REM620
REM620
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2013 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0 Issued: 2013-05-07
Revision: A
ABB 3
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
REM620
Uo
UL1UL2UL3
- IED self-supervision
- Local/Remote push-button on LHMI
I
3I
ESC Clear
- Sequence event
2× 2× O recorder
AND
R
L
3I< I2>M I2>> - User
37M 46M 46R management OR
- Web HMI
Io
Io>>> Io> Io>>
UL1UL2UL3
1)
Check availability of binary inputs/outputs Current transformer 7
from technical documentation
2)
Control and indication function for Voltage transformer 5
3× 2× 2× 3× primary object 1)
Conventional transformer inputs
3U< U2> U1< 3U> 3)
Status indication function for
27 47O- 47U+ 59 primary object
3× 6×
Uo> f>/f<, SYNC ESTART
df/dt
UL1UL2UL3 59G
81
25 ESTART
U12
12×RTD REMARKS
4×mA
3I 12× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
ordering
GUID-A641F704-024A-447F-9112-E61DF258CA8C V1 EN
4 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Protection
ABB 5
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Control
Emergency startup ●
6 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Condition monitoring
Measurement
Frequency measurement ●
Other
ABB 7
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Logging functions
Disturbance recorder ●
Fault recorder ●
Load profile ●
8 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
ABB 9
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
REF620
Example conf. N
ANSI IEC
Io
25 SYNC
3U 47O-/59 U2>/3U>
47U+/27 U1</3U<
Uo
49F 3Ith>F
50L/50NL ARC
3I
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67/67N 3I→/Io→
81 f>/f<,df/dt
81LSH UFLS/R
3I 3I
3I
3U Uo
Io Io Io
RTD RTD
3I 3I
RTD
GUID-6F004016-C4D6-4BBB-B046-18FDDED4346A V1 EN
Figure 2. A dedicated motor substation with the different motor starting methods combined in one switchgear
10 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
REM620
Example conf. N
3U Uo ANSI IEC
47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
3I 49M 3Ith>M
50L/50NL ARC
50P/51P 3I>>>
51LR Ist>
Io 51P/51N 3I/Io
81 f>/f<,df/dt
87M 3dI>M
ESTART ESTART
MAP MAP
OPTM OPTS
RTD
3I
GUID-012EABD8-57B0-496C-B5C3-B726B0DAF97D V1 EN
Figure 3. Direct-on-load starting method, with the motor directly connected to the medium-voltage switchgear
REM620
Example conf. N
ANSI IEC
3U Uo
47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
49M 3Ith>M
50L/50NL ARC
3I 50P/51P 3I>>>
51LR Ist>
51P/51N 3I/Io
81 f>/f<,df/dt
Io 87M 3dI>M
ESTART ESTART
MAP MAP
OPTM OPTS
RTD
3I
GUID-96593CE9-3E6D-46F5-AE9E-619C73CFBB39 V1 EN
Figure 4. Motor started over reactor choke, which decreases motor starting current over the reactor and helps handle the load flow in the
medium-voltage network
ABB 11
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
REM620
Example conf. N
ANSI IEC
3U Uo
47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
3I 49M 3Ith>M
50L/50NL ARC
50P/51P 3I>>>
51LR Ist>
Io 51P/51N 3I/Io
81 f>/f<,df/dt
ESTART ESTART
MAP MAP
OPTM OPTS
RTD
GUID-D4876FE7-FC25-4F7E-BCF2-C6C3508BBF96 V1 EN
Figure 5. Motor starting method with variable-frequency drives VFD that make the control easier and optimize energy consumption
5. Supported ABB solutions At the substation level COM600 uses the data content of the
ABB’s 620 series protection and control IEDs together with bay level IEDs to offer enhanced substation level functionality.
the Grid Automation controller COM600 constitute a genuine COM600 features a Web browser-based HMI providing a
IEC 61850 solution for reliable power distribution in utility and customizable graphical display for visualizing single line mimic
industrial power systems. To facilitate and streamline the diagrams for switchgear bay solutions. Furthermore, the Web
system engineering ABB’s IEDs are supplied with HMI of COM600 offers an overview of the whole substation,
Connectivity Packages containing a compilation of software including IED-specific single-line diagrams, thus enabling
and IED-specific information including single-line diagram convenient information accessibility. To enhance personnel
templates, a full IED data model including event and safety, the Web HMI also enables remote access to
parameter lists. By utilizing the Connectivity Packages the substation devices and processes. Furthermore, COM600
IEDs can be readily configured via the PCM600 Protection can be used as a local data warehouse for technical
and Control IED Manager and integrated with the Grid documentation of the substation and for network data
Automation controller COM600 or the MicroSCADA Pro collected by the IEDs. The collected network data facilitates
network control and management system. extensive reporting and analyzing of network fault situations
using the data historian and event handling features of
The 620 series IEDs offer native support for the IEC 61850 COM600. The data historian can be used for accurate
standard also including binary and analog horizontal GOOSE process performance monitoring by following process and
messaging. Compared to traditional hard-wired inter-device equipment performance calculations with real-time and
signaling, peer-to-peer communication over a switched history values. Better understanding of the process behaviour
Ethernet LAN offers an advanced and versatile platform for by joining time-based process measurements with production
power system protection. Fast software-based and maintenance events helps the user in understanding the
communication, continuous supervision of the integrity of the process dynamics.
protection and communication system, and inherent flexibility
for reconfiguration and upgrades are among the distinctive COM600 also features gateway functionality providing
features of the protection system approach enabled by the seamless connectivity between the substation IEDs and
full implementation of the IEC 61850 substation automation network-level control and management systems such as
standard. MicroSCADA Pro and System 800xA
Product Version
12 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
GUID-8E5ABC5B-5A9B-4248-B2B1-DB5AFA42D801 V1 EN
Figure 6. Industrial power system example using 620 series IEDs, Grid Automation controller COM600 and System 800xA
6. Control The suitability of the binary outputs of the IED which have
REM620 integrates functionality for the control of circuit been selected for the controlling of primary devices should be
breakers, disconnectors and earth switches via the front carefully verified, for example, the make and carry as well as
panel HMI or by means of remote controls. The IED includes the breaking capacity. In case the requirements for the
two circuit breaker control blocks. In addition to the circuit control circuit of the primary device are not met, the use of
breaker control, the IED features four disconnector control external auxiliary relays should be considered.
blocks intended for the motor-operated control of
disconnectors or circuit breaker truck. Furthermore, the IED The graphical LCD of the IED's HMI includes a single-line
offers two control blocks intended for the motor-operated diagram (SLD) with position indication for the relevant primary
control of earthing switch. On top of that, the IED includes devices. Interlocking schemes required by the application are
additional four disconnector position indication blocks and configured using the Signal Matrix or the Application
two earth switch position indication blocks usable with Configuration tools in PCM600.
manually-only controlled disconnectors and earth switches.
A synchrocheck function is incorporated to ensure that the
Two physical binary inputs and two physical binary outputs voltage, phase angle and frequency on either side of an open
are needed in the IED for each controllable primary device circuit breaker satisfy the conditions for a safe
taken into use. Depending on the chosen hardware interconnection of two networks.
configuration of the IED, the number of binary inputs and
binary outputs varies. In case the amount of available binary 7. Measurement
inputs or outputs of the chosen hardware configuration is not The IED continuously measures the phase currents and the
sufficient, connecting an external input or output module, for neutral current. Furthermore, the IED measures the phase
example RIO600, to the IED can extend binary inputs and voltages and the residual voltage. In addition, the IED
outputs utilizable in the IED configuration. The binary inputs calculates the symmetrical components of the currents and
and outputs of the external I/O module can be used for the voltages, the system frequency, the active and reactive
less time-critical binary signals of the application. The power, the power factor, the active and reactive energy
integration enables releasing of some initially reserved binary values as well as the demand value of current and power over
inputs and outputs of the IED. a user-selectable preset time frame. Calculated values are
ABB 13
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
also obtained from the protections and condition monitoring measurement values at the moment when any protection
functions of the IED. function starts. Both Min. and Max. current demand values
are recorded with time stamp. Also both Min. and Max.
The IED is also offered with RTD/mA inputs and can measure power demand values (P, Q, S) are recorded with time stamp.
up to 16 analog signals such as stator winding and bearing By default, the records are stored in a nonvolatile memory.
temperatures via the 12 RTD inputs or the four mA inputs
using transducers. Furthermore, the IED includes a load profile recorder capable
of storing measurement values into the IED's memory. The
The values measured can be accessed locally via the user selected measurement values averaged over the selected
interface on the IED front panel or remotely via the period, ranging from one minute to three hours, are stored in
communication interface of the IED. The values can also be a nonvolatile memory. Depending on the selected
accessed locally or remotely using the web-browser based measurements and averaging period, the overall length of the
user interface. load profile recording ranges from some days to several
months, even a year, making this feature suitable for
8. Disturbance recorder monitoring long-time load behavior for the interested loads.
The IED is provided with a disturbance recorder featuring up
to 12 analog and 64 binary signal channels. The analog 11. Trip-circuit supervision
channels can be set to record either the waveform or the The trip-circuit supervision continuously monitors the
trend of the currents and voltages measured. availability and operability of the trip circuit. It provides open-
circuit monitoring both when the circuit breaker is in its
The analog channels can be set to trigger the recording
closed and in its open position. It also detects loss of circuit-
function when the measured value falls below or exceeds the
breaker control voltage.
set values. The binary signal channels can be set to start a
recording on the rising or the falling edge of the binary signal
or both. 12. Self-supervision
The IED’s built-in self-supervision system continuously
By default, the binary channels are set to record external or monitors the state of the IED hardware and the operation of
internal IED signals, for example the start or trip signals of the the IED software. Any fault or malfunction detected is used
IED stages, or external blocking or control signals. Binary IED for alerting the operator.
signals, such as a protection start or trip signal, or an external
IED control signal over a binary input can be set to trigger the
recording. The recorded information is stored in a nonvolatile 13. Fuse failure supervision
memory and can be uploaded for subsequent fault analysis. The fuse failure supervision detects failures between the
voltage measurement circuit and the IED. The failures are
detected by the negative-sequence based algorithm or by the
9. Event log delta voltage and delta current algorithm. Upon the detection
To collect sequence-of-events (SoE) information, the IED of a failure the fuse failure supervision function activates an
incorporates a non-volatile memory with a capacity of storing alarm and blocks voltage-dependent protection functions
1024 events with associated time stamps. The non-volatile from unintended operation.
memory retains its data also in case the IED temporarily loses
its auxiliary supply. The event log facilitates detailed pre- and
post-fault analyses of feeder faults and disturbances. The 14. Current circuit supervision
increased capacity to process and store data and events in Current circuit supervision is used for detecting faults in the
the IED offers prerequisites to support the growing current transformer secondary circuits. On detecting of a fault
information demand of future network configurations. the current circuit supervision function activates an alarm LED
and blocks certain protection functions to avoid unintended
The SoE information can be accessed locally via the user operation. The current circuit supervision function calculates
interface on the IED front panel or remotely via the the sum of the phase currents from the protection cores and
communication interface of the IED. The information can compares the sum with the measured single reference current
further be accessed, either locally or remotely, using the web- from a core balance current transformer or from separate
browser based user interface. cores in the phase current transformers.
14 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
engineer and administrator level. The access control applies motor. The third option is a high-speed output board
to the front-panel user interface, the web-browser based user including eight binary inputs and three high-speed outputs.
interface and the PCM600 tool. The high-speed outputs have a shorter activation time
compared to the conventional mechanical output relays,
shortening the overall IED operation time with very time-
16. Inputs and outputs
critical applications like arc protection. The high-speed
The IED is equipped with six phase current inputs, one
outputs are freely configurable in the IED application and not
residual-current input, three phase voltage inputs, one
limited to arc protection only.
residual-voltage input and one phase-to-phase voltage for
syncrocheck input. In addition to current and voltage The rated values of the current and voltage inputs are
measurements, the IED's basic configuration includes 12 settable parameters of the IED. In addition, the binary input
binary inputs and 10 binary outputs. Additionally, basic thresholds are selectable within the range of 18…176 V DC
configuration offers six RTD inputs and two mA inputs. The by adjusting the IED’s parameter settings.
phase current inputs and the residual-current inputs are rated
1/5 A, that is, the inputs allow the connection of either 1 A or All binary input and output contacts are freely configurable
5 A secondary current transformers. The optional sensitive with the Signal Matrix or Application Configuration tool of
residual-current input 0.2/1 A is normally used in applications PCM600.
requiring sensitive earth-fault protection and featuring core
balance current transformers. The three phase voltage inputs See the Input/output overview table and the terminal
and the residual-voltage input covers the rated voltages 60... diagrams for detailed information about the inputs and
210 V. Both phase-to-phase voltages and phase-to-earth outputs.
voltages can be connected.
