WJ80 series analog signal to MODBUS TCP

The WJ80 Ethernet I/O Module is an 8-channel 4-20mA analog signal acquisition device that utilizes MODBUS TCP for communication. It features web-based configuration, 3000V isolation, and a wide power supply range, making it suitable for industrial automation and IoT applications. The module supports various input/output configurations and is designed for reliable operation in harsh environments.

Uploaded by

oplc3032
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views18 pages

WJ80 series analog signal to MODBUS TCP

The WJ80 Ethernet I/O Module is an 8-channel 4-20mA analog signal acquisition device that utilizes MODBUS TCP for communication. It features web-based configuration, 3000V isolation, and a wide power supply range, making it suitable for industrial automation and IoT applications. The module supports various input/output configurations and is designed for reliable operation in harsh environments.

Uploaded by

oplc3032
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Ethernet I/O Module

8-CH 4-20mA analog signal to MODBUS TCP Network Data Acquisition module
(WJ80 Series)
Features:
>> Eight channels 4-20mA current/voltage input MODBUS TCP communication protocol
>> Four channels switch input, two channels switch output
>> The built-in web page function can query data through web pages
>> Can set module data through web pages
>> 3000V isolation between signal input and power supply
>> Wide power supply range: 8 ~ 32VDC
>> DIN35 Rail-mounted
>> User can set up module IP address and other parameters on
the web page
>> Web login can be set up accounts and passwords, more secure
>> Dimensions: 120 mm x 70 mm x 43mm
Applications:
>> Industrial Ethernet analog signal monitoring and control
>> It is used for Internet of things, real-time monitoring network
and field equipment communication
>> Intelligent building control, security engineering applications
>> Ethernet industrial automation control system
>> Industrial signal isolation and long-term transmission Figure 1 WJ80
>> Equipment operation monitoring
>> Monitoring and control of equipment operation
>> Measurement of sensor signals
>> Internet of things acquisition and recording
>> Internet of things analog signal acquisition
Product Overview:
WAYJUN WJ80 series products are a collection module of Internet of Things and Industrial Ethernet, which realizes
transparent data interaction between sensor and network. Can forward the sensor data to the network, or the data from
the network to the sensor.

Figure 2: WJ80 Block Diagram


WJ80 series products include power conditioning, analog acquisition and output, switch acquisition, switch output and
RJ-45 network interface communication. The communication mode is MODBUS TCP protocol. TCP is a protocol based

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 1 of 18


Ethernet I/O Module
on transport layer. It is used widely and reliable for connection. Users can set up module IP address, subnet mask and
communication protocol directly on the web page. It can be used to monitor and control the operation of sensor devices.
WJ80 series products are based on SCM's intelligent monitoring and control system, users set IP address, subnet mask
and so on configuration information are all stored in nonvolatile memory EEPROM.
WJ80 series products are designed according to industry standard , isolation between analog signal/ digital signal,high
anti-interference ability and reliability. Operating temperature range is - 45 ~ +85 °C.
Function Description:
WJ80 remote I/O module can be used to measure eight channels analog signal and four channels switching signal, and
there are two channels switching output and one channel 0~4.8V voltage signal output.
1. Analog signal input
16 bits,8 analog signal input. All the products signal input ranges have been calibrated after leaving the factory. When
used, users can also program and calibrate by themselves easily. For specific current or voltage input range, please refer
to product selection.
2. Switching signal input and output, one channel 0~4.8V voltage signal output
8-channel switch signal input, can be connected to dry contact and wet contact, please refer to the wiring diagram for
details. 8-channel switch signal output open collector output.
One channel 0~4.8V voltage signal output can be used for analog signal control.
3. Communication protocol
Communication interface: RJ-45 network interface. The two indicators on the network port position, the Link light
(green light) is on after the network cable is plugged in, and the Data light (yellow light) will flash from time to time.
Communication protocol: Realize industrial Ethernet data exchange by using MODBUS TCP protocol. The control
module can also be accessed directly via the web page.
Network cache: 16K Byte (received and sent)
Communication response time: less than 100mS.
3. Anti-jamming
Module has a transient suppression diode inside, which can effectively suppress various surge pulses and protect the
module
WJ80 Product Selection:

WJ80 - U(A)□ - RJ45


Communication Interface
Input voltage or current signal
U1:0-5V A1:0-1mA RJ45:output is RJ-45 network interface
U2:0-10V A2:0-10mA
A3:0-20mA
U4:0-2.5V A4:4-20mA
U8:user-defined A8:user-defined
Sample 1: part No.:WJ80-A4-RJ45 means 8-channel 4-20mA signal input,output is RS-232 interface
Sample 2: part No.: WJ80-U1-RJ45 means 8-channel 0-5V signal input,output is RS-485 interface
WJ80 General Parameters:
(typical @ +25deg.C, Vs to 24VDC)
Analog input: current input / voltage input
Accuracy: 0.1%
Temperature drift: ±50 ppm/deg.C(±100 ppm/deg.C, max)
Input resistance: 100 ohm (4-20mA/0-20mA/0-10mA current input)
2K ohm (0-1mA current input)

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 2 of 18


Ethernet I/O Module
> 200K (5V/10V voltage input)
Digital input: 4 channels (DI0~DI3).
Low level: Input < 1V
High level: Input 4 ~ 30V
Input resistance: 3K ohm
Switching output: Open collector output, voltage 0~30V, maximum load current 30mA, 2 channels (DO0~DO1).
Analog output: Voltage is 0 ~ 4.8V, output load > 2K ohms.
Communication: MODBUS TCP communication protocol
Web page: Support web page access module, support web page setting module parameters.
Interface: RJ-45 network interface.
Working power supply: +8 ~ 32VDC wide power supply range, internal anti-reverse and over voltage protection circuit
Power consumption: < 2W
Working temperature: - 45 ~ +80 deg.C
Working humidity: 10 ~ 90% (no condensation)
Storage temperature: - 45 ~ +80 deg.C
Storage humidity: 10 ~ 95% (no condensation)
Isolation withstand voltage: 3000V isolation between the analog signal and the digital signal,the switching signal and
the power supply are common ground.
Dimensions: 120 mm x 70 mm x 43mm
WJ80 Factory default parameters:

123456

Figure 3:WJ80 Factory default parameters


How to restore factory setting?
1. When module is working, turn the INIT switch to the INIT position and then back to the NORMAL position.
2. Wait 30 seconds, module restored to the factory settings automatically.As shown in Figure 3. The web login
password is automatically restored to 123456.

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 3 of 18


Ethernet I/O Module
Footprint Function:
PIN Name Function PIN Name Function
1 DI0 Channel 0 switch signal input 12 IN1 Channel 1 analog signal input+
2 DI1 Channel 1 switch signal input 13 IN2 Channel 2 analog signal input+
3 DI2 Channel 2 switch signal input 14 IN3 Channel 3 analog signal input+
4 DI3 Channel 3 switch signal input 15 IN4 Channel 4 analog signal input+
5 DO0 Channel 0 switch signal output 16 IN5 Channel 5 analog signal input+
6 DO1 Channel 1 switch signal output 17 IN6 Channel 6 analog signal input+
7 PW+ Power supply + 18 IN7 Channel 7 analog signal input+
GND Power supply -,switch signal common A.GND Analog signal common ground
8 19
ground
9 RJ-45 Network interface 20 A.GND Analog signal common ground
10 A.GND Analog signal common ground 21 OUT Analog signal output
11 IN0 Channel 0 analog signal output+ 22 A.GND Analog signal common ground
Note: same name PIN interior are connected

Figure 5: WJ80 wiring diagram

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 4 of 18


Ethernet I/O Module
switch signal input wiring diagram
Dry contact input TTL/CMOS Level, 24V level input

Open collector input

switch signal output wiring diagram


Drive Relay Level Output

Optional external power supply :5~30V Optional external power supply :5~30V
It also be a power supply to the module It also be a power supply to the module
Relay operating current is less than 30mA Resistance operating current is less than 30mA
MODBUS TCP protocol
(1) MODBUS TCP Data Frame
Transmitting over TCP/IP, supports Ethernet II and 802.3 frame formats. Figure 3, MODBUS TCP Data Frame
includes a header, function code and data three parts.

