A14 A11-19 Oxygen Gas
A14 A11-19 Oxygen Gas
This warranty does not cover consumable items, batteries, or wear items
subject to periodic replacement including lamps and fuses.
Gas sensors carry a 12 months from date of shipment warranty and are
subject to inspection for evidence of misuse, abuse, alteration, improper storage,
or extended exposure to excessive gas concentrations. Should inspection
indicate that sensors have failed due to any of the above, the warranty shall not
apply.
TABLE OF CONTENTS
TABLE OF CONTENTS .............................................................................................................................. 1
O & M Manual
A14-RK, 8/06 1-1
GasSens Gas Detection System Section 1 - Overview
O & M Manual
A14-RK, 8/06 1-2
GasSens Gas Detection System Section 1 - Overview
INTRODUCTION
GasSens is an on-line monitoring system for the detection of hazardous gases in ambient
air. It is designed to detect and alarm gas leaks from storage cylinders, process piping, or gas
feed equipment in virtually any type of industrial plant environment. Systems are available for
monitoring a variety of gases as shown in Table 1-1.
TABLE 1-1
The GasSens system consists of modular components that can be used in a variety of
configurations to fit specific application requirements. A description of the major system
components follows:
O & M Manual
A14-RK, 8/06 1-3
GasSens Gas Detection System Section 1 - Overview
A11 Sensor/Transmitter
Consists of an electrochemical gas sensor closely coupled to a NEMA 4X transmitter.
This component measures gas concentration and converts the measurement to a digital signal
for transmission to a receiver module. It must be mounted in the area where gas leakage or
buildup is expected, and can either be wall mounted or supported by electrical conduit carrying
interconnecting wiring. Sensor/transmitters are available with optional Auto-Test, an
electrochemical gas generator which automatically tests sensor response daily and alarms any
sensor problems. For hazardous areas, explosion-proof sensor/transmitters are available.
NEMA 4X Enclosures
Four standard enclosures are available for housing receiver and power supply modules.
Polystyrene enclosures are suitable for outdoor environments, and digital displays and alarm
indicators are clearly visible through a clear polycarbonate window on the front. The window
hinges open to gain access to the receiver A/R control switch, and the entire front section of the
enclosure can be removed for ease of mounting and wiring. Enclosures are provided with
knockouts on all four sides to facilitate wiring, and 1/2" FNPT conduit hubs are provided with
each enclosure.
Explosion-proof Enclosures
Two versions are available to allow use of the receiver and power supply modules in
hazardous areas. One version is suitable for a single receiver module, while the second is large
enough to contain both a power supply and a receiver. Enclosures are rated for Class 1, Division
1, Groups C & D. Group B enclosures are also available if required. All explosion-proof
enclosures can be supplied with an external acknowledge and reset switch.
O & M Manual
A14-RK, 8/06 1-4
GasSens Gas Detection System Section 1 - Overview
Audible Horn
A 12 VDC piezoelectric alarm horn is available for mounting into any of the NEMA 4X
enclosures. The horn is wired to the receiver module and will sound intermittently when the
warning setpoint is reached, and continuously when the alarm setpoint is reached. The horn can
be silenced by pushing the A/R switch on the receiver front panel. A single horn can be wired
through multiple receivers and will sound if any receiver goes into alarm.
Strobe Lamp
Provides a bright visual indication of an alarm condition. The strobe uses a xenon flash
lamp to give a high intensity flash approximately 70 times a minute. The strobe is wired to one
of the alarm relays, with power for the strobe supplied from the power supply module. Mounting
is by 1/2" MNPT nipple, making it convenient to mount directly to a NEMA enclosure.
O & M Manual
A14-RK, 8/06 1-5
GasSens Gas Detection System Section 1 - Overview
MECHANICAL INSTALLATION
System enclosures, battery back-up units, and sensor transmitters are all designed for
surface mounting using screws or bolts inserted through the recessed mounting holes at each
corner of the enclosures. Included with each system enclosure is a template with mounting hole
dimensions for two and three module system enclosures, battery back-up enclosure, and
sensor/transmitter enclosure. The template can be used to mark hole centers on walls or
mounting panels.
Mounting recesses are suitable for #6 or #8 machine screws or wood screws. Screw length
will vary with specific site conditions.
Two and three module system enclosures provide knockouts on all four sides to allow wiring
conduit to be connected in the most convenient way. Enclosures are shipped with all knockouts
in place except for the larger knockout on the bottom, where the audible horn is installed if
ordered. See pages 1-6 through 1-9 for dimensional drawings of the one, two, three and six
module enclosures.
Each enclosure is supplied with conduit hubs for connection of 1/2" NPT threaded conduit.
Also included is a seal ring for each hub. Seal rings are required to provide a water tight
conduit hub connection to the enclosure. The following lists the number of hubs that should
be included with each enclosure type.
Conduit hubs are installed in any enclosure knockout labeled PG16. Note that some
knockouts have more than one designation, such as PG11/16. Those with two designations will
have concentric circles for knockouts. The inner circle marks the lower PG number while the
outer circle marks the higher number. Place a thin bladed screwdriver into the circular slot or the
desired knockout size and tap firmly with a hammer. To install the hub, place the seal ring over
the threaded part of the hub. Locate the hub nut on the inside of the enclosure and screw the
hub into the hub nut from the outside. Tighten firmly to insure that the seal ring provides a good
seal between the hub and the outside of the enclosure.
O & M Manual
A14-RK, 8/06 1-6
GasSens Gas Detection System Section 1 - Overview
For installations where conduit will not be used, cable gland seal fittings must be installed in
the conduit hubs. Plastic cable glands are available from most electrical supply stores. Gland
seals with 1/2" NPT threads will screw directly into the conduit hub. Gland seals are also
available from ATI for installation directly into the enclosures in place of the conduit hubs. Refer
to the parts list for the correct part number of the cable gland seals.