If the number of the IED’s own inputs and outputs does not
As an optional addition, the IED basic configuration includes cover all the intended purposes, connecting to an external
one empty slot which can be equipped with one of the input or output module, for example RIO600, increases the
following optional modules. The first option, additional binary number of binary inputs and outputs utilizable in the IED
inputs and outputs module, adds eight binary inputs and four configuration. In this case, the external inputs and outputs are
binary outputs to the IED. This option is especially needed connected to the IED via IEC 61850 GOOSE to reach fast
when connecting the IED to several controllable objects. The reaction times between the IED and RIO600 information. The
second option, an additional RTD/mA input module, needed binary input and output connections between the IED
increases the IED with six RTD inputs and two mA inputs and RIO600 units can be configured in a PCM600 tool and
when additional sensor measurements e.g. for temperatures, then utilized in the IED configuration.
pressures, levels and so on are of interest with the protected
CT VT RTD/mA BI BO
6/2(12/4)3) 12 10
ABB 15
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
17. Station communication features a galvanic communication module with two galvanic
The IED supports a range of communication protocols and one optical Ethernet network interfaces or three galvanic
including IEC 61850, IEC 60870-5-103, Modbus ® and DNP3. interfaces. The third Ethernet interface provides connectivity
Operational information and controls are available through for any other Ethernet devices to an IEC 61850 station bus
these protocols. However, some communication functionality, inside in a switchgear bay. The redundant solution can be
for example, horizontal communication between the IEDs, is applied to the Ethernet-based IEC 61850, Modbus and DNP3
only enabled by the IEC 61850 communication protocol. protocols.
The IEC 61850 communication implementation supports Ethernet network redundancy can be achieved using the high-
monitoring and control functions. Additionally, parameter availability seamless redundancy (HSR) protocol or the
settings, disturbance recordings and fault records can be parallel redundancy protocol (PRP) or a with self-healing ring
accessed using the IEC 61850 protocol. Disturbance using RSTP in managed switches. Ethernet redundancy can
recordings are available to any Ethernet-based application in be applied to all Ethernet-based IEC 61850, Modbus and
the standard COMTRADE file format. The IED supports DNP3 protocols.
simultaneous event reporting to five different clients on the
station bus. The IED can exchange signals with other IEDs The IEC 61850 standard specifies network redundancy which
using the IEC 61860 protocol. improves the system availability for the substation
communication. The network redundancy is based on two
The IED can send binary signals to other IEDs (so called complementary protocols defined in the IEC 62439-3
horizontal communication) using the IEC 61850-8-1 GOOSE standard: PRP and HSR protocols. Both the protocols are
(Generic Object Oriented Substation Event) profile. Binary able to overcome a failure of a link or switch with a zero
GOOSE messaging can, for example, be employed for switch-over time. In both the protocols, each network node
protection and interlocking-based protection schemes. The has two identical Ethernet ports dedicated for one network
IED meets the GOOSE performance requirements for tripping connection. The protocols rely on the duplication of all
applications in distribution substations, as defined by the IEC transmitted information and provide a zero switch-over time if
61850 standard. The IED also supports the sending and the links or switches fail, thus fulfilling all the stringent real-
receiving of analog values using GOOSE messaging. Analog time requirements of substation automation.