Figure 6: MODBUS request/response over TCP/IP


(2) MBAP Header description:
The length of MBAP header (MBAP, MODBUS Application Protocol) is seven Bytes, it is composed of four parts.
As shown in Table 1:

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 5 of 18


Ethernet I/O Module
Fields Length(B) Description
Transaction 2 Bytes Identification of a MODBUS Request / Response transaction.
Identifier
Protocol Identifier 2 Bytes 0=MODBUS protocol
Length 2 Bytes Number of following bytes
Unit identifier 1 Byte Identification of a remote slave connected on a serial line or
on other buses.
Table 1: MBAP header
(3) MODBUS Function Codes Description
MODBUS function contains three types:
(1) Public function code: Defined function code to ensure uniqueness by MODBUS.org recognized
(2) User-defined function code contains two groups: 65~72 and 100~110, no recognition, but does not guarantee the
uniqueness of the code used. If change to the public code, need be required to RFC approved;
(3) Reserved function code for using by certain companies in certain traditional equipment, not as a public purpose.
In a typical public function code, WJ80 series products supports certain function code, as indicated below:

Function Code Name Description


01 Read Coil Status 1 means high level, 0 means high level
03 Read Holding Register 1 means high level, 0 means high level
05 Write Single Coil 1 means triode conduction, 0 means triode off
06 Write Single Register 1 means triode conduction, 0 means triode off
(4) Supported Functions Code Description
01 (0x01) Read Coils
This function code is used to read from 1 to 2000 contiguous status of coils in a remote device. The Request PDU
specifies the starting address, i.e. the address of the first coil specified, and the number of coils. In the PDU Coils are
addressed starting at zero. Therefore coils numbered 1-16 are addressed as 0-15.
The coils in the response message are packed as one coil per bit of the data field. Status is indicated as 1= ON and 0=
OFF. The LSB of the first data byte contains the output addressed in the query. The other coils follow toward the high
order end of this byte, and from low order to high order in subsequent bytes.
If the returned output quantity is not a multiple of eight, the remaining bits in the final data byte will be padded with
zeros (toward the high order end of the byte). The Byte Count field specifies the quantity of complete bytes of data.
Here is an example: function code 01, read 8 channels DI data, register address 00033~00040:
Request Response
Field Name (Hex) Field Name (Hex)
01 Transaction 01
Transaction Identifier
00 Identifier 00
Protocol Identifier 00 Protocol Identifier 00
MBAP 00 MBAP 00
Header 00 Header Length 00
Length
06 04
Unit identifier 01 Unit identifier 01
Function Code 01 Function Code 01
Staring Address Hi 00 Byte Count 01
Staring Address Lo 20 Output status DI7-DI0 00
Quantity of Outputs Hi 00

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 6 of 18


Ethernet I/O Module
Quantity of Outputs Lo 08
03 (0x03) Read Holding Registers
This function code is used to read the contents of a contiguous block of holding registers in a remote device. The
Request PDU specifies the starting register address and the number of registers. In the PDU Registers are addressed
starting at zero. Therefore registers numbered 1-16 are addressed as 0-15.
The register data in the response message are packed as two bytes per register, with the binary contents right justified
within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.
Here is an example: function code 03, read 8 channels DI data, register address: 40033
Request Response
Field Name (Hex) Field Name (Hex)
Transaction 01 01
Transaction Identifier
Identifier 00 00
Protocol Identifier 00 Protocol Identifier 00
MBAP 00 MBAP 00
Header 00 Header 00
Length Length
06 05
Unit identifier 01 Unit identifier 01
Function Code 03 Function Code 03
Staring Address Hi 00 Byte Count 02
Staring Address Lo 20 Register value Hi(0x00) 00
No. of Registers Hi 00 Register value Lo(DI7-DI0) 00
No. of Registers Lo 01

05 (0x05) Write Single Coil


This function code is used to write a single output to either ON or OFF in a remote device. The Request PDU specifies
the forced coil address. Coils are addressed starting at zero. Therefore, coil numbered 1 is addressed as 0. The requested
ON/OFF state is specified by a constant in the coil value field. A value of 0xFF00 hex requests the coil to be ON. A value
of 0x0000 requests the coil to be OFF. All other values are illegal and will not affect the coil.
Correct response and request are the same.
Here is an example: function code 05, set channel DO0 to ON, also as 1, register address: 00001
Request Response
Field Name (Hex) Field Name (Hex)
Transaction 01 01
Transaction Identifier
Identifier 00 00
Protocol Identifier 00 Protocol Identifier 00
MBAP 00 MBAP 00
Header 00 Header 00
Length Length
06 06
Unit identifier 01 Unit identifier 01
Function Code 05 Function Code 05
Output Address Hi 00 Output Address Hi 00
Output Address Lo 00 Output Address Lo 00
Output Value Hi FF Output Value Hi FF
Output Value Lo 00 Output Value Lo 00

