MV Application Guide
MV Application Guide
Application Guide
CONTENTS
Contents
1 Introduction ........................................................................................................................................................................... 4
2 Motors ...................................................................................................................................................................................... 5
2.1 Common types of industrial motors .................................................................................................................................................. 5
Induction motors........................................................................................................................................................................................... 5
Useful formulae .............................................................................................................................................................................................. 6
Slip-ring motors ............................................................................................................................................................................................. 7
Synchronous motors ................................................................................................................................................................................... 9
2.2 Motor starting methods ......................................................................................................................................................................... 10
Direct on-line starting .............................................................................................................................................................................. 10
Primary resistance starting..................................................................................................................................................................... 11
Auto-transformer starting ..................................................................................................................................................................... 13
Star-Delta starting ...................................................................................................................................................................................... 15
Soft starters ................................................................................................................................................................................................... 16
Variable frequency drives (VFD) ....................................................................................................................................................... 17
4 Switchgear............................................................................................................................................................................ 69
4.1 Switchgear Classifications ...................................................................................................................................................................... 70
IEC Switchgear Classification ............................................................................................................................................................... 71
ANSI-defined switchgear ....................................................................................................................................................................... 72
Switchgear Ratings..................................................................................................................................................................................... 72
Switchgear information for enquiries or ordering .................................................................................................................... 72
Switchgear derating .................................................................................................................................................................................. 73
4.2 Standard Enclosure Configurations .................................................................................................................................................. 74
Incomer Feeder Panel (IFP) .................................................................................................................................................................. 74
Direct Incomer Panel (DIP) ................................................................................................................................................................. 75
Bus Coupler Panel (BCP) ...................................................................................................................................................................... 76
Bus Riser Panel (BRP) .............................................................................................................................................................................. 77
Metering Panel (MTP) ............................................................................................................................................................................. 78
Busbar Systems ........................................................................................................................................................................................... 79
4.3 Safety Considerations .............................................................................................................................................................................. 83
Switchgear interlocking systems ......................................................................................................................................................... 83
Internal arc classification ......................................................................................................................................................................... 85
4.4 Switchgear Apparatus .............................................................................................................................................................................. 88
Medium Voltage Circuit Breakers ..................................................................................................................................................... 88
Medium Voltage Contactors ............................................................................................................................................................... 96
Medium Voltage Switches .................................................................................................................................................................. 100
Medium Voltage HRC Fuses ............................................................................................................................................................ 104
Current Transformers .......................................................................................................................................................................... 110
Current Sensors ...................................................................................................................................................................................... 119
Protection Devices ................................................................................................................................................................................. 121
Voltage Transformers ........................................................................................................................................................................... 127
Motor Line Inductors on Soft Starter Applications .............................................................................................................. 130
Medium Voltage Surge Arrestors .................................................................................................................................................. 132
Power Factor Capacitors .................................................................................................................................................................... 136
4.5 Calculations ................................................................................................................................................................................................ 143
Transformer Calculations ................................................................................................................................................................... 143
Motor Calculations................................................................................................................................................................................. 147
Busbar Calculations ................................................................................................................................................................................ 149
Short Circuit Calculations ................................................................................................................................................................... 156
Impedance Method Calculations .................................................................................................................................................... 159
4.6 Switchgear Inspection Checklists .................................................................................................................................................... 162
Mechanical Inspection .......................................................................................................................................................................... 162
Electrical Inspection ............................................................................................................................................................................... 163
Commissioning Tools and Equipment (Typical) .................................................................................................................... 164
4.7 Switchgear-Related IEC Standards ................................................................................................................................................ 165
4.8 Comparison of IEC and IEEE Standards ..................................................................................................................................... 167
Examples of differences in rating requirements ..................................................................................................................... 167
4.9 IEC Switchgear Rating Definitions.................................................................................................................................................. 168
Voltage.......................................................................................................................................................................................................... 168
Current ......................................................................................................................................................................................................... 168
Frequency, fr (Hz) .................................................................................................................................................................................. 169
4.10 Protection index ...................................................................................................................................................................................... 170
IP Ratings ..................................................................................................................................................................................................... 170
NEMA Ratings .......................................................................................................................................................................................... 171
1 Introduction
This reference guide is designed to help engineers in the field of medium voltage select and specify the right MV
equipment for their application.
This guide provides an overview of all the main components in a motor control system, in a format that is readily
understood by people with limited or no experience with motor control in general and soft starters in particular.
We hope this document will help:
consulting engineers wanting to specify motor control equipment
technical departments using motor control equipment
maintenance engineers at locations with soft starters installed
We would welcome your feedback so we can continue to improve this guide.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained
in this manual is subject to change at any time and without prior notice. In no event will responsibility or liability be
accepted for direct, indirect or consequential damages resulting from the use or application of this equipment.
2 Motors
The rotor design determines the starting characteristics of the motor. The stator design determines the
running characteristics of the motor.
AC induction motor
When 3-phase supply voltage is applied to the stator winding of an induction motor, a rotating magnetic field is
produced which cuts through the rotor bars. The rotating speed of this magnetic field is referred to as "synchronous
speed".
Interaction between the rotating magnetic field and the rotor bars induces a voltage which causes current to flow in
the rotor bars. This rotor current produces a magnetic field in each rotor bar. Interaction between the stator's
rotating magnetic field and the rotor bar magnetic fields produces a torque which causes the rotor to be driven in
the same rotational direction as the stator magnetic field.
Torque produced by the rotor varies from stationary to full running speed. This torque is primarily a function of the
rotor resistance and leakage reactance. The latter is determined by the difference in rotational speed between stator
magnetic field and the rotor, otherwise known as slip. Slip is commonly expressed as a percentage of the motor's
synchronous speed.
Motor start performance characteristics can vary greatly depending on rotor design and construction, but in general,
a motor with high locked rotor current will produce low locked rotor torque and vice versa. A high resistance rotor
produces relatively high starting torque but runs at high slip which causes inefficiency. To produce superior starting
and running characteristics, specially shaped rotor bars or double cage rotors are used.
7 x FLC
Full voltage motor current
Full voltage motor torque
6 x FLC 2 x FLT
Load torque (quadratic load, eg
5 x FLC
pump)
Current
Torque
4 x FLC
3 x FLC 1 x FLT
2 x FLC
1 x FLC
03340.B
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
Useful formulae
Motor synchronous speed
Where:
Ns =
f × 60 Ns = synchronous speed (rpm)
p f = mains supply frequency (Hz)
p = number of stator pole pairs
Motor slip speed (%)
Where:
Nslip
(N N r )
= s ×100 Nslip = percentage slip speed (%)
Ns Ns = synchronous speed (rpm)
Nr = rotor speed (rpm)
Motor shaft output power
Where:
N ×T
Po = r r Po = output power (kW)
9550 Nr = rotor shaft speed (rpm)
Tr = rotor torque (Nm)
Motor electrical input power
Where:
Pi = input power (kW)
Pi = 3 × V×I ×cos V = motor line voltage (kV)
I = motor line current (A)
cosØ = motor power factor
Motor efficiency
Where:
eff =
Po
×100 eff = motor efficiency (%)
Pi Po = motor output power (kW)
Pi = motor input power (kW)
Slip-ring motors
A slip-ring induction motor is also referred to as a wound rotor motor. In principle, the stator construction is the
same as that of a squirrel cage induction motor. The rotor is made up of a set of windings embedded in rotor slots
and brought out to a set of slip-rings. External rotor resistance is then connected to the slip-rings via a brush gear
arrangement. The external rotor resistance is variable and is used for starting the motor.
KM1 R2 R1
1 2 4
13227.A
A B
The major advantage of a slip-ring motor is that it produces very high starting torque (150-250% of full
load torque) from standstill to full running speed, while consuming a relatively low level of start current
(200-350% of full load current).
Current
Torque
13187.A 13188.A
Speed Speed
Provided sufficient start torque is developed with a single stage of rotor resistance, soft starters can be successfully
applied to slip-ring motors.
Refer to Slip ring motor control on page 66 for further details.
Synchronous motors
The construction of a synchronous motor stator is the same as a standard induction motor, although the stator
configuration is such that relatively low operating speeds are common (eg 300-600 rpm).
When 3-phase voltage is applied to the stator windings, a magnetic field is generated which rotates at a synchronous
speed around the stator and rotor. The synchronous speed is determined by the stator construction and frequency
of the supply voltage.
Motor synchronous speed
Where:
Ns =
f × 60 Ns = synchronous speed (rpm)
p f = mains supply frequency (Hz)
p = number of stator pole pairs
The rotor design incorporates a squirrel cage winding combined with a DC excitation winding. This allows the motor
to start as a standard squirrel cage induction motor, reaching a running speed of approximately 95% synchronous
speed. At this point, a DC voltage is applied to the excitation winding via a slip-ring and brush arrangement. A fixed
magnetic field is created in the rotor which locks in with the rotating magnetic field of the stator. The motor shaft
now runs at synchronous speed.
Synchronous motor
Fan inside
Excitation rings (x2)
Three phase stator windings
Rotor with poles and excitation windings
Excitation brushes (x2)
As motor shaft load is increased, the operating power factor of the motor is reduced. This power factor can be
improved by increasing the DC excitation level of the rotor. This behaviour allows the AC synchronous motor to
operate very efficiently at a fixed speed, independent of loading.
Soft starters are suitable for this type of application, but an external DC excitation package is required for
synchronous speed control and operation.
7 x FLC
Full voltage motor current
6 x FLC 2 x FLT
Full voltage motor torque
5 x FLC
Load torque (quadratic load, eg pump)
Current
Torque
4 x FLC
3 x FLC 1 x FLT
2 x FLC
1 x FLC
03340.B
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
09454.A
3~
1 3 4
The motor current is equal to the line current and the starting torque is reduced by the square of the current
reduction ratio. The current reduction depends on the ratio of the motor impedance to the sum of the added
primary resistance and motor impedance.
As the motor accelerates, the stator impedance increases, resulting in increasing stator voltage with speed. Once the
motor reaches full speed, the resistors are bridged by a second contactor to supply full voltage to the motor.
The initial start voltage is determined by the value of the resistors used. If the resistors are too high in value, there will
be insufficient torque to accelerate the motor to full speed, so the step to full voltage will result in a high current and
torque step.
The reduced voltage start time is controlled by a preset timer which must be correctly set for the application. If the
time is too short, the motor will not reach full speed before the resistors are bridged. Excessive start time results in
unnecessary motor and resistor heating.
Several stages of resistance can be used and bridged in steps to control the current and torque more accurately.
This minimises the magnitude of the current and torque steps.
Primary resistance starters dissipate a lot of energy during start due to the high current through, and the high voltage
across the resistors. For extended times or frequent starts, the resistors are physically large and must be well
ventilated.
Primary resistance starters are closed transition starters, so they are not subject to 'reclose' transients.
Torque
3 x FLC 1 x FLT
Load torque
2 x FLC
1 x FLC
13193.A
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
Torque
2 x FLC
Current and torque transient
1 x FLC
13190.A
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
Auto-transformer starting
Auto-transformer starters use an auto-transformer to reduce the voltage during the start period. The transformer
has a range of output voltage taps which can be used to set the start voltage, and the start time is controlled by a
timer.
The motor current is reduced by the start voltage reduction, and further reduced by the transformer action resulting
in a line current less than the actual motor current.
The initial line current is equal to the LRC reduced by the square of the voltage reduction. A motor started on the
fifty percent tap of an auto-transformer will have a line start current of one quarter of LRC and a start torque of one
quarter of LRT. If the start voltage is too low, or the start time is too short, the transition to full voltage will occur
with the motor at less than full speed, resulting in a high current and torque step.
The simplest auto-transformer starters are single step and often control two phases only. More sophisticated
starters may step through two or more voltage steps while accelerating from the initial start tap to full voltage.
Auto-transformer starters are usually rated for infrequent starting duties. Frequent or extended start rated
auto-transformers are large and expensive due to the heating in the transformer.
Auto-transformer starters can be constructed as open transition starters but most commonly the Korndorfer closed
transition configuration is employed to eliminate the 'reclose' transients.
Auto-transformer connection
Run contactor
M Thermal overload
3~
Start contactor (A)
Auto-transformer
Start contactor (B)
09455.A
5 x FLC
Auto-transformer start current
Full voltage torque
Current
Torque
4 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
5 x FLC
Auto-transformer start current
Full voltage torque
Current
Torque
4 x FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
Star-Delta starting
Star-delta starters are the most common reduced voltage starter used in industry because of their low cost.
The motor is initially connected in star configuration, then after a preset time the motor is disconnected from the
supply and reconnected in delta configuration. The current and torque in the star configuration are one third of the
full voltage current and torque when the motor is connected in delta.
Main contactor
Thermal overload
Motor (three-phase)
Delta contactor
Star contactor
09456.A
The star and delta configurations provide fixed levels of current and torque, and cannot be adjusted to suit the
application.
If the star configuration does not provide enough torque to accelerate the load to full speed, a high starting
torque motor such as a double cage motor should be employed.
If the motor does not reach full speed in star, the transition to delta configuration will result in a high current
and torque step, defeating the purpose of reduced voltage starting.
Most star-delta starters are open transition starters so the transition from star to delta results in very high current and
torque transients in addition to the high step magnitudes. Closed transition star-delta starters are rarely used due to
the increased complexity and cost. The closed transition starter reduces the 'reclose' effect but does not improve
the controllability of the start parameters.
1
7 x FLC 6 Full voltage start current
2 x FLT
Star-delta start current
6 x FLC
5 x FLC
Full voltage torque
4 x FLC
Star-delta torque
3
3 x FLC 1 x FLT
Stall point
2 x FLC
2
Current and torque transient
Current
Torque
5
4
1 x FLC
13196.A
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed
Soft starters
Electronic soft starters control the voltage applied to the motor by means of an impedance in series with each phase
connected to the motor. The impedance is provided by AC switches – reverse parallel connected SCR-diode or
SCR-SCR circuits. The voltage is controlled by varying the conduction angle of the SCRs.
13191.A
1 2 3
The SCR-SCR switch is a symmetric controller, which results in odd order harmonic generation.
The SCR-diode switch is an asymmetric controller, which causes even order harmonic currents to flow in the motor
and supply. Even order harmonics are undesirable for motor control because of the increased losses and heating
induced in the motor and supply transformers.
Electronic soft starters come in two control formats.
Open loop controllers, which follow a timed sequence. The most common open loop system is timed
voltage ramp, where the voltage begins at a preset start voltage and increases to line voltage at a preset
ramp rate.
Closed loop controllers, which monitor one or more parameters during the start period and modify the
motor voltage in a manner to control the starting characteristics. Common closed loop approaches are
constant current and current ramp.
VFDs are ideal for applications with an extremely limited supply because the starting current is never more
than the motor FLC.
VFD bypassed
In some medium voltage motor applications, a VFD is used to start the motor but is bypassed by a contactor or
circuit breaker when running at mains supply frequency.
This means:
motor start current never exceeds the motor full load current. This is very useful on sites where the mains
supply capacity is limited
the overall motor control system is more reliable because the VFD is only required during starting and
stopping
if the VFD malfunctions, the motor can still be started and run DOL, via the bypass switch. In this case, the
mains supply must have the capacity to start the motor.
Control of the bypass switch can be automatic or manual.
3 2
PR
K1B
13228.A
M 3
Operation:
Contactors K1A and K1B close and the motor is run up to full speed. Once the output of the VFD reaches
main supply frequency, contactors K1A and K1B open. After a short delay, bypass contactor K2 closes.
Contactors K1B and K2 are electrically and mechanically interlocked. The VFD can be isolated from
operation by racking out contactors K1A and K1B.
Motor protection relay PR protects the motor when K2 is closed.
3 Soft Starters
3.1 What is a Soft Starter
A soft starter is an electronic motor controller used on three phase squirrel cage induction motors. During motor
starting, the soft starter controls the voltage or current supplied to the motor. Motor start performance is
optimised by reducing the total start current while optimising the torque produced by the motor. Motor stopping
can also be controlled by ramping down the output voltage over a predetermined time period. This is particularly
useful for eliminating water hammer in pumping applications.
Soft starters use SCRs (silicon controlled rectifiers, also called thyristors), arranged back-to-back for each controlled
phase of the soft starter. This provides phase angle control of the voltage waveform in both directions.
Controlling the voltage controls the current supplied to the motor. The stepless control of motor terminal voltage
eliminates the current and torque transients associated with electromechanical forms of reduced voltage starting,
such as star-delta or autotransformer starters.
13477.A
L1 T1
Voltage waveform
Q1 Firing angle
Q2 Conduction angle
13478.A
Q1 Q2
A soft starter designed to control motor voltage is referred to as an open loop controller. A soft starter designed
to control motor current is referred to as a closed loop controller.
13473.A
Open loop soft start controllers can use a voltage step or timed voltage ramp approach.
Voltage step controllers (also called pedestal controllers) apply a preset level of voltage at start, then step to full
voltage after a user-defined period. Voltage step starters have little advantage over closed transition
electromechanical starters and are rarely used.
2
Initial start voltage
Start time
3
1 Full voltage
13475.A
Timed voltage ramp controllers ramp the voltage from a user-defined start voltage to full voltage, at a controlled
rate. Timed voltage ramp is used extensively in low cost soft starters.
13476.A
The start voltage and ramp rate are often referred to as torque and acceleration adjustments, but soft start can only
influence torque and acceleration, not provide precise control.
The acceleration rate is determined by the motor and machine inertia. A high inertia load requires a slow ramp
time if the current is to be minimised. If the start voltage rises to quickly, current may approach locked rotor current.
A low inertia load requires a short ramp time. Excessive starting time can result in insufficient voltage for stable
operation once the motor has reached full speed.
13474.A
1
Common closed loop systems are:
Constant Current or Current Limit
Timed Current Ramp
Constant Acceleration
Constant current soft start
Constant current starters monitor the starting current. Increasing or decreasing the output voltage increases or
decreases the current supplied to the motor. As the motor accelerates, the stator impedance rises and in order to
maintain a constant current the voltage also rises. The exact relationship between voltage and speed depends on
the motor design.
With a constant current starter, full torque is available as the motor reaches full speed. It is important that the starting
current is high enough to accelerate the motor to full speed under all conditions. If the torque is insufficient for
acceleration at any time during the start, the motor will continue to run at the reduced speed. This will overheat the
motor unless there is excess start time protection.
Timed current ramp soft start
Timed current ramp soft starters increase the current from a selected start level to the maximum start current, at a
controlled rate. This caters for variation in starting torque requirements, or can deliver reduced starting torque
without limiting the maximum starting torque. Typical applications are conveyors which start under varying load
conditions, and pumps which require very low torque at low speed.
This method also suits motors running on generator supplies, as the starting load is gradually applied to the generator
set. This provides stable voltage and frequency control of the generator set during motor starting.
Constant acceleration soft start
Constant acceleration or linear acceleration starters monitor the motor speed, by means of a tacho generator
attached to the motor shaft. The voltage applied to the motor is controlled to deliver a constant rate of acceleration,
over a selected acceleration time. A current limiting circuit can also be used to limit the maximum starting current,
particularly in applications where a potential exists for jammed loads.
1
Torque (% motor full load torque)
700
Full voltage start current
600 200
2 Current limit
500
Full voltage start torque
Current
400
3 Torque output at current limit
300 100
5 Acceleration torque
200 4
Load torque curve
100 6
09677.B
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed (%full speed)
3.2 Benefits
Electrical Benefits
Minimise start current levels to match application requirements. This reduces overall demand on the
electrical supply.
Eliminate current transients during motor starting and stopping. This avoids supply voltage dips which can
affect the performance of other equipment and in severe situations, cause equipment failure.
Reduce the size of electrical transformers, switchgear and cable.
Reduce maximum demand charges from the electricity supplier.
Mechanical Benefits
Minimise start torque levels to match application requirements. This eliminates mechanically damaging
torque transients associated with electromechanical starting methods.
Smooth, stepless torque is applied to the load from the motor shaft. This can:
reduce pipeline pressure surges and water hammer in pump applications
eliminate belt slippage associated with belt driven loads
eliminate belt slap associated with large belt conveyor applications.
