Heat Transfer Laboratory (1)
Heat Transfer Laboratory (1)
Mechanical Engineering
Laboratory Report
Semester : V
Batch (Division):
Name of Student :
Roll number :
Technology, PDEU.
Signature:
CO1, 5,
10 Plate Heat Exchangers
6
Safety Hazards & Protection
Personal Care
1. Do not wear loose clothing, Neck Ties/Scarves; Jewelry
(remove).
2. Tie back long hair.
HAZARD: Noise
OBJECTIVES
THEORY
Fourier’s Law of Heat Conduction is most easily verified (or tested) in the one dimensional
configuration of this experiment. In equation form, Fourier’s Law is;
q = k.A. (dT/dx)
Where, q is the heat flowing through the rod of dimensions (W), k is the thermal conductivity
of the material of dimension W/(m·K), A is the cross sectional area m2), and ∂T/∂x is the
temperature gradient of dimensions (K/m).
k = (q/A).(1(dT/dx))
APPARATUS
The apparatus consists of a metal bar, one end of which is heated by an electric heating coil while
the other end is projected inside the cooling water jacket. The metal rod is surrounded by an
insulating material like asbestos to minimize lateral heat transfer from the rod and thus ensure
a more nearly constant temperature gradient along the length of the rod. The temperature of
the bar is measured along the length at six locations using thermocouples while the radial
temperature distribution is measured by separate thermocouples at two different sections in
the insulating shell. The heater is provided with a dimmer stat for controlling the heat input to
the metal rod while the water flow rate through the jacket can be circulated by flow control
valve. The water flow rate and its temperature rise can be noted down.
Figure1: System Line Diagram
TECHNICAL SPECIFICATIONS
Metal Bar
Material : To Find
Length of metal bar : 0.25 m
Diameter of metal bar : 0.025 m
Electric Heater
Voltage : 220 V
Current : 5-15 Amp
Thermocouples
Type :K
Numbers 08
Temperature range : 0 – 200 C (+ 0.5 Celcius)
OPERATION PROCEDURE
1. Connect the equipment to the power supply.
2. Adjust the heat input to the heater by slowly adjusting the dimmer stat and adjust the
voltage e.g. say 50 V.
3. Start and adjust the cooling water flow rate through the jacket using flow control valve.
4. Wait for sufficient time until study state condition is achieved.
5. Note down the temperature using thermocouple channel on the control panel and
also the mass flow rate of water.
6. Change heat input to the metal rod and repeat the steps 1 to 5.
OBSERVATION TABLE
Table 1: Distance of thermocouple along metal rod
Temperature Distance X (m)
Sensor No.
1 0.035
2 0.075
3 0.115
4 0.155
5 0.195
6 0.235
Plot the variation of temperature along the length of the bar, from the plot determine dT/dx
OBJECTIVES
THEORY
Fourier’s Law of Heat Conduction is most easily verified (or tested) in the one-dimensional
configuration of this experiment. In equation form, Fourier’s Law is;
𝑑𝑇
𝑞 = −𝑘𝐴
𝑑𝑟
Where, q is the heat flowing through the insulating material of dimensions (W), k is the thermal
𝑑𝑇
conductivity of the material of dimension W/(m·K), A is the cross-sectional area (m2), and 𝑑𝑟 is
Consider the transfer of heat by conduction through the wall of a hollow sphere formed by the
insulating powdered layer packed between two thin copper spheres (Ref. Fig. 1). The heat
conduction through insulating power can be written as;
(𝑇𝑖 − 𝑇𝑜 )
𝑞 = 4𝜋𝑘𝑟𝑖 𝑟𝑜
(𝑟𝑜 − 𝑟𝑖 )
The thermal conductivity of insulating powder can be written as;
𝑞. (𝑟𝑜 − 𝑟𝑖 )
𝑘=
4𝜋𝑘𝑟𝑖 𝑟𝑜 (𝑇𝑖 − 𝑇𝑜 )
Average inner sphere temperature,
𝑇1 + 𝑇2 + 𝑇3 + 𝑇4
𝑇𝑖 =
4
Average outer sphere temperature,
𝑇5 + 𝑇6 + 𝑇7 + 𝑇8
𝑇𝑂 =
4
Heat input can be given as,
𝑞 = 𝑉. 𝐼
Knowing above parameters, the thermal conductivity of the insulating powder can be
determined.
APPARATUS
The apparatus consists of two thin-walled concentric copper spheres of different size.
