Konzol Klíma A-F 2,7-3,5-5,3kw Gépkönyv (Eng)
Konzol Klíma A-F 2,7-3,5-5,3kw Gépkönyv (Eng)
Service Manual
Table of Contents
Part Ⅰ : Technical Information........................................................................1
1. Summary.......................................................................................................................1
2. Specifications...........................................................................................................3
2.1 Specification Sheet............................................................................................................3
2.2 Operation Characteristic Curve.........................................................................................7
2.3 Capacity Variation Ratio According to Temperature..........................................................7
2.4 Noise Curve.......................................................................................................................8
3. Outline Dimension Diagram..........................................................................................9
3.1 Indoor Unit.........................................................................................................................9
3.2 Outdoor Unit....................................................................................................................10
4. Refrigerant System Diagram.....................................................................12
5. Electrical Part.........................................................................................................13
5.1 Wiring Diagram................................................................................................................13
5.2 PCB Printed Diagram......................................................................................................16
6. Function and Control.......................................................................................19
6.1 Remote Controller Introduction ......................................................................................19
6.2 GREE+ App Operation Manual.......................................................................................23
6.3 Ewpe Smart App Operation Manual................................................................................24
6.4 Brief Description of Modes and Functions.......................................................................25
Table of Contents
Service Manual
Appendix:.........................................................................................................................88
Appendix 1: Reference Sheet of Celsius and Fahrenheit.....................................................88
Appendix 2: Configuration of Connection Pipe......................................................................88
Appendix 3: Pipe Expanding Method....................................................................................89
Appendix 4: List of Resistance for Temperature Sensor.......................................................90
Table of Contents
Service Manual
GEH12AA-K6DNA1A/I
GEH09AA-K6DNA1F/I
GEH18AA-K6DNA1F/I
Outdoor Unit
GEH09AA-K6DNA1F/O GEH12AA-K6DNA1A/O
GEH18AA-K6DNA1F/O
Remote Controller
YAA1FB8(WiFi)
Technical Information 1
Service Manual
Model List:
2 Technical Information
Service Manual
2. Specifications
2.1 Specification Sheet
Technical Information 3
Service Manual
The above data is subject to change without notice. Please refer to the nameplate of the unit.
4 Technical Information
Service Manual
Technical Information 5
Service Manual
The above data is subject to change without notice. Please refer to the nameplate of the unit.
6 Technical Information
Service Manual
Cooling Heating
11 11
220V 220V
10 • Conditions 10
Indoor : DB27˚C/WB19˚C
9 Outdoor : DB35˚C/WB24˚C 9
8 Indoor air flow : High 8
Pipe length : 5m
7 7
Current (A)
Current (A)
230V
6 230V 6
5 5
240V
4 4
3 3 • Conditions
240V Indoor : DB20˚C/WB15˚C
2 2 Outdoor : DB7˚C/WB6˚C
1 1 Indoor air flow : High
Pipe length : 5m
0 0
0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120
Compressor frequency(Hz) Compressor frequency(Hz)
Cooling Heating
140
140
120
Capacity ratio(%)
120
Capacity ratio(%)
100
100
80
80
60 Conditions
Condition 60 Indoor:DB20°C
40 Indoor:DB27°C WB19°C Indoor air flow:Super High
Indoor air flow: High 40
Pipe length:5m
20 Pipe length:5m
20
0
0
-15 -10 -5 0 5 10 15 20 25 30 35 43
-22 -15 -10 -7 0 2 7 15 18 21 24
Outdoor temp.(°C)
Outdoor temp.(°C)
Technical Information 7
Service Manual
Noise dB(A)
30
Noise dB(A)
30 50 Cooling
49 Cooling
20 09K 49
Heating
20 48 48 Heating
47
46 47
SH H HM M LM L SL
45
SL L LM M HM
Indoor fan motor rotating speed
H SH 14615
2 20
3 425 5306357408 459 50
10 55
11 60
12 13
65 14
70 15
7516
801785
Indoor fan motor rotating speed Compressor frequency(Hz)
Compressor frequency(Hz)
8 Technical Information
Service Manual
700 215
600
205 398
22
Unit:mm
Technical Information 9
Service Manual
596
320 320
848
286 Unit:mm
540
GEH09AA-K6DNA1F/O
257 712
540
320 782
286
Unit:mm Unit:mm
510
10 Technical Information
Service Manual
GEH18AA-K6DNA1F/O
341 892
700
396 963
368
Unit:mm
560
Technical Information 11
Service Manual
Gas pipe
side
Valve
4-Way valve
Discharge
Heat Suction
exchanger
(evaporator)
Heat
exchanger
Liquid pipe (condenser)
side
Valve Electron
Strainer Strainer
expansion
valve
COOLING
HEATING
12 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
GEH12AA-K6DNA1A/I GEH18AA-K6DNA1F/I
:$51,1*
52207(03 78%(7(03 5(&(,9(5$1' 6:,7&+ )$1 02725 3OHDVHGRQ WWRXFKDQ\HOHFWURQLF
6(1625 6(1625 ',63/$<%2$5' 6(/(&7 0
FRPSRQHQWRUWHUPLQDOZKHQWKH
PDFKLQHLVUXQQLQJVWRSSLQJRU
$3 ',63/$< 6 KDVEHHQSRZHUHGRIIIRUOHVV
$3 WKDQPLQXWHVWRSUHYHQW
HOHFWULFVKRFN
57 57 0$*1(7,&
/
5,1*
02725)5$0(
5220 78%( ',63 ',63 &1 '&02725 0$*1(7,&
2* 5,1*
&1 ;7
/
%8 %8
287'22581,7
$335,17('&,5&8,7%2$5' 1 1
/
&$3 &20287
%. %.
/ %1
%1
-803 $&/
<(*1
<(*1 <(*1
6:,1*'2:1 6:,1*83 :,), &200$18$/ (
7(50,1$/
+($/7+/ +($/7+1 <(*1 %/2&.
5' %8
3( 3(
0 0 (9$325$725 (/(&75,&%2;
5' %8
$3 $3
67(33,1* 67(33,1* :,),02'8/( :,5(' &2/'3/$60$
02725 02725 237,21$/ &21752//(5 *(1(5$725
60000700126803
237,21$/
Technical Information 13
Service Manual
GEH09AA-K6DNA1F/I
:$51,1*
52207(03 78%(7(03 5(&(,9(5$1' 6:,7&+ )$1 02725 3OHDVHGRQ WWRXFKDQ\HOHFWURQLF
6(1625 6(1625 ',63/$<%2$5' 6(/(&7 0
FRPSRQHQWRUWHUPLQDOZKHQWKH
PDFKLQHLVUXQQLQJVWRSSLQJRU
$3 ',63/$< 6 KDVEHHQSRZHUHGRIIIRUOHVV
$3 WKDQPLQXWHVWRSUHYHQW
HOHFWULFVKRFN
57 57
02725)5$0(
5220 78%( ',63 ',63 &1 '&02725 0$*1(7,&
2* 5,1*
&1 ;7
/
%8 %8
287'22581,7
$335,17('&,5&8,7%2$5' 1 1
/
&$3 &20287
%. %.
/ %1
%1
-803 $&/
<(*1
<(*1 <(*1
6:,1*'2:1 6:,1*83 :,), &200$18$/ (
7(50,1$/
+($/7+/ +($/7+1 <(*1 %/2&.
5' %8
3( 3(
0 0 (9$325$725 (/(&75,&%2;
5' %8
$3 $3
67(33,1* 67(33,1* :,),02'8/( :,5(' &2/'3/$60$
02725 02725 237,21$/ &21752//(5 *(1(5$725
237,21$/ 600007001268
● Outdoor Unit
GEH09AA-K6DNA1F/O
UXQQLQJVWRSSLQJRUKDVEHHQ
(.9
5,1*
SRZHUHGRIIIRUOHVVWKDQ / / <9
PLQXWHVWRSUHYHQWWKHULVN N57 57 57
N N 97 97
RIHOHFWULFVKRFN
/; /;
%8 ;7 0$*1(7,&5,1* &1 &1 :$<
/ %8 /
,1'22581,7
11 1
%. / %. $30DLQ%RDUG
&208
%1 / %1 /
/ $&/ $&/
<(*1 <(*1 <(*1 3( 29&&203 +($7 2)$1
8 9 :
7(50,1$/ 5' 5'
1 %8 %/2&. %8 <( 5'
0$*1(7,&
/ %1 %. 3(
;
5,1*
14 Technical Information
Service Manual
GEH18AA-K6DNA1F/O
7(036(1625
7(036(1625
7(036(1625
:$51,1* 29(5/2$'3527(&725
3OHDVHGRQ WWRXFKDQ\ 6$7
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH &203
RIWHUPLQDO3 '& DQG :+ :+ 8 &203
1 '& DW$3LVKLJKHU 9 :
WKDQ9WRSUHYHQWWKH 0$*1(7,&
ULVNRIHOHFWULFVKRFN 57 57 57 5,1* / / /
%8 <( 5'
. . .
<(*1 ;
7(50,1$/ :+ %. %8 <( 5'
,1'22581,7
GEH12AA-K6DNA1A/O
UXQQLQJVWRSSLQJRUKDVEHHQ
(.9
5,1*
SRZHUHGRIIIRUOHVVWKDQ / / <9
PLQXWHVWRSUHYHQWWKHULVN 57 57 57
N N N 97 97
RIHOHFWULFVKRFN
/; /;
%8 ;7 0$*1(7,&5,1* &1 &1 :$<
%8 /
,1'22581,7
11 1
%. %. / $30DLQ%RDUG
&208
%1 %1 /
/ $&/ $&/
<(*1 <(*1 <(*1 3( 29&&203 +($7 2)$1
8 9 :
7(50,1$/ 5' 5'
1 %8 %/2&. %8 <( 5'
0$*1(7,&
/ %1 %. ;
5,1*
These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
Technical Information 15
Service Manual
● Top view
8 9 10 11 12 13 14 NO. Name
Interface of tube temperature
1 sensor
Interface of ambient temperature
2 sensor
3 Up swing interface
4 Down swing interface
17 5 WIFI interface
6 Interface of EMC shielding wire
16 7 DC motor interface
8 Earthing wire of main board
9 Terminal of live wire
10 Fuse
11 Terminal for health function
12 Terminal of neutral wire
5 Communication interface
13 between indoor unit and outdoor
15 unit
14 Control interface of Down swing
15 Wired controlled interface
16 Needle stand of jumper cap
17 Interface of display board
7 4 3 2 1
● Bottom view 6
16 Technical Information
Service Manual
Outdoor Unit
09/12K
● Top view
13
3
13 4
5 No. Name
1 Interface of compressor wire
2 Reactor wiring terminal 2
3 Reactor wiring terminal 1
2 4 Terminal of chassis electric heater
5 4-way valve terminal
6 Grounding wire
7 Neutral wire
8 Communication wire
9 Live wire
6
10 Terminal of electronic expansion valve
11 Interface of temperature sensor
12 Overload interface of compressor
13 Terminal of outdoor fan
1
7
8
9
12 11 10
● Bottom view
Technical Information 17
Service Manual
GEH18AA-K6DNA1F/O
● Top view
1 2 3 4 5 6 7 8 9 10
No Name
11 1 Compressor wiring terminal for U V W
2 Terminal of system high pressure protection
3 Compressor overload protection terminal
4 Interface of temperature sensor
5 Terminal of electronic expansion valve
6 Terminal of system low pressure protection
7 Terminal of outdoor fan
8 4-way valve terminal
12
13
9 Terminal of compressor electric heater
10 Terminal of compressor electric heater
11 Interface of electric heating belt of chassis
14
12 Terminal of power supply live wire terminal
Interface of communication wire for indoor unit
13 and outdoor unit
14 Terminal of power supply earthing wire
15 Terminal of power supply neutral wire
15
● Bottom view
18 Technical Information
Service Manual
1 ON/OFF button
Press this button to turn on the unit. Press this button again to turn off the unit.
2 - button
Press this button to decrease set temperature. Holding it down above 2 seconds rapidly decreases set temperature. In AUTO
mode, set temperature is not adjustable.
+ button
Press this button to increase set temperature. Holding it down above 2 seconds rapidly increases set temperature. In AUTO
mode, set temperature is not adjustable.
Technical Information 19
Service Manual
3 MODE button
Each time you press this button , a mode is selected in a sequence that goes from AUTO,COOL, DRY, FAN, and HEAT * , as the
following:
After energization, AUTO mode is defaulted. In AUTO mode, the set temperature will not be displayed on the LCD, and the unit
will automatically select the suitable operation mode in accordance with the room temperature to make indoor room comfortable.(As
for cooling only unit,it won’t have any action when it receives the signal of heating operation.)
4 FAN button
This button is used for setting Fan Speed in the sequence that goes from AUTO, , , , to , then back
to Auto.
