Mock-up-Wind Loads-2016
Mock-up-Wind Loads-2016
Mean Height (h) = 7.20 m Low Rise Building Sec. 6.20 ASCE 7-16
(Eave height may be used if θ<=10°) Sec. 6.5.6.2.2 ASCE 7-16
Roof Slope = 0.00 :10 0.00 Degrees
Length of the building (L) = 12.80 m Horizontal dimension measured parallel to the wind
Width of the building (B) = 2.40 m Horizontal dimension measured normal to the wind
Basic Wind Speed (V) = 169.2 km/hr Ultimate wind speed at 10 mSec. 6.20 ASCE 7-16
Structure Type = Main Wind Force Resisting System Table 6-4 ASCE 7-16
2
Ao = 0.00 m Sec. 6.20 ASCE 7-16
2
Ao = Total area of opening in a wall that receives positive external pressure (m )
2
Aoi = 0.00 m Sec. 6.20 ASCE 7-16
Aoi should be set to 0 for open buildings
Aoi = The sum of the areas of opening in the building envelope (Walls & Roof) not including A o (m2)
2
Ag = 0.00 m Sec. 6.20 ASCE 7-16
2
Agi = 0.00 m Sec. 6.20 ASCE 7-16
Agi should be set to 0 for open buildings
2
Agi = The sum of the gross surface areas of the building envelope (Walls & Roof) not including Ag (m )
Open Building
Velocity Pressure Exp. Coeff. (K z) = 0.93 For Main Wind Force - Table 6-3 ASCE 7-16
- Resisting system (MWFRS)
Velocity Pressure Exp. Coeff. (K z) = 0.93 For Comp. and Claddings Table 6-3 ASCE 7-16
Gust effect factor (G) = 0.85 For Rigid Structures Sec. 6.5.8
Design Wind Pressure (p) = qh [ (Gcpf) - (Gcpi) ] kN/m2 Eqn. 6-18 ASCE 7-16
S 7.2 M
h 7.2 M
B 12.8 M
Lr 2.4 M
S/h 1
B/S 1.77777778
B/S 0.33333333
Lr/S 0.33333333
Cf 1.42
Note:- The Values are [( GCp + Gcpi )] = q = 1.08 0.85 1.42 0.9 0.8 1.099172119
2
kN/m