Reduce maintenance and production down-time.
Application Benefits
Optimise performance for any motor and load combination.
Soft stop reduces or eliminates water hammer in pump applications.
Simplicity. The soft starter provides a complete motor control solution in one package. This includes
advanced motor protection, input/output signals for remote control/monitoring and a wide range of
communication options.
3.3 Anatomy
Key components
Most soft starters have the following main components:
SCRs (also called thyristors)
Snubber circuits
Heatsink
Fans (optional for increased thermal ratings)
Busbars
Current sensors
Printed Circuit Boards (PCBs)
Housing
SCRs
SCRs (silicon controlled rectifiers, also called thyristors) are the primary component of any soft starter. The SCR is
a controlled diode that only allows current to flow in one direction.
An SRC has three terminals. When the gate terminal is triggered with a low voltage signal, the SCR is turned on.
This allows current to pass through from the anode to cathode terminals. An SCR is self commutating and current
stops flowing when it reaches the zero point crossing.
A soft starter has at least two SCRs per phase, connected in reverse-parallel configuration so that current can be
controlled in both directions. The soft starter can control one, two or all three phases.
There are two physical styles of SCR:
modular pack SCRs are a self contained reverse-parallel device. These are often found in low voltage soft
starters with a voltage range of 200 VAC to 690 VAC and a current rating less than 300 A.
disk or hockey puck style devices are a single SCR which needs to be electromechanically configured in
reverse-parallel configuration for soft starter use. This style of SCR is used on higher current rated, low
voltage soft starters with current ratings greater than 300A.
Medium voltage soft starters with an operating voltage range of 2.3kV to13.8kV always use disk style SCRs
connected in series for each half of a phase to obtain the necessary voltage rating.
Modular SCR Disk style ("hockey puck") SCR
Snubber circuits
Snubber circuits are used to suppress a phenomenon called notching which occurs at the zero voltage crossing point.
Snubber circuits provide SCR control stability and a level of overvoltage protection.
In the simplest form, a snubber is a resistor-capacitor network connected in parallel across each SCR. Resistors used
for this purpose are typically wire wound, for the necessary power rating. In medium voltage soft starters, grading
resistors are connected in a series-parallel configuration across all SCRs. This divides the voltage across SCR in each
phase evenly.
Basic LV snubber arrangement
C R
SCR
LV supply Motor
SCR
13489.A
R C
C R C R SCRs
RC snubber network
SCR SCR
Grading resistors
MV supply Motor
SCR SCR
2
R C R C
13490.A
Heatsinks
Heatsinks are designed to efficiently dissipate the heat generated by SCR switching during motor starting and
stopping. Optimum heatsink design maximises the rating of the soft starter by keeping the SCR internal junction
temperature below 130°C.
SCRs are always bonded to a heatsink, using an appropriate thermal paste.
modular SCRs are bonded to an isolated heatsink arrangement.
for disk SCRs, the conducting faces of each SCR are compressed against a conducting heatsink face.
Many soft starters reduce the heatsink size by turning the SCRs off at the end of a start and bypassing the SCR
arrangement during motor running.
Fans
Fans are often used in conjunction with SCR/heatsink assemblies to increase the thermal rating of soft starters in
arduous conditions, eg:
applications requiring high start current and/or times (eg 450%FLC start current for 30 seconds)
applications with excessive starts per hour (eg >10 starts per hour)
installations with excessive operating ambient temperatures (eg 45-60°C)
Busbars
Busbars are used to connect the motor and the mains supply to the SCR power assembly. Busbars are sized
according to the soft starter's maximum current rating. For lower current rated soft starters, aluminium busbars are
common. Higher current applications use tinned copper busbars to minimise the cross sectional area.
There are various methods for connecting conductors to busbars. Low current terminations may use small cage
clamps. High current terminations may use large spreader plates.
To ensure a good electrical connection when clamping together two conducting faces:
clean all conducting surfaces so they are free from oil, grease and other contaminants. Use an appropriate
industrial solvent for best results.
lightly buff the mating surfaces of busbars, spreader plates, cable lugs, etc, then remove any leftover residue
apply an approved electrical jointing compound to all mating surfaces
use the correct type and size of fasteners and tighten to the specified torque
insulate bare exposed electrical joints according to local electrical regulations
Current sensors
Soft starters which control motor start current or provide a motor protection function will have some form of
current sensing on the controlled phases. If only two phases are monitored, the current in the third phase is normally
surmised using vector calculation.
Current transformers are widely used, but other forms of current sensing are becoming mode widely used.
PCBs
Compact printed circuit boards are used to mount all the necessary electronic firmware, such as:
digital microprocessors for I/O function, SCR firing control, motor protection function, communications,
etc
SCR firing circuits
current sensing input circuits (necessary for certain soft starter types)
metering circuits
user interface
digital and analog input and output circuits
terminals for customer interfacing
communication port options
Some soft starter manufacturers have protective conformal coating as an option. Conformal coating protects PCBs
from moisture and general dust and grime. In aggressive gaseous and chemical environments, the soft starter should
be installed in a suitable, totally sealed enclosure.
The soft starter monitors the motor's performance during each start, to improve control for future soft starts. The
best profile will depend on the exact details of each application. If you have particular operational requirements,
discuss details of your application with your local supplier.
4
100%
Adaptive start profile:
90%
80% Early acceleration
70%
Constant acceleration
60% 1
50% Late acceleration
Motor speed
40% 2
30%
Start time
20%
3
04827.C
10%
0
4
100%
Adaptive stop profile:
90%
80% Early deceleration
70% Constant deceleration
60% 1 2 3
50% Late deceleration
Motor speed
40%
Stop ramp time
30%
20% 04835.C
10%
0
Inputs/Outputs
Digital and analog inputs with fixed or programmable functions
Relay or analog outputs with fixed or programmable functions
PT100 or thermistor inputs with adjustable set points
Communication ports for remote control and status monitoring
Protections
Protection ANSI protection code
Under/ Overvoltage 27 / 59
Mains frequency 81
Phase sequence 46
Phase loss 46
Motor overload (electronic thermal model) 49 / 51
Time-overcurrent (I2t) 51
Instantaneous overcurrent (shearpin or locked rotor) 50
Ground fault 50G
Undercurrent 37
Current imbalance 46 / 60
SCR temperature 26
SCR shorted 3
Motor thermistor 26 / 49
PT100 26 / 49
Excess start time (stall at start) 48
Excess starts per hour 66
Power loss 32
Auxiliary input trips 86 / 97
Battery/clock failure 3
For additional information, refer to ANSI protection codes.
KM1
Q1
or
12996.A
Feature List
Starting Comprehensive feedback
Constant current Starter status LEDs
Current ramp Date and time stamped event logging
Stopping Operational counters (starts, hours-run, kWh)
Coast to stop Performance monitoring (current, voltage, power
Soft stop factor, kWh)
Protection User-programmable monitoring screen
Under/ Overvoltage Multi-level password protection
Mains frequency Emergency stop push button
Phase sequence Power Connection
Shorted SCR 50 A to 600 A, nominal
Motor overload (thermal model) 2300 VAC to 7200 VAC
Instantaneous overcurrent (two stages) Accessories (optional)
Time-overcurrent DeviceNet, Modbus or Profibus communication
Ground fault interfaces
Undercurrent Synchronous motor control
Current imbalance PC Software
Motor thermistor Overvoltage protection
Excess start time Control supply transformer
Power circuit MV/LV Control transformer
Auxiliary trip
Extensive input and output options
Remote control inputs
(3 x fixed, 2 x programmable)
Relay outputs
(3 x fixed, 3 x programmable)
Analog output
(1 x programmable)
Serial port (with module)
Key Features
MVS soft starters offer several special functions to ensure ease of use and to provide optimal motor control in all
environments and applications.
Customisable Protection
The MVS offers comprehensive protection to ensure safe operation of the motor and soft starter. The protection
characteristics can be customised extensively to match the exact requirements of the installation.
Advanced Thermal Modelling
Intelligent thermal modelling allows the soft starter to predict whether the motor can successfully complete a start.
The MVS uses information from previous starts to calculate the motor's available thermal capacity, and will only
permit a start which is predicted to succeed.
Comprehensive Event and Trip Logging
The MVS has a 99-place event log to record information on soft starter operation. A separate trip log stores
detailed information about the last eight trips.
Informative Feedback Screens
A digital display screen allows the MVS to display important information clearly. Comprehensive metering
information, details of starter status and last start performance allow easy monitoring of the starter's performance at
all times.
Dual Parameter Set
The MVS can be programmed with two separate sets of operating parameters. This allows the soft starter to
control the motor in two different starting and stopping configurations.
The secondary motor settings are ideal for conventional (squirrel-cage) motors which may start in two different
conditions (such as loaded and unloaded conveyors).
NOTE
MVS soft starters are not suitable for controlling two separate motors. The secondary parameter set
should only be used for a secondary configuration of the primary motor.
The MVS will use the secondary motor settings to control a start when instructed via a programmable input.
Fibre Optics
The MVS uses two-line fibre optic connections between the low voltage control module and the high voltage power
assembly for electrical isolation. This fibre optic link simplifies installation of chassis mount MVS starters into custom
panels.
MVS Power Assembly
The MVS power assembly is a very robust and compact design, minimising panel space requirements. The unique
draw-out design simplifies general maintenance and servicing.
MVS power assembly
Phase arms extend via built-in runner,
including balance resistors, snubbers and
gate drive.
Small footprint and depth saves space.
Conformal coating on all PCBs for
protection in environments up to Pollution
Degree 3.
Current measured on all three phases.
Bypass terminals retain motor protection.
Convenient earth points.
EMC Emission
Equipment Class (EMC) ..................................................................................................................................................................... Class A
Conducted Radio Frequency Emission .................................................................... 10 kHz to 150 kHz: < 120 - 69 dB µV
0.15 MHz to 0.5 MHz: < 79 dB µV
0.5 MHz to 30 MHz: < 73 dB µV
Radiated Radio Frequency Emission .................................................................... 0.15 MHz to 30 MHz: < 80-50 dB µV/m
30 MHz to 100 MHz: < 60-54 dB µV/m
100 MHz to 2000 MHz: < 54 dB µV/m
This product has been designed as Class A equipment. Use of this product in domestic environments may cause
radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic Discharge ............................................................................................... 6 kV contact discharge, 8 kV air discharge
Radio Frequency Electromagnetic Field .................................................................................. 80 MHz to 1000 MHz: 10 V/m
Fast Transients 5/50 ns (main and control circuits) ....................................................... 2 kV line to earth, 1 kV line to line
Surges 1.2/50 µs (main and control circuits) ................................................................. 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption (safe shutdown) ........................................ 5000 ms (at 0% nominal voltage)
Standards Approvals
C .................................................................................................................................................................................. EMC requirements
CE ...................................................................................................................................................................................... EMC EU Directive
1
Short circuit current, with appropriate R rated fuses fitted.
2
Excludes contactors and/or circuit breakers.
2
A2 A3
A1 C73
3
+10
110-130 VAC A2 C74 K2
-15
33
34
A11 A12 TX RX
(Wh) (Bk)
(Bk) (Wh)
A11 A12 RX TX
C23 43
C24 44
C31 54
C32 52
C41 51
C42 64
62
C53
5 61
C54
C63
C64
B4 B10
+
B5 B11
-
A4
03223.F
A5
NOTE
Fibre-optic cables are only supplied in IP00 variants of the MVX soft starter. In all other MVX soft
starters, this is part of the main assembly.
Feature List
Starting Comprehensive feedback
Constant current Digital display with multi-language support
Current ramp Controller buttons for quick access to common tasks
Stopping Starter status LEDs
Coast to stop Date and time stamped event logging
Soft stop Operational counters (starts, hours-run, kWh)
Protection Performance monitoring (current, voltage, power factor,
Under/ Overvoltage kWh)
Mains frequency User-programmable monitoring screen
Phase sequence Multi-level password protection
Shorted SCR Emergency stop
Motor overload (thermal model) Power Connection
Instantaneous overcurrent 15 A to 800 A, nominal
Time-overcurrent 2200 VAC to 11000 VAC
Ground fault Accessories (optional)
Undercurrent DeviceNet, Modbus, Profibus or USB communication
Current imbalance interfaces
Motor thermistor PC Software
Excess start time RTD relay
Power circuit Motor Protection Relay
Auxiliary trip Predictive Maintenance Module (PMM)
Extensive input and output options
Remote control inputs
(3 x fixed, 2 x programmable)
Relay outputs
(3 x fixed, 3 x programmable)
Analog output
(1 x programmable)
Serial port
Key features
MVX soft starters offer several special functions to ensure ease of use and to provide optimal motor control in all
environments and applications.
Customisable Protection
The MVX offers comprehensive protection to ensure safe operation of the motor and soft starter. The protection
characteristics can be customised extensively to match the exact requirements of the installation.
Advanced Thermal Modelling
Intelligent thermal modelling allows the soft starter to predict whether the motor can successfully complete a start.
The MVX uses information from previous starts to calculate the motor's available thermal capacity, and will only
permit a start which is predicted to succeed.
Comprehensive Event and Trip Logging
The MVX has a 99-place event log to record information on soft starter operation. A separate trip log stores
detailed information about the last eight trips.
Informative Feedback Screens
A digital display screen allows the MVX to display important information clearly. Comprehensive metering
information, details of starter status and last start performance allow easy monitoring of the starter's performance at
all times.
Dual Parameter Set
The MVX can be programmed with two separate sets of operating parameters. This allows the soft starter to
control the motor in two different starting and stopping configurations.
The secondary motor settings (parameter groups 9 and 10) are ideal for dual speed motors or conventional
(squirrel-cage) motors which may start in two different conditions (such as loaded and unloaded conveyors).
The MVX will use the secondary motor settings to control a start when instructed via a programmable input (refer
to parameters 6A and 6F Input A or B Function).
Fibre Optics
The MVX uses two-line fibre optic connections (per phase) between the low voltage control module and the high
voltage phase cassette for electrical isolation. This fibre optic link simplifies installation of chassis mount MVX starters
into custom panels.
MVX Phase Cassette
The MVX phase cassette is a robust and extremely compact design, for easy integration into a panel enclosure. The
unique draw-out design simplifies general maintenance and servicing.
A service lifting trolley is supplied with each MVX panel or phase cassette, for easy installation and removal.
K1 A1
CT1-3 T1
L1 T1
T2
L2 T2 M
3
L3 T3 T3
U1 Q3
A3
2 3
3
11082.B
A1 Phase cassette L1-L3 Input power terminals (supply side)
1 3 Phase 50/60 Hz Supply 2 Motor
K1 Main contactor (fused/ withdrawable) Q3 Earth switch
K2 Bypass contactor (fixed) T1-T3 Output power terminals (motor side)
CT1-3 Current transformers (x3) A3 Power interface PCB
U1 Metal oxide varistors (MOVs) 3 Current transformer inputs
Q1 A1
CT1-3 T1
L1 T1
T2
L2 T2 M
3
L3 T3 T3
2
U1
Q3
A3
4 1
2 3
3
11083.B
Enclosures
MVX soft starters can be installed easily into standard enclosures to provide a complete motor control cabinet.
The compact size of the power assembly leaves room for auxiliary equipment to be installed.
The phase cassette should be mounted at the bottom of the enclosure, and the Controller can be mounted on the
front panel. The diagrams below illustrate a possible configuration for installation.
2 5
1 6
3
7
8
4
11081.C
9
Modbus Interface
MVS and MVX soft starters can operate as slaves on a Modbus network via a Modbus Interface.
Soft starter
1 2 Modbus interface
-
B1 RS485 connection onto a Modbus RTU
network
GND
B2 3
13013.A
+
B3
Soft starter
1 2 Profibus interface
DeviceNet Interface
MVS and MVX soft starters can connect to a DeviceNet network using the DeviceNet Interface.
Soft starter
DeviceNet Interface
1 2
RD
(V+) Standard 5-wire connection onto a
WH
(CAN-H) DeviceNet network 120 termination
(SHIELD) resistors are required at each end of the
3
BU
(CAN-L) network cable
13016.A
(V-)
BK
Ethernet options
Industrial plant automation is rapidly moving towards Ethernet based protocols. Ethernet is a real-time, high speed
technology which provides a seamless and unified system linking information from the factory and plant floors
through to the corporate environment. A major advantage of Ethernet based protocols is their accessibility via the
internet.
Industrial Ethernet protocols use the Open Systems Interconnection (OSI) model developed by the International
Standards Organisation (ISO). The standard protocol stack consists of 7 layers, covering the protocol requirements
of all industrial automation systems.
Presentation Layer
Session Layer
Transport Layer
Network Layer
Physical Layer
In basic terms, industrial Ethernet protocols use a common industrial protocol at the application layer (eg Modbus
RTU, Profibus DP or DeviceNet)). This is encapsulated within TCP/IP protocol headers (layers 4 and 3) for
transport over a physical Ethernet network (via layers 2 and 1).
AuCom is developing Ethernet based communication options for use with its medium voltage soft starter products.
These options will be certified to the relevant IEC, ODVA and Profibus international standards.
Modbus TCP (Modbus RTU over Ethernet)
ProfiNet (Profibus DP over Ethernet)
Ethernet/IP (DeviceNet over Ethernet)
Switchgear Requirements
MVS Panel Options
The MVS soft starter is suitable for operating voltages between 2.3 kV ~ 7.2 kV and currents 600 A, and can be
supplied in switchgear panels.
In all MVS panel options, the following LV equipment is standard and is mounted on the LV compartment door:
Controller
emergency stop pushbutton
soft starter reset pushbutton
E3 panel
E3 panel schematic (for use with MV motor 2.3 kV~7.2 kV, 80 A ~ 600 A)
A1 Soft starter power assembly
Q1 Incoming isolator/earth switch
Q1 F1-3 R-rated line fuses
K1 Main contactor
F1-3 K2 Bypass contactor
K1
A1
K2
3
13513.A
E2 panel
E2 panel schematic (for use with MV motor 2.3 kV~7.2 kV, 80 A ~ 600 A)
A1 Soft starter power assembly
K1 Main contactor
K2 Bypass contactor
Short-circuit line protection is provided externally using R-rated fuses or an MV circuit breaker.
1
6 1 Main isolator/earth switch (Q1)
2 R-rated protection fuses (F1-3)
3 Main contactor (K1)
2
4 Bypass contactor (K2)
3 7 5 Power assembly (A1)
4
6 Input terminals (L1, L2, L3)
7 Rear cable compartment
8
5 8 Output terminals (T11, T2, T3)
14078.B
Front view Side view
STO P
3
INPU T B
Exit Menu
Store
13572.B
A1 K2
Q3
13519.A
2
M
U1
A1 Q2
Q3
13520.A
2
M
2 5
1 6
3
7
8
4
11081.C
9
1 Reset pushbutton
1 2
2 Emergency stop pushbutton
START
3 Controller
STOP
RESET
INPUT A
INPUT B
Exit Menu
3
Store
F1 Alt F2
Lo g s To o ls
1 Overpressure flap
2 Bushing
3 Busbar system
4 Fixed contact insulator
5 Shutter
6 Current transformer
7 Earth switch
8 Enclosure
9 Low voltage compartment
10 Circuit breaker compartment
11 Vacuum circuit breaker
12 Door lock
13 Door handle
14 Inspection window
15 Cable compartment
1
Q1
2
F1-3
3
K1 4
A1 5
K2
3
13513.A
13521.A
M
Motor cable (top or bottom exit)
Main isolator/earth switch
R-rated fuses
Main contactor
Bypass contactor
Power assembly
Typical MCC panel line-up
M1 M2
Customer-specific requirements
Additional equipment can be designed and integrated into AuCom MVS and MVX panel solutions, depending on
the customer's specific needs.
In some cases, extra switchgear panels matching the soft starter panels may be required in order to house the extra
equipment.
