CW85
CW85
CHDesign - v2.2
GENERAL
Air conditioners specifically designed for IT applications: maximisation of sensible capacity, efficiency,
reliability, availability and redundancy. They additionally provide for utmost flexibility in terms of
direction of the air delivery and return lines for better adaptation to the different site
layouts.
CONFIGURATIONS
STRUCTURE BTD
For enhanced thermal and acoustic insulation the units consist of a load-bearing frame made of a 22 mm
thick sandwich sheet metal, with internal insulating glass wool material, 30 kg/m³ density. The fire
reaction class of the panelling is A1 (in accordance with EN13501). Air tightness is achieved with
adhesive sealing strips placed allaround the edges of the panels. The internal sheet metal parts are hot
galvanised and have variable thickness (from 2.5 mm for the base to 1 mm for removable panels),
whereas visible parts are painted with an oven-baked epoxy polyester powder coating RAL7016 and have
a textured surface finish. The frame is secured with structural rivets. The front and rear panels are fixed
with ¼ turn fasteners or they are screwed to the top part, respectively, and they are supplied with tabs
for installation in dedicated slots on the base. The front panel opposite the electric switch is hingedand
supplied with a handle for opening. Access to all the main components of the unit is gained from th
front, so no clearance spaces must be left at the sides and back of the unit for both routine and non-
routine maintenance. All the materials making up the unit are CFC-free. All electrical, cooling and
hydraulic connections are normally made from the bottom of the unit. Solutions for lateral connections
are also available upon request.
pag. 2/13
11/09/2023
CHDesign - v2.2
FANS
Units are equipped with 1, 2, 3 and/or 4 radial fans with backward-curved blades, without scroll. Fans
are balanced, as required by standard ISO DIN 1940. The average air capacity value is 82 l/s per kW of
sensible cooling capacity. Fans featuring brushless, electronically commutated (EC) motors offer a
number of advantages:
• greater efficiency at full load if compared with the corresponding AC model;
• Cosfi value close to 1;
• built-in soft starter;
• user-friendly adjustment - the 0-10V control signal enables monitoring the motor speed electronically
with continuous regulation via the microprocessor onboard the unit so as to implement various control
strategies (constant flow, constant pressure, based on thermal load, etc.).
• The motors are provided with integrated electronic protection against overtemperature, overcurrent,
over or under-voltage with absence of one or more phases.
The strategic advantage of EC fans is the cubic ratio between speed and absorption. In other words, the
consumption of a fan running at 70% is 50%, it is 18% when running at 50%, etc. This brings about a
potential saving that is exponential to partial loads. Hence, the need exists to modulate the fan efficiently
and continuously using the correct algorithm required by the application. Air flow is constantly monitored
by a differential pressure switch, which signals an alarm condition when there is no flow or the flow is
poor.
AIR FILTERS
The filters are pleated and in a rigid galvanized steel frame, filtration class ISO Coarse 75% (ISO 16890-
3; G4 - EN779), and designed to minimize head losses and to have a high degree of filtration. The
thickness of the filters can be 50 or 100 mm depending on the sizes or the setups. The filters are always
removed from the front of the unit. Higher efficiency and low head loss filters ISO ePM10 (M5), ISO
ePM10 75% (M6), ISO ePM1 50% (F7) may be supplied upon request (refer to the corresponding options
for further details). If the specific option (CF) is ordered, the condition of the filters is constantly
monitored by a differential pressure switch that signals when they are excessively fouled.
HYDRAULIC CIRCUIT (chilled water unit CW/ DW), (dual fluid units EDA/EDW - DC or FC with
reference to the chilled water circuit)
CHILLED WATER VALVE (chilled water unitCW/DW), (dual fluid units EDA/EDW - DC or FC
with reference to the chilled water circuit)
Chilled water valves are brass body, ball valves with equal percentage flow on the straight line and linear
pag. 3/13
11/09/2023
CHDesign - v2.2
flow on the bypass line, including threaded female connectors. These valves are supplied with a
modulating, microprocessor-controlled servo onboard the machine with 0-10V signal.