GOOSE messaging enables fast transfer of analog
measurement values over the station bus, thus facilitating for In PRP, each network node is attached to two independent
example sharing of RTD input values, such as surrounding networks operated in parallel. The networks are completely
temperature values, to other IED applications. separated to ensure failure independence and can have
different topologies. The networks operate in parallel, thus
For redundant Ethernet solution, the IED offers a fibre-optic providing zero-time recovery and continuous checking of
communication module providing two optical and one redundancy to avoid failures.
galvanic Ethernet network interfaces. Alternatively, the IED
16 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
COM600
SCADA
HSR applies the PRP principle of parallel operation to a single the sender node discards the frame to avoid loops. The HSR
ring. For each message sent, the node sends two frames, ring with 620 series IEDs supports the connection of up to
one through each port. Both the frames circulate in opposite thirty IEDs. If more than 30 IEDs are to be connected, it is
directions over the ring. Every node forwards the frames it recommended to split the network into several rings to
receives from one port to another to reach the next node. guarantee the performance for real-time applications.
When the originating sender node receives the frame it sent,
COM600
SCADA Devices not supporting HSR
Ethernet switch
GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN
The choice between the HSR and PRP redundancy protocols standard Rapid Spanning Tree l Protocol (RSTP) support. The
depends on the required functionality, cost and complexity. managed switch controls the consistency of the loop, routes
the data and corrects the data flow in case of a
The self-healing Ethernet ring solution enables a cost-efficient communication switch-over. The IEDs in the ring topology act
communication ring controlled by a managed switch with as unmanaged switches forwarding unrelated data traffic. The
ABB 17
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Ethernet ring solution supports the connection of up to thirty self-healing Ethernet ring solution avoids single point of failure
620 series IEDs. If more than 30 IEDs are to be connected, it concerns and improves the reliability of the communication.
is recommended to split the network into several rings. The
Client A Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
All communication connectors, except for the front port supported. DNP3 can also be used at the same time with the
connector, are placed on integrated optional communication IEC 61850 protocol.
modules. The IED can be connected to Ethernet-based
communication systems via the RJ-45 connector (100Base- When the IED uses the RS-485 bus for the serial
TX) or the fibre-optic LC connector (100Base-FX). If communication, both two- and four wire connections are
connection to a serial bus is required, the 10-pin RS-485 supported. Termination and pull-up/down resistors can be
screw-terminal or the fibre-optic ST connector can be used. configured with jumpers on the communication card so
external resistors are not needed.
Modbus implementation supports RTU, ASCII and TCP
modes. Besides standard Modbus functionality, the IED The IED supports the following time synchronization methods
supports retrieval of time-stamped events, changing the with a time-stamping resolution of 1 ms:
active setting group and uploading of the latest fault records.
Ethernet-based:
If a Modbus TCP connection is used, five clients can be
• SNTP (Simple Network Time Protocol)
connected to the IED simultaneously. Further, Modbus serial
and Modbus TCP can be used in parallel, and if required both
IEC 61850 and Modbus protocols can be run simultaneously. With special time synchronization wiring:
• IRIG-B (Inter-Range Instrumentation Group - Time Code
The IEC 60870-5-103 implementation supports two parallel Format B)
serial bus connections to two different masters. Besides
basic standard functionality, the IED supports changing of the
active setting group and uploading of disturbance recordings In addition, the IED supports time synchronization via the
in IEC 60870-5-103 format. Further, IEC 60870-5-103 can be following serial communication protocols:
used at the same time with the IEC 61850 protocol. • Modbus
• DNP3
DNP3 supports both serial and TCP modes for connection to • IEC 60870-5-103
one master. Further, changing of the active setting group is
18 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
IEC 61850 ● ● - -
MODBUS RTU/ASCII - - ● ●
MODBUS TCP/IP ● ● - -
DNP3 (serial) - - ● ●
DNP3 TCP/IP ● ● - -
IEC 60870-5-103 - - ● ●
● = Supported
ABB 19
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Table 5. Dimensions
Description Value
Case 246 mm
Case 160 mm
Depth 201 mm
Uaux nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
Burden of auxiliary voltage supply under DC <12.0 W (nominal)/<19.0 W (max) DC <12.0 W (nominal)/<19.0 W (max)
quiescent (Pq)/operating condition AC <13.0 W (nominal)/<21.0 W (max)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Description Value
• Continuously 4A 20 A
Voltage withstand:
• Continuous 240 V AC
• For 10 s 360 V AC
20 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Description Value
Reaction time 3 ms
Description Value
RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C
Description Value 1)
Breaking capacity when the control-circuit time constant L/R<40 ms 1 A/0.25 A/0.15 A
1) X100: SO1
X105: SO1, SO2, when any of the IEDs is equipped with BIO0005.