Motor protection relay (in addition to soft starter motor protection)
RTD (PT100) temperature protection relay
Insulation monitoring relay
Predictive Maintenance Module (PMM)
Metering relay
PLCs, auto changeover contactors, PFC controllers etc
Inverters and switch mode power supplies
Low voltage control equipment (eg indicators, switches, pushbuttons)
LV section panel light
Panel anti-condensation heaters
Motor heater circuit
MV/LV control supply transformer
Voltage transformer (1 or 3 phase)
Extra CTs for protection or metering
LV control transformer
Power factor correction (requires dedicated panel to install capacitor banks and associated switchgear)
Starter current rating: The full load current rating of the soft starter given the parameters detailed in the remaining
sections of the utilisation code.
Start current: The maximum available start current.
Start time: The maximum allowable start time.
On-load duty cycle: The maximum percentage of each operating cycle that the soft starter can operate.
Starts per hour: The maximum allowable number of starts per hour.
4 Start current
2 5 6 Start time
350% On-load time
Current
7 Off time
Nominal motor current
3
Time
Duty cycle = Start time + Run time
Start time + Run time + Off time
Starter current rating: The full load current rating of the soft starter given the parameters detailed in the remaining
sections of the utilisation code.
Start current: The maximum available start current.
Start time: The maximum allowable start time.
Off time: The minimum allowable time between the end of one start and the beginning of the next start.
2 3 Start current
350% Start time
Off time. This includes time while the
Current
Time
NOTE
AuCom MVS and MVX soft starters are AC53b rated and must always be used with a bypass contactor
or circuit breaker.
3.6 Calculations
What is the minimum start current with a soft starter?
Soft starters can limit start current to any desired level. However, the minimum level of start current for a successful
start depends on the motor and load.
To start successfully, the motor must produce more acceleration torque than the load requires, throughout the start.
Reducing the start current also reduces the torque produced by the motor. The start current can only be lowered
to the point where the torque output remains just greater than the load torque requirement.
The likely start current can be estimated from experience, but more precise predictions require analysis of motor
and load speed/torque curves.
400
3 Torque output at current limit
300 100
5 Acceleration torque
200 4
Load torque
100 6
09677.B
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed (%full speed)
400
3 5 Torque output at current limit
300 100
4 Acceleration torque
200
7 Load torque
100
09678.B
6
Stall
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Speed (%full speed)
Calculating required start current for new or existing AC induction motor installations
A number of methods are available to estimate the level of start current a particular machine will require. These
methods range from generalisations producing approximations, through to advanced calculations which yield precise
predictions.
Calculation
Calculations use percentages of full load torque and full load current.
Minimum required start current
Where:
ISTR = minimum required start current (% motor FLC)
ISTR = LRC × TSTR LRC = Motor locked rotor current (% motor FLC)
LRT
TSTR = Minimum required start torque to accelerate machine from
standstill (% motor FLT)
LRT = Motor locked rotor torque (% motor FLT)
Example
A 1100 kW / 3.3 kV motor has a full load current of 235 A and a locked rotor current of 500% FLC. The motor
is required to start a pump with a minimum start current of 15% motor FLT. The motor's locked rotor torque is
150% FLT.
15% FLT
I STR = 500% FLC × 150%FLT
= 500 × 0.316
= 158% FLC
158
= ×235 A
100
= 371 A
300
Torque (%FLT)
Current (%FLC)
(n%) ( Imn % ) ( Tmn % ) ( TIn % ) 500
13632.A
95% 425 160 34.0 Motor speed (%)
100% 100 100 37.0
Torque (%FLT)
500 250
Current (%FLC)
13633.A
95% 350 109 34.0 75 Motor speed (%)
100% 100 100 37.0 0
4.0 x FLC 4.5 x FLC 5.0 x FLC 5.5 x FLC 6.0 X FLC
(n%) (% FLT) (secs) (% FLT) (secs) (% FLT) (secs) (% FLT) (secs) (% FLT) (secs)
0-10%16.4 0.77 24.1 0.52 32.7 0.39 42.0 0.30 42.0 0.30
10% - 20% 23.2 0.55 30.8 0.41 39.3 0.32 48.0 0.26 48.0 0.26
20% - 30% 24.8 0.51 32.4 0.39 40.9 0.31 49.0 0.26 49.0 0.26
30% - 40% 23.2 0.54 31.1 0.41 40.0 0.32 47.5 0.27 47.5 0.27
40% - 50% 22.7 0.56 31.1 0.41 40.6 0.31 47.5 0.27 47.5 0.27
50% - 60% 22.2 0.57 31.2 0.40 41.4 0.31 47.5 0.27 47.5 0.27
60% - 70% 21.2 0.60 31.2 0.40 42.4 0.30 47.5 0.27 47.5 0.27
13634.A
70% - 80% 23.6 0.53 35.5 0.36 48.7 0.26 51.0 0.25 51.0 0.25
80% - 90% 37.1 0.34 54.0 0.23 67.0 0.19 67.0 0.19 67.0 0.19
90% - 100% 65.9 0.19 80.2 0.16 83.0 0.15 83.0 0.15 83.0 0.15
5 secs 4 secs 3 secs 2 secs 2 secs
IM
2
I
TSTR = TM × STR
IM ISTR
TM
Where:
TSTR = revised motor torque TSTR
TM = motor torque level at full voltage start
13532.A
ISTR = motor start current limit level
IM = motor current level at full voltage start
Speed (%full speed)
Example
At 50% motor speed, calculate the revised motor torque for a start current limit of 400% FLC, a DOL current level
of 600% FLC and a DOL motor torque level of 120% FLT.
2
400
TSTR = 120×
600
= 53% FLT
Where:
tacel = time to accelerate from one speed to another (seconds)
JT = total inertia of the motor rotor and load, coupled together n1 n2
(kg·m2). To convert GD2 to kg·m2, divide by 4. Tav
n = speed difference from n1 to n2 (rpm)
13533.A
Example
Calculate the acceleration time of a 2000 kW motor driving a pump load from 40% to 50% full speed. The full
load speed is 2990 rpm. Average acceleration torque from 40% to 50% full speed is 20% motor FLT. The motor
shaft inertia is 60 kg·m2 and the pump inertia is 12 kg·m2.
Total inertia is motor plus load inertia:
JT = 60 + 12 kgm2
= 72 kgm2
Speed difference is 10% of full load speed:
n = n2 n1 × full load speed
= 50% 40% × 2990 rpm
= 299 rpm
Average acceleration torque is 20% of motor FLT.
kW × 9550
FLT =
n
2000 × 9550
=
2990
= 6388 Nm
20
Tav = 6388×
100
= 1278 Nm
Calculate the acceleration time from 40% to 50% full load speed:
JT × n
t acel =
9.55 × Tav
72kgm2 × 299 rpm
=
9.55 × 1278 Nm
21528
=
12205
= 1.76 sec
Typical AuCom medium voltage switchgear arrangement for a single forward-reverse motor starting system
(10 kV~13.8 kV) with MVX soft starter.
For clarity, current transformers and motor protection relays are not shown.
Q1 Q2 Q10
SST
L1
L2
L3 Q20
T1
T2
T3
Q3 Q30
13529.A
1
M1 3M
Operating Sequence
NOTE
The phase sequence of the incoming mains supply and the motor winding connections must be
verified for correct motor rotation.
NOTE
The motor must be stopped before changing its operating direction. There is always a short time
delay built into the selected changeover of the phase rotation. This is typically less than 3 seconds
which is enough time to allow motor flux and thus any back EMF in the motor to decay. The soft
starter SST can use the coast-to-stop or soft stop method.
Multi-motor starting
This standard method of starting several medium voltage motors is often found in the water and mining industries.
Most multi-start control systems have 2 ~ 4 motors of the same kW size.
Each motor is started and stopped from the output of an electronic motor starter. The starter is usually a soft
starter (SST), providing the utility system has the capacity to supply the maximum required current, without any
significant disturbance. A guideline for maximum required current is [4+(n-1]) x motor FLC, where n = total number
of motors in the system. If supply capacity is limited, a variable frequency drive (VFD) may be used instead of a soft
starter.
Once a motor has reached full running speed, it is fed directly from an input bus. In this mode of operation, some
form of motor protection is required for each motor.
A master controller is required to control and supervise the entire multi-start system. This can be a PLC or an
integrated part of the starter.
There are typically two modes of operation.
In Auto mode, the start and stop sequence can be preselected and the master controller handles the entire
switching procedure.
In Manual mode, the starter is disabled and DOL control of each motor is provided by manual switching of
each motor bypass circuit breaker or contactor.
The entire system relies on critical time switching of circuit breakers or contactors, which are usually fixed switching
devices. Withdrawable switching devices are often used on the starter input and output to provide physical
isolation. This allows the starter's input and output to be isolated for servicing, in the event of a fault.
NOTE
The following example shows a typical configuration. There are many different control methods
available for multi-motor starting systems.
A2
1
A1
Q1
Q2 2
Q10A
M1
M
3
Q10B
Q20A
M2
M
3
Q20B
Q30A
M3
M
3
Q30B
13530.A
NOTE
In this example, the master controller (A2) has been preselected to start the motors in order 1,2,3 then
stop them in the reverse order.
NOTE
In this example, the electronic motor starter (A1) is not used to control any motor starting or stopping.
The main input circuit breaker Q1 and main output circuit breaker Q2 remain open
Each motor is manually started in any order. This is usually via a start pushbutton for each motor, which is
directly fed into an input of the master controller (A2).
Each motor is started direct-on-line and fed from the main input bus via the motor's bypass circuit breaker
(Q10B, Q20B, Q30B). Motor protection is provided in this circuit, via a set of current transformers and a
dedicated motor protection relay for each motor.
Each motor is manually stopped in any order. This is usually via a stop pushbutton for each motor, which
is directly fed into an input of the master controller A2. Only a motor freewheel stop is available.
Key features
User interface touch screen
Selectable control options for individual motors
Selectable command source options for individual motors
Motor protection for individual motors
Robust safety interlocking system
Comprehensive panel indication and bus mimicking
SOFT STOP
C B STOP
B = Breaker Line
C = Contactor Contactor
13869.A
13870.A
MIMIC screens emulate switchgear, soft starter and M-1 to M-8 screens select the command source for
motor status motor starting and stopping, and select between DOL or
soft start for each motor (separate screen per motor)
From From From
MC3 MC2 MC1
Line M1_START/STOP ENABLE
6 kV
START
BP3 BP2 BP1 OFF OFF ENABLE
LOCAL REMOTE
Q3 Q2 Q1
STOP
OFF OFF ENABLE
SOFT
DOL START
M3 M3 M2 M2 M1 M1
13868.A
13867.A
Typical slip-ring motor starting system using a soft starter for control
SST
R1 M1 K1
T1 L1
M 1
3 T2 L2
T3 L3
K3 K2
13531.A
Operating sequence
NOTE
The rotor resistance must be engineered to provide the necessary acceleration torque during motor
starting. This example assumes a soft starter which offers a dedicated slip-ring motor control function
(eg AuCom MVS or MVX).
V1
V2
03986.C
S1 S2 S3 S4
P1 P2 P3
1 Sub-states 3 States
t1 Main contactor close time S1 Ready
t2 Rotor resistance contactor close time S2 Pre-start tests
t3 Bypass contactor close time S3 Starting
2 Output voltage S4 Running
V1 100% voltage 4 Phases of operation
V2 Slip-ring retard voltage P1 Start command
P2 Rotor resistance current ramp
P3 Shorted rotor current ramp
Rotor resistance sizing
When using a soft starter for slip-ring motor starting, a single stage, three phase resistance bank must be used.
For an existing installation with a multi-stage resistance bank, the existing final stage resistance can normally be used.
To specify a new single-stage resistance bank, use the following guideline:
Slip-ring rotor resistance sizing formula:
Where:
Ur Rp = rotor resistance per phase ()
Rp = 0.2×
3×Ir Ur = open circuit rotor voltage (V)
P
Pp = 0.2× m
Ir = rotor current (A)
3 Pp = power rating of rotor resistance per phase (kW)
Pm = motor shaft power (kW)
Slip-ring synchronous motors
Although they are rare, there are some older synchronous motors which use a special double winding rotor. One
winding set is used for standard slip-ring rotor starting. The other winding set is a DC excitation winding used for
synchronous speed running.
These motors can be started using a soft starter with final stage resistance, but the control system must include a
synchronisation package. This package is supplied separately to the soft starter and must be integrated into the entire
system. This control method becomes complex and expensive and in most cases an upgrade will involve a complete
replacement of the synchronous motor for a standard squirrel cage induction motor.
NOTE
This information is an overview of the most common conformance standards used in the medium
voltage industry. For specific equipment conformance, always refer to the technical data supplied by the
manufacturer.
Item Title Standard
Switchgear and apparatus High Voltage switchgear & control gear – Part 1: Common IEC62271-1
Specifications
High Voltage switchgear & control gear – Part 200: AC metal IEC62271-200
enclosed switchgear and control gear for rated voltages from
1 kV to 52 kV
High-voltage switchgear and controlgear - Part 304: Design IEC62271-304
classes for indoor enclosed switchgear and controlgear for
rated voltages above 1 kV up to and including 52 kV to be used
in severe climatic conditions
AC metal enclosed switchgear (Chinese standard) GB3906 (2006)
AC Metal-enclosed Switchgear and Control Equipment for DL-T-404
rated voltage from 1 kV to 52 kV (Chinese standard)
General Technology Requirements of High-voltage DL-T-593
Switchgear and Control Equipment. (Chinese standard)
IEEE Standard for Metal-Clad Switchgear IEEE C37.20.2
Internal arc resistance High Voltage switchgear & control gear – Part 200: AC metal IEC62271-200
enclosed switchgear and control gear for rated voltages from Annex A.6, criteria 1 to
1 kV to 52 kV 5
IEEE Guide for Testing Medium-Voltage Metal-Enclosed IEEE C37.20.7 (NEC)
Switchgear for Internal Arcing Faults
Insulation Insulation coordination – Part 1: Definitions, principles and IEC60071-1
rules
Insulation coordination – Part 1: Application guide IEC60071-2
Evaluation and qualification of electrical insulation systems IEC60505
Insulation coordination for equipment within low-voltage IEC60664-1
systems - Part 1: Principles, requirements and tests
Dry, solid insulating materials - Resistance test to high-voltage, IEC61621
low-current arc discharges
Degrees of protection Degrees of protection provided by enclosures (IP ratings & IEC60529
tests)
Classification of groups of Storage IEC60721-3-1
environmental
parameters and their
severities
Transportation IEC60721-3-2
IEC60068-2-32
Stationary use at weather protected locations IEC60721-3-3
Safety UL (2.3kV, 4.2kV and 13.8kV only) UL347B
4 Switchgear
This section provides information and guidance on the design of metal-enclosed medium voltage switchgear panels
and associated switchgear apparatus. If further information is required, refer to the appropriate international
standards or contact your local AuCom representative.
AuCom offers MVS and MVX soft starters in their own unique panel styles. We also offer a range of
metal-enclosed switchgear panels rated up to 36 kV and 2500 A, covering all standard industrial configurations:
Incomer feeder panel
Direct incomer panel
Bus coupler panel
Bus riser panel
Metering panel
Direct-on-line motor starting panel
Power factor correction panel
Transition (termination) panel
Metal-enclosed, medium voltage switchgear panels and associated apparatus, rated from 1 kV to 52 kV, are covered
by IEC 62271-200 (this standard supersedes IEC 60298). Panel design and construction is determined by several
key operating factors and classifications:
Rated voltage Ur (kV)
Determines the minimum insulation level requirements
Rated current Ir (A)
Rated frequency fr (Hz)
Short circuit power SSC (MVA)
Determines elements of mechanical panel design and selection of integrated switchgear apparatus
Accessibility to panel compartments
Continuation of service with main compartment open
Necessary isolation and segregation of live parts
Level of internal arc withstand
Panel compartments
4
1
1 Busbar compartment
2 Cable compartment
3 3 Switching compartment
4 Low voltage compartment
2
11158.A
Busbar Compartment
The busbar compartment houses the main busbar system, which is connected to the fixed upper isolating contacts
of the main switchgear apparatus by means of branch connections. The main busbars are made of high conductivity
copper. The busbar compartment of each panel is isolated from the busbar compartments of the neighbouring
compartments.
Single or double busbar configuration is used depending on the current rating.
Cable Compartment
The cable compartment houses some of the following components:
Branch connections
Earthing busbar
Earth switch
Power cables
Surge arrestors
Instrument transformers (current transformers, voltage transformers)
Switching Compartment
The switching compartment houses the bushing insulators containing fixed contacts for the connection of the
switching apparatus to the busbar and cable compartment. The bushings are single-pole type and are made of cast
resin. They are covered by metallic shutters.
The metallic shutters operate automatically during movement of the switching apparatus from the test position
(racked-out) to the service position (racked-in) and vice versa. Shutters may be locked if required.
The position of the switching apparatus can be seen from the front of the panel through an inspection window.
ANSI-defined switchgear
ANSI defined switchgear is equivalent to IEC classification LSC2B-PM, with the following characteristics:
the main switching device is withdrawable, with disconnecting auxiliary control circuits
separate compartments are provided for voltage transformers and control power transformers
busbar compartments are divided between adjacent enclosures
metal barriers isolate the withdrawable compartment, when the main switching device is drawn-out into
test position
main circuit busbars and connections are covered with fire resistant insulating material
mechanical interlocking prevents stored energy discharge of withdrawable parts
a locking method prevents the withdrawable switching device from being moved into service position
low voltage control parts are segregated from medium voltage apparatus
all voltage transformers must have primary circuit current limiting fuses
Switchgear Ratings
Switchgear is rated according to IEC 62271-1. When choosing switchgear, its rating must be sufficient for the
electrical characteristics at the point of installation, the environmental conditions it needs to operate under, and the
safety requirements. Future expansion of the switchgear distribution system needs to be considered, as this may
affect initial rating requirements.
Switchgear selection is determined by considerations including:
Electrical conditions
System operating voltage (U)
System operating frequency (f)
Nominal operating current (I)
Short circuit current levels at point of installation (ISC, Idyn, etc)
Horizontal busbar arrangement
Environmental conditions
Ambient temperature
Altitude
Pollution degree
Indoor or outdoor installation
Personnel safety considerations
Internal Arc Classification (IAC)
Interlocking of access areas and switchgear apparatus
Access method (eg tools, keys, process, etc)
Withdrawable switchgear apparatus
Switchgear information for enquiries or ordering
When enquiring about, or ordering switchgear, the supplier should at minimum provide the following information.
When enquiring, advise the supplier of any unusual operating condition requirements (eg altitude 1800 metres).
System characteristics
nominal system voltage and frequency
expected highest voltage
type of neutral earthing system
Service conditions
any non-standard service requirements which differ from normal routine
Installation specifics
indoor or outdoor installation
number of phases
busbar arrangement details
rated voltage (Ur)
rated frequency (fr)
Switchgear derating
Switchgear must be derated for altitudes exceeding 1000 metres and ambient temperatures exceeding 40 °C.
Insulation derating according to altitude
The relevant standards specify the derating required for equipment installed at an altitude greater than 1000 metres.
Guideline: derate by 1.25% U peak, per 100 metres above 1000 metres.
This applies for lightning impulse withstand voltage and for power frequency withstand voltage 50 Hz - 1 minute.
Derating for altitude only applies to air-insulated switchgear, not vacuum or SF6-insulated equipment.
Current derating
IEC 62271-1 defines the maximum permissible temperature rise for each device, material and dielectric medium,
using a reference ambient temperature of 40 °C.
The actual temperature rise is affected by:
the rated current
the ambient temperature
the cubicle type and its protection index (IP rating)
1
Derating coefficient k
0.9
0.8
0.7
0.6
13325.A
0.5
0 1000 2000 3000 4000 5000
Altitude (m)
AuCom provides an Incomer Feeder Panel as part of its L-Series switchgear range. This is rated at 12 kV
from 630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin
compartments, special locking door designs and top-exit arc flaps for pressure release.
11163.A
1
1 Circuit breaker (withdrawable)
2 Current transformer set
3 Earth switch
2
4 Voltage transformer (fused and
withdrawable)
3 4
11165.A
AuCom provides an Direct Incomer Panel as part of its L-Series switchgear range. This is rated at 12 kV
from 630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin
compartments, special locking door designs and top-exit arc flaps for pressure release.
