0% found this document useful (0 votes)
23 views4 pages

Schneider Electric Sepam-Serie-20 59723

The document is a product datasheet for the ACE969TP-2 RS485 multi-protocol interface used in the Sepam series 20, 40, 60, and 80. It includes specifications such as communication protocols, dimensions, environmental compatibility, and mechanical robustness. Additionally, it provides information on packaging, warranty, and sustainability certifications.

Uploaded by

Alaece Pereira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views4 pages

Schneider Electric Sepam-Serie-20 59723

The document is a product datasheet for the ACE969TP-2 RS485 multi-protocol interface used in the Sepam series 20, 40, 60, and 80. It includes specifications such as communication protocols, dimensions, environmental compatibility, and mechanical robustness. Additionally, it provides information on packaging, warranty, and sustainability certifications.

Uploaded by

Alaece Pereira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Product datasheet

Specifications

RS485 multi-protocol interface


ACE969TP-2 Sepam series 20,
40, 60, 80
59723

Main
Range Of Product Sepam series 60
Sepam series 80 NPP
Sepam series 40
Sepam series 80

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Sepam series 20

Device Short Name ACE969TP-2

Complementary
Communication Port Protocol DNP3 network: S-LAN interface: RS485 - 2-wire
IEC 60870-5-103 network: S-LAN interface: RS485 - 2-wire
Modbus RTU network: E-LAN interface: RS485 - 2-wire
Modbus RTU network: S-LAN interface: RS485 - 2-wire

Local Signalling Green LED for energized (front face)


LED for receiving data (front face)
LED for sending data (front face)
Red LED flashing for not set up or set up incorrect (front face)
Red LED off for set up and communication operational (front face)
Red LED remains ON for fault (front face)

Mounting Mode Fixed

Mounting Support Symmetrical DIN rail

Height 90 mm

Width 144 mm

Depth 52 mm

Net Weight 0.285 kg

Mechanical Robustness Earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC


60255-21-3
Earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC
60255-21-3
Jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
Shocks de-energized (level: 2) : 30 Gn/11 ms conforming to IEC 60255-21-2
Shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
Vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC
60255-21-1
Vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC
60255-21-1
Vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC
60068-2-6

Maximum Cable Distance 10 Devices <180 m at 12 V DC


Between Devices 10 Devices <750 m at 24 V DC
20 Devices <160 m at 12 V DC
20 Devices <450 m at 24 V DC
25 Devices <125 m at 12 V DC
25 Devices <375 m at 24 V DC
5 Devices <1000 m at 24 V DC
5 Devices <320 m at 12 V DC

Jun 8, 2024 1
Auxiliary Connection Terminal Protective earth: screw-type connector 1 pin(s) 1 cable(s) wire 2.5 mm² <3 m
Supply: screw-type connector 2 pin(s) 1 cable(s) wire 0.2…2.5 mm²
Supply: screw-type connector 2 pin(s) 1 cable(s) wire 1.5 mm²
Supply: screw-type connector 2 pin(s) 1 cable(s) wire 2.5 mm²
Supply: screw-type connector 2 pin(s) 2 cable(s) wire 0.2…1 mm²
Supply: screw-type connector 2 pin(s) 2 cable(s) wire 1 mm²
Functional earth: ring lug 1 pin(s) 1 cable(s)

Wire Stripping Length Supply: 8 mm

Environment
Electromagnetic Compatibility 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV
MC and MD, conforming to ANSI C37.90.1
1 MHz damped oscillating wave: (immunity tests-conducted disturbances), III, 2.5 kV
MC, 1 kV MD, conforming to IEC 60255-22-1
100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV
MC, 1 kV MD, conforming to IEC 61000-4-12
Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
Conducted disturbance emission: (emission tests), B, conforming to EN 55022
Disturbing field emission: (emission tests), conforming to IEC 60255-25
Disturbing field emission: (emission tests), A, conforming to EN 55022
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV
contact, conforming to ANSI C37.90.3
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV
contact, conforming to IEC 60255-22-2
Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz,
conforming to ANSI C37.90.1
Fast transient bursts: (immunity tests-conducted disturbances), A or B, 4kV, 2.5 kHz/
2 kV, 5 kHz, conforming to IEC 60255-22-4
Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz,
conforming to IEC 61000-4-4
Immunity to conducted RF disturbances: (immunity tests-conducted disturbances),
10 V, conforming to IEC 60255-22-6
Immunity to magnetic fields at network frequency: (immunity tests-radiated
disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8
Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...
1 GHz, conforming to IEC 60255-22-3
Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...
1 GHz, conforming to ANSI C37.90.2 (1995)
Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80
MHz...2 GHz, conforming to IEC 61000-4-3
Surges: (immunity tests-conducted disturbances), III, 2 kV MC, 1 kV MD, conforming
to IEC 61000-4-5
Voltage interruptions: (immunity tests-conducted disturbances), 100 %, 10 ms,
conforming to IEC 60255-11

Climatic Withstand Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm
H2S, 0.2 ppm S02, 0.02 ppm NO2, 0.01 ppm Cl2 conforming to IEC 60068-2-60
Continuous exposure to damp heat (in operation) : Ca: 10 days, 93 % RH, 40 °C
(104 °F) conforming to IEC 60068-2-3
Continuous exposure to damp heat (in storage) : Ca: 56 days, 93 % RH, 40 °C (104
°F) conforming to IEC 60068-2-3
Exposure to cold (in operation) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
Exposure to cold (in storage) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
Exposure to dry heat (in operation) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
Exposure to dry heat (in storage) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
Influence of corrosion/gaz test 2 (in operation) : C: 21 days, 75 % RH, 25 °C (- 13
°F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
Salt mist (in operation) : Kb/2 conforming to IEC 60068-2-52
Temperature variation with specified variation rate (in operation) : Nb: - 25 °C to 70
°C (- 13 °F to 158 °F) 5 °C/min (41 °F/min) conforming to IEC 60068-2-14

Ambient Air Temperature For -25…70 °C


Operation

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 6.4 cm

Package 1 Width 12.4 cm

Package 1 Length 18.4 cm

2 Jun 8, 2024
Package 1 Weight 385.0 g

Unit Type Of Package 2 S03

Number Of Units In Package 2 16

Package 2 Height 30.0 cm

Package 2 Width 30.0 cm

Package 2 Length 40.0 cm

Package 2 Weight 6.59 kg

Contractual warranty
Warranty 12 months

Jun 8, 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 Jun 8, 2024