Auto
5 SWING button
Press this button to set up &down swing angle, which circularly changes as below:
This remote controller is universal. If any command , or is sent out, the unit will carry out the command as
indicates the guide louver swings as:
6 I FEEL button
Press this button to turn on I FEEL function. The unit automatically adjust temperature according to the sensed temperature.
Press this button again to cancel I FEEL function.
7 / button
Press this button to achieve the on and off of healthy and scavenging functions in operation status. Press this button for the
first time to start scavenging function; LCD displays " ". Press the button for the second time to start healthy and scavenging
functions simultaneously; LCD displays " " and " ". Press this button for the third time to quit healthy and scavenging
functions simultaneously. Press the button for the fourth time to start healthy function; LCD display " ". Press this button again
to repeat the operation above.
8 SLEEP button
Press this button, can select Sleep 1 ( ), Sleep 2 ( ),Sleep 3 ( ) and cancel the Sleep,circulate between these, after
electrified, Sleep Cancel is defaulted.
Sleep 1 is Sleep mode 1, in Cool mode: after run for one hour in sleep mode, the main unit setting temperature will increase 1 ,
after 2 hours, the setting temperature will increase 2 , but the maximal setting temperature is 30 , then the unit will run at
this setting temperature all along; In Heat mode: after run for one hour in sleep mode, the setting temperature will decrease 1
after 2 hours the setting temperature will decrease 2 , but the minimal setting temperature is 16 , then the unit will run at this
setting temperature all along.
Sleep 2 is sleep mode 2, that is air conditioner will run according to the presetting a group of sleep temperature curve.
Sleep 3- the sleep curve setting under Sleep mode by DIY:
20 Technical Information
Service Manual
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation sleep setting status, at this
time, the time of remote control will display "1hour ",the setting temperature "88" will display the corresponding temperature of last
setting sleep curve and blink (The first entering will display according to the initial curve setting value of original factory);
(2) Adjust "+" and "-" button, could change the corresponding setting temperature, after adjusted, press "Trubo "button for confirmation;
(3) At this time, 1hour will be automatically increased at the timer postion on the remote control, (that are "2hours " or "3hours " or
"8hours "), the place of setting temperature "88" will display the corresponding temperature of last setting sleep curve and blink;
(4) Repeat the above step (2) (3) operation, until 8hours temperature setting finished,sleep,curve setting finished, at this time, the
remote control will resume the original timer display;temperature display will resume to original setting temperature.
Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired:
The user could accord to sleep curve setting method to inquire the presetting sleep curve,enter into user individuation sleep setting
status, but do not change the temperature, press "Turbo" button directly for confirmation.Note: In the above presetting or enquiry
procedure,if continuously within10s, there is no button pressed, the sleep curve setting within 10s, there is no button pressed , the sleep
curve setting status will be automatically quit and resume to display the original displaying. In the presetting or enquiry procedure, press
"ON/OFF" button, "Mode" button, "Timer"button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
9 TEMP button
Press this button, you can see indoor set temperature, indoor ambient temperature on indoor unit’s display. The setting on remote
controller is selected circularly as below:
no display
When selecting " " with remote controller or no display, temperature indicator on indoor unit displays set temperature; When
selecting " " with remote controller, temperature indicator on indoor unit displays indoor ambie nt temperature; 5s later or within 5s
it receives other remote control signal that will return to display the setting temperature.
Caution:
This model hasn't outdoor ambient temperature display function. While remote controller
can operate " " and indoor unit displays set temperature.
It’s defaulted to display set temperature when turning on the unit.
Only for the models with temperature indicator on indoor unit.
10 QUIET button
Auto
Press this button, the Quiet status is under the Auto Quiet mode (display " "signal )and Quiet mode (display " " singal) and Quiet
OFF (there is no signal of " "displayed),after powered on, the Quiet OFF is defaulted. Note: the Quiet function cannot be set up in
Fan and Dry mode;Under the Quiet mode (Display" " Under the Quiet mode) the fan speed is not available.
11 ClOCK button
Press CLOCK button,blinking. Within 5 seconds, pressing + or - button adjusts the present time. Holding down either button above
2 seconds increases or decreases the time by 1 minute every 0.5 second and then by 10 minutes every 0.5 second. During blinking
after setting, press CLOCK button again to confirm the setting, and then will be constantly displayed.
13 TURBO button
Press this button to activate / deactivate the Turbo function which enables the unit to reach the preset temperature in the shortest time.
In COOL mode, the unit will blow strong cooling air at super high fan speed. In HEAT mode, the unit will blow strong heating air at super
high fan speed.
Technical Information 21
Service Manual
14 WiFi button
Press " WiF "i button to turn on or turn off WiFi function. When WiFi function is turned on, the " W i F i " icon will be displayed on remote
controller; Under status of unit off, press "MODE" and "W i F i " " buttons simultaneously for 1s, WiFi module will restore to factory
default setting.
● This function is only available for some models.
15 LIGHT button
Press LIGHT button to turn on the display's light and press this button again to turn off the display 's light. If the light is turned on , is
displayed. If the light is turned off, disappears.
If “H1” is displayed on the remote controller while it’s not operated by the professional person/after-sales person, it belongs to the
misoperation.
Please operate it as below to cancel it.Under the OFF status of remote controller, hold the Mode button for 5s to cancel “H1” display.
Note:
● If remote controller displays “H1”, it belongs to the normal function reminder. If the unit is defrosting under heating mode, it operates
according to H1 defrosting mode. “H1” won’t be displayed on the panel of indoor unit;
● Once you set H1 mode, if you turn off unit by remote controller, H1 will display 3 times on the remote controller and then disappear;
● Also, when you set H1 mode, when you change to heating mode, H1 will display 3 times on the remote controller and then disappear.
Note: battery
● During operation, point the remote control signal sender at the receiving window
on indoor unit.
reinstall
● The distance between signal sender and receiving window should be no more than
8m, and there should be no obstacles between them.
remove
● Signal may be interfered easily in the room where there is fluorescent lamp or
wireless telephone; remote controller should be close to indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries. Cover of battery box
● If the display on remote controller is fuzzy or there’s no display, please replace
batteries.
22 Technical Information
Service Manual
Internet
Gree Cloud
Gree
intelligent Home Wi-Fi Cellular/
home Other Wi-FI
appliances
Home wireless router
Home Wi-Fi
GREE+ APP
Operating Systems
Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances.
For more information, please refer to "Help" in App.
Technical Information 23
Service Manual
Internet
Cloud
Operating Systems
Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed,
register the account and add the device to achieve long-distance control and LAN control of smart home appliances.
For more information, please refer to "Help" in App.
