REM620

The document provides a product guide for the REM620, a motor protection and control IED designed for medium to large asynchronous motors in industrial applications. It details the device's features, including protection functions, control capabilities, measurement options, and supported ABB solutions, along with configuration and communication functionalities. The REM620 is part of ABB's Relion® 620 series, emphasizing scalability and compliance with the IEC 61850 standard.

Uploaded by

mscsarya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views

REM620

The document provides a product guide for the REM620, a motor protection and control IED designed for medium to large asynchronous motors in industrial applications. It details the device's features, including protection functions, control capabilities, measurement options, and supported ABB solutions, along with configuration and communication functionalities. The REM620 is part of ABB's Relion® 620 series, emphasizing scalability and compliance with the IEC 61850 standard.

Uploaded by

mscsarya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

Relion® 620 series

Motor Protection and Control


REM620
Product Guide
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Contents

1. Description.....................................................................3 15. Access control............................................................14


2. Default configuration.......................................................3 16. Inputs and outputs......................................................15
3. Protection functions........................................................9 17. Station communication................................................16
4. Application.....................................................................9 18. Technical data.............................................................20
5. Supported ABB solutions.............................................12 19. Local HMI....................................................................46
6. Control.........................................................................13 20. Mounting methods......................................................46
7. Measurement...............................................................13 21. IED case and IED plug-in unit......................................47
8. Disturbance recorder....................................................14 22. Selection and ordering data.........................................48
9. Event log......................................................................14 23. Accessories and ordering data....................................50
10. Recorded data............................................................14 24. Tools...........................................................................50
11. Trip-circuit supervision.................................................14 25. Connection diagrams..................................................52
12. Self-supervision...........................................................14 26. References..................................................................54
13. Fuse failure supervision...............................................14 27. Functions, codes and symbols....................................55
14. Current circuit supervision...........................................14 28. Document revision history...........................................59

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2013 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0 Issued: 2013-05-07
Revision: A

1. Description series engineering with different function blocks. The default


REM620 is a dedicated motor IED perfectly aligned for the configurations are not aimed to be used as real end-user
protection, control, measurement and supervision of medium- applications. The end-users always need to create their own
size and large asynchronous motors, requiring also differential application configuration with the configuration tool. However,
protection, in the manufacturing and process industry. the default configuration can be used as a starting point by
REM620 is a member of ABB’s Relion ® protection and modifying it according to the requirements.
control product family and its 620 series. The 620 series IEDs
are characterized by their functional scalability and REM620 is available with one default configuration targeting
withdrawable-unit design. for differential protection. The default signal configuration can
be altered by means of the graphical signal matrix or the
The 620 series has been designed to unleash the full potential graphical application functionality of the Protection and
of the IEC 61850 standard for communication and Control IED Manager PCM600. Furthermore, the application
interoperability of substation automation devices. configuration functionality of the IED supports the creation of
multi-layer logic functions using various logical elements
including timers and flip-flops. By combining protection
2. Default configuration
functions with logic function blocks, the IED configuration can
The 620 series IEDs are configured with default
be adapted to user-specific application requirements.
configurations, which can be used as examples of the 620

ABB 3
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

REM620
Uo
UL1UL2UL3

MOTOR PROTECTION AND CONTROL IED EXAMPLE


CONFIGURATION
N
Version 2.0

PROTECTION LOCAL HMI ALSO AVAILABLE

- 16× prog. push-buttons on LHMI


2× - Disturbance and fault recorders
Master Trip A

- Event log and recorded data


Lockout relay U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
- High-Speed Output module (optional)
94/86 IL2 0 A

- IED self-supervision
- Local/Remote push-button on LHMI
I
3I
ESC Clear

- Sequence event
2× 2× O recorder
AND
R
L
3I< I2>M I2>> - User
37M 46M 46R management OR
- Web HMI

Is2t n< 3Ith>M


CONDITION MONITORING COMMUNICATION 1 0 1 0 0 0 1 1 0 0 1 1 0 0
49, 66, 48, 51LR 49M 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
AND SUPERVISION
1 1 0 0 1 1 1 0 1 1 0 1 0
Protocols: 1 0 1 1 0 1 1 0 1 1 0 1 0 0
3× 3× Io IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
ARC 3I>>> Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
50L/50NL 50P/51P IEC 60870-5-1031 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
DNP3
3I
2× 2×
Interfaces:
3I>/Io>BF Ist> 3I> FUSEF CBCM MCS 3I
Ethernet: TX (RJ-45), FX (LC)
51BF/51NBF 51LR 51P-1 60 CBCM MCS 3I
Serial: Serial glass fiber (ST),
RS-485, RS-232/485
U12 2× 2× 2× Io D-sub 9, IRIG-B
Io
3I>→ 3I>>→ 3dl>M OPTS TCS
67-1 67-2 87M OPTM TCM Redundant protocols:
HSR
PRP
RSTP

Io
Io>>> Io> Io>>
UL1UL2UL3

50N/51N 51N-1 51N-2


CONTROL AND INDICATION 1) MEASUREMENT

Uo - I, U, Io, Uo, P, Q, E, pf, f


Object Ctrl 2) Ind 3) - Symmetrical components
Io>→ Io>>→ - Limit value supervision
67N-1 67N-2 CB 2 - - Load profile
DC 4 4
ES 2 2 Analog interface types 1)

1)
Check availability of binary inputs/outputs Current transformer 7
from technical documentation
2)
Control and indication function for Voltage transformer 5
3× 2× 2× 3× primary object 1)
Conventional transformer inputs
3U< U2> U1< 3U> 3)
Status indication function for
27 47O- 47U+ 59 primary object

3× 6×
Uo> f>/f<, SYNC ESTART
df/dt
UL1UL2UL3 59G
81
25 ESTART

U12

12×RTD REMARKS
4×mA
3I 12× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
ordering

GUID-A641F704-024A-447F-9112-E61DF258CA8C V1 EN

Figure 1. Functionality overview

4 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 1. Supported functions

Functionality CTs & VTs

Protection

Three-phase non-directional overcurrent protection, low stage, instance 1 ●

Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 ●

Three-phase directional overcurrent protection, low stage, instance 1 ●

Three-phase directional overcurrent protection, high stage, instance 1 ●

Three-phase directional overcurrent protection, high stage, instance 2 ●

Non-directional earth-fault protection, low stage, instance 1 ●

Non-directional earth-fault protection, high stage, instance 1 ●

Non-directional earth-fault protection, instantaneous stage, instance 1 ●

Directional earth-fault protection, low stage, instance 1 ●

Directional earth-fault protection, high stage ●

Residual overvoltage protection, instance 1 ●

Residual overvoltage protection, instance 2 ●

Residual overvoltage protection, instance 3 ●

Three-phase undervoltage protection, instance 1 ●

Three-phase undervoltage protection, instance 2 ●

Three-phase undervoltage protection, instance 3 ●

Three-phase overvoltage protection, instance 1 ●

Three-phase overvoltage protection, instance 2 ●

Three-phase overvoltage protection, instance 3 ●

Positive-sequence undervoltage protection, instance 1 ●

Positive-sequence undervoltage protection, instance 2 ●

Negative-sequence overvoltage protection, instance 1 ●

Negative-sequence overvoltage protection, instance 2 ●

Frequency protection, instance 1 ●

Frequency protection, instance 2 ●

Frequency protection, instance 3 ●

Frequency protection, instance 4 ●

Frequency protection, instance 5 ●

Frequency protection, instance 6 ●

Negative-sequence overcurrent protection for motors, instance 1 ●

Negative-sequence overcurrent protection for motors, instance 2 ●

Loss of load supervision, instance 1 ●

Loss of load supervision, instance 2 ●

Motor load jam protection ●

Motor startup supervision ●

Phase reversal protection ●

ABB 5
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 1. Supported functions, continued


Functionality CTs & VTs

Thermal overload protection for motors ●

Motor differential protection ●

Circuit breaker failure protection, instance 1 ●

Circuit breaker failure protection, instance 2 ●

Master trip, instance 1 ●

Master trip, instance 2 ●

Arc protection, instance 1 ○

Arc protection, instance 2 ○

Arc protection, instance 3 ○

Multipurpose analog protection, instance 1 ●

Multipurpose analog protection, instance 2 ●

Multipurpose analog protection, instance 3 ●

Multipurpose analog protection, instance 4 ●

Multipurpose analog protection, instance 5 ●

Multipurpose analog protection, instance 6 ●

Multipurpose analog protection, instance 7 ●

Multipurpose analog protection, instance 8 ●

Multipurpose analog protection, instance 9 ●

Multipurpose analog protection, instance 10 ●

Multipurpose analog protection, instance 11 ●

Multipurpose analog protection, instance 12 ●

Control

Circuit-breaker control, instance 1 ●

Circuit-breaker control, instance 2 ●

Disconnector control, instance 1 ●

Disconnector control, instance 2 ●

Earthing switch control, instance 1 ●

Disconnector control, instance 3 ●

Disconnector control, instance 4 ●

Earthing switch control, instance 2 ●

Disconnector position indication, instance 1 ●

Disconnector position indication, instance 2 ●

Earthing switch position indication, instance 1 ●

Disconnector position indication, instance 3 ●

Disconnector position indication, instance 4 ●

Earthing switch position indication, instance 2 ●

Emergency startup ●

Synchronism and energizing check ●

6 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 1. Supported functions, continued


Functionality CTs & VTs

Condition monitoring

Circuit-breaker condition monitoring, instance 1 ●

Circuit-breaker condition monitoring, instance 2 ●

Trip circuit supervision, instance 1 ●

Trip circuit supervision, instance 2 ●

Current circuit supervision ●

Fuse failure supervision ●

Runtime counter for machines and devices, instance 1 ●

Runtime counter for machines and devices, instance 2 ●

Measurement

Three-phase current measurement, instance 1 ●

Three-phase current measurement, instance 2 ●

Sequence current measurement ●

Residual current measurement ●

Three-phase voltage measurement ●

Residual voltage measurement ●

Sequence voltage measurement ●

Three-phase power and energy measurement ●

Frequency measurement ●

Other

Minimum pulse timer (2 pcs), instance 1 ●

Minimum pulse timer (2 pcs), instance 2 ●

Minimum pulse timer (2 pcs), instance 3 ●

Minimum pulse timer (2 pcs), instance 4 ●

Minimum pulse timer (2 pcs, second resolution), instance 1 ●

Minimum pulse timer (2 pcs, second resolution), instance 2 ●

Minimum pulse timer (2 pcs, minute resolution), instance 1 ●

Minimum pulse timer (2 pcs, minute resolution), instance 2 ●

Pulse timer (8 pcs), instance 1 ●

Pulse timer (8 pcs), instance 2 ●

Time delay off (8 pcs), instance 1 ●

Time delay off (8 pcs), instance 2 ●

Time delay off (8 pcs), instance 3 ●

Time delay off (8 pcs), instance 4 ●

Time delay on (8 pcs), instance 1 ●

Time delay on (8 pcs), instance 2 ●

Time delay on (8 pcs), instance 3 ●

Time delay on (8 pcs), instance 4 ●

ABB 7
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 1. Supported functions, continued