X115: SO1, SO2 when REF620 or REM620 is equipped with BIO0005
ABB 21
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Description Value 1)
Breaking capacity when the control-circuit time constant L/R < 40 ms, 1 A / 0.25 A / 0.15 A
at 48/110/220 V DC
1) X100: IRF,SO2
X105: SO3, SO4, when any of the IEDs is equipped with BIO0005
X115:SO3, SO4, when REF620 or REM620 is equipped with BIO0005
Table 12. Double-pole power outputs with TCS function X100: PO3 and PO4
Description Value 1)
Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC (two contacts connected in series)
Table 13. Signal/trip output with high make and carry and with TCS function
Description Value
Breaking capacity when the control-circuit time constant L/R < 40 ms, 1A/0.25A/0.15A
at 48/110/220 V DC (two contacts connected in series)
22 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Table 14. Single-pole power output relays X100: PO1 and PO2
Description Value
Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC
Description Value 1)
Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC
Start 1 ms
1) X105: HSO1, HSO2 HSO3, when any of the IEDs is equipped with BIO0007
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)
ABB 23
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Description Value
Modulation Unmodulated
Table 19. Lens sensor and optical fibre for arc protection
Description Value
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
24 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
• Contact discharge 8 kV
• Air discharge 15 kV
• All ports 4 kV
• 2s 100 A/m
ABB 25
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
• Conducted
• Radiated
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27
26 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C
Description Reference
LV directive 2006/95/EC
Description Reference
Description
ABB 27
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
28 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 x In
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode and Pol quantity = default, current before fault = 0.0 x I n, voltage before fault = 1.0 x U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
ABB 29
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
EFIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Measurement mode = default (depends on stage), current before fault = 0.0 x I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
30 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
EFHPTOC 40...200000 ms 10
EFIPTOC 20...200000 ms 10
ABB 31
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 x In
Voltage
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF
IFault = 2 x set Start value 42 ms 44 ms 46 ms
DEFLPDEF 61 ms 64 ms 66 ms
IFault = 2 x set Start value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20
32 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
DEFHPDEF 40...200000 ms 10
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
ABB 33
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 x Un, Voltage before fault = 1.1 x U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
34 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
ABB 35
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10 to 5.00
Table 48. Negative phase-sequence overcurrent protection for motors (MNSPTOC) main settings
36 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 37
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
1) Current before = 0.0 x I n , f n = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
38 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
Table 58. Thermal overload protection for motors (MPTTR) main settings
Characteristic Value
Operate time 1)2) Biased low stage Instantaneous Typical 40 ms (±10 ms)
high stage3) Typical 15 ms (±10 ms)
ABB 39
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Table 60. Stabilized differential protection for motors (MPDIF) main settings
Characteristic Value
40 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
1) Phase start value = 1.0 x I n, current before fault = 2.0 x set Phase start value , f n = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output
Characteristic Value
ABB 41
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Control functions
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
42 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Measurement functions
Characteristic Value
±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)
Characteristic Value
±1.0% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
±0.5% or ±0.002 x Un
Characteristic Value
±1.0% or ±0.002 x Un
ABB 43
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Characteristic Value
±0.5% or ±0.002 x Un
Characteristic Value
Characteristic Value
44 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Supervision functions
Characteristic Value
Characteristic Value
Operate time1) NPS function UFault = 1.1 x set Neg Seq voltage < 33 ms
Lev
UFault = 5.0 x set Neg Seq voltage < 18 ms
Lev
1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Description Value
ABB 45
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
19. Local HMI breakers cannot be operated remotely from the network
The IED supports process information and status monitoring control center.
from the IED's local HMI via its display and indication/alarm
LEDs. The local LHMI also enables control operations for the
equipment connected and controlled by the IED, either via
display or via manual push buttons available on the local HMI.
LEDs can be configured to show alarms and indications as Figure 10. Example of the LHMI
needed by PCM600 graphical configuration tool. The LEDs
include two separately controllable colors, red and green,
making one LED able to indicate better the different states of
the monitored object.