Heating coil is provided in the inner sphere. The space between the inner and outer sphere is
filled by the insulating powder (Asbestos) whose thermal conductivity is to be determined.
The heat input to the heating coil is adjusted by using dimmer stat. Thermocouples are used
to record the temperature of insulating powder which are embedded on the outer shell
surface.
TECHNICAL SPECIFICATIONS
Test section
Radius of inner sphere : 0.05 m
Radius of outer sphere : 0.1 m
Heating Coil
Voltage : 220 V
Current : 5-15 Amp
Thermocouples
Type : “K” Type
Numbers : 10
Temperature range : 0-200C
Temperature accuracy : 0.5 C
OPERATION PROCEDURE
1. Connect the equipment to the power supply.
2. Adjust the heat input to the heater by slowly adjusting the dimmer stat and adjust
the voltage e.g., say 50 V.
3. Wait for sufficient time until study state condition is achieved.
4. See that this input remains constant throughout the experiment.
5. Note down the temperature using thermocouple channel on the control panel.
6. Change heat input to the metal rod and repeat the steps 1 to 5.
OBSERVATION TABLE
Under the steady state conditions the thermal conductivity of insulating power sample is
calculated as:
RESULT TABLE
Heat Thermal
Time Average temperature (Ti) Average temperature (To)
Input conductivity (k)
(Sec.) (C) (C)
(W) (W/m.C)
RESULTS AND DISCUSSIONS:
Draw the graph of time Vs. average temperature (Ti)
Draw the graph of average temperature (Ti) Vs. Thermal conductivity
Experiment No: Emissivity Measurement
OBJECTIVES
APPARATUS
The experimental set up consists of two circular plates of identical dimensions. One of the
plates is made black by applying a thick layer of lamp black while the other plate whose
emissivity is to be measured is non-black. Heating coils are provided at the bottom of both
plates. The plates are mounted on asbestos cement sheet and kept in an enclosure to
provide undisturbed natural convection conditions. The heat input to the plates is varied by
a dimmer stat and is measured by an ammeter and voltmeter. Each plate is provided with
three thermocouples for temperature measurement. One thermocouple is kept in the
chamber to read the ambient or chamber temperature.
Test section
Test plate diameter : 21.5 cm
Black plate diameter : 21.5 cm
Thickness : 1.5 cm
Water Heater
Voltage : 220 V
Ampere : 5 – 15 A
Thermocouples
Type : “K” Type
Numbers 8
Temperature accuracy : ± 0.5 °C
Temperature range : 0 – 200 °C
OPERATION PROCEDURE
𝑬 𝑻𝟒𝒈 − 𝑻𝟒∞
𝜺= = 𝟒
𝑬𝒃 𝑻𝒃 − 𝑻𝟒∞
RESULT TABLE
Time Tg, Gray Body Tb, Black Body T∞, Cabin
ε, Emissivity
(Sec.) Temperature (°C) Temperature (°C) Temperature (°C)
RESULTS AND DISCUSSIONS:
Draw the graph of Emissivity vs Temperature of the gray body and discuss the
variation in emissivity with change in temperature
Experiment No: Stefan Boltzmann Constant Verification
OBJECTIVES
1. To determine the value of Stefan Boltzmann constant for radiation heat transfer.
APPARATUS
This test rig consists of a Semi-sphere surrounded by hot water. Hot water is obtained from a
insulated water-heating tank. When the specimen is inserted at the center of semi-sphere, heat
is transferred to the disc from semi-sphere by radiation and its temperature begins to rise, and
from temperature rise rate. All temperatures (as shown in schematic diagram) data are shown
in temperature scanner. Hot water Tank temperature controlling by temperature controller.
System power, Voltage, Ampere data shown in the Energy Meter.
The severity of water circulation depends upon temperature as well as time of exposure and
therefore, various time temperature combinations have been proposed for our System. Good
understanding of the equipment experiments of Stefan Boltzmann.
TECHNICAL SPECIFICATIONS
Sr.
Component Detail / Technical specification
No
Power : 0.25 HP
1 Vacuum Pump Capacity : 1.8 CFM
Voltage Range : 220 - 230V, – 50 Hz (1-Ph)
OPERATION PROCEDURE
Fill Water tank for circulation.
Connect the system to the main power supply.
Switch on the Main switch from the panel box.