Functionality CTs & VTs

Set reset (8 pcs), instance 1 ●

Set reset (8 pcs), instance 2 ●

Set reset (8 pcs), instance 3 ●

Set reset (8 pcs), instance 4 ●

Move (8 pcs), instance 1 ●

Move (8 pcs), instance 2 ●

Move (8 pcs), instance 3 ●

Move (8 pcs), instance 4 ●

Generic control points, instance 1 ●

Generic control points, instance 2 ●

Generic control points, instance 3 ●

Remote generic control points ●

Local generic control points ●

Generic up-down counters, instance 1 ●

Generic up-down counters, instance 2 ●

Generic up-down counters, instance 3 ●

Generic up-down counters, instance 4 ●

Generic up-down counters, instance 5 ●

Generic up-down counters, instance 6 ●

Generic up-down counters, instance 7 ●

Generic up-down counters, instance 8 ●

Generic up-down counters, instance 9 ●

Generic up-down counters, instance 10 ●

Generic up-down counters, instance 11 ●

Generic up-down counters, instance 12 ●

Programmable buttons (16 buttons) ●

Logging functions

Disturbance recorder ●

Fault recorder ●

Sequence event recorder ●

Load profile ●

● = Included,○ = Optional at the time of the order

8 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

3. Protection functions 4. Application


The IED offers all the functionality needed to manage motor REM620 has been designed to be the main protection in the
starts and normal operation, also including protection and manufacturing and process industry for medium-sized and
fault clearance in abnormal situations. The main features of large asynchronous motors that require also differential
the IED include motor differential protection, thermal overload protection. Typically, the motor protection IED is used with
protection, motor startup time supervision, locked rotor circuit breaker- or contactor-controlled MV motors and with
protection and protection against too frequent motor starts. contactor-controlled, medium-sized and large LV motors, in a
The IED also incorporates non-directional earth-fault variety of drives. These include both continuously and
protection, negative phase-sequence current unbalance intermittently operated asynchronous motor drives with
protection and backup overcurrent protection. Furthermore, varying load.
the IED offers motor running stall protection, loss-of-load
supervision and phase-reversal protection. REM620 can be used with either single- or double-busbar
configurations with either one or two breakers and with
The default configuration additionally offers directional earth- numerous switching device configurations. It supports a
fault protection, three-phase undervoltage protection, substantial number of both manually and motor-operated
negative phase-sequence overvoltage and positive-sequence disconnectors and earthing switches, and it is capable of
undervoltage protection. Furthermore, the configuration offers running large configurations. The number of controllable
frequency protection including overfrequency, underfrequency devices depends on the number of inputs and outputs left
and rate-of-change frequency protection modes. free from other application needs. The number of available I/
Os can be increased with the RIO600 Remote I/O device.
The RTD/mA module offered as an option for the default
configuration enabled the use of the optional multipurpose REM620 offers extensive possibilities to tailor the
protection function which can be used for tripping and alarm configurations to end application requirements. The tool suite
purposes using RTD/mA measuring data or analog values via for all Relion IEDs is Protection and control IED manager
GOOSE messages. PCM600, which contains all the necessary tools for
configuring the device, including functionality,
In certain motor drives of special importance, there must be a parameterization, the HMI and communication.
possibility to override the motor thermal overload protection
to perform an emergency start of a hot motor. To enable an REM620 is thoroughly adapted for earth-fault protection. By
emergency hot start, REM620 offers a forced start execution using cable current transformers, a sensitive and reliable
feature. earth-fault protection can be achieved. Also phase-current
transformers in Holmgreen (summation) connection can be
Enhanced with optional hardware and software, the IED also used for earth-fault protection. To further improve the arc
features three light detection channels for arc fault protection fault protection and minimize the effects of an arc fault, the
of the circuit breaker, busbar and cable compartment of 620 series IEDs ordered with the arc fault protection option
metal-enclosed indoor switchgear. can be equipped with an I/O card featuring high-speed
outputs operating in one millisecond.
The arc fault protection sensor interface is available on the
optional communication module. Fast tripping increases staff
safety and security and limits material damage in an arc fault
situation. Optional high speed outputs help to minimize the
arc impacts.

ABB 9
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

REF620
Example conf. N
ANSI IEC
Io
25 SYNC
3U 47O-/59 U2>/3U>
47U+/27 U1</3U<
Uo
49F 3Ith>F
50L/50NL ARC
3I
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67/67N 3I→/Io→
81 f>/f<,df/dt
81LSH UFLS/R

3I 3I
3I
3U Uo

Io Io Io

RTD RTD

3I 3I

RTD

REM620 REF620 REM620 REM620


Example conf. N Example conf. N Example conf. N Example conf. N
ANSI IEC ANSI IEC ANSI IEC ANSI IEC

47O-/59 U2>/3U> 47O-/59 U2>/3U> 47O-/59 U2>/3U> 47O-/59 U2>/3U>


47U+/27 U1</3U< 47U+/27 U1</3U< 47U+/27 U1</3U< 47U+/27 U1</3U<
49,66,48,51LR Is2t n< 50L/50NL ARC 49,66,48,51LR Is2t n< 49,66,48,51LR Is2t n<
49M 3Ith>M 59G Uo> 49M 3Ith>M 49M 3Ith>M
50L/50NL ARC 60 FUSEF 50L/50NL ARC 50L/50NL ARC
50P/51P 3I>>> 81 f>/f<,df/dt 50P/51P 3I>>> 50P/51P 3I>>>
51LR Ist> 51LR Ist> 51LR Ist>
51P/51N 3I/Io 51P/51N 3I/Io 51P/51N 3I/Io
81 f>/f<,df/dt 81 f>/f<,df/dt 81 f>/f<,df/dt
87M 3dI>M 87M 3dI>M ESTART ESTART
ESTART ESTART ESTART ESTART MAP MAP
MAP MAP MAP MAP OPTM OPTS
OPTM OPTS OPTM OPTS

GUID-6F004016-C4D6-4BBB-B046-18FDDED4346A V1 EN

Figure 2. A dedicated motor substation with the different motor starting methods combined in one switchgear

10 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

REM620
Example conf. N
3U Uo ANSI IEC

47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
3I 49M 3Ith>M
50L/50NL ARC
50P/51P 3I>>>
51LR Ist>
Io 51P/51N 3I/Io
81 f>/f<,df/dt
87M 3dI>M
ESTART ESTART
MAP MAP
OPTM OPTS

RTD

3I

GUID-012EABD8-57B0-496C-B5C3-B726B0DAF97D V1 EN

Figure 3. Direct-on-load starting method, with the motor directly connected to the medium-voltage switchgear

REM620
Example conf. N
ANSI IEC
3U Uo
47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
49M 3Ith>M
50L/50NL ARC
3I 50P/51P 3I>>>
51LR Ist>
51P/51N 3I/Io
81 f>/f<,df/dt
Io 87M 3dI>M
ESTART ESTART
MAP MAP
OPTM OPTS

RTD

3I

GUID-96593CE9-3E6D-46F5-AE9E-619C73CFBB39 V1 EN

Figure 4. Motor started over reactor choke, which decreases motor starting current over the reactor and helps handle the load flow in the
medium-voltage network

ABB 11
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

REM620
Example conf. N
ANSI IEC
3U Uo
47O-/59 U2>/3U>
47U+/27 U1</3U<
49,66,48,51LR Is2t n<
3I 49M 3Ith>M
50L/50NL ARC
50P/51P 3I>>>
51LR Ist>
Io 51P/51N 3I/Io
81 f>/f<,df/dt
ESTART ESTART
MAP MAP
OPTM OPTS

RTD

GUID-D4876FE7-FC25-4F7E-BCF2-C6C3508BBF96 V1 EN

Figure 5. Motor starting method with variable-frequency drives VFD that make the control easier and optimize energy consumption

5. Supported ABB solutions At the substation level COM600 uses the data content of the
ABB’s 620 series protection and control IEDs together with bay level IEDs to offer enhanced substation level functionality.
the Grid Automation controller COM600 constitute a genuine COM600 features a Web browser-based HMI providing a
IEC 61850 solution for reliable power distribution in utility and customizable graphical display for visualizing single line mimic
industrial power systems. To facilitate and streamline the diagrams for switchgear bay solutions. Furthermore, the Web
system engineering ABB’s IEDs are supplied with HMI of COM600 offers an overview of the whole substation,
Connectivity Packages containing a compilation of software including IED-specific single-line diagrams, thus enabling
and IED-specific information including single-line diagram convenient information accessibility. To enhance personnel
templates, a full IED data model including event and safety, the Web HMI also enables remote access to
parameter lists. By utilizing the Connectivity Packages the substation devices and processes. Furthermore, COM600
IEDs can be readily configured via the PCM600 Protection can be used as a local data warehouse for technical
and Control IED Manager and integrated with the Grid documentation of the substation and for network data
Automation controller COM600 or the MicroSCADA Pro collected by the IEDs. The collected network data facilitates
network control and management system. extensive reporting and analyzing of network fault situations
using the data historian and event handling features of
The 620 series IEDs offer native support for the IEC 61850 COM600. The data historian can be used for accurate
standard also including binary and analog horizontal GOOSE process performance monitoring by following process and
messaging. Compared to traditional hard-wired inter-device equipment performance calculations with real-time and
signaling, peer-to-peer communication over a switched history values. Better understanding of the process behaviour
Ethernet LAN offers an advanced and versatile platform for by joining time-based process measurements with production
power system protection. Fast software-based and maintenance events helps the user in understanding the
communication, continuous supervision of the integrity of the process dynamics.
protection and communication system, and inherent flexibility
for reconfiguration and upgrades are among the distinctive COM600 also features gateway functionality providing
features of the protection system approach enabled by the seamless connectivity between the substation IEDs and
full implementation of the IEC 61850 substation automation network-level control and management systems such as
standard. MicroSCADA Pro and System 800xA

Table 2. Supported ABB solutions

Product Version

Grid Automation controller COM600 4.0 or later

MicroSCADA Pro SYS 600 9.3 FP2 or later

System 800xA 5.1 or later

12 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

GUID-8E5ABC5B-5A9B-4248-B2B1-DB5AFA42D801 V1 EN

Figure 6. Industrial power system example using 620 series IEDs, Grid Automation controller COM600 and System 800xA

