Dc Machines r20 Unit-5
Dc Machines r20 Unit-5
Introduction:
Almost all the major power generation and distribution systems in the world
today are three-phase ac systems. Since three-phase systems play such an
important role in modern life, it is necessary to understand how transformers are
used in them.
Transformers for three-phase circuits can be constructed in two ways. One
approach is simply to take three single-phase transformers and connect them in a
three-phase bank. An alternative approach is to make a three-phase transformer
consisting of three sets of windings wrapped on a common core.
These two possible types of transformer construction are shown in the figures
below.
The construction of a single three-phase transformer is the preferred practice
today, since it is lighter, smaller, cheaper, and slightly more efficient. The older
construction approach was to use three separate transformers. That approach
had the advantage that each unit in the bank could be replaced individually in the
event of trouble, but that does not outweigh the advantages of a combined three
Page 20
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
4. Delta-Wye(star) (∆-Y)
WYE-WYE CONNECTION:
The Y-Y connection details of three-phase transformers are shown in the figure
below.
Page 21
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Figure (b): Star-Star(Y-Y) connection Phasor diagram
Advantage/Application: This is useful and economical for low power high voltage
transformers because the phase voltage is 1/√3 times the line voltage. Hence the
number of turns per phase and the strength of insulation required would be less.
Disadvantages:
1. If loads on the transformer circuit are unbalanced, then the voltages on the
phases of the transformer can become severely unbalanced.
2. Third-harmonic voltages can be large.
Page 22
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
When a three-phase set of voltages is applied to a Y - Y transformer, the voltages
in any phase will be 1200 apart from the voltages in any other phase. However,
the third-harmonic components of each of the three phases will be in phase with
each other, since there are three cycles in the third harmonic for each cycle of the
fundamental frequency. There will always be some third-harmonic components in
a transformer because of the nonlinearity of the core, and these components add
up.
The result is a very large third-harmonic component of voltage on top of the 50 or
6O-Hz fundamental voltage. This third-harmonic voltage can be larger than the
fundamental voltage itself.
Both the unbalance problem and the third-harmonic problem can be solved using
one of the two following techniques:
1.Solidly ground the neutrals of the transformers, especially the primary winding’s
neutral. This connection permits the additive third-harmonic components to
cause a current flow in the neutral instead of building up large voltages. The
neutral also provides a return path for any current imbalances in the load.
2. Add a third (tertiary) winding connected in ∆ to the transformer bank. If a third
∆ connected winding is added to the transformer, then the third-harmonic
components of voltage in the ∆ will add up, causing a circulating current flow
within the winding. This suppresses the third-harmonic components of voltage in
the same manner as grounding the transformer neutrals.
The ∆ connected tertiary windings need not even be brought out of the
transformer case, but they often are used to supply lights and auxiliary power
within the substation where it is located. The tertiary windings must be large
enough to handle the circulating currents, so they are usually made about one-
third the power rating of the two main windings.
Page 23
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
One or the other of these correction techniques must be used any time a Y-Y
transformer is installed. In practice, very few Y-Y transformers are used, since the
same jobs can be done by one of the other types of three-phase transformers.
DELTA-DELTA CONNECTION:
The ∆- ∆ connection details are shown in the figure below.
Page 24
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Figure (c): Delta-Delta (∆-∆) connection wiring diagram
In a ∆- ∆ connection, VLP = VØP and VLS = VØS, so the relationship between primary
and secondary line voltages is given by:
Advantages/Application:
Transformers with this configuration are economical for high power low
voltage application since the number of turns required for a given line
voltage are more (since line voltage is same as phase voltage)
This transformer has no phase shift associated with it and no problems with
unbalanced loads or harmonics.
For the secondary voltage to be perfect sinusoidal the magnetizing currents
must contain third harmonic components. The Delta configuration provides
a closed path for the circulation of third harmonic components of current.
Hence the flux remains sinusoidal thus resulting in better sinusoidal
voltages.
Page 25
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
The phase current is lesser than the Line current (by 1/√3). Hence the
conductor cross sectional area can be smaller thus resulting in saving of
conductor material.