11175.A
Front view Side view Rear view
2 3
11177.A
AuCom provides a Bus Coupler Panel as part of its L-Series switchgear range. This is rated at 12 kV from
630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin
compartments, special locking door designs and top-exit arc flaps for pressure release.
11166.A
Front view Side view Rear view
1
1 Circuit breaker
2 Current transformer set
2 3 Earth switch
3
11169.A
AuCom provides a Bus Riser Panel as part of its L-Series switchgear range. This is rated at 12 kV from
630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin
compartments, special locking door designs and top-exit arc flaps for pressure release.
11170.A
Front view Side view Rear view
1
11172.A
AuCom provides a Metering Panel as part of its L-Series switchgear range. This is rated at 12 kV from
630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin
compartments, special locking door designs and top-exit arc flaps for pressure release.
11173.A
Front view Side view Rear view
1 Earth switch
2 Voltage transformer (fused and
withdrawable)
1 2
11174.A
Busbar Systems
Overview
Medium voltage busbar systems consist of two general arrangements. The main switchgear distribution bus has
three busbar sets (one set per phase) which run horizontally through all the panels in a line-up. These distribution
busbars run through a dedicated chamber within each metal-enclosed panel. Segregation of busbar chambers,
between adjacent panels, is provided by using insulated through-bushings. Inside the horizontal busbar chamber of
each panel, a vertical feeder busbar system can be tapped off the main horizontal system, for incomer, feeder,
bus-coupler, bus-riser, metering or motor starter circuit.
11185.A
Ratings
The nominal current rating (Ir) of an incomer busbar system usually matches the rating of the main busbar system it
is feeding. Likewise, bus-coupler and bus-riser systems have the same current rating as the main busbar system they
are connecting. A feeder circuit busbar system has a nominal current rating to match the expected load.
The nominal current rating is determined by the cross sectional area, shape and configuration of the
individual phase bars.
The short-time withstand current rating (Ik) of the busbar system must be greater than the highest expected
symmetrical fault current at the point of installation. This rating is for a short-time withstand period of 1 or 3
seconds (tk). All busbar systems installed in the same switchgear line-up usually have the same short-time withstand
current/time rating.
The nominal voltage rating (Ur) of a busbar system must be greater than the installation's operating voltage. This
voltage rating determines the minimum phase-to-phase and phase-to-earth busbar clearances.
The nominal frequency rating (fr) of a busbar system must match the installation's operating frequency.
NOTE
The nominal current must be derated for high ambient temperatures (usually above 40 °C).
The nominal voltage and insulation ratings of a busbar system must be adjusted for altitudes over 1000
metres.
Design
Busbar system design must consider:
adequate minimum required clearance between phases and phase to earth
selection of adequate busbar insulator standoffs
bolting arrangements for continuous busbar connections
thermal effects on busbar and insulator standoffs under normal and fault conditions
electrodynamic forces applied to busbars and insulator standoffs under fault conditions
avoidance of mechanical resonance under normal operating and fault conditions
Voltage ratings and clearance
IEC 62271-1 gives typical voltage ratings for busbar systems and insulator standoffs.
Typical voltage ratings and minimum clearances for busbar systems and insulator standoffs
Rated voltage Power frequency withstand Lightning impulse withstand Clearance –
voltage voltage recommended
Ur (kV) Ud (kV) Up (kV) P-P and P-E (mm)
7.2 20 60 70~90
12 28 75 120
17.5 38 95 160
24 50 125 220
36 70 170 320
Source: derived from IEC 62271-1
Current ratings and dimensions
The nominal current rating of a busbar is determined by the type of material, shape and cross sectional area of the
bar and the maximum permissible temperature rise of the material. If the busbar is carrying AC current, the
operating frequency has a slight effect on the busbar rating due to magnetic skin effect.
A busbar system has a short-time withstand current rating. The temperature rise in the event of a short circuit
condition must not exceed the thermal limits of busbar standoffs.
Typical current ratings and nominal dimensions for medium voltage busbar systems
NOTE
Dimensions should be used as a guideline only and may vary.
The dimensions stated in this table are based on bare copper at ambient temperature of 40 °C,
maximum permissible temperature rise of 50 °C, operating at 50 Hz.
Rated current Bar dimensions - Rated short-time withstand Rated short-time withstand
per phase current 1 period 1
(A) W x D (mm) Ik (kA) tk (seconds)
630 50 x 6
1250 80 x 10
1600 100 x 10 12.5/16/20/25/31.5/40/50 0.5/1/2/3
2000 100 x 6 (2 bars)
2500 100 x 10 (2 bars)
3150 100 x 3 (3 bars)
Source: current rating information is derived from IEC 62271-1
1
Most medium voltage switchgear including busbar systems have short-time withstand ratings of 16 kA, 20 kA,
25 kA or 31.5 kA for 3 seconds.
Temperature rise
During short circuit conditions the busbar will rise in temperature, depending on the level of short circuit current and
time duration. This temperature rise must not exceed the thermal limits of any equipment in contact with the
busbar.
NOTE
When engaging parts with different coatings, or where one part is of bare material, the permissible
temperature and temperature rise shall be those of the surface material having the lowest permitted
value.
Electrodynamic withstand
During short circuit conditions, the peak current associated with the first loop of the fault current produces
electrodynamic forces which stress the busbar and insulator standoff supports. Stress on the busbars must not
exceed the limits of the material used. Bending forces must not exceed the mechanical limits of the insulator
standoffs.
Electrodynamic forces
Busbars (parallel) Support
Ip Ip F1
h = e2
F
F1 H
F1 l
13873.A
d
13678.A
Resonant frequency
The busbar system must be checked for potential resonance under normal operating conditions and fault conditions.
This is done by calculating the natural resonant frequency of the system, which must meet the following criteria:
50 Hz supply: not within the ranges 48 Hz to 52 Hz and 96 Hz to 104 Hz
60 Hz supply: not within the ranges 58 Hz to 62 Hz and 116 Hz to 124 Hz
Calculation requirements
Busbar systems are subjected to thermal and electrodynamic stresses under normal operating conditions, but more
so under short circuit fault conditions. It is important to ensure the busbar system will function safely under all
known conditions. When checking the design, the most important considerations are the nominal operating
current, expected fault current at the point of installation, average ambient temperature and the altitude of the
installation.
To check the safety of a busbar system:
Check that the current rating of the busbar system (Ir) exceeds the expected nominal current. Main
factors affecting the busbar rating are busbar material and configuration, ambient temperature and
maximum permissible temperature rise.
Check the maximum expected temperature rise of the busbar during a short circuit fault. In the event of
short circuit current flow (Ith), the surface temperature of a busbar must not exceed the thermal limits of
any material coming in contact with it (ie insulator standoffs).
Check the maximum expected electrodynamic forces imparted on the busbars and insulator standoffs, due
to the peak short circuit fault current (Idyn). Do not exceed the mechanical limitations of the material.
Check that the busbar system will not resonate under normal operating and fault conditions.
Refer to Busbar Calculations on page 149 for calculation details and examples.
A Incomer panel
TXR_L TXR_R
B Left bus
C Right bus
D Feeder panel
Interlock scheme 1 (typical)
Interlock scheme 2 (typical)
A A
Interlock scheme 3 (typical)
E-IL E-IR
Q-IL Circuit breaker - left incomer
E-IL Earth switch - left incomer
2 2
TXR_L Supply transformer - left bus
Q-IL 1 Q-IR
Q-IR Circuit breaker - right incomer
E-IR Earth switch - right incomer
(LOCK) (LOCK) TXR_R Supply transformer - right bus
(KEY) (KEY) Q-BC Circuit breaker - bus coupler
Q-BC
B C Q-FL Circuit breaker - left feeder
E-FL Earth switch - left feeder
(LOCK)
Q-FR Circuit breaker - right feeder
Q-FL 3 Q-FR 3 E-FR Earth switch - right feeder
E_FL E_FR
13679.A
D D
100 300
13707.A
Locations, causes and examples of measures to decrease the probability of internal faults
Locations where internal Possible causes of internal Examples of possible preventive measures
faults are most likely to faults
occur
Cable compartments Inadequate design Selection of adequate dimensions.
Use of appropriate materials.
Faulty installation Avoidance of crossed cables connections.
Checking of workmanship on site. Correct torque
Failure of solid or liquid insulation Checking of workmanship and/or dielectric test
(defective or missing) on site.
Regular checking of liquid levels, where applicable
Disconnectors Maloperation Interlocks. Delayed reopening.
Switches Independent manual operation. Making capacity
Earthing switches for switches and earthing switches. Instructions to
personnel.
Bolted connections and Corrosion Use of corrosion inhibiting coating and/or greases.
contacts Use of plating. Encapsulation, where possible.
Faulty assembly Checking of workmanship by suitable means.
Correct torque. Adequate locking means.
Instrument transformers Ferro-resonance Avoidance of these electrical influences by
suitable design of the circuit.
Short circuit on LV side for VTs Avoid short circuit by proper means for example,
protection cover, LV fuses.
Circuit breakers Insufficient maintenance Regular programmed maintenance.
Instructions to personnel.
All locations Error by personnel Limitation of access by compartmentation.
Insulation embedded live parts. Instructions to
personnel.
Ageing under electric stresses Partial discharge routine tests.
Pollution, moisture, ingress of dust, Measures to ensure that the specified service
vermin, etc conditions are achieved. Use of gasfilled
compartments.
Overvoltages Surge protection. Adequate insulation
co-ordination.
Dielectric tests on site.
Source: IEC 62271-200
A circuit breaker must operate under various conditions without damage or safety risk to personnel:
a circuit breaker operates mostly in the closed position and must continuously sustain its rated current
without exceeding its thermal limits
in the closed position, a circuit breaker must sustain a specific fault current level (Ik) for a short time period
(tk). A circuit breaker's short-time withstand fault current rating must exceed the expected rms
symmetrical fault current level (Is) at the point of installation
a circuit breaker must be capable of sustaining electrodynamic and thermal stresses associated with the
peak let-through energy of a fault. The circuit breaker's make rating must exceed the expected peak fault
current level (Ip) at the point of installation.
Where:
Ip = 2.5 x Is (for a 50 Hz supply with a
Ip = asymmetrical peak let-through fault current, from the first fault
45 ms DC time constant)
loop (kA)
Ip = 2.6 x Is (for a 60 Hz supply with a
Is = rms symmetrical fault current level, with no DC component
45 ms DC time constant)
(kA)
Is
13716.A
Time
Construction
Main switching contact design has two primary components:
a suitable insulation medium to minimise the physical size of the apparatus
a method to reduce any arc and extinguish it during contact breaking
Modern medium voltage circuit breakers tend to be either vacuum or SF6 gas-insulated (sulphur hexafluouride).
Oil filled circuit breakers are less common.
Mechanical operation
Circuit breakers are electromechanically driven using magnetic or stored energy techniques.
magnetic technique: uses an open and close armature, permanently energised in one of the two states.
The energy required to maintain constant magnetic field strength, in either the open or closed state, is
stored using capacitance. Energised armatures interact with mechanical linkages to operate the main
switching contacts. This operating technique provides extremely fast operation and is very energy
efficient.
stored energy technique: incorporates an opening and closing spring. Each spring is charged with potential
energy, by motor operation, or by using a manually operated handle in case of auxiliary power loss.
Mechanical operation of the main switching contacts occurs by releasing the potential energy from a
charged spring. Spring release is activated electrically by the use of small opening and closing solenoids or
by manual pushbuttons which operate mechanical latches.
Withdrawable circuit breakers
Most indoor switchgear installations use withdrawable circuit breakers. These are also referred to as rack style or
draw-out units (DOU).
The main circuit breaker body is fitted on a trolley arrangement known as a truck, which is moved horizontally by
means of a crank handle. By moving the circuit breaker towards the operator, the main contact points separate until
a test position is reached. To reconnect the main contact points, the circuit breaker is moved away from the
operator until the service position is reached. The circuit breaker position cannot be changed unless the circuit
breaker main poles are electrically open.
The main advantage of a withdrawable circuit breaker compared with fixed type circuit breakers is the ability to
safely disconnect and isolate the main circuit for maintenance or circuit breaker replacement.
11163.A
Control methods
IEC Ratings
Medium voltage circuit breakers must be type tested to provide standard ratings. The most commonly used
standards for this testing are IEC 62271-1 and IEC 62271-100.
The following information provides details of some of the more common ratings which must be marked on the
circuit breaker nameplate after type testing.
If the value of tk is not 1 second, the rated short circuit duration must be published on the circuit breaker nameplate.
90 4 = 120 ms
80 3 = 75 ms
Percentage DC component
70 2 = 60 ms
60
50
40
30
20 1 = 45 ms
10
13720.A
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
Time interval from initiation of short circuit current (ms)
The graph illustrates the percentage DC component of a fault, over a period of time, for systems with various time
constants. Most systems use the standard time constant (1) of 45 ms. The total opening time of the circuit
breaker is the pole opening time plus 10 ms for relay sensing, and this figure can be used to determine the
percentage DC component of a fault at the instant of breaking.
Exercise
What is the required short circuit breaking capacity of a circuit breaker, with a pole opening time of 45 ms and an
expected symmetrical short circuit fault level of 21 kA at the point of installation?
Total opening time of the circuit breaker: t = 10 + 45 = 55 ms
The percentage DC component at a total opening time of 55 ms is 30%:
100
90
80
Percentage DC component
70
60
50 1 = 45 ms
40
30
20
10
13721.A
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
Time interval from initiation of short circuit current (ms)
The asymmetrical fault current level is 23 kA. A circuit breaker with a rated short circuit breaking capacity (Isc) of
25 kA can be used.
Rated TRV (Uc) for circuit breakers intended for use on cable systems (Class S1)
IEC 62271-100 defines standard TRV peak voltage ratings.
Voltage envelope for a two parameter TRV waveform on a cable system less than 100 kV
Uc
Voltage
U'
13722.A
0 td t' t3 t
Time
Source: IEC 62271-100
NOTE
These ratings are recommendations only. Individual circuit breaker ratings may specify different values.
IEC Classifications
Medium voltage circuit breakers can be type tested and categorised according to the classifications in
IEC 62271-100.
Medium voltage contactors are suitable for high frequency switching (>10,000 operations), with continuous AC3
current ratings greater than 800 A and rated voltages from 1 kV to 12 kV. Manufacturers provide standard
utilisation category ratings which can be matched to a specific application and the required number of operations.
Indoor contactors can be fixed or withdrawable style. Withdrawable style contactors can usually house primary
protection fuses.
Construction
Medium voltage contactors usually consist of:
flame retardant plastics to house the vacuum interrupters (and fuses, in the case of a withdrawable
contactor)
metal chassis (and truck, in the case of a withdrawable contactor)
busbars for main power circuit connections (or cluster style power connections, in the case of a
withdrawable contactor)
magnetic and mechanical linkage components, for operation of the vacuum interrupter contacts
auxiliary circuit components such as auxiliary contacts, truck position contacts, undervoltage or shunt trip
coils, interlock coil etc
IEC Ratings
Medium voltage contactors must be type tested to provide standard ratings.
The contactor nameplate label must show the manufacturer's name, contactor model and serial number, and certain
rating information. Many manufacturers also provide additional rating information.
13682.A
PR
Assume the 7.2 kV/50 Hz, 200 A contactor has a short-time withstand current rating Ik of 8 kA and the prospective
rms fault current level Isc at the point of installation is 10 kA.
100
50
Maximum cut-off current (kA) peak
20
315
250
200
160
10
100
63
5
2
13684.A
1.0 2 5 10 20 50 100
1 Motor FLC
3
Motor start current
Overload curve - nominal setting (In)
Overload curve - hot
4
Fuse total clearing curve
5
Contactor maximum break current (Ic)
Time (s)
7
13525.A
Current (A)
13693.A
Switch-Disconnector Switching and isolation Rated for carrying continuous load current with
(load-break isolator) a short-time withstand fault current rating (Ik)
Can switch rated current (Ir) but has no fault
make capability
Used with line fuses or a circuit breaker
13690.A
Earth switch Earthing Rated for carrying continuous load current with
a short-time withstand fault current rating (Ik)
No load switching capability, but can make on a
fault (Ip)
Used with a circuit breaker or contactor and
fuse combination
13691.A
Gas insulated Earth-disconnector Switching, isolation and Rated for carrying continuous load current with
(fixed or rotary) earthing a short-time withstand fault current rating (Ik)
Can switch rated load current (Ir)
Can make on fault current (Ip)
Used with line fuses or a circuit breaker
13689.A
13688.A
Applications
A typical medium voltage metal-enclosed switchgear feeder circuit will have a combination of switchgear able to
provide the following functions:
switching of load current
short circuit protection
means of isolation
means of earthing
In most cases, air insulated earth switches or gas insulated earth-disconnectors, are used. The following examples
show common configurations for medium voltage, metal-enclosed switchgear feeder circuits.
protection.
Withdrawable contactor The withdrawable contactor with integrated fuses provides load
switching and circuit isolation when opened and in the draw-out
position. The fuses provide short circuit protection.
The cable-side earth switch is interlocked with the contactor and
can only be closed when the contactor is in the drawn-out position.
13686.A
Gas insulated rotary disconnector The gas insulated rotary disconnector has three physical operating
positions. It provides load switching in the ON position, isolation in
the OFF position and earthing in the EARTH position.
Short circuit protection is provided by fuses, but a fixed type circuit
breaker could be used instead.
13686.A
IEC Ratings
Disconnectors and earth switches are type tested to specific IEC standards. IEC 62271-1 provides standard ratings
and IEC 62271-102 details test methods and specific requirements for medium voltage disconnectors and earth
switches.
The nameplate label must show the manufacturer's name, equipment model and serial number, and certain rating
information. Many manufacturers also provide additional rating information.
Rated voltage, Ur (kV)
Maximum operating voltage (rms) the device can continuously withstand during normal operation. The rated
voltage must be greater than or equal to the system's operating voltage.
Standard values for Ur : 3.6, 7.2, 12, 17.5, 24, 36 kV (source: IEC 62271-1)
Fuse selection depends on the maximum load current, type of load, prospective fault current, system voltage and
ambient temperature of the installation. In a 3-phase installation, it is assumed that all three fuses are subjected to the
same rate of degradation. If one fuse ruptures, it is highly recommended that all three be replaced.
Two categories of fuses are commonly use for medium voltage primary and secondary switchgear installations.
General purpose fuses (also called E-rated fuses by NEMA) are typically used in combination with
contactors or switch-disconnectors.
Motor rated fuses (also called R-rated fuses by NEMA) are used for motor feeder circuits, and must be
used in conjunction with a thermal overload protective device. Motor rated fuses have time delayed,
time-current curves and higher minimum melt characteristics to accommodate the high currents associated
with motor starting.
Fuse characteristics
Pre-arcing curves
Pre-arcing curves are sometimes referred to as time-current curves. They indicate minimum break currents and the
ability for a fuse to pass through medium level overload current, such as motor starting current. The dashed part of
each fuse curve indicates an area of uncertain fuse interruption.
m
Pre-arcing time (seconds or minutes)
2 3 4
Example
A fuse with a nominal rating of 50 A has a minimum break current of 200 A and is capable of passing an overload
current of 240 A for 10 seconds.
Let-through curves
Sometimes referred to as cut-off curves, they indicate the ability of a fuse to limit the peak let-through and rms values
of short circuit current, immediately downstream of the fuse installation.
0
20
0
16
5
10 120
Maximum cut-off current (kA, peak)
10
80
63
50
40 .5
31
25
20
16
10
6
0.1
13698.A
Example
If the prospective rms fault current was 5 kA, the peak let-through current would be approximately 12 kA without
a fuse. If a 50 A fuse was installed, the rms fault current would be limited to 1.5 kA and the peak let-through current
would be 3.8 kA downstream of the fuse.
I2t data
Fuse data sheets provide two I2t figures:
minimum I2t is the amount of let-through energy required to start a fuse melt and create an arc
maximum I2t is the total amount of let-through energy required to extinguish an arc and completely
rupture (open circuit) a fuse.
This data is important for fuse discrimination. The maximum I 2t of the downstream fuse must be less than the
minimum I2t of the upstream fuse.
If a fuse is selected to protect a cable, the maximum I2t of the fuse must be greater than the A2S2 thermal rating of
the cable.