WATER COILS (chilled water unit CW/DW), (dual fluid units EDA/EDW - DC or FC with
reference to the chilled water circuit)
Coils are finned pack type and they consist of copper tubes and aluminium fins with corrugated profile
and hydrophilic surface treatment. All chilled water coils are supplied with an air exhaust valve and a
threaded drain plug, and they are guaranteed for pressures up to 16 bar. A stainless steel condensation
collection basin is installed at the base of the coil, complete with fitting for drain and siphon.
VERSIONS
The version in all models indicates the operating mode required to preserve the thermo-hygrometric
conditions in the relevant environment. HH versions are fitted with cooling, heating and
humidificationdevices. In addition to the temperature probe fitted on he air return line, these units are
provided with a humidity probe that is used to control the humidity parameter as well. More specifically,
when the relative humidity drops below the desired value, the humidifier outputs vapour into the
environment. The HH ersion may be supplied without heaters upon request. Versions CO/CH (where
fitted with an additional humidity probe) and HH are also used for de-humidification of the environment
whenever the humidity value exceeds the desired threshold. Please keep in ind that the unitshave
limited dehumidification properties for the intended type of application. For more efficient de-
humidification, the units can modulate their components to increase their latent heat removal capabilities
via software where these operations re programmed. When de-humidification is required, the units can
reduce the fan speed and increase their de-humidification capability.
The heating elements are made of AISI304 steel and have low surface temperature, spiral AISI304 steel
fins featuring a safety bimetal thermostat. The heating elementsare grouped in banks that are made of
galvanised sheet metal with a locked electric box or they are installed in circle configuration around the
fan (“XS” sizes). The electric heaters are controlled according to power steps (either one or two
depending on the unit size).
• Frames SXS,XS,S: 1 power step.
• All other frames: 2 power steps.
When the necessary option is fitted, the unit can be equipped with an immersed electrode humidifier to
wet the air in cases where the air humidity is below the setpoint stored. The operating principle of the
humidifier is as follows. A container featuring lectrodes is filled with water until the electrodes are slightly
covered, as water serves as the conducting medium between the electrodes. The Joule effect causes the
running current to heat the water which evaporates as soon as it reaches the boilingpoint. The utput
vapour is transferred to the environment. The solution with immersed electrodes is fully safe from a
health standpoint and it is designed for proportional adjustment of vapour generation.
pag. 4/13
11/09/2023
CHDesign - v2.2
The electrical panel located in a dedicated compartment and separately from the air flow is made in
accordance with IEC standards. It includes:
• a main power switch;
• automatic switches for the power circuit and the auxiliary circuit;
• contactors for power loads;
• phase sequence relays (on direct expansion, three-phase units);
• a transformer to separate the power lines of the power circuits and the control circuits;
• a microprocessor electronic controller;
• an auxiliary terminal board for the electrical connection of loads and external signals/ok signals.
The electrical control panel is always accessible from the front part of the unit. The main power switch is
supplied with a door lock handle that prevents opening of the electrical control panel door if the power
supply is enabled. The electrical control panel is structured in such way that it meets protection level
IP42. The microprocessor controller inside the electrical control panel is provided with the following
functions/features:
• display showing the return air temperature;
• humidity (versions HH or featuring the relevant option);
• display showing the temperature in the delivery line;
• display showing the fan speed;
• two-level alarm message(s) (serious alarm and minor alarm);
• log recording of the last 100 alarms;
• operating hour meter;
• display showing the status of the controlled devices;
• display showing the status of inputs and outputs of the microprocessor.
Power supply [V/ph/Hz]: 230/1~/50 ±5% for sizes 6.1, 8.1; 400/3~/50 ±5% for the other models. The
following potential-free contacts are supplied in the terminal board as standard:
• remote ON/OFF;
• serious alarm;
• minor alarm (message).