Disadvantages:
VØP / VØS = a
so the overall relationship between the line voltage on the primary side of the
bank and the line voltage on the secondary side of the bank is:
Page 26
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Figure (a): Wye-Delta (Y-∆) connection representation
Page 27
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Figure (c): Wye -Delta (Y-∆) connection wiring diagram
Advantages/Application:
This connection is advantageous/economical for high power high voltage
step down power transformers. Primary in star configuration can be used
for higher voltage since line voltage is √3 times the phase voltage and thus
the number of turns required per phase will be lesser for a higher line
voltage. The delta side with lower line voltage (line voltage being equal to
phase voltage) can be used as secondary.
The neutral available in primary can be earthed to avoid distortion
Hence transformers with this type of connection are used in the main
receiving end of a transmission line where a step down transformer is
required.
The Y - ∆ connection has no problem with third-harmonic components in its
voltages, since they are consumed in a circulating current on the ∆ side.
This connection is also more stable with respect to unbalanced loads, since
the ∆ partially redistributes any imbalance that occurs. i.e. Load side
(secondary) large unbalanced loads can be handled satisfactorily.
Disadvantages:
This arrangement has one problem. Because of this type of connection,
the secondary voltage is shifted 300 relative to the primary voltage of the
transformer which can be further positive shift or negative shift. The fact
that a phase shift has occurred can cause problems in paralleling the
secondaries of two transformer banks together. The phase angles of
transformer secondaries must be equal if they are to be paralleled, which
means that attention must be paid to the direction of the 300 phase shift
occurring in each transformer bank to be paralleled together.
Page 28
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
formed by connecting c1a2, a1b2 and b1c2 with the lines connected to these
junctions being labeled as a, b and c respectively as shown in Fig. (a). The phasor
diagram is drawn in Fig. (b). It is seen from the phasor diagram on the delta side
that the sum of voltages around delta is zero. This is a must as otherwise closed
delta would mean a short circuit. It is also observed from the phasor diagram that
phase a to neutral voltage (equivalent star basis) on the delta side lags by – 30° to
the phase-to-neutral voltage on the star side. This is also the phase relationship
between the respective line to- line voltages. This connection, therefore, is known
as – 30°-connection. Or YD1 representing 1O clock position. With this notation
secondary Delta lags the primary star by 300.
The + 30°-connection follows from the phasor diagram of Fig. (a) above with the
corresponding connection diagram shown in Fig. (b).
Page 29
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
the above figures .But what was the – 30°-connection will now be the + 30°-
connection and vice versa.
DELTA-WYE CONNECTION:
∆-Y connection details of three-phase transformers are shown in the figures
below. In a ∆-Y connection, the primary line voltage is equal to the primary-phase
voltage VLP = VØP , while the secondary voltages are related by VLS = √3VØS .
Therefore, the line-to-line voltage ratio of this transformer connection is given by
:
Page 30
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Figure (b): Delta - Wye (∆-Y) connection Phasor diagram
Advantages/Application:
This connection is advantageous/economical for high power high voltage
step up power transformers. Primary in Delta configuration can be used for
lower voltage (line voltage being equal to phase voltage) And secondary in
Wye (star) configuration can be used for higher voltage since line voltage is
√3 times the phase voltage and thus the number of turns required per
phase will be lesser for a higher line voltage.
Hence transformers with this type of connection are used at the starting
(Generating station) end of a transmission line where a step up transformer
is required.
Page 31
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Disadvantages:
This connection has the same disadvantages and the same phase shift as the Y - ∆
transformer. The connection shown in the figure above makes the secondary
voltage differ the primary voltage by 30° as in Y -∆.
The resulting configuration is known as open ∆ (or V-V) Connection and is shown
in the figure below.
Figure: Third transformer (VBR) removed from the Three transformer Bank and
the corresponding Phasor diagram
Page 32
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
If the open Delta primary is now excited from a balanced three phase supply, then
the voltage across the gap where the third transformer used to be would exactly
be the same voltage that would be present if the third transformer were still
there .