Ratings
Irrespective of which standard a fuse has been type tested too, the following generic ratings usually apply. Different
standards require different rating information to be published on the fuse nameplate.
Exercise
Select the primary input fuses required to protect an 11 kV/400 VAC, 1000 kVA, 3-phase power transformer.
The range of In(FUSE) is 97.5~106 A. Use 100 A/12 kV, E-rated primary fuses.
Capacitor banks
Two primary factors affect fuse ratings when used with capacitor banks:
the peak inrush current which flows when a capacitor bank is energised. This can be up to 100 times the
nominal current rating of the capacitor bank.
transient voltages produced during capacitor bank switching.
Exercise
Select the protection fuse required for a 300 kVAr/7.2 kV individual 3-phase capacitor bank.
I_CAP
n(FUSE) I_CAP
n(FUSE) U_CAP
Motor circuits
Special motor rated fuses are used for motor starting. These fuses can sustain repeated motor start overload
currents without degradation. Fuses are installed to provide short circuit protection only and the motor circuit
must have separate overload protection.
Fuse selection for a motor application is typically carried out using graphs provided by the fuse manufacturer. These
graphs consider motor starting current (A), motor run-up time (s) and starts per hour.
Typical fuse ratings for 2, 4 or 8 starts per hour, starting time 60 seconds
2 x 250 2
2 x 200
315
250
200
160
100
13697.A
63
Typical fuse ratings for 2, 4, 8, 16 or 32 starts per hour, starting time 15 seconds
1
32 Starts per hour
16
2 x 315
8
2 x 250 4
2 x 200 2
Fuse rating (A)
315
250
200
160
100
13745.A
63
200 1000 10000
Motor starting current (A)
Exercise
A 3.3 kV motor has a full load current of 150 A. Its expected start current is 5.5 times full load current for 10 seconds
and it operates at 2 starts per hour. Select the required protection fuse.
Use the graph for Starting time 15 seconds. The start current will be 5.5 x 150 A = 825 A.
For motor starting current of 825 A, at 2 starts per hour, the required motor rated fuse is 250 A/3.6 kV.
13696.A
O/L
The circuit components and protection must be coordinated to achieve the following results
1
6
3
13783.A
Current (A)
Coordination requirements:
The expected motor start current curve (1) must sit inside (to the left) of the thermal relay protection
curve (2) and the fuse trip curve (3).
The intersection of the thermal relay protection curve and the fuse trip curve must have a lower current
value that the maximum breaking current of the contactor (4).
The fuse rating must not exceed the maximum size stated by the contactor manufacturer.
The thermal withstand curves of the motor (5) and the cable (6) must sit outside (to the right) of the
thermal relay protection curve and the fuse trip curve.
The short circuit withstand current rating of the contactor must exceed the expected rms short circuit
current downstream of the fuse after current limiting.
If a back-up fuse is installed upstream, its minimum I2t value must be greater than the maximum I2t value of
the motor branch fuse.
Current Transformers
A current transformer (CT) is designed to produce a secondary current which is accurately proportional to the
primary current. It consists of a single primary winding, which an external busbar or cable runs through, or it can
have a single primary bar, brought out to two ends for termination. A medium voltage current transformer can
have up to three independent secondary winding sets. The entire current transformer assembly is encapsulated in
resin, inside an insulated casing
Current transformers are used for metering or protection purposes. The accuracy class and size depends on the
individual application - for example, revenue metering would use high accuracy metering CTs.
NOTE
Never leave the secondary winding of a CT open circuit. This creates extremely high voltages which pose
a real danger to personnel.
Ring style CT DIN style CT
IEC Ratings
Rated primary current, Ipr (A)
The primary current rating of a CT must be greater than the expected maximum operating current it is monitoring.
a metering CT's primary current rating should not exceed 1.5 times the maximum operating current
a protection CT's primary current rating needs to be chosen so that the protection pick-up level is attained
during a fault
Standard values for Ipr : 10, 12.5, 15, 20, 25, 30, 40, 50, 60, 75 A, and decimal multiples of these values (source:
IEC 60044-1)
Transformer ratio, Kn
This is the ratio of secondary to primary winding turns.
This coefficient indicates how difficult it would be to manufacture a CT. A higher coefficient means a physically
larger CT, which is more difficult to manufacture.
Ksi < 100 : easy to manufacture
Ksi 100 ~ 500 : difficult to manufacture, with certain limitations
Ksi > 500 : extremely difficult to manufacture
Exercises
1. A CT with a 1 A secondary is connected to an electromagnetic ammeter located10 metres away, using 2.5 mm2
copper cable. Calculate the minimum required VA rating of the CT.
Metering class
A metering class indicates the accuracy of the CT secondary current at 5 to 125% of rated primary current. Above
this level, the CT starts to saturate and the secondary current is clipped to protect the inputs of a connected
metering instrument.
general metering CT would use a metering class CL 0.5 – 1.0
revenue metering CT would use a metering class CL 0.2 – 0.5
Saturation
1
Linear operating range, at accuracy
class tolerance
Flux ()
13702.A
5% 125%
Ipr (%)
Protection class CT
A protection class CT provides a linear transformation of the primary to secondary current at high overload levels.
This characteristic makes them suitable for use with overcurrent protection relays. A relay trip setting is normally
10~15 times the maximum load current and this level should fall on the linear part of the CT secondary current
curve. If a CT saturates before the relay trip level is reached, the fault will remain undetected, leading to equipment
damage and serious danger to personnel.
The most commonly used protection class is a 5PX, where X is the accuracy limit factor (ALF) or multiplication
factor of the rated primary current. The secondary current is +/-1% accurate at rated primary current and +/-5%
accurate at X times rated primary current.
Typical protection class CT ratings are 5P10, 5P15, 5P20.
Saturation
Isc
Linear operating range, at accuracy class
1 tolerance
Ideal protection setting trip zone
50%~100% ALF
Flux ()
Ipr (%)
Example
A 200/1 A CT has a protection class rating of 5P15.
The secondary current is guaranteed to be linear up to 15 times the rated primary current. The secondary current
will be 1 A (+/-1%) at 200 A primary current and 15 A (+/-5%) at 3000 A primary current. For guaranteed
operation, any overcurrent trip setting should be between 7.5 ~ 15 A secondary current.
Selection
The main considerations for selecting a CT are the primary and secondary current ratio, real output power rating
(VA) and accuracy class. Secondary selection considerations are rated primary voltage, frequency and thermal
short-time withstand current.
Primary and secondary current ratio
Rated primary current, Ipr (A)
Incomer from transformer: Ipr ≥ 1.0-1.25 of nominal source current
Feeder to transformer: Ipr ≥ 1.0-1.25 of transformer's rated primary current
Feeder to motor: Ipr ≥ 1.0-1.5 of motor full load current
Feeder to capacitor bank: Ipr ≥ 1.3-1.5 of nominal capacitor current
Rated secondary current, Isr (A)
Use 1 A and 5 A for local installation.
Use 1 A for remote installation.
Real output power (VA)
The real output rating of the CT must be the next highest nominal size above the expected total burden on the CT
secondary. Total burden is the sum of output cable, connectors and instruments.
Class type
Use a metering class CT for metering and indication. A higher class CT gives greater accuracy between the primary
and secondary currents.
Use a 5PX protection class CT for current based protection relay inputs. The ALF must be selected so that the
relay trip point lies on the linear part of the secondary current curve, between 50% and 100% of the ALF.
Exercise
Select appropriate CTs for the following transformer incomer and feeder circuits.
Transformer Incomer
MV/MV transformer (TXR1): 5 MVA, 36/11 kV,
TXR1 36/11kV 10% Z
Instantaneous overcurrent trip setting = 15 x In
for digital protection relay (OC1) driven off CT1-2
CT1-1 A
Electromagnetic ammeter (A) is driven off CT1-1
CT1-2 OC1 Transformer Feeder
MV/LV transformer (TXR2): 2 MVA, 11/0.4 kV,
1 5% Z
Instantaneous overcurrent trip setting = 10 x In
for digital protection relay (OC2) driven off CT2
CT2 OC2
TXR2 11/0.4kV
13703.A
Step 2: Calculated maximum expected short circuit current at CT1 installation, Isc (A)
Ignoring any power cable or busbar impedances:
SEC
300
Using an ALF of 15 (5P15), the trip current level of 3930 A falls within the range 100% to 50% ALF so a 5P15
protection class CT is suitable.
NEMA/IEEE Ratings
These ratings are typically used for current transformers manufactured or used in North American installations. As
well as a stated primary to secondary nominal current ratio, the device also carries an overall accuracy rating in the
format
Where:
AC = accuracy class
AC-CR-BU
CR = class rating
BU = maximum burden (ohms)
Accuracy class
Designates the accuracy of the secondary current with respect to the primary rated current. This accuracy is only
guaranteed provided the maximum burden is not exceeded.
Accuracy class Tolerance at 100% primary current
1.2 ±1.2%
0.6 ±0.6%
0.5 ±0.5%
0.3 ±0.3%
Class rating
Designates the intended application of the device.
B= for metering applications
H= for protection applications. The CT secondary accuracy is guaranteed at 5 to 20 times the nominal
primary rated current
Burden
The maximum load allowed to be connected to the current transformer secondary, to guarantee the accuracy class.
The maximum burden includes secondary cable/wire, connectors and the load. The following table converts burden
in ohms to VA, for a 5 A secondary.
0.04 0.06 0.08 0.12 0.16 0.20 0.24 0.28 0.32 0.36 0.40 0.48 0.56 0.64 0.72 0.80
VA 1 1.5 2 3 4 5 6 7 8 9 10 12 14 16 18 20
Examples
0.5-B-0.1 indicates a current transformer with an accuracy of ±0.5%, and a maximum allowable secondary burden of
0.1 (or 2.5 VA on a 5 A secondary CT). This is a metering class rated current transformer.
1.2-H-0.2 indicates a current transformer with an accuracy of ±1.2%, and a maximum allowable secondary burden
of 0.2 (or 5 VA on a 5 A secondary CT). This is a protection class rated current transformer.
Current Sensors
The basic principle of any current sensor is to produce a small level of secondary voltage, within a specific accuracy
range, which is directly proportional to the measured primary current. In medium voltage applications, isolation
between the primary and secondary circuits is critical.
Although current transformers are the most commonly used device for measuring current, there are a number of
other methods available. Current sensors are usually designed and supplied by manufacturers as proprietary
equipment to match a digital metering or protection relay. Low power current sensors are ideal for use with
modern digital relays, which provide a low burden. Sometimes referred to as hybrid current sensors, each type has
its own merits.
Rogowski coil
A rogowski coil consists of a single primary winding, which is normally a copper bar with termination points at both
ends. The secondary winding is made up of multiple turns on a toroidal, non-ferrous core. The entire construction
is encased in a dielectric insulation material.
The basic operating principle is that the voltage produced across a high impedance secondary load is directly
proportional to the primary current. Accuracy is typically ±1% up to 10 times the rated primary current and ±5%
up to 200 times the rated primary current.
The customer must specify the required nominal primary current, short-time fault current withstand rating and the
insulation level requirements. No other specifications apply, as rogowski coils are supplied by the manufacturer as
a matched item with the associated relay device.
Current to be measured
1
Secondary winding
2
Non-ferromagnetic support
3
Output voltage
4
Z
13750.A
Current to be measured
Magnetic circuit
2
4 Hall cell
Hall cell supply current
Hall output voltage
3 5 Voltage or current amplifier
1 +
6
-
13751.A
flux). The second winding generates a current in the secondary load, which is directly proportional to the measured
primary current.
This method is very accurate with a tolerance in the order of ±0.02%. A zero flux CT can only be used to measure
DC primary current.
Current to be measured
1
Magnetic circuit
2 4 Secondary winding
Secondary circuit current
3
Zero flux detection winding
Z Current amplifier
5
6
13752.A
Protection Devices
Protection devices are used in medium voltage distribution systems to protect line and cable feeders, busbar
systems, transformers, motors, generators and power factor correction banks. Abnormal conditions can be
detected based on secondary current and voltage measurement, or temperature monitoring using thermal devices.
When an abnormal condition is detected, correct coordination of the protection devices will rapidly isolate the fault
to a specific zone in the system.
Older protection devices relied on electromechanical relays to measure system parameters. Modern protection
devices are exclusively low consumption, digital, and microprocessor based, with many communication options
available. Modern high-end protection devices incorporate many parameter settings along with programmable
logic control which provides not only protection functions, but switchgear control and interlocking.
Protection devices are primarily covered by IEC 60255-1.
Protection functions
Overcurrent
This is the most widely used form of protection. In a 3-phase power system, all three line currents are measured
using current transformers. The secondary output of a 1 A or 5 A current transformer is connected to the current
input of a protection device. Within the protection device, analog signals are filtered and sampled before being
converted to digital signals for processing. A trip condition occurs if a preset current level is exceeded for a specific
time.
There are two basic methods of overcurrent protection:
Time-overcurrent protection - provides overload protection similar to a bimetallic thermal overload
device, except thermal modelling adjusts the trip curve shape to allow for dynamic heating and cooling
conditions. If the measured current reaches a point on the overload curve, a trip will occur.
Time-overcurrent is also referred to as "inverse" (I) protection
Instantaneous overcurrent protection - provides medium level and high level short circuit protection. If a
set current level is exceeded for set time period, a trip will occur. This protection is also referred to as
definite minimum time (DMT) protection.
Devices may combine time-overcurrent and instantaneous overcurrent protection. Time-overcurrent is normally
only applied to electrical machines such as transformers and motors, whereas instantaneous overcurrent is applied
to cables, busbar systems etc. Overcurrent protection can be directional, which is sometimes used for more
advanced selective isolation of faults.
Overcurrent protection
1
Time overcurrent (I)
Time (s)
13753.A
Current (A)
Overcurrent protection based on measuring the 3-phase line currents, produces positive sequence current (I 1,
indicative of phase-to-phase faults) or negative phase sequence current (I2, indicative of phase loss or phase
imbalance). Overcurrent protection based on measuring the residual or ground current, produces zero sequence
current (I0, indicative of ground fault or earth leakage).
The configuration of the CTs depends on the functionality of the protection device:
I_A
I_A
I_B
I_B
I_C
I_C
Io
13758.A
13759.A
Positive sequence current, I1 Positive sequence current, I1
Negative sequence current, I2 Negative sequence current, I2
Zero sequence current, I0
HV
13760.A
TXR
Zero sequence current, I0
1
MV
Io
13761.A
Differential
In medium voltage installations, differential protection is mainly used on transformers, motors and generators. Line
currents are measured on both sides of the device, to determine the difference between the input and output
currents (individual or 3-phase average). If the difference exceeds a preset limit, this indicates a phase loss or short
circuit fault condition. A trip will occur, isolating the affected electrical device from the rest of the system.
Transformer application
2 HV supply
3
CT1 CT2
3
Transformer
1 4
Differential protection device
MV supply
13756.A
3
MV motor application
Incoming supply
CT1 CT2
3 2 3 MV motor
1 M
Differential protection device
13756.A
MV generator application
Output supply
CT1 CT2
3 2 3 MV generator
1 G
Differential protection device
13757.A
Bus zone
This protection is used on bus distribution systems. The 3-phase line currents are measured on all feeders
connected to a busbar system. The sum of currents entering should equal the sum of currents leaving the busbar
system. If the difference in individual or 3-phase average currents is not close to zero, a trip will occur.
Bus configurations can be complex, but by using the status information of all the switching devices on a busbar
system, logic within the protection device can selectively isolate the faulty zone.
Distance
This protection is predominantly used on long transmission lines running between primary substations, with radial
feeders along the length of the transmission line. The distance to a fault is determined by calculating the line fault
impedance with a healthy line impedance. Both line voltages and currents are measured to calculate the fault
impedance.
Selective line isolation is achieved by setting a trip zone within the protection device. This trip zone covers a specific
distance along the length of the transmission line from where the protection device is installed. Protection devices
are used in pairs installed at each end of a transmission line, and a fast speed, real-time communication link is required
between devices.
Za Zb
CT CT
VT VT
1 5
4 4
13754.A
3
Voltage
Voltage protection is often used on transformers, motor, generators and power factor banks which can be damaged
due to long term undervoltage or overvoltage conditions.
If the average 3-phase or any individual line voltage falls outside a specific range for a specific period, a trip will occur.
A time delay is used to override temporary surges and dips in the mains voltage.
ANSI codes commonly specified for medium voltage feeders, transformers, motor and power factor banks.
ANSI Function Description Application Components
code required
CT VT
Incomer feeder
Power factor
Transformer
Motor
panel
bank
24 Volts per hertz Activates if the Volts/Hertz ratio falls X X
relay outside a preset range.
25 Synchronising or Operates when the voltage, frequency, X X
synch-check and phase angles between two AC
device systems are within a preset acceptable
range.
26 Apparatus Activates if the monitored apparatus X X X
device exceeds a preset temperature.
27 Undervoltage Activates if the voltage falls below a preset X X X X
relay level.
37 Undercurrent/ Activates if the current or power falls X X
power relay below a preset level.
38 Bearing Activates when the upper temperature X
protective limit of a machine bearing is exceeded or
device abnormal bearing wear is detected.
46 Phase reversal or Monitors line currents and activates when X X X
current phase reversal is detected or when line
imbalance relay current imbalance of negative phase
sequence currents fall outside a preset
range.
47 Phase sequence Monitors line voltages and activates when X X
voltage relay phase reversal is detected.
48 Incomplete Trips or turns off a device if a particular X
sequence relay sequence has not been completed within
a preset time period.
49 Machine or Activates if the monitored machine or X X X
(P,R) transformer transformer part exceeds a preset
thermal relay temperature.
(P = PTC, R = RTD)
50 AC Activates if the current or di/dt values X X X X X
(N,G) instantaneous or exceed a preset level. Normally indicates a
di/dt relay medium to high level fault condition.
(N = neutral, G = ground)
51 AC Activates when the current exceeds a X X X X X
(N,G) time-overcurren preset level based on a thermal overload
t relay trip curve.
(N = neutral, G = ground)
59 Overvoltage Activates if the voltage exceeds a preset X X X X
relay level.
64 Ground (earth) Activates when earth current flow is X X X
detector relay detected from the frame, chassis, case or
structure of a device, indicating a
breakdown of insulation in an electrical
machine or transformer.
Incomer feeder
Power factor
Transformer
Motor
panel
bank
67 AC directional Activates when the current, flowing in a X X
current relay specific direction, exceeds a preset level.
This protection is based on 50 and 51
functions.
79 AC reclosing Controls the automatic reclosing and X
relay locking-out of an AC circuit switching
device.
81 Frequency relay Activates if the frequency falls outside a X X X X
preset range.
86 Locking-out Shuts down or holds equipment out of X
relay service under abnormal conditions. May
be manually or electrically operated.
87 (L, Differential Activates if the detected current on X X X
T, M) protection relay opposite sides of a machine or
transformer are not equal to each other.
(L = line, T = transformer,
G = generator)
Temperature related protection functions such as motor winding and bearing protection require a separate
protection device which can be installed in the LV section of the soft starter panel.
Voltage Transformers
A voltage transformer (VT) or instrument transformer is used to produce a lower secondary voltage which is directly
proportional to the primary voltage both in value and phase angle.
In medium voltage switchgear, a 3-phase voltage transformer arrangement is typically derived by using three, single
phase transformer poles. Each pole consists of a single primary and secondary winding encapsulated in epoxy resin
and encased with insulating material. In most single phase pole designs, the primary winding has integrated fusing.
In a 3-phase arrangement, the primary windings of each individual pole are externally connected in star configuration.
Each end of the secondary winding is brought out to a customer termination box. The secondary windings can be
externally connected in star or delta configuration and must always be separately fused. Star connection of the
secondary winding is preferable, as this provides voltage stability through solid earthing of the neutral point and
3-phase and neutral is available for voltage measurement.
Switchgear installations use either fixed or withdrawable voltage transformers. Withdrawable voltage transformers
are mounted on a draw-out truck arrangement.
