The document outlines the specifications and updates for the construction of a 3x3 pump house, including design requirements and material specifications. It details various notes regarding structural elements, plastering, waterproofing, and painting, as well as updates on seismic definitions and load calculations. Additionally, it requests the provision of elevation drawings and emphasizes adherence to department requirements during execution.

Uploaded by

harshbhavsar8999
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views4 pages

11.12.2024 3X3 Pump House Gad and Str. - R1

The document outlines the specifications and updates for the construction of a 3x3 pump house, including design requirements and material specifications. It details various notes regarding structural elements, plastering, waterproofing, and painting, as well as updates on seismic definitions and load calculations. Additionally, it requests the provision of elevation drawings and emphasizes adherence to department requirements during execution.

Uploaded by

harshbhavsar8999
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

PMC WAPCOS LIMITED

CLIENT GWSSB
AGENCY DIVYA ENTERPRISE,RAJKOT
STRUCTURAL CONSULTANT PARSHWA CONSULTANCY
DOCUMENT TITLE 3x3 PUMP HOUSE
PREPARED BY WAPCOS LIMITED
Nos. 3x3 PUMP HOUSE REPLY ON 09.12.2024

1 KINDLY PROVIDE GAD AND STR. DESIGN IN SEPARATE SHEET PROVIDED GAD AND STR. DESIGN IN SEPARATE SHEET

2 ADD NOTE: FLORING SHOULD BE PROVIDED WITH POLISH KOTA STONE 25 MM THICK ADDED NOTE: FLORING SHOULD BE PROVIDED WITH POLISH KOTA STONE 25
3 ADD NOTE: PROVIDE MS DOOR AND WINDOW WITH MS JALI ADDED NOTE: PROVIDE MS DOOR AND WINDOW WITH MS JALI
ADD NOTE: INSIDE PLASTER PROVIDED WITH 15 MM THICK CM 1:1.5 NIRU FINSHED WATER PROOFING
4 ADDED NOTE: INSIDE PLASTER PROVIDED WITH 15 MM THICK CM 1:1.5 NIRU
COMPOUND.

ADD NOTE: PROVIDE 20 MM THICK SAND FACED CEMENT PLASTER (GUTAKA), 12 MM THICK BACKING
ADDED NOTE: PROVIDE 20 MM THICK SAND FACED CEMENT PLASTER (GUTAK
5 COAT OF CM 1:3 (1 CEMENT : 3 SAND) AND 8 MM THICK FINISHING COAT OF CM 1:1 (1 CEMENT : 1
1:3 (1 CEMENT : 3 SAND) AND 8 MM THICK FINISHING COAT OF CM 1:1 (1 CEM
SAND)

ADD NOTE: 2 COAT WEATHER PROOF EXTERIOR (APEX) PAINT WITH PRIMER SHOULD BE APPLIED. ADDED NOTE: 2 COAT WEATHER PROOF EXTERIOR (APEX) PAINT WITH PRIME
6
(APPROVED BRAND) & INTERNAL – DISTEMPER OF APPROVED BRAND AND QUALITY & INTERNAL – DISTEMPER OF APPROVED BRAND AND QUALITY

7 UPDATE NOTE: LAP LENGTH SHOULD BE 50XDIA. UPDATED NOTE: LAP LENGTH SHOULD BE 50XDIA.

WATER PROOFING TREATMENT, PLINTH PROTECTION AND INSCTICIDE PEST CONTROL TRETMENT ADDED NOTE: WATER PROOFING TREATMENT, PLINTH PROTECTION AND INS
8
PROVIDE AS PER DEPARTMENT REQUIRMENT PROVIDE AS PER DEPARTMENT REQUIRMENT

ADD NOTE: SUPPORT OF CHAJJA SHALL BE REMOVED ONLY AFTER ABOVE WALL / WALL AND SLAB ADDED NOTE: SUPPORT OF CHAJJA SHALL BE REMOVED ONLY AFTER ABOVE
9
ACHIEVES ITS FULL STRENGTH STRENGTH

10 PROVIDE ONE MORE WINDOW IN THE RIGHT SIDE GRID PROVIDED ONE MORE WINDOW IN THE RIGHT SIDE GRID

9 UPDATE SCHEDULE OF OPENING WITH THE MATERIAL MENTION IN REMARK AND SILL HEIGHT UPDATED SCHEDULE OF OPENING WITH THE MATERIAL MENTION IN REMARK
SBC IS CONSIDER 100KN/SQ.MT AT 2Mt. DEPTH , DURING THE EXECUTION LOOSE SOIL OR WATER
SBC IS CONSIDER 100KN/SQ.MT AT 2Mt. DEPTH , DURING THE EXECUTION LO
10 TABLE FOUND THEN WORK SHALL BE STOP AND SAME SHALL BE INFORMED TO CONCERNED
WORK SHALL BE STOP AND SAME SHALL BE INFORMED TO CONCERNED AUTH
AUTHORITY AND DESIGNER.
11 SEISMIC DEFINITION UPDATE AS PER LATEST CODE IN STAAD UPDATED SEISMIC DEFINITION AS PER LATEST CODE IN STAAD
APPLIED BRICK MASONARY LOAD FOUND INCORRECT KINDLY CHECK AND RECTIFY ALSO ADD THE
12 REVISED BRICK MASONARY LOAD AND ADDED CALCULATION IN REPORT
CALCULATION IN THE REPORT

FINISH LOAD CONSIDER IN THE DESIGN REPORT BUT NOT APPLIED IN THE STAAD MODEL KINDLY CHECK FINISHED LOAD IS ALREADY CONSIDERED IN TOTAL DEAD LOAD APPLIED i.e. 6
14
AND UPDATE CALCULATION IN REPORT.
N 09.12.2024 observation

1. PLEASE PROVIDE ELEVATION DRAWING IN GAD 2.


KINDLY SHOW THE DIMENSION OF CHAJJA PROJ.
3. KINDLY SHOW THE BRICK STEPS
DIMENSION
H KOTA STONE 25 MM THICK
OKAY
S JALI OKAY

ICK CM 1:1.5 NIRU FINSHED WATER PROOFING COMPOUND.


OKAY

NT PLASTER (GUTAKA), 12 MM THICK BACKING COAT OF CM


AT OF CM 1:1 (1 CEMENT : 1 SAND)
OKAY

PAINT WITH PRIMER SHOULD BE APPLIED.(APPROVED BRAND)


ALITY
OKAY
OKAY
OTECTION AND INSCTICIDE PEST CONTROL TRETMENT
OKAY
NLY AFTER ABOVE WALL / WALL AND SLAB ACHIEVES ITS FULL
OKAY
OKAY

ENTION IN REMARK AND SILL HEIGHT AS PER DATA SHEET Door should be MS Door and MS window
with MS Jali, update information in table
THE EXECUTION LOOSE SOIL OR WATER TABLE FOUND THEN
CONCERNED AUTHORITY AND DESIGNER.
OKAY
AAD OKAY

ON IN REPORT
OKAY
LOAD APPLIED i.e. 6.125 KN/M . KINDLY REFER RESPECTIVE
2

OKAY

KINDLY PERFORM DEFLECTION CHECK IN THE SLAB DESIGN

SPACING OF THE STIRRUPS IN COLUMN PROVIDE AS PER IS


13920:2016