY AS SHOWN ON FLOOR
B - HORIZONTAL DUCTS
ASSEMBLY FROM WITHIN A WALL. THE INSULATION SHALL BE INSTALLED TO A POINT 12" BEYOND THE PIPE OR DUCT. 9. ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE PER 2013 CMC. 304A (FOR
2. COMBUSTION AIR, KITCHEN AND BATHROOM EXHAUST DUCTS WITHIN SOUND SEPARATION ASSEMBLIES SHALL BE SECURED FASTENING AND SUPPORT OF APPLIANCES) SAME GAGE AS GALVANIZED STEEL
18" 1" X 18" GAGE 2
WRAPPED INSULATION AS REQUIRED PER THE 2013 CMC. 10. 10.FURNISHING AND INSTALLATION OF ALL LOW VOLT. WIRING FOR MECHANICAL SYSTEMS SHALL BE BY THE MECHANICAL DUCT, 1" WIDE OR (NO. 18 GAGE
CONTRACTOR. 10" GALVANIZED STEEL WIRE) ON 10'
3. CEILING CONCEALED SUPPLY AND RETURN DUCTS TO BE COVERED All SIDES WITH 2'' THICK 3/4 LB./CU. FT. OR WITH 1" 30" 1" X 18" GAGE 2
11. 11.ALL NECESSARY EQUIPMENT CURBS, RUNNERS, PLATFORMS, ROOFING, PATCHING, CUTTING, RATING SHAFTS, CENTERS
THICK 1.5 LB,/CU. FT. DENSITY FIBERGLASS INSULATION, OR 1" THICK 3 LB./CU. FT. MINERAL FIBER BOARD, OR MATERIAL
FURRING, FLASHING AND PAINTING SHALL BE BY THE GENERAL CONTRACTOR. 48" 2
WITH A CONDUCTANCE OF 0.30 OR LESS, APPLIED WITH 2" LAPPED JOINTS SECURELY AND NEATLY WIRED AND 1" x 1/8" 20" SAME GAGE AS GALVANIZED STEEL 1"
FASTENED TO DUCT; THE INSULATION TO BE CERTIFIED BY CALIFORNIA ENERGY COMMISSION; (JOHN MANSVILLE IS 12. 12.ALL NECESSARY DRAINS, GAS, CONDENSATE DRAINS WITH TRAPS, MAKE-UP WATER, INCLUDING FINAL CONNECTIONS 3URMHFW2ZQHU
2 WIDE OR (NO. 8 GAGE GALVANIZED STEEL
ACCEPTED) WHEN DUCl\VORK PENETRATE INSULATED WALLS OR ROOF, THE HOLE MUST BE SEALED WITH AN SHALL BE BY THE PLUMBING CONTRACTOR. 60" 1" x 1/8" WIRE) TIED 1" GALVANIZED STEEL BAND
13. CONDUITS AND AUXILIARIES FOR MECHANICAL SYSTEMS SHALL BE BY THE ELECTRICAL CONTRACTOR. THE CONDUIT FOR 40"
APPROVED POLY SEAL MATERIAL. AROUND DUCT ON 10' CENTERS
2
4. INSULATION INSTALLER SHALL POST IN A CONSPICUOUS LOCATION IN THE BUILDING A CERTIFICATE SIGNED BY THE LOW VOLTAGE WIRING OF MECHANICAL SYSTEM EXPOSED TO THE WEATHER SHALL BE APPROVED FOR EXTERIOR USE 80" 1" x 1/8"
INSTALLER AND BUILDER STATING THAT THE INSULATION CONFORMS WITH THE REQUIREMENTS OF TITLE 24, CHAPTER AND BE BY THE ELECTRICAL CONTRACTOR.
2-53 AND THAT THE MATERIAL INSTALLED CONFORMS WITH THE REQUIREMENTS OF TITLE 20, CHAPTER 2, SUB-CHAPTER 14. ALL COMBINAT!ON SMOKE/ FIRE DAMPERS SHALL INTERLOCKED FOR GLOBAL SHUTDOWN WITH ALL DUCT SMOKE
4, ARTICLE 3. DETECTORS, SMOKE AREA DETECTORS, ALL AIR HANDLING EQUIPMENT AND THE ALARM SYSTEM IF PROVIDED.
5. ALL INSULATION MATERIALS SHALL BE CERTIFIED BY THE MANUFACTURER AS COMPLYING WITH THE CALIFORNIA QUALITY 15. ALL DUCT DETECTORS SHALL BE MAGNEHELIC TESTED TO THE MANUFACTURERS SPECIFICATIONS IN THE PRESENCE OF
STANDARD FOR INSULATION MATERIAL. THE CITY OF EL MONTE BUILDING INSPECTOR PRIOR TO THE FINAL APPROVAL. MAXIMUM DIAMETER OF
16. ALL EXTERIOR MOUNTED DUCT DETECTORS SHALL BE RATED AT 150 DEGREES F. OR HIGHER AND BE M0UNTED IN A NEMA ROUND DUCT OR SIDE HORIZONTAL 3 HANGER
6. INSULATION APPLIED TO THE EXTERIOR SURFACE OF DUCTS LOCATED IN THE BUILDINGS SHALL HAVE A FLAME SPREAD OF
RATED ENCLOSURE OF 3-R OR HIGHER. OF RECTANGULAR DUCT SUPPORT ANGLE
NOT MORE THAN 25 AND A SMOKE -DENSITY NOT EXCEEDING 50 PER CBC 605.0
17. ALL ROOFTOP EQUIPMENT REQUIRES EXTERNAL DISCONNECTS.
18. ALL EQUIPMENT SHALL BE LABELED OR LISTED BY A RECOGNIZED APPROVAL AGENCY. 36" 1-1/2' x 1-1/2" x 1/8" 1/4" ROUND ROD OR 1" x 1" x 1/8" ANGLE
PIPING:
19. A RETURN AIR PLENUMS ARE NOT PERMITTED ON THIS JOB WITHOUT PLAN CHECK APPROVAL.
1. PROVIDE A 3/4" MINIMUM CONDENSATE DRAIN FROM EACH AC UNIT TO AN APPROVED DISPOSAL AREA. CONDENSATE 48" 2" X 2" X 1/8" 1/4" ROUND ROD OR 1' X 1" X 1/8" ANGLE
20. ALL MECHANICAL EQUIPMENT DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE. OTHER
WATER SHALL NOT DRAIN OVER A PUBLIC WAY. THE DRAIN SHALL HAVE A SLOPE OF NOT LESS THAN 1/8 INCH PER FOOT
EQUIPMENT THAT IS OVER 5 FEET IN HEIGHT, IT SHALL BE SECURED IF ONE QF THE FOLLOWING APPLY: ( T-16-P) 60" 2'' x 2" x 1/8" 5/16" ROUND ROD OR 1" X 1" X 1/8" ANGLE
AND SHALL BE OF APPROVED CORROSION-RESISTANT PIPE. (THIS WORK IS UNDER PLUMBING SECTION, REFER TO
21. EXCEEDS HEIGHT TO WIDTH RATIO OF 1-1 /2 : 1.
PLUMBING DRAWINGS).
22. CENTER OF GRAVITY IS LOCATED ABOVE MID-HEIGHT.
23. ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE PER BUILDING CODE 1. SPACED VERTICALLY NOT MORE THAN 12 FEET ON CENTERS.
CODE: REQUIREMENTS. 2. SPACED HORIZONTALLY NOT MORE THAN 10 FEET ON
1. MOUNT WALL MOUNTED THERMOSTATS 4' - 0" ABOVE FINISHED FLOOR. 24. ROOF MOUNTED EQUIPMENT SHALL BE LABELED AS TO THE SPACE IT SERVES. CENTERS
2. EACH SINGLE SYSTEM WITH ONE OR MORE AIR CONDITIONING UNITS PROVIDING HEATING OR COOLING IN EXCESS OF 2000 3. SPACED NOT MORE THAN 8 FEET ON CENTERS.
25. MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE FLAMESPREAD INDEX OF NOT MORE THAN 25 AND A
CFM OR AIR SERVING MORE THAN ONE OCCUPANCY, SHALL HAVE SMOKE DETECTORS (PRODUCT OF COMBUSTION) AND SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH CBC SECTION 703.4.2
SHALL BE INSTALLED IN THE MAIN SUPPLY DUCT DOWNSTREAM OF THE FILTERS. ACTIVATION OF THE SMOKE SHALL 26. DUCTS AND PLENUMS SERVING A TYPE I HOOD SHALL BE CONSTRUCTED OF NOT LESS THAN 0.055" (NO. 16
CAUSE THE UNIT TO SHUT DOWN AND ACTIVATE THE FIRE ALARM SYSTEM. (WHERE FIRE DETECTION & ALARM SYSTEMS MANUFACTURER'S STANDARD GAGE) STEEL OR STAINLESS STEEL ALL DUCTS TO COMPLY WITH CHAPTER 5 OF THE
ARE PROVIDED) (2013 CMC. 609). IF THERE ARE A NUMBER OF AIR CONDITIONING UNITS SERVING ONE AREA, OR THERE CALIFORNIA MECHANICAL CODE. ALL JOINTS AND SEAMS SHALL BE MADE A CONTINUOUS LIQUID-TIGHT V/ELO OR BRAZE
IS A COMMON RETURN AIR PLENUM FOR A NUMBER OF AIR CONDITIONING UNITS, ALL SMOKE DETECTORS MUST BE MADE ON THE
INTERCONNECTED TO SHUT-OFF ALL EQUIPMENT EVEN WHEN SMOKE IS DETECTED BY ONLY ONE SMOKE DETECTOR. 27. EXTERIOR SURFACE OF THE DUCT. ALL DUCTS EXPOSED TO THE OUTSIDE ATMOSPHERE AND SUBJECT TO CORROSION
TABLE NO. 6-8
DUCT VELOCITY AND PRESSURE DIFFERENTIAL MAY HAVE TO BE VERIFIED FOR EACH DUCT SMOKE DETECTOR SHALL BE PROTECTED BY GALVANIZATION, NON CORROSIVE PAINTS OR WATERPROOF INSULATION. DUCTWORK SHALL
LOCATION IN ACCORDANCE WITH U.L. LISTING AND EC110-3(B). AUTOMATIC SHUTOFFS NEED NOT BE INSTALLED WHEN SLOPE NOT LESS THAN 1/4" PER LINEAL FOOT TOWARD THE HOOD. CLEAN-OUTS SHALL BE EQUIPPED WITH
CONSTRUCTION DETAILS FOR ROUND AND FLAT-OVAL DUCTS (LOW, MEDIUM AND HIGH PRESSURE)
ALL ROOMS HAVE DIRECT EXIT TO THE EXTERIOR OF THE BUILDING. TIGHT-FITTING 16 GAGE DOORS OPERABLE WITHOUT THE USE OF A TOOL. A TWO HOUR FIRE RESISTANT ENCLOSURE ALUMINUM STEEL -THICKNESS IN INCHES (STEEL-GALVANIZED SHEET GAGE) GIRTH JOINTS 1
3. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF ALL APPLICABLE CODES, LAWS, ORDINANCES AND REGULATIONS OF AROUND THE DUCTWORK IS REQUIRED. THIS ENCLOSURE SHALL BE SEPARATED FROM THE DUCT BY AT LEAST 3" AND DUCT B. & S. GAGE MEDIUM & HIGH PRESSURE
LOW PRESSURE 2 MINIMUM GIRTH
ALL AUTHORITIES HAVING JURISDICTION. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR All PERMITS, ADDITIONAL PLAN DIAMETER MAX MEDIUM &
NOT MORE THAN 12". AIR VELOCITY SHALL BE AT LEAST 1500 AND NOT TO EXCEED 2500 FEET PER MINUTE. (PROVIDE LOW PRESSURE LONGITUDINAL WELDED REINFORCING, MAX
CHECK FEES, INSPECTIONS, ETC. AND FURNISH SIGNED, CERTIFIED AND ACCEPTABLE COPIES TO THE OWNER FOR HIS WIDTH (IN") ROUND FLAT-OVAL SPIRAL SEAM HIGH
CLEAN-OUTS ON KITCHEN EXHAUST DUCTS AT EVERY CHANGE OF DIRECTION AND NO FARTHER THAN 15 FEET APART). ROUND SEAM FITTINGS SPACING & ANGLE SIZE
RECORD. PRESSURE
2013 CMC. CHAPTER 5. 1RUPV5HVWDXUDQWV//&
4. CONTRACTOR SHALL PROVIDE FIRE DAMPERS AT FIRE RATED PENETRATIONS. 28. 25, PROVIDE APPROVED' FIRE EXTINGUISHING S-YSTEM WITH AUTO GAS SHUT -OFF AND MANUAL RESET.
0.019 0.024 0.019 0.024 0.030 /DNHZRRG%OYG
5. DUCTS OPENING INTO CORRIDOR SHALL HAVE INSTALLED A COMBINATION FIRE/SMOKE DAMPER CONFORMING TO CBC 29. PROVIDE APPROVEB FIRE SPRINKLER FOR GREASE DUCT SYSTEM PER NFPA 13 AND 2013 CMC REQUIREMENTS. UP TO 9 24 2" SLIP NONE
(26) (24) (26) (24) (22) %HOOIORZHU&$
STANDARD SECTION 716 (J) WITH A M1N1~JUM LEAKAGE CLASSIFICATION OF ILL. CBC, 4306. FIRE DAMPER DETAIL SHOWN 30. PROVIDE AT LEAST ONE PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 10 BC FOR KITCHEN AREA.
IS FOR REFERENCE FIRE DAMPERS SHALL BE OSHPD FIRE MARSHAL APPROVED ANO INSTALLED STRICTLY PER 31. AIR BALANCE REPORT REQUIRED FOR HVAC AND GREASE DUCT SYSTEMS PRIOR TO FINAL INSPECTION.
MANUFACTURER'S PRINTED INSTRUCTIONS. MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL BE MADE 6WDPS
32. A GREASE DUCT SERVING A TYPE I HOOD WHICH PENETRATES A CEILING, WALL OR FLOOR SHALL BE ENCLOSED IN A 0.019 0.024 0.024 0.030 0.036
AVAILABLE TO THE INSPECTING AUTHORITIES. 9 TO 14 24 4" SLIP NONE
DUCT ENCLOSURE FROM POINT OF PENETRATION. A DUCT MAY ONLY PENETRATE EXTERIOR WALLS AT LOCATIONS (26) (24) (24) (22) (20)
6. DUCT VELOCITY AND PRESSURE DIFFERENTIAL SHALL BE VERIFIED FOR EACH DUCT SMOKE DETECTOR LOCATION IN WHERE UNPROTECTED OPENINGS ARE PERMITTED BY THE BUILDING CODE. DUCT ENCLOSURES SHALL BE
ACCORDANCE WITH U.L. LISTING AND EC110-3(8). DUCT SMOKE DETECTORS SHALL BE MAGNEHELIC TESTED TO THE CONSTRUCTED AS THE BUILDING CODE REQUIRES SHAFT ENCLOSURES TO BE CONSTRUCTED DUCT ENCLOSURES
LISTED SPECIFICATIONS IN THE PRESENCE OF THE CITY BUILDING INSPECTOR PRIOR TO FINAL APPROVAL. SHALL BE AT LEAST ONE-HOUR FIRE RESISTIVE CONSTRUCTION IN ALL BUILDINGS AND SHALL BE OF TWO-HOUR FIRE 0.024 0.030 0.024 0.030 0.036
14 TO 23 22 4" SLIP NONE
7. ACCESS TO INSPECT, SERVICE, REPAIR AND REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION TO ALL -RESISTIVE BUILDINGS. THE DUCT ENCLOSURE SHALL BE SEALED AROUND THE DUCT AT THE POINT OF PENETRATION (24) (22) (24) (22) (20)
EQUIPMENT SHALL BE PROVIDED. UNLESS OTHERWISE SPECIFIED, NOT LESS THAN 30 INCHES OF WORKING SPACE AND AND VENTED TO THE EXTERIOR THROUGH WEATHER-PROTECTED OPENINGS. THE ENCLOSURE SHALL BE SEPARATED
PLATFORM SHALL BE PROVIDED. FROM THE DUCT BY AT LEAST THREE (3) INCHES (76 MM) AND NOT MORE THAN TWELVE (12) INCHES (305 MM) AND SHALL
8. TOILET ROOMS WITHOUT WINDOWS OR WINDOW AREA LESS THAN 5% OF TOILET FLOOR AREA, SHALL HAVE A SERVE A SINGLE GREASE EXHAUST DUCT SYSTEM, (2007 CMC. CHAPTER 5) 23 TO 37 20 0.030 0.036 0.030 0.036 0.036 4" SLIP NONE
MECHANICALLY OPERATED EXHAUST SYSTEM CAPABLE OF PROVIDING A COMPLETE CHANGE OF AIR EVERY 10 MINUTES (22) (20) (22) (20) (20)
33. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL SOURCES OF INDOOR OR OUTDOOR AIR
(6 AIR CHANGE PER HOUR). TOILET EXHAUST DUCTS SHALL BE DIRECTLY CONNECTED TO THE OUTSIDE AND SHALL BE CONTAMINANTS OR LEVELS OF CONTAMINATION.
OF SMOOTH, NON-ABSORBENT AND NON-COMBUSTIBLE SURFACE MATERIAL. 34. IT IS THE RESPONSIBILITY OF THE GENERAL AND MECHANICAL CONTRACTOR TO INFORM THE TENANT'S 0.036 0.047 0.036 0.036 0.047
37 TO 51 18 1 1/4" x 1 1/4" 1 1/4" x 1 1/4"
9. ALL OUTSIDE AIR INTAKES MUST BE 10 FEET MINIMUM AWAY FROM ALL PLUMBING OR APPLIANCE VENTS (OR 3' -0" REPRESENTATIVE, LANDLORD AND TENANT'S ARCHITECT IF ANY SOURCE OR POTENTIAL SOURCE OF INDOOR AIR (20) (18) (20) (20) (18) x 1/8" x 1/8" ON 72"
MINIMUM BELOW APPLIANCE VENTS). OSA INLETS SHALL BE COVERED WITH SCREEN HAVING 1/4" OPENING. CONTAMINATION IS IDENTIFIED. FLANGE
10. ENVIRONMENTAL EXHAUST, SUCH AS BATHROOM, DRYER VENT, ETC. SHALL TERMINATE AT LEAST 3 FEET FROM ,VVXH)RU
35. PRIOR TO ENCLOSING SPACES SUCH AS PLUMBING CHASES, AIR SHAFTS AND RETURN AIR PLENUMS CLEAN ALL AREAS
PROPERTY LINE, ANY OPERABLE WINDOW, AND 10 FEET AWAY FROM ANY FRESH AIR INTAKE. PRODUCT CONVEYING THOROUGHLY. THE CONTRACTOR SHALL GUARANTEE THAT THE PLENUM CHAMBER USED FOR RECIRCULATING OF AIR 1. FOR LOW PRESSURE SYSTEM ANY OF THE FOLLOWING JOINTS ARE ACCEPTABLE: BUTT SLIP; PIPE SLIP; ROLL SLIP; SNAP SLIP; PERMIT
EXHAUST, COMMERCIAL KITCHEN HOOD, ETC. SHALL TERMINATE AT LEAST 10 FEET FROM PROPERTY LINE, OPENINGS WILL BE OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, SOIL STACKS, PLENUM LOCK, AND COMPANION FLANGE.
INTO THE BUILDING, FRESH AIR INTAKE OPENING, ABOVE ADJOINING GRADE. AND 3 FEET FROM EXTERIOR WALL OR ,VVXH'DWH
DOWNSPOUTS, VENTS, EXHAUST DISCHARGES AND OTHER SOURCES WILL BE ENCLOSED SO THAT NO CONTAMINATED
ROOF. 2. ACCEPTABLE LONGITUDINAL SEAMS FOR LOW-PRESSURE SYSTEMS: ACME (GROOVED); SNAP LOCK; STANDING AND SPIRAL.
AIR WILL BE RECIRCULATED. 09-18-17
11. ALL PENETRATIONS IN FIRE WALLS AND FLOOR-AND ROOF -CEILING ASSEMBLIES REQUIRING PROTECTED OPENING SHALL 36. PRIOR TO COMMENCING CONSTRUCTION ACTIVITIES SHUT OFF THE HVAC SYSTEM, BLOCK OFF AIR GRILLES, DIFFUSERS
BE FIRE-STOPPED PROVIDE FIRE STOPPING SPECIFICATIONS INCLUDING MANUFACTURER AND REPORT OF APPROVED AND OTHER OPENINGS OUTSIDE THE IMMEDIATE CONSTRUCTION AREA. OPENINGS TO ADJACENT TENANT SPACES 5HYLVLRQV
TESTING AGENCY. NO. REASON DATE
SHALL BE COVERED WITH FILTER MEDIA TO PREVENT DUST AND OTHER AIRBORNE CONTAMINANTS FROM PASSING TO
12. ALL PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING, HEATING, VENTILATING OR EXHAUST ADJOINING SPACES.
DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. 37. CONTRACTORS TO INSTALL TEMPORARY EXHAUST SYSTEM TO VENTILATE CONSTRUCTION SITE AND KEEP SITE UNDER
13. ALL RIGID DUCTS, PIPES, AND APPLIANCE VENTS LOCATED IN SOUND ASSEMBLIES SHALL BE ISOLATED FROM THE SLIGHT NEGATIVE PRESSURE DURING ALL HOURS OF CONSTRUCTION, EVEN IF AFTER NORMAL BUSINESS HOURS.
BUILDING CONSTRUCTION BY MEANS OF RESILIENT SLEEVES, MOUNTS, OR MINIMUM 1/4" THICK APPROVED RESILIENT 38. CONTRACTORS TO INSTALL TEMPORARY BARRIERS TO PROTECT ADJACENT SPACES FROM DUST, PARTICULATES, DUCT SMOKE DETECTOR SCHEDULE
MATERIAL. (EXCEPTION: GAS PIPING NEED NOT BE LINED). VAPORS AND NOISE. WHERE TEMPORARY BARRIERS ARE INSTALLED ALWAYS MAINTAIN FIRE EXITS AND EXIT WAYS. VELOCITY
14. ALL GAS FIRED HEATING EQUIPMENT SHALL BE "110' (PILOT-LESS) TYPE,
SYMBOL MANUFACTURER AND MODEL POWER REMARKS
15. PROVIDE A 6" CLEARANCE ON FRONT, SIDES AND BACK OF THE FURNACE. MIN MAX
16. SEAL THE CEILING MOUNTED EXHAUST FAN HOUSING TO THE CEILING MEMBRANE. USE APPROVED FIRE STOPPING
SEALANT. 24 VAC / DC
17. THIS PROJECT SHALL COMPLY W/ THE 2013 EDITION OF THE CALIFORNIA BUILDING CODE (T-24), WHICH ADOPTS THE 2013 SD-1 INNOVAIR-DH100ACDCI OR 500 4,000 120 VAC CSFM LISTING 3240-1653:119
APPROVED EQUAL 240 VAC
CBC, 2013 CMC. 2013 CPC & THE 2013 CEC.
18. WHEN MORE THAN ONE HEATING, COOLING, VENTILATING OR REFRIGERATING SYSTEM IS INSTALLED ON THE ROOF OF A
BUILDING OR WITHIN A BUILDING, IT SHALL BE PERMANENTLY IDENTIFIED AS TO THE AREA OR SPACE SERVED BY THE NOTE: COORDINATE POWER REQUIREMENTS WITH ELECTRICAL
EQUIPMENT.
SHEET INDEX
M1.0 HVAC NOTES AND SPECIFICATIONS
KITCHEN NOTES PRINCIPAL IN CHARGE:
STRUCTURAL NOTES M1.1 HVAC SCHEDULES JT
PROJECT MANAGER:
1. AN AIR BALANCE TEST WILL BE REQUIRED TO VERIFY THE PROPER AMOUNT OF OUTSIDE AIR TO COMPLY THE GENERAL CDNTRAC10R SHALL HIRE A CIVIL OR STRUCTURAL ENGINEER REGIS1EREO IN THE STATE OF CALIFORNIA TO
M2.0 HVAC FLOOR PLAN JT
WITH T24 CALCULATIONS, BEFORE FINAL APPROVAL OF THIS PROJECT. DESIGN SEISMIC RESTRAINTS FOR
THE FOLLOWING: DRAWN BY:
M2.1 HVAC ROOF PLAN DL, CQ
2. PRIOR TO MECHANICAL PERMIT FINAL, A SMOKE DETECTOR SHUT-OFF TEST WILL BE REQUIRED. 2013 CMC
609. o. STORAGE RACKS OVER 5'-0" IN HEIGHT. 3URMHFW$GGUHVV
M3.0 HVAC DETAILS
b. MECHANICAL DUCT\VORK AND ROOF MOUNTED MECHANICAL EQUIPMENT.
3. HVAC AND AIR DUCT/ VENT OVER 96 SQUARE INCHES REQUIRE BURGLAR BARS OR SCREEN. c. PIPING (AND/OR) SPRINKLERS. NORM'S RESTAURANT -
d. ELECTRICAL CABLE TRAYS (AND/OR) CONDUITS RUNS. M3.1 HVAC DETAILS INGLEWOOD, CA
4. UPON COMPLETION AND BEFORE FINAL APPROVAL OF THE INSTALLATION OF A VENTILATION SYSTEM W IMPERIAL HWY
TESTING AND BALANCING NOTES SERVING COMMERCIAL FOOD HEAT-PROCESSING EQUIPMENT, A PERFORMANCE TEST MAY BE REQUIRED TO SEISMIC RESTRAINS SHALL BE DEFINED AS BRACINGS, STRUTS, HANGERS AND CONNECTIONS BETWEEN THE ABOVE ITEMS AND M4.0 HOOD DRAWINGS
INGLEWOOD, CA 90303
VERIFY THE RATE OF AIRFLOW AND PROPER OPERATION. THE PERMIT SHALL FURNISH THE NECESSARY THE PRIMARY STRUCTURE AS
1. PROVIDE TESTING AND BALANCING PER SECTION 5.410.4 OF THE CALIFORNIA GREEN BUILDING STANDARDS CODE. M4.1 HOOD DRAWINGS (EXACT ADDRESS TBD BY
TEST EQUIPMENT AND DEVICES REQUIRED TO PERFORM THE TEST. REQUIRED, PROVIDING LATERAL STABILITY IN THE EVENT OF THE CODE PRESCRIBED EARTHQUAKE.
CITY)
2. SYSTEMS TO BE INCLUDED FOR TESTING AND BALANCING INCLUDE: ALL BRACING, STRUTS, HANGERS AND CONNECTIONS SHALL BE DESIGNED IN CONFORMANCE WITH 2013 CBC, ASCE 7-05, CHAPTER M4.2 HOOD DRAWINGS
A. HVAC SYSTEMS AND CONTROLS 13. STRUCTURAL 3URMHFW1XPEHU
B. WATER HEATING SYSTEMS CALCULATIONS AND SEISMIC RESTRAINT DETAILS SHALL BE STAMPED AND PROVIDED TO THE BUILDING INSPECTOR PRIOR TO M4.3 HOOD DRAWINGS
INSPECTION.
78-001-17
3. PERFORM TESTING AND ADJUSTING PROCEDURES IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND
SEISMIC BRACING M4.4 HOOD DRAWINGS
6KHHW7LWOH
APPLICABLE STANDARDS ON EACH SYSTEM. BALANCING SHALL BE IN ACCORDANCE WITH PROCEDURES DEFINED BY THE
TESTING, ADJUSTING, AND BALANCING BUREAU NATIONAL STANDARDS; THE NATIONAL ENVIRONMENTAL BALANCING BUREAU All SUSPENDED UTILITY SYSTEMS WHICH INCLUDE: ELECTRICAL, MECHANICAL, AND PLUMBING EQUIPMENT AND ASSOCIATED M4.5 HOOD DRAWINGS HVAC NOTES AND
PROCEDURAL STANDARDS; ASSOCIATED AIR BALANCE COUNCIL NATIONAL STANDARDS OR AS APPROVED BY THE CONDUIT, DUCTWORK, AND PIPING ARE REQUIRED TO HAVE SEISMIC RESTRAINT ATTACHMENTS DESIGNED TO RESIST THE TOTAL SPECIFICATIONS
ENFORCING AGENCY. DESIGNED SEISMIC FORCES PRESCRIBED IN ASCE 7-05, CHAPTER 13 PROVIDE TYPICAL SEISMIC RESTRAINT DETAILS. M5.0 TITLE 24 ENERGY COMPLIANCE CERTIFICATE
DOCUMENTATION SUBSTANTIATING COMPLIANCE WITH 2013 CBC, ASCE 7-05, CHAPTER 13 TO INCLUDE SEISMIC RESTRAINT
4. AFTER COMPLETION OF TESTING, ADJUSTING, AND BALANCING, PROVIDE A FINAL REPORT OF TESTING SIGNED BY THE ASSEMBLY DETAILS. ANCHORAGE TO OVERHEAD STRUCTURE WITH SUPPORTING ENGINEERING STAMPED BY A LICENSED CIVIL
M5.1 TITLE 24 ENERGY COMPLIANCE CERTIFICATE
INDIVIDUAL RESPONSIBLE PERFORMING THESE SERVICES. OR STRUCTURAL ENGINEER IS REQUIRED AT TIME OF INSPECTION. 'CITY POLICY"
6KHHW1XPEHU
M1.0

12/4/2017 2:24:03 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
MECHANICAL ABBREVIATIONS ROOFTOP UNIT SCHEDULE
CONDENSER
COOLING CAPACITY HEATING CAPACITY BTU/ HR ELECTRICAL
E.A.T. UNIT
A.D. ACCESS DOOR SUPPLY MIN. O.A. E.S.P. E.E.R.
PLAN MARK SERVICE MANUFACTURER MODEL NO. HEAT SUPPLY WEIGHT REMARKS
(CFM) (CFM) W.C. E.A.T. L.A.T. TOTAL SENSIBLE HEAT INPUT AMBIENT (S.E.E.R.)
OUTPUT AFUE % FAN VOLTS PHASE MCA MOCP (LBS)
A.F.F. ABOVE FINISHED FLOOR (°F DB/WB) (°F DB) (MBH) (MBH) (MBH) (°F)
(MBH) (H.P.)
$5&+,7(&785(
CFM CUBIC FEET PER MINUTE &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
PROVIDE PROGRAMMABLE THERMOSTAT, SMOKE DETECTOR IN
RTU-1 DINING LENNOX LGH102H4B 3,400 850 1.0 80 / 67 55 103,800 72,536 180,000 144,000 80 105 3 208 3 43 50 12.0 1500 LBS SUPPLY PLENUM, COMPLETE ECONOMIZER SYSTEM, POWER û‚¹¼ċ™‚ċĖû™‹&Ђí
CUH CABINET UNIT HEATER EXHAUST, C02 SENSOR AND STANDARD ROOF CURB
7KH3URPHQDGH1RUWK
PROVIDE PROGRAMMABLE THERMOSTAT, SMOKE DETECTOR IN /RQJ%HDFK&$
D.G. DOOR GRILLE, SEE ARCH. DWG'S. ZZZLGDH[SHULHQFHQHW
RTU-2 KITCHEN LENNOX LGH092H4B 3,000 750 1.0 80 / 67 55 90,000 69,153 180,000 144,000 80 105 3 208 3 42 50 12.0 1500 LBS SUPPLY PLENUM, COMPLETE ECONOMIZER SYSTEM, C02
SENSOR AND STANDARD ROOF CURB
EF EXHAUST AIR FAN
PROVIDE PROGRAMMABLE THERMOSTAT, SMOKE DETECTOR IN $UFKLWHFW
RTU-3 KITCHEN LENNOX LGH092H4B 3,000 750 1.0 80 / 67 55 90,000 69,153 180,000 144,000 80 105 3 208 3 42 50 12.0 1500 LBS SUPPLY PLENUM, COMPLETE ECONOMIZER SYSTEM, C02
ET EXPANSION TANK SENSOR AND STANDARD ROOF CURB
PROVIDE PROGRAMMABLE THERMOSTAT, SMOKE DETECTOR IN
E.T.R. EXISTING TO REMAIN RTU-4 DINING LENNOX LGH120H4B 4,000 1200 1.0 55 122,000 89,568 180,000 144,000 80 105 5 208 3 56 70 12.0 1500 LBS SUPPLY PLENUM, COMPLETE ECONOMIZER SYSTEM, POWER
*(2))5(<%/,0
80 / 67
EXHAUST, C02 SENSOR AND STANDARD ROOF CURB $,$1&$5%/(('$3
F.C. FLEXIBLE CONNECTION PROVIDE PROGRAMMABLE THERMOSTAT, SMOKE DETECTOR IN
RTU-5 DINING LENNOX LGH102H4B 3,400 850 1.0 80 / 67 55 103,800 72,536 180,000 144,000 80 105 3 208 3 43 50 12.0 1500 LBS SUPPLY PLENUM, COMPLETE ECONOMIZER SYSTEM, POWER Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
F.O.B. FLAT ON BOTTOM EXHAUST, C02 SENSOR AND STANDARD ROOF CURB original
signature by the licensed professional may have been
NOTES: fraudulently altered and shall not be considered an original
F.O.T. FLAT ON TOP copy. All information should be disregarded unless verified
by the professional whose signature appears above.
1. ALL ROOFTOP UNITS SHALL HAVE A MINIMUM OF SCR OF 15 kA. Copyright Protected 2016.
G.I. GALVANIZED IRON 2. ALTERNATE MANUFACTURERS ACCEPTED: TRANE AND CARRIER
(QJLQHHULQJ&RQVXOWDQW
HC HEATING COIL
L WALL LOUVER EXHAUST FAN SCHEDULE
EXTERNAL ELECTRICAL
MOD MOTOR OPERATED CONTROL DAMPER OPER.
STATIC
DESIG'N SERVICE MFG'R MODEL NO. TYPE CFM RPM BHP H.P. PHASE WEIGHT REMARKS
PRESSURE VOLTAGE
N.C NEW CONNECTION TO EXISTING (WATTS) ( ) (LBS.)
(''W.C.)
INTERLOCK WITH EF-2, EF-3, EF-4, EF-5, MAU -1,
N.T.S. NOT TO SCALE CAPTIVE MAU-2, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
EF-1 HOOD 1 DU180 HFA UPBLAST 2400 1.2 1121 0.750 2 3 208 187 LBS REFER TO KITCHEN HOOD DRAWINGS FOR MORE
AIRE
O.C. ON CENTER INFORMATION
INTERLOCK WITH EF-1, EF-3, EF-4, EF-5, MAU -1,
RTU ROOF TOP HVAC UNIT CAPTIVE MAU-2, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
EF-2 HOOD 2 DU180 HFA UPBLAST 2400 1.2 1121 0.750 2 3 208 187 LBS REFER TO KITCHEN HOOD DRAWINGS FOR MORE
AIRE
S SENSOR FOR ROOFTOP UNIT INFORMATION
INTERLOCK WITH EF-1, EF-2, EF-4, EF-5, MAU -1,
SD DUCT SMOKE DETECTOR CAPTIVE MAU-2, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
EF-3 HOOD 3 DU180 HFA UPBLAST 3312 1.3 1326 1.255 2 3 208 187 LBS REFER TO KITCHEN HOOD DRAWINGS FOR MORE
AIRE
INFORMATION
SF SUPPLY AIR FAN 3URMHFW2ZQHU
INTERLOCK WITHEF-1, EF-2, EF-3, EF-5, MAU -1,
CAPTIVE MAU-2, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
S.S. STAINLESS STEEL EF-4 HOOD 4 DU180 HFA UPBLAST 3510 1.1 1322 1.242 2 3 208 187 LBS REFER TO KITCHEN HOOD DRAWINGS FOR MORE
AIRE
INFORMATION
T THERMOSTAT INTERLOCK WITHEF-1, EF-2, EF-3, EF-4, MAU -1,
CAPTIVE MAU-2, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
EF-5 HOOD 5 DU50 HFA UPBLAST 1000 0.5 1355 0.282 1/2 1 115 92 LBS REFER TO KITCHEN HOOD DRAWINGS FOR MORE
UV UNIT VENTILATOR AIRE
INFORMATION
U.C.D. UNDER CUT DOOR, SEE ARCH. DWG'S
CAPTIVE PROVIDE MANUFACTURER ROOF CURB.
EF-6 RESTROOMS DR33HFA DOWNBLAST 700 0.5 1408 0.190 1/3 1 115 74 LBS
U.N.O. UNLESS NOTED OTHERWISE AIRE INTERLOCK WITH BUILDING TIME CLOCK.
ARCH ARCHITECT OR ARCHITECTURAL NOTE:
ALL MOTORS SHALL BE 'ODP' WITH 1.15 SERVICE FACTOR, UNLESS OTHERWISE NOTED.
BLD'G BUILDING
BOT. BOTTOM
CL'G. CEILING
MAKE-UP AIR UNIT SCHEDULE
FAN SECTION COOLING SECTION ELECTRICAL
COL. COLUMN
DESIG'N MFG'R MODEL NO. L.A.T. ROOF CURB REMARKS
S.P. E.A.T. FAN
CFM TYPE (DB°F)/ VOLTAGE PHASE
CONC. CONCRETE (''W.C.) (°F) (H.P.)
(WB°F)
CONST'N CONSTRUCTION INTERLOCK WITHEF-1, EF-2, EF-3, EF-4, MAU -1,
CAPTIVE EVAP; EF-5, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
MAU-1 A2-615 4080 0.5 90 73 / 65 3 208 3 12" REFER TO KITCHEN HOOD DRAWINGS FOR MORE
CONT'R CONTRACTOR AIRE CELDEK
INFORMATION
INTERLOCK WITHEF-1, EF-2, EF-3, EF-4, MAU -1,
DET. DETAIL CAPTIVE EVAP; EF-5, RTU-1, RTU-2, RTU-3, RTU-4, AND RTU-5.
MAU-2 A2-615 5425 0.5 90 73 / 65 5 208 3 12" REFER TO KITCHEN HOOD DRAWINGS FOR MORE
AIRE CELDEK
DN. DOWN INFORMATION
DWG. DRAWING
1RUPV5HVWDXUDQWV//&
E.A.T. ENTERING AIR TEMPERATURE /DNHZRRG%OYG
%HOOIORZHU&$
E.W.T. ENTERING WATER TEMPERATURE
DIFFUSER AND GRILLE SCHEDULE 6WDPS
FL'R FLOOR
MOUNTING CEILING
PLAN MARK SERVICE MODULE NECK SIZE MATERIAL FINISH MANUFACTURER MODEL NO. REMARKS
GA. GAUGE LOCATION TYPE
BAKED ENAMEL/
H/AC HEATING AND AIR CONDITIONING S1 CFM SUPPLY 24x24 SEE PLANS CEILING LAY IN ALUMINUM TITUS PAR SEE NOTES
WHITE
L.A.T. LEAVING AIR TEMPERATURE
BAKED ENAMEL/
S2 CFM SUPPLY 24x24 SEE PLANS CEILING LAY IN ALUMINUM TITUS TMS SEE NOTES
WHITE
L.W.T. LEAVING WATER TEMPERATURE
BAKED ENAMEL/
MT'D MOUNTED S3 CFM SUPPLY 24x24 SEE PLANS CEILING GYP BOARD ALUMINUM TITUS TMS SEE NOTES
WHITE
REQ'D REQUIRED BAKED ENAMEL/
S4 CFM SUPPLY 12x12 SEE PLANS CEILING GYP BOARD ALUMINUM TITUS TMS SEE NOTES
WHITE
,VVXH)RU
S.S.T. SATURATED SUCTION TEMPERATURE
4'-0" FLOWBAR WITH 1" SLOT WIDTH; 2 SLOTS;
SEE BAKED ENAMEL/ PERMIT
S5 CFM SUPPLY SEE PLANS CEILING LAY IN ALUMINUM TITUS FL 10 PROVIDE WITH MANUFACTURER INSULATED
E.S.P. EXTERNAL STATIC PRESSURE REMARKS WHITE
PLENUM. SEE NOTES. ,VVXH'DWH
T.S.P. TOTAL STATIC PRESSURE 09-18-17
5HYLVLRQV
W/ WITH NO. REASON DATE
BAKED ENAMEL/
R1 CFM RETURN 24x24 22x22 CEILING LAY IN ALUMINUM TITUS 355 FL SEE NOTES
WHITE
DIAMETER/ROUND
BAKED ENAMEL/
୉ OVAL R2 CFM RETURN 36x36 34x34 CEILING GYP BOARD ALUMINUM TITUS 355 FL SEE NOTES
WHITE
0'-0'' ELEVATION FOR BOTTOM OF DUCT FROM FINISH FLOOR
BAKED ENAMEL/
E1 CFM EXHAUST 12x12 SEE PLANS CEILING GYP BOARD ALUMINUM TITUS 50 F SEE NOTES
WHITE
MECHANICAL SYMBOLS
BAKED ENAMEL/
T1 CFM TRANSFER 24x6 - SIDEWALL - ALUMINUM TITUS 355 FL SEE NOTES
WHITE
TYPICAL SUPPLY DIFFUSER. S_ CFM
NOTES:
1. PROVIDE 24x24 MODULE FOR All DIFFUSERS INSTALLED IN LAY--IN CEILINGS.
R_ CFM 2. FRAME All AIR DEVICES FOR APPROPRIATE CEILING TYPE.
TYPICAL RETURN OR EXHAUST GRILLE. 3. PROVIDE ALUMINUM FRAME FOR HARD CEILINGS IN TOILETS, JANITOR'S CLOSET AND LOCK-UP ROOM.
E_ CFM 4. FLEXIBLE DUCTS CONNECTING THE DIFFUSERS SHALL BE FULL SIZE OF NECK DIAMETER.
5. MAXIMUM NOISE CRITERION RATING < 30 PRINCIPAL IN CHARGE:
6. BAKED ENAMEL FINISH, COLOR TO BE \I/HITE OR BY ARCHITECTURAL SPECIFICATIONS. JT
7. DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE INDICATED ON PLANS.
AIRFOIL TURNING VANES, TYPICAL FOR ALL SQUARE TURNS. PROJECT MANAGER:
8. MOUNTING FRAME TYPE SHALL BE COORDINATED \l/ITH CEILING CONSTRUCTION TYPE, COORDINATE WITH ARCHITECT. JT
9. NECK DIAMETER SHALL BE PER MANUFACTURER.
DRAWN BY:
10. DEVICE SHALL BE PAINTED BY PAINTING CONTRACTOR TO MATCH ADJACENT CEILING SURFACES PER ARCHITECTURAL SPECIFICATIONS. DL, CQ
FLEXIBLE DUCTWORK, FLEXMASTER TRIPLE LOCK ALUMINUM DUCTWORK,
11. WITH DIRECTIONAL BLADES. 3URMHFW$GGUHVV
MAXIMUM 2'-0'' LONG.
12. PROVIDE SUBMITTAL FOR ARCHITECT'S / ENGINEER REVIEW AND APPROVAL.
T THERMOSTAT WITH DEVICE CONTROLLED. NORM'S RESTAURANT -
INGLEWOOD, CA
S SENSOR WITH DEVICE CONTROLLED. W IMPERIAL HWY
AIR BALANCE SCHEDULE INGLEWOOD, CA 90303
SD DUCT SMOKE DETECTOR
EQUIPMENT RTU-1 RTU-2 RTU-3 RTU-4 RTU-5 EF-1 EF-2 EF-3 EF-4 EF-5 EF-6 MAU-1 MAU-2 TOTALS (EXACT ADDRESS TBD BY
SUPPLY AIR DUCT UP OUTSIDE AIRFLOW ( CFM ) 850 750 750 1,200 850 4,080 5,425 13,905 CITY)
SUPPLY AIR DUCT DOWN RETURN AIRFLOW ( CFM ) 2,550 2,250 2,250 2,800 2,550 12,400 3URMHFW1XPEHU
RETURN/ EXHAUST AIR DUCT UP SUPPLY AIRFLOW ( CFM ) 3,400 3,000 3,000 4,000 3,400 4,080 5,425 26,305
78-001-17
RETURN/ EXHAUST AIR DUCT DOWN EXHAUST AIRFLOW ( CFM ) 2,400 2,400 3,312 3,510 1,000 700 13,322
6KHHW7LWOH
BUILDING PRESSURE ( CFM ) 850 750 750 1,200 850 -2,400 -2,400 -3,312 -3,510 -1,000 -700 4,080 5,425 583
HVAC LEGEND AND
RESULTING BUILDING PRESSURIZATION ( CFM ) 583 SCHEDULES
6KHHW1XPEHU
M1.1