Set the water Temperature
Switch on the water Heater. Wait until hot temperature achieved
Switch on the vacuum pump and set vacuum pressure by closing the valve
Switch off the Vacuum Pump
Switch on the Water Pump
Adjust the water flow by Bypass valve
Note down Data as per requirements
OBSERVATION TABLE
Specimen
Chamber Temp. (C)
Time (Sec) Temp. (C) - TS
T4 T5 T6 TC (Avg.) T7
SHUTDOWN PROCEDURE
After complete the experiment, Switch of the Heater and Pump
Switch off the Main switch
Remove Main Supply
Drain the Water Tank.
𝒅𝑻𝑺
Using the temperature vs time characteristics of test disk, plot curve.
𝒅𝒕
Specimen
Time Average Chamber
Temp. – TC Qrad (W) σ (W/m2 k4)
(Sec) Temp. – TC
(C)
(C)
RESULTS AND DISCUSSIONS
Plot the test plate temperature vs time graph.
Compare experimental Steffen Boltzmann Constant with theoretical Steffen Boltzmann
Constant and write your results and discussion.
Experiment No: Heat Transfer in Natural Convection
OBJECTIVES
1. To determine the surface heat transfer coefficient for a vertical tube losing
heat by natural convection.
2. Theoretical determination of the surface heat transfer coefficient for a vertical
tube losing heat by natural convection.
3. Comparison of theoretical and measured surface heat transfer coefficient.
THEORY
Convection heat transfer occurs by the movement of fluid particles. If the motion of fluid
particles occurs by the variation of density of the fluid due to temperature difference, then the
heat transfer process is called free or natural convection.
The Newton’s law of cooling gives the rate of heat transfer in convection.
𝑞 = ℎ𝐴(𝑇𝑠 − 𝑇𝑎 )
Where h is Convective or film heat transfer co-efficient, h depends upon the fluid properties,
geometry of the surface, Ts is average surface temperature and T7, is ambient temperature. The
average surface temperature can be written as;
𝑇1 + 𝑇2 + 𝑇3 + 𝑇4 + 𝑇5 + 𝑇6
𝑇𝑠 =
6
From dimensional analysis as per the Buckingham - Theorem, a general relationship between
the Nusselt number (Nu), Prandtl number (Pr) and Grashoff number (Gr) been developed as
given below:
𝑁𝑢 = 𝑐(𝐺𝑟. 𝑃𝑟)𝑚
Where c and m are constants.
Nusselt Number:
𝐶𝑜𝑛𝑑𝑢𝑐𝑡𝑖𝑣𝑒 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝐻𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑏𝑦 𝑐𝑜𝑛𝑣𝑒𝑐𝑡𝑖𝑜𝑛
𝑁𝑢 = =
𝐶𝑜𝑛𝑣𝑒𝑐𝑡𝑖𝑣𝑒 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝐻𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑏𝑦 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑖𝑜𝑛
ℎ𝑡ℎ 𝐿
𝑁𝑢 =
𝐾𝑓
Where hth is theoretical heat transfer coefficient, kf is conductivity of air and L is characteristic
length of system.
Prandtl Number:
𝑀𝑜𝑚𝑒𝑛𝑡𝑢𝑚 𝐷𝑖𝑓𝑓𝑢𝑠𝑖𝑣𝑖𝑡𝑦
𝑝𝑟 =
𝑇ℎ𝑒𝑟𝑚𝑎𝑙 𝐷𝑖𝑓𝑓𝑢𝑠𝑖𝑣𝑖𝑡𝑦
𝑐𝑝 𝜇
𝑃𝑟 =
𝐾
Where cp specific heat of air, µ is viscosity of air and k conductivity of air.
Grashoff Number:
(𝐼𝑛𝑒𝑟𝑡𝑖𝑎 𝑓𝑜𝑟𝑐𝑒)(𝐵𝑜𝑢𝑦𝑎𝑛𝑡 𝑓𝑜𝑟𝑐𝑒)
𝐺𝑟 =
(𝑉𝑖𝑠𝑐𝑜𝑢𝑠 𝑓𝑜𝑟𝑐𝑒)
𝐿3 𝛽𝑔∆𝑇
𝐺𝑟 =
𝜐2
1
𝛽=
𝑇
Where 𝛽 is temperature coefficient, g is gravitational constant, ∆𝑇 is temperature difference
and 𝜐 kinematic viscosity of air and L is characteristic length of system.
Knowing above dimensionless numbers, the theoretical convection heat transfer coefficient can
be determined from above equation.