20. Mounting methods
The IED also includes 16 configurable manual push buttons, By means of appropriate mounting accessories, the standard
which can freely be configured by the PCM600 graphical IED case for the 620 series IED can be flush-mounted, semi-
configuration tool. These buttons can be configured to control flush-mounted or wall-mounted.
the IED's internal features e.g. changing setting group,
Furthermore, the IEDs can be mounted in any standard 19”
triggering disturbance recordings and changing operation
instrument cabinet by means of 19” mounting panels available
modes for functions or to control IED external equipment, e.g.
with cut-outs for one IED. Alternatively, the IED can be
starting or stopping the equipment, via IED binary outputs.
mounted in 19” instrument cabinets by means of 4U
These buttons also include a small indication LED for each
Combiflex equipment frames.
button. This LED is freely configurable, making it possible to
use push button LEDs to indicate button activities or as Mounting methods:
additional indication/alarm LEDs in addition to the 11
programmable LEDs. • Flush mounting
• Semi-flush mounting
The local HMI includes a push button (L/R) for the local/ • Rack mounting
remote operation of the IED. When the IED is in the local • Wall mounting
mode, the IED can be operated only by using the local front- • Mounting to a 19" equipment frame
panel user interface. When the IED is in the remote mode, the
IED can execute commands sent remotely. The IED supports Panel cut-out for flush mounting:
the remote selection of local/ remote mode via a binary input. • Height: 162 ± 1 mm
This feature facilitates, for example, the use of an external • Width: 248 ± 1 mm
switch at the substation to ensure that all the IEDs are in the
local mode during maintenance work and that the circuit
46 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
")
(19
.6
280 482
,2
246 262 246 246
177
160
160
160
177
177
153 103
153
48 98
48
Figure 11. Flush mounting Figure 12. Semi-flush mounting Figure 13. Rack mounting
259
318
186
GUID-65A893DF-D304-41C7-9F65-DD33239174E5 V1 EN
ABB 47
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
22. Selection and ordering data number consists of a string of codes generated from the
The IED type and serial number label identifies the protection IED's hardware and software modules.
IED. The label is placed above the HMI on the upper part of
the plug-in unit. An order number label is placed on the side Use the ordering key information to generate the order
of the plug-in unit as well as inside the case. The order number when ordering complete IEDs.
NBMNAANNABC1BNN1XF
# Description
1 IED
620 series IED (including case) N
2 Standard
IEC B
CN C
3 Main application
Motor protection and control M
4 Functional application
Example configuration N
5-6 Analog inputs and outputs
7I (I0 1/5 A) + 5U + 12BI + 10BO + 6RTD in + 2mA in AA
7I (I0 0,2/1 A) + 5U + 12BI + 10BO + 6RTD in + 2mA in AB
7-8 Optional board
Optional I/Os 8BI+ 4BO AA
Optional RTDs 6RTD in + 2mA in AB
Optional Fast I/Os 8BI + 3HSO AC
No optional board NN
9 Communication modules (Serial)
-
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
10 AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1
AB
x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST) + Serial RS-485 connector, RS-232/485
D-Sub 9 connector + input for IRIG-B (cannot be combined with BN
arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (1 x RJ-45) + Serial
RS-485 connector, RS-232/485 D-Sub 9 connector + input for BB
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (3 x RJ-45) with
BD
HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC
+ 1 x LC) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE
+ 2 x LC) with HSR/PRP
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX and -FX (2 x RJ-45 + 1 x LC) with HSR/
NC
PRP
Ethernet 100Base-TX (3 x RJ-45) with HSR/PRP ND
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) with HSR/
NE
PRP
No communication module NN
48 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
NBMNAANNABC1BNN1XF
# Description
11 Communication protocols
IEC 61850 (for Ethernet communication modules and IEDs with-
A
out a communication module )
Modbus (for Ethernet/serial or Ethernet + serial communication
B
modules)
IEC 61850 + Modbus (for Ethernet or serial + Ethernet communi-
C
cation modules)
IEC 60870-5-103 (for serial or Ethernet + serial communication
D
modules)
DNP3 (for Ethernet/serial or Ethernet + serial communication