12/4/2017 2:24:04 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
KEYED NOTES ' '
1. SUPPLY AND RETURN DUCTS (LINED) UP THRU ROOF TO RTU-1.
2. SUPPLY AND RETURN DUCTS (LINED) UP THRU ROOF TO RTU-2.
3. SUPPLY AND RETURN DUCTS (LINED) UP THRU ROOF TO RTU-3.
4. SUPPLY AND RETURN DUCTS (LINED) UP THRU ROOF TO RTU-4.
.1 2 2.4 3 4 5 6 7 8
5. SUPPLY AND RETURN DUCTS (LINED) UP THRU ROOF TO RTU-5.
$5&+,7(&785(
6. 16" Ø GREASE EXHAUST DUCT (DOUBLE WALL) UP THRU ROOF TO EF-1 (2400 CFM). &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
7. 16" Ø GREASE EXHAUST DUCT (DOUBLE WALL) UP THRU ROOF TO EF-2 (2400 CFM).
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
8. 18" Ø GREASE EXHAUST DUCT (DOUBLE WALL) UP THRU ROOF TO EF-3 (3312 CFM).
ZZZLGDH[SHULHQFHQHW
9. 18" Ø GREASE EXHAUST DUCT (DOUBLE WALL) UP THRU ROOF TO EF-4 (3510 CFM).
$UFKLWHFW
10. 12"x12" EXHAUST DUCT UP THRU ROOF TO EF-5 (1000 CFM).
11. 12"X12" EXHAUST DUCT UP THRU ROOF TO EF-6 (700 CFM).
*(2))5(<%/,0
12. MAKE UP AIR DUCT THRU ROOF TO MAU-1 (4080 CFM) $,$1&$5%/(('$3
13. MAKE UP AIR DUCT THRU ROOF TO MAU-2 (5425 CFM) Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
14. 28x10 MAKE UP AIR CONNECTION TO HOOD. BALANCE TO 680 CFM. signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
15. 28X12 MAKE UP AIR CONNECTION TO HOOD. BALANCE TO 882 CFM. by the professional whose signature appears above.
Copyright Protected 2016.
16. 28X12 MAKE UP AIR CONNECTION TO HOOD. BALANCE TO 925 CFM.
(QJLQHHULQJ&RQVXOWDQW
17. 24X8 SUPPLY AIR FROM RTU CONNECTION TO HOOD. BALANCE TO 350 CFM.
18. 24X8 SUPPLY AIR FROM RTU CONNECTION TO HOOD. BALANCE TO 375 CFM.
19. PROVIDE DUCT SMOKE DETECTOR IN SUPPLY PLENUM.
20. PROPOSED LOCATION OF ALL A/C THERMOSTAT IN THE OFFICE AT MINIMUM 4'-0" AFF. PROVIDE MATCHING
SENSORS AT MINIMUM 6'-0" AFF.
12"x12" 21. TRANSFER GRILLE AS HIGH AS POSSIBLE BELOW CEILING. INSTALL GRILLE ON EACH SIDE OF WALL.
D D
22"x16"
11 R1 1425
6"ø 20
R1 1425 22"x14" 14"x14"
S1 400 MAU-1

20"x22"
4" RTU-3
12"ø

RTU-2 "x1 17 40"x16"


24"x8"

22
24"x8"

24"x8"

24"x8"
S 22"x16"

10"ø

10"ø
12"ø

6"ø
RTU-2 30"x14"

8"ø
S1 400
2 19 S1 400
E1 300 E1 300 SD 3URMHFW2ZQHU
SD 17 EF-1 14 17
3 14 14 14 17
19 EF-2 14 12
12"ø 14
8"ø 10"ø 14"x12" RTU-5
12 7

30"x14"
"ø 6

36"x14"
8 10 EF-5
1 12 4
HOOD 2 HOOD 1

10"ø
RTU-1 "ø
18"ø 36"x14"

8"ø
8"ø
SD S RTU-3 R1 2000

6"ø
T R-1 150 EF-3
S1 300 20
20 T
36"x14" T S2 150 40"x14"

6"ø
T R1 1500

14"ø
19 5

14"ø
MAU-2 T HOOD 5
R1 2000
26"x18" 19
S3 200 RTU-4 SD
HOOD 3 HOOD 4

30"x16"
S4 50 19
36"x14"

14"ø 28"x12" 34"x16" SD


EF-4
26"x12" 9 14"ø

36"x14"
26"x18"
S3 200 15 15 15 16 16 16 R1 1500
36"x14"

13 E1 100

10"ø
24"x12" S1 300
C C

10"ø
17 17 18 18

36"x14"
24"x8"

24"x8"

24"x8"
24"x8"
R2 4000

26"x10"
18"x16" 30"x16"

28"x12"
S5 350

10"ø
R2 4000

10"ø
S3 375
8"ø

26"x10"
S3 375 S5 250 GENERAL NOTES 1RUPV5HVWDXUDQWV//&
8"ø S5 250
12"x12" 18"x12" 18"x12" /DNHZRRG%OYG

18"x10"
S5 200 1. PROVIDE MANUAL VOLUME DAMPERS AT ALL SUPPLY, RETURN, AND MAKE UP AIR
%HOOIORZHU&$

10"ø
10"ø
BRANCHES.

10"ø

20"x10"
10"ø
8"ø 6WDPS
8"ø 2. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR BALANCING OF ALL HVAC

32"x10"
S5 200 DISTRIBUTION SYSTEMS. AIR BALANCING SHALL BE PERFORMED BY AN AABC OR NEBB
S5 250 CERTIFIED ENGINEER. COPY OF THE REPORT TO BE FORWARDED TO THE OWNER.
S5 250
S5 250 PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH DUCTS AS REQUIRED. PROVIDE
8"ø
CABLE/ ELECTRONIC VOLUME DAMPERS AT ALL IN-ACCESSABLE CEILING LOCATIONS.
S5 350 S5 350 S5 350 S5 350
3. SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED WITH MINIMUM 1" THICK

18"x10"
8"ø
BLANKET TYPE INSULATION WITH VAPOR BARRIER.
8"ø 8"ø
B.3

26"x10"
4. GREASE DUCT SHALL BE DOUBLE WALL, FACTORY BUILT GREASE DUCT FOR USE WITH
S5 250 S5 250 TYPE I KITCHEN HOODS, WHICH CONFORMS TO THE REQUIREMENTS OF NFPA-96.
S5 250 DOUBLE WALL DUCT SYSTEMS SHALL BE PROVIDED AND INSTALLED WITH ACCORDANCE
S5 250 8"ø TO THE CITY MECHANICAL CODE, FIRE CODE, AND ALL APPLICABLE LOCAL CODES.
8"ø

26"x10"
5. ALL JOINTS AND SEAMS OF THE THE DISHWASHER EXHAUST DUCT TO BE SEALED ,VVXH)RU
8"ø WATERTIGHT W/ SILICON OR EQUAL.
8"ø

18"x10"
T1 500 S5 250 S5 250 S5 250
PERMIT
21 6. MAKE UP AIR SYSTEMS ARE REQUIRED FOR ALL EXHAUST SYSTEMS. THE EXHAUST AND
,VVXH'DWH
MAKE UP AIR SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED SO THAT ONE SWITCH
S5 250 S5 250
RTU-1 S5 250 S5 250 ACTIVATES BOTH. 09-18-17
8"ø
S5 250 S 8"ø 5HYLVLRQV
B NO. REASON DATE
8"ø
B
8"ø
S5 250 8"ø
20
A.8 8"ø
S5 250

20"x10"
8"ø
20 20
8"ø
8"ø S5 250
8"ø
8"ø 8"ø
8"ø
S 8"ø S
A.2 RTU-4 RTU-5 8"ø
8"ø
8"ø 8"ø

8"ø
S5 250
S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250 S5 250
A A
0.9
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
KITCHEN HOOD NOTE DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
BEFORE ORDERING HOODS VERIFY INCOMING WATER PRESSURE OF SPRINKLER SERVICE.
KITCHEN HOODS FIRE SUPPRESSION SYSTEM REQUIRES A MINIMUM WATER PRESSURE OF 45 NORM'S RESTAURANT -
PSI AT THE HOODS TO OPERATE PROPERLY, NOTIFY HOOD MANUFACTURER OF AVAILABLE
PRESSURE TO CONFIRM HOOD DESIGN WILL WORK OR IF NAY DESIGN CHANGES ARE
INGLEWOOD, CA
0.1 1 2 2.4 3 4 5 6 7 8 REQUIRED PRIOR TO ORDERING HOODS. W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HVAC FLOOR PLAN
+9$&)/2253/$1
   
6KHHW1XPEHU
M2.0

12/4/2017 2:24:14 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
KEYED NOTES ' '
.1 2 2.4 3 4 5 6 7 8
1. ROOFTOP GAS-ELECTRIC A/C UNITS, WITH MANUFACTURER'S VIBRATION ISOLATION CURB
COMPLETE WITH CALIFORNIA SEISMIC RESTRAINTS AS REQUIRED.
2. EXHAUST FAN WITH FACTORY MANUFACTURED CURB.
3. MAKE UP AIR UNIT WITH FACTORY MANUFACTURED CURB.
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
(QJLQHHULQJ&RQVXOWDQW
GAS CONNECTION BY
PLUMBING CONTRACTOR.
REFER TO PLUMBING PLANS. (TYP)
D D
2 EF-6
MAU-1 3
RTU-2 1
3" PLUMBING VENT
THRU ROOF; SEE
DETAIL
HB 2 EF-1 EF-2 2
3URMHFW2ZQHU
EF-3 2 EF-5 2
RTU-3 1
1 RTU-1
EF-4 2
MAU-2 3
3" PLUMBING VENT
THRU ROOF; SEE 40 RTU-4 1 RTU-5 1
DETAIL
C C
REFRIGERATION RACK
33A
REFER TO KITCHEN PLANS
CONDENSER
REFER TO KITCHEN PLANS
ROOF DRAIN. TYPICAL
GENERAL NOTES 1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
A. MAINTAIN A MIN. OF 10'·0" BETWEEN ALL EXHAUST AND VENTS TO ANY FRESH AIR SUPPLY OR INTAKES
INTO THE BUILDING (OUTSIDE AIR FOR THE A/C UNITS AND M.AKE UP AIR UNITS)
6WDPS
B. GENERAL CONTRACTOR TO FURNISH ON SITE OR INSTALL FACTORY EQUIPMENT CURB AND LEVEL
PLATFORM. LOCATE 50 THAT ROOF PENETRATIONS OCCUR BETWEEN TRUSSES, PROVIDE DUCT
TRANSITION ADAPTOR WHERE REQUIRED.
C. ALL WORKS ON Ti1E ROOF AND FINAL LOCATIONS OF T!-IE HVAC UNITS SHALL BE COORDINATED AND
APPROVED BY THE OWNER AND STRUCTURAL ENGINEER
D. INSTALLATION OF ANY NEW HVAC CURBS ON ROOF OR ANY ROOF PENETRATIONS SHALL BE PERFORMED
IN STRICT ACCORDANCE WITH WITH THE LOCAL CITY BUILDING CODE AND MANUFACTURER'S
B.3 SPECIFICATIONS TO MAINTAIN ALL APPLICABLE EQUIPMENT WARRANTIES.
E. UNLESS OTHERWISE NOTED, ALL HVAC PIPINGS, VENTS, SHALL BE RUN INTO THE ATTIC SPACE, ABOVE
CEILING OR TO THE BUILDING SHAFT MUST INSULATE ALL PIPING INTO T!-IE BUILDING. NO ADDITIONAL
PENETRATION OF THE ROOF SHALL BE MADE WITHOUT THE 0WNER'S APPROVAL.
,VVXH)RU
F. PROVIDE 4' CASCO HP CLASS I FLEXIBLE DUCTWORK RATED FOR I" SP END CONNECTION TO AIR OUTLET.
FLEXIBLE CONNECTIONS SHALL MEET NFPA SPECS AND BE UL LISTED AND F!RE MARSHALL APPROVED.
PERMIT
,VVXH'DWH
G. ALL JOINTS OF EXP0SED DUCTWORK SHALL BE SEALED FROM AIR LEAKAGE WATERTIGHT WITH ARABOL
AND CANVAS. JOINTS OF PROTECTED DUCTWORK SHALL BE TAPED WITH NASHUA NO. 357 PRESSURE 09-18-17
SENSITIVE TAPE OR EQUAL. 5HYLVLRQV
NO. REASON DATE
H. LABEL ALL EQUIPMENT FOR IDENTIFICATION IN ACCORDANCE AND IN COMPLIANCE WITH BUILDING
B B MECHANICAL CODE TO IDENTIFY EQUIPMENT FOR THE SPACES TO WHICH AREA ARE BEING SERVED.
I. DRAWING IS DIAGRAMMATIC LAYOUT OF DUCTWORK AND EQUIPMENT LOCATION BASED STRUCTURAL
A.8 AND INFORMATION SUPPLIED BY ARCHITECT. MECHANICAL CONTRACTOR TO COORDINATE WITH
STRUCTURAL AND ARCHITECTURAL PLANS PRIOR TO ONSET OF CONSTRUCTION.
A.2
A A
0.9 PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HVAC ROOF PLAN
6KHHW1XPEHU
0HFK M2.1
  

12/4/2017 2:24:16 PM
H:\17317\RVT\17317_R16.rvt
 0.1 1 2 2.4 3 4 5 6 7 8
'HVLJQ&RQVXOWDQW
NOTES: NOTE-A SUPPLY AND RETURN RISERS WITH DUCT SUPPORT RAILS
1. ALL DUCTWORK CONSTRUCTED IN ACCORDANCE WITH ASHRAE BRANCH DUCT 1'' THICK, 3 PCF FLEXIBLE DUCT
1 IN 4 SLOPE MINIMUM 10' FROM
HANDBOOK AND PRODUCT DIRECTORY 1988 EQUIPMENT LINER; DUCT DIMENSIONS SHALL BE FLEXIBLE CONNECTOR
MAIN DUCT ADJACENT BUILDINGS,
VOLUME, CHAPTER NO. 1. 6'' FULL SIZE OF ROOFTOP UNIT
PROPERTY LINES, AND
CONNECTIONS 3'' THICK, 6 PCF RIGID DUCT LINER;
AIR INTAKES
2. ALL CONTRACTOR FABRICATED AND MANUFACTURER AIRFLOW INSTALL TO ROOF IN ALL OPEN
FABRICATED COMPONENTS OF THE OUTSIDE AIR, SUPPLY AIR, 45° SPACES INSIDE ROOF CURB
AIRFLOW
RETURN AIR AND EXHAUST SYSTEMS SHALL BE CONSTRUCTED NOTE-A: HINGED TO ROOF OPENING 1/2''
AND INSTALLED AIR-TIGHT. REFER TO DUCTWORK SEALANT
45° LARGER THAN DUCTWORK
BRANCH TAKE-OFF PERMIT ROOF CONSTRUCTION
DETAILS ON THIS SHEET. PIPE OPENINGS IN SYSTEM INSPECTION AND APPROVED GREASE ALL AROUND $5&+,7(&785(
45° TRANSITION FITTING
COMPONENTS SHALL HAVE SHEET METAL BAFFLES, SET IN 6'' CLEANING RESERVOIR &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
DEPTH AT CONNECTION MIN. 40" STRUCTURAL MEMBER
LEAKAGE.
SEALANT, TO PREVENT 1 IN 4 SLOPE STRUCTURAL MEMBER û‚¹¼ċ™‚ċĖû™‹&Ђí
TO MAIN SHALL BE 1''
MAIN DUCT 6'' LESS THAN MAIN DUCT VENTED ROUTE DUCTWORK TIGHT 7KH3URPHQDGH1RUWK
BRANCH DUCT ROUTE DUCTWORK TIGHT /RQJ%HDFK&$
EXTENSION TO STRUCTURAL MEMBER TO STRUCTURAL MEMBER
1 IN 4 SLOPE DEPTH AND TRANSITION ZZZLGDH[SHULHQFHQHW
BRANCH DUCT NOTE-A
TO BRANCH DUCT ROOF CURB GREASE DUCT SHALL
NOTE-A DIMENSION. EXTEND A MINIMUM $UFKLWHFW
18" ABOVE THE ROOF
SURFACE
TYPICAL DOUBLE BRANCH TYPICAL SINGLE BRANCH RETURN AIR DUCTWORK; SEE
SUPPLY AIR DUCTWORK; PLANS FOR SIZES *(2))5(<%/,0
DOUBLE WALL SEE PLANS FOR SIZES
TAKE-OFF TAKE-OFF $,$1&$5%/(('$3
GREASE DUCT 3'' THICK, 6 PCF RIGID DUCT LINER; INSTALL TO
NOT TO SCALE NOT TO SCALE
SQUARE TURN TRANSITION ELBOW UNDERSIDE OF ROOF CONSTRUCTION WITH
Plans, maps, specifications, studies, and reports not
WITH TURNING VANES FULL COAT OF ADHESIVE AND MECHANICAL containing a red ink seal imprint accompanied by an
original
FASTENERS; SEAL ALL AROUND OPENING WITH signature by the licensed professional may have been
BRANCH DUCT SILICONE BASED SEALANT fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
'D' DIMENSION Copyright Protected 2016.
NOTES:

W
1. FITTING 29° AND LESS DO NOT TYPICAL KITCHEN EXHAUST FAN DETAIL - UPBLAST ROOFTOP UNIT DUCT DROP DETAIL

O
REQUIRE TURNING VANES. (QJLQHHULQJ&RQVXOWDQW

FL
NOT TO SCALE NOT TO SCALE

R
DUCT NECK

AI
2. TURNING VANE IS OF THE SAME L
CL
'D' DIMENSION GAUGE METAL AS THE FITTING.
NECK CONNECTION AT R = 1/3 'W' (W/NOT LESS THAN 3'')
RADIUS = 1-1/2W TOP OF DIFFUSER OR S
PROVIDE 6'' LONG S = 1/3 'W'
MAXIMUM FLEXIBLE GRILLE.
L = 1/3 'W' R OUTLINE OF MECHANICAL ROOFTOP
CONNECTION. EQUIPMENT. INSTALL TO ROOF CURB AS
PER MANUFACTURER'S DIRECTION 1/4'' THICK NEOPRENE GASKET
PROVIDE OR INSTALL
W TURNING VANES W MANUFACTURER SUPPLIED 1/4'' EXHAUST FAN EQUIPMENT BASE;
1. DUCT BRANCH AND DUCT NECK SHALL BE RIGID SHEET METAL PROVIDE 16 GAUGE GALVANIZED IRON
THICK NEOPRENE RUBBER CURB FASTEN TO WOOD NAILER WITH
CONSTRUCTION. COUNTERFLASHING AND FASTEN TO WOOD SCREWS 6'' ON CENTER
2. FLEXIBLE CONNECTION SHALL BE METAL-EDGE VENTILATION GASKET NAILER WITH SCREWS, 6'' ON CENTER
FABRIC OR TRIPLE-LOK FLEXIBLE ALUMINUM AIR DUCT.
PROVIDE TREATED WOOD WOOD NAILER
NAILER, THICKNESS AND PROVIDE RIGID INSULATION, THICKNESS MINIMUM 12'' HIGH
HEIGHT AS REQUIRED FOR AND HEIGHT AS REQUIRED BY CURB
TYPICAL 30° TO 90° RADIUS TYPICAL TOP CONNECTION TO TYPICAL 30° TO 89° CURB DIMENSIONS. FASTEN DIMENSIONS CURB LINER SHALL BE WELDED
NAILER TO CURB WITH MINIMUM 12'' HIGH LIQUID TIGHT TO CURB SHELL
ELL TURN FITTING DIFFUSER OR GRILLE DETAIL TURN FITTINGS ROOFING FELT OR MEMBRANE
SCREWS, 6'' ON CENTER
NOT TO SCALE NOT TO SCALE NOT TO SCALE 3URMHFW2ZQHU
PROVIDE RIGID INSULATION
CANT STRIP, 4'' HIGH MINIMUM ROOF INSULATION
AIRFOIL TURNING VANES THYCURB MODEL TC-1
AIRFOIL TURNING VANES PREFABRICATED UNINSULATED
(SEE SMALL VANE DETAIL) (SEE LARGE VANE DETAIL) EQUIPMENT MANUFACTURER
SUPPLIED TAPERED TYPE ROOF GALVANIZED ROOF CURB WITH 18
CURB. PROVIDE ASSEMBLY OF ROOF INSULATION GAUGE GALVANIZED SHEETMETAL
18'' & SMALLER LINER EXISTING ROOF
CURB AS PER MANUFACTURER'S
BRANCH DUCT 18'' & SMALLER CONSTRUCTION
MAIN DUCT DIRECTIONS
2-1/8'' 3-1/4'' 2-1/4'' RADIUS
TYPICAL TYPICAL DUCT RISER
AIRFLOW DUCT
C
L ROOF CONSTRUCTION
AIRFLOW TURNING ROOF OPENING AS REQUIRED
VANES SIZE AND 1'' RADIUS 90° BY MECHANICAL ROOFTOP NOTES:
SPACING SAME AS 90° EQUIPMENT 1. TYPICAL FOR KITCHEN EXHAUST FAN AND DUCTWORK ONLY.
TURN FITTING OF 2'' RADIUS NOTES: 2. CURB SHALL HAVE BUILT IN PITCH TO MATCH THE PITCH OF THE ROOF.
BRANCH DUCT EQUIVALENT SIZE. 90° 4-1/2'' RADIUS 1. SEE ARCHITECTURAL DRAWINGS FOR ROOF CURB INSTALLATION DIRECTIONS AND ROOFING. 3. SEE ARCHITECTURAL DRAWINGS FOR ROOF CURB INSTALLATION DIRECTIONS AND
SMALL DOUBLE AIRFOIL 2. CURB SHALL BE TAPERED TYPE AND MATCH THE PITCH OF THE ROOF. ROOFING.
TURNING VANE LARGE DOUBLE AIRFOIL 3. SECURELY INSTALL CURB TO ROOF; USE FASTENERS AS REQUIRED BY ROOF CONSTRUCTION. 4. SECURELY INSTALL CURB TO ROOF; USE FASTENERS AS REQUIRED BY ROOF
TURNING VANE CONSTRUCTION.
TYPICAL MECHANICAL EQUIPMENT ROOF CURB INSTALLATION DETAIL KITCHEN EXHAUST ROOF CURB DETAIL
TYPICAL DOUBLE 90° TYPICAL 90° TURN FITTING TYPICAL 90° TURN FITTING NOT TO SCALE NOT TO SCALE
8'' AND SMALLER 19'' AND LARGER
TURN FITTING NOT TO SCALE NOT TO SCALE
(EQUAL CFM SPLIT SHOWN,
UNEQUAL CFM SPLIT SIMILAR)
NOT TO SCALE 5020CC ROUND DAMPER OR
830ACC RECTANGULAR
OPPOSED BLADE DAMPER RIGID DUCTWORK
RECTANGULAR, SQUARE, ROUND
IMPORTANT NOTE AND OVAL DUCTWORK
MASTIC SEALANT
APPLIED UNDER SEALANT SEALANT SHALL BE APPLIED TO DUCTWORK BEFORE ASSEMBLY. FLEXIBLE DUCTWORK
DRIVE SLIP EXCESS LIQUID OR MASTIC SHALL BE REMOVED WITH
FOLDOVER PROPER SOLVENT WHEREVER DUCTWORK IS EXPOSED IN
OCCUPIED AREAS. 1RUPV5HVWDXUDQWV//&
SEALANT /DNHZRRG%OYG
DRIVE SLIP %HOOIORZHU&$
2'' COLLAR INLET, SEE
SEALANT PLANS FOR SIZES 6WDPS
SEALANT SEALANT
SEALANT
DUCT HANGER OUTLINE
DRIVE SLIP 1'' THICK (6 LB. DENSITY) BY 6'' WIDE BY
LENGTH OF BEARING SURFACE WITH
SEALANT AIRFLOW FSK FACING, PROVIDED BY SHEET EXTERNAL DUCT CAULK AND SEAL ALL PENETRATIONS
'S' SLIP METAL CONTRACTOR AS THE INSTAL INSULATION
PITTSBURGH LOCK POCKET LOCK
DUCTWORK SEALANT DUCTWORK SEALANT DETAIL OF INSULATION FLEXIBLE CASING AND WIRE (50'-0" MAXIMUM)
DETAIL NO. 1 DETAIL NO. 2 AT DUCT HANGER
NOT TO SCALE S LOCKING RACK & PINION OPERATOR
NOT TO SCALE NOT TO SCALE EE
S
VI ECT ,VVXH)RU
EW IO
N PERMIT
MANUFACTURER MOUNTING BRACKET
DUCTWORK DETAILS LINED PLENUM ,VVXH'DWH
NOT TO SCALE 09-18-17
FLEXIBLE DUCT
5HYLVLRQV
NO. REASON DATE
GREASE FLOWBAR WITH PLENUM BOX
EXHAUST FAN
FLOWBAR DIFFUSER ASSEMBLY. CEILING CONSTRUCTION
REFER TO AIR DIFFUSER & GRILLE
FACTORY HINGED SCHEDULE.
BASE WITH LATCH SECTION VIEW
40" MIN
VENTED
EXTENSION 1. NOTES:
SOCKET WRENCH
MANUFACTURER ROOF CURB 2. TYPE 1 HOOD AND EXHAUST SHALL COMPLY WITH ALL REQUIREMENTS OF
CHAPTER 5 OF THE 2013 CALIFORNIA MECHANICAL CODE AND NFPA 96.
SUPPLY PLENUM AND DIFFUSER DETAIL
3. FIRE DEPARTMENT APPROVAL SHALL BE REQUIRED ON FIRE PROTECTION NOT TO SCALE
SYSTEM FOR GREASE HOODS AND DUCTS AS REQUIRED BY THE MECHANICAL
CODE AND AS REQUIRED BY THE FIRE CODE.
DAMPER CABLE CONTROL SYSTEM DETAIL
4. HOOD SHALL BE EQUIPPED WITH A DRY CHEMICAL FIRE SUPPRESSION
SYSTEM (OR APPROVED EQUAL) AS REQUIRED BY NFPA 17A. NOT TO SCALE
5. ALL GREASE DUCT SHALL BE MADE WITH CONTINUOUS LIQUID TIGHT WELD OR
BRAZE MADE ON EXTERNAL SURFACE OF THE DUCT SYSTEM.
GREASE EXHAUST DUCTWORK & HOOD SYSTEM SPECIFICATION
DOUBLE WALL
6. LISTED EXHAUST HOODS ARE TO BE INSTALLED IN ACCORDANCE WITH THE
GREASE DUCT. REFER A. THE GREASE EXHAUST SYSTEM SHALL BE CONSTRUCTED SO THAT NO
TO HOOD DRAWINGS TERMS OF THEIR LISTINGS AND THE MANUFACTURER'S INSTALLATION
GREASE WILL BECOME POCKETED IN ANY PORTION THEREOF AND SHALL SLOPE INSTRUCTIONS.
AT NOT LESS THAN 1/4" PER FOOT IF HORIZONTAL LENGTH UNDER 75 FEET LONG
OR 1" PER FOOT IF OVER 75 FEET, BACK TO THE HOOD OR AS REQUIRED BY THE 7. PROVIDE CLEAN OUT AT EVERY CHANGE OF DIRECTION AND EVERY 12 FOOT PRINCIPAL IN CHARGE:
LOCAL AUTHORITIES. PER SECTION 51 0.3 THRU 510.3.4.5
WRAPPED INSULATION COVERING RIGID ROUND DUCT JT
FLEXIBLE DUCT CONNECTION
B. OPENINGS IN DUCT SHALL CONFORM TO CODE REQUIREMENTS AND SHALL 8. EXHAUST OUTLETS SERVING GREASE DUCT SYSTEM SHALL TERMINATE PROJECT MANAGER:
BE PROVIDED FOR COMPLETE AND THOROUGH CLEANING OF DUCT SYSTEM. ABOVE ROOF SURFACE. 10' FROM PROPERTY LINE. 10' FROM AIR INTAKE RIGID ROUND SHEET METAL DUCT JT
OPENINGS AND 10' ABOVE ADJOINING GRADE. BASE OF FAN SHALL BE 2' 1" X 20 GAUGE GALVANIZED SUPPORT STRAP
20" CAPTRATE SOLO C. GREASE HOOD TO EXTEND A MINIMUM OF 6" BEYOND THE COOKING DRAIN LINE SAME SIZE AS RTU CONNECTION BUT DRAWN BY:
9. ABOVE ROOF SURFACE. BALANCING DAMPER
FILTERS WITH HOOK NOT LESS THAN 3/4. PROVIDE UNION AT DL, CQ
SURFACE ON ALL OPEN SIDES OR AS REQUIRED BY LOCAL CODE.
10. HOODS LESS THAN 12" FROM THE CEILING OR WALL SHALL BE FLASHED CONNECTION FOR CLEAN OUT 3URMHFW$GGUHVV
SOLIDLY WITH MATERIALS AS REQUIRED. INSULATED
SUPPLY DUCT RTU OPEN AIR VENT ON
NORM'S RESTAURANT -
11. THE FIRE EXTINGUISHING SYSTEM SHALL BE INTERCONNECTED TO THE FUEL INGLEWOOD, CA
DOWN SIDE OF TRAP
OR CURRENT SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY
CONDITIONED AIR SUPPLY
SHUT OFF ALL EQUIPMENT UNDER THE HOOD WHEN THE SYSTEM IS
W IMPERIAL HWY
0" CLEARANCE TO NON COMBUSTIBLE GRILLE SQUARE TO ROUND
MATERIAL. STAINLESS STEEL (OR ACTUATED. ADAPTOR (IF REQUIRED) INGLEWOOD, CA 90303
EQUIVALENT) WALL PANEL WITHIN 18" IN BALANCING HANDLE. LOCK INTO INSULATED FLEXIBLE DUCT MINIMUM 1/4" PER (EXACT ADDRESS TBD BY
ALL DIRECTIONS OF HOOD PER ARCH MAKEUP AIR SUPPLY GRILLE 12. DUCT BRACING AND SUPPORTS SHALL BE OF NONCOMBUSTIBLE MATERIAL. POSITION AND MARK PERMANENTLY. INSULATE BACKPAN OF FEET SLOPE
PLANS. PROTECTION SADDLE DIFFUSER
CITY)
REFER TO 13. WEATHER PROTECTION FOR OPENINGS TO BE A MINIMUM OF 26 GAUGE
DIFFUSER STARTER COLLAR (MINIMUM 4"). 6" MIN 3URMHFW1XPEHU
HOOD DRAWINGS FOR GALVANIZED STEEL.
INSTALLATION HEIGHTS SS CLASS 1 WALL HOOD TO OVERLAP 4"MAX CONE FLASHING BY
A MIN OF 6" BEYOND COOKING 14. EACH EXHAUST OUTLET WITHIN THE HOOD SHALL SERVE NOT MORE THAN NOTES: 1) PROVIDE AT FLEXIBLE DUCT CONNECTION METAL OR "PANDUIT" DRAWBAND ON THE 78-001-17
SLOPED GREASE DRAIN PLUMBING
EQUIPMENT. PROVIDE A MIN OF 18" 12-FOOT SECTION OF HOOD. INTERIOR FLEXIBLE DUCT HELIX. SECURE THE INSULATION OVER THE DRAW BAND WITH AN
W/ REMOVABLE CUP CEILING
CLEARANCE ABOVE HOOD FROM ALL ADDITIONAL DRAWBAND. CONTRACTOR 6KHHW7LWOH
COMBUSTIBLE CONSTRUCTION OR A 15. EXPOSED GREASE DUCT/ HOOD SYSTEMS SERVING TYPE 1 HOOD SHALL HAVE
MINIMUM OF 3" CLEARANCE 2) PROVIDE BEADING ON ROUND METAL DUCT 12" OR LARGER IN DIAMETER.
A CLEARANCE FROM UNPROTECTED COMBUSTIBLE CONSTRUCTION OF AT SUPPLY DIFFUSER WITH ROOF HVAC DETAILS
EQUIPMENT 3) PROVIDE MINIMUM 4" COLLARS FOR ATTACHMENT OF THE FLEXIBLE DUCT TO ROUND DUCT,
BY OTHERS
PROVIDED THAT THE COMBUSTIBLE LAY-IN FRAME (SURFACE
MATERIAL IS PROTECTED WITH 1 HR LEAST 18 INCHES. CLEARANCE MAY BE REDUCED TO NOT LESS DAMPERS AND DIFFUSERS.
16. THAN 3 INCHES WHEN COMBUSTIBLE CONSTRUCTION IS PROTECTED WITH MOUNT FRAME SIMILAR)
CONSTRUCTION ON HOOD SIDE. 4) BAND RIGID ROUND DUCT INSULATION TO DUCT AND PROVIDE TAPE FOR INSULATION
MATERIAL REQUIRED FOR ONE-HOUR FIRE-RESISTIVE CONSTRUCTION.
OVERLAP. SEE PLUMBING DRAWINGS
5) BALANCING DAMPERS SHALL BE INSTALLED AT ALL BRANCH DUCTS, AND ALL TAKE-OFFS FOR CONDENSATE DRAIN
FROM MAIN DUCT.
LINES AND TIE-INS
6KHHW1XPEHU
RTU CONDENSATE DRAIN DETAIL
TYPE 1 KITCHEN HOOD DETAIL DIFFUSER CONNECTION DETAIL NOT TO SCALE
NOT TO SCALE NOT TO SCALE M3.0

12/4/2017 2:24:17 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
SUPPORT STRUCTURE
SUPPORT STRUCTURE
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
ROD COUPLING û‚¹¼ċ™‚ċĖû™‹&Ђí
ROD COUPLING MASON TYPE SSB
SEISMIC BRACKET MASON TYPE SRC OR UR
7KH3URPHQDGH1RUWK
MASON TYPE MASON TYPE SRC OR UR SEISMIC ROD CLAMP IF
/RQJ%HDFK&$
SSB SEISMIC SEISMIC ROD CLAMP IF ZZZLGDH[SHULHQFHQHW
REQUIRED.
BRACKET REQUIRED.
1 THREADED ROD
THREADED ROD $UFKLWHFW
1
ROD STIFFNER ANGLE
1 ROD STIFFNER ANGLE OR STRUT IF REQUIRED.
OR STRUT IF REQUIRED. *(2))5(<%/,0
1
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
ROD COUPLING FOR LOWER original
ADDITIONAL UPPER DUCT signature by the licensed professional may have been
ROD COUPLING FOR ROD ATTACHMENT. fraudulently altered and shall not be considered an original
SUPPORT TO STIFFEN DUCT DUCT ADDITIONAL UPPER SUPPORT copy. All information should be disregarded unless verified
LOWER ROD ATTACHMENT.
by the professional whose signature appears above.
TO STIFFEN DUCT Copyright Protected 2016.
TRAPEZE SUPPORT
1 IN.
NO. 10 SELF-TAPPING SHEET (QJLQHHULQJ&RQVXOWDQW
METAL SCREWS MAXIMUM 12
IN. O.C. TOP AND BOTTOM
STEEL BRACE
MAXIMUM 9'-6''
TRAPEZE SUPPORT
NO. 10 SELF-TAPPING SHEET
METAL SCREWS MAXIMUM 12
MASON TYPE SSB IN. O.C. TOP AND BOTTOM
SEISMIC BRACKET
STEEL BRACE 1 IN.
MAXIMUM 9'-6''
MASON TYPE SSB
SEISMIC BRACKET
TRANSVERSE SOLID BRACE FOR RECTANGULAR/OVAL DUCT LONGITUDINAL SOLID BRACE FOR RECTANGULAR/OVAL DUCT
NOT TO SCALE NOT TO SCALE
3URMHFW2ZQHU
TRUSS TRUSS
ROUND DUCT
SUPPORT STRUCTURE SUPPORT STRUCTURE FLEXIBLE DUCT 6'-0''
MAXIMUM LENGHT
MASON TYPE SSB ROD COUPLING
MASON TYPE SSB SEISMIC BRACKET
ROD COUPLING MASON TYPE SRC OR UR
SEISMIC BRACKET
SEISMIC ROD CLAMP IF 2'' WIDE UPPORT
MASON TYPE SRC OR REQUIRED. 1'' WIDE SUPPORT STRAP
1 STRAP 3'-0'' MAXIMUM
UR SEISMIC ROD 10'-0'' MAXIMUM SPACING SPACING
CLAMP IF REQUIRED. THREADED ROD
1 1
THREADED ROD NOTES:
1 ROD STIFFNER ANGLE OR 1. STRAPS ARE GALVANIZED MINIMUM HANGER SIZES FOR ROUND DUCT
ROD STIFFNER ANGLE STRUT IF REQUIRED.
STEEL; RODS ARE
OR STRUT IF REQUIRED. UNCOATED OR GALVANIZED MAXIMUM WIRE DIA. STRAP
DIA. ROD
ADDITIONAL UPPER SUPPORT SPACING
STEEL; WIRE IS BLACK
TO STIFFEN DUCT ROD COUPLING FOR LOWER 10'' DN 12' ONE 12 GA. 1/4'' 1'' X 22 GA.
ROD COUPLING FOR DUCT ANNEALED, BRIGHT BASIC,
DUCT ADDITIONAL UPPER SUPPORT ROD ATTACHMENT.
LOWER ROD ATTACHMENT. OR GALVANIZED STEEL. ALL TWO 12 GA.
TO STIFFEN DUCT ARE ALTERNATIVES. 11-18'' 12' 1/4'' 1'' X 22 GA.
ASBH OPTIONAL OR ONE 8 GA.
ATTACHMENT 2. REFER TO SMACNA "HVAC
TRAPEZE SUPPORT 19-24'' 12' TWO 10 GA. 1/4'' 1'' X 22 GA.
DUCT CONSTRUCTION
NO. 10 SELF-TAPPING SHEET 25-36'' 12' TWO 8 GA. 3/8'' 1'' X 20 GA.
METAL SCREWS MAXIMUM STANDARDS" FOR FURTHER
12 IN. O.C. TOP AND BOTTOM AIRCRAFT CABEL INSTRUCTION. 37-50'' 12' 3/8'' 1'' X 20 GA.
51-60'' 12' 3/8'' 1'' X 18 GA.
TRAPEZE SUPPORT MASON TYPE SCBH 61-84'' 12' 3/8'' 1'' X 16 GA.
SEISMIC BRACKET NO. 10 SELF-TAPPING SHEET
METAL SCREWS MAXIMUM 12 1RUPV5HVWDXUDQWV//&
IN. O.C. TOP AND BOTTOM DUCT SUPPORT DETAIL /DNHZRRG%OYG
AIRCRAFT CABEL NOT TO SCALE %HOOIORZHU&$
1 IN.
MASON TYPE SCBH 6WDPS
SEISMIC BRACKET
STRAP, SEE BELOW FOR SIZES STRAP OR ANGLE
MAX. SAG 1/2'' PER FOOT
OF SUPPORT SPACING SHEETMETAL
TRANSVERSE CABLE BRACE FOR RECTANGULAR/OVAL DUCT LONGITUDINAL CABLE BRACE FOR RECTANGULAR/OVAL DUCT DUCTWORK
NOT TO SCALE NOT TO SCALE WIRE, SEE BELOW FOR SIZES
4'' MAXIMUM
OR
,VVXH)RU
STEEL JOIST WELDED STUD WITH NUT
PREVENT BENDING OF PERMIT
STRAP AT THE 90° BEND ,VVXH'DWH
GALV. STEEL ANGLE 09-18-17
1" MINIMUM STEEL HANGER STRAP, SEE PER SMACNA
BELOW FOR SIZES 5HYLVLRQV
MAIN DUCTWORK NO. REASON DATE
FLEX DUCT SIZE BOLTS FOR LOAD
UPPER ATTACHMENT - TYP.
STRUCTURAL STEEL BEAM
SCB ATTACHED TO TOP OF JOIST WITH JAH NOTE: NOTE:
1. NOTE: 1. SHEETMETAL DUCTWORK SUPPORTS
The JAH is used to attach solid or cable SCBV - SEISMIC CABLE 2. 1. DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING. SHALL BE MINIMUM OF 2'' WIDE.
braces to the top cord of bar joists. Attachment BRACE VISE REF. PAGE X3
2. SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR CAUSE OUT OF ROUND SHAPE.
to the lower cord is not recommended. TRAPEZE HANGER LOWER
ATTACHMENT - TYP.
"E" TAPPED HOLE
IN DUCTILE IRON
CASTING. BOLT A
BY OTHERS.
BOLT LENGTH IS MAXIMUM SCB/SSB LOADS RECTANGULAR DUCT HANGERS MINIMUM SIZE
ANGLE LEG LENGTH TO STRUCTURE UP TO 1:1 BRACE ANGLE
PLUS 1 1/2" (40mm)
MINIMUM SCBV TENSION* SHEAR
MAXIMUM HALF PAIR AT 10 FT SPACING PAIR AT 8 FT SPACING PAIR AT 5 FT SPACING PAIR AT 4 FT SPACING
OF DUCT
SIZE lbs (kN) lbs (kN)
PERIMETER STRAP WIRE/ROD STRAP WIRE/ROD STRAP WIRE/ROD STRAP WIRE/ROD
1 690 (3.1) 690 (3.1)
10 GA 10 GA 12 GA 12 GA
2 1450 (6.5) 1450 (6.5) P/2=30'' 1'' X 22 GA 1'' X 22 GA 1'' X 22 GA 1'' X 22 GA
(.135'') (.135'') (.106'') (.106'')
3 2230 (10.0) 2230 (10.0)
P/2=72'' 1'' X 18 GA 3/8'' 1'' X 20 GA 1/4'' 1'' X 22 GA 1/4'' 1'' X 22 GA 1/4''
B *FOR UP TO 1.5:1 OR 2:1 BRACE ANGLE,
P/2=96'' 1'' X 16 GA 3/8'' 1'' X 18 GA 3/8'' 1'' X 20 GA 3/8'' 1'' X 22 GA 1/4'' PRINCIPAL IN CHARGE:
MULTIPLY BY 1.2 OR 1.3 RESPECTIVELY.
JT
P/2=120'' 1-1/2'' X 16 GA 1/2'' 1'' X 16 GA 3/8'' 1'' X 18 GA 3/8'' 1'' X 20 GA 1/4''
PROJECT MANAGER:
P/2=168'' 1-1/2'' X 16 GA 1/2'' 1-1/2'' X 16 GA 1/2'' 1'' X 16 GA 3/8'' 1'' X 18 GA 3/8'' JT
P/2=192'' NOT GIVEN 1/2'' 1-1/2'' X 16 GA 1/2'' 1'' X 16 GA 3/8'' 1'' X 16 GA 3/8'' DRAWN BY:
DL, CQ
D NEOPRENE
SEISMIC RESTRAINT SCHEDULE P/2=193'' UP SPECIAL ANALYSIS REQUIRED
C FRICTION 3URMHFW$GGUHVV
WASHERS PROVIDE SEISMIC SWAY BRACE ON ALL SUSPENDED PIPING PER 2013 CBC. SEISMIC SINGLE HANGER MAXIMUM ALLOWABLE LOAD
SWAY BRACES SHALL CONSIST OF GALVANIZED STEEL AIRCRAFT CABLES OR STEEL WHEN STRAPS ARE LAP JOINED USE THESE MINIMUM FASTENERS: NORM'S RESTAURANT -
SCB or SSB STRAP WIRE OR ROD (DIA.)
ANGLES/CHANNELS. STEEL AIRCRAFT CABLES SHALL BE PRESTRETCHED TO INGLEWOOD, CA
ESTABLISH A CERTIFIED MINIMUM MODULUS OF ELASTICITY. CABLES BRACES SHALL BE 1'' X 18, 20, 22 GA. - TWO #10 OR ONE 1/4''BOLT 1'' X 22 GA. - 260 LBS. 0.106'' - 80 LBS. W IMPERIAL HWY
DESIGNED TO RESIST SEISMIC TENSION AND STEEL BRACES SHALL BE DESIGNED TO 1'' X 16 GA. - TWO 1/4'' DIA. 1'' X 20 GA. - 320 LBS. 0.135'' - 120 LBS.
TYPE JAH DIMENSIONS inches (mm) RESIST BOTH TENSION AND COMPRESSION LOADS WITH A MINIMUM SAFETY FACTOR
INGLEWOOD, CA 90303
1-1/2'' X 16 GA. - TWO 3/8'' DIA. 1'' X 18 GA. - 420 LBS. 0.162'' - 160 LBS. (EXACT ADDRESS TBD BY
Max. Load lbs (kgs) OF 2. BRACE END CONNECTIONS SHALL BE STEEL ASSEMBLIES THAT SWIVEL TO THE PLACE FASTENERS IN SERIES, NOT SIDE BY SIDE. 1'' X 16 GA. - 700 LBS. 1/4'' - 270 LBS.
Size SCB/SSB Size A B C D E SCB SSB FINAL INSTALLATION ANGLE. DO NOT MIX CABLE AND STEEL BRACES TO BRACE THE 1-1/2'' X 16 GA. - 1100 LBS. 3/8'' - 680 LBS.
CITY)
JAH-0 SCB-0 3 (76) 3/4 (19) 1 7/8 (48) 1 3/4 (44) 3/8-16UNC 500 (227) - - SAME SYSTEM. STEEL ANGLES, WHEN REQUIRED, SHALL BE CLAMPED TO THE 1/2'' - 1250 LBS.
JAH-1 SCB/SSB-1 3 (76) 3/4 (19) 1 7/8 (48) 2 1/4 (57) 1/2-13UNC 975 (442) 1500 (680) THREADED HANGER RODS AT THE SEISMIC SWAY BRACE LOCATIONS UTILIZING A 3URMHFW1XPEHU
5/8'' - 2000 LBS.
JAH-2 SCB/SSB-2 3 (76) 3/4 (19) 2 1/8 (54) 3 (76) 5/8-11UNC 2050 (930) 3000 (1361) MINIMUM OF TWO DUCTILE IRON CLAMPS. THE BRACING SYSTEM SHALL HAVE AN 3/4'' - 3000 LBS.
ANCHORAGE PREAPPROVAL ''R'' NUMBER FROM A RECOGNIZED GOVERNMENT AGENCY 78-001-17
JAH-3 SCB/SSB-3 3 (76) 3/4 (19) 2 1/2 (64) 3 3/4 (95) 3/4-10UNC 3150 (1429) 5000 (2268)
SHOWING MAXIMUM RESTRAINT RATINGS VERIFYING IT'S CAPABILITY TO RESIST
6KHHW7LWOH
SEISMIC FORCES. CABLE BRACE ASSEMBLIES SHALL BE TYPE SCB, STEEL BRACE
JOIST ATTACHEMENT HARDWARE ASSEMBLIES SHALL BE TYPE SSB, ROD CLAMPS SHALL BE TYPE SRC, PIPE CLEVIS NOTES: HVAC DETAILS
BRACES SHALL BE TYPE CCB AND MULTIPLE ANCHOR LOAD DISTRIBUTION BRACKETS 1. DIMENSIONS OTHER THAN GAGE ARE IN INCHES.
NOT TO SCALE 2. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL
SHALL BE TYPE SLDB ALL AS MANUFACTURED BY MASON INDUSTRIES, INC. OR EQUAL
AND AS APPROVED BY LOCAL AUTHORITIES. 3. 12, 10 OR 8 GA. WIRE IS STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED TYPE.
4. REFER TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR FURTHER INSTRUCTION.
TYPICAL DUCT HANGING DETAIL 6KHHW1XPEHU
SEISMIC SUPPORT DETAILS NOT TO SCALE
NOT TO SCALE
M3.1

12/4/2017 2:24:18 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
HOOD INFORMATION - Job#3055271 D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
EXHAUST PLENUM HOOD CONFIG. VHB-G Series Specification
MAX.
HOOD RISER(S) HOOD
TAG MODEL LENGTH COOKING TOTAL MUA CFM AC CFM END TO The VHB-G series heat/condensate hood is a single wall vent hood used in
NO. CONSTRUCTION ROW
TEMP. EXH. CFM WIDTH LENG. HEIGHT DIA. CFM VEL. S.P. END non-grease applications for the removal of heat, vapor etc. Hood shall have
6030 450 430 SS the size, shape and performance specified on the drawings.
1 ITEM #76L 11' 3.00" 2400 4" 16" 2400 1719 -0.821" 2040 700 LEFT ALONE
ND-2-ACPSP-F Deg. Where Exposed
6030 450 430 SS Construction shall be type 304 stainless steel with a #3 or #4 polish where
2 ITEM #76R 12' 0.00" 2400 4" 16" 2400 1719 -0.797" 2040 700 RIGHT ALONE
ND-2-ACPSP-F Deg. Where Exposed exposed. Hood shall have a full perimeter gutter with a 1/2" OD Bolt thread
I N
H
I T
NF P A

B U IL T
6
No . 9

5430 4" 14" 1656 1549 -0.723" 430 SS drain connection. Hood shall be wall or island type with fully welded 10 gauge
NCE
A CCORDA

600
3 ITEM #107L 13' 3.00" 3312 2650 750 LEFT ALONE corner hanging angles. Corner hanging angles have a .625 x 1.500 slot
ND-2-ACPSP-F Deg. 4" 14" 1656 1549 -0.723" Where Exposed
pre-punched at the factory, allowing hanging rods to be used for quick and
5430 600 4" 14" 1698 1588 -0.761" 430 SS
4 ITEM #107R 12' 7.00" 3397 2718 780 RIGHT ALONE safe installations. Hanging rod and connection is provided by and installed by
ND-2-ACPSP-F Deg. 4" 14" 1698 1588 -0.761" Where Exposed
R
D

others.
E
T

$5&+,7(&785(
S

4230 430 SS
I

700
L

5 ITEM # 214 8' 0.00" 1000 12" 12" 4" 1000 1000 -0.085" 0 0 ALONE ALONE
Deg.
S

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U
C

VHB-G 100%
The hood manufacturer shall supply complete submittal drawings including
HOOD INFORMATION hood section views(s) and hood plan view(s). These drawings must be made û‚¹¼ċ™‚ċĖû™‹&Ђí
FILTER(S) LIGHT(S) UTILITY CABINET(S) available to the engineer, architect and owner for their use in construction, 7KH3URPHQDGH1RUWK
FIRE HOOD
www.captiveaire.com

HOOD FIRE SYSTEM ELECTRICAL SWITCHES operation and maintenance. /RQJ%HDFK&$


TAG WIRE SYSTEM HANGING
NO. TYPE QTY. HEIGHT LENGTH EFFICIENCY @ 7 MICRONS QTY. TYPE LOCATION SIZE
GUARD TYPE SIZE MODEL # QUANTITY PIPING WGHT ZZZLGDH[SHULHQFHQHW
1 Light 916 Exhaust duct collar to be 4" high with 1" flanges. Duct sizes, CFM and static
1 ITEM #76L Captrate Solo Filter 8 20" 16" 85% See Filter Spec. 3 12" x 12" LED NO Left 12"x60"x30" Ansul R102 3.0 DCV-2111 YES
1 Fan LBS pressure requirements shall be as shown on the drawings. Hood shall be ETL
$UFKLWHFW
864
Sanitation listed.
2 ITEM #76R Captrate Solo Filter 9 20" 16" 85% See Filter Spec. 3 12" x 12" LED NO YES
LBS
835
3 ITEM #107L Captrate Solo Filter 9 20" 16" 85% See Filter Spec. 3 12" x 12" LED NO YES *(2))5(<%/,0
LBS
1 Light 821 $,$1&$5%/(('$3
4 ITEM #107R Captrate Solo Filter 9 20" 16" 85% See Filter Spec. 4 12" x 12" LED NO Wall Mnt 12"x66"x30" Ansul R102 3.0/3.0/3.0/1.5 DCV-2111 YES
1 Fan LBS
259 Plans, maps, specifications, studies, and reports not
5 ITEM # 214 3 L55 Series E26 NO NO containing a red ink seal imprint accompanied by an
LBS
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
PERFORATED SUPPLY PLENUM(S) copy. All information should be disregarded unless verified
R R
SPECIFICATION: CAPTRATE GREASE-STOP SOLO FILTER by the professional whose signature appears above.
RISER(S) Copyright Protected 2016.
HOOD NO. TAG POS. LENGTH WIDTH HEIGHT TYPE THE CAPTRATE GREASE-STOP SOLO FILTER IS A SINGLE-STAGE FILTER FEATURING
WIDTH LENG. DIA. CFM S.P.
A UNIQUE S-BAFFLE DESIGN IN CONJUNCTION WITH A SLOTTED REAR BAFFLE DESIGN,
MUA 10" 28" 680 0.211" TO DELIVER EXCEPTIONAL FILTRATION EFFICIENCY.
FILTER IS STAINLESS STEEL CONSTRUCTION, AND SIZED TO FIT INTO STANDARD
(QJLQHHULQJ&RQVXOWDQW
MUA 10" 28" 680 0.211"
2-INCH DEEP HOOD CHANNEL(S).
1 ITEM #76L Front 147" 24" 6" MUA 10" 28" 680 0.211"
AC 8" 24" 350 0.073" UNITS SHALL INCLUDE STAINLESS STEEL HANDLES AND A FASTENING DEVICE TO SECURE THE TWO
COMPONENTS WHEN ASSEMBLED. 21"
AC 8" 24" 350 0.073"
GREASE EXTRACTION EFFICIENCY PERFORMANCE SHALL REMOVE AT LEAST 75% OF GREASE
MUA 10" 28" 680 0.211" PARTICLES FIVE MICRONS IN SIZE, AND 90% GREASE PARTICLES SEVEN MICRONS IN SIZE AND
MUA 10" 28" 680 0.211" LARGER, WITH A CORRESPONDING PRESSURE DROP NOT TO EXCEED 1.0 INCHES OF WATER GAUGE.
2 ITEM #76R Front 144" 24" 6" MUA 10" 28" 680 0.211" THE CAPTRATE GREASE-STOP SOLO WAS TESTED TO ASTM STANDARD ASTM F2519-05. 42" 12"
AC 8" 24" 350 0.073" R R
FILTER COLLECTION EFFICIENCY 2" Captrate Grease-Stop Solo Filter
AC 8" 24" 350 0.073" 100
MUA 12" 28" 882 0.248" 90
12"
MUA 12" 28" 882 0.248" 80
R R
3 ITEM #107L Front 162" 26" 6" MUA 12" 28" 882 0.248" RESISTANCE VS. AIRFLOW - 2" Captrate Grease-Stop Solo Filter
70
1.6
Missouri Specialized Accounts

AC 8" 24" 375 0.076" U.L. Listed L55 Series E26 Canopy Light Fixture -
60 1.4
AC 8" 24" 375 0.076" High Temp Assembly
1.2
50
MUA 12" 28" 905 0.300" 1
40
MUA 12" 28" 905 0.300" 0.8
30
4 ITEM #107R Front 154" 26" 6" MUA 12" 28" 905 0.300" 0.6

RESISTANCE (in. H20)

FILTRATION EFFICIENCY (%)


AC 8" 24" 390 0.082" 20 0.4
AC 8" 24" 390 0.082" 10 0.2
48" 48"
0
0
0 200 400 600 800 1000
0.1 1 10 3URMHFW2ZQHU
PARTICLE DIAMETER (um) AIRFLOW (cfm)
CAPTRATE FILTERS ARE BUILT IN COMPLIANCE WITH:.
ING L AB
NFPA #96 ST O BUILT

TE
IN

RA
R ACCORDANCE
NSF STANDARD #2

NS F
TORY
WITH 8' 0.00"Nom./8' 0.00"OD
. NFPA

H
UL STANDARD #1046

A
N I C No. 96
N
A R B O R, M
INT. MECH. CODE (IMC) L I ST E D
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

PLAN VIEW - Hood #5 (ITEM # 214)


8' 0.00" LONG 4230VHB-G
4' LED LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 2700K-3500K, INCLUDES (2)
LED-312022W BULBS
FIELD WRAPPER 17.00" HIGH
(SEE HOOD OPTIONS TABLE) 3' LED LIGHT FIXTURE, RECESSED, COLOR
TEMPERATURE 2700K-3500K, INCLUDES (2)
60" LED-312013W BULBS 42"
54" L55 SERIES E26 CANOPY LIGHT FIXTURE -
EXHAUST RISER EXHAUST RISER HIGH TEMP ASSEMBLY, INCLUDES CLEAR THERMAL
EXHAUST RISER AND SHOCK RESISTANT GLOBE (L55 FIXTURE)
HANGING ANGLE SUPPLY RISER WITH
HANGING ANGLE
VOLUME DAMPER HANGING ANGLE SUPPLY RISER WITH
SEE HOOD TABLE 2 3/4" VOLUME DAMPER SEE HOOD TABLE
23.5% OPEN STAINLESS SEE HOOD TABLE 2 3/4"
STEEL PERFORATED PANEL 23.5% OPEN STAINLESS
20" CAPTRATE SOLO STEEL PERFORATED PANEL
FILTER WITH HOOK 20" CAPTRATE SOLO
6"
FILTER WITH HOOK 6"
3" INTERNAL STANDOFF 24"
3" INTERNAL STANDOFF 26"
30" NOM. LED 30" NOM.
30" NOM.
24"
24"
DRAIN FULL
IT IS THE RESPONSIBILITY PERIMETER
OF THE ARCHITECT/OWNER TO IT IS THE RESPONSIBILITY 1RUPV5HVWDXUDQWV//&
GUTTER
ENSURE THAT THE HOOD CLEARANCE OF THE ARCHITECT/OWNER TO /DNHZRRG%OYG
FROM LIMITED-COMBUSTIBLE ENSURE THAT THE HOOD CLEARANCE
AND COMBUSTIBLE MATERIALS FROM LIMITED-COMBUSTIBLE %HOOIORZHU&$
IS IN COMPLIANCE WITH AND COMBUSTIBLE MATERIALS
LOCAL CODE REQUIREMENTS. IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS. 6WDPS
GREASE DRAIN
WITH REMOVABLE CUP GREASE DRAIN
48.0" MAX WITH REMOVABLE CUP
48.0" MAX
NORM'S RESTAURANT
ENGLEWOOD,CA.

80" 80" AFF REFERENCE 80" AFF REFERENCE DATE:

8/31/2017
80" AFF REFERENCE
DWG.#:
3132020 ,VVXH)RU
PERMIT
4"
DRAWN
EQUIPMENT SJDSR ,VVXH'DWH
BY:
EQUIPMENT
BY OTHERS EQUIPMENT  Y OTHERS
B
 Y OTHERS
B 09-18-17
SCALE:
3/4" = 1'-0" 5HYLVLRQV
NO. REASON DATE
19 1/2"
4"
MASTER DRAWING
GAS CHASE CUTOUT
(FOR GAS AND POWER LINES)
36"
RIGHT WIDE VERTICAL END PANEL
42"
WITH ADJUSTABLE LEGS
SECTION VIEW - MODEL 6030ND-2-ACPSP-F SECTION VIEW - MODEL 5430ND-2-ACPSP-F SECTION VIEW - MODEL 4230VHB-G SHEET NO.
HOOD - #1 (ITEM #76L) HOODS - #3 (ITEM #107L), #4 (ITEM #107R) HOOD - #5 (ITEM # 214) 1
HOOD - #2 (ITEM #76R)
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.0

12/4/2017 2:24:19 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
2 1/4" 130 1/2" 2 1/4" 53 1/2" 32 1/2" 53 1/2"
3"
12" 12"
I N
H
I T
NF P A

B U IL T
6
No . 9

NCE
A CCORDA

16" 16"
R
D
E
T

$5&+,7(&785(
S
I

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U
C

û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
www.captiveaire.com

60" /RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
U.L. Listed 12" x 12" Recessed
LED Light
U.L. Listed 12" x 12" Recessed
LED Light
*(2))5(<%/,0
$,$1&$5%/(('$3
Utility
Cabinet 28" 28" 28" 28" 28" 28" Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
10" 10" 10" 10" 10" 10" by the professional whose signature appears above.
Copyright Protected 2016.
7" 7" 7" 7" 7" 7"
CAPTIVE-AIRE HOODS ARE
24"
MUA Connections MUA Connections BUILT IN COMPLIANCE WITH
HVAC Connections HVAC Connections
(QJLQHHULQJ&RQVXOWDQW
8" 8" 8" 8"
NFPA #96
5" 5" 5" 5"
AND ARE RECOGNIZED BY ONE
OR MORE OF THE FOLLOWING:
24" 24" 24" 24"
63 1/2" 71 1/2" 77 3/4" 66 1/4"
NSF INTERNATIONAL
24 1/2" 49" 49" 24" 48" 48" ETL LISTED FILE# 3054804-001
ETL TESTED IN COMPLIANCE
Missouri Specialized Accounts

36 3/4" 73 1/2" 36" 72"


WITH U.L. 710 STANDARDS.
12" 11' 3.00"Nom./11' 3.00"OD 12' 0.00"Nom./12' 0.00"OD
PLAN VIEW - Hood #2 (ITEM #76R)
PLAN VIEW - Hood #1 (ITEM #76L) 12' 0.00" LONG 6030ND-2-ACPSP-F
NOTE: Additional hanging angles provided for hoods 12' and longer. ND-2 Series with AC-PSP Accessory Specification
11' 3.00" LONG 6030ND-2-ACPSP-F 3URMHFW2ZQHU
ACPSP ships loose for field installation
ACPSP ships loose for field installation The model ND-2 with AC-PSP Accessory is a compensating canopy hood rated
for all types of cooking equipment. The hood shall have the size, shape and
performance specified on drawings.
Construction shall be type 430 stainless steel, with a #3 or #4 polish where
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

exposed. The manufacturer, ETL


and NSF shall determine the individual component construction. Construction
shall be dependent on the
24.00" structural application to minimize distortion and other defects. All seams, joints
and penetrations of the hood enclosure to the lower outermost perimeter that

Duct
Duct
directs and captures grease-laden vapor and exhaust gases shall have a
liquid-tight continuous external weld in accordance with NFPA 96. The hood

Plenum
Plenum
Plenum
Plenum

shall be wall type with a minimum of four connections for hanger rods.
Connectors shall have 9/16" holes pre-punched in 1 ½" x 1 ½" angle iron at the
factory to allow for hanger rod connection by others.
The hood shall be furnished with U.L. classified filters, supplied in size and
quantity as required by ventilator.
The filters shall extend the full length of the hood and the filler panels shall not
be more than 6" in width.
The hood manufacturer shall supply complete computer generated submittal
drawings including hood sections
Hood # 1 (ITEM #76L) Hood # 2 (ITEM #76R) view(s) and hood plan view(s). These drawings must be available to the
engineer, architect and owner for their use in construction, operation and
maintenance.
Exhaust duct collar to be 4" high with 1" flange. Duct sizes, CFM and static
pressure requirements shall be as shown on drawings. Static pressure
requirements shall be precise and accurate; air velocity and volume
2W 2W
information shall be accurate within 1-ft increments along the length of the
ventilator.
U.L. incandescent light fixtures and globes shall be installed and pre-wired to a
junction box. The light fixtures shall be installed with a maximum of 4'0" spacing
on center and allow up to a 100 watt standard light bulb.
1B 3 1RUPV5HVWDXUDQWV//&
29 29 29 30 29
5 7 The hood shall have: /DNHZRRG%OYG
28 28 28 28 28
- A double wall insulated front to eliminate condensation and increase rigidity. %HOOIORZHU&$
10 11 1N 21.50" 29.25" 1N 1N 1N The insulation shall have a flexural modulus of 475 EI, meet UL 181
34
requirements and be in accordance with NFPA 90A and 90B.
6WDPS
27.00" 11.00" 97.00" 144.00" - An integral front baffle to direct grease laden vapors toward the exhaust filter
bank.
- A built-in wiring chase provided for outlets and electrical controls on the hood
face and shall not
245 penetrate the capture area or require an external chase way.
- Removable grease cup for easy cleaning.
Drawn By: The hood shall be ETL Listed as "Exhaust Hood Without Exhaust Damper",
NORM'S RESTAURANT
ENGLEWOOD,CA.

1NS System Size: ANSUL-3.0 Total FP required: 9 NSF Listed and built in accordance with NFPA 96.
Hood # 1 11' 3.00" Long x 54" Wide x 24" High
The hood shall be listed for 450°F cooking surfaces at 150 CFM/ft, 600°F
Riser # 1 Size: 16" Dia.
cooking surfaces at 200 CFM/ft, and 700°F cooking surfaces at 250 CFM/ft. The 8/31/2017
DATE:
Hood # 1 Metal Blow-Off Caps included. hood shall be ETL Listed as "Exhaust Hood Without Exhaust Damper".
Hood # 2 12' 0.00" Long x 54" Wide x 24" High
DWG.#:
Riser # 1 Size: 16" Dia. Factory will install the AC-PSP accessory which will delivers up to 80% make-up
Hood # 2 Metal Blow-Off Caps included. air while providing a termination point for AC air in a separate insulated plenum. 3132020 ,VVXH)RU
Make-up air plenum shall be located closest to hood. Both the make-up air
plenum and AC plenum shall contain two layers of perforated stainless steel
PERMIT
DRAWN
diffuser plates to provide even air distribution. SJDSR ,VVXH'DWH
BY:
SCALE:

09-18-17
3/4" = 1'-0" 5HYLVLRQV
NO. REASON DATE
MASTER DRAWING
SHEET NO.

Range-Med
High Proximity
24.00" L x24.00" D
Griddle (1 fl)
High Proximity
24.00" L x24.00" D
Kettle
No Proximity Rating
32.00" Diameter
Kettle
No Proximity Rating
32.00" Diameter
Table
No Proximity Rating
26.00" L x24.00" D
Oven
High Proximity
40.00" L x40.00" D
Steamer
No Proximity Rating
22.00" L x24.00" D
2
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.1

12/4/2017 2:24:19 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
26' 4" D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
2 1/4"
2 1/4" 56 3/4" 41" 56 3/4" 2 1/4" 52 3/4" 41" 52 3/4"
3"
I N
H

12" 12" 12" 12"


I T
NF P A

B U IL T
6
No . 9

NCE
A CCORDA

14" 14" 14" 14"


FIELD WIRE TO
REMOTE FIRE CABINET
R
D
E
T

DCV CONTROL PANEL $5&+,7(&785(


S
I

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U
C

û‚¹¼ċ™‚ċĖû™‹&Ђí
54" 7KH3URPHQDGH1RUWK
www.captiveaire.com

/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
U.L. Listed 12" x 12" Recessed U.L. Listed 12" x 12" Recessed
LED Light LED Light
*(2))5(<%/,0
28" 28" 28" 28" 28" 28" $,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
12" 12" 12" 12" 12" 12" fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
8" 8" 8" 8" 8" 8" Copyright Protected 2016.
26" LIGHTING FOR ACPSP Job # 2607888 - Hoods #3, #4
MUA Connections MUA Connections
INPUT: 120V AC, 1 Phase, 50/60Hz, 3.5 Watts per light.
HVAC Connections HVAC Connections
TO CONTROL LIGHTS WITH HOOD LIGHT SWITCH, WIRE PER
HOOD ELECTRICAL CONTROL PANEL SCHEMATIC. (QJLQHHULQJ&RQVXOWDQW
8" 8" 8" 8" TO CONTROL LIGHTS WITH BUILDING LIGHT SWITCH, WIRE
8" 8"
5" 5" 5" 5" BLACK AND WHITE WIRE TO A 120VAC SERVICE.
END TO END ACPSPS REQUIRE 120VAC FIELD WIRING FROM
J-BOX TO J-BOX. REPLACE LIGHTS WITH LED LIGHTS ONLY.
24" 24" 24" 24"
12" 23" 23" 23" 23" 23" 23" 12" 12" 26" 26" 26" 26" 26" 12"
39 3/4" 79 1/2" 39 3/4" 36 1/2" 93" 21 1/2"
27" 54" 54" 25 3/4" 51 1/4" 51 1/4"
3" 3"
40 1/2" 81" 38 1/2" 77"
Missouri Specialized Accounts

13' 3.00"Nom./13' 3.00"OD 12' 7.00"Nom./12' 7.00"OD


13'-6.00" Overall Length 12'-10.00" Overall Length
PLAN VIEW - Hood #3 (ITEM #107L) PLAN VIEW - Hood #4 (ITEM #107R)
13' 3.00" LONG 5430ND-2-ACPSP-F 12' 7.00" LONG 5430ND-2-ACPSP-F
NOTE: Additional hanging angles provided for hoods 12' and longer. NOTE: Additional hanging angles provided for hoods 12' and longer.
3URMHFW2ZQHU
24.00" 24.00" 24.00" 24.00" 24.00" 24.00"
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

Duct
Duct
Duct
Duct

Plenum
Plenum
Plenum
Plenum

Hood # 3 (ITEM #107L) Job # 2607888 Hood # 4 (ITEM #107R) Job # 2607888
1W 1W 1W 1W
1B 1B 1B
30 30 30 29 30 29 30 30 30
1A 3 4
28 28 28 28 28 28 28 28 28
5 5 5
1N 51.75" 29.25" 1N 1N 39.25" 39.25" 1N 34
6 9 9 1RUPV5HVWDXUDQWV//&
10 11 12 /DNHZRRG%OYG
15.50" 6.75" 56.50" 14.00" 12.00" 12.00" 36.50" 60.50" 11.00" 24.00" 11.00" 34.25" 10.25" %HOOIORZHU&$
5.75" 12
50.00" 6WDPS
1NS 1NS 1NS
Drawn By:
1NS 1NS
System Size: ANSUL-3.0/3.0/3.0/1.5-WC Total FP required: 33
SHEVLES SHEVLES Hood # 3 13' 3.00" Long x 54" Wide x 30" High
1NS
NORM'S RESTAURANT
ENGLEWOOD,CA.

Cheesemelter
No Proximity Riser # 1 Size: 14" Dia.
1N 1N 2120 2120 Riser # 2 Size: 14" Dia.
48.00" L x12.00" D
Hood # 3 Metal Blow-Off Caps included. DATE:

8/31/2017
3N 3N 3N
Hood # 4 12' 7.00" Long x 54" Wide x 30" High
2120 2120 Riser # 1 Size: 14" Dia. DWG.#:
Riser # 2 Size: 14" Dia. 3132020 ,VVXH)RU
20.00" Hood # 4 Metal Blow-Off Caps included.
PERMIT
DRAWN
SJDSR ,VVXH'DWH
BY:
SCALE:

09-18-17
3/4" = 1'-0" 5HYLVLRQV
NO. REASON DATE
MASTER DRAWING
SHEET NO.