O & M Manual
A14-RK, 8/06 1-7
GasSens Gas Detection System Section 1 - Overview
BOTTOM VIEW
O & M Manual
A14-RK, 8/06 1-8
GasSens Gas Detection System Section 1 - Overview
BOTTOM VIEW
O & M Manual
A14-RK, 8/06 1-9
GasSens Gas Detection System Section 1 - Overview
O & M Manual
A14-RK, 8/06 1 - 10
GasSens Gas Detection System Section 1 - Overview
ELECTRICAL INSTALLATION
Field wiring required for a detection system includes connection of AC power, connection of
two conductor cable between the receiver and the sensor/transmitter, and connection of the
battery back-up unit if it was purchased with the system. ATI does not supply an AC power cord
with the system. A 25 foot length of 2 conductor interconnect cable is supplied for connection of
the sensor/transmitter to the receiver. Longer lengths up to 1000 feet may be used when
required.
Single point detection systems are supplied with the power supply, receiver, and optional
horn factory wired as shown in Figure 1-5 below.
Figure 2-2 in section 2 of this manual shows a detailed terminal wiring drawing for the
Receiver module. Figure 3-1 in section 3 shows a detailed terminal wiring drawing for the power
supply module.
A GasSens gas detection system will always contain an A14 Receiver and an A11 Sensor/
transmitter. Normally, an A17 Power Supply module will also be included, and an A19 Battery
Back-up Unit will often be used to provide standby power for the system. Figures 1-8 and 1-9
provide interconnect wiring diagrams for typical single channel systems.
O & M Manual
A14-RK, 8/06 1 - 11
GasSens Gas Detection System Section 1 - Overview
Two point detectors include one power supply and two receivers. These systems are
shipped factory wired as shown in Figure 1-6 below.
O & M Manual
A14-RK, 8/06 1 - 12
GasSens Gas Detection System Section 1 - Overview
O & M Manual
A14-RK, 8/06 1 - 13
GasSens Gas Detection System Section 1 - Overview
Multipoint systems supplied in “Large” type enclosures use a 65 watt power supply located in
the top of the enclosure. This power supply is designed to power up to 12 of the A14 receiver
modules. Figure 1-8 shows typical wiring for this type of system.
O & M Manual
A14-RK, 8/06 1 - 14
GasSens Gas Detection System Section 1 - Overview
Sensor/transmitters contain two 2-position terminal blocks, one for receiver connection and one
for connection of the Auto-Test generator. Connection of the two wires from the receiver are not
polarity sensitive. These wires can be hooked up without regard to terminal position.
Connection of the generator is polarity sensitive. The generator will not function unless
connected properly. Sensor/transmitters supplied with the generator from the factory will be
factory wired. Adding a generator to an existing unit requires the installer to be sure that
generator wiring follows the diagram in Figure 1-8 below.
O & M Manual
A14-RK, 8/06 1 - 15
GasSens Gas Detection System Section 1 - Overview
The remainder of this manual is divided into sections that describe each component of the
system. Mechanical and electrical installation are the only requirements to provide a workable
system. Power supply modules and battery back-up units require no adjustments. Receiver
modules are factory set to the range specified on the order, and alarm setpoints will be set to
default values unless otherwise specified on the order. Sensor/transmitters are factory
calibrated, and should require no adjustments when placed in service. Calibration can be
checked if desired according to the instructions in the Sensor/transmitter section of this manual.
Normal operation of the system is done using the switch on the Receiver module. The
"Operation" portion of the Receiver section (section 2) should be read and understood before
placing the detection system into operation.
O & M Manual
A14-RK, 8/06 1 - 16
GasSens Gas Detection System Section 2 - A14 Receiver Module
RECEIVER MODULE
Introduction
Series A14 Receivers provide the user interface to the gas detection system. Each receiver
is connected to a series A11 sensor/transmitter with a 2 conductor cable, and displays
information on the gas concentration in the sensor area. Receivers are powered by a separate
12 VDC power supply (part no. 00-0055) supplied as part of the system, or by a power supply
furnished by the user (12 VDC only).
4 DIGIT LED DISPLAY - INDICATES GAS
CONCENTRATION
Receivers are housed in a compact noryl case designed for mounting to a 35 x 7.5 mm DIN
rail. The rails are supplied in standard ATI system enclosures, or can be supplied by a system
integrator as part of a custom panel arrangement. A spring clip on the back of the enclosure
holds the module to the rail. To remove from a rail, slide a thin bladed screwdriver through the
black loop at the top of the module and pull outward until the module releases from the rail. To
mount to the rail, reverse the procedure. When mounting, slide the bottom of the module
against the bottom of the rail before extending the spring clip.
Electrical Connection
Electrical connections to the receiver are made to two pluggable terminal blocks as shown in
Figure 2-2. Transmitter connections must be made at the time of installation, while power and
horn connections are factory wired when the receiver is part of a complete system. Connections
should be made and checked before power is applied to the module. Never connect or alter
connections while power is on.
O & M Manual
A14-RK, 8/06 2-1
GasSens Gas Detection System Section 2 - A14 Receiver Module
TB1
TB2
A1 A2 A3 TROUBLE
TB1 TB2
1: +12 Module Power positive (12 VDC) 1: A1 NO Alarm 1 normally open contact
2: C Module Power Common 2: A1 C Alarm 1 common
3: Earth Ground (REQUIRED) 3: A1 NC Alarm 1 normally closed contact
4: H+ Audible Horn positive 4: A2 NO Alarm 2 normally open contact
5: H- Audible Horn negative 5: A2 C Alarm 2 common
6: RR Remote Reset 6: A2 NC Alarm 2 normally closed contact
7: RR Remote Reset 7: A3 NO Alarm 3 normally open contact
8: MA+ 4-20 mA output positive 8: A3 C Alarm 3 common
9: MA- 4-20 ma output negative 9: A3 NC Alarm 3 normally closed contact
10: Earth Ground 10: TROUBLE NC trouble normally closed contact
11: TR Transmitter Input 11: TROUBLE C Trouble common
12: TR Transmitter Input 12: TROUBLE NO Trouble normally open contact
NOTE: Relay contact designation is shown for relays in normal mode of operation for relays A1,
A2 and A3. If fail-safe relay operation is selected, NO and NC designations are reversed
for that relay. The TROUBLE relay is set to fail-safe operation at the factory, and the
designation shown above is for the trouble relay in fail-safe mode.