6. Control The suitability of the binary outputs of the IED which have
REM620 integrates functionality for the control of circuit been selected for the controlling of primary devices should be
breakers, disconnectors and earth switches via the front carefully verified, for example, the make and carry as well as
panel HMI or by means of remote controls. The IED includes the breaking capacity. In case the requirements for the
two circuit breaker control blocks. In addition to the circuit control circuit of the primary device are not met, the use of
breaker control, the IED features four disconnector control external auxiliary relays should be considered.
blocks intended for the motor-operated control of
disconnectors or circuit breaker truck. Furthermore, the IED The graphical LCD of the IED's HMI includes a single-line
offers two control blocks intended for the motor-operated diagram (SLD) with position indication for the relevant primary
control of earthing switch. On top of that, the IED includes devices. Interlocking schemes required by the application are
additional four disconnector position indication blocks and configured using the Signal Matrix or the Application
two earth switch position indication blocks usable with Configuration tools in PCM600.
manually-only controlled disconnectors and earth switches.
A synchrocheck function is incorporated to ensure that the
Two physical binary inputs and two physical binary outputs voltage, phase angle and frequency on either side of an open
are needed in the IED for each controllable primary device circuit breaker satisfy the conditions for a safe
taken into use. Depending on the chosen hardware interconnection of two networks.
configuration of the IED, the number of binary inputs and
binary outputs varies. In case the amount of available binary 7. Measurement
inputs or outputs of the chosen hardware configuration is not The IED continuously measures the phase currents and the
sufficient, connecting an external input or output module, for neutral current. Furthermore, the IED measures the phase
example RIO600, to the IED can extend binary inputs and voltages and the residual voltage. In addition, the IED
outputs utilizable in the IED configuration. The binary inputs calculates the symmetrical components of the currents and
and outputs of the external I/O module can be used for the voltages, the system frequency, the active and reactive
less time-critical binary signals of the application. The power, the power factor, the active and reactive energy
integration enables releasing of some initially reserved binary values as well as the demand value of current and power over
inputs and outputs of the IED. a user-selectable preset time frame. Calculated values are

ABB 13
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

also obtained from the protections and condition monitoring measurement values at the moment when any protection
functions of the IED. function starts. Both Min. and Max. current demand values
are recorded with time stamp. Also both Min. and Max.
The IED is also offered with RTD/mA inputs and can measure power demand values (P, Q, S) are recorded with time stamp.
up to 16 analog signals such as stator winding and bearing By default, the records are stored in a nonvolatile memory.
temperatures via the 12 RTD inputs or the four mA inputs
using transducers. Furthermore, the IED includes a load profile recorder capable
of storing measurement values into the IED's memory. The
The values measured can be accessed locally via the user selected measurement values averaged over the selected
interface on the IED front panel or remotely via the period, ranging from one minute to three hours, are stored in
communication interface of the IED. The values can also be a nonvolatile memory. Depending on the selected
accessed locally or remotely using the web-browser based measurements and averaging period, the overall length of the
user interface. load profile recording ranges from some days to several
months, even a year, making this feature suitable for
8. Disturbance recorder monitoring long-time load behavior for the interested loads.
The IED is provided with a disturbance recorder featuring up
to 12 analog and 64 binary signal channels. The analog 11. Trip-circuit supervision
channels can be set to record either the waveform or the The trip-circuit supervision continuously monitors the
trend of the currents and voltages measured. availability and operability of the trip circuit. It provides open-
circuit monitoring both when the circuit breaker is in its
The analog channels can be set to trigger the recording
closed and in its open position. It also detects loss of circuit-
function when the measured value falls below or exceeds the
breaker control voltage.
set values. The binary signal channels can be set to start a
recording on the rising or the falling edge of the binary signal
or both. 12. Self-supervision
The IED’s built-in self-supervision system continuously
By default, the binary channels are set to record external or monitors the state of the IED hardware and the operation of
internal IED signals, for example the start or trip signals of the the IED software. Any fault or malfunction detected is used
IED stages, or external blocking or control signals. Binary IED for alerting the operator.
signals, such as a protection start or trip signal, or an external
IED control signal over a binary input can be set to trigger the
recording. The recorded information is stored in a nonvolatile 13. Fuse failure supervision
memory and can be uploaded for subsequent fault analysis. The fuse failure supervision detects failures between the
voltage measurement circuit and the IED. The failures are
detected by the negative-sequence based algorithm or by the
9. Event log delta voltage and delta current algorithm. Upon the detection
To collect sequence-of-events (SoE) information, the IED of a failure the fuse failure supervision function activates an
incorporates a non-volatile memory with a capacity of storing alarm and blocks voltage-dependent protection functions
1024 events with associated time stamps. The non-volatile from unintended operation.
memory retains its data also in case the IED temporarily loses
its auxiliary supply. The event log facilitates detailed pre- and
post-fault analyses of feeder faults and disturbances. The 14. Current circuit supervision
increased capacity to process and store data and events in Current circuit supervision is used for detecting faults in the
the IED offers prerequisites to support the growing current transformer secondary circuits. On detecting of a fault
information demand of future network configurations. the current circuit supervision function activates an alarm LED
and blocks certain protection functions to avoid unintended
The SoE information can be accessed locally via the user operation. The current circuit supervision function calculates
interface on the IED front panel or remotely via the the sum of the phase currents from the protection cores and
communication interface of the IED. The information can compares the sum with the measured single reference current
further be accessed, either locally or remotely, using the web- from a core balance current transformer or from separate
browser based user interface. cores in the phase current transformers.

10. Recorded data 15. Access control


The IED has the capacity to store the records of 128 latest To protect the IED from unauthorized access and to maintain
fault events. The records enable the user to analyze the information integrity, the IED is provided with a four-level, role-
power system events. The available measurement modes based authentication system with administrator-
include DFT, RMS and peak-to-peak. Fault records store IED programmable individual passwords for the viewer, operator,

14 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

engineer and administrator level. The access control applies motor. The third option is a high-speed output board
to the front-panel user interface, the web-browser based user including eight binary inputs and three high-speed outputs.
interface and the PCM600 tool. The high-speed outputs have a shorter activation time
compared to the conventional mechanical output relays,
shortening the overall IED operation time with very time-
16. Inputs and outputs
critical applications like arc protection. The high-speed
The IED is equipped with six phase current inputs, one
outputs are freely configurable in the IED application and not
residual-current input, three phase voltage inputs, one
limited to arc protection only.
residual-voltage input and one phase-to-phase voltage for
syncrocheck input. In addition to current and voltage The rated values of the current and voltage inputs are
measurements, the IED's basic configuration includes 12 settable parameters of the IED. In addition, the binary input
binary inputs and 10 binary outputs. Additionally, basic thresholds are selectable within the range of 18…176 V DC
configuration offers six RTD inputs and two mA inputs. The by adjusting the IED’s parameter settings.
phase current inputs and the residual-current inputs are rated
1/5 A, that is, the inputs allow the connection of either 1 A or All binary input and output contacts are freely configurable
5 A secondary current transformers. The optional sensitive with the Signal Matrix or Application Configuration tool of
residual-current input 0.2/1 A is normally used in applications PCM600.
requiring sensitive earth-fault protection and featuring core
balance current transformers. The three phase voltage inputs See the Input/output overview table and the terminal
and the residual-voltage input covers the rated voltages 60... diagrams for detailed information about the inputs and
210 V. Both phase-to-phase voltages and phase-to-earth outputs.
voltages can be connected.
If the number of the IED’s own inputs and outputs does not
As an optional addition, the IED basic configuration includes cover all the intended purposes, connecting to an external
one empty slot which can be equipped with one of the input or output module, for example RIO600, increases the
following optional modules. The first option, additional binary number of binary inputs and outputs utilizable in the IED
inputs and outputs module, adds eight binary inputs and four configuration. In this case, the external inputs and outputs are
binary outputs to the IED. This option is especially needed connected to the IED via IEC 61850 GOOSE to reach fast
when connecting the IED to several controllable objects. The reaction times between the IED and RIO600 information. The
second option, an additional RTD/mA input module, needed binary input and output connections between the IED
increases the IED with six RTD inputs and two mA inputs and RIO600 units can be configured in a PCM600 tool and
when additional sensor measurements e.g. for temperatures, then utilized in the IED configuration.
pressures, levels and so on are of interest with the protected

Table 3. Input/output overview table

Conf. Analog channels Binary channels

CT VT RTD/mA BI BO

A 7 5 6/2 12(20)1) 10(14)1)

6/2 12(20)2) 10(13)2)

6/2(12/4)3) 12 10

1) With optional BIO0005 module


2) With optional BIO0007 module
3) With optional RTD0003 module

ABB 15
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

17. Station communication features a galvanic communication module with two galvanic
The IED supports a range of communication protocols and one optical Ethernet network interfaces or three galvanic
including IEC 61850, IEC 60870-5-103, Modbus ® and DNP3. interfaces. The third Ethernet interface provides connectivity
Operational information and controls are available through for any other Ethernet devices to an IEC 61850 station bus
these protocols. However, some communication functionality, inside in a switchgear bay. The redundant solution can be
for example, horizontal communication between the IEDs, is applied to the Ethernet-based IEC 61850, Modbus and DNP3
only enabled by the IEC 61850 communication protocol. protocols.

The IEC 61850 communication implementation supports Ethernet network redundancy can be achieved using the high-
monitoring and control functions. Additionally, parameter availability seamless redundancy (HSR) protocol or the
settings, disturbance recordings and fault records can be parallel redundancy protocol (PRP) or a with self-healing ring
accessed using the IEC 61850 protocol. Disturbance using RSTP in managed switches. Ethernet redundancy can
recordings are available to any Ethernet-based application in be applied to all Ethernet-based IEC 61850, Modbus and
the standard COMTRADE file format. The IED supports DNP3 protocols.
simultaneous event reporting to five different clients on the
station bus. The IED can exchange signals with other IEDs The IEC 61850 standard specifies network redundancy which
using the IEC 61860 protocol. improves the system availability for the substation
communication. The network redundancy is based on two
The IED can send binary signals to other IEDs (so called complementary protocols defined in the IEC 62439-3
horizontal communication) using the IEC 61850-8-1 GOOSE standard: PRP and HSR protocols. Both the protocols are
(Generic Object Oriented Substation Event) profile. Binary able to overcome a failure of a link or switch with a zero
GOOSE messaging can, for example, be employed for switch-over time. In both the protocols, each network node
protection and interlocking-based protection schemes. The has two identical Ethernet ports dedicated for one network
IED meets the GOOSE performance requirements for tripping connection. The protocols rely on the duplication of all
applications in distribution substations, as defined by the IEC transmitted information and provide a zero switch-over time if
61850 standard. The IED also supports the sending and the links or switches fail, thus fulfilling all the stringent real-
receiving of analog values using GOOSE messaging. Analog time requirements of substation automation.
GOOSE messaging enables fast transfer of analog
measurement values over the station bus, thus facilitating for In PRP, each network node is attached to two independent
example sharing of RTD input values, such as surrounding networks operated in parallel. The networks are completely
temperature values, to other IED applications. separated to ensure failure independence and can have
different topologies. The networks operate in parallel, thus
For redundant Ethernet solution, the IED offers a fibre-optic providing zero-time recovery and continuous checking of
communication module providing two optical and one redundancy to avoid failures.
galvanic Ethernet network interfaces. Alternatively, the IED

16 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

COM600
SCADA

Ethernet switch Ethernet switch


IEC 61850 PRP

REF615 REF620 RET620 REM620 REF615


GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V1 EN

Figure 7. Parallel redundancy protocol (PRP) solution

HSR applies the PRP principle of parallel operation to a single the sender node discards the frame to avoid loops. The HSR
ring. For each message sent, the node sends two frames, ring with 620 series IEDs supports the connection of up to
one through each port. Both the frames circulate in opposite thirty IEDs. If more than 30 IEDs are to be connected, it is
directions over the ring. Every node forwards the frames it recommended to split the network into several rings to
receives from one port to another to reach the next node. guarantee the performance for real-time applications.
When the originating sender node receives the frame it sent,