The power rating and accuracy of a transformer arrangement will depend on its application. For metering,
protection and indication, power ratings are small, with accuracies in the range of ±0.5-3.0%. A voltage transformer
used to provide a control supply may have a power rating above 5 kVA. In this case, accuracy is not as important.
Relevant standards: IEC 61869-3, IEEE C57.13.
Voltage transformer (3-phase, fixed) Control supply transformer (single phase, fixed)
1 1
L1 L2 L3 L1 L2 L3
2
Nominal voltage
Example: 3.3 kV/110 VAC
Denotes a primary phase-to-phase voltage rating of 3300 V and
a secondary phase-to-phase voltage rating of 110 VAC.
13762.A
3300/110 VAC
110 VAC and phase-to-earth rating of 63.5 VAC (ie: 110 x √3) 3300- 3/110- 3 VAC
Many manufacturers use a continuous overload rating of 1.2 times the primary voltage rating without exceeding
thermal capabilities which can lead to winding and insulation failure.
Output power
This is the apparent output power rating of a transformer when nominal voltage is applied to the primary.
For a 3-phase voltage transformer Where:
arrangement, S = √3 x U x I S = apparent output power (VA)
U = secondary line voltage rating (V)
For a single phase voltage transformer I = secondary line current rating (A)
arrangement, S = U x I
Standard values are: 10, 15, 25, 30, 50, 75, 100, 120 VA
Control supply power transformers are usually single phase transformers, with an output power rating of 500 VA to
5000 VA. For further details, refer to Control power supply transformer sizing on page 128.
Accuracy class
Designates the maximum error of the transformed voltage and phase angles at rated primary voltage.
IEC 61869-3 specifies standard accuracy classes for voltage transformers.
Exercise
A transformer with its primary connected to 7.2 kV, has a 110 VAC secondary with a total inrush loading of
850 VA and a resistive load of 100 VA. The total sealed VA of the load is 200 VA.
A voltage drop of 85% is acceptable during the inrush stage. The power factor of the inrush current is 0.3.
Calculate the necessary power rating of the control supply power transformer.
1. The total inrush loading is 950 VA (850 VA + 100 VA). The next highest Inrush VA figure in the 85% volt
drop column is 1267 VA.
2. An Inrush VA of 1267 VA equates to a Nominal VA rating of 200 VA.
3. 200 VA seems acceptable as this is equivalent to the total sealed load VA.
4. The inrush current has a power factor of 0.3. Using the power factor adjustment factor, the transformer has
a revised Nominal VA rating of 222 VA (200 x 1.11). The next highest standard size would be 250 VA.
Use a 7.2 kV/110 VAC, 250 VA single phase control supply power transformer.
Transformer primary fuses must withstand the inrush magnetising current which flows when a
transformer primary is switched on. With a medium voltage primary, E-rated fuses are used and often
selected to withstand 25 times the nominal primary current for 0.01 second and 12 times the nominal
primary current for 0.1 second.
300
1500
200
1000
100
500
0
0
63.05 63.10
-500
-1000
13766.A
-1500
55 59 63 67 71
The current transient, peak value and rate-of-rise are are installation dependent, and are determined by many factors
external to the soft starter. The di/dt value of the current transient is proportional to the system voltage (for
example, the value for a 6.6 kV system will be approximately twice as much as a 3.3 kV system).
At a critical cable length, the cable capacitance must be negated by line inductance to avoid damaging current
transients. Air-core line inductors are specified according to the installation and are fitted close to the soft starter
output terminals.
4
5
1 M
2 3
13768.A
Soft starter SCRs are most vulnerable to current transient damage at two stages of the motor starting procedure:
in the initial ramp-up to the start current (current limit) level.
when the SCRs reach full conduction and just before the motor current falls to the running current level.
The latter stage is potentially more damaging. AuCom medium voltage soft starters are bypassed in run state and
the SCRs are turned off, minimising the risk of current transient damage.
NOTE
This calculation involves many assumptions. Double the required compensation inductance before
selecting the output inductors.
Exercise:
Calculate the compensation inductance required for a 4.2 kV MVS soft starter installation. Assume the maximum
SCR didt rating to be 100 A/µs.
This calculation should be doubled to use a minimum compensation inductance of 102 µH per phase.
A protection device earths the current associated with an overvoltage transient. This limits the terminal voltage at
the point of installation to a level below the withstand voltage of the equipment.
5
Possible voltage without arrestors
Magnitude of overvoltage /p.u.
4
1 Withstand voltage of equipment
2
Voltage limited by arrestors
3
A Lightning overvoltages (microseconds)
2 3 B Switching overvoltages (milliseconds)
C Temporary overvoltages (seconds)
1 D Highest system voltage (continuous)
13802.A
0
A B C D
Duration of overvoltage
In the past, overvoltage protection was provided using spark-gap arrestors. Today,
most indoor medium voltage systems use metal-oxide (MO) arresters which provide
a compact and dependable solution for overvoltage protection. MO arresters are
covered by IEC 60099-4 and IEEE C62.22-2009. MO arresters are often used in gas
insulated, indoor switchgear to avoid restrike during equipment switching
2
Leakage current, Il (mA)
Line to earth peak voltage (kV)
Selection Ratings
There are four ratings to consider when selecting MO arrestors for an installation.
Nominal discharge current (In)
Maximum discharge current the MO arrestor can shunt to earth, without exceeding its thermal and mechanical
limits. Manufacturers usually state two discharge current ratings:
Current produced as a result of a lightning strike voltage transient. This discharge current is assumed to be
an 8/20 µs waveform with the following standard ratings:
1.5 kA, 2.5 kA, 5 kA, 10 kA, 20 kA
For the majority of secondary indoor switchgear systems, a rating of 10 kA is used for selection (sometimes
referred to as "distribution class")
Current produced as a result of an equipment switching voltage transient. This discharge current is
assumed to be a 30/60 µs waveform with standard ratings from 125 A to 1000 A.
For the majority of secondary indoor switchgear systems, a rating of 500 A is used for selection (sometimes
referred to as "distribution class")
Continuous operating voltage (Uc)
This is based on the maximum-peak operating voltage likely to occur in the system when a single phase-to-earth fault
occurs. IEEE standards refer to this rating as MCOV (maximum continuous operating voltage).
For a solidly earthed neutral system:
Exercise
A 17.5 kV secondary distribution, indoor switchgear system requires MO arrestors to be fitted on the incomer side.
The system supply is 15 kV/50 Hz and is isolated from earth. Use calculated ratings and the manufacturers’ data
sheet for selection.
The highlighted numbers 1~4 refer to the solution page.
Step 1: Calculate the MO arrestor ratings
Rated voltage
Rated voltage (Ur) ≥ 1.25 times continuous operating voltage (Uc)
Ur ≥ 1.25 x 15
Ur ≥ 18.75 kV
Solution:
A type MWD15 meets the selection criteria.
13808.A
PFC controller
VT
1
CT
13807.A
M1 M2 M3
C1 C2 C3
1
2
13809.A
M Q
P (kW)
P = 1500 kW
= 0.96
pf1 = 0.88 (initial power factor)
pf2 = 0.95 (target power factor)
Where:
Q = capacitor bank power (kVAr)
P = motor shaft power (kW)
Q= (tan tan 2)
1
= motor efficiency at full load
1 = phase angle of motor power factor at full load (=cos-1 x pf1)
2 = phase angle of target power factor at full load (=cos-1 x pf2)
Nominal current
Exercise
Calculate the total capacitance and nominal current of a 500 kVAr power factor bank operating on a 6.6 kV/50 Hz
supply system.
C = Q
1000
U2(2 f)
= 500
1000
6.62(2 50)
= 500 1000
43.56 314.16
= 36 µF
The capacitance is 36 µF.
The values of peak inrush current and oscillation frequencies are typically in the order of a few kA at some 100 Hz
for a single capacitor bank, and a few 10 kA at some 100 kHz for multiple back-to-back capacitor banks.
Voltage switching transients
Capacitor bank switching produces oscillating voltage transients which are reflected back onto the network supply.
The severity of this phenomenon can be lessened by reducing the capacitor bank peak inrush current.
Ip
13810.A
Inrush reactors
IEC 60871-1 specifies that the peak inrush current of a capacitor bank must not exceed 100 times
its rated nominal current.
If this value is likely to be exceeded, extra inductive reactance must be installed in-line with the
capacitor bank. This not only reduces the peak inrush current, but also dampens the effect of
transient overvoltages which occur at switch-on.
Fuse pre-melt figures and the making capacity of associated switchgear need to account for the
expected peak inrush current.
13811.A
Inrush reactors are constructed of a primary coil encapsulated in a resin case. Classified as an air core inductor, they
are rated according to the following electrical characteristics:
nominal voltage (kV) - must be equal to or greater than the system voltage
nominal current (A) - must be equal to or greater than the capacitor bank nominal current
inductance (µH)
Calculations: Re-rating a capacitor bank for specific voltage
To re-rate the power (Q) of a capacitor bank to match a specific system voltage:
Where:
Q1 = re-rated capacitor bank power at required system voltage
(kVAr)
Q2 = capacitor bank power at manufacturer's specified nominal
voltage (kVAr)
U1 = system voltage
U2 = capacitor bank nominal voltage
Exercise
A capacitor bank has a nominal power rating of 500 kVAr at 7.2 kV. Calculate the re-rated capacitor bank power
if used on a 6.6 kV system.
2
Q1 = Q2 × 1
2
= 500
= 500
NOTE
The capacitor bank nominal voltage rating is typically 1.2 times the system voltage, to protect against
transient and harmonic voltages. The capacitor bank power must be re-rated after selection.
U = 6.3 kV
Inom Ip
13812.A
Q = 250 kVAr
U = 6.3 kV
Inom Ip
L1 L2 L3 L4
13814.A
C1 C2 C3 C4
• capacitor banks C1, C2, C3, C4 are each rated for 900 kVAr at 7.2 kV.
• inrush reactance L1, L2, L3, L4 are each rated at 40 µH.
Step 1: Calculate the re-rated capacitor bank power (Q1) at system voltage (U1)
Q1 = re-rated capacitor bank power at required system voltage (kVAr)
Q2 = capacitor bank power at manufacturer's specified nominal voltage (kVAr)
U1 = system voltage
U2 = capacitor bank nominal voltage
Q1 U1
Q2 U2
U1
Q1 = Q2 ×
U2
= ×
900×0.766
689 kVAr
The re-rated power at 6.3 kV is 689 kVAr.
Step 3: Calculate the equivalent capacitance of banks which are switched in (C eq)
Ceq =C2+C3+C4
= 55+55+55
165 µF
The equivalent capacitance is 165 µF.
Step 4: Calculate the equivalent inductance of banks which are switched in (Leq)
1
Leq = 1+ 1+ 1
L2 L3 L4
= 1
1+ 1+ 1
40 40 40
= 40
3
=13.3 µH
The equivalent inductance is 13.3 µH.
2 55 × 165 1
= 6300 × × ×
3 55 + 165 40 + 13.3
2 9075 1
= 6300 × × ×
3 220 53.3
1
= 6300 × 0.67 × 41.25 ×
53.3
NOTE
When selecting line fuses for upstream protection, the fuse pre-melt figure must be greater than the
capacitor bank's peak inrush current.
If using a circuit breaker for upstream protection, the circuit breaker's making capacity at rated voltage
must be at least equal to the capacitor bank's peak inrush current.
4.5 Calculations
Transformer Calculations
Rated secondary current, Ir
A transformer's rated secondary current (Ir) is the maximum current it can supply before the output terminal voltage
starts to drop below its rated voltage (Ur). The rated secondary current can be calculated using the following
formula (assuming the applied primary voltage, U prim, is at its rated value).
Where
Ir = rated secondary current (A)
S = transformer power (kVA)
Ur = rated secondary voltage (kV)
13844.A
Ir (A)
S (kVA) Isc (A)
Z (%)
Short circuit current, Isc
Assuming the transformer is fed from an unlimited supply, the maximum short circuit current across the output
terminals (Isc) is determined by the impedance of the transformer (expressed as a percentage).
Percentage impedance (Z%) is calculated by shorting the output terminals of the transformer and increasing the
applied primary voltage (Uprim) from zero to a value where the rated current, Ir, flows through the secondary.
Percentage impedance is the ratio of applied primary voltage to rated primary voltage.
Example: If it takes 10% of the rated primary voltage to cause rated current to flow in the shorted secondary, the
percentage impedance Z=10%
Ir
A Short circuit
Uprim kV 1
Primary/secondary
13845.A
2
Z (%)
Where
Isc = transformer's maximum output short circuit current (A)
Ir = rated secondary current (A)
Z% = percentage impedance
The calculated short circuit current of a transformer, Isc is often used to rate the downstream distribution switchgear
it is feeding. In reality, the expected short circuit current at the switchgear installation will be less than the calculated
short circuit current, due to any impedance in the feeder circuit (ie impedance of feeder cables, switchgear, busbars
etc). All switchgear has a short-time withstand current rating (Ik), which is typically type tested for 3 seconds (tk).
Transformer
Ik > Isc
Switchgear installation
Isc
2
Ik
Q1 Q2 Q3
13847.A
Example
To calculate the short-time withstand current rating of the downstream switchgear, Ik, we must calculate the rated
secondary current and the short circuit current of the feeder transformer.
Transformer power S = 20 MVA
Secondary rated voltage Ur = 11 kV
Impedance Z% = 8%
Assume infinite power system.
U-int
Ir I-load
Load
Z-int
(Z%)
E Ur 1
13846.A
Where
Ir = rated secondary current (A)
S = transformer power (kVA)
Ur = rated secondary voltage (kV)
E = transformer internally generated EMF (kV)
Z% = percentage impedance (%)
Z-int = transformer internal impedance ()
U-int = internal voltage drop (kV)
I-load = load current (A)
Ur' = secondary output voltage due to overload (kV)
Example
Transformer power S = 30 MVA
Secondary rated voltage Ur = 6.6 kV
Impedance Z% = 10%
Assume infinite power system
Exercise
Calculate the transformer's output terminal voltage drop if the load was drawing 6000 A (I-load).
Motor Calculations
FLC T N
Load
Ur M 1
13848.A
P_IN P_LOSS P_OUT
Where:
Input power P_IN P_IN = electrical input power (kW)
Output power P_OUT P_OUT = mechanical output shaft power (kW)
P_OUT P_LOSS = motor losses (kW), ie iron, copper,
magnetic, friction, windage losses
Motor losses P_LOSS Ur = motor rated supply voltage (kV)
P_LOSS f = nominal rated supply frequency (Hz)
Motor efficiency eff eff = motor full load efficiency (p.u.)
FLC = motor full load current (A)
Motor full load current FLC p.f. = motor full load power factor (p.u.)
N = motor full load speed (rpm)
Motor full load speed N Ns = motor synchronous speed (rpm)
Motor synchronous speed Ns poles = number of motor stator poles
T = full load motor shaft torque (Nm)
slip = motor slip at full load (p.u.)
Exercise
For a motor running at full load, calculate the full load current, the total electrical input power and the amount of
full load slip, given that:
P_OUT = 2000 kW
Ur = 3.3 kV
f = 50 Hz
eff = 0.95
p.f. = 0.88
N = 1485 rpm
poles =4
N Ns 1slip
N
1 slip
Ns
N
slip 1
Ns
1485
1
1500
1 0.99
0.01 p.u.
Busbar Calculations
Busbar calculations verify the thermal and electrodynamic design limits, and check that no resonance will occur.
Thermal withstand
Rated current, Ir (A)
The rating of a busbar system depends on the material, shape, size and configuration of the individual busbars, as well
as the operating conditions. The calculated busbar rating per phase must be greater than the maximum expected
operating current.
249
. × n
0.61
×S0.5× P0.39 Where
I =K × I = maximum allowable current per phase (A)
p20× 1+ 20
K = total coefficient factor
e e = maximum allowable busbar temperature (°C)
n = nominal ambient temperature (40 °C)
p20 = resistivity at 20 °C:
copper = 1.83 cm; aluminium = 2.90 cm
α = temperature coefficient of resistivity = 0.004
a P = busbar perimeter, 2(e+a) (cm)
S = busbar cross-section, e· a (cm2)
13857.A
NOTE
When engaging parts with different coatings, or where one part is of bare material, the permissible
temperature and temperature rise shall be those of the surface material having the lowest permitted
value.
Exercise
Check that the busbar rating (per phase) is greater than the required e=1 e=1
nominal rating of Ir = 2000 A. The busbar system is installed in an
enclosed duct.
13858.A
K K1 K2 K3 K4 K5 K6
1.83 1 1 0.8 1 1
1.464
24.9 n
0.61
S 0.5 P 0.39
I K
p20 1 20
24.9 90 40
0.61
80.5 18 0.39
1.464
1.83 1 0.004 90 20
24.9 10.87 2.83 3.09
1.464
1.83 1.28
2366.87
1.464
2.34
1.464 1546.97
2264.77 A
This system is adequate. I > Ir, 2265 A > 2000 A.
Exercise
A busbar system has two copper bars per phase, with a short-time withstand rating of 31.5 kA for 3 seconds. Each
busbar is 8 cm wide and 1 cm deep. Calculate the total temperature of the busbar after a short circuit.
0.24 p20 Ith2 t k
sc
n S2 c
0.24 1.83 31.52 3
2 82 0.091 8.9
0.24 1.83 992.25 3
256 0.091 8.9
1307.39
207.33
6.31 °C
The short circuit temperature rise is 6.3 °C. The maximum allowable continuous temperature of the busbar
system is 90 °C. The potential total temperature after short circuit is 96.3 °C.
Insulator stand-offs and all other items in physical contact with the busbar must be able to withstand this
temperature.
Electrodynamic withstand
Electrodynamic forces
Busbars (parallel) Support
Ip Ip F1
h = e2
F
F1 H
F1 l
13873.A
d
13678.A
d
Multiplication factor Kn
Number of stand-offs 2 3 4 5
Multiplication factor Kn 0.5 1.25 1.10 1.14
The bending resistance of an individual insulator stand-off must be greater than the calculated absorbed force, F´.
The maximum allowable stress which a busbar can absorb, , is determined by the busbar material.
Where:
l = distance between insulator stand-offs on the same phase (cm)
V/I = inverse modulus of inertia for bars of the same phase (cm3)
14009.A
x' I/v cm3 50 32 19.2 16 9.6 12.5 10 7.5 6.25
Exercise
14011.A
for the installation.
15 cm 15 cm
Step 1: Calculate the forces between the parallel busbars of different phases.
Assume a short-time withstand current rating, Ik, of 31.5 kA at 50 Hz.
p k
2 78.752 10 2
F1l
V
12 I
66180 1
12 11.55
1
4406.67
11.55
381.53 daN/cm2
The stress imparted on the busbars is 381 daN/cm2.
The imparted stress is less than the maximum allowable stress for ¼ hard copper busbars: 381 < 1200 daN/cm2.
The busbar dimensions and material are suitable for the application.
Resonant frequency
The busbar system must be designed to avoid resonance at the nominal system frequency and twice this value. The
calculations should include some tolerance:
Where:
f = resonant frequency (Hz)
E = modulus of elasticity:
copper = 1.3 x 106 daN/cm2
aluminium = 0.67 x 106 daN/cm2
m = linear mass of busbar (daN/cm)
I = moment of inertia of the busbar cross-section, relative to the
perpendicular vibrating plane (cm4)
l = distance between insulator stand-offs of the same phase (cm)
Exercise
Verify the resonant frequency of the busbar system in the Exercise above.
The resonant frequency is well away from 50 Hz and 100 Hz. The busbar solution is suitable.
Formulae
Short circuit
NOTE
The switchgear “make rating” must be greater than the peak fault current, and the “break rating” must be
greater than the short circuit current..
Upstream network
Where:
Z = network short circuit impedance ()
Ssc = short circuit power (MVA)
U = system voltage (kV)
Reflecting the short circuit impedance of the upstream network through to the secondary of the transformer:
Where:
Zsc-sec = network short circuit impedance at the secondary of the
transformer ()
Zsc-prim = network short circuit impedance at the primary of the
transformer ()
Usec = transformer secondary voltage (kV)
Uprim = transformer primary voltage (kV)
The total impedance seen by a short circuit fault at the secondary terminals of the transformer is the sum of the
transformer impedance, Zsc-TR, and the short circuit network impedance at the transformer secondary (Zsc-sec).