O & M Manual
A14-RK, 8/06 2-2
GasSens Gas Detection System Section 2 - A14 Receiver Module
Factory Configuration
All receivers are identical except for the gas symbol attached to the green power LED.
Operating range, alarm relay configuration, display intensity, and Auto-Test activation are
selectable using 4 banks of DIP switches located on the configuration circuit board inside the
module.
Receivers are factory configured for the operating range specified on the customer order. If
the system is ordered with the Auto-Test option, this is also factory configured. Factory
configuration of the relays is as follows:
Relay 1 - Configured to trip at the Warning setpoint and set for normal, non-latching
operation.
Relay 2 - Configured to trip at the Alarm setpoint and set for normal, latching operation.
Relay 3 - Configured to trip at the Alarm setpoint and set for normal, latching operation.
Alarm Delay - Configured for 2 second delay.
Warning and Alarm setpoints are factory set to standard values depending on the operating
range. Except for oxygen systems, alarms are set to activate above the setpoints. Oxygen
alarms are set to activate below the setpoints.
The LED display will operate in either normal or high intensity mode. Normal mode is the
factory default setting, and is used when receivers are located indoors or in shaded areas. High
intensity mode is selected when receivers will be mounted outdoors. In high intensity mode, the
LED display can be read in direct sunlight.
Configuration Switches
Figure 2-3 indicates the location of each bank of DIP switches on the configuration P.C.
board and Figure 2-4 provides a description of the function of each switch on each bank.
BANK C
BANK D
BANK A
BANK B
O & M Manual
A14-RK, 8/06 2-3
GasSens Gas Detection System Section 2 - A14 Receiver Module
O & M Manual
A14-RK, 8/06 2-4
GasSens Gas Detection System Section 2 - A14 Receiver Module
Setpoint Selection
The operating range and the Warning and Alarm setpoints can be changed, if desired, by
using the configuration switches identified in Figure 2-4. The Warning setpoint is set using
switches A2-A8 and the Alarm setpoint is set using switches B2-B8. A binary number is used to
select setpoints as a percent of operating range. For example, if you have a receiver range of 0-
10 PPM and want to adjust a setpoint for 3 PPM, set the appropriate DIP switches to the binary
number for 30% from Table 2-1 below. Switches can be set using the tip of a ball point pen or
other tool with a small point on one end. Switch are two position, up indicating 'on' or a value of
'1' and down indicating 'off' or a value of '0'.
TABLE 2-1
O & M Manual
A14-RK, 8/06 2-5
GasSens Gas Detection System Section 2 - A14 Receiver Module
Range Selection
Display range selection is made using binary numbers to represent the full scale operating
range for the receiver. Table 2-2 provides the proper switch settings for the ranges available on
each receiver. Range selection is made using switches C1-C4. The 4-20 mA output signal is
proportional to the selected range.
Ranges marked with 'LSD Fixed' indicate that the least significant digit on the display always
reads zero.
TABLE 2-2
Relay Configuration
Receivers contain 3 SPDT relays that actuate based on gas concentration. Relays can be
set to actuate when the gas concentration either goes above or falls below the setpoint. Most
gas leak detection applications require alarms to activate above a specific setpoint, but alarms
for oxygen deficiency require relay actuation below the setpoints. Switch A1 selects relay
operation either above or below setpoints and applies to all relays.
Each relay can be assigned to either the warning or alarm setpoint. As shown in Figure 2-4,
switches D3, D6, and C6 configure each relay . When warning is selected, the relay will activate
when the warning lamp on the front panel lights. When alarm is selected, the relay will activate
with the alarm lamp on the front panel.
Relays may be either Latching or Non-latching. A latching relay activates when gas
concentration exceeds the setpoint, but will only deactivate when the A/R button is pressed, and
then only if the gas concentration has fallen below the setpoint. A non-latching relay will
automatically deactivate when the gas concentration falls below the setpoint without A/R button
being pressed. Selection of the latch/non-latch function uses switches D4, D7, and C7.
O & M Manual
A14-RK, 8/06 2-6
GasSens Gas Detection System Section 2 - A14 Receiver Module
Relays may be configured for either Fail-safe or Normal operation. The designation of
normal or fail-safe refers to the operation of the relay coil during normal operation. A relay
configured for Normal operation will have the relay coil energized when an alarm occurs and de-
energized during normal operation. A relay configured for Fail-safe operation has the relay coil
energized when conditions are normal and de-energizes when an event occurs. A fail-safe relay
will change state if power to the receiver is interrupted.
A short time delay precedes the activation of warning and alarm relays when a setpoint is
exceeded. This brief delay of 2 seconds eliminates false alarms due to transients that might be
encountered in a particular installation. The 2 second delay is the factory default and is selected
with switch B1. A 10 second delay may be selected if required in a specific application. The
delay time of either 2 or 10 seconds affects both the warning and alarm indicator lamps and the
associated relays.
Using relay 3 in the horn configuration eliminates the need for additional relay logic to
silence an external horn. This can provide significant cost savings in the installation of a
complete alarm system.
Display Intensity
The LED display on the receiver will operate in either normal or high intensity mode. The
factory setting is normal mode. Switch D2 is used to select high intensity mode for outdoor
installations.
O & M Manual
A14-RK, 8/06 2-7
GasSens Gas Detection System Section 2 - A14 Receiver Module
OPERATION
Startup
Receiver front panels contain four LED bar indicators and a 4 digit LED display. The digital
display indicates gas concentration in either PPM, PPB, or percent. The green LED bar is
marked with the gas symbol and units of measurement (PPM, PPB, or %) specified on the
customer order. LED bars also indicate WARNING, ALARM, and TROUBLE conditions.