Fryer-M w/Drip Board


High Proximity
14.50" L x18.00" D
Fryer-M w/Drip Board
High Proximity
14.50" L x18.00" D
Griddle - M
Low Proximity
60.00" L x24.00" D
Range-Sm
High Proximity
36.00" L x24.00" D
Griddle - M
Low Proximity
60.00" L x24.00" D
Gas Radiant Charbroiler -
S
High Proximity
48.00" L x24.00" D
Griddle (1 fl)
High Proximity
24.00" L x24.00" D
Fryer-M w/Drip Board
High Proximity
14.50" L x18.00" D
3
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.2

12/4/2017 2:24:20 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
ELECTRICAL PACKAGES - Job#2607888 D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
SWITCHES FANS CONTROLLED
NO. TAG PACKAGE # LOCATION OPTION
LOCATION QUANTITY FAN TAG TYPE H.P. VOLT FLA
Utility Cabinet Left 1 Light EF-1 #76L Exhaust 3 2.000 208 6.1
1 #76 DCV-2111 Utility Cabinet Left Smart Controls DCV EF-2 #76L Exhaust 3 2.000 208 6.1 DUCT TEMPERATURE SENSOR
Hood # 1 1 Fan SF-1 ITEM 76 Supply 3 3.000 208 8.7
I N
H
I T
NF P A

B U IL T
6
No . 9

Face Mount Right Side of EF-3 #107L Exhaust 3 2.000 208 6.1
NCE
A CCORDA

1 Light
Hood
2 DCV-2111 Wall Utility Cabinet Right Smart Controls DCV EF-3 #107R Exhaust 3 2.000 208 6.1
Hood # 4 1 Fan SF-2 ITEM #107 Supply 3 5.000 208 15.0
R
D
E
T

$5&+,7(&785(
S
I

MODEL NUMBER DRAWN BY SCHEMATIC TYPE DESCRIPTION OF OPERATION: A B C D E F G H I


S

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U

JOB NO
C

DCV-2111 INSTALL Demand Control Ventilation, w/ control for 2 Exhaust Fans, 1 Supply Fan, Exhaust on in Fire, Lights out in Fire, Fans
FACTORY WIRING
3032020 modulate based on duct temperature. INVERTER DUTY THREE PHASE MOTOR REQUIRED! Room temperature sensor shipped UNLESS SPECIFIED OTHERWISE, ALL FACTORY AC WIRING 16 AWG. ALL FACTORY DC WIRING 18 AWG. PUT END OF LINE PLUG IN MOTOR POWER CIRCUIT SCHEMATIC
JOB NAME DATE DWG NO loose for field installation.Verify distance between VFD and Motor; additional cost could apply if distance exceeds
NORM'S RESTAURANTEnglewood,CA... 50 feet.
EMPTY RJ45 JACKS, PN: EOL120A NOTE: IF VFD HAS 1PH 240V INPUT, USE L1 & L2 ONLY. CIRCUIT BOARDS
8/31/2017 ECP #1-1 SWITCHES û‚¹¼ċ™‚ċĖû™‹&Ђí
1 CAT-5 CABLE. LENGTH AS REQUIRED. IF VFD HAS 1PH 120V INPUT, USE L1 & N ONLY. ECPM03
1
J9 120V
HMI 1 DCV Rev. 1.18
DC-
GND

14 AWG SM-1
MTR: EXH-1 7KH3URPHQDGH1RUWK
WH 2x
CONTROL INPUT J4 FLA: 6.1 HMI Rev. 2.05
www.captiveaire.com

N1 1 N1 ECPM03 BK BK
DC-
DC+

BK 3 PH L1 BK HP: 2.000
2 FAN: 05
ROUTER AR1 2 AR1 120V H1=LINE, 208 V
BK U/T1P100: 01 RA-x RD-x /RQJ%HDFK&$
SF-1 ITEM L2 BK BK V/T2 N/A
LOAD LEG 1 BLACK FLA:8.7 BK N1=NEUTRAL, 15A
COMMCAT-5 ETHERNET CONNECTION
BL

BREAKER PANEL TO CONTROL PANEL Load Wiring U3 GAS 3 GAS 15 A L3 GR W/T3P107: P101: 120 VAC 24 VDC CONTROL PANEL
HP:3.000 BREAKER. DO 00
LOAD LEG 2 BLACK BK 24V 8 9 10 11 12 13 14 GR RELAY ZZZLGDH[SHULHQFHQHW
WH/BL

Responsibility: Electrician SM-3 V3 VOLT:208 V CONTROL PANEL - - KTS 4 KTS COM-1 GND P108: 87 01   RELAY
 01
LOAD LEG 3 BLACK TO WIRE DIRECTLY TO COMMUNICATION NOT CONNECT GND BK BK N/A 0%    0%
3 WIRE TO W3 24V EN ILA BK ILA BKU1 P131:
BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED 120V HOT RED WORLD WIDE KS 5 TO SHUNT TRIP -+ J6 1 2 3 4 5 6 7 Wired to V1
BK L1 P150: 01 %1+.   ## %1+.
VFD QUICK SF1 MODULE. SEE CASLINK OWNERS 2 BK DC RO ILB RD ILB BK BK L2 P167: 60
BREAKER PANEL CONTROL PANEL ST 6 ST BREAKER. SEE PS-01 Master CORE W1 %1/    %1/
120V NEUTRAL WHITE WEB MANUAL FOR FURTHER INSTRUCTIONS. DC+ + ILC ILC L3/NP194: 225 LCD
CONNECTOR N1 N1 INSTALLATION (if applicable)
4 GROUND GREEN PCU 7 N L AC DC- - - RJC-1 P410:
Hot GND BK 2x SCHEMATIC FOR BK VFD: ESV152N02YXB571 11 INTERFACE
H1 H1 8 H1 ADDITIONAL REQ. CMA BK A COMPONENT LIST ROOM TEMPERATURE $UFKLWHFW
BREAKER 1PH Neutral RD
DC+
RO1

N1 MUST HAVE ITS OWN METAL CONTROL PANELT1A CAT-5 CMB RD B MTR: EXH-2 LABEL DESCRIPTION
120 V Ground
C1 CMC Shielded C 14 AWG SM-2 FLA: 6.1 SENSOR
GND CONDUIT. WIRE TO PROVIDED TO T1B GR BK BK ST-X Starter
5
N1
H1

15 A WIRE TO CONTROL BOARD. ROOM TEMP PANEL LID - Twisted 3 PH L4 HP: PN: varies
CONDUIT DROP. KITCHEN TEMP SENSOR MOUNTED IN ROOM AWAY GND Pair J1 208 V L5
BK BK U/T1P100: 2.000 01 OL-X Overload
CONTROL POWER. DO NOT WIRE FROM HEAT SOURCES. SEE MANUAL ECPM03 BK BK V/T2 N/A PN: varies
TO SHUNT TRIP BREAKER. SENSOR 15 A L6 P101:
REMOVE JUMPER GR W/T3P107: 00 C-X Contactor
6 ON PCB
MAKE UP AIR IN MUA #1 3 NOTE: All items on ECPM03 J3 line to be daisy chained GR GND P108: 87 PN: varies
1ST HOOD LIGHT BREAKER SHARED W/ CONTROL from one component to the next, with EOL120A at end GND BK BK
DAMPER IL1A D3 CONTROL PANELT2A U2 N/A PS-1 Power Sup. 24VDC TYPICAL HOOD CONTROL PANEL INSTALLATION
POWER. SWITCH #1 of line. Place PN: EOL120A in empty RJ45 port. BK BK L1 P150: P131:
01 PN: MDP18-24A- 1C
LINE PROVING IL1B D7 TO T2B FACTORY WIRED TEMPERATUREHOOD 1 V2 BK BK L2 P167: 60 *(2))5(<%/,0
L1 ECPM03/DAISY CHAIN RA-x 120V Relay DPDT
BREAKER 3PH LINE 1
W2 L3/NP194: 225 PN: 34.110.0184.0
7 INTERLOCK LOW VOLTAGE CONNECTION FOR
TERMINAL NAMES DUCT SENSOR SENSOR. MOUNTED IN EXHAUSTRISER
DUCT
208 V
L2 DO NOT APPLY
DAMPER INTERLOCK. SHOULD P410:
LINE IF MUA BY OTHERS J3 VFD: ESV152N02YXB571 12
L3 HAVE CONTINUITY WHEN DAMPER $,$1&$5%/(('$3
MCA: 7.6 A Ground IS PROVEN OPEN. RD-x 24VDC Light Relay
GND NOT REQUIRED FOR ALL UNITS. CONTROL PANELT3A MTR: SF-1 ITEM PN:34.110.0188.0
8 MOCP: 15 A EXH-1 SM-1 1 JUMPER1 JUMPER1 JUMPER 14 AWG SM-3 FLA: 8.7
SEE MAKE-UP AIR SCHEMATIC. TO T3B 11 11 11 BK BK TS-x Duct Thermostat
WIRE TO CONTROL BOARD. HOOD 2 3 PH HP: 3.000 PN:A/CP-PO-T4"-EXPL
WIRE TO VFD QUICK CONNECTOR DUCT SENSOR SENSOR MOUNTED IN EXHAUST RISER
DUCT 1 4 208 V
L7 BK
L8 BK
BK U/T1P100: 01 Demand Control Ventilation Hood Control Panel Specifications:
LINE
1SM-1 1SM-2 1SM-3 20 A
BK V/T2 N/A
9 L4 L9 GR W/T3 P101:
P107: Plans, maps, specifications, studies, and reports not
GR 00
BREAKER 3PH LINE GND P108: 90 Controls shall be listed by ETL (UL 508A)
L5 2 2 2 GND BK BK
• containing a red ink seal imprint accompanied by an
208 V LINE THE FOLLOWING CONNECTIONS J7 120V U3 N/A
L6 MAY OR MAY NOT BE BK BK L1 P150: P131:
01 original
10 MCA: 7.6 A Ground CONTROL PANEL TO ACCESSORY ITEMS REQUIRED BASED ON JOBSITE RD-1 BKV3 BK L2 P167: 60
GND BK BK BK W3 signature by the licensed professional may have been
MOCP: 15 A EXH-2 SM-2 Responsibility: Electrician SPECIFICATIONS IO1 1 IO1 4 6 H1 L3/NP194: 225
BK
P410: The control enclosure shall be NEMA 1 rated and listed for installation inside of the exhaust hood utility cabinet. The control enclosure may fraudulently altered and shall not be considered an original
SHUNT COIL B1 2 B1 N1 VFD: ESV222N02YXB571 21 •
WIRE TO VFD QUICK CONNECTOR CONTROL PANEL COMPONENT HOT TO SHUNT COIL HOOD LIGHTS
W1 JUMPER
11 CONTROL PANELST BK copy. All information should be disregarded unless verified
LINE NEUTRAL FROM SHUNT COIL 5 EF1 3 EF1 be constructed of stainless steel or painted steel.
L7 MICROSWITCH 1 SIGNAL FOR N1 BK by the professional whose signature appears above.
BREAKER 3PH LINE SF1 4 SF1
L8 CAP EXTERNAL ST TERMINAL IS ENERGIZED Copyright Protected 2016.
208 V LINE
CONTROL PANEL 4:NO OFF OV1 5 RJC-x RJ45 to Twist. Pair
12 L9 SHUNT TRIP IN FIRE CONDITION.
TO 1:C 2:NC PN:RJ 45_MODBUS_CONV.
MCA: 10.9 A Ground C1
GND COM-1 CASLink MODULE • Temperature probe(s) located in the exhaust duct riser(s) shall be constructed of stainless steel.
MOCP: 20 A SF-1 ITEM SM-3
FIRE SYSTEMAR1 WIRE C1 TO COMMON (1). COMMON
PN:COMM01
13
MICROSWITCH WIRE AR1 TO NORMALLY CLOSED (2). CONTROL PANELC2
WIRE TO VFD QUICK CONNECTOR NORMALLY OPEN
C1 TO AR1 SHOULD HAVE MS-1 4:NO CAP
OFF SPARE FIRE AR2
CONTINUITY WHEN ARMED. SYSTEM DRY SPARE CONTACTS WILL MAKE C2 TO
1:C 2:NC AR2 WHEN SYSTEM IS ARMED. THEY 6 • A digital controller shall be provided to activate the hood exhaust fans dynamically based on a fixed differential between the ambient and (QJLQHHULQJ&RQVXOWDQW
C1 CONTACT ARE USED TO DISABLE EQUIPMENT BL BK
14 KTS H1
IF MORE THAN ONE MS-2 4:NO CAP
OR PROVIDE SIGNALS. (NOT FOR CR-X CARTRIDGE SWITCH duct temperatures sensors. This function shall meet the requirements of IMC 507.2.1.1
FIRE SYSTEM, WIRE OFF BUILDING FIRE ALARM WHICH MUST BK WH PN:423878
IN SERIES AS SHOWN 1:C 2:NC BE WIRED DIRECTL TO THE ANSUL AR1 7 RA-1 8 N1
CONTROL PANEL TO FANS ALARM INITIATING SWITCH LOCATED
15 IN ANSUL AUTOMAN) BL PR
Responsibility: Electrician AR1 DC+ 8 RD-1 7 RO1
LEGEND A digital controller shall provide adjustable hysteresis settings to prevent cycling of the fans after the cooking appliances have been turned
CONTROL PANEL FANS COMMON BK WH FIELD WIRING •
ANSUL CONTROL PANELSFC1 SF1 7 RA-2 8 FACTORY
16 CARTRIDGE SW NORMALLY OPEN BK- BLACK YW- YELLOW
FAN: 01 EXH-1 DRY CONTACTSFO1 WIRING off and/or the heat in the exhaust system is reduced.
LOAD LEG 1 7 BL- BLUE GY- GREY
Load Wiring U1 FLA:6.1 CONTROL PANEL 2:NC ON/OFF WITHSFC2 COMMON BR- BROWN PR- PURPLE
LOAD LEG 2 HP:2.000
SM-1 V1 TO BLACK 1:C 4:NO NORMALLY OPEN OR- ORANGE RD- RED
17 LOAD LEG 3
VOLT:208 V H1 SUPPLY FAN SFO2
WH- WHITE
WIRE TO W1 KILL SWITCH KTS BLACK GROUP 1 SPARE CONTACTS WILL MAKE
GROUND COMMON TO NORMALLY OPEN OR/BL- OR/BL STRIPE • A digital controller shall provide an adjustable minimum fan run-time setting to prevent fan cycling.
VFD QUICK GND LOOP 120V SIGNAL THROUGH KILL WHEN SUPPLY FAN IS ON. BL/RD- BL/RD STRIPE
CONNECTOR WIRE TO SWITCH LOOP. SWITCH SHOULD RD/GN- RD/GN STRIPE
18 DISCONNECT
MUST HAVE ITS OWN CONDUIT BE CLOSED IN NORMAL STATE
AND OPEN IN ALARM. CR-1 2:NC + WH/BL- WH/BL STRIPE
DO NOT SHARE CONDUIT! 4:NO DCV SPEED VO+ MAKE UP AIR INTERLOCK. FAN
1:C - TO BMS BK WH
FAN: 02 EXH-2 H! JUMPER EF1 H N • Variable Frequency Drives (VFDs) shall be provided for fans as required. The digital controller shall modulate the VFDs between a
LOAD LEG 1 0-10V OUTPUTVO- 8 JOB NAME
19 Load Wiring U2 FLA:6.1 ON PCBWIRE TO ECPM03 TERMINALS. PANEL COOLING
LOAD LEG 2 CONFIGURABLE OUTPUT. NORM'S RESTAURAN...

IL1B
IL1A
SM-2 V2 HP:2.000 IF MORE THAN ONE ANSUL CR-2 2:NC
DRAWING TITLE minimum setpoint and a maximum setpoint on demand. The duct temperature sensor input(s) to the digital controller shall be used to
LOAD LEG 3
VOLT:208 V (TOTAL) SEE ECPM03 OWNERS MANUAL.
CARTRIDGE SW, WIRE IN 1:C 4:NO J10 DCV-2111
WIRE TO W2 + ECPM03 DRY CONTACTS (SHOWN DE-ENERGIZED)
20 GROUND DESCRIPTION OF OPERATION calculate the speed reference signal.
VFD QUICK GND SERIES AS SHOWN
KTS VFD ANALOG 30 - TO BMS 14 AWG RA-1-1
WIRE TO Demand Control
CONNECTOR 0-10V OUTPUT 2 ON/OFF Ventilation, w/ control
DISCONNECT
MUST HAVE ITS OWN CONDUIT WIRE TO VFD TERMINAL STRIP. AR2 WITH FIRE for 2 Exhaust Fans, 1
NO
IN VFD PROPORTIONAL TO FREQUENCY.
DO NOT SHARE CONDUIT! C2 Supply Fan, Exhaust on
21 ALL SWITCHES FACTORY WIRED SEE VFD OWNERS MANUAL. C YW in Fire, Lights out in
CONTROL PANELJ4 (EACH VFD) Fire, Fans modulate
• The VFD speed range of operation shall be from 0% to 100% for the system, with the actual minimum speed set as required to meet
TO CAT-5 CONNECTION BMS SWITCH 14 AWG RA-2-1 based on duct
C NO 9 temperature. INVERTER
SWITCHES CONTROL PANELH1 ON/OFF minimum ventilation requirements.
Missouri Specialized Accounts

22 SFO1 NO WITH DUTY THREE PHASE MOTOR


TO IO1 REQUIRED! Room
SFC1 C YW SUP temperature sensor
HOOD LIGHTS 1 EXTERNAL SIGNAL SWITCH THROUGH BMS shipped loose for field
WILL ACTIVATE ZONE1 FANS AND 14 AWG RA-2-2 installation.Verify
BLACK SWITCH LIGHTS
23 CONTROL PANELB1 distance between VFD • An internal algorithm to the digital controller shall modulate supply fan VFD speed proportional to all exhaust fans that are located in the
WHITE SFO2 NO and Motor; additional
TO W1 cost could apply if
GREEN SFC2 C YW distance exceeds 50 same fan group as the supply fan.
HOOD LIGHTSGND feet.
24 1400 W MAX WIRE TO J-BOX ON TOP OF HOOD 10 JOB NO DRAWN BY
3032020
TYPE DATE
FACTORY 8/31/2017 • The system shall operate in PREP MODE during light cooking load or COOL DOWN MODE when sufficient heat remains underneath the
SC-20 x 18 x 8.62 BOX DWG NO
ECP #1-2
hood system after cooking operations have completed. Operation during either of these periods will disable the supply fans and provide an
MODEL NUMBER DRAWN BY SCHEMATIC TYPE DESCRIPTION OF OPERATION: MODEL NUMBER DRAWN BY SCHEMATIC TYPE DESCRIPTION OF OPERATION: exhaust fan speed that is equal to the minimum ventilation requirement.
JOB NO DCV-2111 INSTALL Demand Control Ventilation, w/ control for 2 Exhaust Fans, 1 Supply Fan, Exhaust on in Fire, Lights out in Fire, Fans
JOB NO DCV-2111 INSTALL Demand Control Ventilation, w/ control for 2 Exhaust Fans, 1 Supply Fan, Exhaust on in Fire, Lights out in Fire, Fans
3132020 modulate based on duct temperature. INVERTER DUTY THREE PHASE MOTOR REQUIRED! Room temperature sensor shipped 3132020 modulate based on duct temperature. INVERTER DUTY THREE PHASE MOTOR REQUIRED! Room temperature sensor shipped
JOB NAME DATE DWG NO loose for field installation.Verify distance between VFD and Motor; additional cost could apply if distance exceeds JOB NAME DATE DWG NO loose for field installation.Verify distance between VFD and Motor; additional cost could apply if distance exceeds
NORM'S RESTAURANT ENGLEWOOD,CA... 8/31/2017 ECP #2-1 50 feet. NORM'S RESTAURANT ENGLEWOOD,CA... 8/31/2017 ECP #2-2 50 feet.
• A digital controller shall disable the supply fan(s), activate the exhaust fan(s), activate the appliance shunt trip, and disable an electric gas 3URMHFW2ZQHU
1 1
valve automatically under the following conditions (as applicable):
2 FAN: 06 HOOD LIGHTS 1 2 a. Fire condition detected on a covered hood
LOAD LEG 1 BLACK SF-2 ITEM FLA:15.0 BLACK COMMON
BREAKER PANEL TO CONTROL PANEL Load Wiring U3 HP:5.000 CONTROL PANELB1 CONTROL PANELSFC1
LOAD LEG 2 BLACK WHITE NORMALLY OPEN b. Excessive temperature detected on any duct temperature sensor in the system (250 F adjustable)
Responsibility: Electrician SM-3 V3 VOLT:208 V TO W1 DRY CONTACTSFO1
LOAD LEG 3 BLACK GREEN
3 WIRE TO W3 HOOD LIGHTSGND 3 ON/OFF WITH COMMON
BREAKER SIZE SHOWN IS THE MAXIMUM ALLOWED 120V HOT RED SFC2
VFD QUICK SF1 1400 W MAX WIRE TO J-BOX ON TOP OF HOOD SUPPLY FAN SFO2 NORMALLY OPEN
BREAKER PANEL CONTROL PANEL 120V NEUTRAL WHITE
CONNECTOR N1 N1 ROUTER GROUP 1 SPARE CONTACTS WILL MAKE • A digital controller shall allow for external BMS fan control via Dry Contact (external control shall not override fan operation logic as required
4 GROUND GREEN 4
Hot GND COMMCAT-5 ETHERNET CONNECTION COMMON TO NORMALLY OPEN
H1 WHEN SUPPLY FAN IS ON. by code).
BREAKER 1PH Neutral CONTROL PANEL -
120 V
N1 MUST HAVE ITS OWN METAL -
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

Ground TO WIRE DIRECTLY TO COMMUNICATION +


5 15 A
GND CONDUIT. WIRE TO PROVIDED 5 DCV SPEED VO+
CONDUIT DROP. WORLD WIDE MODULE. SEE CASLINK OWNERS - TO BMS
CONTROL POWER. DO NOT WIRE WEB MANUAL FOR FURTHER INSTRUCTIONS. 0-10V OUTPUTVO- TO ECPM03 TERMINALS.
TO SHUNT TRIP BREAKER. REMOVE JUMPER ON PCBWIRE
CONFIGURABLE OUTPUT. • An LCD interface shall be provided with the following features:
6 1ST HOOD LIGHT BREAKER SHARED W/ CONTROL ON PCB
MAKE UP AIR IN MUA #1 6 (TOTAL) SEE ECPM03 OWNERS MANUAL.
POWER. SWITCH #1 DAMPER IL1A D3
CONTROL PANELT1A + a. On/Off push button fan & light switch activation
LINE PROVING IL1B D7 VFD ANALOG 30
L1 TO T1B - TO BMS b. Integrated gas valve reset for electronic gas valves (no reset relay required)
BREAKER 3PH LINE
7 LOW VOLTAGE CONNECTION FOR
TERMINAL NAMES
WIRE TO CONTROL BOARD. ROOM TEMP 7 0-10V OUTPUT 2
L2 INTERLOCK DO NOT APPLY
DAMPER INTERLOCK. SHOULD KITCHEN TEMP SENSOR MOUNTED IN ROOM AWAY WIRE TO VFD TERMINAL STRIP.
208 V LINE IF MUA BY OTHERS
IN VFD PROPORTIONAL TO FREQUENCY.
L3 HAVE CONTINUITY WHEN DAMPER SENSOR FROM HEAT SOURCES. SEE MANUAL SEE VFD OWNERS MANUAL. c. VFD Fault display with audible & visual alarm notification
MCA: 7.6 A Ground IS PROVEN OPEN. (EACH VFD)
GND NOT REQUIRED FOR ALL UNITS. BMS SWITCH
8 MOCP: 15 A EXH-3 SM-1 8 d. Duct temperature sensor failure detection with audible & visual alarm notification
SEE MAKE-UP AIR SCHEMATIC. CONTROL PANELT2A C NO
WIRE TO VFD QUICK CONNECTOR T2B
CONTROL PANELH1
TO WIRE TO CONTROL BOARD. HOOD 3 TO IO1 e. Mis-wired duct temperature sensor detection with audible & visual alarm notification
LINE DUCT SENSOR SENSOR MOUNTED IN EXHAUST RISER
DUCT 1 SIGNAL SWITCH THROUGH BMS
9 L4 9 EXTERNAL
BREAKER 3PH LINE WILL ACTIVATE ZONE1 FANS AND f. A single low voltage Cat-5 RJ45 wiring connection
208 V
L5 SWITCH LIGHTS
LINE
L6 CONTROL PANEL TO ACCESSORY ITEMS CONTROL PANELT3A g. An energy savings indicator that utilizes measured kWh from the VFDs
10 MCA: 7.6 A Ground 10
MOCP: 15 A GND TO T3B WIRE TO CONTROL BOARD. HOOD 3
EXH-4 SM-2 Responsibility: Electrician DUCT SENSOR SENSOR MOUNTED IN EXHAUST RISER
DUCT 2
WIRE TO VFD QUICK CONNECTOR CONTROL PANEL COMPONENT
11 11
LINE
L7 MICROSWITCH 1 CONTROL PANELT4A
BREAKER 3PH LINE
L8 4:NO
CAP TO T4B WIRE TO CONTROL BOARD. HOOD 4
208 V LINE CONTROL PANEL OFF
12 L9 DUCT SENSOR SENSOR MOUNTED IN EXHAUST RISER
DUCT 1 12
TO 1:C 2:NC
MCA: 18.8 A Ground C1
MOCP: 30 A GND FIRE SYSTEMAR1
SF-2 ITEM SM-3 MICROSWITCH WIRE C1 TO COMMON (1).
13 WIRE AR1 TO NORMALLY CLOSED (2). CONTROL PANELT5A 13
WIRE TO VFD QUICK CONNECTOR C1 TO AR1 SHOULD HAVE CAP TO T5B
MS-1 4:NO OFF WIRE TO CONTROL BOARD. HOOD 4
CONTINUITY WHEN ARMED. DUCT SENSOR SENSOR MOUNTED IN EXHAUST RISER
DUCT 2
1:C 2:NC
14
C1 14
IF MORE THAN ONE CAP PSP LIGHTS
MS-2 4:NO OFF
FIRE SYSTEM, WIRE MATCH HOT BLACK
CONTROL PANEL TO FANS IN SERIES AS SHOWN 1:C 2:NC CONTROL PANEL
HOOD NEUTRAL WHITE
15 TO LIGHT 15
Responsibility: Electrician AR1 GROUND GREEN
PSP LED INPUT
CONTROL PANEL FANS LIGHTS WIRE TO J-BOX ON TOP OF PSP.
ANSUL CONNECT TO RESPECTIVE HOOD
16 CARTRIDGE SW LIGHTING CIRCUIT. NOTE: DO NOT 16
FAN: 03 EXH-3 WIRE IN SERIES WITH HOOD LIGHTS.
LOAD LEG 1
Load Wiring U1 FLA:6.1 CONTROL PANEL 2:NC
LOAD LEG 2 HP:2.000
SM-1 V1 TO BLACK 1:C 4:NO
17 LOAD LEG 3
VOLT:208 V H1 THE FOLLOWING CONNECTIONS 17
WIRE TO W1 KILL SWITCH KTS BLACK
GROUND MAY OR MAY NOT BE
VFD QUICK GND LOOP 120V SIGNAL THROUGH KILL REQUIRED BASED ON JOBSITE
CONNECTOR WIRE TO SWITCH LOOP. SWITCH SHOULD SPECIFICATIONS
18 DISCONNECT
MUST HAVE ITS OWN CONDUIT BE CLOSED IN NORMAL STATE 18
AND OPEN IN ALARM. CR-1 2:NC SHUNT COIL
DO NOT SHARE CONDUIT! 4:NO HOT TO SHUNT COIL
1:C CONTROL PANELST
FAN: 04 EXH-4 H! NEUTRAL FROM SHUNT COIL
LOAD LEG 1 SIGNAL FOR N1
19 Load Wiring U2 FLA:6.1 19
LOAD LEG 2 HP:2.000 IF MORE THAN ONE ANSUL CR-2 2:NC EXTERNAL ST TERMINAL IS ENERGIZED
SM-2 V2 VOLT:208 V
LOAD LEG 3 1:C 4:NO SHUNT TRIP IN FIRE CONDITION.
WIRE TO W2 CARTRIDGE SW, WIRE IN
GROUND
20 VFD QUICK GND SERIES AS SHOWN 20
WIRE TO KTS
COMMON
CONNECTOR DISCONNECT CONTROL PANELC2
MUST HAVE ITS OWN CONDUIT NORMALLY OPEN
DO NOT SHARE CONDUIT! HMI SPARE FIRE AR2
21 WIRE DIRECTLY TO CONTROL BOARD SPARE CONTACTS WILL MAKE C2 TO 21
CONTROL PANELJ4 1 SYSTEM DRY AR2 WHEN SYSTEM IS ARMED. THEY
TO CAT-5 CONNECTION CONTACT ARE USED TO DISABLE EQUIPMENT
REMOTE OR PROVIDE SIGNALS. (NOT FOR
22 PLACE END OF LINE PLUG BUILDING FIRE ALARM WHICH MUST 22
MOUNTED IN EMPTY JACK. PN: EOL120A 2
EOL120A BE WIRED DIRECTL TO THE ANSUL
SWITCHES ALARM INITIATING SWITCH LOCATED
IN ANSUL AUTOMAN)
23 23
24 24
1RUPV5HVWDXUDQWV//&
A B C D E F G H I
/DNHZRRG%OYG
FACTORY WIRING
UNLESS SPECIFIED OTHERWISE, ALL FACTORY AC WIRING 16 AWG. ALL FACTORY DC WIRING 18 AWG. PUT END OF LINE PLUG IN MOTOR POWER CIRCUIT SCHEMATIC %HOOIORZHU&$
EMPTY RJ45 JACKS, PN: EOL120A NOTE: IF VFD HAS 1PH 240V INPUT, USE L1 & L2 ONLY. CIRCUIT BOARDS
SWITCHES
1 CAT-5 CABLE. LENGTH AS REQUIRED. IF VFD HAS 1PH 120V INPUT, USE L1 & N ONLY. ECPM03
J9 120V
HMI 1 DCV Rev. 1.18

DC-
GND
14 AWG SM-1
MTR: EXH-3
WH 2x
CONTROL INPUT J4 FLA: 6.1 HMI Rev. 2.05
N1 1 N1 ECPM03 BK BK

DC-
DC+
BK 3 PH L1 BK HP: 2.000 3132020- NORM'S RESTAURANT ENGLEW OOD,CA. 3132020 - NORM'S RESTAURANT ENGLEW OOD,CA. 3132020 - NORM'S RESTAURANTENGLEW OOD,CA. 3132020 - NORM'S RESTAURANT ENGLEW OOD,CA.
6WDPS
AR1 2 AR1 120V H1=LINE, 208 V L2
BK U/T1P100: 01 RA-x RD-x AirHandler Wiring JOB Evaporative Cooler Wiring JOB AirHandler Wiring JOB Evaporative Cooler Wiring JOB
BK N1=NEUTRAL, 15A BK BK V/T2 N/A

BL
GAS 3 GAS 15 A L3 GR W/T3P107: P101: 120 VAC 24 VDC
BREAKER. DO 24V 8 9 10 11 12 13 14 GR 00 A2607888-5
DRAWING NUMBER SHIP DATE8/31/2017 A2-G15 EC2607888-5
DRAWING NUMBER SHIP DATE8/31/2017 A2-G15 A2607888-6
DRAWING NUMBER SHIP DATE8/31/2017 A2-G15 EC2607888-6
DRAWING NUMBER SHIP DATE8/31/2017 A2-G15
BK RELAY MODEL MODEL MODEL MODEL

WH/BL
KTS 4 KTS NOT CONNECT COM-1 GND BK GND P108: 87 01   RELAY
 01
U1
BK N/A 0%    0%
24V EN ILA BK ILA BK P131: Installed Options Installed Options
KS 5 TO SHUNT TRIP -+ J6 1 2 3 4 5 6 7 Wired to BK L1 P150: 01 !ATTENTION ELECTRICIAN! Installed Options !ATTENTION ELECTRICIAN! Installed Options
DC V1 %1+.   ## %1+. Motorized Back Draft Damper Motorized Back Draft Damper
2 BK RO ILB RD ILB BK BK L2 P167: 60 DROP FOR DISCONNECT CONNECTION DROP FOR DISCONNECT CONNECTION
ST 6 ST BREAKER. SEE PS-01 Master CORE W1 %1/    %1/ IS FACTORY SUPPLIED Cooling Interlock IS FACTORY SUPPLIED Cooling Interlock
DC+ + ILC ILC (if applicable)
L3/NP194: 225
INSTALLATION DC- - - P410: CONNECT POWER TO THE DROP
DCV/VFD Wiring
CONNECT POWER TO THE DROP
DCV/VFD Wiring
PCU 7 N L AC RJC-1 VFD: ESV152N02YXB571 11
BK 2x SCHEMATIC FOR BK
H1 8 H1 ADDITIONAL REQ. CMA BK A COMPONENT LIST
RD

DC+
RO1
CAT-5 CMB RD B MTR: EXH-4 LABEL DESCRIPTION
C1 CMC Shielded C 14 AWG SM-2 FLA: 6.1 WH WH
GR BK BK ST-X Starter 1 1 N 1 1 N
Twisted

N1
H1
PANEL LID - 3 PH L4 HP: 2.000 PN: varies N N
BK WH WH

GND
Pair J1 208 V L5
BK U/T1P100: 01 OL-X Overload SW-01 SW-01
ECPM03 15 A
BK BK V/T2 N/A PN: varies BK 1 2 BK BL BK R B BK 1 2 BK BL BK R B
L6 P101: 11 11
GR W/T3P107: 00 C-X Contactor 2 BK 3 4 BK GR 2 11 W 2 BK 3 4 BK GR 2 11 W
3 NOTE: All items on ECPM03 J3 line to be daisy chained GR PN: MT-01 MT-01
GND P108: 87 varies BK 5 6 BK BK 5 6 BK
from one component to the next, with EOL120A at end GND BK BK N/A Power Sup. 24VDC RD(DCV SF1) 7 8 WH (DCV N1) RD(DCV SF1) 7 8 WH (DCV N1)
U2 PS-1 GR GR
of line. Place PN: EOL120A in empty RJ45 port. BK BK L1 P150: P131:
01 PN: MDP18-24A-1C GR MOCP = 10 AMPS FOR CONTROL WIRING Component Identification GR MOCP = 10 AMPS FOR CONTROL WIRING Component Identification
V2 SW-01 Component Identification SW-01 Component Identification
ECPM03/DAISY CHAIN BK BK L2 P167: 60 RA-x 120V Relay DPDT 3 Label Description Location 3 3 Label Description Location 3
W2 L3/NP194: 225 PN: 34.110.0184.0 (MAY NOT BE NEEDED DEPENDING ON OPTIONS) NOTE: Label Description Location (MAY NOT BE NEEDED DEPENDING ON OPTIONS) NOTE: Label Description Location
P410: IF DCV IS NOT PRESENT, RD AND WH WIRES FROM IF DCV IS NOT PRESENT, RD AND WH WIRES FROM
SEPARATE 120VAC SOURCE If cable is CM1NO2VL2BO2 SW-01 Thermostat [2] SEPARATE 120VAC SOURCE If cable is CM1NO2VL2BO2 SW-01 Thermostat [2]
J3 BL BL
NORM'S RESTAURANT
ENGLEWOOD,CA.

VFD: ESV152N02YXB571 12 4 BK WH 4
change SW-02 Overflow Switch [6] 4 BK WH 4
change SW-02 Overflow Switch [6]
RD-x 24VDC Light Relay MT-01 Supply motor [2] BK->BR & WH->BL MT-01 Supply motor [2] BK->BR & WH->BL
MTR: SF-2 ITEM PN:34.110.0188.0 MT-02 Damper motor [5] TI-01 Spray Timer [5-7] MT-02 Damper motor [5] TI-01 Spray Timer [5-7]
1 JUMPER1 JUMPER1 JUMPER 12 AWG SM-3 FLA: 15.0 TI-01 VA-01 VA-01 Internal Solenoid Valve [5] TI-01 VA-01 VA-01 Internal Solenoid Valve [5]
11 11 11 BK BK MT-02(MS4104F) BR 15 18 OR [BK] [WH] MT-02(MS4104F) BR 15 18 OR [BK] [WH]
3 PH L7 HP: 5 5 SV 5 5 SV
4 208 V L8
BK BK U/T1P100: 5.000
01 BL 1 2 GR BL 1 2 GR
1SM-1 1SM-2 1SM-3 BK BK V/T2 N/A 11 11
30 A L9 GR W/T3 P101:
GR P107: 00 SW-02 TI-01 SW-02 TI-01
GND P108: 90 6 6 6 6
2 2 2 GND BK BK BK C NC OR BK A1 A2 WH BK C NC OR BK A1 A2 WH
J7 120V N/A D T N D T N DATE:

8/31/2017
U3 BK BK L1 P150: P131:
01 JUMPER A1 AND B1 JUMPER A1 AND B1
RD-1 V3 BK BK L2 P167: 60 FOR RZ7-FSH3VU23 TIMER FOR RZ7-FSH3VU23 TIMER
BK BK BK W3 7 7 7 7
IO1 1 IO1 4 6 H1 L3/NP194: 225
BK
P410:
B1 2 B1 HOOD LIGHTS
W1 JUMPER N1 VFD: ESV402N02TXB571 21
BK 8 8 8 8 DWG.#:
5 EF1 3 EF1
BK
SF1 4 SF1
SW-01 Main disconnect switch [2] SW-01 Main disconnect switch [2] 3132020 ,VVXH)RU
OV1 5 RJC-x RJ45 to Twist. Pair 9 9 9 9
PN: WH WH
RJ45_MODBUS_CONV.
N N
COM-1 CASLink MODULE
PN:COMM01
10 10 10 10
PERMIT
DRAWN
6 11 11 11 11
BL BK SJDSR
KTS H1 PRESSURE PRESSURE
,VVXH'DWH
SWITCH SWITCH BY:
CR-X CARTRIDGE SWITCH
WH T A1 A2 T A1 A2
BK PN:423878 12 12 JUMPER 12 12 JUMPER
A1 AND B1 A1 AND B1
AR1 N1 FOR FOR
RZ7-FSH3VU23 RZ7-FSH3VU23
7 RA-1 8 TIMER 16 SV
TIMER 16 SV
OVERFL OW OVERFL OW
SWITCH SWITCH
15 18 15 18 09-18-17
BL PR TIMER TIMER
D D SCALE:
DC+ 8 RD-1 7 RO1
13 13 B 13 13 B
LEGEND W W
BK WH FIELD WIRING R R
SF1 7 RA-2 8 FACTORY Internal Internal
BK- BLACK YW- YELLOW B W B W
Water Water 5HYLVLRQV
R Solenoid R Solenoid
7 WIRING
BL- BLUE GY- GREY 14 14 11
14 14 11
3/4" = 1'-0"
BR- BROWN PR- PURPLE N N NO. REASON DATE
OR- ORANGE RD- RED
WH- WHITE 15 15 15 15
OR/BL- OR/BL STRIPE
BL/RD- BL/RD STRIPE MOTOR INFO MOTOR INFO
RD/GN- RD/GN STRIPE SUPPLY 3HP-208V-3P-8.7FLA SUPPLY 5HP-208V-3P-15.0FLA MASTER DRAWING
WH/BL- WH/BL STRIPE 16 16 16 16
MAKE UP AIR INTERLOCK. FAN
BK WH
JUMPER EF1 H N
8 JOB NAME 17 17 17 17
PANEL COOLING
NORM'S RESTAURAN...

IL1B
IL1A
DRAWING TITLE
J10 DCV-2111 Roof line Roof line
ECPM03 DRY CONTACTS (SHOWN DE-ENERGIZED) 18 18 18 18
DESCRIPTION OF OPERATION MOTOR CIRCUIT MCA: 10.9A
ELECTRICAL INFORMATION MOTOR CIRCUIT MCA: 18.8A
ELECTRICAL INFORMATION
14 AWG RA-1-1 Demand Control CONTROL CIRCUIT MCA: 1.0A CONTROL CIRCUIT MCA: 1.0A
ON/OFF Ventilation, w/ control MOTOR CIRCUIT MOP: 15A MOTOR CIRCUIT MOP: 30A
AR2 WITH FIRE for 2 Exhaust Fans, 1 CONTROL CIRCUIT MOP: 15A CONTROL CIRCUIT MOP: 15A
NO 19 19 19 19
C2 Supply Fan, Exhaust on E A E A
C YW P P
in Fire, Lights out in
Fire, Fans modulate
9 14 AWG RA-2-1 based on duct Field Wired Normally open valve Field Wired Normally open valve
20 20 20 20
ON/OFF temperature. INVERTER
and Piped To building and Piped To building
SFO1 NO WITH DUTY THREE PHASE MOTOR
REQUIRED! Room NOTES drain NOTES NOTES drain NOTES
SFC1 C YW SUP temperature sensor DENOTES FIELD WIRING DENOTES FIELD WIRING DENOTES FIELD WIRING DENOTES FIELD WIRING
shipped loose for field 21 DENOTES INTERNAL WIRING 21 21 DENOTES INTERNAL WIRING 21
DENOTES INTERNAL WIRING DENOTES INTERNAL WIRING
14 AWG RA-2-2 installation.Verify From building From building
WIRE COLOR WIRE COLOR
distance between VFD water supply water supply
Normally closed valve Normally closed valve
and Motor; additional WIRE COLOR BK - BLACK YW - YELLOW WIRE COLOR BK - BLACK YW - YELLOW
SFO2 NO cost could apply if 22 BK - BLACK YW - YELLOW 22 BL - BLUE GR - GREEN 22 BK - BLACK YW - YELLOW 22 BL - BLUE GR - GREEN
distance exceeds 50 BR - BROWN GY - GRAY BR - BROWN GY - GRAY SHEET NO.
SFC2 C YW BL - BLUE GR - GREEN BL - BLUE GR - GREEN
feet. BR - BROWN GY - GRAY OR - ORANGE PR - PURPLE BR - BROWN GY - GRAY OR - ORANGE PR - PURPLE
JOB NO DRAWN BY OR - ORANGE PR - PURPLE RD - RED PK - PINK OR - ORANGE PR - PURPLE RD - RED PK - PINK
10 23 23 WH - WHITE 23 23 WH - WHITE
3132020 RD - RED PK - PINK RD - RED PK - PINK
TYPE DATE WH - WHITE WH - WHITE 4
FACTORY 8/31/2017
SC-20 x 18 x 8.62 BOX DWG NO
ECP #2-3
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.3

12/4/2017 2:24:20 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
EXHAUST FAN INFORMATION - Job#3055271
FAN EF-5
WEIGHT
UNIT TAG FAN UNIT MODEL # CFM ESP. RPM H.P. B.H.P. VOLT FLA SONES
(LBS.) FAN DU50HFA EXHAUST FAN FEATURES:
NO.
FANS EF-1,EF-2,EF-3,EF-4 FEATURES:
1 EF-1 #76L DU180HFA 2400 1.200 1121 2.000 0.7510 3 208 6.1 156 13.6 - DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS)
DU180HFA EXHAUST FAN 28 7/8" - ROOF MOUNTED FANS
- ROOF MOUNTED FANS
2 EF-2 #76L DU180HFA 2400 1.200 1121 2.000 0.7510 3 208 6.1 156 13.6 39 3/8 - RESTAURANT MODEL - UL705
- UL705 AND UL762 - VARIABLE SPEED CONTROL
3 EF-3 #107L DU180HFA 3312 1.300 1326 2.000 1.2550 3 208 6.1 156 20
I N

- VARIABLE SPEED CONTROL


H
I T
NF P A

B U IL T
6
No . 9

- INTERNAL WIRING
NCE
A CCORDA

4 EF-3 #107R DU180HFA 3510 1.100 1322 2.000 1.2420 3 208 6.1 156 21 - INTERNAL WIRING
- WEATHERPROOF DISCONNECT
- WEATHERPROOF DISCONNECT
7 ITEM 0100 DISH FAN DU50HFA 1000 0.500 1355 0.500 0.2820 1 115 5.6 74 13.1 - THERMAL OVERLOAD PROTECTION (SINGLE PHASE) - THERMAL OVERLOAD PROTECTION (SINGLE PHASE)
- HIGH HEAT OPERATION 300°F (149°C)
R
D
E

8 EF-6 RESTROOM DR33HFA 700 0.500 1408 0.333 0.1900 1 115 4.4 56 11 - GREASE CLASSIFICATION TESTING
T

OPTIONS $5&+,7(&785(
S
I

ECM WIRING PACKAGE-EXHAUST FANS - MANUAL SPEED CONTROL. &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð


U
C

MUA FAN INFORMATION - Job#3055271 NORMAL TEMPERATURE TEST 27 1/4"


33 3/4 EXHAUST FAN MUST OPERATE CONTINUOUSLY SCR-13 BIRD SCREEN
FAN
DESIGN
EVAP COOLER EVAP COOLER EVAP COOLER EVAP COOLER
WEIGHT WHILE EXHAUSTING AIR AT 300°F (149°C) 21 1/2" I 15-BDD DAMPER û‚¹¼ċ™‚ċĖû™‹&Ђí
UNIT TAG FAN UNIT MODEL # BLOWER HOUSING ESP. RPM H.P. B.H.P. VOLT FLA ENTERING DB ENTERING WB LEAVING DB LEAVING WB SONES 22 5/8 UNTIL ALL FAN PARTS HAVE REACHED 7KH3URPHQDGH1RUWK
CFM (LBS.)
www.captiveaire.com

NO. TEMP. TEMP. TEMP. TEMP.


