Understanding Insulation Resistance Testing
Understanding Insulation Resistance Testing
Resistance Testing
Why have an insulation testing program?
A regular program of testing insulation resistance is strongly
recommended to prevent electrical shocks, assure safety
of personnel and to reduce or eliminate down time. It helps
to detect deterioration of insulation in order to schedule repair
work such as: vacuum cleaning, steam cleaning, drying and
rewinding. It is also helpful when evaluating the quality of the
repairs before the equipment is put back into operation.
30
25
20
15 Interpretation of Results
Proper interpretation of spot reading tests requires access
10
9
8 to records of results from previous spot reading tests. For
conclusive results, only use results from tests performed at
7
6
5
4
CONDUCTION
the same test voltage for the same amount of time, and under
3
OR LEAKAGE
CURRENT ABSORPTION
similar temperature and humidity conditions. These readings
2.5
2
CURRENT
are used to plot a curve of the history of insulation resistance.
1.5 A curve showing a downward trend usually indicates a loss of
1 insulation resistance due to unfavorable conditions such as:
.1 .15 .2 .25 .3 .4 .5 .6 .7 .8 .9 1.0 1.5 2 2.5 3 4 5 6 7 8 9 10
SECONDS
humidity, dust accumulation, etc. A very sharp drop indicates
an insulation failure. See Figure 1.
Understanding Insulation Resistance Testing (pdf) 02/06 Rev. 02
➞
• less than 1 = failed
• 1.0 to 1.25 = OK
100
➞A • 1.4 to 1.6 = excellent
Note: This is not a commonly used test
Interpretation of Results
Time-Resistance Testing Method Compare the readings taken at different voltage levels, look-
This method is fairly independent of temperature and often ing for any excessive reduction in insulation resistance values
can give you conclusive information without records of past at the higher voltage levels. Insulation that is thoroughly dry,
tests. It is based on the absorption effect of good insulation clean, and without physical damage should provide roughly
compared to that of moist or contaminated insulation. the same resistance values despite changes in test voltage
Simply take successive readings at specific times and note levels. If resistance values decrease substantially when tested
the differences in readings (see curves, Figure 2). Tests by at higher voltage levels, this should serve as a warning that
this method are sometimes referred to as absorption tests. insulation quality may be deteriorating due to dirt, moisture,
cracking, aging, etc.
Good insulation shows a continual increase in resistance
(see curve D) over a period of time (in the order of 5 to Polarization Index (PI) = 10-minute reading
10 minutes). This is caused by the absorption; good 1-minute reading
insulation shows this charge effect over a time period much
The IEEE Std 43-2000 lists the following minimum values for
longer that the time required to charge the capacitance of the polarization index for AC and DC rotating machines:
the insulation.
Class A: 1.5 Class B: 2.0 Class C: 2.0
If the insulation contains moisture or contaminants, the
absorption effect is masked by a high leakage current 1000 D➞
which stays at a fairly constant value – keeping the resist-
ance reading low (R = E/I) (see curve E).
Reading in Megohms
1 2 3 4 5 6 7 8 9 10
A further advantage of this two reading test is that it gives Time in Minutes
you a clearer picture, even when a “spot reading” says the Figure 2
insulation looks ok. Absorption curve of test conducted on 350 HP Motor: Curve D indicates a
good insulation with an excellent polarization index of 5. Curve E indicates a
Time-resistance tests on large rotating electrical machinery potential problem. The polarization index is only 140/95, or 1.47.
– especially with high operating voltage – require high (2) IEEE Std. 43-2000, “Recommended Practice for Testing Insulation
insulation resistance ranges and a very constant test voltage. Resistance of Rotating Machinery.” Available from the Institute of Electrical and
Electronics Engineers, Inc., 345 E. 47th St., New York, NY 10017.
B B
1 I1
Ay Ay
Rz Rz
Advantages of DC Testing
• Lighter size and weight of test equipment
• Non-destructive
• Historical data can be compiled
What test voltage should I use? a. High voltage winding to low voltage winding
There are two schools of thought regarding the voltage to test and ground
insulation at. The first applies to new equipment or cable and
b. High voltage winding to ground with low voltage
can use AC or DC test voltages.
winding to guard
When AC voltage is used, the rule of thumb is 2 x nameplate c. High voltage winding to low voltage winding
voltage + 1000. When DC voltage is used (most common on
megohmmeters manufactured today) the rule of thumb is d. Low voltage winding to ground and high voltage
simply 2 x nameplate voltage except when higher voltages winding to guard
are used. See chart below for suggested values. e. High voltage winding to low voltage winding
Equipment/Cable Rating DC Test Voltage
24 to 50V 50 to 100VDC
50 to 100V 100 to 250VDC
100 to 240V 250 to 500VDC
440 to 550V 500 to 1000VDC
2400V 1000 to 2500VDC
4100V 1000 to 5000VDC
X3 H1
X2 X3 H3
X1 H2 X2 H2
a. High voltage winding
X1 H1 to low voltage winding
and ground
X0
a. High voltage winding
to low voltage winding
and ground
X3 H1
X2
X3 H3
X1 H2
X2 H2 b. High voltage winding
to ground with low
X1 H1
voltage winding to
X0
guard
b. Low voltage winding
to high voltage winding
and ground
X3 H1
X2 X3 H3
X1 H2 X2 H2
X3 H1
X2 X3 H3
X3 H1
X2 X3 H3
X1 H2 X2 H2
e. High voltage winding
X1 H1 to low voltage winding
X0
Multi-Conductor
a. Single conductor Stator
T1 T2 T3 N
Insulation Conductor
ƒ1 ƒ2
Field
Ground Sheath – single conductor
a. Single conductor
Three-conductor
cable
Three-conductor
cable
Repair and Calibration Service – for information on repair & calibration, obtaining a user manual:
[email protected]
Technical and Product Application Support – for technical and application support:
[email protected]
South America, Central America, Mexico, Caribbean, Australia & New Zealand: