D-MASONRY WALLS:
1. ALL CONCRETE MASONRY BLOCKS SHALL BE HOLLOW BLOCK TYPE (DENSITY OF 19.5 KN/M 3)
2. THE COMPRESSIVE STRENGTH OF MASONRY f'm SHALL NOT BE LESS THAN 10.5 MPA.
3. MORTAR BED JOINTS, SHALL HAVE A MINIMUM 28 DAY CYLINDER COMPRESSIVE
GALVANISED WALL TIE BRACKET (TYP.)
STRENGTH OF 12 MPA (TYPE S MORTAR) SHALL NOT EXCEED 15mm IN THICKNESS.
USED CONCRETE NAIL TO FIX ON
4. FOR CMU WALLS REINFORCEMENT REFER TO THE TABLE. BARS SHALL BE PLACED AT THE END AND
CONCRETE COLUMN AT EVERY 2nd
CORNERS OF THE WALLS AND AS SHOWN ON THE STANDERED DRAWINGS. COURSE (400mm VERTICALLY)
5. BOND BEAM SHALL BE USED AT THE TOP OF WALLS AS SHOWN IN THE BELOW DETAIL. (AS PER APPROVED SAMPLE)
6. HORIZONTAL JOINT REINFORCING SHALL BE LADDER TYPE WIRE JOINTS AT 400 mm MAXIMUM SPACING.
7. THE WEIGHT OF NORMAL BLOCKS FOR PARTITIONS WALLS SHALL NOT
EXCEED THE FOLLOWING VALUES: (ALL VALUES CONSIDER 0.48 KN/M2 As per SBC301-2018)
T12 OR T14 VERTICAL BAR (TYP.)
• FOR 10cm THICK PARTITION WALL WEIGHT = 2.26 KN/m 2 (NO GROUT) (AT EVERY 800mm)
• FOR 15cm THICK PARTITION WALL WEIGHT = 3.1 KN/m 2 (PARTIALLY GROUTED)
• FOR 20cm THICK PARTITION WALL WEIGHT = 3.94 KN/m 2 (PARTIALLY GROUTED) CEMENT MORTAR FILLING (TYP.)
INSIDE HOLLOW BLOCK
FOR VERTICAL BAR
CEMENT MORTAR
LADER TYPE REINF. (TYP.) OPTION-(1) FLOOR SLAB
FILLING (TYP.)
(HOR. & VER.) AT EVERY 2nd COURSE
(6-10mm THK.) (400mm VERTICALLY)
HOLLOW CORE BLOCK WALL
(150/200mm THK.)
CHAMFER LINE OF
CONCRETE COLUMN
FAIR FACE BOND BEAM
CONCRETE COLUMN
TOP OF STRUCTURE SLAB
تس ليح زواي ا الح وائط البل وك الخارجي ة CORNER
ZONE
CORNER
ZONE
FLOOR SLAB
EXTERIOR CORNER ZONE WALL REINFORCEMENT L
WALL THICKNESS VERTICAL HEIGHT
(mm) REINFORCEMENT (mm)
OPENING TO SHOW INSIDE DETAIL
T16@800 5600 BUILDING
200 T14@800 4600 t=200mm INTERNL BLOCK WALLS
LEVEL FLOOR
HEIGHT/m L/m h/m BOND BEAM BOND COLUMN
T10@800 3600 ISOMETRIC TYPICAL CONNECTION T10@200
CORNER CORNER
ZONE ZONE
DETAIL IN BLOCK WALL & COLUMN 6T12
150 ----- ----- L
NTS ALL FLOORS 6T14
وص لة منظوري ة نموذجي ة لتفص يلة اتص ال ح ائط بل وك م ع عم ود خرس انى < 6.5 <5.0 < 3.2
T10@200
CORNER ZONE = 0.1 x MIN. (L, B) BUT NOT LESS THAN 1.0m
200 400
EXTERIOR WALL REINFORCEMENT ة وائط البل وك الخارجي تس ليح الح
t=150mm INTERNL BLOCK WALLS
WALL THICKNESS VERTICAL HEIGHT LEVEL FLOOR
(mm) REINFORCEMENT (mm) HEIGHT/m
GALVANISED WALL TIE BRACKET (TYP.) L/m h/m BOND BEAM BOND COLUMN
USED CONCRETE NAIL TO FIX ON
T16@800 6000 CONCRETE SLAB AT EVERY 1200mm
3T12
3T14 T10@200
ALL FLOORS
200 T14@800 5000 < 5.0 < 5.0 < 2.5
T10@200
BOTTOM OF
SEALANT STRUC. SLAB
T10@800 3950
150 400
WITH BACKING ROD
CONCRETE FILLING (TYP.)