THERMAL EQUILIBRIUM, AND WITHOUT ANY /RQJ%HDFK&$
DETERIORATING EFFECTS TO THE FAN WHICH
5 SF-1 ITEM 76 A2-G15 G15-PB A2 4080 0.500 859 3.000 2.0040 3 208 8.7 90.0°F 65.0°F 73.0°F 65.0°F 613 19.8 WOULD CAUSE UNSAFE OPERATION.
ZZZLGDH[SHULHQFHQHW
GREASE DRAIN
6 SF-2 ITEM #107 A2-G15 G15-PB A2 5425 0.500 903 5.000 3.2130 3 208 15.0 90.0°F 65.0°F 73.0°F 65.0°F 719 21 ABNORMAL FLARE-UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY $UFKLWHFW
WHILE EXHAUSTING BURNING GREASE VAPORS 2"
2
FAN OPTIONS AT 600°F (316°C) FOR A PERIOD OF
FAN 16 1/2 15 MINUTES WITHOUT THE FAN BECOMING
UNIT TAG OPTION (Qty. - Descr.) EF-6 DAMAGED TO ANY EXTENT THAT COULD CAUSE 13 1/4"
NO. AN UNSAFE CONDITION.
*(2))5(<%/,0
FAN DR33HFA EXHAUST FAN
1 EF-1 #76L 1 - Grease Box $,$1&$5%/(('$3
26 1/4 OPTIONS 16"
2 EF-2 #76L 1 - Grease Box 24
GREASE BOX Plans, maps, specifications, studies, and reports not
3 EF-3 #107L 1 - Grease Box
containing a red ink seal imprint accompanied by an
4 EF-3 #107R 1 - Grease Box 28 21" original
signature by the licensed professional may have been
1 - Motorized Backdraft Damper for Size 2 Housing fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
1 - Evaporative Cooler Wiring Harness by the professional whose signature appears above.
5 SF-1 ITEM 76
Copyright Protected 2016.
1 - Separate 120V Wiring Package (Required and used only for DCV or Prewire
26 1/2" 19 1/2"
with VFD) - Three Phase Only
26 1/2" 19 1/2"
1 - Motorized Backdraft Damper for Size 2 Housing
1 - Evaporative Cooler Wiring Harness
(QJLQHHULQJ&RQVXOWDQW
6 SF-2 ITEM #107 19 1/8
1 - Separate 120V Wiring Package (Required and used only for DCV or Prewire VENTED
with VFD) - Three Phase Only CURB
CURB
1 - SCR-13 Bird Screen
1 - I 15-BDD Damper 20" 14"
7 ITEM 0100 DISH FAN
1 - ECM Wiring Package-Exhaust - Manual or 0-10VDC Reference Speed Control (NIDEC
Motor) 20 GAUGE 20 GAUGE
STEEL STEEL
1 - I 15-BDD Damper CONSTRUCTION CONSTRUCTION
8 EF-6 RESTROOM 1 - ECM Wiring Package-Exhaust - Manual or 0-10VDC Reference Speed Control (NIDEC 2
Motor)
12 1/8
3" FLANGE
16 3" FLANGE
Missouri Specialized Accounts

CURB ASSEMBLIES 21
ON ROOF OPENING
NO. WEIGHT ITEM SIZE ROOF OPENING
FAN DIMENSIONS
FEATURES: 24
19 1/2" 24 16" DIMENSIONS
1 #1 41 LBS Curb 26.500"W x 26.500"L x 20.000"H Vented Hinged 16"
- DIRECT DRIVE CONSTRUCTION 19 1/2"
2 #2 41 LBS Curb 26.500"W x 26.500"L x 20.000"H Vented Hinged
(NO BELTS/PULLEYS)
3 #3 41 LBS Curb 26.500"W x 26.500"L x 20.000"H Vented Hinged
- ROOF MOUNTED FANS
4 #4 41 LBS Curb 26.500"W x 26.500"L x 20.000"H Vented Hinged - UL705
5 #5 42 LBS Curb 31.000"W x 31.000"L x 12.000"H - SAFETY DISCONNECT CURB 3URMHFW2ZQHU
#5 Rail 4.000"W x 4.000"L x 36.000"H
- STANDARD BIRD SCREEN
14"
6 #6 42 LBS Curb 31.000"W x 31.000"L x 12.000"H
- SPEED CONTROL
#6 Rail 4.000"W x 4.000"L x 36.000"H
7 #7 18 LBS Curb 19.500"W x 19.500"L x 14.000"H 20 GAUGE
OPTIONS STEEL
8 #8 18 LBS Curb 19.500"W x 19.500"L x 14.000"H CONSTRUCTION FAN #6 A2-G15 - SUPPLY FAN (SF-2 ITEM #107)
ECM WIRING PACKAGE-EXHAUST FANS - MANUAL SPEED CONTROL. 1. UNTEMPERED SUPPLY UNIT WITH 15" BLOWER IN SIZE #2 HOUSING
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

I 15-BDD DAMPER
2. EVAP COOLER (LPD CELDEK) –
FAN #5 A2-G15 - SUPPLY FAN (SF-1 ITEM 76) W/INTAKE HOOD W/EZ FILTERS
3" FLANGE 3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT
1. UNTEMPERED SUPPLY UNIT WITH 15" BLOWER IN SIZE #2 HOUSING
2. EVAP COOLER (CELDEK) W/INTAKE 4. MOTORIZED BACK DRAFT DAMPER 22" X 24", STANDARD
HOOD W/EZ FILTERS GALVANIZED CONSTRUCTION, 1 1/4" REAR FLANGE, WITH MS4104F MOTOR, WALL SUPPLY MOUNT, FOR SIZE 2 UNTEMPERED FAN HOUSING (5192)
3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT 5.
4. MOTORIZED BACK DRAFT DAMPER 22" X 24", STANDARD GALVANIZED ROOF OPENING SEPARATE 120VAC WIRING PACKAGE FOR MAKE-UP AIR UNITS. OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE PANEL OR WITH DCV
CONSTRUCTION, 1 1/4" REAR FLANGE, WITH MS4104F MOTOR, WALL SUPPLY MOUNT, FOR SIZE 2 UNTEMPERED FAN HOUSING (5192) 16 DIMENSIONS PACKAGE. PROVIDES SEPARATE 120VAC INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY ELECTRICIAN FROM DCV TO MUA SWITCH.
5. SEPARATE 16 6. 120V
120VAC WIRING PACKAGE FOR MAKE-UP AIR UNITS. OPTION MUST BE SELECTED WHEN MOUNTING VFD IN PREWIRE PANEL OR WITH DCV PACKAGE. WIRING CONNECTION TO ENERGIZE EVAPORATIVE COOLERS FROM UNTEMPERED SUPPLY FANS.
PROVIDES SEPARATE 120VAC INPUT TO SUPPLY FAN. THIS 120V SIGNAL MUST BE RUN BY ELECTRICIAN FROM DCV TO MUA SWITCH.
6. 120V WIRING BLOWER DISCHARGE
CONNECTION TO ENERGIZE EVAPORATIVE COOLERS FROM UNTEMPERED SUPPLY FANS.
CURB
BLOWER DISCHARGE
CURB
5 1/2"
5 1/2"
19"
20"
1 1/2"
WATER
16"
DRAIN
18"
1 1/2"
WATER 40 3/4" 18 3/4"
DRAIN AIRFLOW
18 3/4"
5 3/4"
AIRFLOW 6 1/8"
6 1/4"
4 1/2" 1RUPV5HVWDXUDQWV//&
6 1/8"
16" /DNHZRRG%OYG
4 1/2" %HOOIORZHU&$
FLEX CONDUIT
16" FOR FIELD
WIRING 6WDPS
FLEX CONDUIT
FOR FIELD
WIRING 129 7/8"
R
125 7/8" 78 1/4"
37 3/8" 72 1/4" L ISTED 40 1/8" 38 1/8"
R 37 3/8"
NORM'S RESTAURANT
ENGLEWOOD,CA.

40 1/8" 32 1/8"
L ISTED
DATE:

8/31/2017
AIRFLOW
LIFTING LUG
LIFTING LUG DWG.#:
AIRFLOW AIRFLOW AIRFLOW 3132020 ,VVXH)RU
AIRFLOW
LPD CELDEK PERMIT
AIRFLOW FILTER/CONTROL
CELDEK DRAWN
SERVICE DISCONNECT ACCESS DOOR
SJDSR ,VVXH'DWH
BY:
FILTER/CONTROL 43 3/8"
SERVICE DISCONNECT
36 3/4" SWITCH ACCESS DOOR 09-18-17
36 3/4" SWITCH
SCALE:
BLOWER/MOTOR 1/2" NPT 5HYLVLRQV
BLOWER/MOTOR 3/4" = 1'-0"
ACCESS DOOR 1/2" NPT WATER INLET NO. REASON DATE
ACCESS DOOR
24" SERVICE WATER INLET 24" SERVICE
CLEARANCE REQ. MASTER DRAWING
CLEARANCE REQ.
3 3/4"
3 3/4"
8 1/4"
8 1/4"
ADJUSTABLE
12" EQUIPMENT CURB LEG ADJUSTABLE
12" EQUIPMENT CURB LEG
31"
31" 31"
31" SHEET NO.
ROOF OPENING 2" SMALLER THAN CURB DIMENSION.
ROOF OPENING 2" SMALLER THAN CURB DIMENSION.
5
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.4

12/4/2017 2:24:21 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
D E SC RIPTIO N D A TE :

'HVLJQ&RQVXOWDQW
Double Wall Grease Duct Specification
Furnish double wall, factory built grease duct for use with Type I kitchen hoods, which conforms to the requirements of NFPA-96. Products shall be ETL
listed to UL-1978 and UL-2221 for venting air and grease vapors from commercial cooking operation. Models DW-2R, 3R and 3Z are used for grease
REDUCED CLEARANCE
duct applications when installed in accordance with these instructions and National Fire Protection Association "NFPA 96"; Standard for Ventilation DETAIL
I N
H
I T
NF P A

B U IL T
6
No . 9

NCE
A CCORDA

Control and Fire Protection of Commercial Cooking Operations. Double wall grease ducts are listed for a continuous internal temperature of 500
degrees F and intermittent temperatures of 2000 degrees F. 3/4" REDUCED
CLEARANCE
R
D
E
T

The duct sections shall be constructed of an inner duct wall and an outer wall with insulation in between. The inner duct wall shall be constructed of .036 $5&+,7(&785(
S
I

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U
C

inch thick, 430 type stainless steel and be available in diameters 8" through 24". The outer wall shall be constructed of stainless steel at a minimum of
.024 inch thickness. The duct, based on model number, shall include layers of Super Wool 607 Plus insulation between the inner and outer wall. Grease û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
www.captiveaire.com

duct joints shall be held together by means of formed V clamps and sealed with 3M Fire Barrier 2000+. The duct wall assembly shall be tested and listed /RQJ%HDFK&$
at ¾" or zero inch clearance, according to classifications. ZZZLGDH[SHULHQFHQHW
Classifications and Clearances $UFKLWHFW
UL 2221: Standard for Fire Resistive Grease Duct Enclosure Assemblies. Chapter 7 of this standard references a test labeled Internal Fire Test. Section
7.1.1 references two installation conditions, Condition A and Condition B. Condition A represents all installation condition except for installation within *(2))5(<%/,0
non-ventilated combustible enclosures. Condition B represents installation within a non-ventilated combustible enclosure. $,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
Model DW-3Z is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies) as an alternate to 2-Hr. fire resistive shaft enclosures with COMBUSTIBLE containing a red ink seal imprint accompanied by an
original
SURFACE signature by the licensed professional may have been
a minimum zero clearance to combustibles (sizes 8" to 24" diameter). Model 3Z is listed in accordance with the requirements for duct enclosure fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
Condition A and B. by the professional whose signature appears above.
DUCT Copyright Protected 2016.
DOUBLE V-BAND
Model DW-3R is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies) as an alternate to 2-Hr. fire resistive shaft enclosures with
a reduced clearance to combustibles (sizes 8" to 24" diameter). Model 3R is listed in accordance with the requirements for duct enclosure Condition B. (QJLQHHULQJ&RQVXOWDQW
Model DW-2R is classified under UL2221 (Test of Fire Resistive Duct Enclosure Assemblies) as an alternate to 2-Hr. fire resistive shaft enclosures with
a reduced clearance to combustibles (sizes 8" to 16" diameter). Model 2R is listed in accordance with the requirements for duct enclosure Condition B.
Exhaust fan
FACTORY BUILT DOUBLE WALL GREASE DUCT MODEL DW-3R SPECIFICATION: FACTORY BUILT DOUBLE WALL GREASE DUCT MODEL DW-2R SPECIFICATION:
FURNISH DOUBLE WALL, FACTORY BUILT GREASE DUCT FOR USE WITH TYPE I KITCHEN HOODS, WHICH FURNISH DOUBLE WALL, FACTORY BUILT GREASE DUCT FOR USE WITH TYPE I KITCHEN HOODS, WHICH
CONFORMS TO THE REQUIREMENTS OF NFPA-96. PRODUCTS SHALL BE ETL LISTED TO UL-1978 AND UL-2221 CONFORMS TO THE REQUIREMENTS OF NFPA-96. PRODUCTS SHALL BE ETL LISTED TO UL-1978 AND UL-2221 Vented curb per NFPA-96
FOR VENTING AIR AND GREASE VAPORS FROM COMMERCIALCOOKING OPERATION. TESTING HAS BEEN FOR VENTING AIR AND GREASE VAPORS FROM COMMERCIALCOOKING OPERATION. TESTING HAS BEEN
EXTENDED TO RECONGNIZE ASTM E2336 AND AC101 DUE TO SIMILAR TESTING CRITERIA. MODELS DW-2R, 3R EXTENDED TO RECONGNIZE ASTM E2336 AND AC101 DUE TO SIMILAR TESTING CRITERIA. MODELS DW-2R, 3R
AND 3Z ARE USED FOR GREASE DUCT APPLICATIONS WHEN INSTALLED IN ACCORDANCE WITH THESE AND 3Z ARE USED FOR GREASE DUCT APPLICATIONS WHEN INSTALLED IN ACCORDANCE WITH THESE
INSTRUCTIONS AND NFPA 96; STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL
Missouri Specialized Accounts

INSTRUCTIONS AND NFPA 96; STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL
COOKING OPERATIONS. DOUBLE WALL GREASE DUCTS ARE LISTED FOR A CONTINUOUS INTERNAL COOKING OPERATIONS. DOUBLE WALL GREASE DUCTS ARE LISTED FOR A CONTINUOUS INTERNAL
TEMPERATURE OF 500 DEGREES F AND INTERMITTENT TEMPERATURES OF 2000 DEGREES F. TEMPERATURE OF 500 DEGREES F AND INTERMITTENT TEMPERATURES OF 2000 DEGREES F.
THE DUCT SECTIONS SHALL BE CONSTRUCTED OF AN INNER DUCT WALL AND AN OUTER WALL WITH THE DUCT SECTIONS SHALL BE CONSTRUCTED OF AN INNER DUCT WALL AND AN OUTER WALL WITH Fan adapter plate Adjustable Duct
INSULATION IN BETWEEN. THE INNER DUCT WALL SHALL BE CONSTRUCTED OF .036 INCH THINK, 430 TYPE INSULATION IN BETWEEN. THE INNER DUCT WALL SHALL BE CONSTRUCTED OF .036 INCH THINK, 430 TYPE
STAINLESS STEEL AND BE AVAILABLE IN DIAMETERS 8" THROUGH 24". THE OUTER WALL SHALL BE STAINLESS STEEL AND BE AVAILABLE IN DIAMETERS 8" THROUGH 24". THE OUTER WALL SHALL BE with ceramic gasket
CONSTRUCTED OF STAINLESS STEEL AT A MINIMUM OF .024 INCH THICKNESS. THE DUCT, BASED ON MODEL CONSTRUCTED OF STAINLESS STEEL AT A MINIMUM OF .024 INCH THICKNESS. THE DUCT, BASED ON MODEL
NUMBER, SHALL INCLUDE LAYERS OF SUPER WOOL 607 PLUS INSULATION BETWEEN THE INNER AND OUTER NUMBER, SHALL INCLUDE LAYERS OF SUPER WOOL 607 PLUS INSULATION BETWEEN THE INNER AND OUTER Adjustable collar
AIR FLOW

WALL. GREASE DUCT JOINTS SHALL BE HELD TOGETHER BY MEANS OF FORMED V CLAMPS AND SEALED WITH WALL. GREASE DUCT JOINTS SHALL BE HELD TOGETHER BY MEANS OF FORMED V CLAMPS AND SEALED WITH
3M FIRE BARRIER 2000+. THE DUCT WALL ASSEMBLY SHALL BE TESTED AT 3/4" OR ZERO INCH CLEARANCE, 3M FIRE BARRIER 2000+. THE DUCT WALL ASSEMBLY SHALL BE TESTED AT 3/4" OR ZERO INCH CLEARANCE,
ACCORDING TO CLASSIFICATIONS. ACCORDING TO CLASSIFICATIONS.
CLASSIFICATIONS AND CLEARANCES CLASSIFICATIONS AND CLEARANCES 3URMHFW2ZQHU
UL 2221: STANDARD FOR FIRE RESISTIVE GREASE DUCT ENCLOSURE ASSEMBLIES. CHAPTER 7 OF THIS UL 2221: STANDARD FOR FIRE RESISTIVE GREASE DUCT ENCLOSURE ASSEMBLIES. CHAPTER 7 OF THIS
STANDARD REFERENCES A TEST LABELED INTERNAL FIRE TEST. SECTION 7.1.1 REFERENCES TWO STANDARD REFERENCES A TEST LABELED INTERNAL FIRE TEST. SECTION 7.1.1 REFERENCES TWO
INSTALLATION CONDITIONS, CONDITION A AND CONDITION B. CONDITION A REPRESENTS ALL INSTALLATION INSTALLATION CONDITIONS, CONDITION A AND CONDITION B. CONDITION A REPRESENTS ALL INSTALLATION
CONDITION EXCEPT FOR INSTALLATION WITHIN NON-VENTILATEDCOMBUSTIBLE ENCLOSURES. CONDITION B CONDITION EXCEPT FOR INSTALLATION WITHIN NON-VENTILATEDCOMBUSTIBLE ENCLOSURES. CONDITION B
REPRESENTS INSTALLATION WITHIN A NON-VENTILATED COMBUSTIBLE ENCLOSURE. REPRESENTS INSTALLATION WITHIN A NON-VENTILATED COMBUSTIBLE ENCLOSURE.
MODEL DW-3R IS CLASSIFIED UNDER UL2221 AS AN ALTERNATE TO 2-HR FIRE RESISTIVE SHAFT ENCLOSURES MODEL DW-2R IS CLASSIFIED UNDER UL2221 AS AN ALTERNATE TO 2-HR FIRE RESISTIVE SHAFT ENCLOSURES
WITH A REDUCED CLEARANCE TO COMBUSTIBLES (SIZES 8" TO 24" DIAMETER). MODEL 3R IS LISTED IN WITH A REDUCED CLEARANCE TO COMBUSTIBLES (SIZES 8" TO 16" DIAMETER). MODEL 2R IS LISTED IN
ACCORDANCE WITH THE REQUIREMENTS FOR DUCT ENCLOSURE CONDITION B. Outer double V-clamp
ACCORDANCE WITH THE REQUIREMENTS FOR DUCT ENCLOSURE CONDITION B.
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

MODEL DW-3R: 3/4" CLEARANCE TO COMBUSTIBLES FROM THE SURFACE OF THE DUCT OUTER SHELL; ZEROR MODEL DW-2R: 3/4" CLEARANCE TO COMBUSTIBLES FROM THE SURFACE OF THE DUCT OUTER SHELL; ZEROR
INCH CLEARANCE FROM COMBUSTIBLES FROM THE TIP OF THE OUTER V BAND. INCH CLEARANCE FROM COMBUSTIBLES FROM THE TIP OF THE OUTER V BAND. Inner V-clamp
DOUBLE WALL GREASE DUCT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S DOUBLE WALL GREASE DUCT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
"INSTALLATION, OPERATION AND MAINTENANCE MANUAL," ETL LISTING, STATE AND LOCAL CODES. FANS "INSTALLATION, OPERATION AND MAINTENANCE MANUAL," ETL LISTING, STATE AND LOCAL CODES. FANS
SHALL BE SUPPORTED INDEPENDENTLY FROM THE GREASE DUCT SECTIONS. PROTECT GREASE DUCT FROM SHALL BE SUPPORTED INDEPENDENTLY FROM THE GREASE DUCT SECTIONS. PROTECT GREASE DUCT FROM
TWISTING OR MOVEMENT CAUSED BY FAN TORQUE OR VIBRATION. TWISTING OR MOVEMENT CAUSED BY FAN TORQUE OR VIBRATION.
CERTIFICATIONS: CERTIFICATIONS:
THE DW-3R SERIES HAS BEEN CERTIFIED BY ITS. THIS CERTIFICATION MARK INDICATES THAT THE PRODUCT THE DW-2R SERIES HAS BEEN CERTIFIED BY ITS. THIS CERTIFICATION MARK INDICATES THAT THE PRODUCT
HAS BEEN TESTED TO AND HAS MET THE MINIUM REQUIREMENTS OF A WIDELY RECOGNIZED (CONSENSUS) HAS BEEN TESTED TO AND HAS MET THE MINIUM REQUIREMENTS OF A WIDELY RECOGNIZED (CONSENSUS)
U.S. AND CANADIAN PRODUCTS SAFETY STANDARD, THAT THE MANUFACTURING SITE HAS BEEN AUDITED, U.S. AND CANADIAN PRODUCTS SAFETY STANDARD, THAT THE MANUFACTURING SITE HAS BEEN AUDITED,
AND THAT THE APPLICANT HAS AGRRED TO A PROGRAM OF PERIODIC FACTORY FOLLOW-UP INSPECTIONS TO AND THAT THE APPLICANT HAS AGRRED TO A PROGRAM OF PERIODIC FACTORY FOLLOW-UP INSPECTIONS TO
VERIFY CONTINUED PERFORMANCE. VERIFY CONTINUED PERFORMANCE.
Standard duct
Insulated cleanouts to be provided
in accordance with all state and local
code requirements.
3R 2R
Horizontal support assembly - see installation manual for
requirements.
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
Vertical support assembly.
See installation manual for %HOOIORZHU&$

AIR FLOW
requirements.
6WDPS
See installation manual Adjustable ducts are used on runs over 100ft to compensate for
for minimum overlap thermal expansion. See installation manual for requirements.
requirements.
NORM'S RESTAURANT
ENGLEWOOD,CA.

Duct run shown is for example purposes only.


See mechanical plans for additional information. 8/31/2017
DATE:
DWG.#:
18 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW14DWCLASY-2
3132020 ,VVXH)RU
PERMIT
DRAWN
Insulated riser cover
SJDSR ,VVXH'DWH
BY:
SCALE:

09-18-17
Riser
3/4" = 1'-0" 5HYLVLRQV
NO. REASON DATE
MASTER DRAWING
Additional information including installation manual available at
www.captiveaire.com.
HOOD
SHEET NO.
6
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.5

12/4/2017 2:24:21 PM
H:\17317\RVT\17317_R16.rvt
REVISIONS
DESCRIPT ION DAT E:

'HVLJQ&RQVXOWDQW
IN
A

H
IT
NF P

T
I L
B U
6
. 9
No

DC
N
A CORA E

37"
DW18DWTEASY-3
PART #
R

WALL DUCT TEE


18 - DOUBLE
24 - DOUBLE V BAND FOR 18 - DOUBLE WALL
D

24 - DOUBLE V BAND FOR 24 - DOUBLE V BAND FOR OUTER SHELL DUCT TEE ACCESS
14- 18 ROUND 2 ROUND OUTER SHELL OUTER SHELL PART # DW18DWCLASY- 3
E

ECCENTRIC ADAPTER PART # DW18DWCLASY- 3 PART # DW18DWCLASY- 3


COVER
PART # PART #
T

DW1418DWRNDADPEC3ASY- 3 DW18DWTEAD-3

$5&+,7(&785(
DUCT
PART #
PART #
S

20 - DOUBLE V BAND FOR


I

OUTER SHELL
DW1417DWLT-3
DW1427DWAJD-3

14-17 STRAIGHT

PART # DW14DWCLASY- 3
L

DUCT ADJUSTABLE
14 - 27 DOUBLE WALL
S

&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
U
C

û‚¹¼ċ™‚ċĖû™‹&Ђí
14 - 90 DOUBLE WALL
ELBOW
PART # DW1490DWASY- 3

7KH3URPHQDGH1RUWK
www.cap tivea ire .co m

AIR FLOW
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
4
20 - DOUBLE V BAND FOR
20 - DOUBLE V BAND FOR
OUTER SHELL
OUTER SHELL
PART # DW14DWCLASY- 3
PART # DW14DWCLASY- 3 20 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW14DWCLASY- 3
24 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW18DWCLASY- 3 $UFKLWHFW
18-02 2 DEGREE OFF SET
DUCT
PART #
DW1802DWOFFSE TASY-3
AIR FLOW

14- 18 ROUND 2 ROUND


14 - 27 DOUBLE WALL ECCENTRIC ADAPTER
DUCT ADJUSTABLE PART #
PART # DW1418DWRNDADPEC3ASY- 3
DW1427DWAJD-3
9'5 1/2"
20 - DOUBLE V BAND FOR

54.00"
OUTER SHELL
PART # DW14DWCLASY- 3
*(2))5(<%/,0
20 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW14DWCLASY- 3
$,$1&$5%/(('$3
14 - 27 DOUBLE WALL
DUCT ADJUSTABLE
PART # 60.00" 60.00"
14-11 STRAIGHT DW1427DWAJD-3
DUCT
PART #
DW1411DWLT-3
29.00" 60.00" 60.00" 60.00" 60.00" 65.50"
AIR FLOW

20 - DOUBLE V BAND FOR


OUTER SHELL Plans, maps, specifications, studies, and reports not
20 - DOUBLE V BAND FOR PART # DW14DWCLASY- 3
OUTER SHELL
PART # DW14DWCLASY- 3
containing a red ink seal imprint accompanied by an
14- 02 2 DEGREE OFF SET 14- 02 2 DEGREE OFF SET original
DUCT DUCT
PART # PART #
DW1402DWOFFSETASY- 3 DW1402DWOFFSETASY- 3
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
3" copy. All information should be disregarded unless verified
20 - DOUBLE V BAND FOR
by the professional whose signature appears above.
20 - DOUBLE V BAND FOR OUTER SHELL
OUTER SHELL PART # DW14DWCLASY- 3
PART # DW14DWCLASY- 3
12" 12" 12" 12" 12" 12" Copyright Protected 2016.
16" 䳯 14" 䳯 14" 䳯 14" 䳯 14"
2.00" 14 - DOUBLE WALL
14 - DOUBLE WALL DUCT TEE ACCESS
DUCT TEE ACCESS COVER
33" 33" COVER PART #
PART # DW14DWTEAD-3
DW14DWTEAD-3
(QJLQHHULQJ&RQVXOWDQW
43.00"
60" 39 3/4" 79 1/2" 39 3/4" 3"
3" 36 1/2" 93" 21 1/2"
58.00" 38.00"
Utility
Cabinet 28" 28"
Missouri Specialized Accounts

10" 10"
MUA Connections MUA Connections
7" 7" 7" HVAC Connections HVAC Connections
24"
MUA Connections MUA Connections
HVAC Connections HVAC Connections
8"
5" 5"
24" 13'-6.00" Overall Length 12'-10.00" Overall Length
63 1/2" 71 1/2" 77 3/4" 66 1/4"
3URMHFW2ZQHU
12" 11' 3.00"Nom./11' 3.00"OD 12' 0.00"Nom./12' 0.00"OD
3376 Lynch Rd., Pacific, MO, 63069 PHONE: (314) 605-5316 FAX: (919) 516-8730 EMAIL: [email protected]

PLAN VIEW - Hood #2 (ITEM #76R)


PLAN VIEW - Hood #1 (ITEM #76L) 12' 0.00" LONG 6030ND-2-ACPSP-F
11' 3.00" LONG 6030ND-2-ACPSP-F
54.00"
43.00"
60.00"
Transition Plate 16" Transition
Transition Plate
Plate 16" 16" Transition Plate 18" Transition Plate 18"
Duct to 26- 1_2" Curb Duct
Duct to
to 26-
26-1_21_2" Curb Duct to 26- 1_2" Curb Duct to 26- 1_2" Curb
PART # DW2616TP PART # DW2616TP PART # DW2618TP PART # DW2618TP
16-11 STRAIGHT 16-11 STRAIGHT
DUCT DUCT
PART # PART #
DW1611DWLT-2 DW1611DWLT-2
20.00" 20 - DOUBLE V BAND FOR 18-23 STRAIGHT 18-23 STRAIGHT
OUTER SHELL 20 - DOUBLE V BAND FOR
PART # DW16DWCLASY- 2 OUTER SHELL DUCT DUCT
PART # DW16DWCLASY- 2 PART # PART #
DW1823DWLT-3 DW1823DWLT-3

AIR FLOW
AIR FLOW
24 - DOUBLE V BAND FOR
24 - DOUBLE V BAND FOR
OUTER SHELL
OUTER SHELL
PART # DW18DWCLASY- 3
PART # DW18DWCLASY- 3
16 - 27 DOUBLE WALL 16 - 27 DOUBLE WALL
DUCT ADJUSTABLE DUCT ADJUSTABLE
PART # PART #
DW1627DWAJD-2 DW1627DWAJD-2
14.00" 14.00"
18 - 27 DOUBLE WALL
DUCT ADJUSTABLE
18 - 27 DOUBLE WALL PART #
DUCT ADJUSTABLE DW1827DWAJD-3
PART #
DW1827DWAJD-3

AIR FLOW
AIR FLOW

16- 02 2 DEGREE OFF SET 16-02 2 DEGREE OFF SET 22.95"


20 - DOUBLE V BAND FOR 20 - DOUBLE V BAND FOR DUCT DUCT
20 - DOUBLE V BAND FOR OUTER SHELL PART #
OUTER SHELL PART #
OUTER SHELL PART # DW16DWCLASY- 2 DW1602DWOFFSE TASY-2
PART # DW16DWCLASY- 2 PART # DW16DWCLASY- 2 DW1602DWOFFSETASY- 2
20 - DOUBLE V BAND FOR
20 - DOUBLE V BAND FOR 20 - DOUBLE V BAND FOR OUTER SHELL
OUTER SHELL OUTER SHELL PART # DW16DWCLASY- 2
PART # DW16DWCLASY- 2 PART # DW16DWCLASY- 2
24 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW18DWCLASY- 3
14- 18 ROUND 2 ROUND
24 - DOUBLE V BAND FOR 14- 18 ROUND 2 ROUND ECCENTRIC ADAPTER
OUTER SHELL ECCENTRIC ADAPTER PART #
16 - 90 DOUBLE WALL PART # DW18DWCLASY- 3
ELBOW PART # DW1418DWRNDADPEC3ASY- 3
PART # DW1690DWASY-2 DW1418DWRNDADPEC3ASY- 3
16 - 90 DOUBLE WALL
ELBOW
PART # DW1690DWASY- 2 24 - DOUBLE V BAND FOR
14-11 STRAIGHT OUTER SHELL
DUCT PART # DW18DWCLASY- 3
PART #
AIR FLOW DW1411DWLT-3
16 - DOUBLE WALL 14 - DOUBLE WALL
DUCT TEE ACCESS DUCT TEE ACCESS
COVER 16 - DOUBLE WALL COVER
PART # DUCT TEE ACCESS PART #
DW16DWTEAD-2 COVER DW14DWTEAD-3
PART #
DW16DWTEAD-2
1RUPV5HVWDXUDQWV//&
14 - 90 DOUBLE WALL
ELBOW
PART # DW1490DWASY- 3
16 - 27 DOUBLE WALL
DUCT ADJUSTABLE
16-02 2 DEGREE OFF SET PART #
AIR FLOW
DUCT 20 - DOUBLE V BAND FOR
DW1627DWAJD-2 20 - DOUBLE V BAND FOR OUTER SHELL
PART # OUTER SHELL 20 - DOUBLE V BAND FOR
DW1602DWOFFSE TASY-2 20 - DOUBLE V BAND FOR PART # DW16DWCLASY- 2
PART # DW16DWCLASY- 2 OUTER SHELL
20 - DOUBLE V BAND FOR
OUTER SHELL
PART # DW16DWCLASY- 2

16-02 2 DEGREE OFF SET


DUCT
PART #

OUTER SHELL
PART # DW16DWCLASY- 2 PART # DW16DWCLASY- 2

/DNHZRRG%OYG
DW1602DWOFFSE TASY-2
18 - DOUBLE
WALL DUCT TEE
PART #
DW18DWTEASY-3
16-11 STRAIGHT
DUCT
16-11 STRAIGHT
DUCT

%HOOIORZHU&$
PART # PART #
DW1611DWLT-2 DW1611DWLT-2
20 - DOUBLE V BAND FOR 2 3/4" 20 - DOUBLE V BAND FOR
OUTER SHELL 24 - DOUBLE V BAND FOR
20 - DOUBLE V BAND FOR 20 - DOUBLE V BAND FOR OUTER SHELL
PART # DW16DWCLASY- 2 24 - DOUBLE V BAND FOR 24 - DOUBLE V BAND FOR 24 - DOUBLE V BAND FOR OUTER SHELL
OUTER SHELL OUTER SHELL PART # DW14DWCLASY- 3
OUTER SHELL OUTER SHELL OUTER SHELL PART # DW18DWCLASY- 3
PART # DW16DWCLASY- 2 PART # DW14DWCLASY- 3 PART # DW18DWCLASY- 3
PART # DW18DWCLASY- 3 PART # DW18DWCLASY- 3
䳯 16" 䳯 16"
6WDPS
20 - DOUBLE V BAND FOR 6"
OUTER SHELL
PART # DW14DWCLASY- 3
20 - DOUBLE WALL RISER 20 - DOUBLE WALL RISER
20 - DOUBLE WALL RISER 20 - DOUBLE WALL RISER COVER COVER
COVER COVER PART # DW20DWRISER- 3 PART # DW20DWRISER- 3
PART # DW20DWRISER- 2 PART # DW20DWRISER- 2 20 - DOUBLE WALL RISER
COVER
PART # DW20DWRISER- 3
26" 52.00" 41.00"
LED 93.00"
30.00" 30" NOM.
HOOD #1 HOOD #2 24"
14'2" 11' 3.00" LONG 6030ND-2-ACPSP-F HOOD #3 (107L) 170.00"
12' 0.00" LONG 6030ND-2-ACPSP-F
HOOD #4 (107R)
NORM'S RESTAURANT
ENGLEWOOD, CA,

DATE:

8/31/2017
DWG.#:
48.0" MAX
3132020 ,VVXH)RU
PERMIT
DRAWN
BY:

,VVXH'DWH
80.00" 80" AFF REFERENCE
SCALE:

09-18-17
1/2" = 1'-0" 5HYLVLRQV
NO. REASON DATE
EQUIPMENT
BY OTHERS
MASTER DRAWING
SECTION VIEW - MODEL 5430ND-2-ACPSP-F FRONT VIEW - MODEL 5430ND-2-ACPSP-F
SHEET NO.
HOOD #3 (107L) HOOD #4 (107R)
7
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
HOOD DRAWINGS
6KHHW1XPEHU
M4.6

12/4/2017 2:24:22 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
(QJLQHHULQJ&RQVXOWDQW
3URMHFW2ZQHU
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
6WDPS
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
TITLE-24, ENERGY
COMPLIANCE
CERTIFICATES
6KHHW1XPEHU
M5.0

12/4/2017 2:24:27 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
(QJLQHHULQJ&RQVXOWDQW
3URMHFW2ZQHU
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
6WDPS
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
TITLE-24, ENERGY
COMPLIANCE
CERTIFICATES
6KHHW1XPEHU
M5.1