The Blue Think Data software fully incorporates the knowhow and expertise of Swegon-Blue Box in Data
Cooling applications. Blue Think Data is developed and constantly updated in-house through a continual
improvement process. Blue Think Data was conceived for the best functionality of the various units and
systems installed in multiple machines, and at the same time it guarantees the highest safety level for
both the components and application. The graphic interface was designed for immediate feedback on the
operating condition as well as for easy and efficient access to the various functionalities. Blue Think Data
incorporates the following key functions:
• control of return temperature;
• Outlet temperature water control(only for motocondenser with inverter);
• delivery temperature restriction;
• control of either relative or absolute humidity in the return line (only applies to units with the
necessary sensor and/or humidifier);
• multiple solutions for ventilation control (with modulating fans and their options);
• integrated condensation control (where the relevant options have been selected);
pag. 5/13
11/09/2023
CHDesign - v2.2
• advanced alarm management: recording of 100 alarms in the memory, division of alarms into two
categories (minor and serious alarms), smart automatic reset;
• auto restart after a voltage failure;
• function for absorption limitation, which is implemented either via the setting of a limit absorption
value or via an external digital request signal (only if the relevant options have been selected);
• integrated clock for timer-controlled switch-on/off and setpoint variation according to time bands;
• password-protected levels of access to parameter setup pages, protection against undesired tampering
or tampering by unauthorised/non qualified staff;
• multi language interface, which the operator can select in real time;
• management of multiple locally networked units (up to 32) for integrated and optimised operation (if
the corresponding option has been selected).
Specific functionalities (e.g. Local Network, Air free cooling, Ventilation) and set-up solutions are
illustrated in more in-depth details in the relevant sections.
HARDWARE
input/output boards including a 32-bit, 100 MHz microprocessor, with a 128-Mbyte non-volatile (FLASH)
memory, 90Mbyte of which are available as file storage, and a 16 Mbyte data memory (RAM). Three
different board sizes are used to optimise the number of nputs and outputs with respect to the
application; a humidifier-specific I/O board (which is therefore only fitted if this option is selected)
communicating with the master board in serial mode;a driver for the electronic expansion valve (where
this option is elected) to pilot the electronic valve and integrate its data and functions in the machine.
Communicationwith the master board is in serial mode. The graphic terminal is a 4.3” touch screen
panel. The electronic technology featured and the 65.000 colour display help manage high quality
images and advanced functions. The touch screen panel is also designed for easier man-machine
interaction as it makes screen browsing much more user-friendly. The display is also supplied with a LED
bar featuring different message- ssociated colours. The machine status can be viewed at any time
without having to go close to the display. Another innovative feature is the front position of the USB
outlet for easier access without the use of specific tools.
TESTING
All units are leak tested for possible leaks. Units are filled with a mix of nitrogen and helium (30 bar for
direct expansion systems). The circuit is pressurised and left in such condition for a predefined period of
time (which varies according to the mix used), after which the pressure level is tested. The entire circuit
is also checked for micro leaks with a sniffer. The units are then subjected to a functional test which
includes the following, among others:
• inspection that the correct options are fitted and the necessary documentation is available;
• software uploading in the unit controller and parameter setup, based on the unit and the featured
options;
• inspection that the probes can read correctly and probe calibration, where necessary;
• functional dry run testing.
The units are finally delivered as follows:
• chilled water or direct expansion unit versions without compressor - with a nitrogen-filled
hydraulic/refrigerant circuit.
All Datatech units are anchored to a pallet at the time of shipment, with corners protected by
polyethylene angular pieces and wrapped in stretch film.
pag. 6/13
11/09/2023
CHDesign - v2.2
Selected accessories:
VEC - EC fans
-
pag. 7/13
11/09/2023
CHDesign - v2.2
.............................................................................................................................................................
COOLING
Sound data
Calculated sound power dB(A) 77
Sound pressure(C0) [2.0 m] dB(A) 56
pag. 8/13
11/09/2023
CHDesign - v2.2
Air filter
Extract filter
Number 3
Class Coarse
(A0) Technical data shown are not binding. The Company shall have the right to introduce at any time whatever modifications necessary to the improvement of the product.
(A2) According to standard: Gross
(C0) Noise pressure is calculated according to the following sound propagation method: Hemispherical ISO EN 3744 source
pag. 9/13