WJ80 series analog signal to MODBUS TCP
WJ80 series analog signal to MODBUS TCP
8-CH 4-20mA analog signal to MODBUS TCP Network Data Acquisition module
(WJ80 Series)
Features:
>> Eight channels 4-20mA current/voltage input MODBUS TCP communication protocol
>> Four channels switch input, two channels switch output
>> The built-in web page function can query data through web pages
>> Can set module data through web pages
>> 3000V isolation between signal input and power supply
>> Wide power supply range: 8 ~ 32VDC
>> DIN35 Rail-mounted
>> User can set up module IP address and other parameters on
the web page
>> Web login can be set up accounts and passwords, more secure
>> Dimensions: 120 mm x 70 mm x 43mm
Applications:
>> Industrial Ethernet analog signal monitoring and control
>> It is used for Internet of things, real-time monitoring network
and field equipment communication
>> Intelligent building control, security engineering applications
>> Ethernet industrial automation control system
>> Industrial signal isolation and long-term transmission Figure 1 WJ80
>> Equipment operation monitoring
>> Monitoring and control of equipment operation
>> Measurement of sensor signals
>> Internet of things acquisition and recording
>> Internet of things analog signal acquisition
Product Overview:
WAYJUN WJ80 series products are a collection module of Internet of Things and Industrial Ethernet, which realizes
transparent data interaction between sensor and network. Can forward the sensor data to the network, or the data from
the network to the sensor.
123456
Optional external power supply :5~30V Optional external power supply :5~30V
It also be a power supply to the module It also be a power supply to the module
Relay operating current is less than 30mA Resistance operating current is less than 30mA
MODBUS TCP protocol
(1) MODBUS TCP Data Frame
Transmitting over TCP/IP, supports Ethernet II and 802.3 frame formats. Figure 3, MODBUS TCP Data Frame
includes a header, function code and data three parts.
00041 0040 Output Switch Read/write The output state of channel 0~1, 1
00042 0041 Output Switch Read/write means the transistor is on, 0 means
the transistor is off.
00043 0042 Switching power Read/write Power-on and reset output status of
output channel 0~1.
00044 0043 Switching power Read/write
output
40041 0040 Output Switch Read/write Integer, the output state of channel
40042 0041 Output Switch Read/write 0~1, 1 means the transistor is on, 0
means the transistor is off.
40043 0042 Switching power output Read/write Power-on and reset output status of
40044 0043 Switching power output Read/write channel 0~1.
Address 0X(PLC) Address(PC,DCS) Data Property Data Description
40051 0050 Analog output Read/write Integer, 0 ~ 4800 means 0 ~ 4.8VDC
40052 0051 Analog Read/write Integer, power-on and reset output
power output voltage values
40160 0159 Channel 0~7 range write Integer, 0x0001-0x7FFF. If the range
of all channels is the same, you can
set this register. After the setting is
completed, the 40161 ~ 40168
registers will be modified to the
same value of the current register.
40161 0160 Channel 0 range Read/write
40162 0161 Channel 1 range Read/write
Integer, 0x0001-0x7FFF, the data of
40163 0162 Channel 2 range Read/write
the 40061~40068 register after
40164 0163 Channel 3 range Read/write
modification is converted according
40165 0164 Channel 4 range Read/write
to this range
40166 0165 Channel 5 range Read/write
40167 0166 Channel 6 range Read/write
40168 0167 Channel 7 range Read/write
>+12.000+16.000+16.000+16.000+16.000+16.000+16.000+18.168,1110,11,00,2000,0000 (cr)
Description: The input on the module is (the data format is the engineering unit):
Channel 0: +1 2.000mA Channel 1: +16.000mA Channel 2: +16.000mA Channel 3: +16.000mA
Channel 4: +16.000mA Channel 5: +16.000mA Channel 6: +16.000mA Channel 7: +18.168mA
DI3, DI2, DI1 are high level, DI0 is low level;
DO1 and DO0 current state: output transistor is turned on, and the transistor is disconnected after DO1 and DO0
are reset.
AO output voltage is 2V, and is 0V after AO reset.
After the parameters are filled in, click the “Save and Restart” button, the module will save the parameters and restart
automatically.
Module Calibration:
We have calibrated the module, the user can use directly.
You can also use the product calibration function to re-calibrate the module. During calibration, the module need to
been entered the appropriate signal, different input range needs different input signals.
In order to improve calibration accuracy, it is recommended to calibrate using the following equipment:
1. A stable output, low noise DC voltage / current signal source
2. A five and a half or more high-precision voltage / current measuring instruments to monitor the accuracy of the
input signal
Calibration:
1. According to the module input range, connects to the corresponding input signal.
Which WJ80 module zero calibration is at input 0,full scale calibration is at the input full-scale 100% . For example,
input signal is 4-20mA, when calibrate zero, input 0mA, when full-scale calibration, input 20mA.
input signal is 0-5V, when calibrate zero, input 0V, when the full-scale calibration, input 5V.
2. To WJ80 module input zero signal, usually is 0mA or 0V.
3. Until the signal stabilized, MODBUS protocol modify register 40101 (channel 0) to 0xFF00 and the module
performs zero calibration. (To calibrate other channels, please modify the corresponding channel register data to
0xFF00).
4. To WJ80 module input 100% of full scale current or voltage signal
5. Until the signal is stable, MODBUS protocol modify register 40101 (channel 0) to 0xFFFF and the module
performs zero calibration. (To calibrate other channels, please modify the corresponding channel register data to
Warranty
Two years (but violate operating rules and requirements to create damage, clients need pay maintenance costs)
Copyright
Copyright © 2018 Shenzhen WAYJUN Industrial Automation
Specifications subject to change without notice.
Brand
In this manual, mentioned other trademarks and copyright belongs to their respective owners.
Version: V2.0