COM600
SCADA Devices not supporting HSR

Ethernet switch

Redundancy Redundancy Redundancy


Box Box Box

IEC 61850 HSR

REF615 REF620 RET620 REM620 REF615

GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN

Figure 8. High availability seamless redundancy (HSR) solution

The choice between the HSR and PRP redundancy protocols standard Rapid Spanning Tree l Protocol (RSTP) support. The
depends on the required functionality, cost and complexity. managed switch controls the consistency of the loop, routes
the data and corrects the data flow in case of a
The self-healing Ethernet ring solution enables a cost-efficient communication switch-over. The IEDs in the ring topology act
communication ring controlled by a managed switch with as unmanaged switches forwarding unrelated data traffic. The
ABB 17
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Ethernet ring solution supports the connection of up to thirty self-healing Ethernet ring solution avoids single point of failure
620 series IEDs. If more than 30 IEDs are to be connected, it concerns and improves the reliability of the communication.
is recommended to split the network into several rings. The

Client A Client B

Network A
Network B

Managed Ethernet switch Managed Ethernet switch


with RSTP support with RSTP support

GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN

Figure 9. Self-healing Ethernet ring solution

All communication connectors, except for the front port supported. DNP3 can also be used at the same time with the
connector, are placed on integrated optional communication IEC 61850 protocol.
modules. The IED can be connected to Ethernet-based
communication systems via the RJ-45 connector (100Base- When the IED uses the RS-485 bus for the serial
TX) or the fibre-optic LC connector (100Base-FX). If communication, both two- and four wire connections are
connection to a serial bus is required, the 10-pin RS-485 supported. Termination and pull-up/down resistors can be
screw-terminal or the fibre-optic ST connector can be used. configured with jumpers on the communication card so
external resistors are not needed.
Modbus implementation supports RTU, ASCII and TCP
modes. Besides standard Modbus functionality, the IED The IED supports the following time synchronization methods
supports retrieval of time-stamped events, changing the with a time-stamping resolution of 1 ms:
active setting group and uploading of the latest fault records.
Ethernet-based:
If a Modbus TCP connection is used, five clients can be
• SNTP (Simple Network Time Protocol)
connected to the IED simultaneously. Further, Modbus serial
and Modbus TCP can be used in parallel, and if required both
IEC 61850 and Modbus protocols can be run simultaneously. With special time synchronization wiring:
• IRIG-B (Inter-Range Instrumentation Group - Time Code
The IEC 60870-5-103 implementation supports two parallel Format B)
serial bus connections to two different masters. Besides
basic standard functionality, the IED supports changing of the
active setting group and uploading of disturbance recordings In addition, the IED supports time synchronization via the
in IEC 60870-5-103 format. Further, IEC 60870-5-103 can be following serial communication protocols:
used at the same time with the IEC 61850 protocol. • Modbus
• DNP3
DNP3 supports both serial and TCP modes for connection to • IEC 60870-5-103
one master. Further, changing of the active setting group is

18 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 4. Supported station communication interfaces and protocols

Interfaces/Protocols Ethernet Serial

100BASE-TX RJ-45 100BASE-FX LC RS-232/RS-485 Fibre-optic ST

IEC 61850 ● ● - -

MODBUS RTU/ASCII - - ● ●

MODBUS TCP/IP ● ● - -

DNP3 (serial) - - ● ●

DNP3 TCP/IP ● ● - -

IEC 60870-5-103 - - ● ●
● = Supported

ABB 19
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

18. Technical data

Table 5. Dimensions

Description Value

Width Frame 262.2 mm

Case 246 mm

Height Frame 177 mm, 4U

Case 160 mm

Depth 201 mm

Weight Complete IED max. 5.1 kg

Plug-in unit only max. 3.0 kg

Table 6. Power supply

Description Type 1 Type 2

Uaux nominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC

48, 60, 110, 125, 220, 250 V DC

Maximum interruption time in the auxiliary 50 ms at Un rated


DC voltage without resetting the IED

Uaux variation 38...110% of Un (38...264 V AC) 50...120% of Un (12...72 V DC)

80...120% of Un (38.4...300 V DC)

Start-up threshold 19.2 V DC (24 V DC × 80%)

Burden of auxiliary voltage supply under DC <12.0 W (nominal)/<19.0 W (max) DC <12.0 W (nominal)/<19.0 W (max)
quiescent (Pq)/operating condition AC <13.0 W (nominal)/<21.0 W (max)

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)

Fuse type T4A/250 V

Table 7. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Current inputs Rated current, In 0.2/1 A1) 1/5 A2)

Thermal withstand capability:

• Continuously 4A 20 A

• For 1 s 100 A 500 A

Dynamic current withstand:

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

Voltage inputs Rated voltage 60...210 V AC

Voltage withstand:

• Continuous 240 V AC

• For 10 s 360 V AC

Burden at rated voltage <0.05 VA

1) Ordering option for residual current input


2) Residual current and/or phase current

20 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 8. Binary inputs

Description Value

Operating range ±20% of the rated voltage

Rated voltage 24...250 V DC

Current drain 1.6...1.9 mA

Power consumption 31.0...570.0 mW

Threshold voltage 18...176 V DC

Reaction time 3 ms

Table 9. RTD/mA measurement

Description Value

RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427

Supported resistance range 0...2 kΩ

Maximum lead resistance (three-


wire measurement) 25 Ω per lead

Isolation 2 kV (inputs to protective earth)

Response time <4 s

RTD/resistance sensing current Maximum 0.33 mA rms

Operation accuracy Resistance Temperature

± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C

mA inputs Supported current range 0…20 mA

Current input impedance 44 Ω ± 0.1%

Operation accuracy ±0.5% or ±0.01 mA

Table 10. Signal output with high make and carry

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms 1 A/0.25 A/0.15 A

Minimum contact load 100 mA at 24 V AC/DC

1) X100: SO1
X105: SO1, SO2, when any of the IEDs is equipped with BIO0005.
X115: SO1, SO2 when REF620 or REM620 is equipped with BIO0005

ABB 21
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 11. Signal outputs and IRF output

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 15 A

Breaking capacity when the control-circuit time constant L/R < 40 ms, 1 A / 0.25 A / 0.15 A
at 48/110/220 V DC

Minimum contact load 10 mA at 5 V AC/DC

1) X100: IRF,SO2
X105: SO3, SO4, when any of the IEDs is equipped with BIO0005
X115:SO3, SO4, when REF620 or REM620 is equipped with BIO0005

Table 12. Double-pole power outputs with TCS function X100: PO3 and PO4

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC (two contacts connected in series)

Minimum contact load 100 mA at 24 V AC/DC

Trip-circuit monitoring (TCS):

• Control voltage range 20...250 V AC/DC

• Current drain through the monitoring circuit ~1.5 mA

• Minimum voltage over the TCS contact 20 V AC/DC (15...20 V)

1) PSM0003: PO3, PSM0004: PO3, PSM0003: PO4 and PSM0004: PO4.

Table 13. Signal/trip output with high make and carry and with TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R < 40 ms, 1A/0.25A/0.15A
at 48/110/220 V DC (two contacts connected in series)

Minimum contact load 100 mA at 24 V AC/DC

22 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 14. Single-pole power output relays X100: PO1 and PO2

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC

Minimum contact load 100 mA at 24 V AC/DC

Table 15. High-speed output HSO

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 6A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R < 40 ms, 5 A/3 A/1 A
at 48/110/220 V DC

Start 1 ms

Reset 20 ms, resistive load

1) X105: HSO1, HSO2 HSO3, when any of the IEDs is equipped with BIO0007

Table 16. Front port Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s

Table 17. Station communication link, fibre-optic

Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)

LC MM 62.5/125 or 50/125 μm 1300 nm 2 km <8 dB


glass fibre core

ST MM 62.5/125 or 50/125 μm 820-900 nm 1 km <11 dB


glass fibre core

1) (MM) multi-mode fibre, (SM) single-mode fibre


2) Maximum allowed attenuation caused by connectors and cable together

ABB 23
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 18. IRIG-B

Description Value

IRIG time code format B004, B0051)

Isolation 500V 1 min.

Modulation Unmodulated

Logic level TTL Level

Current consumption 2...4 mA

Power consumption 10...20 mW

1) According to 200-04 IRIG -standard

Table 19. Lens sensor and optical fibre for arc protection

Description Value

Fibre-optic cable including lens 1.5 m, 3.0 m or 5.0 m

Normal service temperature range of the lens -40...+100°C

Maximum service temperature range of the lens, max 1 h +140°C

Minimum permissible bending radius of the connection fibre 100 mm

Table 20. Degree of protection of flush-mounted IED

Description Value

Front side IP 54

Table 21. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+85ºC (<16h)1)2)

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude Up to 2000 m

Transport and storage temperature range -40...+85ºC

1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC

24 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 22. Electromagnetic compatibility tests

Description Type test value Reference

1 MHz/100 kHz burst disturbance test: IEC 61000-4-18


IEC 60255-22-1, class III
IEEE C37.90.1-2002

• Common mode 2.5 kV

• Differential mode 2.5 kV

3 MHz, 10 MHz and 30 MHz burst disturbance IEC 61000-4-18


test: IEC 60255-22-1, class III

• Common mode 2.5 kV

Electrostatic discharge test: IEC 61000-4-2


IEC 60255-22-2
IEEE C37.90.3-2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference test:

10 V (rms) IEC 61000-4-6


f=150 kHz...80 MHz IEC 60255-22-6, class III

10 V/m (rms) IEC 61000-4-3


f=80...2700 MHz IEC 60255-22-3, class III

10 V/m ENV 50204


f=900 MHz IEC 60255-22-3, class III

20 V/m (rms) IEEE C37.90.2-2004


f=80...1000 MHz

Fast transient disturbance test: IEC 61000-4-4


IEC 60255-22-4
IEEE C37.90.1-2002

• All ports 4 kV

Surge immunity test: IEC 61000-4-5


IEC 60255-22-5

• Communication 1 kV, line-to-earth

• Other ports 4 kV, line-to-earth


2 kV, line-to-line

Power frequency (50 Hz) magnetic field IEC 61000-4-8


immunity test:

• Continuous 300 A/m


• 1...3 s 1000 A/m

Pulse magnetic field immunity test: 1000 A/m IEC 61000-4-9


6.4/16 µs

Damped oscillatory magnetic field immunity IEC 61000-4-10


test:

• 2s 100 A/m

• 1 MHz 400 transients/s

Voltage dips and short interruptions: 30%/10 ms IEC 61000-4-11


60%/100 ms
60%/1000 ms
>95%/5000 ms

ABB 25
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 22. Electromagnetic compatibility tests, continued


Description Type test value Reference

Conducted common mode disturbances: 15 Hz...150 kHz IEC 61000-4-16


Test level 3 (10/1/10 V rms)