24 Technical Information
Service Manual
Technical Information 25
Service Manual
26 Technical Information
Service Manual
Warnings
cient fixing bolt must be installed; make sure the installation
support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur-
ing installation.
Electrical Safety Precautions: 6. Make sure no foreign objects are left in the unit after fin-
ishing installation.
1. Cut off the power supply of air conditioner before
checking and maintenance. Improper installation may lead to fire hazard, explosion,
2. The air condition must apply specialized circuit and electric shock or injury.
prohibit share the same circuit with other appliances.
3. The air conditioner should be installed in suitable
location and ensure the power plug is touchable.
4. Make sure each wiring terminal is connected firmly
during installation and maintenance.
5. Have the unit adequately grounded. The grounding
wire cant be used for other purposes.
6. Must apply protective accessories such as protective
boards, cable-cross loop and wire clip.
7. The live wire, neutral wire and grounding wire of
power supply must be corresponding to the live wire,
neutral wire and grounding wire of the air conditioner.
8. The power cord and power connection wires cant be
pressed by hard objects.
9. If power cord or connection wire is broken, it must be
replaced by a qualified person.
Warnings
1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in
injury.
2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling
mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low
pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery
should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service
center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so
that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire.
WARNING:
●Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.
Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualified
personnel may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for
example:open flames , an operating gas appliance or an operating electric heater.)
●Do not pierce or burn.
●Appliance shall be installed, operated and stored in a room with a floor area larger than “X”m2 (see table a).(only applies to
appliances that are not fixed appliances).
●Appliance filled with flammable gas R32. For repairs, strictly follow manufacturer’s instructions only.Be aware that
refrigrants not contain odour.
●Read specialists manual.
Installation notes
●The air conditioner is not allowed to use in a room that has running fire (such as fire source,working coal gas ware,
operating heater).
●It is not allowed to drill hole or burn the connection pipe.
●The air conditioner must be installed in a room that is larger than the minimum room area.
The minimum room area is shown on the nameplate or following table a.
●Leak test is a must after installation.
table a - Minimum room area(m2)
Charge amount (kg) ≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
floor location 4 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
Minimum
room window mounted 4 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
area( m 2 )
wall mounted 4 4 4 4 4 4 4 4 4 4.2 4.6 5 5.5 6
ceiling mounted 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Maintenance notes
●Check whether the maintenance area or the room area meet the requirement of the nameplate.
— Its only allowed to be operated in the rooms that meet the requirement of the nameplate.
●Check whether the maintenance area is well-ventilated.
— The continuous ventilation status should be kept during the operation process.
●Check whether there is fire source or potential fire source in the maintenance area.
— The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.
●Check whether the appliance mark is in good condition.
— Replace the vague or damaged warning mark.
Welding
●If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below:
a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding
●Make sure that there isnt any naked flame near the outlet of the vacuum pump and its well-ventilated.
●The refrigerant should be recycled into the specialized storage tank.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Requirements for Electric Connection
1. Safety Precaution
(1) Must follow the electric safety regulations when installing the unit.
(2) If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to
(avoid a hazard.
(3) According to the local safety regulations, use qualified power supply circuit and air switch.
(4) A air switch having a contact separation of at least 3mm in all poles should be fixed in fixed wiring.
(5) The appliance shall be installed in accordance with national wiring regulation.
(6) The air switch must have the functions of magnetic tripping and heat tripping in order to prevent short circuit or overload. Please
install the air switch with suitable capacity according to the sheet below.
(7) Make sure the power supply matches with the requirement of air conditioner.Unstable power supply or incorrect wiring may result
in electric shock, fire hazard or malfunction. Please install proper power supply cables before using the air conditioner.
(8) Properly connect the live wire, neutral wire and grounding wire of power socket.
(9) Be sure to cut off the power supply before proceeding any work related to electric safety.
(10) Do not put through the power before finishing installation.
2. Grounding Requirement
(1) The air conditioner is first class electric appliance. It must be properly grounded with specialized grounding device by a
professional. Please make sure it is always grounded effectively, otherwise it may cause electric shock.
(2) The yellow-green wire in air conditioner is grounding wire, which can't be used for other purposes.
(3) The grounding resistance should comply with national electric safety regulations.
(1) Such a place where cool air can be distributed throughout the
room.
(2) Such a place where condensation water is easily drained out.
(3) Such a place that can handle the weight of indoor unit.
(4) Such a place which has easy access for maintenance.
(5) The appliance shall not be installed in the laundry. Molding
Grid(field supply)
Floor lnstallation Wall Installation
There are 2 styles of installation
● Ceiling type ● Floor type Location for securing the installation panel.
Each type is similar to the other as follows:
The indoor unit should be sited in a place where:
700
(1) The restrictions on installation specified in the indoor unit
installation drawings are met.
(2) Both air intake and exhaust have clear paths met. 200
(3) The unit is not in the path of direct sunlight.
(4) The unit is away from the source of heat or steam.
120
(8) The unit is at least 1 metre away from any television or radio
30
set(unit may cause interference with the picture or sound).
0
16
Unit: mm
30
Installation and Maintenance 31
Service Manual
70mm
Installtion or more
paper plank
50mm
or more
50mm
or more
3. Refrigerant Piping
(1) Drill a hole ( 65mm in diameter ) in the spot indicated by the symbol in the illustration ad below .
(2) The location of the hole is different depending on which side of the pipe is taken out .
(3) For piping ,see6.Connecting the refrigerant pipe , under Indoor Unit Installation.
(4) Allow space around the pipe for a easier indoor unit pipe connection.
Wall
45
60
45
45
45
Unit: mm
CAUTION
Min.allowable length
●The suggested shortest pipe length is 2.5m,in order to avoid noise from the outdoor unit and vibration. (Mechanical noise and
vibration may occur depending on how the unit is installed and the environment in which it is used.)
●See the installation manual for the outdoor unit for the maximum pipe length.
●For multi-connections ,see the installation manual for the multi-outdoor unit.
wall
350
Refrigerant pipe
45
Floor Unit: mm
75
4. Boring a Wall Hole and Installing Wall Embedded Pipe
● For walls containing metal frame or metal board ,be sure to use a wall embedded
pipe and wall cover in the feed-through hole to Inside Outside
Wall embedded pipe
● Be sure to caulk the gaps around the pipes with caulking material to prevent (field supply)
Caulking
water leakage.
(1) Bore a feed-through hole of 55mm in the wall so it has a down slope toward the
outside. Φ55 mm
(2) Insert a wall pipe into the hole. Wall hole cover
(field supply)
(3) Insert a wall cover into wall pipe . Wall embedded pipe
(field supply)
(4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with
putty.