E
modules)
IEC 61850 + IEC 60870-5-103(for serial + Ethernet communica-
G
tion modules)
IEC 61850 + DNP3(for Ethernet or serial + Ethernet communica-
H
tion modules)
12 Language
English 1
English and Chinese 2
13 Front panel
Large LCD with Single Line Diagram - IEC B
Large LCD with Single Line Diagram - CN D
14 Option 1
Arc protection (requires a communication module, cannot be
B
combined with communication module optionsS BN or BB)
None N
15 Option 2
None N
16 Power supply
Power supply 48-250 VDC, 100-240 VAC 1
Power supply 24-60 VDC 2
17 Reserved
-
18 Product version 2.0 XF
GUID-600ABF01-7959-4459-A46C-BAB01DB6AF72 V1 EN
Example code: N B M N A A N N A B C 1 B N N 1 X F
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-161F35FF-C0CC-4411-B6F4-2109C0623B48 V1 EN
ABB 49
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
50 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Signal monitoring ● ●
Application configuration - ●
Event viewing ● ●
Online monitoring - ●
● = Supported
ABB 51
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
N
n Positive
Current
a Direction
da dn
REM620
Uab X100
X120
2) + 1
1 1/5A
Uaux
P1 IL1_N -
2
S1
2 N
S2
3 1/5A 3
P2 IL2_N IRF
4 N
4
5 1/5A
IL3_N 5
6 N
7 1/5A PO1
IL1
8 N 6
9 1/5A 7
IL2
P1 S1 10 N PO2
11 1/5A
S2 IL3 8
P2 12 N
9
13 1/5A
10
Io
14 N SO1
11
M X130
12
13
SO2
3~ 1
2
BI 1
14
16
3 PO3
BI 2
4
P2
S2 17
5 15
S1 BI 3 19
P1
6 TCS1 18
20
7 22
BI 4
8 PO4
60 -
9 210V
21
U_SYN 23
10 N
TCS2
60 - 24
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N
X110
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22
X115 X115
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X13
1)
Light sensor input 1
X14
1)
Light sensor input 2
GUID-19F39D16-3819-4030-877F-08E5872EEC5D V1 EN
52 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
11
BI 7
12
BI 8
13
GUID-5298DCA3-4597-44C2-850A-889384DF423B V1 EN
8
BI 7
9
BI 8
10
GUID-D019E095-29EF-41B1-BDF4-D9D427201B88 V1 EN
Figure 18. Optional BIO0007 module for fast outputs (slot X105)
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22
GUID-987D427B-C5F7-4073-8D5F-D0C37BEAF5E5 V1 EN
ABB 53
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
26. References The download area on the right hand side of the web page
The www.abb.com/substationautomation portal offers you contains the latest product documentation, such as technical
information about the distribution automation product and manual, installation manual, operation manual, etc.
service range.
The Features and Application tabs contain product related
You will find the latest relevant information on the REM620 information in a compact format.
protection IED on the product page.
54 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Protection
Directional earth-fault protection, low stage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
ABB 55
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Thermal overload protection for motors MPTTR1 3Ith>M (1) 49M (1)
Circuit breaker failure protection, instance 1 CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)
Circuit breaker failure protection, instance 2 CCBRBRF2 3I>/Io>BF (2) 51BF/51NBF (2)
Control
Disconnector control, instance 1 DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
Disconnector control, instance 2 DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control, instance 1 ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Disconnector control, instance 3 DCXSWI3 I <-> O DCC (3) I <-> O DCC (3)
Disconnector control, instance 4 DCXSWI4 I <-> O DCC (4) I <-> O DCC (4)
Earthing switch control, instance 2 ESXSWI2 I <-> O ESC (2) I <-> O ESC (2)
56 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Earthing switch position indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch position indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Condition monitoring
Runtime counter for machines and devices, instance 1 MDSOPT1 OPTS (1) OPTM (1)
Runtime counter for machines and devices, instance 2 MDSOPT2 OPTS (2) OPTM (2)
Measurement
Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Other
ABB 57
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
Time delay off (8 pcs), instance 1 TOFGAPC1 TOF (1) TOF (1)
Time delay off (8 pcs), instance 2 TOFGAPC2 TOF (2) TOF (2)
Time delay off (8 pcs), instance 3 TOFGAPC3 TOF (3) TOF (3)
Time delay off (8 pcs), instance 4 TOFGAPC4 TOF (4) TOF (4)
Logging functions
58 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0
ABB 59
60