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 7 of 18


Ethernet I/O Module
06 (0x06) Write Single Register
This function code is used to write a single holding register in a remote device. The Request PDU specifies the
address of the register to be written. Registers are addressed starting at zero. Therefore register numbered 1 is addressed
as 0.
The normal response is an echo of the request.
Here is an example: function code 06, set channels DO0~DO7, all as 1, Hex is 0xFF, register ddress: 40001
Request Response
Field Name (Hex) Field Name (Hex)
Transaction 01 01
Transaction Identifier
Identifier 00 00
Protocol Identifier 00 Protocol Identifier 00
MBAP 00 MBAP 00
Header 00 Header 00
Length Length
06 06
Unit identifier 01 Unit identifier 01
Function Code 06 Function Code 06
Registers Address Hi 00 Registers Address Hi 00
Registers Address Lo 00 Registers Address Lo 00
Registers Value Hi 00 Registers Value Hi 00
Registers Value Lo FF Registers Value Lo FF

(5) WJ80 Register Address Description


Support function codes 01 and 05
Address 0X(PLC) Address(PC,DCS) Data Property Data Description
00031 0030 Input Switch Read only
Level state of the digital input
00032 0031 Input Switch Read only
channel 0~3, 1: High level, 0: Low
00033 0032 Input Switch Read only
level
00034 0033 Input Switch Read only

00041 0040 Output Switch Read/write The output state of channel 0~1, 1
00042 0041 Output Switch Read/write means the transistor is on, 0 means
the transistor is off.
00043 0042 Switching power Read/write Power-on and reset output status of
output channel 0~1.
00044 0043 Switching power Read/write
output

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 8 of 18


Ethernet I/O Module
Support function codes 03 and 06
Address 0X(PLC) Address(PC,DCS) Data Property Data Description
40001 0000 Input Analog Read only
40002 0001 Input Analog Read only
40003 0002 Input Analog Read only
40004 0003 Input Analog Read only Integer, channel 0~7 data,
40005 0004 Input Analog Read only 0x0000-0x7FFF
40006 0005 Input Analog Read only
40007 0006 Input Analog Read only
40008 0007 Input Analog Read only

40021 0020 4-20mA special Read only


40022 0021 4-20mA special Read only
40023 0022 4-20mA special Read only
40024 0023 4-20mA special Read only Integer, channel 0~7 data,
40025 0024 4-20mA special Read only 4mA=0x0000,20mA=0x7FFF
40026 0025 4-20mA special Read only
40027 0026 4-20mA special Read only
40028 0027 4-20mA special Read only

40031 0030 Input Switch Read only


Integer, the level state of switch
40032 0031 Input Switch Read only
input channel 0~3, 1: High level, 0:
40033 0032 Input Switch Read only
Low level
40034 0033 Input Switch Read only

40041 0040 Output Switch Read/write Integer, the output state of channel
40042 0041 Output Switch Read/write 0~1, 1 means the transistor is on, 0
means the transistor is off.
40043 0042 Switching power output Read/write Power-on and reset output status of
40044 0043 Switching power output Read/write channel 0~1.
Address 0X(PLC) Address(PC,DCS) Data Property Data Description
40051 0050 Analog output Read/write Integer, 0 ~ 4800 means 0 ~ 4.8VDC
40052 0051 Analog Read/write Integer, power-on and reset output
power output voltage values

40061 0060 Input Analog Read only


40062 0061 Input Analog Read only
40063 0062 Input Analog Read only
Integer, channel 0~7 data, range
40064 0063 Input Analog Read only
defined by 40161~40168 registers
40065 0064 Input Analog Read only
40066 0065 Input Analog Read only
40067 0066 Input Analog Read only
40068 0067 Input Analog Read only

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 9 of 18


Ethernet I/O Module
40081 ~ 40088 0080 ~ 0087 User-defined Read only Integer, channel 0~7 data, range
4-20mA defined by 40181~40188 registers.
When the data is less than 4 mA, it is
displayed as 0, and when the data is
20 mA, it is displayed as the set
value. The middle is displayed
proportionally.

