Assignment 2365 Design
Assignment 2365 Design
Question:
Draw a fully labelled circuit diagram illustrating the three-phase 400V supply
system and earthing arrangement for the EV charging equipment. The diagram
must show the total earth fault loop path.
Placement Criteria:
C) Placement of Luminaires
Question 3:
Selection of Circuit Protective Devices:
Based on the design specifications and the final circuits provided, the following circuit
protective devices are selected:
Key Considerations:
• Breaking Capacity: All devices must have a breaking capacity of at least 3.7 kA to handle the
prospective short-circuit current.
• RCD Protection: All socket circuits and circuits in special locations (e.g., bathrooms, pool area)
require 30 mA RCD protection.
• Type of MCB/RCBO: Type B for general circuits, Type D for circuits with high inrush currents
(e.g., motors, pumps).
This selection ensures compliance with BS 7671 and the design specifications provided in the assignment.
Café & Kitchen Area Circuits in the same layout as the Pool Area Circuits:
Café & Kitchen Area Circuits Device Rating Breaking Additional Notes
Type Capacity Protection
- Circuit break 1 (1 MCB 6A ≥ 3.7 kA None General
connection) (Type B) lighting
circuit.
- Emergency light circuit 1 MCB 6A ≥ 3.7 kA None Emergency
(8 connections) (Type B) lighting
circuit.
- Emergency light circuit 2 MCB 6A ≥ 3.7 kA None Emergency
(5 connections) (Type B) lighting
circuit.
- Emergency light circuit 3 MCB 6A ≥ 3.7 kA None Emergency
(5 connections) (Type B) lighting
circuit.
- Light circuit 1 (6 MCB 6A ≥ 3.7 kA None General
connections) (Type B) lighting
circuit.
- Light circuit 2 (6 MCB 6A ≥ 3.7 kA None General
connections) (Type B) lighting
circuit.
- Light circuit 3 (7 MCB 6A ≥ 3.7 kA None General
connections) (Type B) lighting
circuit.
- Socket circuit 1 (10 RCBO 32 A ≥ 3.7 kA 30 mA Sockets
connections) (Type A) RCD require RCD
protection.
- Socket circuit 2 (4 RCBO 20 A ≥ 3.7 kA 30 mA Sockets
connections) (Type A) RCD require RCD
protection.
- Unswitched fused RCBO 20 A ≥ 3.7 kA 30 mA Requires
connection circuit (1 (Type A) RCD RCD
connection) protection.
- Radial double socket x 2 RCBO 16 A ≥ 3.7 kA 30 mA Sockets
for fridges (Type A) RCD require RCD
protection.
- Radial double socket for RCBO 16 A ≥ 3.7 kA 30 mA Sockets
food holding unit (Type A) RCD require RCD
protection.
- Radial double socket for RCBO 16 A ≥ 3.7 kA 30 mA Sockets
dishwasher (Type A) RCD require RCD
protection.
- Socket to connect the RCBO 32 A ≥ 3.7 kA 30 mA Sockets
cooker (Type A) RCD require RCD
protection.
- Radial double socket RCBO 20 A ≥ 3.7 kA 30 mA Sockets
circuit (2 connections in (Type A) RCD require RCD
seating area) protection.
- Radial lighting circuit in MCB 6A ≥ 3.7 kA None General
seating area (Type B) lighting
circuit.
(Type B MCB 32 A)
(Type A RCBO 30 mA/16 A)
(Type B 6A RCBO)
Summary
All circuits meet the required standards for:
Question 5: Determine the minimum possible cross-sectional area of the CPC for
one of the circuits supplying the fridges, satisfying the requirements for
disconnection as ADS under earth fault conditions and the adiabatic equation as
per Regulation 543.1.3 in BS 7671.
Circuit Details
Where:
For a 16A Type B MCB, the maximum Zs is 2.87 Ω (from Table 41.3, BS 7671). Since the
calculated Zs=0.12 ΩZs =0.12Ω, the circuit satisfies the disconnection requirement.
Where:
Final Answer
The minimum possible cross-sectional area (CSA) of the CPC for the fridge circuit is
6 mm². This satisfies both:
Summary
• Maximum Demand Before Diversity: 292A - Maximum Demand After Diversity: 240.6A
Explanation:
1. Electrical Separation:
a. Shaver points typically use a double-wound isolating transformer.
b. This means the input supply (230V) and the output supply (e.g., 115V or 230V) are not
directly connected.
c. The transformer separates the user from the mains supply, so there's no direct path for
electric current to flow through a person to the earth.
2. Low Power:
a. Shaver sockets are designed for low-power devices only (like shavers or electric
toothbrushes).
b. Lower power reduces the risk of dangerous currents.
3. Built-in Protection:
a. The transformer inside the shaver point includes thermal protection or a fuse.
b. If the transformer overheats or develops a fault, the power supply is automatically
disconnected.
4. Double Insulation:
a. Shaver points are often double insulated, meaning no exposed conductive parts can
come into contact with live parts.
b. This adds another layer of protection against electric shock.
5. No Earth Connection Needed:
a. The output from the transformer is isolated, from earth connection.
b. Even if you accidentally touch one of the live terminals, there's no complete circuit for
current to flow through your body to earth.
• Where PME conditions apply: The minimum CSA for main protective bonding
conductors is 10 mm² (or as calculated by the adiabatic equation). This is
specified in Table 54.8, Note 2 of the On-Site Guide.
• For non-PME applications: The minimum CSA is 6 mm² (or as calculated by the
adiabatic equation). This is also specified in Table 54.8, Note 2.
3. Functional Earth
• The minimum CSA for functional earth conductors is typically 2.5 mm² (or as
specified by the manufacturer). This is referenced in Section 5.4 of the On-Site
Guide.
4. Earthing Conductor
• Example: Switch for the air handling unit in the café kitchen.
• Further Requirements:
o The switch must be easily accessible and located within 2 meters of the
equipment to allow quick access during maintenance.
o It must be capable of switching the full load current of the equipment.
For example, if the air handling unit has a load current of 16A, the switch
must be rated for at least 16A.
o The switch must be clearly labelled to indicate its purpose (e.g., "Air
Handling Unit Switch").
3. Functional Switching
Functional Switching
Below is the completed Table 1 and Table 2 for every circuit in the pool/café block
area. Each circuit is broken down into two pages (69 and 70).
Circuit 1: Circuit Breaker Circuit (1 connection)
Table 1 – Design Grid: Sample 1
Circuit Number 1
Watts (where stated) 1000 W
Ib (Design Current) 6A
In (Device Rating and Type) 6A Type B MCB
Method of Installation PVC surface conduit
Ambient Temp in °C 40°C
Cable Type/Insulation 90°C thermosetting
Ca (Ambient Factor) 1.03
Cg (Grouping Factor) 0.8
Length in Metres 15m
Max Volt Drop 6.9V
mV/A/m (max) 29
Size Selected (mm²) 1.5
It (Tabulated Current) 20A
Iz (Must be Larger than In) 20A > 6A
Actual Voltage Drop 2.61V
Max Disc. Time 0.4s
Actual Zs 0.12 Ω
Max Zs as BS 7671 7.67 Ω