APPARATUS
The apparatus consists of a vertical brass tube enclosed in a rectangular duct. The front side
of the duct is made of transparent section to facilitate visual observation, while the duct is
open at top and bottom. An electrical heating element embedded in a copper tube acts as the
heat source. The surface temperature is measured at different heights using thermocouples.
The surface of the tube is polished to minimize radiation losses. A voltmeter and an ammeter
enable the determination of wattage dissipated by the heater. The chamber temperature can
also be measured.
Figure1: System Line Diagram
TECHNICAL SPECIFICATIONS
Tube
Material : Brass
Diameter : 0.038 m
Length : 0.5 m
Electric Heater
Voltage : 220 V
Current : 5-15 Amp
Thermocouples
Type : “K” Type
Numbers : 07
Temperature range : 0-200 °C
Temperature accuracy : ± 0.5 °C
OPERATION PROCEDURE
1. Connect the equipment to the power supply.
2. Adjust the heat input to the heater by slowly adjusting the dimmer stat and adjust
the voltage e.g., say 50 V.
3. Wait for sufficient time until study state condition is achieved.
4. Note down the temperature using thermocouple channel on the control panel.
5. Change the heat input and repeat the steps 1 to 4.
OBSERVATION TABLE
Ambient
Time Electric Heater Temperature on the surface of pipe (°C) Temperature
(Sec,) (°C)
V A W T1 T2 T3 T4 T5 T6 T7 T8
SHUTDOWN PROCEDURE
1. Adjust the heat input to the tube to zero by adjusting dimmer stat.
2. Turn off the main switch on the control panel.
3. Turn off the main switch and disconnect the test rig from the power supply.
SAMPLE CALCULATIONS: Reading No:________
𝑄𝑇 = 𝑉 ∗ 𝐼
𝐴𝑠 = 2𝜋𝑟𝐿
𝑄𝑐𝑜𝑛𝑣 = 𝑄𝑇 − 𝑄𝑟𝑎𝑑
𝑄𝑐𝑜𝑛𝑣 = ℎ𝐴𝑠 Δ𝑇
𝑄𝑐𝑜𝑛𝑣
ℎ𝑒𝑥𝑝 =
𝐴𝑠 Δ𝑇
RESULT TABLE
OBJECTIVES
1. To determine the convective heat transfer coefficient for air flows under forced
convection.
2. Theoretical determination of force convective heat transfer coefficient for above
conditions.
3. Comparison of theoretical and measured convective heat transfer coefficient.
THEORY
Convection heat transfer occurs by the movement of fluid particles. If the motion of fluid
particles occurs by the variation of density of the fluid due to temperature difference, then the
heat transfer process is called free or natural convection.
The Newton’s law of cooling gives the rate of heat transfer in convection.
𝑞 = ℎ𝐴(𝑇𝑠 − 𝑇𝑎 )
Where h is Convective or film heat transfer co-efficient, h depends upon the fluid properties,
geometry of the surface, Ts is average surface temperature and Tair,avg , is average ambient
𝑇1 + 𝑇2 + 𝑇3 + 𝑇4 + 𝑇5
𝑇𝑠 =
5
𝑇𝑖𝑛 + 𝑇𝑜𝑢𝑡
𝑇𝑎𝑖𝑟,𝑎𝑣𝑔 =
2
The experimental heat transfer coefficient is given as;
𝑞
ℎ𝑒𝑥𝑝 =
𝐴(𝑇𝑠 − 𝑇𝑎 )
The apparatus consists of a blower to supply air and test conduit. The air from the blower passes
through a flow passage, heater and then to the test section. Air flow is measured by an orifice
meter placed near the test section. A band heater placed around the tube heats the air and is
controlled by a dimmer stat. Temperature of the air at the inlet and outlet are measured using
thermocouples embedded in the walls at different distances from the entrance. Test section is
enclosed in a water jacket where the circulating water removes air. Water flow rate is
determined using a measuring jar. A bypass on the air system enables tests to be conducted at
different Reynolds numbers.