40101 0100 Channel 0 calibration Read/write


40102 0101 Channel 1 calibration Read/write The product has been calibrated at
40103 0102 Channel 2 calibration Read/write the factory and can be used directly
40104 0103 Channel 3 calibration Read/write without calibration. If you really
40105 0104 Channel 4 calibration Read/write need to recalibrate, please check the
40106 0105 Channel 5 calibration Read/write calibration section and follow the
40107 0106 Channel 6 calibration Read/write steps.
40108 0107 Channel 7 calibration Read/write

40160 0159 Channel 0~7 range write Integer, 0x0001-0x7FFF. If the range
of all channels is the same, you can
set this register. After the setting is
completed, the 40161 ~ 40168
registers will be modified to the
same value of the current register.
40161 0160 Channel 0 range Read/write
40162 0161 Channel 1 range Read/write
Integer, 0x0001-0x7FFF, the data of
40163 0162 Channel 2 range Read/write
the 40061~40068 register after
40164 0163 Channel 3 range Read/write
modification is converted according
40165 0164 Channel 4 range Read/write
to this range
40166 0165 Channel 5 range Read/write
40167 0166 Channel 6 range Read/write
40168 0167 Channel 7 range Read/write

Address 0X(PLC) Address(PC,DCS) Data Property Data Description


40180 0179 User-defined 4-20mA write Integer, 0x0001-0x7FFF, if all
Channel 0~7 range channels have the same range, this
register can be set. After the setting
is completed, the 40181 ~ 40187
registers will be modified once to the
same value as the current register.
40181 ~ 40188 0180 ~ 0187 User-defined 4-20mA Read/write Integer, 0x0001-0x7FFF, the data of
Channel 0~7 range the 40081~40088 register after
modification is converted according
to this range

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 10 of 18


Ethernet I/O Module

40204 0203 Conversion rate Read/write Integer, range 0x0000-0x0009,


The factory default is 2, please
recalibrate the module after
modification.
0x0000 = 2.5 SPS,0x0001 = 5 SPS,
0x0002 = 10 SPS, 0x0003 = 20
SPS,
0x0004 = 40 SPS, 0x0005 = 80
SPS,
0x0006 = 160 SPS,0x0007 = 320
SPS,
0x0008 = 500 SPS,0x0009 = 1000
SPS
40211 0210 Module name Read only High: 0x00 Low: 0x80
40221 0220 Channel status Read/write High: 0x00
Low: channel status (0xFF)

Character protocol Socket communication


In the working mode of Websocket, TCP Server, TCP Client, UDP Mode, etc., the following character protocol
communication can be used.
If the auto upload data is set to "Yes" in the configuration settings,
In the working mode of Websocket, TCP Server, and TCP Client,
The data will be uploaded automatically after the communication
connection is successful. UDP Mode does not automatically
To upload data, you need to send a command to read the data.

1. Read Measurement Data Command


Description: Returns the all channels analog input measurement and switch state data from the module in the
currently configured data format
Command Format:#00
Response format:
>(AI data) ,(DI data), (DO data), (DO Reset data), (AO data), (AO Reset data) (cr) the command is valid
?00(cr) the command is invalid or illegal
Parameters: # delimiter character. Hexadecimal 3EH
(AI data) represents AI analog data. The data format can be an engineering unit, a percentage of FSR, and
a hexadecimal complement. See section 3 of the command set for details. Hexadecimal is the
ASCII code for each character.
(DI data) represents DI switch state. 4 numbers, the order is DI3~DI0. The value is 0: input is low,
Value is 1: input is high
(DO data) represents DO switch state. 2 numbers, the order is DI1~DI0.The value is 0: the output transistor
is disconnected, value 1: output transistor is conduction
(DO Reset data) represents DO switch state after reset. 2 numbers, the order is DI1~DI0,
Value is 0: Output triode is off, value is 1: Output triode is on

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 11 of 18


Ethernet I/O Module
(AO data) represents AO analog output value. 4 numbers, range 0000~4800, represents voltage 0~4.8V
(AO Reset data) represents AO analog output value after reset. 4 numbers, range 0000~4800, represents
voltage 0~4.8V
(cr) terminating character, carriage return (0Dh)
Other notes: If the format is wrong or the communication is incorrect, the module does not respond.
If a channel has been closed, the read data is displayed as a space character or 0.
Example: Commands (character format) #00

>+12.000+16.000+16.000+16.000+16.000+16.000+16.000+18.168,1110,11,00,2000,0000 (cr)
Description: The input on the module is (the data format is the engineering unit):
Channel 0: +1 2.000mA Channel 1: +16.000mA Channel 2: +16.000mA Channel 3: +16.000mA
Channel 4: +16.000mA Channel 5: +16.000mA Channel 6: +16.000mA Channel 7: +18.168mA
DI3, DI2, DI1 are high level, DI0 is low level;
DO1 and DO0 current state: output transistor is turned on, and the transistor is disconnected after DO1 and DO0
are reset.
AO output voltage is 2V, and is 0V after AO reset.