12 VDC power for the receiver is supplied from the power supply module. When power is
first applied, the LED display will turn on and will step through three information displays. The
first number displayed is the full scale range. A 0-10 PPM unit will be indicated by "10.0" on the
display. After 3 seconds, the display will indicate the warning setpoint, the concentration at
which the warning relay will activate, with the WARNING lamp illuminated. After 3 seconds, the
display will indicate the alarm setpoint, with the ALARM lamp illuminated. At the end of this
sequence, the display will begin to indicate gas concentration. However, all alarm functions will
be inhibited for 5 minutes while the system is allowed to stabilize. This is indicated by
WARNING and ALARM lamps flashing in an alternating pattern. During this period, alarms will
not function, but the display will indicate the presence of any gas that might be in the area of the
sensor. Normally, the display will spike when power first comes on, and will slowly recover to
zero over the 5 minute period in which alarms are inhibited.
The front panel of the receiver contains one button, marked A/R, which is used for a number
of different functions. When the receiver is in normal operation, a gas leak that exceeds the
warning setpoint will cause the WARNING indicator to flash and the internal horn to sound
intermittently. If the alarm setpoint is exceeded, the ALARM indicator will flash and the horn will
sound steadily. Pressing the A/R button the first time will silence the audible horn, and will
change the WARNING and ALARM indicators from flash to steady on. The indicator lamps will
remain lit until the gas condition has cleared. The WARNING indicator will automatically shut off
when gas concentration falls below the setpoint, but the ALARM indicator will remain lit.
Pressing the button after the alarm condition has cleared will reset the ALARM indicator.
Operation of the individual relays depends on the configuration selected for each one. As
shipped from the factory, relay 1 will energize when the WARNING indicator lights and will
automatically reset when the gas condition clears and the WARNING indicator shuts off. Relays
2 and 3 are configured to energize and latch when the ALARM indicator lights. These relays will
reset when the A/R button is pressed to reset the ALARM indicator. Changes in the relay
configuration switches will alter this operational sequence.
O & M Manual
A14-RK, 8/06 2-8
GasSens Gas Detection System Section 2 - A14 Receiver Module
For systems supplied with the Auto-Test option, the TROUBLE lamp will also indicate the
failure of a sensor to respond to the gas test that occurs automatically every 24 hours. Should
this type of failure occur, the TROUBLE indicator will flash, the trouble relay will change state,
and the audible horn will activate. Pressing the A/R switch will silence the horn, but the lamp
and relay cannot be reset for at least 10 minutes. The flashing TROUBLE light indicates that the
sensor and gas generator should be tested for proper operation using the manual Auto-Test. If
the sensor does not respond, the system should be tested using calibration or test gas as
described in the sensor/transmitter instructions. Pressing the A/R button resets the trouble relay
and indicator.
ATI's optional Auto-Test feature is a valuable tool for verifying the proper operation of a gas
detection system while saving manpower normally required for routine testing. Auto-Test is an
electrochemical gas generator fixed to the gas sensor and controlled from the receiver. Every
24 hours, the receiver automatically activates the gas generator and monitors the output of the
gas sensor. When the sensor responds normally, the generator is shut off and the system
returns to normal operation. With this feature in place, operation of every gas sensor is verified
daily. Manual testing is reduced to periodic calibration every 3-12 months, or when the receiver
indicates that a sensor has not passed its normal test.
While an Auto-Test is in progress, the alarm relays are inhibited. This is indicated by the
alternating flash pattern on the WARNING and ALARM indicators used during the 5 minute
power on delay. Typically, an Auto-Test will progress only a few minutes before the sensor
begins to respond. The actual time varies depending on the gas. A chlorine test normally takes
less than 30 seconds while a sulfur dioxide test can take as long as four minutes. Alarm relays
will remain inhibited for 10 minutes after completion of the test to allow the sensor to recover.
The alternating flash pattern will continue during this time.
During the first two minutes of the 10 minute inhibit period, alarms are completely inhibited.
The warning and alarm relays will not activate during this period. During the second 8 minute
period, the alarms are only partially inhibited. The inhibit flash pattern will continue during the 8
minute period, but the inhibit will be superseded by an alarm should the measured gas
concentration exceed 50% of range. This means that alarm protection is partially restored to
protect against any major leak during this period. At the end of the 10 minute inhibit period, the
alternating flash will end and the unit will return to normal operation.
O & M Manual
A14-RK, 8/06 2-9
GasSens Gas Detection System Section 2 - A14 Receiver Module
When the Auto-Test is activated, the generator will turn on for a maximum of 5 minutes. If no
sensor response is detected during this time, the generator will turn off and the receiver will wait
for 15 minutes before initiating another Auto-Test. If no sensor response is detected after the
second test, the trouble indicator will flash, trouble relay will change state, and the horn will
sound. The test sequence will be repeated twice more at one hour intervals. If the system
passes, alarms will automatically shut off. If it fails, the alarms will continue to be energized. If
the trouble alarm has been manually acknowledged and reset between tests, a failure will
reactivate the trouble alarm.
NOTE: No Auto-Test will be initiated if the measured gas concentration is above either of
the two setpoints. If this condition exists, the receiver will wait for another 24
hours before initiating another Auto-Test sequence.
To activate the lamp test, press and hold the A/R button for 2 seconds and all front panel
indicators will light. The horn will also sound briefly. Immediately release the button and the
indicators will return to normal. During this test, alarm relays will not be activated.
Relay Inhibit
Alarm relays in the receiver can be inhibited for up to 4 hours to allow calibration or testing of
sensor/transmitters without activating external alarm or control devices. Inhibit is activated
through the use of the A/R button.