12/4/2017 2:24:47 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
GRAVITY GREASE GENERAL NOTES PLAN CHECK NOTES PLUMBING LEGEND FIXTURE COUNT
INTERCEPTOR SIZING 1. PLUMBING CONTRACTOR SHALL NOTIFY WATER COMPANY OF 1. ALL REQUIRED CLEANOUTS SHALL BE INSTALLED PER SECTION 707.0 SYMBOL ABBREV. DESCRIPTION SYMBOL ABBREV. DESCRIPTION
CPC 2013; TABLE 1014.3.6 PROPOSED NEW SERVICES TIE INTO EXISTING STREET MAINS AND AND 719.0 OF THE 2014 LOS ANGELES COUNTY BUILDING CODE/2013 SANITARY SEWER OR WASTE (ABOVE WSFU
W SS SS OR W MV MIXING VALVE QTY TAG DESCRIPTION WSFU EA.
USE TOTAL DFU'S INTERCEPTOR SIZE PAY COST FOR NEW SERVICES, HOOK-UP INSTALLATIONS AND CALIFORNIA PLUMBING CODE. NO CLEANOUT SPACING SHALL GRADE) TOTAL
WATER METERS. (UNLESS OTHERWISE NOTED ON PLANS.) EXCEED 100 FEET. SANITARY SEWER OR WASTE (BELOW 1 #03 MOP SINK 3 3
W SS SS OR W (E) EXIST. EXISTING
8 500 GALLON GRADE)
GW GW GREASE WASTE - KEY CONSTRUCTION NOTE 2 #14A CARBONATOR 1 2
21 750 GALLON 2. VERIFY EXACT LOCATION OF ALL EXISTING SITE PIPING, CABLES, 2. ALL NEW POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR
ETC. BEFORE TRENCHING. TO USE ACCORDING TO THE METHOD SET IN SECTION 609.9 OF THE V VENT X" - Y X"=PIPE SIZE, Y=FIXTURE UNITS 1 #32 WASHER 4 4
35 1,000 GALLON V
PLUMBING CODE.
90 1,250 GALLON 3. DIAGRAMMATICAL DRAWINGS. DO NOT SCALE PLUMBING FLOOR CD CD CONDENSATE DRAIN BTUH BRITISH THERMAL UNIT 1 #33 ICE MAKER 1 1
$5&+,7(&785(
X 172 1,500 GALLON PLAN FOR EXACT LOCATION OF PIPE RUNS. 3. THE RANGE HOOD FILTERS WASH WATER WILL BE DISCHARGED 2 #51 HAND SINK 1 2 &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
CW CW COLD WATER MBH BTUH X 1000
THRU THE GREASE INTERCEPTOR OR CLEANING OF THE FILTERS
216 2,000 GALLON 4. VERIFY ELECTRICAL CHARACTERISTICS WITH ELECTRICAL PLANS WILL BE DONE OFF SITE BY A SERVICE COMPANY. HW HOT WATER CFH CUBIC FEET PER HOUR (1 MBH = 1 CFH) 1 #52 S.S. WORKTABLE W/SINK 3 3
û‚¹¼ċ™‚ċĖû™‹&Ђí
HW 7KH3URPHQDGH1RUWK
307 2,500 GALLON PRIOR TO BID OR MATERIAL PURCHASE. /RQJ%HDFK&$
HWR HWR HOT WATER RETURN N.T.S. NOT TO SCALE 1 #62 S.S. PREP TABLE W/2-COMP SINK 3 3
4. THE WASH WATER GENERATED FROM WASHING CANS, CARTS, MATS, ZZZLGDH[SHULHQFHQHW
342 3,000 GALLON 5. VERIFY AND COORDINATE ROUGH-IN AND FIXTURE LOCATIONS WITH ETC. WILL BE ROUTED TO THE GREASE INTERCEPTOR. G G NATURAL GAS I.E. INVERT ELEVATION 1 #67 S.S POT SINK ASSEMBLY 2-FAUCETS 6 6
428 4,000 GALLON FIXTURE, ARCHITECTURAL, KITCHEN AND MECHANICAL DRAWINGS
UP PIPE UP CONN CONNECTION 1 #84 40 GAL. KETTLE W/FAUCET 3 3 $UFKLWHFW
PRIOR TO FABRICATION OR INSTALLATION OF PIPE. 5. THE GREASE INTERCEPTOR SHALL BE ACCESSIBLE AT ALL TIME.
576 5,000 GALLON
DN TEE DOWN FU FIXTURE UNIT 1 #86 40 GAL. KETTLE W/FAUCET 3 3
720 7,500 GALLON 6. VERIFY AND COORDINATE STRUCTURAL DRAWINGS FOR LOCATION 6. CONDENSATE WATER FROM AIR CONDITIONING AND/OR
2112 10,000 GALLON OF ALL FOUNDATION PENETRATIONS AND PROVIDE AS REQUIRED ALL REFRIGERATION UNITS SHALL BE ROUTED TO A PROPER PLUMBING DN PIPE DOWN GPM GALLONS PER MINUTE 1 #97A PRE RINSE FAUCET 3 3 *(2))5(<%/,0
NECESSARY SUPPORTS PER STRUCTURAL DETAILS. FIXTURE AND BE DISCHARGED TO THE SANITARY SEWER. $,$1&$5%/(('$3
2640 15,000 GALLON FCO FLOOR CLEANOUT GPH GALLONS PER HOUR 1 #99 DISH MACHINE 14 14
1
7. SLOPE ALL WASTE LINES MINIMUM OF Plans, maps, specifications, studies, and reports not
_" PER FOOT OR AS 7. THE INSTALLATION OF THE PRETREATMENT SYSTEM SHALL
4 DCO DOUBLE CLEANOUT HP HORSEPOWER 1 #105 FAUCET 3 3
containing a red ink seal imprint accompanied by an
REQUIRED BY LOCAL CODES. CONFORM WITH MANUFACTURER'S SPECIFICATIONS. original
FIRE PROTECTION DESIGN CRITERIA WCO WALL CLEANOUT PSI POUNDS PER SQUARE INCH 1 #112 FILL FAUCET 3 3 signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
8. PROVIDE AND INSTALL ALL INDIRECT WASTE LINES FROM HVAC 8. AT THE TIME OF PERMIT ISSUANCE, CONTRACTOR SHALL SHOW copy. All information should be disregarded unless verified
SOV SHUT-OFF VALVE AP ACCESS PANEL 1 #127 S.S. COUNTER W/UTILITY SINK 3 3 by the professional whose signature appears above.
THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR Copyright Protected 2016.
UNITS AND COOLER COILS. THEIR WORKERS COMPENSATION INSURANCE CERTIFICATE.
PROVIDING A NEW SPRINKLER LAYOUT WITH THE SYSTEM DESIGNED NO 1 #128 HAND SINK 1 1
SOV SHUT-OFF VALVE, NORMALLY OPEN W/ WITH
UNDER THE SUPERVISION OF A LICENSED PROFESSIONAL ENGINEER,
AND PROVIDE ALL MATERIALS REQUIRED FOR A COMPLETE 9. FLUSH VALVES, FAUCET STOPS, ETC. SHALL BE ADJUSTED TO THEIR 9. ALL WORK SHALL CONFORM TO THE STATE OF CALIFORNIA TITLE 24 NC SOV SHUT OFF VALVE, NORMALLY CLOSED FLR FLOOR 2 #129 DIPPERWELL 1 2 (QJLQHHULQJ&RQVXOWDQW
INSTALLATION FOR THE PROPOSED FINISH OF THIS SPACE. NORMAL WORKING CONDITIONS. REGARDLESS OF THE INFORMATION INDICATED ON THESE PLANS. IT
CONTRACTOR SHALL PREPARE ALL NEEDED DRAWINGS WITH PROPER PE IS THE THE RESPONSIBILITY OF THE INDIVIDUAL SUPERVISING THE C.V. CHECK VALVE CLG CEILING 2 #133 DIPPERWELL WITH FAUCET 1 2
SEALS, PERFORM ALL REQUIRED CALCULATIONS, HAVE APPROVAL OF 10. WORK SHALL NOT BE COVERED UNTIL IT HAS BEEN INSPECTED, CONSTRUCTION TO ENSURE THAT THE WORK IS DONE IN
ALL STATE, LOCAL AND INSURANCE UNDERWRITING AUTHORITIES, AS TESTED AND APPROVED BY THE PLUMBING INSPECTOR AND OTHER ACCORDANCE WITH CODE REQUIREMENTS PRIOR TO REQUESTING B.V. BALANCING VALVE ABV ABOVE 1 #136A FILL FAUCET 3 3
WELL AS MEETING ALL NFPA REQUIREMENTS. THE SPRINKLER SYSTEM GOVERNMENTAL AUTHORITIES HAVING JURISDICTION. INSPECTION. U UNION BEL BELOW 1 #156 FOUNTAINETTE 1 1
SHALL BE TESTED UNDER PRESSURE BY THE FIRE PROTECTION
CONTRACTOR, INSPECTED AND APPROVED BY LOCAL FIRE MARSHAL, 11. NOTIFY FIXTURE CONTRACTORS THAT PLUMBING ROUGH-INS HAVE 10. THE ISSUANCE OF A PERMIT SHALL NOT PREVENT TO OFFICIAL FROM P.V. AUTOMATIC GAS SHUT OFF VALVE UG UNDERGROUND 1 #162 HOT CHOCOLATE DISPENSER 1 1
PRIOR TO ACCEPTANCE OF OWNER. BEEN INSTALLED FIVE DAYS PRIOR TO POURING SLAB OR FINISH REQUIRING THE CORRECTION OF ERRORS OR FROM PREVENTING
SOC SHUT OFF COCK (GAS) DN DOWN 2 #163 JUICE DISPENSER 1 2
MATERIAL COVERING PAVEMENT PIPING FOR THEIR APPROVAL. ANY VIOLATION OF THE CODES ADOPTED BY THE CITY, RELEVANT
LAWS, ORDINANCE, RULES AND/OR REGULATIONS. EAAV SHUT OFF COCK (GAS) CONT. CONTINUED 1 #164 ICE BIN/SODA DISPENSER 1 1
12. INSTALLATION SHALL COMPLY WITH THE 2013 EDITION OF THE
CALIFORNIA BUILDING CODE (T-24) WHICH INCLUDES THE 2013 CBC, 11. THIS PROJECT SHALL COMPLY WITH THE 2013 EDITION OF THE HB HOSE BIBB TYP. TYPICAL 1 #165 WATER FILLER 1 1
SANITARY SEWER SIZE 2013, CMC, 2013 CPC WITH THE 2014 LOS ANGELES COUNTY BUILDING CALIFORNIA BUILDING CODE(T-24), WHICH ADOPTS THE 2013 CBC, S.W. SOFTENED WATER A.D.A. AMERICAN DISABILITIES ACT 1 #166 TEA MAKER 1 1
SW
CODE AMENDMENTS. 2013, CMC, AND 2013 CPC, WITH THE 2014 LOS ANGELES COUNTY
AMENDMENTS. FW F.W. FILTERED WATER A.F.F. ABOVE FINISHED FLOOR 1 #167 COFFEE MAKER 1 1
DIRECT INDIRECT DFU
QTY TAG DESCRIPTION DFU EA. 13. WATER CLOSETS SHALL HAVE A WATER CONSUMPTION OF NOT
DRAIN DRAIN TOTAL AFS A.F.S AUTOMATIC FIRE SPRINKLER KEC KITCHEN EQUIPMENT CONTRACTOR 1 #179 ICE BIN/SODA DISPENSER 1 1
MORE THAN 1.28 GALLONS OF WATER PER FLUSH.
1 #32 WASHER - 2" 3 3 TEMPERATURE & PRESSURE RELIEF
BIDDING AND CLARIFICATIONS T&P B.F.F. BELOW FINISHED FLOOR 1 #181 TEA MAKER 1 1
VALVE
1 #33 ICE MAKER - 2" FS 4 4 14. URINALS SHALL HAVE A WATER CONSUMPTION OF NOT MORE THAN 3URMHFW2ZQHU
DESIGN DRAWINGS ARE SCHEMATIC. VTR VENT THRU ROOF N.I.C.P. NOT IN PLUMBING CONTRACT 1 #183 COFFEE MAKER 1 1
0.125 GALLONS OF WATER PER FLUSH.
#35 ICE BIN
WHA WATER HAMMER ARRESTOR D.S. DOWN SPOUT 1 #186 DIPPERWELL W/FAUCET 1 1
15. LAVATORY FAUCETS SHALL BE EQUIPPED WITH AERATORS AND THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR
#45 COOLER EVAPORATOR COIL
SHALL BE DESIGNED AND MANUFACTURED SO THEY WILL NOT OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS A.T.P. AUTOMATIC TRAP PRIMER HDR. HEADER 1 #189 HAND SINK 1 1
1 #36 TROUGH DRAIN 3" - 6 6 EXCEED A WATER FLOW RATE OF 0.5 GALLONS PER MINUTE. OF THE DESIGN AND INCLUDE IN HIS BID ALL COST TO MEET THE DESIGN
INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR FD FLOOR DRAIN MTD. MOUNTED 5 WC WATER CLOSEST 5 25
1 #42 FREEZER EVAPORATOR COIL - 2" FS 4 4 OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT FLOOR SINK (COORDINATE GRATE
16. SELF CLOSING OR SELF METERING FAUCETS SHALL BE INSTALLED FS Y.B. YARD BOX 2 UR URINAL 1 2
CONTRACTORS COST. REQUIRED)
1 #96 SOILED DISHTABLE - 4" FS 8 8 ON LAVATORIES INTENDED TO SERVE THE TRANSIENT PUBLIC.
RP RE-CIRCULATION PUMP CONN. CONNECTION 5 LAV LAVATORY 1 5
METERED FAUCETS SHALL DELIVER NOT MORE THAN 0.2 GALLONS
#97 S.S. SCRAP SINK PER WATER USE. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL
W.C. WATER CLOSET 1 HB HOSE BIBB 2.5 2.5
CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COST
#99 DISHWASHER
17. FAUCETS FOR KITCHEN SINKS SHALL BE EQUIPPED WITH AERATORS OF ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING L. LAVATORY 2 EC EVAPORATIVE COOLER 2.5 5
#102 S.S.CLEAN DISH TABLE AND SHALL BE DESIGNED AND MANUFACTURED SO THEY WILL NOT CODES, THE PLANS AND SPECIFICATION NOT WITHSTANDING. THE
U. URINAL TOTAL WSFU 116.5
EXCEED A WATER FLOW RATE OF 1.8 GALLONS PER MINUTE. CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY
6 WC WATER CLOSEST 3" - 4 20 APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN (N) NEW TOTAL GPM 74
1 UR URINAL 2" - 2 4 I\NTENT.
5 LAV LAVATORY 1-1/2" - 1 5 ADA COMPLIANCE NOTES PLUMBING FIXTURE CONNECTION SCHEDULE
4 FD 2" FLOOR DRAIN (EMERGENCY) 2" - 0 0 1. INSULATED EXPOSED HOT WATER AND WASTE PIPING WITH NEATLY
PRE-FORMED INSULATION COVERS BY McGUIRE "PROWRAP", OR SEISMIC BRACING SYM. DESCRIPTION MFR MODEL W TRAP V CW HW REMARKS/ SPECIFICATIONS
1 WS WATER SOFTENER - 2" FS 4 4 EQUAL. WATER
ALL SUSPENDED UTILITY SYSTEMS WHICH INCLUDE: MECHANICAL AND WC-1 AMERICAN 2234.001 FLOOR MOUNT AMERICAN STANDARD MODEL #
CLOSET 4" INT. 2" 1 1/4" -
TOTAL DFU (SANITARY SEWER) 58 PLUMBING EQUIPMENT AND ASSOCIATED CONDUIT, DUCTWORK, AND STANDARD OR EQ. 2234.001, "MADERA" WITH VITREOUS CHINA. 1.28 GPF,
2. FIXTURE MOUNTING HEIGHTS FOR THE PHYSICALLY DISABLED SHALL PIPING ARE REQUIRED TO HAVE SEISMIC RESTRAINT ATTACHMENTS ELONGATED
CONFORM TO THE AMERICANS WITH DISABILITIES ACT AND ALL DESIGNED TO RESIST THE TOTAL DESIGNED SEISMIC FORCES SIPHON JET BOWL, 11/2" TOP SPUD. SLOAN ROYAL
OTHER AUTHORITIES HAVING JURISDICTION. PRESCRIBED IN ASCE 7-05, CHAPTER 13. PROVIDE DOCUMENTATION MODEL OPTIMA MODEL #111.28 ES-S TMP
GREASE INTERCEPTOR SIZE DETERMINATION SUBSTANTIATING COMPLIANCE WITH 2014 LOS ANGELES COUNTY TRANSFORMER
BUILDING CODE/2013 CBC, ASCE 7-05, CHAPTER 13 TO INCLUDE SEISMIC 120V/I DVDC MODEL#EL-154 FLUSH VALVE.
DIRECT INDIRECT DFU
QTY TAG DESCRIPTION DFU EA. ENERGY NOTES RESTRAINT ASSEMBLY DETAILS. ANCHORAGE TO OVERHEAD
DRAIN DRAIN TOTAL
STRUCTURE WITH SUPPORTING ENGINEERING STAMPED BY A LICENSED WATER
1 #03 MOP SINK 2" - 3 3 1. DOMESTIC WATER HEATERS SHALL BE CERTIFIED AND LISTED BY CIVIL OR STRUCTURAL ENGINEER IS REQUIRED AT TIME OF INSPECTION. WC-2 AMERICAN 3461.128
CLOSET 4" INT. 2" 1 1/4" - FLOOR MOUNT AMERICAN STANDARD MODEL
THE CALIFORNIA ENERGY COMMISSION. EXCEPTION: NON-STORAGE STANDARD OR EQ.
1 #14A CARBONATOR - 2" FS 4 4 (ACCESSIBLE) #3461.128, "MADERA" WITH VITREOUS CHINA, 1.28
TYPE ELECTRIC WATER HEATERS. GPF, ELONGATED SIPHON JET BOWL, 11/2" TOP SPUD,
#164 ICE BIN/SODA DISPENSER SLOAN ROYAL MODEL OPTIMA MODEL #111.28 ES-S 1RUPV5HVWDXUDQWV//&
2. SERVICE WATER HEATING SYSTEM SHALL BE EQUIPPED WITH PIPE MATERIAL SCHEDULE TMP TRANSFORMER 120V/10 VDC MODEL#EL-154
#165 WATER FILLER /DNHZRRG%OYG
AUTOMATIC TEMPERATURE CONTROLS CAPABLE OF ADJUSTMENT FLUSH VALVE.
FROM THE LOWEST TO THE HIGHEST ACCEPTABLE TEMPERATURE SERVICE PIPE FITTINGS LOCATIONS %HOOIORZHU&$
1 #14A CARBONATOR - 2" FS 4 4
SETTING FOR THE INTENDED USE AS LISTED IN TABLE 3, CHAPTER 50
#179 ICE BIN/SODA DISPENSER OF THE ASHRAE HANDBOOK, HVAC SYSTEMS & APPLICATIONS APPROVED APPROVED ABOVE GRADE 6WDPS
WASTE AND VENT UR URINAL AMERICAN WHlTE VITREOUS CHINA, 0.125 GPF, WALL MOUNT, 1
VOLUME. PVC PIPE PVC PIPE BELOW GRADE 6590.001 2" INT. 2" 1 1/4" -
2 #51 HAND SINK 1-1/2" - 1 2 (ACCESSIBLE) STANDARD 1/4"TOP INLET SPUD. SLOAN ROYAL. MODEL OPTIMA
HOT AND COPPER TYPE "L" WROUGHT MODEL#186-0.125 ESS
1 #52 S.S. WORKTABLE W/SINK - 2" FS 4 4 3. LAVATORY FAUCETS AND SINK(NOT INCLUDING SERVICE SINK ABOVE
COLD WATER HARD DRAWN COPPER TMO, ELECTRICAL POWERED SENSOR FLUSH VALVE
GRADE
FAUCET) SHALL MEET THE FLOW REQUIREMENTS OUTLINED IN THE WITH VACUUM BREAKER. PR0VIDE EL-154
1 #62 S.S. PREP TABLE W/2-COMP SINK - 2" FS 4 4
APPLIANCE EFFICIENCY STANDARDS. WROUGHT TRANSFORMER
HOT AND COPPER TYPE
1 #67 S.S POT SINK ASSEMBLY 2-BOWLS - 3" FS 6 6 SOLDIER JOINT BELOW GRADE 120V/10VODC FLUSH VALVE.
COLD WATER "K" HARD DRAWN
4. LAVATORIES IN PUBLIC RESTROOMS SHALL HAVE CONTROLS TO FITTINGS
S.S POT SINK ASSEMBLY 1-BOWL 1-1/2" - 3 3 MEET THE FOLLOWING: CONDENSATE WROUGHT
COPPER TYPE "M" ABOVE L LAVATORY AMERICAN SEE 1 1/2" 1 1/2" 1 1/2" 1/2" 1/2" AMERICAN STANDARD MODEL SELECTRONIC
DRAIN; SOLDIER JOINT
2 #85 TROUGH DRAIN 3" - 6 12 GRADE (ACCESSIBLE) STANDARD ARCH INNSBROOK ELECTRIC FAUCET, TRAP, STOPS, &
4.1. MAXIMUM FLOW RATE 0.5 GPM. INDIRECT WASTE HARD DRAWN FITTINGS
SUPPLIES. AC POWERED 6057.205 SENSOR FAUCET
3 #104 TROUGH DRAIN 3" - 6 18 SCHEDULE 40 MALLEABLE ABOVE
GAS WITH THERMAL MIXING VALVE MODEL #605XTMV. 0.5
4.2. FLOW RATE FOR SELF CLOSING VALVES 0.2 GALLON/CYCLE. BLACK STEEL IRON GRADE GPM.
1 #112A S.S. REFRIGERATED BASE - 2" FS 4 4
CAST IRON CAST IRON ,VVXH)RU
1 #112B S.S. REFRIGERATED BASE - 2" FS 4 4 4.3. MAXIMUM OUTLET TEMPERATURE: 110°F. ABOVE GRADE
STORM DRAIN HUBLESS HUBLESS BELOW GRADE L-1 LAVATORY AMERICAN 0356.28 PERMIT
#116 COIL WRAPPED FOR EGG STATION 1 1/2" 1 1/2" 1 1/2" 1/2" 1/2" AMERICAN STANDARD MODEL SELECTRONIC
(ACCESSIBLE) STANDARD OR EQ INNSBROOK ELECTRIC FAUCET, TRAP, STOPS, &
ALTERNATE MATERIALS MAY BE USED IF THEY ARE ACCEPTABLE TO ALL ,VVXH'DWH
1 #127 S.S. COUNTER W/UTILITY SINK - 2" FS 4 4 AUTHORITIES HAVING JURISDICTION. ALTERNATE MATERIALS MUST BE SUPPLIES. AC POWERED 6057.205 SENSOR FAUCET
WITH THERMAL MIXING VALVE MODEL #605XTMV. 0.5 09-18-17
#129 DIPPERWELL ACCEPTABLE AND PROVIDE A COST SAVINGS TO THE OWNER
GPM. 5HYLVLRQV
#133 DIPPERWELL W/FAUCET NO. REASON DATE
PLUMBING EQUIPMENT SCHEDULE 2"
#136 DROP-IN HOT FOOD WELL SYMBOL DESCRIPTION SPECIFICATION WCO WALL CLEANOUT J.R. SMITH 4553 - - - - WITH STAINLESS STEEL ACCESS
3"
TOILET ROOMS BOX OR EQUAL.
1 #128 HAND SINK 1-1/2" - 1 1 4"
CP-1 CIRCULATING PUMP BELL & GOSSETT MODEL NBF-12F/ LW, INLINE, 1/20 HP, 1 PHASE - 115V; 3.0 GPM @ 10.5 FEET
#129 DIPPERWELL - 2" FS 4 4 OF HEAD. 2"
FCO FLOOR CLEANOUT J.R. SMITH 4053 WITH NONSKID NICKEL BRONZE TOP OR EQUAL
3" - - - -
#133 DIPPERWELL W/FAUCET WH-1 HOT WATER HEATER LAARS NEOTHERM MODEL NTV-399 WATER HEATER, NATURAL GAS. INPUT 399,000 WITH 96% FIN. ROOMS
EFFICIENCY. PROVIDE CONDENSATE NEUTRALIZER KIT. PROVIDE STAINLESS STEEL VENTING WITH A 4"
#135 COIL WRAPPED PAN FLUSH MOUNT WALL TERMINAL, SEE INSTALLATION INSTRUCTIONS FOR APPROVED 2" WITH PRIME COATED STEEL COVER OR EQUAL
MANUFACTURERS PROVIDE COMBUSTION AIR INTAKE TO WALL INTAKE. ELECTRICAL 120V-1 PHASE; WCO WALL CLEANOUT J.R. SMITH 4553 - - - -
1 #156 FOUNTAINETTE - 2" FS 4 4 3"
8 AMPS. FIN ROOMS
1 #186 DIPPERWELL W/FAUCET - 2" FS 4 4 4"
ET-1 RUN 1/2" TO FLOOR DRAIN-MOUNT IN WALL BEHIND
#190 SOUP WARMER EXPANSION TANK WILKINS MODEL WXTP-50V
PR-500 - - - 1/2" - ACCESS PANEL. USE DISTRIBUTION UNIT DU-2 OF 2
TP TRAP PRIMER PPP INC.
PRIME-RITE UNIT FEED.
#191 S.S. REFRIGERATED BASE
ST-1 STORAGE TANK LAARS 175 GALLON, JACKETED VERTICAL STORAGE TANK.
#195 S.S.COLD PAN 2" 2" WITH CAST ALUMINUM DOME STRAINER AND TRAP
PRESSURE REDUCING FS FLOOR SINK ZURN Z1901-K-LD - - PRIMER CONNECTION. GRATE AS REQUIRED
1 #189 HAND SINK 1-1/2" - 1 1 PRV-1 2 1 /2" WILKINS MODEL 500XLYSBR 3" 3" 2"
VALVE 2-23
4" 4"
12 FD 2" FLOOR DRAIN 2" - 4 48
BFP-1 BACK FLOW PREVENTER 2 1 /2" WILKINS MODEL # 375A WITH NICKEL BRONZE TOP. & TRAP PRIMER
1 FS 2" FLOOR SINK 2" - 4 4 FD FLOOR DRAIN ZURN ZN415B-P 2" 2" 2" - - CONNECTION. CLEAN & POLISH STRAINER TOP AFTER
INSTALLATION
TOTAL DFU (GREASE WASTE) 138 GI-1 GREASE INTERCEPTOR 1500 GREASE INTERCEPTOR BY JENSEN PRECAST. SEE DETAIL
PRINCIPAL IN CHARGE:
HOSE BIBB JT
HB EXTERIOR ACORN 8120 CR - - - 3/4" - WITH VACUUM BREAKER
PROJECT MANAGER:
INSULATION TABLE JT
RHB ROOF HOSE BIBB WOODFORD SRH-MS - - - 3/4" - WITH VACUUM BREAKER
DRAWN BY:
NOMINAL PIPE SIZE (IN.) SHEET INDEX DL, CQ
FLUID CONDUCTIVITY INSULATING WHA-1 WATER HAMMER J.R. SMITH 5005 - - - 1/2" - WITH ACCESS PANEL 3URMHFW$GGUHVV
RUNOUTS 1 AND 5 AND PLUMBING FIXTURE SCHEDULE, NOTES
TEMP. RANGE (BTU-INCH MEAN 1.25-2 2.5-4 ARRESTOR P1.0
UP TO 2 LESS LARGER SYMBOLS & ABBREVIATION NORM'S RESTAURANT -
RANGE PER HOUR PER RATING TEMP
(F) SQFT PER F) (F) INSULATION THICKNESS RD ROOF DRAIN ZURN Z121 - - - - - FOR 4" STORM PIPE CONNECTION P2.0 PLUMBING COLD & HOT WATER FLOOR PLAN INGLEWOOD, CA
REQUIRED (IN.) VERIFY W/ ARCHITECT W IMPERIAL HWY
- - - - - FOR 4" STORM PIPE CONNECTION P2.1 PLUMBING WASTE & VENT FLOOR PLAN INGLEWOOD, CA 90303
SERVICE WATER HEATING SYSTEMS (RECIRCULATING SECTIONS, ALL IN PIPING IN ELECTRIC OD OVER FLOW ZURN Z121-89
TRACE TAPE SYSTEMS, AND THE FIRST 8 FEET OF PIPING FROM THE STORAGE TANK FOR NON DRAIN VERIFY W/ ARCHITECT (EXACT ADDRESS TBD BY
RECIRCULATING SYSTEMS. P2.2 PLUMBING GAS PLAN CITY)
DSN DOWNSPOUT ZURN Z199 - - - - - FOR 4" STORM DISCHARGE,
NOZZLE VERIFY W/ ARCHITECT P2.3 PLUMBING ROOF PLAN 3URMHFW1XPEHU
ABOVE 105 0.24 - 0.28 100 0.5 1.0 1.0 1.5 1.5 PLUMBING WATER RISER ISOMETRIC 78-001-17
JS JANITOR'S SINK SELECTION BY OTHER SELECTION 3" 3" 2" 3/4" 3/4" WITH T&S B-0665-BSTR COMMERCIAL FAUCET, WITH P3.0
DIAGRAM
BY OTHER TOP SUPPORT WALL BRACE. FAUCET, STOPS, 6KHHW7LWOH
SUPPLIES, AND TRAP WITH VACUUM BREAKER PLUMBING SEWER RISER ISOMETRIC
P3.1
DIAGRAM PLUMBING FIXTURE
ALTERNATE NOTES ALTERNATE STAINLESS STEEL TROUGH DRAINS WILL SCHEDULE, NOTES
TD-1 SS TROUGH ADVANCE FTG-5418 3" 3" 2" - - P3.2 PLUMBING GAS RISER ISOMETRIC DIAGRAM
1. PROVIDE ALTERNATE COST TO ELIMINATE TROUGH DRAINS IN DRAIN TABCO BE ACCEPTED IF DEEMED EQUAL BY SYMBOLS &
MEN'S ROOM AND REPLACE WITH STANDARD FLOOR DRAINS. OWNER/ENGINEER ABBREVIATION
ALTERNATE STAINLESS STEEL TROUGH DRAINS WILL P4.0 PLUMBING KITCHEN EQUIPMENT SCHEDULE
TD-2 SS TROUGH ADVANCE FTG-7212 3" 3" 2" - -
DRAIN TABCO BE ACCEPTED IF DEEMED EQUAL BY
2. PROVIDE ALTERNATE COST TO SWITCH SPECIFIED WATER HEATING P5.0 PLUMBING DETAILS
OWNER/ENGINEER
SYSTEM WITH STANDARD TANK TYPE WATER HEATING SYSTEM. ALTERNATE STAINLESS STEEL TROUGH DRAINS WILL
TD-3 SS TROUGH ADVANCE FTG-3612 2" 2" 2" - -
TANK TYPE WATER HEATING SYSTEM MUST MATCH CAPACITIES OF BE ACCEPTED IF DEEMED EQUAL BY P5.1 PLUMBING DETAILS
DRAIN TABCO 6KHHW1XPEHU
SPECIFIED SYSTEM AND FIT IN MECHANICAL ROOM AND BE OWNER/ENGINEER
COORDINATED WITH ALL OTHER EQUIPMENT IN ROOM. TD-4 SS TROUGH ADVANCE FTG-2412 2" 2" 2" - - ALTERNATE STAINLESS STEEL TROUGH DRAINS WILL P6.0 PLUMBING NOTES AND SPECIFICATIONS
DRAIN TABCO BE ACCEPTED IF DEEMED EQUAL BY P1.0
OWNER/ENGINEER

12/4/2017 2:25:00 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
.1 2 2.4 3 4 5 6 7 8
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
1854 1848 1848 1848 1848 1848 1854 1836 1836 1854
5T 5T 5T 5T 5T 5T 5T 5T 5T 5T
(QJLQHHULQJ&RQVXOWDQW
1842 1842
5T 5T
52
51 TRAP PRIMER
1848 1836 1848 1848 1836 1836 3/4" 1854
1836 UP TO EVAPORATIVE 67
5T 5T 5T 5T 5T 5T 5T 5T
ISOLATION VALVE COOLER
(TYPICAL) 62 67 TRAP PRIMER 2 1/2" CWS
D D
WC-2 ) 8 8
2436 $7.-
* * 5T
#+4«+0
33 %1
TRAP PRIMER * CONTINUED
ON SITE
WC-2 TRAP PRIMER
PLAN; SEE
FW CIVIL
CWS 6" DRAWINGS
HWS
HWR
HWR 140 3URMHFW2ZQHU
CONTROL
ELECTRICAL

/ 3/4" UP TO - -
WC-1 ISOLATION VALVE 1860
51 ROOF HB 5T 9&
(TYPICAL) 3 (H) - -
56#%-'&
105
ANSUL

97A 32 9*
-
UR TRAP PRIMER
WC-1 1842
5T
86 84
3/4" UP TO
LIMIT 156 1848
L L EVAPORATIVE SWITCH 5T MIXING VALVE STATION;

5
TRAP PRIMER 99
COOLER

FW
TRAP PRIMER SEE DETAIL
.
L L ) 1848
- - - - - - 5T
112 8 - 1860 1860
* * 8 5T 5T
163 1848
5T
L-1
163 1848 1872
5T 5T

WC-2
166
181
C 162
C
128
179
14A
TRAP PRIMER (F)
129 164
136A
129
14A 165
(2)
POS
POS 183 127 167
133 133
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
)
. 6WDPS
189 186
TRAP PRIMER
B.3
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
B B
A.8
A.2
A A
0.9
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING COLD & HOT
WATER FLOOR PLAN
3/80%,1*&2/' +27:$7(5)/2253/$1
   
0.1 1 2 2.4 3 4 5 6 7 8 6KHHW1XPEHU
P2.0

12/4/2017 2:25:06 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
.1 2 2.4 3 4 5 6 7 8
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
CONTINUED ON SITE PLAN,
SEE CIVIL DRAWINGS.
INVERT ELEVATION: -5'-4" 1854 1848 1848 1848 1848 1848 1854 1836 1836 1854
5T 5T 5T 5T 5T 5T 5T 5T 5T 5T
(QJLQHHULQJ&RQVXOWDQW
1842 1842
5T 1" CONDENSATE DRAIN 5T
TO FS
3/4" CONDENSATE 4" UP TO RD
DRAIN TO FS 4" UP TO ORD
1848 1836 1848 1848 1836 1836 1836 1854
5T 5T 1 1/2"1 1/2" 5T 5T 5T 5T 1 1/2" 5T 5T 67
WCO 1 1/2" 1 1/2" 1 1/2" 1 1/2"
4" UP TO RD 1 1/2"
D D
2"

) 8 8
2"

3" 3" FCO


3"

WC-2 4" UP TO ORD 42 2436 $7.-


2"

* * FS 62 5T
#+4«+0 2" %1
*
2"

FS
3"

FS
2"

2"

3/4"
2"

2"

2"

FS
3"

4" VTR FS FS

4"
3"
1 1/2"

WC-2 TD-2 TD-2 TD-2 FCO


2"

2"

JS 51 4" 4" 2"


104 104 3/4" CONDENSATE 104
4"

1"
CO DRAIN DOWN 4" 1" 4"
2"
3"
CO 4" DSN

2"
4" 2" 1 1/2" 2" 3" 52
4" DSN 2" TD-1 FD 4"
36 3" VTR
3"

FD 3" 2" UR FCO FD FD FD FD


TD-4 3URMHFW2ZQHU
2" 3" 33
1 1/2"

FD

3"
2" 3" 2" 2" 2"
2"

WC-1 2" 35
3" GW
2"

2"

/
32
51 FCO 45 TD-1 85 85 TD-1
- -
1860
2"

5T FCO 9&
4" 4" SAN (H) - -
56#%-'&
3"
2"

WC-1 FCO

3"
FS
2"

ANSUL

2" 96 9*

2"
2"
3"

1 1/2"

2"
TD-4 3/4" 97

1 1/2"
-
2" FD
2"

FD 99
UR 2" 1842 2"
3" 102 1 1/2" 5T

2"
3/4" CONDENSATE 3" VTR

2"

3/4"
2" 3/4"

3"
4" GW

1 1/2"
FS

2"
L DRAIN UP LIMIT 2" 1848

1 1/2"
L 3/4" CONDENSATE

1 1/2"
1 1/2"
1 1/2"
1 1/2"
SWITCH

1 1/2"
4" 5T
2"

2"

5
2"
DRAIN UP 3/4" CONDENSATE
1 1/2" 2" 2" 2"
DRAIN UP

2"
FCO .