Emission tests: EN 55011, class A


IEC 60255-25

• Conducted

0.15-0.50 MHz < 79 dB(µV) quasi peak


< 66 dB(µV) average

0.5-30 MHz < 73 dB(µV) quasi peak


< 60 dB(µV) average

• Radiated

30-230 MHz < 40 dB(µV/m) quasi peak, measured at 10 m


distance

230-1000 MHz < 47 dB(µV/m) quasi peak, measured at 10 m


distance

Table 23. Insulation tests

Description Type test value Reference

Dielectric tests 2 kV, 50 Hz, 1 min IEC 60255-5 and


500 V, 50 Hz, 1 min, communication IEC 60255-27

Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27

Insulation resistance measurements >100 MΏ, 500 V DC IEC 60255-5 and


IEC 60255-27

Protective bonding resistance <0.1 Ώ, 4 A, 60 s IEC 60255-27

Table 24. Mechanical tests

Description Reference Requirement

Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc) Class 2


IEC 60255-21-1

Shock and bump test IEC 60068-2-27 (test Ea shock) Class 2


IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2

Seismic test IEC 60255-21-3 Class 2

26 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 25. Environmental tests

Description Type test value Reference

Dry heat test • 96 h at +55ºC IEC 60068-2-2


• 16 h at +85ºC1)

Dry cold test • 96 h at -25ºC IEC 60068-2-1


• 16 h at -40ºC

Damp heat test • 6 cycles (12 h + 12 h) at +25°C…+55°C, IEC 60068-2-30


humidity >93%

Change of temperature test • 5 cycles (3 h + 3 h) IEC60068-2-14


at -25°C...+55°C

Storage test • 96 h at -40ºC IEC 60068-2-1


• 96 h at +85ºC IEC 60068-2-2

1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C

Table 26. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)


EN 60255-1 (2009)

Table 27. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)


EN 60255-26 (2007)

Table 28. RoHS compliance

Description

Complies with RoHS directive 2002/95/EC

ABB 27
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Protection functions

Table 29. Three-phase non-directional overcurrent protection (PHxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

PHLPTOC ±1.5% of the set value or ±0.002 x In

PHHPTOC1) ±1.5% of set value or ±0.002 x In


and (at currents in the range of 0.1…10 x In)
PHIPTOC ±5.0% of the set value
(at currents in the range of 10…40 x In)

Start time 2)3) Minimum Typical Maximum

PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms

PHHPTOC1) and PHLPTOC:


IFault = 2 x set Start value
22 ms 24 ms 25 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1) Not included in REM620


2) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
3) Includes the delay of the signal output contact
4) Includes the delay of the heavy-duty output contact

28 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) main settings

Parameter Function Value (Range) Step

Start Value PHLPTOC 0.05...5.00 x In 0.01

PHHPTOC 0.10...40.00 x In 0.01

PHIPTOC 1.00...40.00 x In 0.01

Time multiplier PHLPTOC 0.05...15.00 0.01

PHHPTOC 0.05...15.00 0.01

Operate delay time PHLPTOC 40...200000 ms 10

PHHPTOC 40...200000 ms 10

PHIPTOC 20...200000 ms 10

Operating curve type1) PHLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

PHHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time

1) For further reference, see Operation characteristics table

Table 31. Three-phase directional overcurrent protection (DPHxPDOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current/voltage measured: fn ±2 Hz

DPHLPDOC Current:
±1.5% of the set value or ±0.002 x In
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°

DPHHPDOC Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle: ±2°

Start time1)2) Minimum Typical Maximum

IFault = 2.0 x set Start value 38 ms 43 ms 46 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Measurement mode and Pol quantity = default, current before fault = 0.0 x I n, voltage before fault = 1.0 x U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20

ABB 29
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 32. Three-phase directional overcurrent protection (DPHxPDOC) main settings

Parameter Function Value (Range) Step

Start value DPHLPDOC 0.05...5.00 x In 0.01

DPHHPDOC 0.10...40.00 x In 0.01

Time multiplier DPHxPDOC 0.05...15.00 0.01

Operate delay time DPHxPDOC 40...200000 ms 10

Directional mode DPHxPDOC 1 = Non-directional


2 = Forward
3 = Reverse

Characteristic angle DPHxPDOC -179...180 deg 1

Operating curve type1) DPHLPDOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

DPHHPDOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

1) For further reference, refer to the Operating characteristics table

Table 33. Non-directional earth-fault protection (EFxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

EFLPTOC ±1.5% of the set value or ±0.002 x In

EFHPTOC ±1.5% of set value or ±0.002 x In


and (at currents in the range of 0.1…10 x In)
EFIPTOC ±5.0% of the set value
(at currents in the range of 10…40 x In)

Start time 1)2) Minimum Typical Maximum

EFIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value 11 ms 12 ms 14 ms

EFHPTOC and EFLPTOC:


IFault = 2 x set Start value 22 ms 24 ms 25 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Measurement mode = default (depends on stage), current before fault = 0.0 x I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20

30 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 34. Non-directional earth-fault protection (EFxPTOC) main settings

Parameter Function Value (Range) Step

Start value EFLPTOC 0.010...5.000 x In 0.005

EFHPTOC 0.10...40.00 x In 0.01

EFIPTOC 1.00...40.00 x In 0.01

Time multiplier EFLPTOC 0.05...15.00 0.01

EFHPTOC 0.05...15.00 0.01

Operate delay time EFLPTOC 40...200000 ms 10

EFHPTOC 40...200000 ms 10

EFIPTOC 20...200000 ms 10

Operating curve type1) EFLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

EFHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

EFIPTOC Definite time

1) For further reference, see Operation characteristics table

ABB 31
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 35. Directional earth-fault protection (DEFxPDEF)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

DEFLPDEF Current:
±1.5% of the set value or ±0.002 x In
Voltage
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°

DEFHPDEF Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°

Start time 1)2) Minimum Typical Maximum

DEFHPDEF
IFault = 2 x set Start value 42 ms 44 ms 46 ms

DEFLPDEF 61 ms 64 ms 66 ms
IFault = 2 x set Start value

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 x I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I n, Start value multiples in range of 1.5 to 20

32 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 36. Directional earth-fault protection (DEFxPDEF) main settings

Parameter Function Value (Range) Step

Start Value DEFLPDEF 0.010...5.000 x In 0.005

DEFHPDEF 0.10...40.00 x In 0.01

Directional mode DEFLPDEF and DEFHPDEF 1=Non-directional


2=Forward
3=Reverse

Time multiplier DEFLPDEF 0.05...15.00 0.01

DEFHPDEF 0.05...15.00 0.01

Operate delay time DEFLPDEF 60...200000 ms 10

DEFHPDEF 40...200000 ms 10

Operating curve type1) DEFLPDEF Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

DEFHPDEF Definite or inverse time


Curve type: 1, 3, 5, 15, 17

Operation mode DEFLPDEF and DEFHPDEF 1=Phase angle


2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88

1) For further reference, refer to the Operating characteristics table

Table 37. Residual overvoltage protection (ROVPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 x set Start value 55 ms 56 ms 58 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact

Table 38. Residual overvoltage protection (ROVPTOV) main settings

Parameter Function Value (Range) Step

Start value ROVPTOV 0.010...1.000 x Un 0.001

Operate delay time ROVPTOV 40...300000 ms 1

ABB 33
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 39. Three phase undervoltage protection (PHPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 0.9 x set Start value 62 ms 64 ms 66 ms

Reset time < 40 ms

Reset ratio Depends on the set Relative hysteresis

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 x Un, Voltage before fault = 1.1 x U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20

Table 40. Three-phase undervoltage protection (PHPTUV) main settings

Parameter Function Value (Range) Step

Start value PHPTUV 0.05...1.20 x Un 0.01

Time multiplier PHPTUV 0.05...15.00 0.01

Operate delay time PHPTUV 60...300000 ms 10

Operating curve type1) PHPTUV Definite or inverse time


Curve type: 5, 15, 21, 22, 23

1) For further reference, see Operation characteristics table

Table 41. Positive-sequence undervoltage protection (PSPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 0.99 x set Start value 51 ms 53 ms 54 ms


UFault = 0.9 x set Start value 43 ms 45 ms 46 ms

Reset time < 40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

34 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 42. Positive-sequence undervoltage protection (PSPTUV) main settings

Parameter Function Value (Range) Step

Start value PSPTUV 0.010...1.200 x Un 0.001

Operate delay time PSPTUV 40...120000 ms 10

Voltage block value PSPTUV 0.01...1.0 x Un 0.01

Table 43. Negative-sequence overvoltage protection (NSPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 × set Start value 33 ms 35 ms 37 ms


UFault = 2.0 × set Start value 24 ms 26 ms 28 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 44. Negative-sequence overvoltage protection (NSPTOV) main settings

Parameter Function Value (Range) Step

Start value NSPTOV 0.010...1.000 x Un 0.001

Operate delay time NSPTOV 40...120000 ms 1

Table 45. Frequency protection (FRPFRQ)

Characteristic Value

Operation accuracy f>/f< ±10 mHz

df/dt ±100 mHz/s (in range |df/dt| < 5 Hz/s)


± 2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s)

Start time f>/f< < 80 ms

df/dt < 120 ms

Reset time < 150 ms

Operate time accuracy ±1.0% of the set value or ±30 ms

ABB 35
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 46. Frequency protection (FRPFRQ) main settings

Parameter Function Value (Range) Step

Operation mode FRPFRQ 1=Freq<


2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt

Start value Freq> FRPFRQ 0.9000...1.2000 xFn 0.0001

Start value Freq< FRPFRQ 0.8000...1.1000 xFn 0.0001

Start value df/dt FRPFRQ -0.200...0.200 xFn /s 0.005

Operate Tm Freq FRPFRQ 80...200000 ms 10

Operate Tm df/dt FRPFRQ 120...200000 ms 10

Table 47. Negative phase-sequence overcurrent protection for motors (MNSPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Start time1)2) Minimum Typical Maximum

IFault = 2.0 x set Start value 22 ms 24 ms 25 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10 to 5.00

Table 48. Negative phase-sequence overcurrent protection for motors (MNSPTOC) main settings

Parameter Function Value (Range) Step

Start value MNSPTOC 0.01...0.50 x In 0.01

Operating curve type MNSPTOC ANSI Def. Time -


IEC Def. Time
Inv. Curve A
Inv. Curve B

Operate delay time MNSPTOC 100...120000 ms 10

Cooling time MNSPTOC 5...7200 s 1

Operation MNSPTOC Off -


On

36 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 49. Loss of load supervision (LOFLPTUC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Start time Typical 300 ms

Reset time < 40 ms

Reset ratio Typical 1.04

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Table 50. Loss of load supervision (LOFLPTUC) main settings

Parameter Function Value (Range) Step

Start value high LOFLPTUC 0.01...1.00 x In 0.01

Start value low LOFLPTUC 0.01...0.50 x In 0.01

Operate delay time LOFLPTUC 400...600000 ms 10

Operation LOFLPTUC Off -


On

Table 51. Motor load jam protection (JAMPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Table 52. Motor load jam protection (JAMPTOC) main settings

Parameter Function Value (Range) Step

Operation JAMPTOC Off -


On

Start value JAMPTOC 0.10...10.00 x In 0.01

Operate delay time JAMPTOC 100...120000 ms 10

ABB 37
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 53. Motor startup supervision (STTPMSU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Start time1)2) Minimum Typical Maximum