Press and hold the button for approximately 5 seconds. The lamp test will occur first, but
continue to hold the button down. Once the lamps have shut off, release the button. The
WARNING and ALARM lamps will begin an alternating flash pattern, and, if the receiver is
configured for Auto-Test, the flash will switch to the trouble lamp. If you do nothing, the flash will
switch between the WARNING/ALARM lamps and TROUBLE lamp twice and then revert to
normal operation.
If the A/R button is pressed and released while the WARNING and ALARM lamps are in
alternating flash, the receiver will go into the relay inhibit mode (if a horn is connected, a quick
beep will sound when the inhibit is selected). The WARNING and ALARM lamps will continue
their alternating flash for 4 hours or until the A/R button is pressed again. During this period, the
display will indicate gas concentration, but the relays will not. Transmitters may be calibrated
while the inhibit is on without activating external alarms.
O & M Manual
A14-RK, 8/06 2 - 10
GasSens Gas Detection System Section 2 - A14 Receiver Module
Manual Auto-Test
Gas detection systems purchased with the optional Auto-Test generator may be tested by
manual activation of the generator from the receiver module. This function will operate only if
the Auto-Test configuration switch D1 is 'on'. As with the lamp test and alarm inhibit, access to
manual operation of the generator is through the A/R button.
Press and hold the button for approximately 5 seconds. The lamp test will occur first but
continue to hold the button down. When the lamps have shut off, release the button. The
number of hours since the last successful auto-test (automatic or manual) will appear on the
display. When the WARNING/ALARM flash is alternating with the TROUBLE flash, you can
select manual activation of the generator rather than relay inhibit. Press the A/R button when
the TROUBLE lamp is flashing (if a horn is connected, a quick beep will sound when the Auto-
Test is selected). The green gas indicator will begin to flash, indicating that the generator is
activated. The system will go through a normal Auto-Test sequence, exactly the same as the
sequence used every 24 hours. If you observe the display, you will see increasing gas values as
the sensor begins to respond. Upon completion of a successful test, the horn will sound a single
beep. The inhibit will remain on for an additional 10 minutes while the sensor recovers to zero.
Should the test be unsuccessful, the TROUBLE lamp will light and the alarm relay and horn will
activate. Pressing the A/R button will silence the horn, but the alarm cannot be reset for at least
10 minutes after a failure of the manually activated Auto-Test. This period will allow time to
manually inspect the sensor to determine the reason for the failure
If the manual Auto-Test sequence results in a trouble alarm, check the sensor/transmitter.
Either the sensor or generator has failed, or the diffusion path between the two is physically
blocked. Methods for testing individual gas sensors can be found in specific sensor/transmitter
instructions.
Remote Reset
Receivers are provided with input terminals for connection of a remote reset switch. The
remote reset input provides horn silence and alarm reset functions using a switch located at a
remote point. When receivers are located at sites with telemetry equipment, the remote reset
input may be connected to a relay contact in the telemetry system.
The remote reset input accomplishes the same acknowledge and reset functions as the A/R
button on the front panel. When a switch closure is detected across the remote reset terminals,
the detector horn will silence and any latching relays will reset, provided that the gas condition
has cleared. The remote reset input will not activate any of the testing or inhibit functions of the
receiver.
Analog Output
Receivers provide an isolated 4-20 mA output signal for interface with recorders, data
loggers, or computer systems. The span of the 4-20 mA signal is the same as the range of the
receiver selected during the receiver configuration. The output will drive loads up to 1200 ohms.
O & M Manual
A14-RK, 8/06 2 - 11
GasSens Gas Detection System Section 2 - A14 Receiver Module
A14 Receiver modules with a software revision G or higher use the analog output to indicate
that a successful Auto-Test has occurred. This allows a recording device to show evidence of
the successful test. During an Auto-Test, the 4-20 mA output is locked at 4 mA while the test is
in process. If the test is successful, the output will go up by 3% (to 4.48 mA) and will remain at
that value until the 10 minute inhibit period is complete, after which it will return to 4 mA.
A14 Receiver modules with software revision G or higher have the capability of temporarily
deactivating the Auto-Test function without having to open the module and change the DIP
switch that controls this function. This might be necessary if an Auto-Test failure has been
traced to a failure of the generator. If proper sensor operation has been verified, the automatic
daily activation of the test function can be bypassed until a replacement generator has been
installed.
To deactivate the Auto-Test, press and hold the A/R button for a full 15 seconds. As you
hold the button, the lamps will turn on and then shut off again. Finally, the green power LED will
shut off so that there will be no lamps lit at all. Release the A/R button. After this is done, you
will see the green LED periodically flash quickly. This is simply a visual reminder that the Auto-
Test has been temporarily deactivated.
To return the receiver to normal operation, press and hold the A/R button until all the lamps
and display segments light up. Then let go of the switch and the unit will return to normal
operation. Alternately, simply turn the power off and then back on. This will also override the
temporary inhibit.
NOTE: If power goes off while the Auto-Test is temporarily deactivated, it will come back on in
normal mode. You must again deactivate the Auto-Test again or it will attempt the test
24 hours later.
O & M Manual
A14-RK, 8/06 2 - 12
GasSens Gas Detection System Section 2 - A14 Receiver Module
TROUBLESHOOTING
Receiver modules will normally provide trouble free operation over many years of service.
However, should problems arise, a few simple tests can be done to determine if the receiver is
functioning properly.
LED display and green gas indicator do not light when power is applied to the system.
1. Check polarity of the power connection at terminals 1 and 2 of TB1. Terminal 1 must be
positive and terminal 2 must be negative.
2. With a voltmeter, check the power supply at terminals 1 and 2 of TB1. Input power supply
must be 11 to 15 VDC.
Receiver module powers up correctly, but does not respond when test gas is applied to
sensor/transmitter.
1. Disconnect transmitter connections at terminals 11 and 12 of TB1. Check the voltage on the
terminals with a voltmeter. The voltage should be about 12 VDC.
2. Connect a milliamp meter between terminal 11 and 12 of TB1. The current should measure
about 20 mA.