5. Drain Piping
(1) Use commercial regid polyvinyl chloride pipe general VP 20 pipe, outer diameter 26mm, inner diameter 20mm for the drain pipe.
(2)The drain hose (outer diameter 18mm at connecting end, 220mm long)is supplied with the indoor unit. Prepare the drain pipe picture below
position.
(3) The drain pipe should be inclined downward so that water will flow smoothly without any accumulation.(Should not be trap.)
(4) Insert the drain hose to this depth so it wont be pulled out of the drain pipe.
(5) Insulate the indoor drain pipe with 10mm or more of insulation material to prevent condensation.
(6) Remove the air filters and pour some water into the drain pan to check the water flows smoothly.
3 tabs
6. Installing Indoor Unit
Preparation Casing
■For Moldings
●Remove the pillars. (Remove the slit portions on the
bottom frame using nippers.) Remove 4 screws Open the front panel
Bottom frame
Casing
Casing
Installation
●Secure using 6 screws for floor installations.(Do not forget to secure to the rear wall.)
●For wall installations, secure the mounting plate using 5 screws and the indoor unit using 4 screws.The mounting plate should be
installed on a wall which can support the weight of the indoor unit.
(1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the
wall.
(2) Secure the mounting plate to the wall with screws.
Casing 200m
m
Molding
6screws
6screws
(3) Once refrigerant piping and drain piping connections are complete, fill in the gap of the through hole with putty. A gap can lead to
condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes.
(4) Attach the front panel and front grille in their original positions once all connections are complete.
CAUTION
(1) DO not use mineral oil on flared part.
(2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
(3) Never use piping which had been used for previous installations. Only use parts which are delivered with the unit.
(4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
(5) The drying material may dissolve and damage the system.
(6) Incomplete flaring may cause refrigerant gas leakage.
If no flare cap is
available,cover
the flare mouth
with tape to keep
dirt or water out.
When using commercial copper pipes and fittings, observe the Gas pipe
following: Liquid pipe
(1) Insulation material: Polyethylene foam
Heat transfer rate:0.041 to 0.052W/mK(0.035 to 0.045kca/(mhoC
Liquid pipe
Refrigerant gas pipes surface temperature reaches 110 max. Gas pipe insulation
insulstion
Choose heat insulation materials that will withstand this temperature.
Finising tape
(2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Liquid pipe
Gas side Liquid side Gas pipe thermal insulation
thermal insulation
09/12K 18K 09/12K 18K
O.D. 9.55mm O.D. 12.7mm O.D. 6.4mm I.D. 12-15mm I.D. 14-16mm I.D. 8-10mm
Thickness 0.8mm Thickness 10mm Min.
(3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Refrigerant
pipe Refrigerant Refrigerant
pipe pipe
Slit
Slit
Insulation sheet
Tape
Auxiliary pipe
CAUTION
(1) Insulate the joint of the pipes securely. Incomplete insulation may lead to water leakage.
(2) Push the pipe inside so it does not place undue force on the front grille.
Indoor unit
Wire retainer
Firmly secure wire
retainer so that
wires sustain no
Front metal external stress. Use the specified wire type.
Firmly fix the wires with the
plate cover
terminal screws
CAUTION
(1) Do not use tapped wires, stranded wires, extensioncords, or starburst connections, as they may cause overheating,
electrical shock, or fire.
(2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc, from
the terminal block.) Doing so may cause electric shock or fire.)
(1) Take sufficient protective measures when installing the outdoor gas valve
Union nut
unit.
(2) Make sure the support can withstand at least four times the unit Fig.E
weight. (3) Pretightening the union nut with hand.
(3) The outdoor unit should be installed at least 3cm above the (4) Tighten the union nut with torque wrench .
floor in order to install drain joint.(As show in Fig.A)
Refer to the following table for wrench moment of force:
(4) For the unit with cooling capacity of 2300W~5000W, 6
Hex nut diameter(mm) Tightening torque(N.m)
expansion screws are needed; for the unit with cooling capacity of
Φ6 15~20
6000W~8000W, 8 expansion screws are needed; for the unit with
Φ9.52 30~40
cooling capacity of 10000W~16000W, 10 expansion screws are
Φ12 45~55
needed.
Φ16 60~65
Φ19 70~75
5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire
and signal control wire (only for cooling and heating unit) to the
Drain vent Chassis wiring terminal according to the color; fix them with screws.(As
Drain hose
Outdoor drain joint show in Fig.F)
At least 3cm above the floor
N(1) 2 3
2. Install Drain Joint(Only for cooling and heating unit) N(1) 2 3 L N
N L yellow- blue black brown brown blue yellow-
(1) Connect the outdoor drain joint into the hole on the chassis. green (black)
green
L N
(2) Connect the drain hose into the drain vent.(As show in Fig.B)
blue black brown yellow- blue brown yellow-
green (black) green
8.4 Vacuum Pumping and Leak Detection 8.5 Check after Installation and Test
1. Use Vacuum Pump Operation
(1) Remove the valve caps on the liquid valve and gas valve and 1. Check after Installation
the nut of refrigerant charging vent. Check according to the following requirement after finishing
(2) Connect the charging hose of piezometer to the refrigerant installation.
charging vent of gas valve and then connect the other charging
NO. Items to be checked Possible malfunction
hose to the vacuum pump.
Has the unit been The unit may drop, shake or
(3) Open the piezometer completely and operate for 10-15min to 1
installed firmly? emit noise.
check if the pressure of piezometer remains in -0.1MPa. Have you done the It may cause insufficient cooling
(4) Close the vacuum pump and maintain this status for 1-2min 2
refrigerant leakage test? (heating) capacity.
to check if the pressure of piezometer remains in -0.1MPa. If the Is heat insulation of It may cause condensation and
3
pressure decreases, there may be leakage. pipeline sufficient? water dripping.
(5) Remove the piezometer, open the valve core of liquid valve It may cause condensation and
4 Is water drained well?
and gas valve completely with inner hexagon spanner. water dripping.
(6) Tighten the screw caps of valves and refrigerant charging Is the voltage of power
vent. supply according to the It may cause malfunction or
5
voltage marked on the damage the parts.
Liquid valve Piezometer Lo Hi
nameplate?
Is electric wiring and
Gas valve It may cause malfunction or
6 pipeline installed
Valve cap damage the parts.
Refrigerant charging correctly?
vent Is the unit grounded
7 It may cause electric leakage.
Nut of refrigerant securely?