IFault = 1.1 x set Start detection A 27 ms 30 ms 34 ms

Operate time accuracy ±1.0% of the set value or ±20 ms

Reset ratio Typical 0.90

1) Current before = 0.0 x I n , f n = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 54. Motor start-up supervision (STTPMSU) main settings

Parameter Function Value (Range) Step

Motor start-up A STTPMSU 1.0...10.0 x In 0.1

Motor start-up time STTPMSU 1...80.0 s 1

Lock rotor time STTPMSU 2...120 s 1

Operation STTPMSU Off -


On

Operation mode STTPMSU IIt -


IIt, CB
IIt & stall
IIt & stall, CB

Restart inhibit time STTPMSU 0...250 min 1

Table 55. Phase reversal protection (PREVPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Start time1)2) Minimum Typical Maximum

IFault = 2.0 x set Start value 22 ms 24 ms 25 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

38 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 56. Phase reversal protection (PREVPTOC) main settings

Parameter Function Value (Range) Step

Start value PREVPTOC 0.05...1.00 x In 0.01

Operate delay time PREVPTOC 100...60000 ms 10

Operation PREVPTOC Off -


On

Table 57. Three-phase thermal overload protection for motors (MPTTR)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

Current measurement: ±1.5% of the set value or ±0.002 x In (at


currents in the range of 0.01...4.00 x In)

Operate time accuracy1) ±2.0% of the theoretical value or ±0.50 s

1) Overload current > 1.2 x Operate level temperature

Table 58. Thermal overload protection for motors (MPTTR) main settings

Parameter Function Value (Range) Step

Env temperature mode MPTTR FLC Only -


Use RTD
Set Amb Temp

Env temperature set MPTTR -20.0...70.0 °C 0.1

Alarm thermal value MPTTR 50.0...100.0 % 0.1

Restart thermal value MPTTR 20.0...80.0 % 0.1

Overload factor MPTTR 1.00...1.20 0.01

Weighting factor p MPTTR 20.0...100.0 0.1

Time constant normal MPTTR 80...4000 s 1

Time constant start MPTTR 80...4000 s 1

Operation MPTTR Off -


On

Table 59. Stabilized differential protection for motors (MPDIF)

Characteristic Value

Operation accuracy At the frequency f = fn

±3% of the set value or ±0.002 x In

Operate time 1)2) Biased low stage Instantaneous Typical 40 ms (±10 ms)
high stage3) Typical 15 ms (±10 ms)

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 20 ms

1) Fn = 50 Hz, results based on statistical distribution of 1000 measurements


2) Includes the delay of the high speed power output contact
3) Ifault = 2 x High operate value

ABB 39
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 60. Stabilized differential protection for motors (MPDIF) main settings

Parameter Function Value (Range) Step

High operate value MPDIF 100...1000 %Ir 10

Low operate value MPDIF 5...30 %Ir 1

Slope section 2 MPDIF 10...50 % 1

End section 1 MPDIF 0...100 %Ir 1

End section 2 MPDIF 100...300 %Ir 1

DC restrain enable MPDIF 0=False


1=True

CT connection type MPDIF 1=Type 1


2=Type 2

CT ratio Cor Line MPDIF 0.40...4.00 0.01

CT ratio Cor Neut MPDIF 0.40...4.00 0.01

Table 61. Circuit breaker failure protection (CCBRBRF)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 x In

Operate time accuracy ±1.0% of the set value or ±20 ms

Retardation time < 20 ms

Table 62. Circuit breaker failure protection (CCBRBRF) main settings

Parameter Function Value (Range) Step

Current value (Operating phase CCBRBRF 0.05...1.00 x In 0.05


current)

Current value Res (Operating CCBRBRF 0.05...1.00 x In 0.05


residual current)

CB failure mode (Operating mode CCBRBRF 1=Current -


of function) 2=Breaker status
3=Both

CB fail trip mode CCBRBRF 1=Off -


2=Without check
3=Current check

Retrip time CCBRBRF 0...60000 ms 10

CB failure delay CCBRBRF 0...60000 ms 10

CB fault delay CCBRBRF 0...60000 ms 10

40 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 63. Arc protection (ARCSARC)

Characteristic Value

Operation accuracy ±3% of the set value or ±0.01 x In

Operate time Minimum Typical Maximum

Operation mode = "Light 12 ms3) 14 ms3) 16 ms3)


+current"1)2) 7 ms4) 8 ms4) 11 ms4)

Operation mode = "Light only"2) 9 ms3) 10 ms3) 12 ms3)


4 ms4) 6 ms4) 6 ms4)

Reset time < 40 ms3)


< 55 ms4)

Reset ratio Typical 0.96

1) Phase start value = 1.0 x I n, current before fault = 2.0 x set Phase start value , f n = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2) Includes the delay of the heavy-duty output contact
3) Normal power output
4) High-speed output

Table 64. Arc protection (ARCSARC) main settings

Parameter Function Value (Range) Step

Phase start value (Operating ARCSARC 0.50...40.00 x In 0.01


phase current)

Ground start value (Operating ARCSARC 0.05...8.00 x In 0.01


residual current)

Operation mode ARCSARC 1=Light+current


2=Light only
3=BI controlled

Table 65. Multipurpose protection (MAPGAPC)

Characteristic Value

Operation accuracy ±1.0% of the set value or ±20 ms

Table 66. Multipurpose analog protection (MAPGAPC) main settings

Parameter Function Value (Range) Step

Start value MAPGAPC -10000.0...10000.0 0.1

Operate delay time MAPGAPC 0...200000 ms 100

Operation mode MAPGAPC Over -


Under

ABB 41
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Control functions

Table 67. Emergency start function (ESMGAPC) main settings

Parameter Function Value (Range) Step

Operation ESMGAPC Off -


On

Motor stand still A ESMGAPC 0.05...0.20 x In 0.01

Table 68. Synchrocheck (SECRSYN)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±1 Hz

Voltage: ±3.0% of the set value or ±0.01 x Un


Frequency: ±10 mHz
Phase angle: ±3°

Reset time < 50 ms

Reset ratio Typical 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Table 69. Synchronism and energizing check (SECRSYN) main settings

Parameter Function Value (Range) Step

Live dead mode SECRSYN -1=Off


1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live

Difference voltage SECRSYN 0.01...0.50 xUn 0.01

Difference frequency SECRSYN 0.001...0.100 xFn 0.001

Difference angle SECRSYN 5...90 deg 1

Synchrocheck mode SECRSYN 1=Off


2=Synchronous
3=Asynchronous

Control mode SECRSYN 1=Continuous


2=Command

Dead line value SECRSYN 0.1...0.8 xUn 0.1

Live line value SECRSYN 0.2...1.0 xUn 0.1

Close pulse SECRSYN 200...60000 ms 10

Max energizing V SECRSYN 0.50...1.15 xUn 0.01

Phase shift SECRSYN -180...180 deg 1

Minimum Syn time SECRSYN 0...60000 ms 10

Maximum Syn time SECRSYN 100...6000000 ms 10

Energizing time SECRSYN 100...60000 ms 10

Closing time of CB SECRSYN 40...250 ms 10

42 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Measurement functions

Table 70. Three-phase current measurement (CMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 71. Current sequence components (CSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn = ±2 Hz

±1.0% or ±0.002 x In
at currents in the range of 0.01...4.00 x In

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

Table 72. Residual current measurement (RESCMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn = ±2 Hz

±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 73. Three-phase voltage measurement (VMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz


At voltages in range 0.01…1.15 x Un

±0.5% or ±0.002 x Un

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 74. Voltage sequence components (VSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz


At voltages in range 0.01…1.15 x Un

±1.0% or ±0.002 x Un

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

ABB 43
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 75. Residual voltage measurement (RESVMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn = ±2 Hz

±0.5% or ±0.002 x Un

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 76. Three-phase power and energy (PEMMXU)

Characteristic Value

Operation accuracy At all three currents in range 0.10…1.20 x In


At all three voltages in range 0.50…1.15 x Un
At the frequency fn ±1 Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71

±1.5% for power (S, P and Q)


±0.015 for power factor
±1.5% for energy

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

Table 77. Frequency measurement (FMMXU)

Characteristic Value

Operation accuracy ±10 mHz


(in measurement range 35 - 75 Hz)

44 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Supervision functions

Table 78. Current circuit supervision (CCRDIF)

Characteristic Value

Operate time1) < 30 ms

1) Including the delay of the output contact

Table 79. Current circuit supervision (CCRDIF) main settings

Parameter Function Value (Range) Step

Start value CCRDIF 0.05...0.20 x In 0.01

Maximum operate current CCRDIF 1.00...5.00 x In 0.01

Table 80. Fuse failure supervision (SEQRFUF)

Characteristic Value

Operate time1) NPS function UFault = 1.1 x set Neg Seq voltage < 33 ms
Lev
UFault = 5.0 x set Neg Seq voltage < 18 ms
Lev

Delta function ΔU = 1.1 x set Voltage change rate < 30 ms

ΔU = 2.0 x set Voltage change rate < 24 ms

1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements

Table 81. Motor run time counter (MDSOPT)

Description Value

Motor run-time measurement accuracy1) ±0.5%

1) Of the reading, for a stand-alone IED, without time synchronization.

ABB 45
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

19. Local HMI breakers cannot be operated remotely from the network
The IED supports process information and status monitoring control center.
from the IED's local HMI via its display and indication/alarm
LEDs. The local LHMI also enables control operations for the
equipment connected and controlled by the IED, either via
display or via manual push buttons available on the local HMI.

LCD display offers front-panel user interface functionality with


menu navigation and menu views. In addition, the display
includes a user-configurable two-page single-line diagram
(SLD) with a position indication for the associated primary
equipment and primary measurements from the process. The
SLD can be modified according to user requirements by using
Graphical Display Editor in PCM600.

