Bond_Beams_MAC_rev072020_WithIntro_v1_2024
Bond_Beams_MAC_rev072020_WithIntro_v1_2024
Bond Beams
Masonry wall construction consists of an assembly of concrete masonry units (CMU) and reinforcement
(as needed by design). Continuity of the masonry wall is recommended to tie the structure together. Bond
beams in masonry walls are a very common method to achieve continuity to allow all of the wall segments
to work together as a single unit. This Insight will discuss the use and detailing of bond beams.
Standard CMU blocks do not readily incorporate horizontal rebar, thus special masonry units are
typically used at the bond beam locations. Bond beam units are prefabricated blocks, as shown at the top
of Figure 3, with either
Figure 2:
part of the webs
Bond Beams
removed during
TMS 402-13
fabrication or saw-cut
Section 2.2
slots creating “knock-
Commentary
out” panels which are
removed with a hammer
by the mason in the (2a) Stepped (2b) Sloped
field. Both unit types
have vertical cores
Typically, a bond beam is located at the top course of each masonry wall or
parapet as well as at each roof and floor diaphragm. Bond beams at each of these
locations generally have the horizontal rebar extend through control joints (see
Figure 1). This helps provide continuity for structural integrity of the building.
Additionally, the bond beams can serve as collector elements and/or diaphragm
chords for the building lateral system. Bond beams in other locations, depending
on the project requirements, usually will be detailed to terminate the
Figure 3: Bond
reinforcement on each side of control joints and may or may not have a smooth
Beam Units
dowel with one end debonded crossing the joint.
NCMA TEK 3-2A
Bond beams are also one option to connect intersecting masonry walls if the
transfer of loads between them is necessary per the structural design (see Figure 4). In this case, bond
beams must be located within the wall at a maximum spacing of 48” on center, have the reinforcement be
fully developed each side of the intersection, and have at least half of the masonry units interlock at the
interface. One example of a situation where this connection may be required is when a shear wall does not
have adequate capacity, thus the intersecting wall is tied to the end of the shear wall to serve as a flange
for additional capacity. For gravity loading, masonry walls have capacity to support large concentrated
loads from steel bar joists, beams, or other structural elements. Depending on the masonry wall detailing,
the calculated wall capacity will vary.
The masonr y bond pattern and
bearing plate size determine the
effective bearing length of the wall
and thus how much wall area can be
included in the capacity calculation
(see Figure 5). For stack bond, the
load dispersement cannot go further
than the first CMU head joint that
the sloped line meets. Thus if a point
load is bearing directl y on the
masonry, the effective length will
likely only be the length of one block
unless the bearing plate straddles a
joint. As demonstrated in figure 5,
Figure 4: Bond Beam at Wall Intersection inserting a bond beam into the wall at
TMS 402-13 Section 5.1.1 Commentary
One more condition where bond beams are effective is in the shear walls of buildings located in areas of
high seismicity. Horizontal reinforcement increases the in-plane ductility of the masonry assembly.
Section 7.3.2 of TMS 402-13 provides minimum horizontal reinforcement requirements based on the
seismic classification of the building site, the magnitude of the lateral loads, and the detailing designation
of the shear wall. For shear walls with lower seismic detailing, the horizontal reinforcement minimum can
be satisfied with either joint reinforcement or bond beam reinforcement. Higher seismic detailing is more
stringent with bond beam reinforcement as the only option.