Primary
1 Secondary
2
13849.A
Isc
Transformers
Where:
Zsc-TR = transformer output short circuit impedance ()
ZTR = transformer impedance ()
Usec = transformer secondary voltage (kV)
STR = transformer power (MVA)
Synchronous generator
Where:
Zsc-syn = synchronous machine short-circuit impedance ()
U 2 X
= syn syn Xsyn = synchronous reactance (%)
Ssyn 100
Usyn = synchronous machine output voltage (kV)
Ssyn = synchronous machine output power (MVA)
A synchronous machine has three stages of reactance during a short-circuit fault. The reactance is lowest at the
beginning of a fault, causing the highest level of short circuit current. From this level, the short circuit current decays
to a steady state.
Subtransient stage
This is usually the first few cycles of a fault occurrence. The peak short circuit current at this stage determines the
fault “make rating” of a circuit breaker, and the mechanical withstand.
Transient stage
This stage typically lasts for 10 to 20 power cycles and determines the thermal withstand and “break rating” of a
circuit breaker.
Permanent stage
This is the short circuit current level until the fault is interrupted by protection and clearing of the fault. In reality, this
stage never occurs as the fault is cleared beforehand.
C Transient stage
D Permanent stage
13850.A
Ir Isc
Time
Where:
Zsc-mtr = motor output short circuit impedance ()
Umtr = motor input voltage (kV)
Pmtr = motor rated power (kW)
An asynchronous motor will contribute approximately 4 to 6 times its rated current into a short circuit fault.
Cables
Busbars
Isc1
Transformer (TR):
CB1 CB2
Up = 36 kV
Us = 11 kV @ 50 Hz
S = 20 MVA
Z% = 10% 13851.A
Xd´´ = 15%
Xd´ = 20%
2
For the purposes of this calculation, ignore all impedances of circuit breakers, cables and busbars.
The first step is to calculate the individual impedances.
U2 Xd
S 100
2
11 20
15 100
1.6
The transient impedance is 1.6 .
Transformer impedance (ZTR):
1000 36
ZG
13852.A
Subtransient stage
CB2
ZNET
ZTR
13853.A
Isc2
ZTR
Subtransient stage
13854.A
Isc3
Case 2
1 Source
Feeder
Source (Network):
Up = 36 kV TR
Ssc = 1000 MVA
CB2
Transformer (TR):
Up = 36 kV
Us = 11 kV @ 50 Hz
S = 20 MVA
Z% = 10%
14006.A
CB1 CB3
Motor (M):
U = 11 kV @ 50 Hz Isc1
Isc3
P = 2000 kW
M
2
For the purposes of this calculation, ignore all impedances of circuit breakers, cables and busbars.
The first step is to calculate the individual impedances.
1000 36
ZM
13928.A
CB2
ZNET
ZTR
13853.A
Isc2
CB3
ZNET
ZM (ZNET ZTR)
ZM
ZM (ZNET ZTR)
ZTR
13929.A
Isc3
Mechanical Inspection
Location:
Date:
Inspection staff:
Cubicle serial number:
Contract:
Description Passed Comments
(Y/N)
Eye bolts fitted
Explosion vent flaps: screws fitted, holes taped
Holes not used for arc duct: filled with fixings
LV doors: cutouts
LV doors: opening and closing
VCB doors: opening and closing
Cable compartment doors: opening and closing
Door locks
Racking label
VCB locking label
Danger labels (front and rear)
Cable compartment door: "unlocking" label
VCB compartment: padlocking mechanism fitted and
operating
Shutter operation
Shutter danger labels
Earth switch: interlock with VCB
Earth switch: interlock with solenoid (use 'N/A/ if not
fitted)
Earth switch: operation
Earth switch auxiliaries (check alignment and
operation)
VCB: test racking
VCB: mechanical interlock
VT: test racking
Busbar GPO3 bushing plates
Screw bushings horizontal busbar (small / large)
All internal copper work
Horizontal busbar copper work and joints
Earth bars
Earth bar links
Rear cover
Fixings for rear cover
Panel builder check sheets
Keys for all access doors
Earth switch handle
Standard VCB racking handle
Rear busbar chamber covers and fixings
Cubicle joining bolts supplied
Electrical Inspection
Location:
Date:
Inspection staff:
Cubicle serial number:
Contract:
Electrical schematic drawing number
Control voltages required for testing
Description Passed Comments
(Y/N)
LV door apparatus
Voltage indicators
Selector switches
Keys for selector switches (Fortress or other)
Pushbuttons
Indicators (colours)
Control device door labels (functions)
Device numbering (internal)
Terminal numbering
CT test block assemblies
VT test block assemblies
Check MCB ratings
Power supply ratings and operation
110 VAC distribution
220 VAC distribution
110 VDC distribution
24 VDC distribution
LV door earth link
Heaters and thermostats
Heater operation
Check CT rating plates
Earth connection at CTs
Check VT rating plates
Earth switch auxiliary labels
VT fuses fitted in fixed VTs
Test sheets: VCB
Test sheets: withdrawable VT
Test sheets: fixed VT
Solenoid for earth switch interlock (use 'N/A' if not
fitted)
Solenoid on cable compartment door (use 'N/A' if
not fitted)
Programming relays
Test control wiring and VCB operation
Voltage test on fixed VTs
Voltage test on withdrawable VTs
Bushings for holes between cubicles
Drawings as-built information
Inter-cubicle cabling marked and ready for To be done on site
termination
62271-302 High voltage switchgear and controlgear: Alternating current circuit breakers
with intentionally non-simultaneous pole operation
62271-303 High voltage switchgear and controlgear: Use and handling of sulphur 61634
hexafluoride (SF6)
62271-304 High voltage switchgear and controlgear: Design classes for indoor enclosed 60932
switchgear and controlgear for rated voltages above 1 kV and up to and
including 52 kV to be used in severe climatic conditions
62271-305 High voltage switchgear and controlgear: Capacitive current switching capability
of air-insulated disconnectors for rated voltages above 52 kV
62271-310 High voltage switchgear and controlgear: Electrical endurance testing for circuit
breakers above a rated voltage of 52 kV
NOTE
Edition dates have been deliberately omitted from the IEC Standard Number. When referring to a
standard, always ensure you are using the latest edition.
IEC and IEEE have a cooperation agreement and some standards are jointly developed.
ANSI is the US representative to IEC.
In some cases, the requirements of similar standards from different organisations may conflict, or one standard may
include requirements not present in another standard.
NOTE
If equipment must comply with more than one standard, the requirements of each standard should be
individually checked.
NOTE
This list gives some examples of differences between major standards. Always refer to the specific
standard(s) for full details.
The standard value of rated duration for short-time withstand current is 1 second for IEC 62271-1, but
2 seconds for ANSI C37.20.3.
The acceptable limits for temperature rise of busbars are more stringent in ANSI C37.20.3 than
IEC 62271-1.
ANSI C37.20.3 stipulates design requirements (including materials, fusing and interlocking) that are not
present in IEC 62271.
ANSI and IEC stipulate different testing requirements and procedures.
Voltage
Operating voltage, U (kV)
This is the system's operating voltage at the point where the switchgear is installed. The operating voltage must
always be less than or equal to the rated voltage of the switchgear equipment.
Rated voltage, Ur (kV)
This is the maximum rms voltage the switchgear equipment can continuously operate at, under normal conditions.
The rated voltage is always higher than the systems operating voltage and determines the insulation levels of the
equipment.
Medium voltage, metal-enclosed switchgear is defined for use on operating voltages from1 kV to 52 kV. Within this
voltage range, IEC 62271-1 defines standard switchgear rated voltages as:
Series I equipment (used in European 50 Hz installations): 3.6, 7.2, 12, 17.5, 24, 36, 52 kV
Series II equipment (used in Non-European 60 Hz installations): 4.76, 8.25, 15, 15.5, 25.8, 27, 38, 48.3 kV
13856.A
conditions such as lightning. It is simulated using a standard
voltage waveform 1.2 µs 50 µs
Current
Operating current, I (A)
This is the maximum rms current expected to flow through the equipment. The operating current must always be
less than or equal to the rated current of the equipment.
Rated current, Ir (A)
This is the maximum rms current the equipment can continuously operate at, under normal conditions. This rating
is based on an ambient operating temperature of 40°C, within an allowable maximum temperature rise. For
temperatures above 40°C, switchgear rated current must be derated.
IEC 62271-1 specifies standard ratings as base 10 multiples of 1, 1.25, 1.6, 2, 2.5, 3.15, 4, 5, 6.3, 8
NOTE
Switchgear peak withstand current rating is commonly referred to as rated short circuit making capacity.
AC component
1
DC component
2
Ip = 2.5 x Ik
(f = 50 Hz)
2 x Ik
Fault current (kA)
13936.A
45 ms
Time (ms)
IP rating components
Characteristic 1 Characteristic 2 Additional Letter Supplementary Letter
0 Non-protected Non-protected A = back of hand H = high voltage apparatus
1 ≥ 50 mm diameter Vertically dripping B = finger M = motion during water test
2 ≥ 12.5 mm diameter Dripping at 15 ° tilt C = tool S = stationary during water test
3 ≥ 2.5 mm diameter Spraying D = wire W = weather conditions
4 ≥ 1.0 mm diameter Splashing
5 Dust-protected Jetting
6 Dust-tight Powerful jet
7 Temporary immersion
8 Continuous immersion
Source: IEC 60529
IEC 62271-1 specifies protection ratings for enclosures. Equipment designed for indoor installation is not typically
IP rated against ingress of water (a placeholder X is used instead of a rating for this characteristic):
NEMA Ratings
NEMA 250 is a product standard that addresses many aspects of enclosure design and performance.
NEMA Protection against solid objects Closest IP equivalent *
1 Indoor, protection from contact. IP 20
2 Indoor, limited protection from dirt and water. IP 22
3 Outdoor, some protection from rain, sleet, windblown dust and ice. IP 55
3R Outdoor, some protection from rain, sleet and ice. IP 24
4 Indoor or outdoor, some protection from windblown dust, rain, splashing IP 66
water, hose-directed water and ice.
4X Indoor or outdoor, some protection from corrosion, windblown dust, IP 66
rain, splashing water, hose-directed water and ice.
6 Indoor or outdoor, some protection from ice, hose-directed water, entry IP 67
of water when submerged at limited depth.
12 Indoor, protection from dust, falling dirt and dripping non-corrosive IP 54
liquids.
13 Indoor, protection from dust, spraying water, oil and non-corrosive liquids. IP 54
NOTE
* NEMA and IP ratings are not directly equivalent and this information provides an approximate correlation only.
5 Schematic Diagrams
5.1 Electrical Symbols - Common Switching Functions
The following table shows the standard IEC and ANSI symbols for common switching functions
IEC 60617-2 is a European standard. ANSI Y32.2 is a North American standard. As a general rule,
countries using a 50 Hz supply normally adhere to IEC standards and countries using a 60 Hz supply
normally adhere to ANSI standards.
Motor operated circuit breaker using voltage fed open and close command signals via momentary contact
pushbuttons
Auxiliary supply
6
Motor (spring charge)
1
Close shunt coil
5
Open shunt coil
MS MC MO Circuit breaker controller
14040.A
External trip contact (eg from MPR)
2 3 4
Magnetic operated circuit breaker using volt-free open and close command signals via bistable relay contacts
Auxiliary supply
S1 KA1 Circuit breaker control (open/close)
4 Circuit breaker controller
Q1-1 Q1-2 External trip contact (eg from MPR)
A Control supply
1 B Command inputs (common, close,
open)
A B
3
KA1
14041.A
2
Typically, command signals require an external voltage source and the contactor controller itself requires a separate
auxiliary voltage source. Depending on the contactor make and model, electrical options are available. Some
examples are:
Undervoltage shunt trip only used with DCO control
Lock-out solenoid needs to be externally energised before contactor main poles can be electrically
operated
Racking solenoid needs to be externally energised before a withdrawable contactor can be moved
between the test and service positions
Auxiliary contacts indicate the electrical state of the main contactor poles
Racking contacts indicate whether a withdrawable contactor is in the service or test position
Fuse blow indicator contacts indicate fuse condition. - operated by striker pin and only available on contactors
with integral medium voltage fuses
Auxiliary supply
KA1
Contactor controller
3
Control signal (maintained)
A B
14042.A
Auxiliary supply
3
Contactor controller
1
External trip contact (eg from MPR)
2
A Control supply
B Close input
A B C C Open input
14043.A
NOTE
For safety reasons, manual mode cannot be used in certain network configurations.
Overview
The following are examples of common operating modes in automatic changeover systems. Most ATS controllers
can be programmed to operate in any one of these modes.
N1+N2
N1 N2
K1 K2
14044.A
DB
N1+G
N1 G
K1 K3
14045.A
DB
AUTO mode:
N1 is the prioritised power source and, if healthy, will always supply the receiving network (DB). If power source
N1 is lost, the controller commands the standby generator to start. Once the generator is at correct voltage and
frequency, power source G is switched in to supply the receiving network (DB). The controller switches back to
N1 once it has been re-established.
MANUAL mode:
Select N1 or G as the power source.
N1+N2+N3
N1 N2 N3
K1 K2 K3
14046.A
DB
N1+N2+G
N1 N2 G
K1 K2 K3
14047.A
DB
N1+N2+S
N1 N2
K1 K2
S
14048.A
DB1 DB2
AUTO mode:
Providing power sources N1 and N2 are healthy, N1 will supply network DB1 and N2 will supply network DB2.
Bus coupler S will remain open.
If power source N1 is lost, this supply is isolated and bus coupler S is closed. Power source N2 now supplies
networks DB1 and DB2. Once power source N1 is re-established, bus coupler S is opened and N1 will supply
network DB1 and N2 will supply network DB2.
If power source N2 is lost, this supply is isolated and bus coupler S is closed. Power source N1 now supplies
networks DB1 and DB2. Once power source N2 is re-established, bus coupler S is opened and N1 will supply
network DB1 and N2 will supply network DB2.
MANUAL mode:
Select N1 and N2 as power sources with bus coupler S open.
Select power source N1 with bus coupler S closed and power source N2 isolated.
Select power source N2 with bus coupler S closed and power source N1 isolated.
E3 panel option
The standard E3 panel option consists of a combined main isolator/earth switch, a main and bypass contactor and a
set of MV fast-acting line fuses (R-rated). Refer to the MVS section for details of optional panel equipment.
The panel can be supplied in a stand-alone format or with rear, horizontal busbars for an MCC switchgear line-up.
2
Q1
L1A L1
2 F1 1 T1
L1B
L2A L2
2 F2 1 T2
L2B
F3 L3A L3 1
2 1 T3
L3B
E
K1
2 1
4 3
6 5
3 A1
U1 T1 T1 L1
M1
T1B
M V1 T2 T2 L2
3 T2B
W1 T3 T3 L3
T3B
K2
2 1
4 3
6 5
14049.A
E2 panel option
The standard E2 panel option consists of a main and bypass contactor. A means of isolation and earthing, as well
as some form of line protection, must be supplied and installed separately, upstream of the E2 panel. Refer to the
MVS section for details of optional panel equipment.
L1
L2
L3
1
E
K1
2 1
4 3
6 5
3 A1
U1 T1 T1 L1
M1
T1B
M V1 T2 T2 L2
3 T2B
W1 T3 T3 L3
T3B
K2
2 1
4 3
6 5
14050.A
2 1
4 3
6 5
3
14051.A
Q2
2 1
4 3
6 5
A1
L1 T1
L2 T2
L3 T3
U3 U2 U1
M1 3
T1
M T2
3
T3
Q3
14052.A
6 Resources
NOTE
AuCom reserves the right to modify or change the specification of its products at any time without
notice.
MEDIUM VOLTAGE
CONTENTS
Contents
Introduction ......................................................................................................................................2
1.1 Scope .............................................................................................................. 2
1.2 Supplier Qualifications..................................................................................... 2
1
INTRODUCTION
Introduction
1.
1.1 Scope
This document specifies the minimum requirements for a solid state reduced
voltage motor starter for medium voltage application.
The solid state reduced voltage starter shall control three phases at ____ V,
___ Hz and shall be rated to suit the application and motor characteristics. Where
possible motor and load curves will be provided and the supplier will use this data
to justify selection. The starter shall provide soft starting and soft stopping of the
motor as required.
The manufacturer shall have produced solid state reduced voltage starters for a
minimum of 20 years.
2
ENVIRONMENTAL SPECIFICATIONS
Environmental Specifications
2.
The equipment shall be suitable for use at temperatures from -10 ºC to +60 ºC.
The equipment shall be suitable for operation at altitudes up to 1000 m above sea
level without derating.
The equipment shall be suitable for use in environments with relative humidity
between 5% and 95% (non-condensing).
The thyristor assembly for each phase shall consist of a discrete module, and be
individually replaceable
2.3 Safety
The equipment shall employ only air insulation between phases.
The IP00 starter should be capable of being enclosed without any additional
clearances at the side of the product.
The equipment shall provide means to safely test its correct installation:
• The equipment shall provide a means to test the installation using a low
voltage motor.
• The equipment shall provide a means to test operation of all control circuitry
and protection mechanisms, without connection to medium voltage. Functions
to be tested include, at minimum:
• motor starting
• motor stopping
• protection activation
3
LOGIC CONTROL CONFIGURATION
The control interface shall provide a means for an operator to quickly access and
configure parameters.
The control interface shall provide an operator with a short list of critical
parameters for common applications, including:
• pump
• fan
• compressor
• generic
The equipment shall permit the operator to save the current configuration to an
internal file. There shall be two files available.
The equipment shall permit the operator to reload a previously saved configuration
set from an internal file. There shall be two files available.
The equipment shall support remote management via a control network with a
choice of Modbus, Profibus and Devicenet as a minimum.
The equipment shall provide an on-board real-time clock; but failure of this clock
due to low battery shall not trip the starter.
4
LOGIC CONTROL CONFIGURATION
The equipment shall provide a kickstart option for starting the motor.
The equipment shall permit the user to select between multiple profiles for stopping
the motor.
The equipment shall provide a feedback ramp option for stopping the motor.
The equipment shall be suitable for use with dual-speed and slip-ring motors
Thermal modeling that allows the soft starter to dynamically calculate the motor
temperature, predict the motors available thermal capacity, to predict whether the
motor can successfully complete a start.
5
LOGIC CONTROL CONFIGURATION
The equipment shall provide at least three additional relays with user-selectable
functionality, enabling indication of:
• Ready state
• Low current state
• High current state
• Motor temperature state
• Trip states (with adjustable delays);
• Motor overload
• Current imbalance
• Undercurrent
• Instantaneous overcurrent
• Mains frequency
• Ground fault
• Time-overcurrent
• SCR overtemperature
• Phase loss
• Motor thermistor
• Undervoltage
6
LOGIC CONTROL CONFIGURATION
The equipment shall record full details of its state at the time of every protection
activation. The recorded details shall include, at minimum:
• time and date stamp.
• protection type
• motor operating status
• mains frequency
• line current
• line voltage
The equipment's protection log shall store no fewer than eight trips.
7
SUPPORT AND SERVICES
4.1 Commissioning
The equipment supplier shall be capable of providing commissioning of the
equipment.
4.2 Documentation
The equipment shall be provided with a complete set of user and support
documentation, including:
• User manual
• Recommended list of spare parts
• Schematic & GA drawings
4.3 Training
The equipment supplier shall be capable of providing a complete training schedule
with the equipment.
The equipment supplier shall undertake to deliver the complete training programme
if required by the customer.
The training programme shall deliver to the customer the skills to:
• appropriately programme the equipment to meet customer requirements
• safely commission the equipment
• safely operate the equipment
• identify and rectify operating problems caused by incorrect programming
• identify and diagnose operating problems caused by faulty equipment
The supplier shall guarantee to provide servicing support for the equipment for a
period of not less than 10 years.
8
SPECIFICATION:
MEDIUM VOLTAGE
CONTENTS
Contents
Introduction ......................................................................................................................................2
1.1 Scope .............................................................................................................. 2
1.2 Supplier Qualifications..................................................................................... 2
1.3 Starter Ratings ................................................................................................ 2
1
INTRODUCTION
Introduction
1.