2. Read channel N data command


Description: Returns channel N analog input data from the module in the currently configured data format.
Command Format:#00N
Parameters: N Channel codes 0 to 7 are AI, 8 is DI, 9 is DO, and A is AO.
Response format: >(data)(cr) the command is valid
?00(cr) the command is invalid or illegal or the channel is closed
Parameters: > Delimiter
(data) represents returning the data of channel N. The data format can be an engineering unit, a percentage of
FSR, and a hexadecimal complement. See section 3 of the command set for details.
(cr) terminating character, carriage return (0Dh)
Other notes: If the format is wrong or the communication is incorrect, the module does not respond.
Example: Commands (character format) #000
(Hexadecimal format) 23303030
Module response (character format): >+18.000 (cr)
(Hexadecimal format) 3E2B31382E3030300D
Description: The input on the module channel 0 is (the data format is the engineering unit): +18.000mA

3. Set WJ80 Module Command


Description: Set data formats, decimal point, range and channel status for a WJ80 module. counter data is
stored in a EEPROM.
Command Format:$01FDNNNNNABCD
Parameters: $01 Configuration command 3 initial characters
F Data format
0: Engineering Units
1: % of FSR
2: Twos complement
3: 4mA displays 0 (measurement data is subtracted 4mA automatically and then converted according
to range)
D Data decimal point position, value rang is from 1 to 5. Indicates that there are several numbers in front of

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 12 of 18


Ethernet I/O Module
the decimal point. For example, 3 means 000.00.
NNNNN represents the data range, value rang is from 00000 to 99999 (decimal). For example, 10000 means
the range is 10000.
ABCD Four hexadecimal numbers,
The first number and the second number are both 0
0 0 0 0 0 0 0 0
The third number represents 7~4 channels
A B
The fourth number represents the 3~0 channel
Bit value is 0: channel is disabled
IN7 IN6 IN5 IN4 IN3 IN2 IN1 IN0
Bit value is 1: Enable channel
Bit7 Bit 6 Bit 5 Bit 4 Bit 3 Bit2 Bit 1 Bit 0
C D

Response format: !01(cr) the command is valid


?00(cr) the command is invalid or illegal
Example: Commands $01022000000FF
Module response !01(cr)
Description: $01 Configuration command 3 initial characters
0 Engineering Units
2 Indicates that there are 2 numbers before the decimal point
20000 Indicates that the range is 20000
00FF Indicates that the channels are open

4. Read Configuration Status Command


Description: Read configuration for WJ80 module.
Command Format: $00
Response format: !00FDNNNNNABCD (cr) the command is valid
?00(cr) the command is invalid or illegal
Parameters: !00 Reply 3 first characters
F Data format
0: Engineering Units
1: % of FSR
2: Twos complement
3: 4mA displays 0 (measurement data is subtracted 4mA automatically and then converted according
to range)
D Data decimal point position, value rang is from 1 to 5. Indicates that there are several numbers in front
of the decimal point. For example, 3 means 000.00.
NNNNN represents the data range, value rang is from 00000 to 99999 (decimal). For example, 10000 means the
range is 10000.
ABCD Four hexadecimal numbers,
The first number and the second number are both 0
0 0 0 0 0 0 0 0
The third number represents 7~4 channels
A B
The fourth number represents the 3~0 channel
Bit value is 0: channel is disabled
IN7 IN6 IN5 IN4 IN3 IN2 IN1 IN0
Bit value is 1: Enable channel
Bit7 Bit 6 Bit 5 Bit 4 Bit 3 Bit2 Bit 1 Bit 0
C D

(cr) terminating character, carriage return (0Dh)

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 13 of 18


Ethernet I/O Module
Other notes: If the format is wrong or the communication is incorrect, the module does not respond.
Example: Commands $00
Module response !00115000000FF (cr)
Description: !00 Reply 3 first characters
1 % of FSR
1 Indicates that there is one numbers in front of the decimal point
50000 Indicates that the range is 50000
00FF Indicates that the channels are open

5. Set Module AD Conversion Rate


Description: Sets the AD conversion rate of the module. Among them, channel conversion rate = AD conversion rate /
opened channel numbers. The slower the sampling rate, the more accurate the acquired data. Users can adjust it
according to their needs. The factory default conversion rate is 20SPS.
Note: Please recalibrate the module after modifying the conversion rate, otherwise the measured data
will be biased. It is also possible to indicate the conversion rate when ordering, and we recalibrate at the factory's
required conversion rate when the product is shipped.
Command Format: $03R
Parameters: $03 Set the conversion rate command to 3 initial characters
R Conversion rate code, which can be 0~9
Code R 0 1 2 3 4 5 6 7 8 9
Conversion
2.5 SPS 5 SPS 10 SPS 20 SPS 40 SPS 80 SPS 160 SPS 320 SPS 500 SPS 1000 SPS
rate
Response format: !03(cr) the command is valid
?00(cr) the command is invalid or illegal
Other notes: If the format is wrong or the communication is incorrect, the module does not respond.
Example 1: Commands $036
Module response !03(cr)
Description: set AD conversion rate is 160SPS.
Example 2: Commands $035
Module response !03(cr)
Description: set AD conversion rate is 80SPS.

6. Read Module AD Conversion Rate


Description: Read the module AD conversion rate. Among them, channel conversion rate = AD conversion rate /
numbers of channel opened. The slower the sampling rate, the more accurate the acquired data.
Command Format: $02R
Response format: !02(cr) the command is valid
?00(cr) the command is invalid or illegal
Parameters: R Conversion rate code, which can be 0~9
Code R 0 1 2 3 4 5 6 7 8 9
Conversion
2.5 SPS 5 SPS 10 SPS 20 SPS 40 SPS 80 SPS 160 SPS 320 SPS 500 SPS 1000 SPS
rate
(cr) terminating character, carriage return (0Dh)
Other notes: If the format is wrong or the communication is incorrect, the module does not respond.

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 14 of 18


Ethernet I/O Module
Example 1: Commands $02
Module response !026(cr)
Description: set AD conversion rate is 160SPS.
Example 2: Commands $02
Module response !025(cr)
Description: set AD conversion rate is 80SPS.

Actions and settings on the webpage


Enter the default module IP in the computer or mobile browser,the default is 192.168.0.7, which can open the module
webpage (provided that the computer IP or mobile IP and module are on the same network segment. The login webpage
should be based on the IP address of the current module.
Login operation), enter the password, the default is 123456, click "Login",
You can enter the data display interface, there are Chinese and
English switch signs in the upper right corner, click then
you can switch between Chinese and English signs.
1. web page real-time collection:
Since this page uses websocket to realize real-time data collection by webpage,
it is recommended to test using Google Chrome or IE10 browser.
After the connection is successful, the web page will automatically update
the data (note how the module works, it must be set to "Websocket," and the
automatic upload data should be set to "Yes" or you can't get the data),
you can also set the AI range through the webpage and other parameters.
DO and AO parameters can also be set through the webpage. if your
mobile browser supports websocket, you can also use your mobile phone to
read data and set parameters.

2.configure network parameters:


(a) module name
The module name defaults is WJ80-RJ45, and user can modify
as needed.
(b) MAC address
The MAC address can be changed according to user needs.
(c) IP address
The current module IP address, factory default is: 192.168.0.7,
the IP address can be modified.
(c) subnet mask
Used to divide the subnet range size (usually 255.255.255.0),
which can be modified by the user.
(d) default gateway
The only way to access the external network (usually fill in the router IP address).

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 15 of 18


Ethernet I/O Module
(d) working method
The default is Websocket, which supports up to 6 Websocket communication.
Can be set to TCP Server, TCP Client, UDP Mode, Modbus TCP, etc.
communication method. Up to 6 TCP Servers can be supported in TCP Server mode.
(c) local port
The local port default is 23 and can be modified by the user.
(c) remote port
The working mode is TCP Client, and UDP Mode is filled in according to the actual situation.
(e) remote server address
It is the IP address of the remote server. The working mode is TCP Client, and UDP Mode is filled in according to the
actual situation.
(e) automatically upload data
Whether to upload measurement data automatically in Websocket, TCP Server, TCP Client, UDP Mode, etc.
(f) upload time interval
The time interval at which the measurement data is uploaded automatically. The default is to upload data once in 1
second.
(b) version number
The version is incremented from 1.0.
(g) password
Setting parameters must be entered with the correct password to take effect. The password is the web login password,the
factory default is 123456.

After the parameters are filled in, click the “Save and Restart” button, the module will save the parameters and restart
automatically.

Module Calibration:
We have calibrated the module, the user can use directly.
You can also use the product calibration function to re-calibrate the module. During calibration, the module need to
been entered the appropriate signal, different input range needs different input signals.

In order to improve calibration accuracy, it is recommended to calibrate using the following equipment:
1. A stable output, low noise DC voltage / current signal source
2. A five and a half or more high-precision voltage / current measuring instruments to monitor the accuracy of the
input signal
Calibration:
1. According to the module input range, connects to the corresponding input signal.
Which WJ80 module zero calibration is at input 0,full scale calibration is at the input full-scale 100% . For example,
input signal is 4-20mA, when calibrate zero, input 0mA, when full-scale calibration, input 20mA.
input signal is 0-5V, when calibrate zero, input 0V, when the full-scale calibration, input 5V.
2. To WJ80 module input zero signal, usually is 0mA or 0V.
3. Until the signal stabilized, MODBUS protocol modify register 40101 (channel 0) to 0xFF00 and the module
performs zero calibration. (To calibrate other channels, please modify the corresponding channel register data to
0xFF00).
4. To WJ80 module input 100% of full scale current or voltage signal
5. Until the signal is stable, MODBUS protocol modify register 40101 (channel 0) to 0xFFFF and the module
performs zero calibration. (To calibrate other channels, please modify the corresponding channel register data to

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 16 of 18


Ethernet I/O Module
0xFFFF).
6. Finished

FAQ about WJ80


1>> Across the network Segment problems
If the communication PC and device IP are not a network segment, and it is in a straight line, or under a sub-router,
then they are unable to communicate simply.
Example:
Device IP: 192.168.0.7
Subnet Mask: 255.255.255.0
PC's IP: 192.168.1.100
Subnet Mask: 255.255.255.0
Device IP is 192.168.0.7, then the result could not land equipment page on the PC, also can not ping it.
If you want them to be able to communicate, you need set to 255.255.0.0 about the subnet mask of device/PC and the
router, so that we can login module pages.
2>> Device can ping but can not open the page
There may be several causes:
1) The device is set up static IP, but conflicts to the existing device network IP
2) HTTP server port was to be modified (default should be 80)
3) Other reasons
Workaround: Re-set up an unused IP to the device, restore factory settings or input the correct port when open the
browser.
3>> every once in a while, dropped reconnection occurs
Every once in a while, dropped reconnection phenomena occur
Cause: The serial server has an IP address conflict with other device
4>> Communication is not normal, not on the network links, or can not search
Currently used computer firewall needs to be closed (in the windows firewall settings)
Three local ports, not conflict, that is, must be set to different values, the default 23, 26, 29
With illegal MAC address, such as all-FF MAC address, there maybe appear unable to connect the target IP address,
or MAC address repeat.
Illegal IP address, such as a router and network are not in a network segment, you may not be able to access the
Internet.
5>> Find hardware problems
Bad power adapter, or plug connection is undesirable
Power light is not on, the LAN light is not bright, that is no power supply or the hardware is broken
Cable or network port hardware issues, view the status of the network port lights
Network interface hardware problems, you can check the network port status, etc., green light should be the long
bright, yellow light should be flashing, instead of the long light or long off, otherwise it is a hardware problem
Wrong password, if you forget the password, you can restore the factory configuration (switch to init, the device is
on 30 seconds, then put on the switch to normal. The parameters are shown in Figure 3. Web login password is restored
to 123456 automatically)

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 17 of 18


Ethernet I/O Module
Size(unit:mm) DIN35 Rail Mounted

Warranty
Two years (but violate operating rules and requirements to create damage, clients need pay maintenance costs)
Copyright
Copyright © 2018 Shenzhen WAYJUN Industrial Automation
Specifications subject to change without notice.
Brand
In this manual, mentioned other trademarks and copyright belongs to their respective owners.

Version: V2.0

Shenzhen WAYJUN Industrial Automation E-mail:[email protected] www.wayjun.net Page 18 of 18