150 ----- ----- INSIDE HOLLOW BLOCK
AT EVERY 12th COURSE INTERNL BLOCK WALLS
t=100mm
1T12 BAR LEVEL FLOOR
HEIGHT/m
(50mm INSIDE COLUMN) L/m h/m BOND BEAM BOND COLUMN
WIRE MESH FOR CONCRETE FILLING
INTERIOR WALL REINFORCEMENT ة وائط البل وك الخارجي تس ليح الح INSIDE HOLLOW BLOCK AT EVERY 12th
3T12
WALL THICKNESS VERTICAL HEIGHT LADER TYPE REINF. (TYP.) 3T12 T10@200
(mm) REINFORCEMENT (mm) AT EVERY 3rd COURSE ALL FLOORS
(400mm VERTICALLY) < 3.5 < 3.5 < 2.0
T10@200
200 T10@800 8750 CEMENT MORTAR FILLING (TYP.)
(HOR. & VER.) (6-10mm THK.) 100 300
CHAMFER LINE OF
150 T12@800 7100 CONCRETE COLUMN
FAIR FACE EXTERNL BLOCK WALLS
DOUBLE WALL (t= 200+100+150mm)
CONCRETE COLUMN LEVEL FLOOR
1T12 OR 1T14 VERTICAL BAR (TYP.) VERT. WALL HEIGHT/m
L/m h/m BOND BEAM BOND COLUMN
(AT EVERY 800mm) REINFORCING NEED
TO BE DRILL AND EPOXY
CEMENT MORTAR FILLING (TYP.)
WALL REINFORCING SCHEDULE. INSIDE HOLLOW BLOCK
100 MM EMBED.
AT TOP AND BOT. T10@200
FOR VERTICAL BAR OF WALL T10@200
NTS
ج دول تس ليح الح وائط البل وك GALVANISED WALL TIE BRACKET (TYP.)
10T12
USED CONCRETE NAIL TO FIX ON
CONCRETE COLUMN AT EVERY 2nd 8T14
COURSE (400mm VERTICALLY) ALL FLOORS < 6.6 < 6.0 < 3.2
TOP OF
STRUC. SLAB
450 200
HOLLOW CONCRETE MASSONRY BLOCK WALL
(150/200mm THK.)
t=200mm EXTERNL BLOCK WALLS
LEVEL FLOOR
ELEVATION TYPICAL CONNECTION DETAIL HEIGHT/m
t=100mm t=150mm t=200mm L/m h/m BOND BEAM BOND COLUMN
WALL THICKNESS IN BLOCK WALL & COLUMN (OPTION-(2))
2T12 4T12
NTS اس قاط رأس ى- وص لة نموذجي ة لتفص يلة اتص ال ح ائط بل وك م ع عم ود خرس انى
2T12
T10@200
6T12
T10@200
TOP BOND BEAM T10@200 T10@200 6T14
ALL FLOORS < 4.00 < 4.00 < 2.00 T10@200
100
150 200
100/150/200 mm CMU WALL T12 @ 1200 mm OC VERT. BARS
200 400
2T16 @ END 2T16 VERT. BARS
WALLS/OPENING LAP SPLICE, 50xBAR DIA., TYP.
T DENOTES THICKNESS OF BLOCK WALL
TABLE FOR TOP BOND BEAM
NTS
AT END WALL AT CORNER T10mm OR EQUIV. TABLE FOR BOND BEAMS AND BOND COLUMNS REINFORCEMENT
WIRE
MESH @ 400 O.C. NTS
HORIZONTAL BARS ج دول لتس ليح للكم رات واﻻعم دة الرابط ة ف ى الج دران المب انى م ن البل وك
COMPRESSIBLE SEALANT
SHOULD BE FIRE RATED. IN
ACCORDANCE TO FIRE
STRUCTURAL DETAILS
COMPRESSIBLE SEALANT SHOULD BE
STRATEGY. FIRE RATED. IN ACCORDANCE TO FIRE
STRATEGY.
20mm CLEAR
UPPER FLOOR
SLAB
AT INTERSECTION UPPER FLOOR
SLAB
STEEL PIPE TO BE FILLED STEEL PIPE TO BE FILLED
WITH GREASE & WITH 20mm WITH GREASE & WITH 20mm
COMPRESSIBLE MATERIAL @ COMPRESSIBLE MATERIAL @
ONE END ONE END
2T16mm VERT CORNER BARS
PLAN CONNECTION DETAIL IN BLOCK WALL & COLUMN
LATERAL SUPPORT FOR TOP OF MASONRY WALLS
NTS
وك ائط البل ى الح ة وا عل ة لقم يزة الجانبي يلة للرك تفص
مس قط افق ى- وص لة نموذجي ة لتفص يلة اتص ال ح ائط بل وك م ع عم ود خرس انى
STR-02
SBC\601-602