TECHNICAL SPECIFICATIONS
Test Section
Outer diameter of tube : 48 mm
Inner diameter of tube : 40 mm
Length of test section : 500 mm
Heating rod : 16 mm
Electric Heater
Voltage : 220 V
Current : 5-15 Amp
Blower
Capacity : 0.75 Hp
Thermocouples
Type : K Type
Temperature range : 0-200 °C
Temperature accuracy : ± 0.5 °C
OPERATION PROCEDURE
1. Connect the equipment to the power supply.
2. Switch on the main system.
3. Switch on the blower.
4. Switch on the heater.
5. Adjust the heat input to the heater by slowly adjusting the dimmer stat and adjust
the voltage
6. Wait for sufficient time until study state condition is achieved.
7. Note down the temperature using thermocouple channel on the control panel.
8. Change the heat input and repeat the steps 1 to 5.
OBSERVATION TABLE
𝑇1 + 𝑇2 + 𝑇3 + 𝑇4 + 𝑇5
𝑇𝑠 =
5
𝑇𝑖𝑛 + 𝑇𝑜𝑢𝑡
𝑇𝑎𝑖𝑟,𝑎𝑣𝑔 =
2
𝜋 2
𝑎 = 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑜𝑟𝑖𝑓𝑖𝑐𝑒 = 𝑑
4
𝜌𝑤𝑎𝑡𝑒𝑟
∆ℎ𝑎𝑖𝑟 = ∆ℎ𝑎𝑖𝑟 ×
𝜌𝑎𝑖𝑟
𝑄𝑎𝑖𝑟
𝑉𝑎𝑖𝑟 = , 𝐴𝑝 = 𝐴𝑟𝑒𝑎 𝑜𝑓 𝑃𝑖𝑝𝑒
𝐴𝑝
𝐴𝑠 = 2𝜋𝑟𝐿
𝑤
𝜎 = 5.67 ∗ 10−8
𝑚2 ∗ 𝐾4
𝑄𝑐𝑜𝑛𝑣 = 𝑄𝑇 − 𝑄𝑟𝑎𝑑
𝑄𝑐𝑜𝑛𝑣
ℎ𝑒𝑥𝑝 =
𝐴𝑠 Δ𝑇
Theoretical
𝑁𝑢 = 0.023(𝑅𝑒)0.8 (𝑃𝑟)0.4
𝜌𝑉𝑑
𝑅𝑒 =
𝑘
𝜇𝐶𝑝
𝑃𝑟 =
𝑘
ℎ𝑡ℎ × 𝐷
𝑁𝑢 = , 𝐷 = 𝐼𝑛𝑠𝑖𝑑𝑒 𝑑𝑖𝑎𝑚𝑡𝑒𝑟 𝑜𝑓 𝑝𝑖𝑝𝑒
𝑘
RESULT TABLE
Time Percentage
Qconv mair Tair,avg hexp hth
(Sec.) difference (∆h %)
RESULTS AND DISCUSSIONS
OBJECTIVES
1. To determine the effectiveness of heat exchanger under parallel flow and counter
flow condition.
2. To determine the overall heat transfer coefficient of heat exchanger under
parallel flow and counter flow condition.
3. Theoretical estimation of overall heat transfer coefficient for the experiment
conditions.
4. Comparison of experimental and theoretical heat transfer coefficient.
5. Determine NTU (no. of transfer unit for outer surface) for parallel flow
and counter flow conditions.
THEORY
A double pipe heat exchanger consists of two concentric, different diameter tubes with fluid
flowing in each as indicated in Figures 1. If the two fluids travel in opposite directions as illustrated
in Figure 1a, the exchanger is a counter flow type. If the fluids travel in the same direction as shown
in Figure 1b, parallel flow exists. The same apparatus is used for either flow configuration.
The heat exchange between the hot and cold water can be written as;
𝑞ℎ = 𝑚̇ℎ,𝑤 𝐶𝑝,𝑤 (𝑇ℎ𝑖 − 𝑇ℎ𝑜 )
Counter Flow -
∆𝑇1 − ∆𝑇2
(∆𝑇)𝐿𝑀𝑇𝐷 =
∆𝑇
l n (∆𝑇1 )
2
Effectiveness -
It is defined as the ration of actual heat transfer to maximum heat transfer that could be
possibly be transferred from one fluid to the other.
𝐶ℎ (𝑇ℎ𝑖 − 𝑇ℎ𝑜 ) 𝐶𝑐 (𝑇𝑐𝑜 − 𝑇𝑐𝑖 )
𝜀= =
𝐶𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 ) 𝐶𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 )
As shown in the Schematic Diagram from 65 ltr storage tank (heater in hot tank) Pump
circulate the water to the Heat exchanges. Electromagnetic Flow meter is used for the
measurement of the flow. Pump-1 is circulating the Hot water to the heat exchanger and
Pump-2 Circulate the Cold Water. Water flow is fully controllable by the VFD providing in
the control panel. For the temperature measurement RTD-pt100 Temp. sensor used. Flow
path, Temperature sensors & valves location and numbers are as shown in the above detail
schematic diagram.