1 1/2"
4" 4" 4" 4"
L L ) 1848
CO - - - - - - 156 5T
1 1/2" 1860 1860

4"
* 8 * 8 - 5T 5T

2"
1 1/2"
FS

1 1/2"
1 1/2" 1 1/2" 2"

2"
1848

1 1/2" V
2"
WC-2 5T

3"
4"

1 1/2"

2"
3"
4" DSN 4"

2"
2"
2"

2"
4" L-1

1 1/2"
FS FS CO 4"
CO 112A 5T 5T
FD TD-3 1 1/2" CO 4" DSN

1 1/2"
FD 112B
2" V 2" 4"
116
C FD FD C
FS FS 127 133
3/4" CONDENSATE 14A 129 136 1 1/2"
DRAIN UP FS

4"
179 129

3" SAN
FS 2"
4" UP TO ORD 2" (F) 133 4" UP TO ORD
165

4"
135

2"
164 4" UP TO RD
4" UP 1 1/2"
14A

1 1/2"
TO RD 4" GW
(2)
POS FCO

1 1/2"
POS 128 "
4" 4" 1 1/2 4" SAN 4" SAN
FCO

3"
FD FCO /2"
11 /2"
2" 2"

3"
FCO FD 11 1RUPV5HVWDXUDQWV//&
FCO /DNHZRRG%OYG
3" %HOOIORZHU&$
FS 2"
186 191 )
190 195 . 6WDPS

2"
189
B.3
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
B B
A.8
A.2
A A
0.9
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING WASTE &
VENT FLOOR PLAN
:$67( 9(17)/2253/$1
   
0.1 1 2 2.4 3 4 5 6 7 8 6KHHW1XPEHU
P2.1

12/4/2017 2:25:14 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
.1 2 2.4 3 4 5 6 7 8
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
2" GAS PIPING UP THRU Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
ROOF, CONTINUED ON P2.3 original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
NEW GAS METER WITH SHUT-OFF Copyright Protected 2016.
VALVES, PRESSURE REGULATOR BY
GAS COMPANY. 2,607 CFH @ 7" W.C.
(QJLQHHULQJ&RQVXOWDQW
INCOMING GAS SERVICE BY
GAS COMPANY, CONTINUED
ON SITE PLAN
D D
4"

2"
AUTOMATIC GAS VALVE;
958 CFH; FURNISHED BY 2"
KEC, INSTALLED BY P.C.
3"

3URMHFW2ZQHU
2 1/2" 3" 3" WATER HEATER WH-1
399 CFH
3/4"
2"

1"

3/4"
1"

3/4"
1 1/4"

31
2" 50 CFH
80 86 84 83
2@60 CFH 115 CFH 115 CFH 200 CFH

2 1/2"
AUTOMATIC GAS VALVE;
550 CFH; FURNISHED BY
KEC, INSTALLED BY P.C.
2 1/2"

3/4"
1"

1"
1"

3/4"

1 1/4"
1 1/4"
1"
111 115 114 122 120 118 124
220 CFH 113 40 CFH 120 CFH 120 CFH 180 CFH 48 CFH 110 CFH
120 CFH
C C
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
6WDPS
B.3
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
B B
A.8
A.2
A A
0.9
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
CONSTRUCTION NOTES 3URMHFW$GGUHVV
INSTALLER MUST VERIFY THE SIZE OF THE GAS
NORM'S RESTAURANT -
CONNECTOR TO MATCH EQUIPMENT SUPPLY INGLEWOOD, CA
INLET AND EQUIPMENT MANUFACTURER'S W IMPERIAL HWY
RECOMMENDED GAS VALVES/CONNECTOR KITS INGLEWOOD, CA 90303
OR SYSTEM. SEE GAS RISER DIAGRAM.
(EXACT ADDRESS TBD BY
ALL CONNECTION TO GAS UTILIZATION CITY)
APPLIANCES SHALL COMPLY WITH CALIFORNIA
MECHANICAL CODE (CMC) CHAPTER 13. 3URMHFW1XPEHU
VERlFY ALL ROUGH-IN CONNECTIONS WITH 78-001-17
KITCHEN EQUIPMENT PLAN.
6KHHW7LWOH
THE ENTIRE GAS PIPING SYSTEM AND EQUIPMENT
SHALL BE FURNISHED WITH SEISMIC SHUT-OFF PLUMBING GAS PLAN
AND MANUAL SHUT-OFF DEVICES/CONTROLS AND
COLOR CODED OR IDENTIFIED AS REQUIRED.
3/80%,1**$63/$1
   
0.1 1 2 2.4 3 4 5 6 7 8 6KHHW1XPEHU
P2.2

12/4/2017 2:25:18 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
.1 2 2.4 3 4 5 6 7 8
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
(QJLQHHULQJ&RQVXOWDQW
2" GAS PIPING THRU
GAS PIPING ROUTED ON ROOF, ROOF, SEE DETAIL
SEE GAS SUPPORT DETAIL
D D
GAS PIPING ROUTED ON ROOF,
SEE GAS SUPPORT DETAIL
4" RD
2"

4" ORD 3/4" CONDENSATE 4" ORD MAU-1


4" PLUMBING VENT DRAIN DOWN 4" RD
THRU ROOF; SEE RHB

1 1/4"
DETAIL 3/4" CONDENSATE
DRAIN DOWN 3URMHFW2ZQHU

1 1/2"
RTU-2
130 CFH RTU-3 2" 2"
GAS CONNECTION TO
130 CFH
GAS PIPING ROUTED ON ROOF, HVAC UNIT, SEE DETAIL
1 1/4"

SEE GAS SUPPORT DETAIL


GAS CONNECTION TO 3/4" CONDENSATE
HVAC UNIT, SEE DETAIL 3" PLUMBING VENT DRAIN DOWN

1 1/4"
1 1/4"

THRU ROOF; SEE GAS CONNECTION TO GAS CONNECTION


3/4"

DETAIL HVAC UNIT, SEE DETAIL TO HVAC UNIT, SEE


3/4" CONDENSATE DRAIN DETAIL
DOWN 3" PLUMBING VENT
RTU-1 THRU ROOF; SEE RTU-5
130 CFH DETAIL 130 CFH
RTU-4
130 CFH
MAU-2
GAS CONNECTION TO
HVAC UNIT, SEE DETAIL
C C
3/4" CONDENSATE DRAIN
DOWN
4" ORD
4" RD
4" RD
4" ORD
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
6WDPS
B.3
,VVXH)RU
PERMIT
,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
B B
A.8
A.2
A A
0.9
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
CONSTRUCTION NOTES DRAWN BY:
DL, CQ
INSTALLER MUST VERIFY THE SIZE OF THE GAS 3URMHFW$GGUHVV
CONNECTOR TO MATCH EQUIPMENT SUPPLY
INLET AND EQUIPMENT MANUFACTURER'S NORM'S RESTAURANT -
RECOMMENDED GAS VALVES/CONNECTOR KITS INGLEWOOD, CA
OR SYSTEM. SEE GAS RISER DIAGRAM. W IMPERIAL HWY
ALL CONNECTION TO GAS UTILIZATION INGLEWOOD, CA 90303
APPLIANCES SHALL COMPLY WITH CALIFORNIA (EXACT ADDRESS TBD BY
MECHANICAL CODE (CMC) CHAPTER 13. CITY)
VERlFY ALL ROUGH-IN CONNECTIONS WITH
KITCHEN EQUIPMENT PLAN. 3URMHFW1XPEHU
THE ENTIRE GAS PIPING SYSTEM AND EQUIPMENT 78-001-17
SHALL BE FURNISHED WITH SEISMIC SHUT-OFF
AND MANUAL SHUT-OFF DEVICES/CONTROLS AND 6KHHW7LWOH
COLOR CODED OR IDENTIFIED AS REQUIRED. PLUMBING ROOF PLAN
3/80%,1*522)3/$1
   
0.1 1 2 2.4 3 4 5 6 7 8 6KHHW1XPEHU
P2.3

12/4/2017 2:25:20 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
2.0 WSFU û‚¹¼ċ™‚ċĖû™‹&Ђí
17.0 WSFU
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
$UFKLWHFW
2.0 WSFU
9.0 WSFU *(2))5(<%/,0
$,$1&$5%/(('$3
MAU-2
WC-2 Plans, maps, specifications, studies, and reports not
5.0 WSFU containing a red ink seal imprint accompanied by an
original
WC-1 WC-2 signature by the licensed professional may have been
1 1/4" 1 fraudulently altered and shall not be considered an original
1/2 /2" copy. All information should be disregarded unless verified
" by the professional whose signature appears above.
1" Copyright Protected 2016.
WC-1 HW
2" 2" S
/4" 2"
11 CW
S
L 41.5 WSFU 14 WSFU
38.5 WSFU (QJLQHHULQJ&RQVXOWDQW
UR 2" 4 WSFU 45.5 WSFU
L
W
L "F WR 48.5 WSFU
3/4 "H
UR S 3/4
1/2 CW 12.5 WSFU 21 HB
L " 1" /2"
/4" 1.0 WSFU
11 11 WSFU
6.0 WSFU
1"
10 WSFU

1/2"
3 WSFU 2

1/2"
1

3/4"
/2"
4 WSFU W /2" CW
" F 1 1/2" 18 WSFU 3/4 S
3/4 "H
1/2 WR
"
" 1/2
3/4 " 1 WSFU
3/4 " 3/4 51.0 WSFU
" 3/4 1/2 "F

3/4"
3/4"
" 9 WSFU 1" W
HW
S
1/2
" 2 WSFU 51
2 WSFU 1/2 59.0 WSFU
WC-2 "
3URMHFW2ZQHU
3 4 WSFU
1/2 1"
1/2 " HW
" S1
40 5 WSFU
105 8 WSFU 1" /2"
181 1 11
40 /2"
179 L-1 S1 "
1/2 HW 1/2
" 1"
" 1
14A 3/4
1/4
"
1 WSFU "
1/2
112
21 WSFU "
1/2 " "
183 5 WSFU
1/2 1/2
8 WSFU
9 WSFU 63 WSFU

1/2"
11
1 WSFU W 22 WSFU

3/4"
1/2"
/2"
"F
2 WSFU " 3/4 13 WSFU
1/2 60 WSFU

1/2"
2 WSFU "
3/4 1/2 66 WSFU MAU-1
"H 1/2
WS " 25 WSFU
28 WSFU
128
129 1/2 97A
" 1 WSFU 33
136A 51 2"
99
" " "
1/2 1/2 52 1/2 "
133 " 1/2
1/2

1/2"
"
1/2 156 1/2
1/2 " 1/2
"
"H 133 3 WSFU "
WS " 1/2
129

3/
1/2" 127 1/2

4"
3/
69 WSFU 72 WSFU

4"
1/2
"C
WS 1/2 31 WSFU
"

1/2"
1

1/2"
34 WSFU 2 1 1/4
"
2" /2" C FW
3 WSFU HW W
S S
3/4 1RUPV5HVWDXUDQWV//&
189 163 " HW /DNHZRRG%OYG
2 WSFU 62 R

1/2"
163 " %HOOIORZHU&$
1/2 /2" 84.5 WSFU
162 166 1
"
86 40 WSFU 6WDPS

1/2"
1/2 "
1/2
14A

1/2"
164
74.5 WSFU

1/2"
165 37 WSFU

1/2"
84
186

1/2"
" 77.5 WSFU 1/2
" 1/2
1/2 "
167 40 WSFU
" WATER SOFTENER.
1/2 67 COORDINATE WITH VENDOR.
"
1/2
67
WATER FILTER;
COORDINATE WITH VENDOR. ,VVXH)RU
PERMIT
,VVXH'DWH
32
09-18-17
5HYLVLRQV
NO. REASON DATE
WATER
HEATER.
SEE
SCHEDULE
2 1/2" INCOMING
DOMESTIC WATER SUPPLY
MIXING VALVE STATION.
SEE DETAIL
6" FIRE SPRINKLER
WATER SERVICE
:$7(55,6(5,620(75,&',$*5$0

PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING WATER
RISER ISOMETRIC
DIAGRAM
6KHHW1XPEHU
P3.0

12/4/2017 2:25:22 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
4" VTR $5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW

4"
$UFKLWHFW
3"
*(2))5(<%/,0
$,$1&$5%/(('$3
Plans, maps, specifications, studies, and reports not
3" containing a red ink seal imprint accompanied by an
original
/2" signature by the licensed professional may have been
11 fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified

3"

2"
by the professional whose signature appears above.
Copyright Protected 2016.
WCO

2"
WC-2

2"
(QJLQHHULQJ&RQVXOWDQW

2"
2"
2"

2"

1 1/2"
FD
WC-1 WC-2

1 1/2"
L WC-1 3"

3"
L UR

3"
TD-4

2"
2"
8 DFU
UR

3"

2"
11
/2"
L /2"
11

2"
L

3"
2 DFU

2"
42 2" 3" VTR
2" FS

2"
TD-4
/2"
11 3URMHFW2ZQHU
2"
4 DFU
20 DFU

2"
FD
/2"

1 1/2"
11 /2"
11
FCO

1 1/2"
WC-2

1 1/2"
2"
4" 03

1 1/2"
2"

4"
4 DFU 51

1 1/2"
JS
24 DFU 2"
2"

1 1/2"
L-1 FCO 3" VTR

1 1/2"
2"
FD

2"

4"
3"
0 DFU 4 DFU FCO 3"

2"
3"
FS
2"

1 1/2"
3"

1 1/2"
1 DFU TD-2 2"
104

2"
4" 104

1 1/2"
S AN TD-2 3"

1 1/2"
4"

2"
1 1/2"
3"

1 1/2"
14A 3" 12 DFU 3" 10 DFU
179 104

1 1/2"
112A FS 2" FD V
TD-2 2"

2"
16 DFU

1 1/2"
4 DFU

1 1/2"
2" 8 DFU

1 1/2"
4 DFU

2"
FD 20 DFU
28 DFU FCO 4 DFU 3"

1 1/2"
2" 2"
GW /2" FCO

3"
FD 11

3"
3" 112B

1 1/2"

1 1/2"
128 33

1 1/2"
/2" 116 4 DFU

1 1/2"
3"
11 35

3"
6 DFU 45

1 1/2"
2" 2" 33 DFU 25 DFU 36 51

1 1/2"
FS 2" FS

2"
4 DFU FCO

2"
2" 2"
FS

3"
4 DFU FS TD-1

1 1/2"
3" 3" 2" 1RUPV5HVWDXUDQWV//&
FD 129 4 DFU
4 DFU 2" /DNHZRRG%OYG
133 8 DFU 22 DFU FS
1 DFU 135 FD 4" %HOOIORZHU&$
2" 4" 4 DFU 52 11
127 2" 4 DFU /2"
156

1 1/2"
4" 2" 6WDPS
133 GW 6 DFU FD /2"

1 1/2"
4" 129 45 DFU 11
FS 1
SA
N FS 1/2
29 DFU 136 10 DFU "
FS 8 DFU FCO
3"
3" 4 DFU

1 1/2"
FCO

1 1/2"
FD 14 DFU 2"
5 DFU 2"
TD-3 73 DFU

3"
51 DFU

1 1/2"
195 2" 4" FD

1 1/2"
189 FD FS
186 TD-1

1 1/2"
42 DFU 4" 3"
190
165 2" 62
191 2" 85 2"
164

1 1/2"
2"
1 1/2"
1 1/2"
3" 14A
2" 4 DFU N 37 DFU 3"
2" 22 DFU SA 85 DFU
4" 85
1 DFU FS ,VVXH)RU
FCO TD-1 2"
2" GW 31 DFU
1 1/2 4" 17 DFU PERMIT
2" " FCO 4 DFU
FD
1 1/2"

,VVXH'DWH
21 DFU
1 1/2" 67 09-18-17
27 DFU 2"
4 DFU 1 1/2"
5HYLVLRQV
2" NO. REASON DATE
1 1/2"

13 DFU
1 1/2"

2" GW
127 DFU
13 DFU /2"
11 67
3"
4"
3" 131 DFU GW 2"
GW FD
4" FS
9 DFU FCO
FCO WS

2"
32 3"

4" GW
FS
6 DFU
2"

2"
3 DFU 4 DFU
FD
2"
2"
144 DFU 2" 0 DFU
7 DFU
2"
51 DFU
N
SA
4" PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
151 DFU DL, CQ
3URMHFW$GGUHVV
4"
GW NORM'S RESTAURANT -
INGLEWOOD, CA
4"
SA W IMPERIAL HWY
N
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
58 DFU
3URMHFW1XPEHU
78-001-17
6(:(55,6(5,620(75,&',$*5$0 6KHHW7LWOH
 PLUMBING SEWER
RISER ISOMETRIC
DIAGRAM
6KHHW1XPEHU
P3.1

12/4/2017 2:25:23 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
$5&+,7(&785(
CONSTRUCTION NOTES &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
INSTALLER MUST VERIFY THE SIZE OF THE GAS 7KH3URPHQDGH1RUWK
CONNECTOR TO MATCH EQUIPMENT SUPPLY
INLET AND EQUIPMENT MANUFACTURER'S
/RQJ%HDFK&$
RECOMMENDED GAS VALVES/CONNECTOR KITS
ZZZLGDH[SHULHQFHQHW
OR SYSTEM. SEE GAS RISER DIAGRAM.
$UFKLWHFW
ALL CONNECTION TO GAS UTILIZATION
APPLIANCES SHALL COMPLY WITH CALIFORNIA
MECHANICAL CODE (CMC) CHAPTER 13.
RTU-1
130 CFH *(2))5(<%/,0
VERlFY ALL ROUGH-IN CONNECTIONS WITH
KITCHEN EQUIPMENT PLAN. $,$1&$5%/(('$3
THE ENTIRE GAS PIPING SYSTEM AND EQUIPMENT Plans, maps, specifications, studies, and reports not
SHALL BE FURNISHED WITH SEISMIC SHUT-OFF containing a red ink seal imprint accompanied by an
original
AND MANUAL SHUT-OFF DEVICES/CONTROLS AND signature by the licensed professional may have been
COLOR CODED OR IDENTIFIED AS REQUIRED. fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
/4" Copyright Protected 2016.
11
RTU-2
130 CFH (QJLQHHULQJ&RQVXOWDQW
11
/2"
/4" 3URMHFW2ZQHU
11
RTU-3
130 CFH
2"
111
220 CFH
113
21
/4" /2" 120 CFH
11 115
40 CFH
114
" 120 CFH
1" 3/4 21
/2"
1"
122 AUTOMATIC GAS VALVE
120 CFH
1" 120
180 CFH
118
/4" 48 CFH RTU-4 1RUPV5HVWDXUDQWV//&
11 130 CFH /4" /DNHZRRG%OYG
11
%HOOIORZHU&$
"
3/4 "
3/4 /4" 6WDPS
1" 124 11
110 CFH 80
60 CFH
"
3/4
80

1"
60 CFH
2"
*$65,6(5,620(75,&',$*5$0 2" RTU-5
1" 130 CFH
 2"
86
2"

3"
115 CFH
1"
,VVXH)RU
84
115 CFH 3" PERMIT
4" ,VVXH'DWH
AUTOMATIC GAS VALVE 09-18-17
/4" 2"
11
5HYLVLRQV

2"
83 NO. REASON DATE
200 CFH GAS METER
4"

3/4"
2"
31 ?
50 CFH ?
4"
WH-1
399 CFH
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING GAS RISER
ISOMETRIC DIAGRAM
6KHHW1XPEHU
P3.2

12/4/2017 2:25:24 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
û‚¹¼ċ™‚ċĖû™‹&Ђí
7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
4"
4" $UFKLWHFW
RD

4"
*(2))5(<%/,0

4"
$,$1&$5%/(('$3
ORD
Plans, maps, specifications, studies, and reports not
containing a red ink seal imprint accompanied by an
original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
4" DSN by the professional whose signature appears above.
Copyright Protected 2016.
CO
4" (QJLQHHULQJ&RQVXOWDQW
4"

4"

4"
RD CO
CO
4" DSN
ORD
3URMHFW2ZQHU
ORD
RD
4"
CO CO
4"
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
4" %HOOIORZHU&$
4"
6WDPS
CO
CO
ORD
RD
,VVXH)RU
4" PERMIT
4" ,VVXH'DWH
09-18-17
5HYLVLRQV
NO. REASON DATE
4"

4"
4" DSN

4"

4"
PRINCIPAL IN CHARGE:
JT
PROJECT MANAGER:
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
4" DSN
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING STORM
ISOMETRIC DIAGRAM
672505,6(5,620(75,&',$*5$0

6KHHW1XPEHU
P3.3

12/4/2017 2:25:25 PM
H:\17317\RVT\17317_R16.rvt
PLUMBING/MECHANICAL CONTRACTOR NOTES PLUMBING REQUIREMENT MECHANICAL REQUIREMENTS 'HVLJQ&RQVXOWDQW
MAKE-UP
1 ALL PLUMBING REQUIREMENTS INDICATED IN THESE PLANS ARE FOR K.EC AND/OR OWNER WATER WASTE GAS EXHAUST
SUPPLIED EQUIPMENT AS SHOWN ON EQUIPMENT PLANS AND DESCRIBED IN EQUIPMENT AIR
SCHEDULES. REFER TO THE ARCHITECTURAL PLANS, THE OWNER, ENGINEERING DRAWINGS, AND
THE GENERAL CONTRACTOR FOR ANY ADDITIONAL PLUMBING REQUIREMENTS. ALL PLUMBING WORK
SHALL COMPLY WITH ALL APPLICABLE CODES AND/OR GOVERNMENTAL AGENCIES HAVING
JURISDICTION OVER PROJECT LOCATION.
GAS

SIZE

SIZE
(MBTU)

2
BY P.C.
BY P.C.
BY P.C.

THE KITCHEN EQUIPMENT DRAWINGS INDICATE LOCATION AND TYPE OF ROUGH-IN/STUB ONLY.
G.P.H.

PLUMBING CONTRACTOR TO PROVIDE AND INSTALL ALL SUPPLY, RETURN, WASTE, VENT, AND FUEL
STATIC
STATIC

HOT WATER
HOT WATER
HOT WATER

110 DEGREE
140 DEGREE
180 DEGREE
COLD WATER
QUANTITY OF
QUANTITY OF
QUANTITY OF

LINE PIPING IN ACCORDANCE WITH THE PLUMBING DRAWINGS, AND CONFORMING WITH ALL $5&+,7(&785(
HOT WATER
WASTE TYPE
WASTE SIZE

QUANTITY

ITEM NUMBER
CFM TOTAL
CFM TOTAL
ITEM NUMBER

CONNECTIONS
CONNECTIONS
CONNECTIONS

INSTALLED BY:
PRESSURE
PRESSURE

MOUNTED ON
CONNECTION

FURNISHED BY:
GAS ROUGH-IN
CONSUMPTION

ROUGH-IN SIZE
ROUGH-IN SIZE
ROUGH-IN SIZE
ROUGH-IN SIZE

APPLICABLE CODES AND/OR GOVERNMENTAL AGENCIES HAVING JURISDICTION OVER PROJECT DESCRIPTION MANUFACTURER MODL NO. PLUMBING REMARKS REMARKS &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
LOCATION. 2 MOP SINK BASIN 1.00 GC/PC GC/PC FLOOR DW 2" 1.00 2 û‚¹¼ċ™‚ċĖû™‹&Ђí
SERVICE FAUCET W/ APPROVED 7KH3URPHQDGH1RUWK
3 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL PLUMBING SERVICES TO ROUGH-IN 3 TYPE BACKFLOW PREVENTION 1.00 PC PC WALL 1/2" 15 1/2" 1/2" 2.00 3
LOCATION AND FROM ROUGH-IN TO EQUIPMENT POINT OF CONNECTION INCLUDING FINAL DEVICE
/RQJ%HDFK&$
EQUIPMENT CONNECTIONS AS REQUIRED AND/OR NECESSARY FOR PROPER OPERATION OF PC TO FURNISH & INSTALL APPROVED TYPE
ZZZLGDH[SHULHQFHQHW
FURNISHED EQUIPMENT. INSTALLATION SHALL MEET APPLICABLE CODES OR GOVERNMENT ITEM 159 1/2" BACKFLOW PREVENTION DEVICE TO THIS
14A CARBONATOR 2.00 OSV OSV 1/2" 1 EA. IW 3/4" 1.00 0
AGENCIES HAVING JURISDICTION OF PROJECT LOCATION. / 176 FILTERED ITEM AS REQUIRED BY LOCAL CODE. IW TO
$UFKLWHFW
FS BY PC. VERIFY REQ'TS. W/ OSV
CENTRAL WATER FILTRATION SEE SEE SEE
16 1.00 OSV OSV WALL VERIFY REQUIREMENTS W/ OSV 16
4 KEC SHALL PROVIDE ALL FAUCETS AND SINK WASTE ASSEMBLIES UNLESS OTHERWISE SPECIFIED. SYSTEM REMARK REMARK REMARK
PLUMBING CONTRACTOR SHALL INSTALL ALL COMPONENTS AND MAKE FINAL CONNECTIONS. *(2))5(<%/,0
SEE SEE SEE
18 WATER SOFTENER 1.00 OSV OSV WALL VERIFY REQUIREMENTS W/ OSV 18 $,$1&$5%/(('$3
REMARK REMARK REMARK
5 PLUMBING ENGINEER/CONTRACTOR TO VERIFY ALL REQUIREMENTS OF OWNER FURNISHED SEE VERIFY REQUIREMENTS W/
31 DRYER 1.00 OSV OSV ITEM 32 50.00 1.00 VERIFY REQUIREMENTS W/ OSV VERIFY 31 Plans, maps, specifications, studies, and reports not
EQUIPMENT WITH OWNERS SELECTED VENDOR PRIOR TO ROUGHING-IN ANY UTILITIES. REMARK OSV containing a red ink seal imprint accompanied by an
original
FUNNEL DRAIN OUT OF WALL. VERIFY signature by the licensed professional may have been
32 WASHER 1.00 OSV OSV CURB 1/2" 40.00 1/2" 1/2" 2.00 DW 2" 1.00 32 fraudulently altered and shall not be considered an original
REQUIREMENTS W/ OSV copy. All information should be disregarded unless verified
6 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL REDUCING VALVES/STOPS NECESSARY AT by the professional whose signature appears above.
1/2" Copyright Protected 2016.
HOT/COLD WATER SUPPLY LINES FOR GENERAL WATER PRESSURE NOT TO EXCEED 40 P.S.I.G. 33 ICE MAKER 1.00 KEC KEC ITEM 35 MANITOWOC SY-3074C 3/8" 1.00 IW 1" 1.00 IW TO FLOOR SINK BY PC 33
FILTERED
MAXIMUM AT KITCHEN EQUIPMENT.
35 ICE BIN 1.00 KEC KEC LEGS MANITOWOC F-1300 IW 1" 1.00 IW TO FLOOR SINK BY PC 35
(QJLQHHULQJ&RQVXOWDQW
7 PLUMBING CONTRACTOR TO FURNISH 20 P.S.I.G. MAXIMUM WATER PRESSURE AT WAREWASHER/ 36 FLOOR TROUGH 1.00 KEC GC/PC FLOOR DW 3" 1.00 36
DISHWASHER.
42 FREEZER EVAPORATOR COIL 1.00 KEC KEC ITEM 41 COLDZONE IW 1" 1.00 IW TO FLOOR SINK BY PC. 42
8 PLUMBING CONTRACTOR TO FURNISH AND INSTALL PRESSURE TYPE VACUUM BREAKERS,
45 COOLER EVAPORATOR COIL 3.00 KEC KEC ITEM 44 COLDZONE IW 1" 1 EA. IW TO FLOOR SINK BY PC. 45
BACKFLOW PREVENTERS, DOUBLE CHECK VALVE ASSEMBLIES AND REDUCED PRESSURE PRINCIPLE
DEVICES. AS REQUIRED BY CODE OR GOVERNMENT AGENCIES HAVING JURISDICTION OF PROJECT HAND SINK W/ SOAP AND TOWEL
LOCATION, UNLESS OTHERWISE SPECIFIED. 51 2.00 KEC KEC WALL NATIONAL BAR SYSTEMS NHS-1 1/2" 5 EA. 1/2" 1/2" 2 EA. DW 1-1/2" 1 EA. 51
DISPENSER
52 S/S WORKTABLE W/ SINK 1.00 KEC KEC LEGS CUSTOM FABRICATION CUSTOM 1/2" 10.00 1/2" 1/2" 2.00 IW 1-1/2" 1.00 IW TO FLOOR SINK BY PC 52
9 PLUMBING CONTRACTOR TO PROVIDE AND INSTALL ALL WASTE LINES, BOTH DIRECT AND INDIRECT, 62 S/S PREP TABLE W/ 2-COMP. SINKS 1.00 KEC KEC LEGS CUSTOM FABRICATION CUSTOM 1/2" 20.00 1/2" 1/2" 2.00 IW (2) 1-1/2" 2.00 IW TO FLOOR SINK BY PC 62
UNLESS OTHERWISE SPECIFIED. INDIRECT WASTE LINES ARE TO BE ADEQUATELY SIZED AND
EXTEND FROM EQUIPMENT DRAIN TO FLOORSINK. DRAIN LINES WITHIN FIXTURES MUST BE ROUTED PLUMBING ENGINEER TO VERIY DRAIN TYPE
67 S/S POT SINK ASSEMBLY 1.00 KEC KEC LEGS CUSTOM FABRICATION CUSTOM (2) 1/2" 90.00 (2) 1/2" 1/2" 4.00 DW / IW (3) 1-1/2" 3.00 67
TO CONFORM TO INTERIOR STRUCTURES. INDIRECT WASTE LINES FROM ICE BINS AND COLD (IW OR DW) W/ LOCAL CODES
STORAGE ROOMS ARE TO BE INSULATED TO PROHIBIT SWEATING. 75 FIRE SUPPRESSION SYSTEM 1.00 OWNER OWNER WALL ANSUL VERIFY REQUIREMENTS W/ OTHERS 75
WALL/ *VERIFY REQUIREMENTS W/
76 EXHAUST HOOD (TYPE I) 1.00 OWNER OWNER CAPTIVE AIRE * * * * 76
CEILING OTHERS
10. PLUMBING CONTRACTOR TO INSTALL FIRE PROTECTION SYSTEM GAS SHUT-OFF VALVE FURNISHED
BY K.EC AT GAS SUPPLY LINE TO COOKING EQUIPMENT IN AN EASILY ACCESSIBLE LOCATION AND 77 MAKE UP AIR SYSTEM 1.00 HVAC HVAC --- 77
PRESSURE TEST PRIOR TO CONNECTING TO ANY EQUIPMENT.
ELECTRICAL CONTROL PACKAGE
79 1.00 OWNER OWNER ITEM 76 CAPTIVE AIRE 79
FOR ITEM 76
3URMHFW2ZQHU
11. PLUMBING CONTRACTOR TO FURNISH AND INSTALL A GAS PRESSURE REGULATING VALVE CAPABLE "TOTAL GAS = 120, 000 BTU/HR. MANIFOLD
80 CONVECTION OVEN-2 DECK 1.00 KEC KEC CASTERS VULCAN SG44 3/4" (2) 60 1.00 80
GAS CONNECTION."
OF PROVIDING OUTLET PRESSURE FROM 4" TO 7" W.G. FOR NATURAL GAS FUEL, AND 9" TO 12" W.G.
FOR PROPANE GAS FUEL, WHEN SPECIFIED. 83 RANGE (OPEN BASE) 1.00 KEC KEC CASTERS JADE JMRH-4ST 3/4" 200.00 1.00 83
40 GAL. KETTLE W/ FIXED TYPE FILL
12. PLUMBING CONTRACTOR TO VERIFY REQUIREMENTS FOR GREASE LADEN WASTE WITH ALL LOCAL 84 1.00 KEC KEC LEGS GROEN AHS-40 1/2" 40.00 1/2" 1/2" 2.00 1/2" 115.00 1.00 84
FAUCET
CODES AND GOVERNMENT AGENCIES HAVING JURISDICTION OF PROJECT LOCATION PRIOR TO
ROUGHING-IN OF ANY SUCH WASTE LINE(S). S/S DRAIN PAN WITH TROUGH AND
85 1.00 KEC KEC FLOOR CUSTOM FABRICATION CUSTOM DW (2) 3" 2.00 85
GRATE
40 GAL. KETTLE W/ FIXED TYPE FILL
86 1.00 KEC KEC LEGS GROEN AHS-40 1/2" 40.00 1/2" 1/2" 2.00 1/2" 115.00 1.00 86
FAUCET
ABBREVIATIONS S/S SOILED DISHTABLE W/ RACK
96 1.00 KEC KEC LEGS CUSTOM FABRICATION CUSTOM IW 1-1/2" 2.00 IW TO FLOOR SINK BY PC 96
SHELF
ARCH = ARCHITECTURAL IW = INDIRECT WASTE
CLG = CEILING JB = JUNCTION BOX 97 S/S SCRAP SINK W/ PRE BASKET 1.00 KEC KEC ITEM 96 IW 2" 1.00 IW TO FLOOR SINK BY PC 97
CFM = CUBIC FEET PER MINUTE KEC = KITCHEN EQUIPMENT CONTRACTOR
CONN = CONNECTION KW = KILOWATTS 97A PRE-RINSE FAUCET 1.00 KEC KEC ITEM 96 1/2" 40.00 1/2" 1/2" 2.00 97A
DR = DOUBLE PURPOSE RECEPTACLE LBS = POUNDS
DW = DIRECT WASTE MAX = MAXIMUM DISHMACHINE W/ TOP MOUNT IW TO FLOOR SINK BY PC 12" DEEP FLOOR
EC = ELECTRICAL CONTRACTOR MBTU = BRITISH THERMAL UNITS 99 1.00 OWNER OWNER LEGS CMA EST-66 1/2" 119.00 1/2" 1/2" 2.00 IW 2" 1.00 99
BOOSTER SINK WITH MINIMUM 3" DIA. WASTE LINE
EQUIP = EQUIPMENT PER HOUR (THOUSANDS)
E/R = EXISTING RELOCATE/RE-INSTALL MC = MILLWORK CONTRACTOR BOOSTER HEATER - 70 DEGREE RISE
EX = EXISTING BY OWNER MIN = MINIMUM 99B 1.00 OWNER OWNER LEGS 99B
EXH = EXHAUST MISC = MISCELLANEOUS (PART OF ITEM 99)
F = FAHRENHEIT NEMA = NATIONAL ELECTRICAL
FD = FLOOR DRAIN MANUFACTURES ASSOCIATION 100 EXHAUST SYSTEM 1.00 HVAC HVAC --- 100
FLR = FLOOR NIC = NOT IN CONTRACT
FMR = FIXTURE MOUNTED RECEPTACLE OSV = OWNER SELECTED VENDOR WALL/
101 EXHAUST HOOD 1.00 OWNER OWNER CAPTIVE AIRE 101
FPM = FEET PER MINUTE OW = OWNER CEILING
FS = FLOOR SINK POS = POINT OF SALE
GC = GENERAL CONTRACTOR PC = PLUMBING CONTRACTOR 102 S/S CLEAN DISHTABLE 1.00 KEC KEC LEGS CUSTOM FABRICATION CUSTOM IW 1-1/2" 1.00 IW TO FLOOR SINK BY PC 102
GPH = GALLONS PER HOUR SR = SINGLE PURPOSE RECEPTACLE
GPM = GALLONS PER MINUTE SP = STATIC PRESSURE 104 S/S FLOOR TROUGH 3.00 KEC GC / PC FLOOR DW 3" EA. 1 EA. 104
HD = HUB DRAIN TEMP = TEMPERATURE SERVICE FAUCET W/ APPROVED
HPM = HORSEPOWER MOTOR W/ = WITH
HVAC = HEATING, VENTING AND OR WC = WATER COLUMN 105 TYPE BACKFLOW PREVENTION 1.00 PC PC WALL 1/2" 15 1/2" 1/2" 105
AIR CONDITIONING DEVICE
106 S/S FLOOR TROUGH 1.00 KEC GC / PC FLOOR DW 3" 1.00 106
WALL/ *VERIFY REQUIREMENTS W/
107 EXHAUST HOOD (TYPE I) 1.00 OWNER OWNER CAPTIVE AIRE * * * * 107
CEILING OTHERS
108 EXHAUST SYSTEM 1.00 HVAC HVAC --- 108
109 FIRE SUPPRESSION SYSTEM 1.00 OWNER OWNER WALL ANSUL VERIFY REQUIREMENTS W/ OTHERS 109
1RUPV5HVWDXUDQWV//&
111 FRYER ASSEMBLY W/ FILTER 1.00 KEC KEC CASTERS PITCO SG14S-2FD 1" 220.00 1` 111 /DNHZRRG%OYG
112 FILL FAUCET 1.00 KEC KEC WALL FISHER 4730 1/2" 112 %HOOIORZHU&$
S/S REFRIGERATED BASE
112A 1.00 KEC KEC LEGS UTILITY REFRIGERATOR LHR-66T-4D IW 3/4" 1.00 112A
(4-DRAWER) 6WDPS
S/S REFRIGERATED BASE
112B 1.00 KEC KEC LEGS UTILITY REFRIGERATOR LHR-102T-6D IW 3/4" 1.00 112B
(6-DRAWER)
113 60" GRIDDLE (CUSTOM CHUTE) 1.00 KEC KEC ITEM 112 JADE JGT-2460 3/4" 120.00 1.00 113
114 EGG BURNER - STEPPED 1.00 KEC KEC ITEM 112 JADE JHPE-3-336 3/4" 120.00 1.00 114
115 CHEESE MELTER 1.00 KEC KEC WALL LANG 248CMW 1/2" 40.00 1.00 115
116 COIL WRAPPED FOR EGG STATION 1.00 KEC KEC ITEM 116 CUSTOM FABRICATION CUSTOM IW 3/4" 1.00 IW TO FLOOR SINK BY PC 116
ELECTRICAL CONTROL PACKAGE
117 1.00 OWNER OWNER WALL 117
FOR ITEM 107
118 24" GRIDDLE (STANDARD CHUTE) 1.00 KEC KEC ITEM 112 JADE JGT-2424 3/4" 48.00 1.00 118
120 48" BROILER 1.00 KEC KEC ITEM 112 IMPERIAL IABS-48 3/4" 180.00 1.00 120
122 60" GRIDDLE (CUSTOM CHUTE) 1.00 KEC KEC ITEM 127 JADE JGT-2460 3/4" 120.00 1.00 122
,VVXH)RU
124 FRYER ASSEMBLY W/ FILTER 1.00 KEC KEC CASTERS PITCO SG14S-1FD 3/4" 110.00 1` 124
S/S CHEF'S/ PICKUP COUNTER W/ PERMIT
127 1.00 KEC KEC CURB CUSTOM FABRICATION CUSTOM 1/2" 5.00 1/2" 1/2" 2.00 IW 1-1/2" 1.00 IW TO FLOOR SINK BY PC 127
UTILITY SINK
,VVXH'DWH
128 HAND SINK WITH TOWEL DISPENSER 1.00 KEC KEC ITEM 127 NATIONAL BAR SYSTEMS NHS-2 1/2" 5.00 1/2" 1/2" 2.00 DW 1-1/2" 1.00 128
09-18-17
129 HEATED DIPPER WELL W/ TIMER 2.00 KEC KEC ITEM 127 1/2" 3/8" 1 EA. IW 1" 1 EA. IW TO FLOOR SINK BY PC 129
5HYLVLRQV
133 DIPPERWELL W/ FAUCET 2.00 KEC KEC ITEM 127 FISHER 3041 1/2" 5 EA. 3/8" 1 EA. IW 1" 1 EA. IW TO FLOOR SINK BY PC 133 NO. REASON DATE
135 S/S COIL WRAPPED PAN 1.00 KEC KEC ITEM 127 CUSTOM FABRICATION CUSTOM IW 1" 1.00 IW TO FLOOR SINK BY PC 135
136 DROP-IN HOT FOOD WELL 1.00 KEC KEC ITEM 127 WELLS MOD-400TD IW 1/2" 1.00 IW TO FLOOR SINK BY PC 136
136A FILL FAUCET 1.00 KEC PC ITEM 1127 1/2" 5.00 1/2" 1.00 136A
FOUNTAINETTE -29" DEEP
156 1.00 KEC KEC CURB RANDELL CUSTOM 1/2" 1/2" 1.00 IW 1/2", 1" 2.00 IW TO FLOOR SINK BY PC 156
EQUIPMENT
"FILTERED WATER REQUIRED. VERIFY
162 HOT CHOCOLATE DISPENSER 1.00 OSV OSV ITEM 159 1/2" 1/2" 1.00 162
REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. VERIFY
163 JUICE DISPENSER 2.00 OSV OSV ITEM 159 1/2" 1/2" 1.00 163
REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. IW TO FLOOR
164 ICE BIN/ SODA DISPENSER 1.00 OSV OSV ITEM 159 1/2" 1/2" 1.00 IW (2) 1" 2.00 164
SINK BY PC VERIFY REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. IW TO FLOOR
165 WATER FILLER 1.00 KEC KEC ITEM 159 FISHER 12513 1/2" 3/8" 1.00 IW 1" 1.00 165
SINK BY PC VERIFY REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. VERIFY
166 TEA MAKER 1.00 OSV OSV ITEM 159 1/2" 1/2" 1.00 166
REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. VERIFY
167 COFFEE MAKER 1.00 OSV OSV ITEM 159 1/2" 1/2" 1.00 167
REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. IW TO FLOOR
179 ICE BIN/ SODA DISPENSER 1.00 OSV OSV ITEM 176 1/2" 1/2" 1.00 IW (2) 1" 2.00 179
SINK BY PC VERIFY REQUIREMENTS W/ OSV"
"FILTERED WATER REQUIRED. VERIFY
181 TEA MAKER 1.00 OSV OSV ITEM 176 1/2" 1/2" 1.00 181
REQUIREMENTS W/ OSV"
PRINCIPAL IN CHARGE:
"FILTERED WATER REQUIRED. VERIFY
183 COFFEE MAKER 1.00 OSV OSV ITEM 176 1/2" 1/2" 1.00 183 JT
REQUIREMENTS W/ OSV"
PROJECT MANAGER:
186 DIPPER WELL W/ TH FAUCET 1.00 KEC KEC ITEM 187 FISHER 3041 1/2" 3/8" 1.00 IW 1" 1.00 IW TO FLOOR SINK BY PC 186
JT
189 HAND SINK WITH TOWEL DISPENSER 1.00 KEC KEC ITEM 187 NATIONAL BAR SYSTEMS NHS-2 1/2" 5.00 1/2" 1/2" 2.00 DW 1-1/2" 1.00 189 DRAWN BY:
DL, CQ
190 SOUP WARMER 2.00 KEC KEC ITEM 187 WELLS SS-10TDU-120 IW 1/2" 1 EA. IW TO FLOOR SINK BY PC 190
3URMHFW$GGUHVV
S/S REFRIGERATED BASE WITH
191 1.00 KEC KEC CURB IW 1" 3.00 IW TO FLOOR SINK BY PC 191
JUMPER LIDS NORM'S RESTAURANT -
195 S/S COLD PAN 2.00 KEC KEC ITEM 187 CROWN CUSTOM IW 3/4" 1 EA. IW TO FLOOR SINK BY PC 195 INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING KITCHEN
EQUIPMENT SCHEDULE
6KHHW1XPEHU
P4.0

12/4/2017 2:25:26 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
ROD
NUT TOP AND
BOTTOM
INSULATION INSULATION STAINLESS STEEL CLAMPS
ROD 1/4'' TEST CONNECTION WITH
ROD MAXIMUM THYCURB MODEL NO, BALL VALVE AND CAP
PIPE TP-1 PIPING COVER WITH FASTEN COVER TO
1/2'' BELOW NUT
OUTSIDE WALL GALVANIZED STEEL CAP CURB WITH SCREWS,
AND NEOPRENE BOOTS 6'' ON CENTER, LINE SIZE UNION
MINIMUM (2) PER SIDE
$5&+,7(&785(
FASTEN NOZZLE TO WALL WITH ROUTE VENT (IF EQUIPPED) TO LINE SIZE SHUT-OFF &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
VANDAL-PROOF STAINLESS ATMOSPHERE FULL SIZE OF VALVE û‚¹¼ċ™‚ċĖû™‹&Ђí
STEEL BOLTS AND EXPANSION OUTLET WITH TURNED DOWN G 7KH3URPHQDGH1RUWK
THYCURB MODEL NO. MINIMUM 12'' HIGH
PIPE ANCHORS; CAULK ALL AROUND SCREENED OUTLET /RQJ%HDFK&$
TC-1 GALVANIZED ZZZLGDH[SHULHQFHQHW
SHEETMETAL FLANGE
STEEL ROOF CURB SEE PLANS FOR
SHEETMETAL HANGER HANGER SHIELD ROOF INSULATION PIPE SIZES
ROD SHIELD CAST BRONZE DOWNSPOUT NOZZLE $UFKLWHFW
SECONDARY PRESSURE REGULATING
DOWNSPOUT, SEE VALVE NORMALLY FURNISHED WITH
ROD MAXIMUM ROD PIPE PLANS FOR SIZE
NUT TOP AND ROD EQUIPMENT *(2))5(<%/,0
1/2'' BELOW NUT DIRT LEG, FULL SIZE OF
BOTTOM 15'', VERIFY WITH ARCHITECT PIPING AND 6'' MINIMUM $,$1&$5%/(('$3
ROOF CONSTRUCTION PIPING THRU ROOF, SEE
CLEVIS EQUIPMENT CONNECTION WITH LONG
PLANS FOR NUMBER OF
HANGER REDUCER IF REQUIRED Plans, maps, specifications, studies, and reports not
PIPES AND PIPE SIZES containing a red ink seal imprint accompanied by an
NUT TOP original
PIPE PAVING OR GRADE signature by the licensed professional may have been
AND BOTTOM fraudulently altered and shall not be considered an original
NOTES: copy. All information should be disregarded unless verified
SHEETMETAL by the professional whose signature appears above.
1. CUT AND PATCH EXISTING ROOF AS REQUIRED FOR NEW CURB Copyright Protected 2016.
HANGER
SHIELD INSTALLATION. TYPICAL GAS PIPING CONNECTION DETAIL
SHEETMETAL HANGER 2. CURB SHALL BE TAPERED TYPE AND MATCH THE PITCH OF THE ROOF.
SHIELD NOT TO SCALE (QJLQHHULQJ&RQVXOWDQW
INSULATION 3. SECURELY INSTALL CURB TO ROOF; USE FASTENERS AS REQUIRED BY ROOF
DOWNSPOUT NOZZLE DETAIL CONSTRUCTION.
ROD MAXIMUM 1/2'' BELOW NUT
NOT TO SCALE
TYPICAL PIPING THRU ROOF DETAIL
TYPICAL HANGER DETAIL NOT TO SCALE
NOT TO SCALE
EXTENSION 1/2'' LESS
PROVIDE 1'' ELASTOMERIC INSULATION OVER HEAT EXTERIOR WATER DAM THAN ROOF INSULATION VENT
TRACING CABLE ON CONDENSATE LINE OF FREEZER THICKNESS ROOF DRAIN DOME AND LOOP VENT, ROUTE TIGHT TO WALL LINE
BOX ONLY, (ELECTRIC HEATING CABLE IS BY OTHERS) FLASHING COLLAR UNDERSIDE OF COUNTERTOP ESCUTCHEON 3URMHFW2ZQHU
EXTENSION SAME ROOF DRAIN DOME AND ROOF DRAIN EXTENSION
ROOF MEMBRANE FIXTURE
HEIGHT AS ROOF FLASHING COLLAR
EVAPORATOR COIL EQUIPMENT
PROVIDE INSULATION
CLEANOUT IN THICKNESS
TURNS AND ENDS G
OF PIPE ROOF ROOF DRAIN EXTENSION ROOF
NO INSULATION MEMBRANE CONST'N.
ON PIPE RISER
ROOF CO CO
DRAIN INTO FLOOR MAKE CONNECTION LINE SIZE BALL VALVE
CONST'N FLOOR LINE
DRAIN WITH AIR GAP SILICONE SEAL TO COIL DRAIN PAN ROOF ROOF INSULATION
OF TWO PIPE AROUND PIPE AS REQUIRED METAL DECK 'P' TRAP
INSULATION PITCH UP
DIAMETERS PENETRATION CONCRETE DECK QUICK CONNECT
SUMP RECEIVER QUICK CONNECT
METAL DECK
FLOOR DRAIN WALK-IN COOLER CONCRETE DECK ROOF DRAIN BODY L-SHAPED UNDERDECK
SUMP RECEIVER DIRT LEG
OR FREEZER BOX CLAMP
CO
DOWNSPOUT FLEXIBLE CONNECTOR
ROOF DRAIN BODY L-SHAPED
UNDERDECK CLAMP
DOWNSPOUT
CONNECT BASE OF VENT PITCH DN.
NOTE: TO WASTE LINE RESTRAIING CABLE
1. INSTALL PIPE AS HIGH AS POSSIBLE, ANCHORED TO WALL OF BOX WITH SUPPORTS AT TYPICAL ROOF DRAIN DETAIL FLOOR LINE
MAXIMUM SIX FOOT CENTERS. USE TYPE ''M'' HARD COPPER TUBE AND FITTINGS WITH NOT TO SCALE
LEAD-FREE SOLDER JOINTS. SLOPE HORIZONTAL PIPE AT MINIMUM TWO PERCENT REFER TO
LOCAL CODE FOR INDIRECT DRAIN REQUIREMENTS. LOOP VENT DETAIL
TYPICAL OVER FLOW ROOF DRAIN DETAIL NOT TO SCALE TYPICAL FOOD SERVICE EQUIPMENT NAT. GAS CONN. DETAIL
NOT TO SCALE
COOLER/FREEZER CONDENSATE DRAIN DETAIL NOT TO SCALE
NOT TO SCALE
1RUPV5HVWDXUDQWV//&
FINAL BACKFILL SHALL BE /DNHZRRG%OYG
SUPPORT STRUCTURE
SUPPORT STRUCTURE SUITABLE MATERIAL %HOOIORZHU&$
FINISHED CONCRETE FLOOR SLAB, EXCAVATED FROM THE
SEE ARCHITECTURAL DRAWINGS
TRENCH OR PIT-RUN SAND
6WDPS
SUPPORT ANCHORAGE AND GRAVEL
SUPPORT ANCHORAGE
ROD COUPLING IF REQUIRED
ROD COUPLING IF REQUIRED MASON TYPE SRC OR UC SEISMIC GRANULAR FILL, SEE
MASON TYPE SSB ROD CLAMP IF REQUIRED ARCHITECTURAL
SEISMIC BRACKET MASON TYPE SRC OR MASON TYPE SSB DRAWINGS.
UC SEISMIC ROD CLAMP SEISMIC BRACKET 1 THREADED ROD
IF REQUIRED PIPING LOOP
1 ROD STIFFENER ANGLE OR TYPICAL
STRUT IF REQUIRED INITIAL BACKFILL SHALL
UNDERGROUND 6'' MINIMUM
THREADED ROD BE NATURAL SAND
1 PIPING IN TRENCH
WHICH PASSES THRU A
1 3/8'' SIEVE AND
4'' CONTAINS NO SILT, TYPICAL ROOF
ROD STIFFENER ANGLE 6'' MINIMUM
CLAY OR OTHER PIPING SUPPORT;
OR STRUT IF REQUIRED
ORGANIC MATERIAL SEE DETAIL ,VVXH)RU
TRAPEZE SUPPORT THE SUB-GRADE SHALL BE
PERMIT
PIPE CLAMP OR U-BOLT PIPE
UNDISTURBED EARTH OF BEDDING MATERIAL SHALL BE ,VVXH'DWH
SUITABLE MATERIAL TO CRUSHED STONE, 1/2'' TO NO. PORTAL; SEE ROOF
TRAPEZE SUPPORT SUPPORT GENERAL 200 SIEVE IN SIZE DETAIL 09-18-17
CONSTRUCTION OR SHALL BE 5HYLVLRQV
COMPACTED THUS OR SHALL WIDTH OF TRENCH AT TOP OF PIPE NO. REASON DATE
STEEL BRACE MAXIMUM BE REMOVED AND REPLACED SHALL BE 4 X DIAMETER PLUS 8'' AND
9'-6" (2.9 m) WITH BEDDING MATERIAL WIDTH AT TOP OF TRENCH SHALL BE
CONTRACTOR'S RESPONSIBILITY
MASON TYPE SSB
SEISMIC BRACKET
NOTE: GAS PIPING THRU ROOF PENETRATION DETAIL
STEEL BRACE MAXIMUM PIPE CLAMP OR U-BOLT 1. LOCAL AND STATE AUTHORITIES HAVING JURISDICTION SHALL APPROVE THIS OR OTHER NOT TO SCALE
9'-6" (2.9 m) INSTALLATION.
MASON TYPE SSB
SEISMIC BRACKET TYPICAL UNDERGROUND PIPING DETAIL
NOT TO SCALE
TRANSVERSE SEISMIC SOLID BRACE TRAPEZE SUPPORTED PIPE/CONDUIT LONGITUDINAL SEISMIC SOLID BRACE TRAPEZE SUPPORTED PIPE/CONDUIT
NOT TO SCALE NOT TO SCALE
SEALANT BEAD TURN-DOWN LEAD FLASHING
STAINLESS STEEL INTO TOP OF VENT PIPE
PIPE CLAMP GAS OR CONDENSATE PIPING ON ROOF CLAMP; MINIMUM ONE SIZE
LARGER THAN PIPE TO ALLOW
MOLDED PIPE BOOT SHEET LEAD FLASHING BOOT FOR MOVEMENT, SECURE
SUPPORT STRUCTURE SUPPORT STRUCTURE MIN. 4 LB./S.F. AND 24'' SQ. THREADED ROD CLAMP TO STRUT WITH STRUT
FURNISHED BY PRINCIPAL IN CHARGE:
ROOFING CONTR. CONNECTORS
JT
24''x24'' ROOFING WALKWAY PAD,
PROJECT MANAGER:
SUPPORT ANCHORAGE SUPPORT ANCHORAGE 12'' COORDINATE SELECTION WITH
MEMBRANE BUILT-UP ROOFING STRUT, FIELD ADJUST JT
ROOFING MANUFACTURER
ROOFING TO KEEP STRUT LEVEL DRAWN BY:
ROD COUPLING IF REQUIRED DL, CQ
ROD COUPLING IF REQUIRED
MASON TYPE SSB ROOF 3URMHFW$GGUHVV
MASON TYPE SRC OR UC SEISMIC SEISMIC BRACKET
NORM'S RESTAURANT -
ROD CLAMP IF REQUIRED MASON TYPE SRC OR UC SEISMIC ROOF CONSTRUCTION INGLEWOOD, CA
ROD CLAMP IF REQUIRED
MASON TYPE SSB 1 1 W IMPERIAL HWY
THREADED ROD
SEISMIC BRACKET INGLEWOOD, CA 90303
1 1
THREADED ROD
(EXACT ADDRESS TBD BY
NOTES: CITY)
ROD STIFFENER ANGLE STEEL BRACE MAXIMUM ROD STIFFENER ANGLE 1. PIPING ON ROOF SHALL BE SUPPORTED 6'-0''(3'-0") ON CENTER FOR 3/4'' TO 1'', 8'-0''(4"-0")
OR STRUT IF REQUIRED 9'-6" (2.9 m) OR STRUT IF REQUIRED ROOF ON CENTER FOR 1-1/4'' TO 2'', 10'-0''(5"-0") ON CENTER FOR 2-1/2'' TO 3'' AND 12'-0''(6"-0") ON 3URMHFW1XPEHU
STEEL BRACE MAXIMUM CUT OPENING OR SLEEVE
9'-6" (2.9 m) CONSTRUCTION ROOF CONSTRUCTION CENTER FOR 4'' TO 6''. PLASTIC PIPING SHALL BE DISTANCE AS INDICATED WITH (X'-X").
2. PIPING SHALL FOLLOW SLOPES OF ROOF WHEREVER POSSIBLE; PROVIDE SWING JOINTS
78-001-17
MASON TYPE SSB AT CHANGES IN SLOPE. CONDENSATE PIPING SHALL MAINTAIN CONTINUOUS SLOPE FOR 6KHHW7LWOH
SEISMIC BRACKET DRAINAGE.
PIPE HANGER 3. CHANGES IN PIPE SIZE SHALL BE WITH ECCENTRIC REDUCERS FOR A CONTINUOUS LEVEL
PLUMBING DETAILS
MASON TYPE CCB CLEVIS CROSS BRACE
VENT STACK BOTTOM OF PIPE ON SUPPORTS.
PIPE CLAMP
PIPE HANGER INCREASER IF REQ'D. 4. STRUT CLAMPS AND BOLTS SHALL BE GALVANIZED AND CADMIUM FOR STEEL PIPE OR
COPPER AND BRASS FOR COPPER PIPING.
5. PROVIDE PIPE SUPPORT ASSEMBLY AS MANUFACTURED BY C-PORT COMPANY OR EQUAL.
PIPE CLAMP MAY BE ROTATED TO
GAIN ACCESS TO STRUCTURE MAXIMUM 4 IN. (102 mm)
ABOVE
TYPICAL PIPING ROOF SUPPORT DETAIL (PRODUCT) 6KHHW1XPEHU
VENT THRU ROOF DETAIL NOT TO SCALE
LONGITUDINAL SEISMIC SOLID BRACE FOR CLEVIS SUPPORTED PIPE/CONDUIT NOT TO SCALE
TRANSVERSE SEISMIC SOLID BRACE FOR CLEVIS SUPPORTED PIPE/CONDUIT P5.0
NOT TO SCALE NOT TO SCALE

12/4/2017 2:25:26 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
TO WATER
HEATER HWS(140)
HWS
HWR
1-1/2"
2"
BY PASS INCOMING COLD 1-1/2"
BY PASS WATER
3/4"
$5&+,7(&785(
&ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
TYPICAL SHUT-OFF
û‚¹¼ċ™‚ċĖû™‹&Ђí
VALVE 7KH3URPHQDGH1RUWK
/RQJ%HDFK&$
ZZZLGDH[SHULHQFHQHW
CWS
HWR

HWS(140)

$UFKLWHFW
WATER *(2))5(<%/,0
BRINE BRADLEY $,$1&$5%/(('$3
SOFTENER BY
TANK NRS-4
VENDOR
HIGH-LOW
Plans, maps, specifications, studies, and reports not
RECIRCULATION containing a red ink seal imprint accompanied by an
STATION original
signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
copy. All information should be disregarded unless verified
by the professional whose signature appears above.
Copyright Protected 2016.
(QJLQHHULQJ&RQVXOWDQW
MIXING VALVE STATION DETAIL
WATER FILTER DETAIL NOT TO SCALE
NOT TO SCALE
ET-1 TYPICAL CHECK VALVE
CP-1
3/4"
B
HW(140)
THERMOMETER
3/4" 1-1/2"
TYPICAL ASME TEMP/PRESSURE A
HWS(140) RELIEF VALVE 2"
HWR HWS(140) 3URMHFW2ZQHU
TOP VIEW (COVERS AND RINGS REMOVED)
CWS CWS
24" CAST IRON FRAMES AND COVERS 3", 6" AND 12"
WITH GASKET (GASTIGHT) STANDARD GR2432 GRADE RINGS
2" 2" AS REQUIRED
AT EXTRA COST
1-1/2" 24"
SEE GAS PIPING PLAN INVERT
INVERT
INLET
OUTL ET
CONTINUED FOR SIZES AND ROUTING
TANKSTAT C 4" PIPE AND FITTINGS
ON MIXING D STANDARD E
1-1/4"
G

STATION
DETAIL 3/4" GAS COCK SIDE SECTION VIEW
LIQUID MINIMUM MINIMUM TANK
MODEL DEPTH OF
CAPACITY DIM A DIM B DIM C DIM D DIM E EXCAVATION EXCAVATIO WEIGHT
NUMBER BURY
(GALLONS) WIDTH LENGTH LBS.
JP320G 320 3'-0" 7'-0" 4'-6" 3'-7" 3'-4" 4'-0" 8'-0" 1' TO 6' 6,600
2" DIRT LEG JP500G 500 4'-0" 6'-0" 5'-10" 4'-10" 4'-7" 5'-0" 7'-0" 1' TO 6' 6,750
JP750G 750 4'-0" 8'-1" 6'-0" 5'-0" 4'-9" 5'-0" 9'-1" 1' TO 6' 9,000
JP1000G 1000 5'-1" 8'-2" 6'-0" 5'-0" 4'-9" 6'-1" 9'-2" 1' TO 6' 11,000
JP1200G 1200 5'-9" 8'-6" 6'-0" 5'-0" 4'-9" 6'-9" 9'-6" 1' TO 6' 12,600
JP1500G 1500 5'-7" 10'-8" 6'-0" 5'-0" 4'-9" 6'-7" 11'-8" 1' TO 6' 14,900
DESIGN LOAD: H-20 TRAFFIC WITH DRY SOIL CONDITIONS (WATER LEVEL BELOW TANK.)
SUITABLE SUB-BASE BEDDED WITH GRANULAR MATERIAL SHALL BE PREPARED TO HANDLE
ANTICIPATED LOADS.
FOR COMPLETE DESIGN AND PRODUCT INFORMATION
CONTACT JENSEN PRECAST.
3/11/08 Jensen Precast reserves the right to make changes to product design
JP320-JP1500_GREASE_SOCAL_B.dwg and/or dimensions without notice. Please contact Jensen Precast whenever
C 2008 Jensen Precast necessary for confirmation or advice on product design.
TYPICAL REDUCER;
IF REQUIRED WH-1
ST-1
TYPICAL UNION FLOOR SINK
TYPICAL BALL VALVE
GREASE INTERCEPTOR DETAIL
NOT TO SCALE
DOMESTIC WATER HEATER PIPING DETAIL
NOT TO SCALE
1RUPV5HVWDXUDQWV//&
/DNHZRRG%OYG
%HOOIORZHU&$
DRAIN CONNECTION 6WDPS
PRIMING AND CLEANOUT CAP
TOTAL AIR SYSTEM STATIC
PRESSURE PLUS TWO INCHES
PITCH DOWN
COIL DRAIN PAN
,VVXH)RU
LINE SIZE UNION
PERMIT
,VVXH'DWH
2'' AIR GAP
09-18-17
CLOSE-COUPLED WATER SEAL TRAP
5HYLVLRQV
INDIRECT WASTE RECEPTOR OR SPLASH ON GRADE/ROOF NO. REASON DATE
NOTES:
1. SCHEDULE 40, GALVANIZED STEEL PIPE AND FITTINGS.
2. SEE PLANS FOR PIPE SIZES.
TYPICAL COIL CONDENSATE DRAIN PIPING DETAIL (DRAW-THRU)
NOT TO SCALE
TO FILTERED WATER
EQUIPMENT
PRINCIPAL IN CHARGE:
BY PASS JT
PROJECT MANAGER:
INCOMING COLD WATER
JT
DRAWN BY:
DL, CQ
3URMHFW$GGUHVV
NORM'S RESTAURANT -
INGLEWOOD, CA
W IMPERIAL HWY
INGLEWOOD, CA 90303
(EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
WATER FILTER BY VENDOR;
VERIFY EXACT TYPE AND 6KHHW7LWOH
INSTALLATION
PLUMBING DETAILS
6KHHW1XPEHU
WATER FILTER DETAIL
NOT TO SCALE
P5.1

12/4/2017 2:25:27 PM
H:\17317\RVT\17317_R16.rvt
'HVLJQ&RQVXOWDQW
PLUMBING 9. NOISE AND VIBRATION 11 M.MOTORS AND ELECTRICAL APPARATUS D. Welding Joints: Use qualified welders only. Make welds 22.CLEANOUTS
The general conditions and general requirements It is the specific intent of these Specifications and design Provide motors of proper power and speed to suit with electric arc using suitable coated rods. Properly bevel A. Provide cleanouts of same nominal size as the
sections shall apply directly to this section as though conditions that the entire system including equipment, specified makes of equipment, horsepower and and clean all joints before welding. Weld in accordance with pipes they serve, except where cleanouts are
printed herein. piping,and all other parts be noiseless and free of electrical characteristics as indicated on the Drawings. American Welding Society Standards and governing codes. required in pipes 4" and larger provide 4" cleanouts.
1. SCOPE vibration transmission. Provide and install vibration 12. TRENCHING AND BACKFILLING 16.UNIONS B. Make cleanouts accessible. After pressure tests
A. Work included all labor,materials,equipments and dampers, sound insulation pads, flexible connectors and A. Do all necessary trench excavations, .shoring and Install unions on connections to all equipment on the are made and approved, thoroughly graphite the
incidentals required to furnish and install all plumbing similar material as required, to prevent transmission to backfilling required for the proper laying of all downstream side of all threaded or soldered valves cleanout threads.
work as indicated on the plans, specified herein, the building structure of sound and vibration caused by underground piping. Make trenches at least 12 inches and elsewhere as indicated on the Drawings. 2.3. TAGGING AND IDENTIFICATION
and/or as necessary to complete the work including the flow of fluids, motors, and motor operated equipment. wider than the greatest diameter of the pipe. Should 17.VALVES Label all valves with securely attached metal tags
$5&+,7(&785(
but not limited to the following If, as a result of the installation, noise or vibrations rock be encountered, excavate some to the depth of A. Install shut-off valves in all main services, at fixtures, and showing the service and valve number. Stamp tags &ÐÐØĠgċ¼ØÐgЎ™ā¼¯Ð¼Ð
1. Sanitary soil, waste and vent system, Combination occurs in the building, make the necessary corrections at one foot below the bottom of the pipe, and fill where required to provide complete isolation of all with black filled numbers and letters. Prior to final
waste and vent system.
û‚¹¼ċ™‚ċĖû™‹&Ђí
no cost to the Owner. Do not reduce the capacity of any the space with well tamped sand and pea grovel. equipment, devices ,etc. for their proper servicing. Arrange inspection, submit to Architect two copies of chart 7KH3URPHQDGH1RUWK
2. Domestic hot and cold water systems. equipment. B. Lay pipe on a bed of sand at least two inches deep. valves to give complete and regulating control of piping showing valve number, service, valve location and /RQJ%HDFK&$
3. Condensate drain system. 10. WARRANTY Cover pipe with another two inches of sand. systems throughout the building. Install all valves with best of area controlled. ZZZLGDH[SHULHQFHQHW
4. Plumbing fixtures, equipment. trim. Be responsible for all work under this Section, adjust all 1.3.MANUFACTURER'S RECOMMENDATIONS workmanship, with neat appearance and grouping, so that all 24. TESTING
5. Rough-in and final connections of water and drain valves. controls, vacuum breakers and other incidental Install all equipment, material, fixtures, and devices in parts are easily accessible for maintenance. A. Test all work under the supervision of the $UFKLWHFW
not included in this Section or as to equipment, items. Leave the system in perfect operating condition. accordance with the recommendations of the B. Install trap primer with shut-off valve and union. representative of the Architect and/or Owner and
furnished by Owner. Repair, regulate and replace any defective workmanship, manufacturer and the requirements of the Drawings 18.PIPE SUPPORTS inspected by all authorities having jurisdiction over
6. Gas system. materials, and equipment which may become apparent and Specifications. In the event of conflict, consult the A. Support suspended piping with clevis or trapeze hangers this work. Deliver four (4) sets of all test charts and *(2))5(<%/,0
7. Excavation and backfilling. within one year after the date of the final acceptance of Architect for a decision and perform the Work in and rods. In concrete slabs support piping from inserts or $,$1&$5%/(('$3
reports to the Architect.
8. Testing. the Work, at no additional cast to the Owner. Furnish the accordance with his decision. anchors. Where steel framing is used, attach supports with B. Pressure Tests: Plans, maps, specifications, studies, and reports not
2. EXAMINATION OF THE SITE Owner all manufacturer's written warranties of materials 14.INSTALLATION OF PIPING suitable clamps and to wood framing use suitable bolts or lag Test the various parts of the systems before piping is containing a red ink seal imprint accompanied by an
original
Examine the site and all conditions thereon or therein. and equipment. A. General: screws. concealed as required by governing authorities and signature by the licensed professional may have been
fraudulently altered and shall not be considered an original
Take into consideration all conditions that may affect 11. MATERIALS 1. Clean all pipe and remove all scale, sand, dirt, etc., B. Support each item independently from other pipes. Do not pay all costs for same. copy. All information should be disregarded unless verified
by the professional whose signature appears above.
the work under this Contract. Lack of this information Provide all new materials, in proper condition, of the best Copyright Protected 2016.
before installation. Use full lengths of pipe whenever use wire for hanging or strapping pipes. 1. Entire soil, waste and vent piping shall be tested
wilI not be considered as justification for extra cost or quality for the purpose intended, clearly marked or possible to minimize the number of couplings. C. Space hangers and supports for horizontal steel pipes with minimum of 10 feet head of water for three (3)
allowances to the Contract sum. stamped with the manufacturer's name and/or stamp and 2. Cut pipes accurately to measurements established according to the following schedule: hours. (QJLQHHULQJ&RQVXOWDQW
3. CODES AND REGULATIONS rating. on the site. Work pipes into place without springing or D. All piping which is not isolated from contact with the 2. All domestic water piping shall be tested under a
A. Ordinances and Regulations: In addition to A. Soil, waste and vent: Cast iron no hub pipe and forcing, and properly clear equipment, doors and building by its insulation shall be installed with a hydrostatic pressure of 150 PSI far three (3) hours.
complying with the specified requirements, comply fittings with stainless steel clamp. ABS if landlord/code openings of buildings. manufactured type isolator.Horizontal piping in stud walls 3. All gas piping shall be tested under air pressure of
with pertinent regulations of governmental agencies allows it. 3. Install all piping to run parallel to the building may be isolated with hair felt pads securely wired in place. 50 PSI held for four (4) hours without any drop in
having jurisdiction. B. Domestic Water( above ground): Type L hard drawn construction and arrange to form neat and symmetrical E. Isolator shall be Semco Trisolators. Series NO. 100 for pressure. check each joint and gas cock with soap
B. Permits and Inspections: Apply and pay for all copper ASTM B88. and wrought copper fittings. patterns to insure the best appearance possible,. I.PS. piping and Series NO. 500 for coppertubing as sud.
permits for the installation or construction of the C. Domestic Water (below ground; inside building): Type 4. Unless· otherwise specified, conceal all pipe in walls, manufactured by Stoneman Engineering and Mfg. Co. Pipe C. Operating Tests:
plumbing work required by any legally constituted K soft drawn copper. partitions or furred spaces. size: 1.Before final acceptance, perform operating tests
public authorities having jurisdiction D. Domestic Water (below ground; outside building, 3" 5. Install piping at the exterior of the building, at a Maximum spacing on center for a duration of eight (8) hours. Furnish all labor and
and furnish all necessary drawings required for same. and smaller): type k hard drawn copper. minimum depth of 18" below finish grade. Do not 1-1/4" and smaller---- 8'-0" instruments for tests.
Arrange for inspections and examinations as required, E. Domestic Water (below ground; outside. building 4" expose pipes on the exterior of building. 1-1 I 2 " and larger---- 1 O' - O" D. Should the Contractor refuse or neglect to make
and deliver certificates of all inspections to the Owner. and larger): ductile iron class 51. conform to AWWA 6. Use proper shoring and rigging methods. Other locations: Valves, fittings and change in direction. any tests necessary to satisfy the Owner, or his
4. DRAWINGS AND SPECIFICATIONS standard C-151. pipe and fittings shall be cement lined in 7. Proceed with the rough piping as rapidly as the F. Space hangers and supports for horizontal copper tubing representative, that he has carried out the true intent
A. The Drawings are in part diagrammatic and are accordance with AWWA standard C-10.4. fittings shall general construction work will permit and have all of according to the following schedule: and meaning of the Specifications, the Owner may
intended to convey the scope of the work; they conform to AWWA standard C-110. 250 psi pressure the rough piping in and stubbed out to the proper point Tube size: make such tests and charge the expense there of to
indicate the general arrangement and approximate rating, standard outside coating and cement mortar and tested, in each case, before any lath, plaster or Maximum spacing on centers: the Contractor. 3URMHFW2ZQHU
sizes of equipment, piping, etc. lining. joint shall conform to AWWA standard C-11, finish work of the ceilings, partitions, walls, or floors 1-1/2" and smaller---- 6'-0" 25. CLEANING
Follow the Drawings as closely as practical in laying mechanical or push-on joints. are in place. 2 " and larger--·-- 8'-0" A. Thoroughly clean all equipment and piping to
out the work, be guided by the conditions at the job F. Indirect drain: Type L hard drawn copper tubing ASTM 8. Install all pipes with allowances for expansion and Other locations: Valves, fittings end change in direction. remove dust, scale, plaster, or any internal
and consult the Construction Drawings of the other B.88 with wrought copper fittings. contraction. Construct so that strains will be evenly G. Provide sway bracing on hangers longer than 18". obstructions before any covering is installed or any
trades to become familiar with all conditions affecting G. Gas: 2-1/2'' and smaller: Schedule 40 black steel pipe distributed without damage to the system. Avoid H. Arrange pipe supports to prevent excessive deflection, piping, or equipment is painted and/or placed in
the Work. with 150 psi. black bonded malleable iron screwed building erection stresses into the piping. and to avoid excessive bending stress. operation. Clean exposed ports of equipment,
8. Verify all clearances in areas where Work will be fittings. 3'' and larger: Schedule 40 black steel pipe with 9. Make connection between copper or brass piping I. Support vertical piping with riser clamps secured to the remove oil and grease, and leave the bright metal
installed and coordinate the Work with that of the 150 psi butt welded black malleable iron fittings. and steel with approved dielectric couplings. piping and resting on the building structure. Provide at each parts clean and polished. Restore finished surfaces
other trades and other Sections of the Specifications. 11 B. PIPE FITTINGS 10.Avoid connections and equipment installation that floor unless otherwise noted. it damaged, and deliver entire installation in
C. Where job conditions, or the Architect require 1. Provide fittings for cast iron soil pipe of the same could cause a cross connection between water supply J. Support piping independently at pumps, tanks and similar approved condition.
reasonable changes in indicated locations and material, weight and quality specified for pipe. and drainage. locations, so that weight of pipe will not be supported by the 8. During the progress of the work, carefully clean up
arrangement, make such changes without additional 2. Provide for black steel pipes 2-1 /2" and smaller, 11.Cover all exposed connections to plumbing fixtures equipment. after your men, and leave the premises and all
charge. banded, black malleable iron fittings. with polished and chromium plated seamless copper K. Hubless piping: Provide hangers on the piping at each portions of the building in which you are working,
D. It is the intent of the Drawings and Specifications 3. Provide for copper water pipes, wrought copper solder casing. side of, and within 6" of, hubless pipe coupling so the free from debris. Upon completion of the work,
to provide complete operating systems, unless joint fittings. Cast fittings will not be permitted. 12.Show no tool marks or threads on exposed plated, coupling will bear no weight. Maintain alignment and prevent remove all rubbish, debris and surplus materials
specifically noted to the contrary. The omission from 4. Provide for exposed fixture connections, 85% cast red polished, or enameled connections from fixtures. sagging of pipe, and make adequate provision to prevent resulting therefrom from the premises, and leave the
the Drawings or Specifications of any minor details of brass, polished and chromium plated fittings. B. Soil, Waste, Vent and Drainage Piping: shearing and twisting of the pipe and the joint. Do not site in
construction, installation, materials, or specialties 11 C.UNIONS 1. Install piping as straight as possible and make all provide hangers on couplings. Horizontal spacing: 5'-0" a clean and acceptable condition as approved by the
necessary for a safely operable system shall not Union shall be provided at all equipment, at points change in direction with fittings. Make offsets at 45 Other locations: F.ittings and change in direction. Architect.
relieve the Contractor from furnishing the such items adjacent to all valves, and elsewhere as required to degrees or less. L. Support piping on roof on 2" x 4" redwood blocks 12" long C. Before being placed in operation, flush clean
in place, complete. permit servicing of fixtures. Unions to as manufactured 2. Extend all vent pipes at least 6" above finished roof at maximum of 8'-0" O.C. Anchor piping to blocks. inside of pipes, etc. Clean all strainers after
5. SUBSTITUTIONS by Crane or equal. surfaces and higher wherever required by local M. Hanger rods shall conform to the following table: operational tests. Clean plumbing fixtures of
A. Whenever a product is specified by trade name or 11 D. VALVES plumbing ordinances. pipe size 2" and smaller: 3/8 inch rod protective materials and clean and polished entire
manufacturer's name, either in the Specifications or 1. General: Non rising stem may be used only where C. Water Piping: pipe size 2-1/2" and 3": 1 /2 inch rod assemblies. Clean floor drain grates and
on the Drawings, such designation is intended to there is insufficient clearance. Solder joint or screwed 1. Run leveI without pockets and as straight as pipe size 4" and 5": 5/8 inch rod 19. check each fixture to insure against trap stoppage.
establish a standard of merit and design. type valves shall be used in copper piping. Valves of one possible. 19.INSULATION 26.WATER SYSTEM STERILIZATION
B. Submit written requests for substitutions in type shall be of the same manufacturer. NIBCO or 2. Install hot and cold water lines at least 12" apart. A. Insulate all domestic hot water supply and return piping. Before the use of any portion of water system and
triplicate. Include catalog numbers, capacities, ratings approved equal 3. Isolate all water lines from all parts of the building Do not cover unions. thickness shall be in accordance with before final acceptance of the system, the purity of
and the cuts of products specified as well as products VALVES SCHEDULE structure and hangers with 1/2" thick waffle pattern, table on P-1 (energy notes). material to be some as specified the system must meet the requirements of the State 1RUPV5HVWDXUDQWV//&
to be substituted. Also include accurate cost data on Gate valve: NIBCO NO. S-113 hair felt strips of a 2" minimum width completely below in "B". Board of Health. Submit a Certificate from an /DNHZRRG%OYG
the proposed substitution in comparison with the Globe valve: NIBCO S-211-Y surrounding the pipes. Use pipe isolators to isolate all B. Insulate all condensate drain piping with 1/2" thick approved testing laboratory that the water system %HOOIORZHU&$
products specified and whether or not modification of Check valve: NIBCO NO. S-413-Y pipe hangers and supports. Armstrong 2000 or elastomeric or lmcoa polyolfin foam pipe meets all the purity requirements of the State Board
the Contract amount is to be considered. Ball valve: NIBCO NO. S-580 2. 6WDPS
4. Install water hammer arrestors in on upright position insulation. All joints shall be sealed with lmcoa adhesive. all of Health. Obtain written approval from water testing
C. Substitutions of unlisted manufacturers will not be Pressure and Temperature Relief Valve: McDonnel and on hot and cold water piping headers, at each quick fittings to be insulated with miter cut pieces. Water pipes run laboratory and submit to general contractor for
allowed after the Contract is signed. Miller, Mueller, or Watts. closing valves and where indicated on the Drawings. in exterior wall chases are to be covered with 3/ 4" approval.
6. SUBMITTALS Gas cock: Nordstorm or equal. 5. Install vacuum breaker on water lines where insulation. 27.GROUTING
A. Product Data: Submit material list of items 11E. PIPE SUPPORTS required by code even if not specifically mentioned in Fiberglass insulation is NOT allowed. Grout behind all wall-hung plumbing fixtures with
proposed to be provided under this Section. Include FEE MASON or approved equal the Specification or indicated on the Drawings. C. Provide insulation continuous through hangers and hard, white durable plaster materials, eliminating all
Manufacturers' specifications, catalog cuts, and other 11F. SLEEVES 6. Arrange thermometers for easy reading from the rollers. voids and cracks and providing sufficient
data needed to comply with the specified Provide Elcen "E-Z Crete" rust-proof sleeves of the size floor and install all pressure gauges with shut-off cocks. D. Insulate the tail piece, "p" trap, trap arm and hot water plane--bearing surfaces for mounting.
requirements. Submit all product data at one time, required. D. GAS PIPING: supply piping at each fixture for handicapped use. Handi 28.ADJUSTING
bound between covers. Partial submittals will not 11G. ACCESS PANELS & BOXES 1. run level without pockets and as straight as possible. Lav-Guard Insulation Kits manufactured by TRUEBRO INC. Upon completion of and after cleaning of system and
be accepted. Provide access panels as manufactured by J.R.Smith 2. make all connections to gas burning equipment and 20. PIPE WRAPPING equipment, carefully adjust for normal operation the
B. Shop Drawings or other data as required to Elmdor or equal in quality and style . Provide access appliances using straight- way even handle service SPIRALLY WRAP ALL, UNDERGROUND STEEL AND automatic parts of plumbing systems.
,VVXH)RU
indicate method of installation and attachment of panels with the same fire rating as the wall or ceiling in cock before connection to burner. COPPER PIPING WITH PLASTIC TAPE ONE HALF 29.0PERATION AND MAINTENANCE
piping, and equipment, except where such details are which they are installed. 15.JOINTS LAPPED TO GIVE DOUBLE THICKNESS. WRAP ALL INSTRUCTIONS PERMIT
fully shown on the Drawings. 1. plaster wall and ceiling: elmdor pw series okl hinged A. Screwed Steel Pipe: Cut threads with new clean FIELD JOINTS AFTER PRESSURE TEST. WHERE SOIL Upon completion of the work of this Section and ,VVXH'DWH
C. Record Drawings and Manuals: Provide and keep prime coated steel trimless access panel with plaster dies. carefully - ream and inspect each piece of pipe IS CORROSIVE ATTACH ANODES TO ALL before final acceptance, deliver to the Architect two 09-18-17
at job site a complete record set of blueline prints, ground. before erection. Apply pipe dope to male threads only. UNDERGROUND STEEL PIPING WITH ISOLATION copies of an operation and maintenance manual.
corrected daily to show every change from the original 2. tile, drywall and ceiling: elmdor pw series akl hinged Expose no more than two threads. UNIONS IN ACCORDANCE WITH RECOMMENDATIONS 5HYLVLRQV
NO. REASON DATE
Drawings and Specifications. Prints for this purpose stainless steel flanged access panel with bright finish for B. Copper Tubing: Cut pipe square, using proper tools OF A CORROSION ENGINEER.
may be obtained from the Architect. Deliver the set to tile walls, prime coated steel for painted walls. and remove all burrs, thoroughly clean end of pipe A. For insulated pipe, provide sleeves of adequate size to
the Architect. Pay for blueprinting Project Record 3. Acoustical tile: Elmdor AT Series AKL hinged prime equal to depth of fitting, using sand cloth, sandpaper or accommodate the full thickness of pipe covering, with
Drawings. coated steel flanged access panel. steel wool for cleaning purposes. Apply a coat of No. clearance for packing and calking.
7. OPENINGS 4. Fire rated Wall and Ceiling: Elmdor FR Series AKL with 5D Streamline paste to pipe and fittings. Liquid flux will B. Caulk the space between sleeve and pipe or pipe
A. Openings or holes for piping or equipment will not recessed turn latch. not be permitted. Use 95-5 solder. install all piping in covering,
be allowed in any structural members without consent 11 H. FLASHING accordance with manufacturer's instruction. using a non combustible, permanently plastic, waterproof,
of the Architect. Provide for each pipe passing through the roof 3 LBS. C. Copper or Brass Pipe: Cut threads with new clean non-staining compound which leaves a smooth finished
B. Framed openings have been indicated on the seamless lead flashing assembly. flashing to have steel dies, full thicknesses of dies. Make joints with friction appearance, or pack with non combustible insulating rope to
Architectural and Structural Drawings. At a time in reinforced conical boot and counterflashed with hooded clamps and friction wrenches. Thoroughly ream each within 1/2" of both wall faces, and provide the waterproof
advance of the work, verify the location and size of cast iron counter-flashing sheet lead turned down to the piece of pipe. Apply tape to male threads. compound described above.
openings or furnish new instructions as to the pipe and sealed to the pipe. Manufactured by Stoneman C. Finish and escutcheons:
requirements for these openings. Should the or equal. 1. Smooth up rough edges around sleeves with plaster or
furnishing of this information be neglected, delayed 111.PRESSURE GAUGES AND THERMOMETER spackling compound.
or incorrect, and additional cutting. notching, or boring Marsh Trerice of approved equal 2. Provide 1" wide chrome or nickel plated escutcheons held
is found to be required, the work shall be done as in place with set screw for all pipes exposed to view in
directed by the Architect at no additional cost to the finished spaces.
Owner.
c. Make absolutely watertight any openings through
waterproofed construction caused by the penetration
of piping in a manner approved by the architect. PRINCIPAL IN CHARGE:
JT
8. QUALITY ASSURANCE AND PRODUCT
PROJECT MANAGER:
HANDLING JT
A. Use all means necessary to protect plumbing DRAWN BY:
materials before, during and after installation and to DL, CQ
protect the installed work and materials of all other 3URMHFW$GGUHVV
trades. NORM'S RESTAURANT -
B. In the event of damage, immediately make all INGLEWOOD, CA
repairs and replacements necessary to the W IMPERIAL HWY
satisfaction of the Architect end at no additional cost INGLEWOOD, CA 90303
to the Owner. (EXACT ADDRESS TBD BY
CITY)
3URMHFW1XPEHU
78-001-17
6KHHW7LWOH
PLUMBING NOTES -
SPECIFICATIONS
6KHHW1XPEHU
P6.0

12/4/2017 2:25:28 PM
H:\17317\RVT\17317_R16.rvt

You might also like