In addition to the hazards/risks normally associated with the types of work detailed
on this drawing, note the following :
1 2 3 CONSTRUCTION
Structural instability during erection. Provide appropriate temporary supports or bracing.
DECOMMISSIONING / DEMOLITION
Catnic Heavy Duty Lintel Catnic Heavy Duty Lintel Structural instability during demolition. Provide appropriate temporary supports.
CN81C CN81C It is assumed that all works will be carried out by a competent contractor working, where
appropriate, to an approved method statement
Max.4910
1 All Structural Steelwork including Connection design to be in accordance with EC3.
B4 achieve a minimum 30m minute fire rating. 2 The national structural steelwork specification (NSSS) for building construction 8th edition
applies to this project.
3 Technical requirements for execution of steel structures to be in accordance with
BS EN 1090-2, execution class, Exc2.
4 All fabricated steelwork delivered to site to be CE marked in compliance with BS EN 1090-1.
STRUCTURAL STEELWORK MEMBER SIZES KEY 5 All steelwork to be hot rolled section to BS EN 10025 or hot finished structural hollow sections
two columns,upper beams & foundation Beam B5 = 203x133x30 UB - Grade S355 JO Surfaces to be unpainted for all bolted moment connections.
The wall needs to be 215 thick solid wall to beam.Steel sizes:203x203 UC 52 (S275) CONCRETE
match the wall above. The architect to PS1 - 300x100x215 deep Concrete padstones 1 All reinforced concrete to be strength class C32/40 (RC 40) having a minimum
Max.2640
MASONRY
CN81C
1 All external brickwork to be freeze/thaw resistant (F2,S2 or F2,S1 to BS EN 771) where there
is a high risk of prolonged wetting and freezing. Bricks of compressive strength Class 20 (to
BS EN 771-2) are suitable for most applications. Bricks of strength Class 30 and declared as
freeze/thaw resistant (to BS EN 771-2) are recommended in areas of severe freeze/thaw
exposure or for use where bricks may be persistently wet (eg parapets, chimneys, sills and
below dpc).
2 Blocks should comply with BS EN 771 and be used in accordance with BS EN 1996-2, with a
compressive strength of 7.3 N/mm².
3 All mortar shall be designation (iii), (M4) 1:1:5½ cement: lime: sand, except below ground
where mortar designation (ii), (M6) 1:½:4 cement: lime: sand, is to be used.
4 Preliminary compressive strength tests shall be carried out on the mortar in accordance with
BS 5628: part 1: appendix a1.Regular testing of the mortar during construction shall be
carried out.
C 5 All cavity walls to have stainless steel wall ties at 900mm horizontal and 450mm vertical
centers and must embed at least 50mm in to each leaf.
Max3730
1.0 12.06.2024 Issued for Construction SU SS BK
Ver Date Description Of Change Drn Chk App
B
E www.sdblimited.com
Max.300
Structural Design Bureau Limited
Suite 5, Park House, 1-4 Park Terrace, Worcester Park, Surrey KT4 7JZ
Tel: +44(0)208 240 9987
Catnic Heavy Duty Lintel Email: [email protected]
Key Plan
CN81C
Client Scale
Martin Kacmar 1:30
Project Name
5 Arundel Avenue, Morden SM4 4DR