TECHNICAL SPECIFICATIONS
Sr.
Part name Detail / Technical specification
No
Hot & Cold Water Capacity : 65 litres
1
Storage tanks MOC : SS304
Capacity : 3 kW
2 Water Heater
MOC : SS316
Make & Model : Lubi SMSJ 051
Power : 0.5 HP/0.37 kW
Centrifugal pumps Voltage : 415 V ( 3-phase )
3
(2 NOS) Contact part : SS
Head : 18 m
Current : 1.5 amp max
Make : Accumax
Type : Electromagnetic
4 Flow meter (2 NOS)
Range : 0-150 LPM
Line size : 1/2”
Heat Transfer Area : 0.15 m2
Internal Tube Dia : 1”
Internal Tube Material : Copper
Internal tube Thickness : 1.5 mm
Tube in Tube Heat
5 Internal Tube Length : 1500 mm
Exchanger
External Tube Dia : 2”
External Tube Material : SS304
External tube Thickness : 2 mm
External Tube Length : 1500 mm
Temperature Sensor
6
( 17 NOS ) RTD pt-100 type
OPERATION PROCEDURE
∆𝐓
𝒒 = 𝐔𝐨 𝐀 𝐨 ∆𝐓 =
∑𝐑
𝟏 𝟏 𝟏
= +
𝐔𝐨 𝐡𝐢 𝐡𝐨
𝑵𝒖 = 𝟎. 𝟎𝟐𝟑𝑹𝒆𝟎.𝟖 𝑷𝒓𝟏/𝟑
And
𝒉𝒊 𝒅𝒊
𝑵𝒖 =
𝑲
Where Dh = do-di
RESULT TABLE
A. Parallel Flow
Time mh mc qh qc q U-Exp ε, U-th
LMTD NTU
(Min) (kg/s) (kg/s) (W) (W) (W) (W/m2K) Effectiveness (W/m2K)
B. Counter Flow
Time mh mc qh qc q U-Exp ε, U-th
LMTD NTU
(Min) (kg/s) (kg/s) (W) (W) (W) (W/m2K) Effectiveness (W/m2K)
RESULTS AND DISCUSSIONS: (Discuss the results on following graphs)
1. Plot results of experimental value of Overall heat transfer vs Flow rate for both
parallel and counter flow
2. Plot results of theoretical and experimental value of Overall heat transfer vs Flow
rate for both parallel and counter flow
3. Plot results effectiveness vs Flow rate for both parallel and counter flow
Experiment No: Shell and Tube Heat Exchangers
OBJECTIVES
THEORY
The setup consists of two centrifugal pumps, two flow meters, two SS water storage
tank, a water heater, heat exchangers (tube in tube, plate heat exchanger, and shell & tube
Heat exchanger ), and a control panel. The schematic arrangement and flow diagram of
the setup are shown in Figure 2 and Figure 3.
As shown in the schematic diagram, from the 65-liter storage tank (heater in hot tank)
pump circulates the water to the heat exchanges. An electromagnetic flow meter is used
for the measurement of the flow. Pump-1 circulates the hot water to the heat exchanger
and pump-2 circulates the cold water. Water flow is fully controllable by the VFD provided
in the control panel. For the temperature measurement, RTD-pt100 temperature sensors
are used. Figure 3 shows the flow diagram of the setup and the corresponding
nomenclature are given in Table 1.
TC : Hot water tank temperature controller (oC)
T1 : Ambient temperature (oC)
T2 : Heat exchangers hot water inlet temperature (oC)
T3 : Tube in tube heat exchanger’s hot water inlet temperature (oC)
T4 : Tube in tube heat exchanger’s hot water outlet temperature (oC)
T5 : Tube in tube heat exchanger outlet hot water temperature (oC)
T6 : Plate heat exchanger outlet hot water temperature (oC)
T7 : Shell & Tube heat exchanger outlet hot water temperature (oC)
T8 : Customize heat exchanger outlet hot water temperature (oC)
T9 : Cold water tank temperature (oC)
T10 : Heat exchangers cold water inlet temperature (oC)
T11 : Tube in tube heat exchanger’s external tube cold water inlet temperature (oC)
T12 : Tube in tube heat exchanger’s external tube cold water outlet temperature (oC)
T13 : Tube in tube heat exchanger outlet cold water temperature (oC)
T14 : Plate heat exchanger outlet cold water temperature (oC)
T15 : Shell & Tube heat exchanger outlet cold water temperature (oC)
T16 : Customize heat exchanger outlet cold water temperature (oC)
Sr.