Charging vent Does the power cord It may cause malfunction or
8
follow the specification? damage the parts.
Vacuum pump
Is there any obstruction It may cause insufficient cooling
9
Inner hexagon in air inlet and air outlet? (heating) capacity.
spanner The dust and
sundries caused It may cause malfunction or
10
during installation are damaging the parts.
Close
removed?
Open
The gas valve and liquid
It may cause insufficient cooling
11 valve of connection pipe
(heating) capacity.
are open completely?
2. Leakage Detection Is the inlet and outlet It may cause insufficient cooling
(1) With leakage detector: 12 of piping hole been (heating) capacity or waster
Check if there is leakage with leakage detector. covered? eletricity.
(2) With soap water:
2. Test Operation
If leakage detector is not available, please use soap water for
(1) Preparation of test operation
leakage detection. Apply soap water at the suspected position
● The client approves the air conditioner installation.
and keep the soap water for more than 3min. If there are air
● Specify the important notes for air conditioner to the client.
bubbles coming out of this position, theres a leakage.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air
conditioner cant start cooling.
9. Maintenance
9.1 Error Code List
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
During cooling and drying Possible reasons:
High operation, except indoor 1. Refrigerant was superabundant;
pressure fan operates, all loads stop 2. Poor heat exchange (including
1 E1
protection of operation. filth blockage of heat exchanger
system During heating operation, the and bad radiating environment );
complete unit stops. Ambient temperature is too high.
1.Low-pressure protection
Low pressure The Dual-8 Code Display will 2.Low-pressure protection of
2 protection of E3 show E3 until the low pressure system
system switch stop operation. 3.Low-pressure protection of
compressor
High During cooling and drying
discharge operation, compressor and Please refer to the malfunction
3 temperature E4 outdoor fan stop while indoor analysis (discharge protection,
protection of fan operates. During heating overload).
compressor operation, all loads stop.
During cooling and drying
1. Supply voltage is unstable;
operation, compressor and
Overcurrent 2. Supply voltage is too low and
4 E5 outdoor fan stop while indoor
protection load is too high;
fan operates. During heating
3. Evaporator is dirty.
operation, all loads stop.
During cooling operation,
Communi- compressor stops while
Refer to the corresponding
5 cation E6 indoor fan motor operates.
malfunction analysis.
Malfunction During heating operation, the
complete unit stops.
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
When the outdoor unit receive
signal of Gathering refrigerant
Gathering
10 Fo ,the system will be forced to Nominal cooling mode
refrigerant
run under cooling mode for
gathering refrigerant
1. Loosening or bad contact of
indoor ambient temp. sensor and
Indoor During cooling and drying
mainboard terminal.
ambient operation, indoor unit operates
2. Components in mainboard fell
temperature while other loads will stop;
11 F1 down leads short circuit.
sensor is during heating operation,
3. Indoor ambient temp. sensor
open/short the complete unit will stop
damaged.(check with sensor
circuited operation.
resistance value chart)
4. Mainboard damaged.
1. Loosening or bad contact of
Indoor
AC stops operation once evaporator temp. sensor and
Indoor
reaches the setting mainboard terminal.
evaporator 2. Components on the mainboard
temperature. Cooling, drying:
temperature fall
12 F2 internal fan motor stops
sensor is down leads short circuit.
operation while other loads 3. Indoor evaporator temp. sensor
open/short
stop operation; heating: AC damaged.(check temp. sensor
circuited
stop operation value
chart for testing)
4. Mainboard damaged.
Outdoor During cooling and drying
Outdoor temperature sensor
ambient operating, compressor stops
hasnt been connected well or
temperature while indoor fan operates;
13 F3 is damaged. Please check it by
sensor is During heating operation,
referring to the resistance table for
open/short the complete unit will stop
temperature sensor)
circuited operation
Outdoor During cooling and drying
Outdoor temperature sensor
condenser operation, compressor stops
hasnt been connected well or
temperature while indoor fan will operate;
14 F4 is damaged. Please check it by
sensor is During heating operation,
referring to the resistance table for
open/short the complete unit will stop
temperature sensor)
circuited operation.
During cooling and drying 1.Outdoor temperature sensor
Outdoor operation, compressor will sop hasnt been connected well or is
discharge after operating for about 3 damaged. Please check it by
temperature mins, referring to the resistance table for
15 F5
sensor is while indoor fan will operate; temperature sensor)
open/short During heating operation, the 2.The head of temperature sensor
circuited complete unit will stop after hasnt been inserted into the copper
operating for about 3 mins. tube
Limit/
All loads operate normally,
decrease Refer to the malfunction analysis
while
16 frequency F6 (overload, high temperature
operation frequency for
due to resistant)
compressor is decreased
overload
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
Decrease Overload or temperature is too
All loads operate normally,
frequency high;
while
18 due to F9 Refrigerant is insufficient;
operation frequency for
high air Malfunction of electric expansion
compressor is decreased
discharge valve (EKV)
Limit/
decrease All loads operate normally,
Poor air-return in indoor unit or fan
19 frequency FH while operation frequency for
speed is too low
due to compressor is decreased
antifreezing
Compressor
Min Showing during min. cooling or
22 P0
frequence in min. heating test
test state
Compressor
rated Showing during nominal cooling or
23 P1
frequence in nominal heating test
test state
Compressor
maximum Showing during max. cooling or
24 P2
frequence in max. heating test
test state
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
Compressor
intermediate Showing during middle cooling or
26 P3
frequence in middle heating test
test state
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
During cooling and drying Refer to the malfunction
Desynchro- operation, compressor will stop analysis (IPM protection, loss
while indoor fan will operate;
33 nizing of H7 of synchronism protection and
During heating operation, the
compressor complete unit will stop overcurrent protection of phase
operation. current for compressor.
During cooling and drying
operation, compressor will stop
PFC while indoor fan will operate; Replace outdoor control panel AP1
34 HC
protection During heating operation, the or Reactor
complete unit will stop
operation.
Indoor unit
and outdoor compressor and Outdoor fan Indoor unit and outdoor unit doesnt
37 LP
unit doesnt motor cant work match
match
During cooling and drying
operation, compressor will stop
Failure start- while indoor fan will operate;
38 LC Refer to the malfunction analysis
up During heating operation, the
complete unit will stop
operation.
Anti-freezing
Not the error code. It’s the
39 protection for E2
status code for the operation.
evaporator
1. Outdoor ambient temperature
exceeds the operation range of unit
(eg: less than-20oC or more than
Cool: compressor and outdoor
60oC for cooling; more than 30oC
Undefined fan stops operation, while
for heating);
40 outdoor unit oE indoor fan operates; Heat:
2. Failure startup of compressor?
error compressor, outdoor fan and
3. Are wires of compressor not
indoor fan stop operation.
connected tightly?