The local HMI also includes 11 programmable LEDs. These GUID-7A40E6B7-F3B0-46CE-8EF1-AAAC3396347F V1 EN

LEDs can be configured to show alarms and indications as Figure 10. Example of the LHMI
needed by PCM600 graphical configuration tool. The LEDs
include two separately controllable colors, red and green,
making one LED able to indicate better the different states of
the monitored object.
20. Mounting methods
The IED also includes 16 configurable manual push buttons, By means of appropriate mounting accessories, the standard
which can freely be configured by the PCM600 graphical IED case for the 620 series IED can be flush-mounted, semi-
configuration tool. These buttons can be configured to control flush-mounted or wall-mounted.
the IED's internal features e.g. changing setting group,
Furthermore, the IEDs can be mounted in any standard 19”
triggering disturbance recordings and changing operation
instrument cabinet by means of 19” mounting panels available
modes for functions or to control IED external equipment, e.g.
with cut-outs for one IED. Alternatively, the IED can be
starting or stopping the equipment, via IED binary outputs.
mounted in 19” instrument cabinets by means of 4U
These buttons also include a small indication LED for each
Combiflex equipment frames.
button. This LED is freely configurable, making it possible to
use push button LEDs to indicate button activities or as Mounting methods:
additional indication/alarm LEDs in addition to the 11
programmable LEDs. • Flush mounting
• Semi-flush mounting
The local HMI includes a push button (L/R) for the local/ • Rack mounting
remote operation of the IED. When the IED is in the local • Wall mounting
mode, the IED can be operated only by using the local front- • Mounting to a 19" equipment frame
panel user interface. When the IED is in the remote mode, the
IED can execute commands sent remotely. The IED supports Panel cut-out for flush mounting:
the remote selection of local/ remote mode via a binary input. • Height: 162 ± 1 mm
This feature facilitates, for example, the use of an external • Width: 248 ± 1 mm
switch at the substation to ensure that all the IEDs are in the
local mode during maintenance work and that the circuit

46 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

")
(19
.6
280 482

,2
246 262 246 246

177
160
160

160
177

177
153 103
153
48 98
48

GUID-89F4B43A-BC25-4891-8865-9A7FEDBB84B9 V1 EN GUID-1DF19886-E345-4B02-926C-4F8757A0AC3E V1 EN GUID-D83E2F4A-9D9B-4400-A2DC-AFF08F0A2FCA V1 EN

Figure 11. Flush mounting Figure 12. Semi-flush mounting Figure 13. Rack mounting

259

318
186

GUID-65A893DF-D304-41C7-9F65-DD33239174E5 V1 EN

Figure 14. Wall mounting

21. IED case and IED plug-in unit


For safety reasons, the IED cases for current measuring IEDs
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a IED unit is
withdrawn from its case. The IED case is further provided with
a mechanical coding system preventing current measuring
IED units from being inserted into a IED case for a voltage
measuring IED unit and vice versa, i.e. the IED cases are
assigned to a certain type of IED plug-in unit.

ABB 47
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

22. Selection and ordering data number consists of a string of codes generated from the
The IED type and serial number label identifies the protection IED's hardware and software modules.
IED. The label is placed above the HMI on the upper part of
the plug-in unit. An order number label is placed on the side Use the ordering key information to generate the order
of the plug-in unit as well as inside the case. The order number when ordering complete IEDs.

NBMNAANNABC1BNN1XF

# Description
1 IED
620 series IED (including case) N
2 Standard
IEC B
CN C
3 Main application
Motor protection and control M
4 Functional application
Example configuration N
5-6 Analog inputs and outputs
7I (I0 1/5 A) + 5U + 12BI + 10BO + 6RTD in + 2mA in AA
7I (I0 0,2/1 A) + 5U + 12BI + 10BO + 6RTD in + 2mA in AB
7-8 Optional board
Optional I/Os 8BI+ 4BO AA
Optional RTDs 6RTD in + 2mA in AB
Optional Fast I/Os 8BI + 3HSO AC
No optional board NN
9 Communication modules (Serial)
-
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
10 AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1
AB
x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST) + Serial RS-485 connector, RS-232/485
D-Sub 9 connector + input for IRIG-B (cannot be combined with BN
arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (1 x RJ-45) + Serial
RS-485 connector, RS-232/485 D-Sub 9 connector + input for BB
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (3 x RJ-45) with
BD
HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC
+ 1 x LC) with HSR/PRP
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE
+ 2 x LC) with HSR/PRP
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX and -FX (2 x RJ-45 + 1 x LC) with HSR/
NC
PRP
Ethernet 100Base-TX (3 x RJ-45) with HSR/PRP ND
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) with HSR/
NE
PRP
No communication module NN

If serial communication is chosen, please choose a serial communication module


including Ethernet (for example “BC”) if a service bus for PCM600 or the WebHMI is
required.
GUID-7DDA4163-29F6-469A-8E69-A6D3FE3F24D0 V1 EN

48 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

NBMNAANNABC1BNN1XF

# Description
11 Communication protocols
IEC 61850 (for Ethernet communication modules and IEDs with-
A
out a communication module )
Modbus (for Ethernet/serial or Ethernet + serial communication
B
modules)
IEC 61850 + Modbus (for Ethernet or serial + Ethernet communi-
C
cation modules)
IEC 60870-5-103 (for serial or Ethernet + serial communication
D
modules)
DNP3 (for Ethernet/serial or Ethernet + serial communication
E
modules)
IEC 61850 + IEC 60870-5-103(for serial + Ethernet communica-
G
tion modules)
IEC 61850 + DNP3(for Ethernet or serial + Ethernet communica-
H
tion modules)
12 Language
English 1
English and Chinese 2
13 Front panel
Large LCD with Single Line Diagram - IEC B
Large LCD with Single Line Diagram - CN D
14 Option 1
Arc protection (requires a communication module, cannot be
B
combined with communication module optionsS BN or BB)
None N
15 Option 2
None N
16 Power supply
Power supply 48-250 VDC, 100-240 VAC 1
Power supply 24-60 VDC 2
17 Reserved
-
18 Product version 2.0 XF
GUID-600ABF01-7959-4459-A46C-BAB01DB6AF72 V1 EN

Example code: N B M N A A N N A B C 1 B N N 1 X F

Your ordering code:

Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Code
GUID-161F35FF-C0CC-4411-B6F4-2109C0623B48 V1 EN

Figure 15. Ordering key for complete IEDs

ABB 49
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

23. Accessories and ordering data

Table 82. Cables

Item Order number

Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5

Cable for optical sensors for arc protection 3.0 m 1MRS120534-3.0

Cable for optical sensors for arc protection 5.0 m 1MRS120534-5.0

Table 83. Mounting accessories

Item Order number

Semi-flush mounting kit 2RCA030573A0001

Wall mounting kit 2RCA030894A0001

19" Mounting panel kit 2RCA031135A0001

24. Tools Web-browser based user interface is disabled by default. The


The IED is delivered as a pre-configured unit including the interface can be enabled with the PCM600 tool or from the
example configuration. The default parameter setting values front panel user interface. The functionality of the interface
can be changed from the front-panel user interface, the Web- can be limited to read-only access by means of PCM600.
browser based user interface (WebHMI) or the PCM600 tool
in combination with the IED-specific connectivity package. The IED connectivity package is a collection of software and
specific IED information, which enable system products and
The Protection and Control IED Manager PCM600 offers tools to connect and interact with the IED. The connectivity
extensive IED configuration functions such as IED signal packages reduce the risk of errors in system integration,
configuration, application configuration, graphical display minimizing device configuration and set-up times.
configuration including single line diagram configuration, and Furthermore, the Connectivity Packages for the 620 series
IEC 61850 communication configuration including horizontal IEDs include a flexible update tool for adding one additional
GOOSE communication. local HMI language to the IED. The update tool is activated
using PCM600 and it enables multiple updates of the
When the Web-browser based user interface is used, the IED additional HMI language, thus offering flexible means for
can be accessed either locally or remotely using a Web possible future language updates.
browser (IE 7.0 IE 8.0 or IE 9.0). For security reasons, the

Table 84. Tools

Configuration and setting tools Version

PCM600 2.5 or later

Web-browser based user interface IE 7.0, IE 8.0 or IE 9.0

REM620 Connectivity Package 2.0

50 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 85. Supported functions

Function WebHMI PCM600

IED parameter setting ● ●

Saving of IED parameter settings in the IED ● ●

Signal monitoring ● ●

Disturbance recorder handling ● ●

Alarm LED viewing ● ●

Access control management ● ●

IED signal configuration (signal matrix) - ●

Modbus® communication configuration (communication


management) - ●

DNP3 communication configuration (communication


management) - ●

IEC 60870-5-103 communication configuration


(communication management) - ●

Saving of IED parameter settings in the tool - ●

Disturbance record analysis - ●

XRIO parameter export/import ● ●

Graphical display configuration - ●

Application configuration - ●

IEC 61850 communication configuration, GOOSE


(communication configuration) - ●

Phasor diagram viewing ● -

Event viewing ● ●

Saving of event data on the user's PC ● -

Online monitoring - ●
● = Supported

ABB 51
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

25. Connection diagrams


L1
L2
L3
A

N
n Positive
Current
a Direction

da dn

REM620
Uab X100
X120
2) + 1
1 1/5A
Uaux
P1 IL1_N -
2
S1
2 N

S2
3 1/5A 3
P2 IL2_N IRF
4 N
4
5 1/5A
IL3_N 5
6 N

7 1/5A PO1
IL1
8 N 6
9 1/5A 7
IL2
P1 S1 10 N PO2
11 1/5A
S2 IL3 8
P2 12 N
9
13 1/5A
10
Io
14 N SO1
11
M X130
12
13
SO2
3~ 1
2
BI 1
14
16
3 PO3
BI 2
4
P2
S2 17
5 15
S1 BI 3 19
P1
6 TCS1 18
20
7 22
BI 4
8 PO4
60 -
9 210V
21
U_SYN 23
10 N
TCS2
60 - 24
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N

X110
5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22

X115 X115
1 14
BI 1
2 SO1
16
3
BI 2 15
4 17
5 SO2
BI 3 19
6
18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10

11
BI 7
12

BI 8
13

X13
1)
Light sensor input 1

X14
1)
Light sensor input 2

X15 1) Order selectable -Optional


1) 2) The IED features an automatic short-circuit
Light sensor input 3
mechanism in the CT connector when plug-in
unit is detached

GUID-19F39D16-3819-4030-877F-08E5872EEC5D V1 EN

Figure 16. Connection diagram for the A configuration

52 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

620 BIO option


X105 X105
1
BI 1 14
2
SO1
3 16
BI 2 15
4
17
5 SO2
BI 3
6 19
18
20
BI 4
7 SO3
22
8
BI 5 21
9 23
SO4
BI 6 24
10

11
BI 7
12

BI 8
13

GUID-5298DCA3-4597-44C2-850A-889384DF423B V1 EN

Figure 17. Optional BIO0005 module (slot X105)

620 BIO option


X105
X105
1
BI 1
HSO1
2
BI 2 15
16
3 HSO2
BI 3
19
4 20
BI 4
5
HSO3
6
BI 5 23
24
7
BI 6

8
BI 7

9
BI 8
10

GUID-D019E095-29EF-41B1-BDF4-D9D427201B88 V1 EN

Figure 18. Optional BIO0007 module for fast outputs (slot X105)

620 RTD option


X105

5 mA
mA 1
6
7 mA
mA 2
8
9
RTD 1
10
11
RTD 2
12
13
RTD 3
14
15 Common RTD GND
16 Common RTD GND
17
RTD 4
18
19
RTD 5
20
21
RTD 6
22

GUID-987D427B-C5F7-4073-8D5F-D0C37BEAF5E5 V1 EN

Figure 19. Optional RTD0003 module (slot X105)

ABB 53
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

26. References The download area on the right hand side of the web page
The www.abb.com/substationautomation portal offers you contains the latest product documentation, such as technical
information about the distribution automation product and manual, installation manual, operation manual, etc.
service range.
The Features and Application tabs contain product related
You will find the latest relevant information on the REM620 information in a compact format.
protection IED on the product page.