Thus, the open-delta connection lets a transformer bank work as a three phase
transformer with only two transformers, allowing some reduced power flow to
continue even with a damaged phase removed.
Power Delivered in Open Delta configuration:
How much apparent power can the bank supply with one of its three
transformers removed? At first, it seems that it could supply two-thirds of its
rated apparent power, since two-thirds of the transformers are still present.
Things are not that simple. To understand what happens when a transformer is
removed, let us see the figures (a) and (b) below. Figure (a) shows ∆ - ∆
connection and figure (b) shows V-V connection.
Page 33
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Fig(a) : ∆ - ∆ connection Fig(a) : V- V
connection
We know that the power output from a three phase system is √3 VLIL Cos φ
where Cos φ is the power factor. Hence in figure (a) ∆ - ∆ capacity = √3 VLIL Cos
φ = √3 VL √3IPh Cos φ (since IL = √3IPh)
Summary conclusion:
The total load carried by an open ∆ (V- V) connection is 57.7 % of the total
capacity of the ∆- ∆ and not 2/3rd (66.6 % ) of the total capacity of the ∆- ∆ as
might be expected. Thus for example, in a ∆- ∆ bank of three transformers each of
100kVA if one transformer is removed, then the total capacity of the resulting V-V
bank becomes 57.7 % of 300kVA i.e. 173.2kVA and not 200kVA.
In other words in V-V configuration the resultant capacity becomes 86.6% of the
rated capacity of the two transformers put together. i.e. 0.866 x 200kVA = 173.2
kVA .
Page 34
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
When the three phase load is too small to warrant the installation of full
three phase transformer bank.
When one of the three transformers in a ∆ - ∆ bank is disabled service is at
a reduced capacity is adequate , till the faulty transformer is repaired and
restored.
When it is expected that in the future , the total load will increase
necessitating the closing of the open ∆.
Illustrative examples:
Example1: The following test results were obtained for a 20 kVA,2400/240 V
distribution transformer : O.C test(l.v side)240 V,1.066 A,126.6 WS.C test (h.v
side) 57.5V, 8.34 A, 284 W Calculate a) Equivalent circuit parameters when
referred to h.v side and draw it. b) Efficiency of the transformer at half full-load
with 0.8 power factor lagging. C) Regulation at full load 0.8 power factor lagging.
( JNTU May-15)
V0
X 0 ' 259.095
Im
V1 2400
K 10
V2 240
R0 R0 'K 2 45.497k
Page 35
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
X 0 X 0 ' xK 2 25.91k ……..Referred to h.v side
Wsc 284
R1e 4.083k
2
I le 8.342
V
∴ Z 1e sc 6.8944
I sc
X 1e Z 12e R12e 5.555
The equivalent circuits referred to h.v. side is shown in the figure below.
Page 36
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
0.5 20 103 0.8
100
0.5 20 103 0.8 126.6 [0.5 2 284]
= 97.589 %
= 2.293 %
Example 2 : Two similar 200 kVA, single phase transformers gave the following
results in Sumpner’s test : Mains wattmeter W1 = 4 kW, Series wattmeter W2 = 6
kW at full load current. Find out individual transformer efficiencies at i) Full load
at unity p.f.and ii) Half load at 0.8 p.f. lead. (JNTUK April-12)
W2 6
∴ (Pcu)F.L. = Full load copper loss for each transformer = = 3 kW
2 2
i) At full load,
VArating cos 2
% 100 with cos Ø2 = 1
VArating cos 2 Pi ( pcu ) F .L
Page 37
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
200 103 1
100
200 103 1 2 103 3 103
= 97.56 %
1
ii) At half load, cos Ø2 = 0.8 and n = = 0.5
2
n (VArating) cos 2
∴ % 100
n (VArating) cos 2 Pi n 2 ( Pcu ) F .L
= 96.67 %
Page 38
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
1.6
250 = Kh ×60×
200
i.e. Kh = 0.607
60
2
90 = Ke × 602
200
i.e. Ke = 0.00225
60
Now E = 230 V, f = 50 Hz
1.6
Ph = 0.607 ×50×
230
∴ = 348.795 W
50
2
Pe = 0.00225 ×50 ×
2 230
= 119.025 W
50
∴ Core loss = Ph + Pe = 467.82 W at 230 V, 50 Hz
V1 V
∴ = 8.8 and 2 = 8.8
f1 f2
∴ Ph = A f and Pe = B f2
∴ Pi = Ph + Pe = A f + B f2
Page 39
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Thus eddy current loss a normal voltage and frequency is,
Example 5:Two single phase transformer with equal turns have impendance of
(0.5 +j3) ohm and (0.6 +j10) ohm with respect to the secondary.If they operate in
parallel, determine how they will share a total load of 100 kW at p.f. 0.8 lagging ?