Problems in the receiver module can only be caused by an electronic component failure. In
most cases, the simplest solution is to remove the module and install a replacement.
Troubleshooting the electronic circuit boards is best handled by trained technician familiar with
the circuits. As modules are small and easily shipped, it is best to return defective modules to
ATI for service.
Modules failing during the warranty period will be exchanged by ATI with replacement units.
Contact the ATI service department for assistance.
O & M Manual
A14-RK, 8/06 2 - 13
GasSens Gas Detection System Section 2 - A14 Receiver Module
PC BOARD ASSEMLBY
O & M Manual
A14-RK, 8/06 2 - 14
Universal Power Supply Section 3 – A17 Power Supply Module
The power supply module used in the GasSens system (part #00-0055) is a self-adjusting supply
that will accept the AC power provided in virtually every country in the world. Any AC (50-60 Hz.) or DC
voltage from 85 volts to 270 volts can be connected to the power input terminals on TB4. There are no
adjustments of any kind required.
The output of the power supply is a regulated 13.7 VDC. There are 3 sets of DC terminals at the top
of the module for connection to receivers and external battery back-up unit. This voltage permits float
charging of a an optional separate 12 volt lead acid battery for detector system back-up.
Power supply modules are rated for 1 ampere output, and will deliver higher current for periods.
Each optional receiver module draws a maximum of 300 mA, and will normally draw about 125 mA. The
optional external battery back-up unit can draw up to 750 mA for a few hours if the battery is deeply
discharged, which will drop sharply as the battery approaches full charge. The audible horn draws less
than 10 mA average current, and an optional strobe will draw approximately 400 mA when activated.
The power supply is internally fused at 2 Amps. The fuse is not user replaceable. (Note: Only
Qualified Service Personnel will replace the fuse, using the same type and rating as indicated on the
fuse.)
The power supply has a power-on indicator LED and provides a SPDT relay to indicate power failure.
The relay coil is energized by power from the input power terminals and will de-energize if power is lost.
This relay is convenient for input to telemetry systems to indicate loss of power at a remote site.
Mounting of power supply modules is done by clipping them to a standard 35 x 7.5 mm DIN rail. A
spring loaded clip holds the module to the rail and is used for mounting and removal. From the front, the
clip is seen as a black loop at the top rear of the module. To remove from a rail, place a small
screwdriver into the opening in the black loop and pull outward until the module releases from the rail.
Reverse the procedure to mount the module.
CAUTION
The power supply module is sealed, and the seal should not be broken. Never attempt to
disassemble or service the power supply module. Service on this module should only be done
only by a qualified service technician familiar with the circuit design and equipped with the
proper service equipment. Severe electrical shock may result from touching internal
components with input power applied.
O & M Manual
A14-RK, 8/06 3- 1
Universal Power Supply Section 3 – A17 Power Supply Module
Figure 3-1 provides detailed information on the terminals provided on the power supply. All terminal
blocks are plug-in type, and can be easily unplugged should removal of the module be necessary.
1: +12 External Battery (+) 1: +12 Receiver Module (+) 1: +12 Receiver Module (+)
2: C External Battery (-) 2: C Receiver Module 2: C Receiver Module Common
Common
3: Earth Ground 3: Earth Ground 3: Earth Ground
TB4 TB5
NOTE: AC power input must be properly earth grounded for safe operation. 220 VAC power without a
neutral line may not be used with this power supply.
O & M Manual
A14-RK, 8/06 3- 2
Universal Power Supply Section 3 – A17 Power Supply Module
O & M Manual
A14-RK, 8/06 3- 3
GasSens Gas Detection System Section 4 - Optional Equipment
OPTIONAL EQUIPMENT
Battery back-up units for GasSens detection systems (part #00-0057) are separate components
housed in a NEMA 4X wall mount enclosure. Back-up units include a 4 ampere-hour sealed lead acid
battery with a control circuit attached to the battery terminals. The battery is held in place on an
aluminum bracket fixed to the plastic enclosure.
Installation
Figure 4-1 shows the dimensions of the battery back-up unit and the mounting hole centers. Two
conduit hubs are supplied with the unit, one for use on the battery back-up enclosure and one for use on
the receiver enclosure. When mounting the battery back-up unit, be careful to hold the module
securely when screwing the enclosure in place. The battery is heavy and could cause injury to
feet if it should fall directly on them. The battery and attached circuit board are held in place with a
wire tie. Should you wish to remove the battery, the wire tie must be cut. When replacing the battery,
secure with a new wire tie. Replacement batteries from ATI are supplied with the proper wire tie.
O & M Manual
A14-RK, 8/06 4-1
GasSens Gas Detection System Section 4 - Optional Equipment
Electrical connection is made between the battery back-up unit and the power supply module. The
circuit board mounted on the battery contains a 2 position plug-in terminal block marked plus and minus.
The plus terminal is connected to terminal B+ of the power supply and the minus terminal is connected to
B- of the power supply.
Operation
When power is applied to the power supply module, a relay on the battery back-up circuit board
energizes and places the battery back-up into operation. There are no user adjustments in the battery
back-up unit. If the battery is not fully charged, the power supply will begin supplying charge current to
the battery, and will float charge the battery as long as the power supply is on.
Should the power supply loose its input power, the battery back-up will immediately supply power to
receiver modules to maintain detection system operation without interruption. The back-up period will
vary depending on whether the detector is single channel or two channel, on whether displays are in
normal or high intensity mode, and on how many relays are configured for fail-safe operation. The
minimum period expected for a single channel system is 12 hours and for a two channel system is 6
hours. Normally, the back-up period is twice as long as the minimums.
The circuit board attached to the battery serves two functions. First, it regulates the charging current
to the battery to a maximum of 0.75 amps. This prevents possible damage to the battery due to an
excessively high charge current. Second, it isolates the battery from the detection system when the
battery voltage falls below 10 volts. This is done through a relay, and protects the battery against
damage caused by very deep discharge.