54 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

27. Functions, codes and symbols

Table 86. REM620 functions, codes and symbols

Function IEC 61850 IEC 60617 IEC-ANSI

Protection

Three-phase non-directional overcurrent protection,


PHLPTOC1 3I> (1) 51P-1 (1)
low stage, instance 1

Three-phase non-directional overcurrent protection,


PHIPTOC1 3I>>> (1) 50P/51P (1)
instantaneous stage, instance 1

Three-phase directional overcurrent protection, low


DPHLPDOC1 3I> -> (1) 67-1 (1)
stage, instance 1

Three-phase directional overcurrent protection, high


DPHHPDOC1 3I>> -> (1) 67-2 (1)
stage, instance 1

Three-phase directional overcurrent protection, high


DPHHPDOC2 3I>> -> (2) 67-2 (2)
stage, instance 2

Non-directional earth-fault protection, low stage,


EFLPTOC1 Io> (1) 51N-1 (1)
instance 1

Non-directional earth-fault protection, high stage,


EFHPTOC1 Io>> (1) 51N-2 (1)
instance 1

Non-directional earth-fault protection, instantaneous


EFIPTOC1 Io>>> (1) 50N/51N (1)
stage, instance 1

Directional earth-fault protection, low stage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)

Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)

Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)

Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)

Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (3)

Three-phase undervoltage protection, instance 1 PHPTUV1 3U< (1) 27 (1)

Three-phase undervoltage protection, instance 2 PHPTUV2 3U< (2) 27 (2)

Three-phase undervoltage protection, instance 3 PHPTUV3 3U< (3) 27 (3)

Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)

Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)

Three-phase overvoltage protection, instance 3 PHPTOV3 3U> (3) 59 (3)

Positive-sequence undervoltage protection, instance 1 PSPTUV1 U1< (1) 47U+ (1)

Positive-sequence undervoltage protection, instance 2 PSPTUV2 U1< (2) 47U+ (2)

Negative-sequence overvoltage protection, instance 1 NSPTOV1 U2> (1) 47O- (1)

Negative-sequence overvoltage protection, instance 2 NSPTOV2 U2> (2) 47O- (2)

Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1)

Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81 (2)

Frequency protection, instance 3 FRPFRQ3 f>/f<,df/dt (3) 81 (3)

Frequency protection, instance 4 FRPFRQ4 f>/f<,df/dt (4) 81 (4)

Frequency protection, instance 5 FRPFRQ5 f>/f<,df/dt (5) 81 (5)

Frequency protection, instance 6 FRPFRQ6 f>/f<,df/dt (6) 81 (6)

Negative-sequence overcurrent protection for motors,


MNSPTOC1 I2>M (1) 46M (1)
instance 1

ABB 55
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 86. REM620 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Negative-sequence overcurrent protection for motors,


MNSPTOC2 I2>M (2) 46M (2)
instance 2

Loss of load supervision, instance 1 LOFLPTUC1 3I< (1) 37M (1)

Loss of load supervision, instance 2 LOFLPTUC2 3I< (2) 37M (2)

Motor load jam protection JAMPTOC1 Ist> (1) 51LR (1)

Motor start-up supervision STTPMSU1 Is2t>, n> (1) 49,66,48,51LR (1)

Phase reversal protection PREVPTOC1 I2>> (1) 46R (1)

Thermal overload protection for motors MPTTR1 3Ith>M (1) 49M (1)

Motor differential protection MPDIF1 3dl>M (1) 87M (1)

Circuit breaker failure protection, instance 1 CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)

Circuit breaker failure protection, instance 2 CCBRBRF2 3I>/Io>BF (2) 51BF/51NBF (2)

Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)

Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)

Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)

Multipurpose analog protection, instance 1 MAPGAPC1 MAP (1) MAP (1)

Multipurpose analog protection, instance 2 MAPGAPC2 MAP (2) MAP (2)

Multipurpose analog protection, instance 3 MAPGAPC3 MAP (3) MAP (3)

Multipurpose analog protection, instance 4 MAPGAPC4 MAP (4) MAP (4)

Multipurpose analog protection, instance 5 MAPGAPC5 MAP (5) MAP (5)

Multipurpose analog protection, instance 6 MAPGAPC6 MAP (6) MAP (6)

Multipurpose analog protection, instance 7 MAPGAPC7 MAP (7) MAP (7)

Multipurpose analog protection, instance 8 MAPGAPC8 MAP (8) MAP (8)

Multipurpose analog protection, instance 9 MAPGAPC9 MAP (9) MAP (9)

Multipurpose analog protection, instance 10 MAPGAPC10 MAP (10) MAP (10)

Multipurpose analog protection, instance 11 MAPGAPC11 MAP (11) MAP (11)

Multipurpose analog protection, instance 12 MAPGAPC12 MAP (12) MAP (12)

Control

Circuit-breaker control, instance 1 CBXCBR1 I <-> O CB (1) I <-> O CB (1)

Circuit-breaker control, instance 2 CBXCBR2 I <-> O CB (2) I <-> O CB (2)

Disconnector control, instance 1 DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)

Disconnector control, instance 2 DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)

Earthing switch control, instance 1 ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)

Disconnector control, instance 3 DCXSWI3 I <-> O DCC (3) I <-> O DCC (3)

Disconnector control, instance 4 DCXSWI4 I <-> O DCC (4) I <-> O DCC (4)

Earthing switch control, instance 2 ESXSWI2 I <-> O ESC (2) I <-> O ESC (2)

Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)

56 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 86. REM620 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)

Earthing switch position indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)

Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)

Disconnector position indication, instance 4 DCSXSWI4 I <-> O DC (4) I <-> O DC (4)

Earthing switch position indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)

Emergergency startup ESMGAPC1 ESTART (1) ESTART (1)

Synchronism and energizing check SECRSYN1 SYNC (1) 25 (1)

Condition monitoring

Circuit-breaker condition monitoring, instance 1 SSCBR1 CBCM (1) 52CM (1)

Circuit-breaker condition monitoring, instance 2 SSCBR2 CBCM (2) 52CM (2)

Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

Current circuit supervision, instance 1 CCRDIF1 MCS 3I (1) CSM 3I (1)

Fuse failure supervision SEQRFUF1 FUSEF (1) 60 (1)

Runtime counter for machines and devices, instance 1 MDSOPT1 OPTS (1) OPTM (1)

Runtime counter for machines and devices, instance 2 MDSOPT2 OPTS (2) OPTM (2)

Measurement

Three-phase current measurement, instance 1 CMMXU1 3I (1) 3I (1)

Three-phase current measurement, instance 2 CMMXU2 3I(B) (1) 3I(B) (1)

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)

Residual current measurement, instance 1 RESCMMXU1 Io (1) In (1)

Three-phase voltage measurement VMMXU1 3U (1) 3V (1)

Residual voltage measurement RESVMMXU1 Uo (1) Vn (1)

Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)

Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1)

Frequency measurement FMMXU1 f (1) f (1)

Other

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP (1) TP (1)

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP (2) TP (2)

Minimum pulse timer (2 pcs), instance 3 TPGAPC3 TP (3) TP (3)

Minimum pulse timer (2 pcs), instance 4 TPGAPC4 TP (4) TP (4)

Minimum pulse timer (2 pcs, second resolution),


TPS (1) TPS (1)
instance 1 TPSGAPC1

Minimum pulse timer (2 pcs, second resolution),


TPS (2) TPS (2)
instance 2 TPSGAPC2

Minimum pulse timer (2 pcs, minute resolution),


TPM (1) TPM (1)
instance 1 TPMGAPC1

Minimum pulse timer (2 pcs, minute resolution),


TPM (2) TPM (2)
instance 2 TPMGAPC2

ABB 57
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 86. REM620 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Pulse timer (8 pcs), instance 1 PTGAPC1 PT (1) PT (1)

Pulse timer (8 pcs), instance 2 PTGAPC2 PT (2) PT (2)

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF (1) TOF (1)

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF (2) TOF (2)

Time delay off (8 pcs), instance 3 TOFGAPC3 TOF (3) TOF (3)

Time delay off (8 pcs), instance 4 TOFGAPC4 TOF (4) TOF (4)

Time delay on (8 pcs), instance 1 TONGAPC1 TON (1) TON (1)

Time delay on (8 pcs), instance 2 TONGAPC2 TON (2) TON (2)

Time delay on (8 pcs), instance 3 TONGAPC3 TON (3) TON (3)

Time delay on (8 pcs), instance 4 TONGAPC4 TON (4) TON (4)

Set reset (8 pcs), instance 1 SRGAPC1 SR (1) SR (1)

Set reset (8 pcs), instance 2 SRGAPC2 SR (2) SR (2)

Set reset (8 pcs), instance 3 SRGAPC3 SR (3) SR (3)

Set reset (8 pcs), instance 4 SRGAPC4 SR (4) SR (4)

Move (8 pcs), instance 1 MVGAPC1 MV (1) MV (1)

Move (8 pcs), instance 2 MVGAPC2 MV (2) MV (2)

Move (8 pcs), instance 3 MVGAPC3 MV (3) MV (3)

Move (8 pcs), instance 4 MVGAPC4 MV (4) MV (4)

Generic control points, instance 1 SPCGGIO1 SPCGGIO (1) SPCGGIO (1)

Generic control points, instance 2 SPCGGIO2 SPCGGIO (2) SPCGGIO (2)

Generic control points, instance 3 SPCGGIO3 SPCGGIO (3) SPCGGIO (3)

Remote Generic control points SPCRGGIO1 SPCRGGIO (1) SPCRGGIO (1)

Local Generic control points SPCLGGIO1 SPCLGGIO (1) SPCLGGIO (1)

Generic Up-Down Counters, instance 1 UDFCNT1 UDCNT (1) UDCNT (1)

Generic Up-Down Counters, instance 2 UDFCNT2 UDCNT (2) UDCNT (2)

Generic Up-Down Counters, instance 3 UDFCNT3 UDCNT (3) UDCNT (3)

Generic Up-Down Counters, instance 4 UDFCNT4 UDCNT (4) UDCNT (4)

Generic Up-Down Counters, instance 5 UDFCNT5 UDCNT (5) UDCNT (5)

Generic Up-Down Counters, instance 6 UDFCNT6 UDCNT (6) UDCNT (6)

Generic Up-Down Counters, instance 7 UDFCNT7 UDCNT (7) UDCNT (7)

Generic Up-Down Counters, instance 8 UDFCNT8 UDCNT (8) UDCNT (8)

Generic Up-Down Counters, instance 9 UDFCNT9 UDCNT (9) UDCNT (9)

Generic Up-Down Counters, instance 10 UDFCNT10 UDCNT (10) UDCNT (10)

Generic Up-Down Counters, instance 11 UDFCNT11 UDCNT (11) UDCNT (11)

Generic Up-Down Counters, instance 12 UDFCNT12 UDCNT (12) UDCNT (12)

Programmable buttons(16 buttons) FKEYGGIO1 FKEY (1) FKEY (1)

Logging functions

Disturbance recorder RDRE1 DR (1) DFR (1)

58 ABB
Motor Protection and Control 1MRS757845 A
REM620
Product version: 2.0

Table 86. REM620 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Fault recorder FLTMSTA1 FR (1) FR (1)

Sequence event recorder SER1 SER (1) SER (1)

Load profile LDPMSTA1 LOADPROF (1) LOADPROF (1)

28. Document revision history

Document revision/date Product version History

A/2013-05-07 2.0 First release

ABB 59
60
Contact us

1MRS757845 A © Copyright 2013 ABB. All rights reserved.