Z2
Load shared by transformer 2 = Q
Z1 Z 2
Page 40
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
0.5 j 3
= [125 /- 36.860]
(0.5 j 3) (0.6 j10)
380.125 /_ 43.67 0
= 0
= 29.13 /- 41.490 kVA
13.046 /_ 85.16
Example 6: Two single phase transformer A and B of equal voltage ratio are
running in parrallel and supplying a load of 1000 A at 0.8 p.f. lag. The equivalent
impedance of the two transformers are (2+j3)and (2.5+j5) ohms respectively.
Calculate the current supplied by each transformer and the ratio of the kW output
of the two transformer.
Page 41
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
∴ Cos Ø = 0.8, Ø = cos -1 0.8 = 36.860
∴ I = 1000 /- 36.860 A = (800-j 600) A
We have, I = IA + IB
∴ 800 - J 600 = [1.54 + j 0.1924] IB + IB
= [2.54 + j 0.1924] IB
800 j 600 1000/_ 36.860
∴ IB =
2.54 j 0.1924 2.5472/_ 4.330
= 392.58 / - 41.190 A
∴ IB = 392.58 /- 41.190 A = 295.42 -j258.53 A
Now, IA = (1.54+ j 0.1924) IB
= [1.5519 <7.120][392.58<-41.190]
∴ IA = 609.24 /- 34.070 A = 504.66 - j 341.29 A
The ratio of kW outputs is nothing but the ratio of inphase components of the
two currents.
outputofTransformerA 504.66
= 1.7
outputofTransformerB 295.42
E A Z B Z L (E A EB )
IA =
Z A Z B Z L (Z A Z B )
EB Z A Z L (E A EB )
And IB =
Z A Z B Z L (Z A Z B )
Page 42
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
[207 /_ 0 0 ][ 0.1 j 0.6] (2 j1.5)[207 /_ 0 0 205 /_ 0 0 ]
IA =
(0.15 j 0.5)(0.1 j 0.6) (2 j1.5)[(0.15 j 0.5) (0.1 j 0.6)]
EB Z A Z L (E A EB )
and similarly we get IB =
Z A Z B Z L (Z A Z B )
[205 /_ 0 0 ][ 0.15 j 0.5] (2 j1.5)[207 /_ 0 0 205 /_ 0 0 ]
=
(0.15 j 0.5)(0.1 j 0.6) (2 j1.5)[(0.15 j 0.5) (0.1 j 0.6)]
Solving, IB = (33.5534 /-42.890) A
= (24.5832 - j 22.8362) A
Now total current is given by,
IL = IA + IB
= (32.866 - j 26.463) + (24.5832 - j 22.8362)
= (57.4492 - j 49.2992) A
= 75.70 /-40.630 A
The load voltage, VL = IL ZL = (75.70 /- 40.630)(2+j 1.5)
= (75.70 /- 40.630) (2.5 /36.860)
= 189.25 /- 3.770 volts
The angle between VL and IA can be calculated as,
ØA = (-38.840) - (-3.770) = -35.070
∴ p.f. = cos ØA = cos (35.07)
= 0.8184 (lagging)
The angle between VL and IB can be Calculated as,
ØB = (-42.890) - (-3.770) = -39.120
p.f. = cos ØB = cos (39.12)
= 0.7758 (lagging
Page 43
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
Power output of transformer A = VL IA cos ØA
= 189.25×42.196×0.8184
= 6535.40 W = 6.5354 Kw
𝑉𝑝 ℎ 1 11 ×10 3
∴ Vph2 = = = 1100 V
10 10
Example 2: A bank of three single phase transformers has its h.v. terminals
connected to 3 wire, 3-phase, 11kV system. It’s l.v. terminals are connected to a 3
wire, 3-phase load rated at 1500 kVA , 2200 V. specify the voltage, current and
kVA ratings of each transformer for both h.v
Solution:
The load is 1500 kVA hence the rating of each transformer is (1500/3) = 500 kVA
and is same for all configurations. Since input is 11kV and output is 2200V, in all
configurations the line voltages are also same on both primary side and secondary
side. . i.e. VL1=11kV and VL2 = 2,200 V. The voltage and current ratings are
specified on Phase basis only and hence lets us find out VPh and I Ph on both HV
side and LV side for the given four configurations.