1.
1.1 Scope
This document specifies the minimum requirements for a solid state reduced
voltage motor starter for medium voltage application.
The solid state reduced voltage starter shall control three phases at ____ V,
___ Hz and shall be rated to suit the application and motor characteristics. Where
possible motor and load curves will be provided and the supplier will use this data
to justify selection. The starter shall provide soft starting and soft stopping of the
motor as required.
The manufacturer shall have produced solid state reduced voltage starters for a
minimum of 20 years.
The supplier must be able to provide documentation confirming that the equipment
is correctly rated and fit for purpose.
2
ENVIRONMENTAL SPECIFICATIONS
Environmental Specifications
2.
The equipment shall be suitable for use at temperatures from -10 ºC to +60 ºC.
The equipment shall be suitable for operation at altitudes up to 1000 m above sea
level without derating.
The equipment shall be suitable for use in environments with relative humidity
between 5% and 95% (non-condensing).
The thyristor assembly for each phase shall consist of a discrete module, and be
individually replaceable
• All panels must provide separate chambers for all main sections including Bus
bars, Line Contactor, Soft starters and LV control. The entire panel, including
inter-chamber, must be arc fault certified to 31.5kA for 1 seconds.
3
ENVIRONMENTAL SPECIFICATIONS
The equipment shall provide means to safely test its correct installation:
1. The equipment shall provide a means to test the installation using a low
voltage motor.
2. The equipment shall provide a means to test operation of all control circuitry
and protection mechanisms, without connection to medium voltage. Functions
to be tested include, at minimum:
• motor starting
• motor stopping
• protection activation
NOTE
For installations with motor FLC >160 A, the line and bypass contactors must be replaced by a
withdrawable and fixed circuit breaker respectively.
4
LOGIC CONTROL CONFIGURATION
Remote control of the starter shall be possible using either two or three wire
control.
The control interface shall provide a means for an operator to quickly access and
configure parameters.
The control interface shall provide an operator with a short list of critical
parameters for common applications, including:
• pump
• fan
• compressor
• generic
The equipment shall permit the operator to save the current configuration to an
internal file. There shall be two files available.
The equipment shall permit the operator to reload a previously saved configuration
set from an internal file. There shall be two files available.
The equipment shall support remote management via a control network with a
choice of Modbus, Profibus and DeviceNet as a minimum.
The equipment shall provide an on-board real-time clock; but failure of this clock
due to low battery shall not trip the starter.
5
LOGIC CONTROL CONFIGURATION
The equipment shall provide a kick-start option for starting the motor.
The equipment shall permit the user to select between multiple profiles for stopping
the motor.
The equipment shall provide a feedback ramp option for stopping the motor.
The equipment shall be suitable for use with dual-speed and slip-ring motors
Thermal modeling that allows the soft starter to dynamically calculate the motor
temperature, predict the motors available thermal capacity, to predict whether the
motor can successfully complete a start.
6
LOGIC CONTROL CONFIGURATION
The equipment shall provide at least three additional relays with user-selectable
functionality, enabling indication of:
• Ready state
• Low current state
• High current state
• Motor temperature state
• Trip states (with adjustable delays);
• Motor overload
• Current imbalance
• Undercurrent
• Instantaneous Overcurrent
• Mains frequency
• Ground fault
• Time-overcurrent
• SCR over temperature
• Phase loss
• Motor thermistor
• Undervoltage
7
LOGIC CONTROL CONFIGURATION
The equipment shall record full details of its state at the time of every protection
activation. The recorded details shall include, at minimum:
• time and date stamp.
• protection type
• motor operating status
• mains frequency
• line current
• line voltage
The equipment's protection log shall store no fewer than eight trips.
8
SUPPORT AND SERVICES
4.1 Commissioning
The equipment supplier shall be capable of providing commissioning of the
equipment.
4.2 Documentation
The equipment shall be provided with a complete set of user and support
documentation, including:
• User manual
• Recommended list of spare parts
• Schematic & GA drawings
4.3 Training
The equipment supplier shall be capable of providing a complete training schedule
with the equipment.
The equipment supplier shall undertake to deliver the complete training programme
if required by the customer.
The training programme shall deliver to the customer the skills to:
• appropriately programme the equipment to meet customer requirements
• safely commission the equipment
• safely operate the equipment
• identify and rectify operating problems caused by incorrect programming
• identify and diagnose operating problems caused by faulty equipment
The supplier shall guarantee to provide servicing support for the equipment for a
period of not less than 10 years.
9
SPECIFICATION:
MEDIUM VOLTAGE
CONTENTS
Contents
Introduction ......................................................................................................................................2
1.1 Scope .............................................................................................................. 2
1.2 Supplier Qualifications..................................................................................... 2
1
INTRODUCTION
Introduction
1
1.1 Scope
This document specifies the minimum requirements for power factor correction
when used in conjunction with electronic soft starters.
2
ENVIRONMENTAL SPECIFICATIONS
Environmental Specifications
2
The equipment shall be suitable for use at temperatures from -10 ºC to +60 ºC.
The equipment shall be suitable for operation at altitudes up to 1000 m above sea
level without derating.
The equipment shall be suitable for use in environments with relative humidity
between 5% and 95% (non-condensing).
The integrated power factor panel must be enclosed up to IP4X and include:
• All panels must provide separate chambers for all main sections including
Busbars, Contactor, Capacitors. The entire panel, including inter-chamber,
must be arc fault certified to 31.5kA for 3 seconds.
3
SUPPORT AND SERVICES
3.1 Documentation
The equipment shall be provided with a complete set of user and support
documentation, including:
• User manual
• Recommended list of spare parts
• Schematic & GA drawings
3.2 Training
The equipment supplier shall be capable of providing a complete training schedule
with the equipment.
The equipment supplier shall undertake to deliver the complete training programme
if required by the customer.
The training programme shall deliver to the customer the skills to:
• appropriately programme the equipment to meet customer requirements
• safely commission the equipment
• safely operate the equipment
• identify and rectify operating problems caused by incorrect programming
• identify and diagnose operating problems caused by faulty equipment
The supplier shall guarantee to provide servicing support for the equipment for a
period of not less than 10 years.
IEC 62271-200
IEC 60947-4-2
IEC 60664
IEC 60529
NZS4219
IEEE 242
IEC60871
CE EMC EU Directive
C -tick EMC Requirements
Marine Lloyds
4
SPECIFICATION:
Switchgear
MEDIUM VOLTAGE
CONTENTS
Contents
Introduction ......................................................................................................................................2
1.1 General ............................................................................................................ 2
1.2 Submission ...................................................................................................... 2
1.3 Quality Assurance ........................................................................................... 2
Documentation .................................................................................................................................3
2.1 Drawings ......................................................................................................... 3
2.2 Project Manuals............................................................................................... 3
2.3 Factory Testing & Commissioning Test Sheets .............................................. 3
1
INTRODUCTION
Introduction
1.
1.1 General
This Section defines the general requirements for MV switchgear and associated electrical works.
This specification, used in conjunction with purchase documents, data sheets, and / or drawings
establishes the minimum requirements for the design, fabrication and testing of the switchgear
aspects of the work for the Plant.
• Reference to other industrial standards for compliance shall be interpreted as an integral part of
this specification.
• The Contractor / Supplier shall be responsible for obtaining from the Client all necessary
approvals and information required to complete the Works.
• All electrical work shall be carried out in accordance with local regulations or other recognized
international standards.
• The approval of equipment and material by the relevant authority shall not prejudice the rights of
the Client to reject such equipment or material that does not comply with the specification.
• If required the Contractor / Supplier shall engage professionally qualified specialists/experts to
carry out any special activities associated with the provision of special electrical equipment and
to comply with all local relevant regulations.
1.2 Submission
The Contractor / Supplier shall submit designs, drawings, data, documents and other such
information as specified and required for the Client's review.
All submittals shall be in English.
The Client will either:
1. Review the submittal; or
2. Review the submittal subject to notations; or
Where the submittal is reviewed, it will be so endorsed by the Client and one copy returned to the
Contractor / Supplier.
The Contractor / Supplier shall make the required alterations and transmit the required copies of the
altered submittal.
All work under the Contract shall comply in all respects with the submittals reviewed by the Client
described above.
Review by the Client of any drawing, method of work, or any information regarding materials and
equipment the Contractor proposes to furnish, shall not relieve the Contractor / Supplier of
responsibility for any errors therein and shall not be regarded as an assumption of risks or liability.
Such acceptance shall be considered to mean only that the Client has no objection to the Contractor
/ Supplier using, upon the Contractor's own full responsibility, the plan or method of work proposed,
or furnishing the materials and equipment proposed.
1.3 Quality Assurance
The Contractor / Supplier shall be ISO 9000 certified. The Contract / Supplier must provide
certification compliance and demonstrate this to the Client.
2
DOCUMENTATION
Documentation
2.
2.1 Drawings
Unless approved by the Client, all drawings shall be prepared using AutoCAD or an approved
computer aided drafting (CAD) package. All drawings shall be A3 size
CAD files of all the Contract Drawings will be provided to the Contractor / Supplier upon receipt of
the Contractor's / Suppliers written request.
Electrical wiring and circuit diagrams shall be neat, clear, un-crowded and shall show all equipment
using standard symbols. All electrical equipment wiring and terminals shall be numbered in
accordance with the Specification requirements.
3
ELECTRICAL SUPPLY
Electrical Supply
3.
3.1 General
The main power supply to the plant shall be from the power supply authority at XXkV
All equipment provided under this Contract shall be suitable for continuous operation at the voltage
and conditions noted below. Compliance is required to clause 9.101 of IEC 62271-200; “Information
with enquiries and orders”
All equipment and work associated with the Contract shall be entirely suitable for operation on the
plant power supply systems as specified; and tabled below
Nominal voltage between phases xxkV
Number of Phases 3
System fundamental frequency TBA Hz
System Neutral TBA
Design Fault Level xx kA for xx sec
Loss of Service Continuity Category TBA
Internal Arc Classification TBA
3.2 Standards
The work, equipment and other items shall comply with the requirements of relevant IEC and other
nominated standards, codes and regulations; including those referenced throughout the
Specification and any other Authorities having jurisdiction over any portion of the work, and on the
method of performing such work.
Where there is any discrepancy between the referenced standards and this Specification (and
associated Contract Drawings), the requirements of this Specification (and associated Contract
Drawings) shall have precedence.
3.2.1 Switchgear
Designed to:
a) Switchgear and apparatus IEC62271-1
IEC62271-200
IEC62271-304
GB3906 (2006)
DL-T-404
DL-T-593
b) Internal arc resistance IEC62271-200
Annex A.6, criteria 1 to 5
c) Levels of insulation (coordination guide) IEC60071
d) Degrees of protection IEC60529
e) Seismic The Uniform Building code,
Section 1629.6.8
IEC60721-2-6, Table 1 for static
load test
f) Drilled holes and screw connections for busbars DIN43673-1
g) Classification of groups of environmental parameters IEC60721-3-1
and their severities – Storage
h) Classification of groups of environmental parameters IEC60721-3-2
and their severities – Transportation IEC60068-2-32
i) Classification of groups of environmental parameters IEC60721-3-3
and their severities –
Stationary use at weather protected locations
4
ELECTRICAL SUPPLY
3.2.2 MV Equipment
a) Circuit breakers IEC62271-100
b) Alternating current disconnectors and earthing IEC62271-102
switches
c) Contactors IEC60470
d) Fuses IEC60282-1
e) PFC capacitors IEC60871-1
f) Current transformers IEC60044-1
g) Voltage transformers IEC60044-2
h) Current sensors IEC60044-8
i) Voltage sensors IEC60044-7
3.2.3 LV Equipment
a) LV Switchgear and Controlgear Part 1 General Rules IEC60947-1
b) LV Switchgear and Controlgear Part 2 Circuit breakers IEC60947-2
c) LV Switchgear and Controlgear Part 5-1 Control circuit IEC60947-5-1
devices etc
d) LV Switchgear and Controlgear Part 7-1 Auxiliary IEC60947-7-1
equipment, terminal blocks
All equipment provided shall be painted or protected against nominated corrosive environments. The
Contractor /Supplier to specify the coating system provided.
Anti-corrosive paint to a minimum thickness of 50 micron shall be applied to the cleaned metal
surface. The finish shall be resistant to the harmful effects of the specified environment.
Unless otherwise specified or shown on the Drawings, all electrical, control system and
instrumentation equipment and enclosures shall have the following minimum protection ratings:
• IP4X for equipment, cubicles, panels and switchgear enclosures mounted in indoor air
conditioned switch rooms or other non-process conditioned rooms.
3.4 Material Quality
Materials selected shall be new, free from manufacturing defects, and suitable for undiminished
performance for the design life of the plant.
Materials shall be “fire resistant”, non-flame-propagating and waterproof.
5
ELECTRICAL SUPPLY
Glass fiber and plastic material shall withstand the operating temperatures and exposure to sunlight.
Appropriate measures shall be taken to prevent chemical deterioration of the contact surfaces.
MV SWITCHBOARD
1. The “metal enclosed” MV Switchboard under this contract shall comprise the panels as shown
on the drawings and / or schedules.
2. The switchboard shall comply with the latest issue of IEC 62271-1 and IEC 62271-200 and with
the nominated IP rating against the external environment
3. The switchboard shall be of the modular “metal enclosed” floor mounted, extensible type
equipped with circuit breakers, busbars. instruments. relays and all accessories as is described
in the specifications hereinafter and the Drawings.
4. All cubicles shall be of standard pattern and dimensions, robust in construction; dust and vermin
proof. and suitable for indoor use. The design of the cubicles and associated equipment shall be
such as to enable extensions to be made at either end.
5. The switchboard cubicles shall have separate compartments for the switchgear, busbars, cable
termination, relays and controls. The compartment shall restrict access to that area described
above only.
6. Pressure relief flaps shall be provided on the top of each HV cubicle to relief excess pressure
deeming an internal fault.
7. All circuit breakers or contactors shall be of the withdrawable isolating type. with the trucks
identical and interchangeable in every switchgear cubicle. A positive guide shall be provided for
the truck entry into the cubicle and clear indications given when the truck is at the engaged
position.
6
ELECTRICAL SUPPLY
9. Circuit breaker truck shall only be movable from engaged position to isolated position and vice
versa only when the circuit breaker is open.
10. Circuit breaker truck shall be locked in cubicle panel while the circuit breaker remains closed,
11. Circuit breaker cannot be closed unless the circuit breaker truck is in the fully engaged position.
3.7 Shutters
1. During the isolation of the circuit breaker, the busbars and cable orifices shall be automatically
covered by self-closing shutters. The shutters for the busbar and cable orifices shall be
independent of each other so that one can be opened manually without interfering with the other.
2. Provision shall also be provided for padlocking the shutters. All busbars or cable orifices shall
have prominent markings or labelling to clearly identify them. The safety shutters shall be
metallic type and shall be earthed.
7
ELECTRICAL SUPPLY
4. All current transformers (C.Ts) shall be of the epoxy- resin encapsulated type and shall conform
to the requirements of IEC 60044-1, for the type of duty required.
5. The CT’s shall be installed on the side of the circuit breaker remote from the busbars. The
primary winding shall be of the bar type and of approved cross-section compatible with the circuit
breaker rating.
6. The secondary windings of each set of C.Ts shall be earthed at one point.
7. C.Ts. for protective purposes shall be of the nominated protection Class, rated burden and
saturation factor sufficient to cater for the normal relay settings and load burdens required in the
protection scheme.
8. Current transformers used for metering and indicating instruments shall have accuracy not less
than the nominated; typically Class 0.5 and Class 1.0 respectively. Each transformer shall be
capable of providing the necessary VA to operate the related instruments.
3.12 Labels
1. Each item of equipment shall carry the manufacturer's rating plates, with information and
compliance with the relevant standard.
2. Further labelling shall be provided to indicate the main functions of each service and control
equipment item.
3. All wiring terminal positions and terminations shall be identified by local labels to indicate the
group services, e.g. closing, tripping, etc. This shall be in addition to the cable ferrule method.
8
RESOURCES
NOTE
This table does not provide a one-to-one correspondence between AWG and metric cables. This table
states the smallest standard metric cable which will provde at least as much carrying capacity as the AWG
cable. To substitute an AWG cable for a specified metric cable, use an AWG cable with the same or
greater cross-section.
6.4 Incoterms
International Commercial terms (Incoterms) are published by the International Chamber of Commerce, and define
the responsibilities, costs and risks associated with the transportation and delivery of goods.
Key Incoterms for AuCom supplied equipment are:
EXW Buyer arranges carriage from named place of delivery.
Ex Works Buyer assumes risk when goods are made available.
(named place of delivery) Buyer assumes costs when goods are made available.
CIP Seller arranges and pays for transportation and insurance to named port of
Carriage and Insurance Paid to destination.
(named place of destination) Buyer assumes risk when goods are received at the carrier.
Buyer assumes costs when goods reach the named destination.
CIF Seller arranges and pays for transportation and insurance to named
Cost, Insurance and Freight destination.
(named port of destination) Buyer assumes risk when goods are loaded on board the ship at the point
of departure.
Buyer assumes costs when goods reach the named port of destination.
DDP Seller arranges carriage to the named place of destination, ready for
Delivered Duty Paid unloading.
(named place of destination) Buyer assumes risks when goods are available for unloading at the named
place of destination.
Buyer assumes costs when goods are available for unloading at the named
place of destination.
7 References
ABB (2000), MWD Surge Arrestors (CHHOS/AR 3209.00E).
ABB (2006), ABB Switchgear Manual, 11th Edition.
http://www02.abb.com/global/seitp/seitp161.nsf/0/bf1431b2c459e7a3c1256f5d004a29bb/$file/index_abb_en.html
ABB (2007), Fuses (Catalogue 3405PL004-W1-en).
ASTM (2002), Standard specification for standard nominal diameters and cross-sectional areas of AWG sizes of solid
round wires used as electrical conductors.
BIPM (International Bureau of Weights and Measures), http://bipm.org.
Copper Development Association (2001), Copper for Busbars.
http://www.copperinfo.co.uk/busbars/pub22-copper-for-busbars/homepage.shtml
http://www.copperinfo.co.uk/busbars/pub22-copper-for-busbars/homepage.shtml
IEC (2003), IEC 60044-1. Instrument transformers - Part 1: Current transformers.
IEC (2003), P-IEC 60044-2. Instrument transformers - Part 2: Inductive voltage transformers.
IEC (2004), IEC-60228. Conductors of insulated cables.
IEC (2009), IEC 60255-1. Measuring relays and protection equipment - Part 1: Common requirements.
IEC (1988), P-IEC 60255-6. Electrical relays - Part 6: Measuring relays and protection equipment.
IEC (2005), IEC 60871-1. Shunt capacitors for AC power systems having a rated voltage above 1000 V - Part 1:
General.
IEC (2007), IEC 61869-1. Instrument transformers - Part 1: General requirements.
IEC (2011), IEC 61869-3. Instrument transformers - Part 3: Additional requirements for inductive voltage
transformers.
IEC (2007), IEC 62271-1. High-voltage switchgear and controlgear - Part 1: Common specifications.
IEC (2008), IEC 62271-100. High-voltage switchgear and controlgear - Part 100: Alternating current circuit breakers.
IEC (2011), IEC 62271-102. High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors
and earthing switches.
IEC (2011), IEC 62271-106. High-voltage switchgear and controlgear - Part 106: Alternating current contactors,
contactor-based controllers and motor-starters.
IEC (2011), IEC 62271-200. High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and
controlgear for rated voltages above 1 kV and up to and including 52 kV.
IEC (2006), IEC 62271-202. High voltage switchgear and controlgear - Part 202: High-voltage/low-voltage
prefabricated substation.
IEEE (2008), C57.13-2008. IEEE Standard Requirements for Instrument Transformers.
Melsom, S.W. and Booth, H.C. (1922), The Efficiency of Overlapping Joints. JIEE 60, 889-899.
Schneider Electric (2000), Medium Voltage Technical Guide (AMTED300014EN).