Part name Detail / Technical specification
No
Hot & Cold Water Capacity : 65 litres
1
Storage tanks MOC : SS304
Capacity : 3 kW
2 Water Heater
MOC : SS316
Make & Model : Lubi SMSJ 051
Power : 0.5 HP/0.37 kW
Centrifugal pumps Voltage : 415 V ( 3-phase )
3
(2 NOS) Contact part : SS
Head : 18 m
Current : 1.5 amp max
Type : Electromagnetic
4 Flow meter (2 NOS) Range : 0-150 LPM
Line size : 1/2”
Temperature
8 RTD pt-100 type
Sensor
A two tube pass and one shell pass shell and tube heat exchanger is investigated in this
experiment. The cross flow shell and tube heat exchanger (STHE) is treated as counter flow
with introduction of correction factor. Temperature profile of shell and tube heat exchanger
is shown in Figure 3. The hot fluid is pass to the shell side while cold fluid passes through
the tube side.
The heat exchange between the hot and cold water can be written as;
Effectiveness:
It is defined as the ration of actual heat transfer to maximum heat transfer that could be
possibly be transferred from one fluid to the other.
𝑄 𝐶𝑐 (𝑇𝑐𝑜 − 𝑇𝑐𝑖 )
𝜀= =
𝑄𝑚𝑎𝑥 𝐶𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 )
Where,
𝑄𝑚𝑎𝑥 = (𝑚𝐶𝑝 )𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 )
Also, the number of transfer units is given by
𝑈𝐴
𝑁𝑇𝑈 =
(𝑚𝐶𝑝 )𝑚𝑖𝑛
OPERATION PROCEDURE
1. Make all the connections as shown in figure and check valve positions and any
leakage through the system
2. Connect the equipment to the power supply.
3. Switch on the main system.
4. Adjust the desired flow rate of water
5. Switch on the electric geyser set the hot water temperature say 50 to 60 0C.
6. Allow sufficient time for thermal equilibrium to attain between hot and cold water
7. After reaching to thermal equilibrium conditions, note down the readings of
temperature by rotating knob.
8. Note down the reading of hot and cold-water flow rate.
9. Repeat the experiment for different flow rates.
10. Follow the steps 1 to 8 by changing the flow conditions through the test rig.
OBSERVATION TABLE
SHUTDOWN PROCEDURE
1. Turn off the electric geyser.
2. Allow cold water to flow through electric geyser till its temperature goes down to
room temperature.
3. Turn off the main switch on the control panel.
4. Turn off the main switch and disconnect the test rig from the power supply.
RESULT TABLE
Sr. mh mc Q U ε,
LMTD NTU
No (kg/s) (kg/s) (W) (W/m2K) Effectiveness
OBJECTIVES
THEORY
Plate heat exchangers (the plate and frame) were introduced in the 1930s mainly for
the food industries because of their ease of cleaning, and their design reached maturity in
the 1960s with the development of more effective plate geometries, assemblies, and
improved gasket materials. The range of possible applications has widened considerably
and, at present, under specific and appropriate conditions, overlaps and successfully
competes in areas historically considered to be the domain of tubular heat exchangers.
They are capable of meeting an extremely wide range of duties in many industries.
Therefore, they can be used as an alternative to tube-and-shell type heat exchangers for
low- and medium-pressure liquid-to-liquid heat transfer applications.
A typical plate heat exchanger is shown in an exploded view in Figure 1. The
elements of the heat exchanger are a fixed plate, compression plate, pressing equipment,
and connecting ports. The heat transfer surface is composed of a series of plates with parts
for fluid entry and exit in the four corners. The flow pattern through a plate heat exchanger
is illustrated in Figure 2.
APPARATUS
This setup consists of two centrifugal pumps, two flow meters, two SS water storage
tank, a water heater, heat exchangers (tube in tube, plate heat exchanger, and shell & tube
heat exchanger ), and a control panel. The schematic arrangement and flow diagram of the
setup are shown in Figure 3 and Figure 4.