4. Is compressor damaged?
5. Is main board damaged?
Malfunction of During cooling and drying
phase current operation, compressor will stop
41 detection U1 while indoor fan will operate; Replace outdoor control panel AP1
circuit for During heating operation, the
compressor complete unit will stop
During cooling and drying
Malfunction of
operation, compressor will stop
voltage
42 U3 while indoor fan will operate; Supply voltage is unstable
dropping for
During heating operation, the
DC bus-bar
complete unit will stop
Display Method of
Indoor Unit
Malfunction
No. Dual-8 A/C status Possible Causes
Name
Code
Display
Cold air
Not the error code. It’s the
45 prevention E9
status code for the operation.
protection
Malfunction
1.Power supply is abnormal;
of zero-cross
48 U8 The complete unit stops 2.Detection circuit of indoor control
detection
mainboard is abnormal.
circuit
1.Main board of indoor unit is
damaged;
Malfunction Loads operate normally, 2.Detection board is damaged;
49 of detecting JF while the unit can’t be 3.The connection between
plate(WIFI ) normally controlled by APP. indoor unit and detection
board is not good;
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
No Is malfunction Yes
eliminated
Yes
No Is malfunction Yes
eliminated
No Is malfunction Yes
eliminated
No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No
No Is malfunction Yes
eliminated
End
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
Start
Yes
End
Start
Yes
Is malfunction
eliminated
The end
Outdoor unit
1. Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
No
Yes
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
Yes
End
(2) IPM protection, phase current overcurrent (the control board as below indicates the control board
of outdoor unit) H5/P5
Mainly detect:
(1) Compressor COMP terminal (2) voltage of power supply (3) compressor
(4) Refrigerant-charging volume (5) air outlet and air inlet of outdoor/indoor unit
Troubleshooting:
1. Whether the heat exchangers of indoor unit and outdoor unit are Measure the resistance
dirty? Whether the radiation is affected because the unit is between three terminals (UVW)
covered by the objects? of compressor and the copper pipe
2. When indoor fan and outdoor unit are operate normally? with resistance measuring meter
3. Whether the system pressure is too high?
4. Whether the pressure is because there's too much refrigerant?
Whether the
resistance value is more than
500ohm?
Whether there's Correct it one by one
abnormal phenomenons according to the Service
described as above? Manual, and then turn on
the unit. Replace the
compressor
Replace control
board
End
3. High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor
unit)
Mainly detect:
●Is outdoor ambient temperature in normal range?
●Are the outdoor and indoor fans operating normally?
●Is the heat dissipation environment inside and outside the unit good?
Fault diagnosis process:
No
No
Yes
Replace the
outdoor fan
End
Yes
Yes
Yes
No
No
Replace the
compressor
Yes
End
5. Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:
No
Is stop time of the No Check if the fan terminal Replace the fan
Is the outdoor fan working
compressor longer than OFAN is connected correctly capacitor C1
normally?
3 minutes?
Yes
Yes Replace the
outdoor fan
Is the outdoor unit blocked Yes
Remove foreign objects
by foreign objects?
Are the wires for the compressor connected
correctly? Is connection sequence right? No
Is the connection made in clockwise
direction?
Replace the
No control panel AP1
Connect the Yes
wires correctly
Yes
If the fault is eliminated?
No
No Replace the
compressor
Replace the
compressor
End
End
6. Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
Yes
No
Replace the
control panel
AP1
No
End
Start
No
If the fault is eliminated?
No
Replace the main board
of the indoor unit
Yes
Yes Yes
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesnt rotate motor to have the fan run normally eliminated
No No
Yes No
Is there blockage inside the system? Yes Flush the heat exchangers with high
(Filth blockage, ice plug, greasy Is malfunction Yes
blockage, the cut off valve hasnt been pressure nitrogen eliminated
opened completely)
No No
No
End
15 16
17
14
18
33 13 19
20
12
21
22
11 23
24
10
9
8
7
6
5
4
3
2
1
25
26
27
28
Part Code
Description
NO. GEH12AA-K6DNA1A/I GEH09AA-K6DNA1F/I GEH18AA-K6DNA1F/I Qty
Product Code CV010N02900 CV010N02700 CV010N02800
1 Front Panel Assy 20012756 20012756 20012756 1
2 Filter Sub-Assy 11122139 11122139 11122139 1
3 Front Case Assy 20012601 20012601 20012601 1
4 Evaporator Assy 01100100160 01100100160 01100100164 1
5 Cold Plasma Generator 1114001604 1114001604 1114001604 1
6 Rear Case Assy 000001060071 000001000051 000001060071 1
7 Centrifugal Fan 10312005 10312005 10312005 1
8 Fan Motor 1570410001201 1570410001201 1570410001201 1
9 SteppingMotor 1521210101 1521210101 1521210101 1
10 Crank 73012005 73012005 73012005 1
11 Swing Assy 10102042 10102042 000211060003 1
12 Terminal Board 422000000022 422000000022 422000000022 1
13 Switch Board 30112007 30112007 30112007 1
14 Display Board 30568131 30568131 30568131 1
15 Fuse 46010055 46010055 46010055 1
16 Radiator / / / /
17 Signal Wire 4003004202 4003004202 4003004202 1
18 Jumper 4202300112 4202300111 4202300114 1
19 Main Board 300002000631 300002000631 300002000631 1
20 Electric Box 20112116 20112116 20112116 1
21 Electric Box Assy 100002002951 100002002848 100002002386 1
22 Air Louver (upper) 10512143 10512143 10512143 2
23 Swing Lever 10582096 10582096 10582096 1
24 Shaft of Guide Louver 10542020 10542020 10542020 1
25 Water Tray Assy 20182141 20182141 20182141 1
26 Air Louver (lower) 10512144 10512144 10512144 1
27 Axis (lower step motor) 10542034 10542034 10542034 1
28 SteppingMotor 1521210805 1521210805 1521210805 1
29 Connecting Cable 4002052317 4002052317 4002052317 0
30 Temperature Sensor 3900004508 3900004508 3900004508 1
31 Remote Controller 305001000111 305001000111 305001000111 1
32 Temperature Sensor 390000591 390000591 3900004508 1
33 Detecting Plate 30110154 30110154 30110154 1
GEH12AA-K6DNA1A/O
1 2 4 5 6 7
3
21 22 23 24 25
28
20
8
19 9
10
18
11
17
16
12
13
14
15
26
27
The component picture is only for reference; please refer to the actual product.