The isolation relay that protects against deep discharge will also protect the battery against an
external short circuit of the wires connected to the battery. If a short occurs, the relay will immediately
open, protecting the battery and limiting the current that the battery will deliver.
To de-energize the relay, slide the control circuit board off the battery terminals briefly and then slide
it back on. As soon as the battery connection is broken, the relay coil will drop out, and will not energize
until power is applied to the power supply module in the system. This procedure is recommended any
time the detection system is to be shut down for more that a few days.
O & M Manual
A14-RK, 8/06 4-2
GasSens Gas Detection System Section 4 - Optional Equipment
O & M Manual
A14-RK, 8/06 4-3
GasSens Gas Detection System Section 4 - Optional Equipment
STROBE LIGHT
The accessory alarm indicating strobe light (part number 35-0002) available for use with the
GasSens alarm system is a weatherproof high-intensity strobe operating from a 12 VDC power source.
The strobe can be conveniently mounted on the top or either side of the alarm enclosure using one of the
1/2" NPT hubs supplied with the unit. The bottom of the strobe also contains a 1/2" NPT mounting
adapter, so that only a 1/2" pipe nipple is needed to complete the assembly. The necessary nipple is
available from most hardware stores or plumbing supply outlets.
For remote applications, the strobe should be mounted to 1/2" conduit, with a junction box nearby for
splicing the strobe wires to the interconnect wiring running to the alarm unit. This wiring should be kept
separate from AC power wiring to avoid accidental connection of AC power to the strobe, which will
damage the lamp.
The 12 VDC power to operate the strobe can be picked up from the power supply module which is
part of the alarm unit. Figure 4-2 shows the typical wiring diagram for connection of the strobe. The
wiring diagram shows the plus side of the 12 VDC supply brought to the common of the alarm contact,
one side of the strobe wired to the normally open (NO) contact, and the other side of the strobe
connected to the minus side of the 12 VDC supply. Connection of the strobe lamp directly across the
alarm relay will not operate the strobe because alarm contacts are unpowered.
CAUTION: Strobe light connection is polarity sensitive. Check wiring to be sure that the +12 is
connected to the red strobe wire.
O & M Manual
A14-RK, 8/06 4-4
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
INTRODUCTION
Series A11 sensor/transmitters combine electrochemical gas sensors and an electronic amplifier
that transmits gas concentration using a current pulse position technique. When ordered as an option,
sensor/transmitters are also supplied with a gas generator that provides the Auto-Test automatic sensor
testing system.
Gas sensors are housed in a corrosion resistant plastic housing connected to the transmitter
enclosure through a knockout. A short sensor cable with a three pin socket connects the sensor to the
transmitter circuit board. For hazardous area applications, sensor/transmitters are housed in a cast iron
explosion-proof enclosure and the sensor is contained in a stainless steel shell with explosion-proof cable
seal.
Sensors/transmitters are powered from a current limited 12 volt supply provided by the receiver.
Do not attempt to operate the transmitter from another 12 volt power supply or the transmitter
will be damaged. If you wish to perform a calibration on the bench, use a spare receiver module to
power the transmitter. A separate 12 volt supply can be used if the current is limited to a maximum of
20mA.
INSTALLATION
Sensor/transmitters are surface mounted using screws or bolts as required. Figure 5-1 provides
the dimensions for the NEMA-4X transmitter. NEMA-4X enclosures will accommodate #6 or #8 screws
which are not supplied. For NEMA-4X transmitters not equipped with Auto-Test, the sensor may be
oriented either horizontally as shown in Figure 5-1 or facing downward. For pipe mounting, special 2"
pipe mounting brackets are available.
Explosion-proof transmitters mount directly to the conduit system and are supported by the
conduit. The sensor orientation may be either horizontal or facing downward, as shown in Figure 5-2. To
maintain the explosion-proof integrity of the transmitter, a suitable cable entry seal must be used in
accordance with the applicable electrical code.
NOTE: Gas sensors are shipped with a protective plastic cap over the end. This cap should be
left in place to avoid damage to the sensor during installation. If the detection system is
to be activated within a few days of installation, the cap should be removed when
installation is complete. Otherwise, leave the cap in place until the system is to be
activated. Be sure to leave the protective cap on the sensor if painting is to be done in
the area of the sensor.
Installation wiring requires connection of a 2 conductor cable from the receiver. Connection is
made at the terminals marked TB1 on Figure 5-3. This connection is not polarity sensitive so you can
connect either conductor to either terminal. The cable supplied with the system in unshielded #20 gauge
stranded.
__________________________________________________________________________________
O & M Manual 5-1
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
Notes:
__________________________________________________________________________________
O & M Manual 5-2
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
__________________________________________________________________________________
O & M Manual 5-3
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
SENSOR LOCATION
Oxygen gas mixes uniformly throughout most enclosed spaces. However, oxygen sensors are
normally used to detect oxygen deficiency, caused by the displacement of oxygen by another gas such
as carbon dioxide or nitrogen. When locating an oxygen sensor in an enclosed space, the user should
evaluate the hazard associated with the space. Normally, the oxygen sensor would be located about 5
feet from the floor, but a higher or lower elevation may be better in applications where a gas that is either
heavier or lighter than air is the source of the hazard.
INTERFERENCES
The A11-19 sensor/transmitter uses an electrochemical sensor manufactured by ATI. It is
designed to measure oxygen gas concentration in air with a maximum of sensitivity and a minimum of
interference from other gases.
Oxygen sensors are affected by only two possible interferences. The first and least likely, is
percent levels of oxidant gases such as chlorine, bromine, or ozone. Oxygen sensors will respond to
these gases as if they were oxygen, indicating higher oxygen levels than really exist. However, storage
areas containing these types of gases should always be equipped with separate oxidant gas leak
detectors.
The second possible interference is high concentrations of Carbon Dioxide. CO2 can slightly
enhance the oxygen sensor signal at levels above 10% CO2. This effect will generally result in slightly
higher oxygen measurements, but the effect is relatively small and will not offset the large signal change
caused by the exclusion of oxygen by high CO2 levels.