Page 45
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
i) 11 kV Y and 2200 V Δ
11 103
Vph1 = = 6350.8529 V
3
Vph1 Iph1 = 500 × 103 i.e. Iph1 = 78.729 A
Vph2 = 2200 V
Vph2 Iph2 = 500 × 103 i.e. Iph2 = 227.2727 A
ii) 11 kV Δ and 2200 V Y
2200
Vph1 = 11 kV and Vph2 = 3 = 1270.1705 V
500 103
∴ Iph1 = 11 103 = 45.45 A
500 103
∴ Iph2 = 1270.1705 = 393.6479 A
iii) 11 kV Y and 2200 V Y
11 103 2200
Vph1 = 3 = 6350.8529 V, Vph2 = 3 = 1270.1705 V
500 103
∴ Iph1 = 6350.8529 = 78.729 A
1500 103
∴ Iph2 = 1270.1705 = 393.6479 A
Solution : VL1 = 6.6 kV, VL2 = 1.1 kV, Vph1 = VL1, Vph2 = VL2/√3
I 1 ( FL )
∴ I1 (Ph) = = 60.606 A
3
Page 46
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
K = (VPh1/VPh2)= (6.6 x 103)/ (1.1 x 103/√3) =10.393
Example 4: A 5000 kVA, 3 phase transformer 6.6 /33 kV, Δ/ Y has a no load loss of
15 kW and full load of 50 kW. The impedance drop at full load is 7%. Calculate the
primary voltage when a load of 3200 kW at 0.8 p.f. is delivered at 33 kV.
VA 5000 103
∴ IL2 = = 87.4773 A = Iph2
3VL 2 3 33 103
7 33 103
Impedance drop per phase = 7 % of VPh2 = × = 1333.6791 V
100 3
1333.6791 1333.6791
∴ Z2e = = 15.2459 Ω/ph
I ph 2 87.4773
35 103
But, Pcu(FL) = 3 × I 22ph R2e i.e. R2e = = 1.524 Ω
3 (87.4773) 2
Page 47
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
P2 3200 103
IL2 = = 69.98 A = I2ph
3VL 2 cos 3 33 103 0.8
V ph1 33
∴ K= = 5.1975
V ph 2 6.35
R1 = 35 Ω, R2 = 0.876 Ω
VA 500 103 I 1 ( FL )
I1(FL) = = 8.7477 A Therefore : I1ph(FL)=
3VL1 3 33 10 3
3
Page 48
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)
I 1 ( FL )
∴ Pcu(FL) = 3× I 12ph (FL) × R1e and I1ph =
3
2
8.7477
= 3 × × 58.6643 = 4489.1245 W
3
VA cos
∴ %ղFL = × 100
VA cos Pi Pcu ( FL )
= 98.15 %
0.5 VAcos
%ղHL = × 100
0.5 VA cos Pi [( 0.5) 2 Pcu ( FL )]
0.5 VAcos
= × 100 = 97.956 %
0.5 VA cos 3050 [( 0.5) 2 4489.12]
Page 49
Malla Reddy College of Engineering and Technology
Department of EEE (2021-22)