Part Code
Description
NO. GEH12AA-K6DNA1A/O Qty
Product Code CV010W02900
1 Left Side Plate 01303200P 1
2 Fan Motor 1501308511 1
3 Motor Support 01703136 1
4 Condenser Assy 011002060521 1
5 Top Cover Sub-Assy 000051060038 1
6 Rear Grill 01475014 1
7 Clapboard Sub-Assy 01233180 1
8 Compressor and Fittings 009001060066 1
9 Compressor Gasket 009012000027 3
10 4-Way Valve Assy 030152060255 1
11 Big Handle 2623343106 1
12 Valve Cover 22243006 1
13 Cut off Valve 071302391 1
14 Cut off Valve 07130239 1
15 Valve Support 0171314201P 1
16 Front Grill 22413047 1
17 Cabinet 01433033P 1
18 Axial Flow Fan 10333011 1
19 Chassis Sub-assy 017000060080P 1
20 Electric Box Assy 100002064438 1
21 Electric Box 20113034 1
22 Main Board 300027060573 1
23 Reactor 43130184 1
24 Wire Clamp 71010103 1
25 Terminal Board 422000060016 1
26 Electrical Heater / /
27 Electrical Heater (Chassis) 7651000414 1
28 Electric Expansion Valve Sub-Assy 030026060275 1
GEH09AA-K6DNA1F/O
Part Code
Description
NO. GEH09AA-K6DNA1F/O Qty
Product Code CV010W02700
1 Electric Box Assy 100002064342 1
2 Electric Box Sub-Assy 017007060831 1
3 Main Board 300027060561 1
4 Reactor 43130184 1
5 Terminal Board 422000060016 1
6 Wire Clamp 71010103 1
7 Front Grill 22413049 1
8 Front Panel 01533034P 1
9 Axial Flow Fan 10333004 1
10 Chassis Sub-assy 017000060298P 1
11 Fan Motor 1501308511 1
12 Small Handle 26233100 1
13 Top Cover Sub-Assy 000051060006 1
14 Motor Support 01703104 1
15 Condenser Assy 011002060497 1
16 Rear Grill 01473009 1
17 Electronic Expansion Valve 07133821 1
18 Cut off Valve 071302391 1
19 Big Handle 262334332 1
20 Valve 07100003 1
21 Valve Support 0171314201P 1
22 Right Side Plate Sub-Assy 00013006002001 1
23 4-Way Valve Assy 030152060251 1
24 Clapboard Sub-Assy 0123338502 1
25 Magnet Coil 4300040050 1
26 Compressor and Fittings 009001060050 1
27 Drainage Connecter 06123401 1
28 Electrical Heater(Compressor) 7651000414 1
GEH18AA-K6DNA1F/O
Part Code
Description
NO. GEH18AA-K6DNA1F/O Qty
Product Code CV010W02800
1 Front Grill 22413045 1
2 Front Panel 01535013P 1
3 Drainage Connecter 06123401 1
4 Chassis Sub-assy 02803270P 1
5 Drainage hole Cap 06813401 1
6 Compressor and fittings 00103919G 1
7 Magnet Coil 4300040087 1
8 4-Way Valve Assy 030152060322 1
9 Cut off Valve Assy 1/2 07133774 1
10 Cut off Valve Sub-Assy 07133058 1
11 Valve support assy 01715010P 1
12 Right Side Plate 0130509402P 1
13 Valve cover 22245002 1
14 Handle 26233053 1
15 Wiring Clamp 26115004 1
16 Electronic Expansion Valve assy 07133774 1
17 Electric Expand Valve Fitting 030174000058 1
18 Rear Grill 01473043 1
19 Condenser Assy 0116348702 1
20 Reactor / /
21 Clapboard Assy 01233153 1
22 Coping 012049000007P 1
23 Supporting Board(Condenser) 01795010 1
24 Motor Support Sub-Assy 01705036 1
25 Fan Motor 1501506402 1
26 Axial Flow Fan 10335008 1
27 Left Side Plate 01305093P 1
28 left handle 2623525404 1
29 Electric Box Assy 100002064320 1
30 Wire Clamp 71010003 1
31 Terminal Board 422000060009 1
32 Electric Box 20113027 1
33 Radiator 49013060 1
34 Main Board 300027060548 1
35 Insulated Board (Cover of Electric Box) 20113003 1
36 Temperature Sensor 3900030901 1
Steps Procedure
1. Remove panel
water tray
screws
fixer of piping
8. Remove evaporator
centrifugal blade
Steps Procedure
Big handle
Screws
Top panel
Remove the screws fixing top panel and
then remove the top panel.
Screw
Front grille
Steps Procedure
Screws
Screws
Panel
Screws
Nut
Steps Procedure
Screws 2
Screws 1
Screws 2
Steps Procedure
9. Remove motor
Motor
Screws
Screws
Steps Procedure
Liquid valve
Screws
Gas valve
Screws
Valve support
Screws
Steps Procedure
Note:
Protect the ports of discharge pipe and
suction pipe to avoid foreign objects to
enter it.
Compressor
Foot nuts
Condenser
Screw
GEH12AA-K6DNA1A/O
Step Procedure
4. Remove grille
grille
front panel
Step Procedure
8. Remove motor and motor support
motor support
motor and disconnect the leading wire
insert of the motor. Then remove the
motor.
motor
motor support and lift the motor support to
remove it.
isolation sheet
sheet and then remove the isolation
sheet.
gas valve
Step Procedure
compressor
nuts
GEH18AA-K6DNA1F/O
Steps Procedure
Screw
Valve cover
Screw
Screws
Steps Procedure
Screws
Rear grill
Screws 2 Screws 1
Screws 2
Right
side plate
Screws 2
Steps Procedure
Screws
Motor
Motor
support
Screws
Steps Procedure
Note:
When pulling out the wiring terminal, pay
attention to loose the clasp and don’t pull
it so hard.
Soundproof
sponge
Note:
When unsoldering the spot weld, wrap Screws
the 4-way valve with wet cloth completely
to avoid damaging the valve due to high
temperature.
Screws
Steps Procedure
Screws
Liquid valve
Screws
Screws
Gas valve
Valve support Screws
Note:
Protect the ports of discharge pipe and
suction pipe to avoid foreign objects to Compressor
enter it.
Screws
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Note: The additional refrigerant charging amount in Sheet 2 is recommendedvalue, not compulsory.
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
For product improvement, specifications and appearance in this manual are subject to change without prior notice.