CALIBRATION
Oxygen sensor/transmitters are factory calibrated for the operating range specified on the order,
with the calibrated range shown on the calibration tag attached inside the lid of the transmitter enclosure.
The typical operating range for oxygen deficiency applications is 0-25%, with a WARNING setpoint of
19.5% and an ALARM setpoint of 16%. Recalibration of an oxygen system should be done every 3-6
months.
Calibration of an O2 sensor/transmitter can be done in the field using fresh air or calibration kits
available from ATI. A small kit (Part no. 00-0193) provides enough gas for about 7 calibrations, while a
larger kit (Part no. 00-0185) provides gas for about 25 calibrations. Calibration kits include a cylinder of
nitrogen, a cylinder of 18.0% oxygen span gas, a fixed flow regulator, tubing, and a carrying case. A
sensor calibration adapter must be purchased separately. The calibration procedure requires a digital
voltmeter (DVM) to read the output of the transmitter if the receiver is located remote from the
transmitter. If the receiver is nearby, the LED display on the receiver may be used for calibration. If
calibration is to be done using compressed gas from calibration kits, a calibration adapter is needed.
NOTE: If using the receiver display when adjusting the transmitter zero, place the receiver in
the “Inhibit” mode as described in Section 2 of this manual. When in the inhibit mode,
the blanking around zero is disabled so that the zero can be set accurately.
Prior to calibration, remove the cover from the sensor/transmitter enclosure and connect a DVM to
the test points shown in Figure 5-3. The same octagonal transmitter circuit board shown in Figure 5-3
will be found in the explosion-proof transmitter. The test points will provide a 0-1.00 VDC signal
proportional to transmitter range. For a standard 0-25% unit, 0% is 0.00 volts and 25% is 1.00 volt.
__________________________________________________________________________________
O & M Manual 5-4
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
TRANSMITTER ZERO
Oxygen sensors normally have a very stable zero, which is precisely set at the factory prior to
shipment. The zero should be checked and verified at the time a sensor/transmitter is recalibrated.
Transmitter zero is adjusted when the sensor is exposed to nitrogen gas supplied as part of a calibration
kit.
To check zero using nitrogen gas, attach the calibration adapter to the sensor as shown in Figure
5-3. Attach the outlet of the nitrogen cylinder to the calibration adapter and turn on the gas flow.
Observe the DVM reading while allowing gas to flow for 3-5 minutes. The test point voltage should drop
to 0.00 volts over the 5 minute period. If the voltage drops to 0.00 ± 0.02 volts, no adjustment is
necessary. If not, adjust the zero to 0.00 volts using the ZERO potentiometer identified in Figure 5-3.
TRANSMITTER SPAN
Using ambient fresh air as a standard is the easiest way for setting the oxygen transmitter span.
This assumes that the ambient air is not depleted of oxygen, and has a value of 20.9%. This would
normally be true in any well ventilated room. If this is the case, the oxygen sensor/transmitter may be
calibrated while the sensor is exposed to fresh air. To do so, simply adjust the test point voltage to 0.84
VDC when the room is well ventilated.
To span the sensor/transmitter using 18.0% oxygen gas from a calibration kit, connect tubing from
your span gas cylinder to the sensor calibration adapter. Turn on the gas flow and adjust to
approximately 500 cc/min. (ATI calibration kits contain fixed flow regulators that automatically provide
500 cc/min. flow). The reading on the DVM attached to the transmitter test points will display the output
voltage corresponding to 18.0% O2, or 0.72 VDC. Allow the gas to flow to the sensor for 5 minutes and
observe the reading on the DVM. The reading should be relatively stable ± 0.02 VDC. If necessary, use
the SPAN potentiometer to adjust the DVM to read 0.72 ± 0.02 VDC. If using the Receiver module
display for calibration, adjust the span until the receiver reads 18.0.
If an oxygen standard of another value is being used, calculate the calibration voltage using the
following formula.
__________________________________________________________________________________
O & M Manual 5-5
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
While zero and span adjustments are required only periodically, gas sensors should be checked
regularly for proper response. The response check can be done quickly by simply aiming the outlet tube
from a nitrogen gas cylinder at the face of the sensor and turning on the gas flow for 10-20 seconds. The
sensor output will begin to drop quickly as oxygen is excluded from the sensor.
The sensor response test will create a condition where alarm relays will be activated unless they
are inhibited as described in the receiver section. To observe the response at the transmitter, it is
necessary to connect a DVM to the test points indicated in Figure 5-3 If the receiver is nearby, you may
simply observe the digital display on the receiver. If the sensor does not respond, it should be replaced.
__________________________________________________________________________________
O & M Manual 5-6
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
SENSOR REPLACEMENT
Electrochemical sensors used in the A11 are warranted for 12 months and generally last 18-24
months or more. When sensor replacement is required, it can be done easily and quickly. Open the
transmitter and unplug the sensor cable from the transmitter circuit board. Unscrew the sensor from the
nut on the inside of the enclosure and screw in the replacement sensor. For explosion-proof
transmitters, there is no nut, since the stainless steel sensor housing threads directly into the enclosure.
Connect the new sensor to the pins on the transmitter board and replace the transmitter cover.
After a new sensor has been connected, allow 12 hours for the new sensor to completely stabilize. Then
perform a zero and span as described on page 5-5 and 5-6.
__________________________________________________________________________________
O & M Manual 5-7
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
O2 NEMA-4X SENSOR/TRANSMITTER
PARTS LIST
__________________________________________________________________________________
O & M Manual 5-8
A11-19-E, 11/09
GasSens Gas Detection System Section 5 - A11-19 O2 Sensor/Transmitter
O2 EXPLOSION-PROOF SENSOR/TRANSMITTER
PARTS LIST
__________________________________________________________________________________
O & M Manual 5-9
A11-19-E, 11/09