As shown in the schematic diagram, from the 65-liter storage tank (heater in hot tank)
pump circulates the water to the heat exchanges. An electromagnetic flow meter is used
for the measurement of the flow. Pump-1 circulates the hot water to the heat exchanger
and pump-2 circulates the cold water. Water flow is fully controllable by the VFD provided
in the control panel. For the temperature measurement, RTD-pt100 temperature sensors
are used. Figure 2 shows the flow diagram of the setup and the corresponding
nomenclature are given in Table 1.
TC : Hot water tank temperature controller (oC)
T1 : Ambient temperature (oC)
T2 : Heat exchangers hot water inlet temperature (oC)
T3 : Tube in tube heat exchanger’s hot water inlet temperature (oC)
T4 : Tube in tube heat exchanger’s hot water outlet temperature (oC)
T5 : Tube in tube heat exchanger outlet hot water temperature (oC)
T6 : Plate heat exchanger outlet hot water temperature (oC)
T7 : Shell & Tube heat exchanger outlet hot water temperature (oC)
T8 : Customize heat exchanger outlet hot water temperature (oC)
T9 : Cold water tank temperature (oC)
T10 : Heat exchangers cold water inlet temperature (oC)
T11 : Tube in tube heat exchanger’s external tube cold water inlet temperature (oC)
T12 : Tube in tube heat exchanger’s external tube cold water outlet temperature (oC)
T13 : Tube in tube heat exchanger outlet cold water temperature (oC)
T14 : Plate heat exchanger outlet cold water temperature (oC)
T15 : Shell & Tube heat exchanger outlet cold water temperature (oC)
T16 : Customize heat exchanger outlet cold water temperature (oC)
Sr.
Part name Detail / Technical specification
No
Hot & Cold Water Capacity : 65 litres
1
Storage tanks MOC : SS304
Capacity : 3 kW
2 Water Heater
MOC : SS316
Make & Model : Lubi SMSJ 051
Power : 0.5 HP/0.37 kW
Centrifugal pumps Voltage : 415 V ( 3-phase )
3
(2 NOS) Contact part : SS
Head : 18 m
Current : 1.5 amp max
Type : Electromagnetic
4 Flow meter (2 NOS) Range : 0-150 LPM
Line size : 1/2”
The heat transfer in plate heat exchanger is obtained by considering it as a counter flow
arrangement with introduction of correction factor and given as;
𝑞 = 𝐹 𝑈0 𝐴0 (∆𝑇)𝐿𝑀𝑇𝐷
Where, F is the correction factor, U0 is over all heat transfer coefficient, A0 is outer surface
area of tube and (∆T)LMTD is Logarithmic Mean Temperature Difference.
𝑞
𝑈0,𝐸𝑥𝑝 = 𝐹 𝐴 (∆𝑇)
0 𝐿𝑀𝑇𝐷
The heat exchange between the hot and cold water can be written as;
Effectiveness
It is defined as the ration of actual heat transfer to maximum heat transfer that could be
possibly be transferred from one fluid to the other.
𝑄 𝐶𝑐 (𝑇𝑐𝑜 − 𝑇𝑐𝑖 )
𝜀= =
𝑄𝑚𝑎𝑥 𝐶𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 )
Where,
𝑄𝑚𝑎𝑥 = (𝑚𝐶𝑝 )𝑚𝑖𝑛 (𝑇ℎ𝑖 − 𝑇𝑐𝑖 )
Also, the number of transfer units is given by
𝑈𝐴
𝑁𝑇𝑈 =
(𝑚𝐶𝑝 )𝑚𝑖𝑛
OPERATION PROCEDURE
1. Make all the connections as shown in figure and check valve positions and any
leakage through the system
2. Connect the equipment to the power supply.
3. Switch on the main system.
4. Adjust the desired flow rate of water
5. Switch on the electric geyser set the hot water temperature say 50 to 60 0C.
6. Allow sufficient time for thermal equilibrium to attain between hot and cold water
7. After reaching to thermal equilibrium conditions, note down the readings of
temperature by rotating knob.
8. Note down the reading of hot and cold-water flow rate.
9. Repeat the experiment for different flow rates.
10. Follow the steps 1 to 8 by changing the flow conditions through the test rig.
OBSERVATION TABLE
Hot Water Cold Water
Sr.
Flow rate Inlet Outlet Flow rate Inlet Outlet
No
(LPM) Temp. (°C) Temp. (°C) (LPM) Temp. (°C) Temp. (°C)
SHUTDOWN PROCEDURE
RESULT TABLE
Sr. mh mc Q U ε,
LMTD NTU
No (kg/s) (kg/s) (W) (W/m2K) Effectiveness