0% found this document useful (0 votes)
6 views

2

The document outlines the supply, installation, testing, and commissioning of various CCTV and fire alarm systems, including specific equipment such as cameras, NVRs, and fire alarm panels. It details the quantities and specifications for each item, including technical requirements and compliance certifications. The document serves as a comprehensive procurement list for security and fire safety systems.

Uploaded by

vravishankar01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

2

The document outlines the supply, installation, testing, and commissioning of various CCTV and fire alarm systems, including specific equipment such as cameras, NVRs, and fire alarm panels. It details the quantities and specifications for each item, including technical requirements and compliance certifications. The document serves as a comprehensive procurement list for security and fire safety systems.

Uploaded by

vravishankar01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

No Description of Items Unit Qty.

SH-II ( CCTV Systems )


1 Supply Installation & commissining of Indoor Type Dome camera with
1/2.7" 2 MP progressive CMOS, 1080P high definition , 2.7-12 mm
motorized focus zoom lens,Min Triple Stream Support, Inbuilt Smart IR LED,
0.1 lux color/0 lux with IR LEDs on,H.264 high profile, True WDR min 120
dB, True Day/Night, 3DNR and Built in Power over Ethernet (PoE), Min 128
GB Micro SD Card Storage support, IP66, IK10 vandal proof, Having
Operating temp range : –20°C to 60° C. Certifications: ONVIF compliant,
UL, CE, FCC Each 6
2 Supply, Installation, Testing & Commissioning of IP Network TDN Low- Light
IR Bullet Camera, 1/2.7" CMOS, 2 MP @ 25fps, Min. Illumination required
0.01 lux @ F1.4 (color), 120 dB True WDR, Min. Pixels 1920 × 1080, triple
stream, 2.7–12 mm motorized focus & zoom lens, BLC, HLC, 3DNR,
Privacy Mask, IR LEDs Smart IR with upto 50m IR distance, Dual channel
Audio G.711a/G.711u/AAC, 128GB SD card support, Alarm: 2 In/ 1out, PoE,
H.264 High Profile and MJPEG, PoE Class 3 and 12V DC, IP 67, IK 10
vandal proof, Having Operating temp range : –40°C to 60° C. Certifications:
ONVIF Profile S & Profile G compliant, UL, CSA 60950-22, CE (EN 50130-4
& EN Each 3
3 Supply, Installation, Testing and Commissioning of 16 Channel NVR with 4
SATA, with 1080p Realtime Live View H.265/H.264 MJPEG dual codec
decoding Up to 12 MP resolution preview & playback Max 320 Mbps
incoming bandwidth support 4 SATA HDDs up to 32TB, Support RAID 5 and
6, Supports fisheye video de-warping in local and web user
interface,Supports visual or auditory notifications(a flashing light, bell,or
siren) ONVIF compliant, UL, CE, FCC and & RoHS compliant.
Each 1
4 Supply Installation & commissioning of Surveillance Class SATA 7200 RPM
4TB HDD For Real Time Recording etc complete as required. Each 2
5 SITC of workstation for CMS for CCTV monitoring with CPU Intel@
Core"i5, Memory: 8 CB 1600 MHz DDR3 RAM with 8GB and 4GB graphic
card, Windows OS including LED monitor 24 " and mouse and Keyboard
with all accessories etc complete as required. Each 1
6 Supplying , installation , testing and commissioning of LED 42" FULL HD
TV, Display Type - LED Display Features Screen Format Full HD, LED
Resolution 1920 x 1080 Pixels (Full HD), Audio Stereo System, Hear Crisp
and Clear Sound, including stands, bracket, etc complete as required. Each 1
7 Supplying , installation , testing and commissioning of 24 port POE Switch
including terminations, connnections etc. complete as required Each 1
8 Supplying , installation , testing and commissioning of 15 U Network rack for
mounting of NVR & Switch, Panel, Patch Cords etc. complete as required Each 1
9 Supplying , installation , testing and commissioning of following accessories
in the existing Rack including terminations, connnections etc. complete as
required
a) Patch /Jack Panel Each 1
b) Patch Cord 1 mtr long. Each 10
10 Supplying and fixing of following sizes of medium class PVC conduit along
with accessories in surface/recess including cutting the wall and making
good the same in case of recessed conduit as required.
b) 25mm Mtr 80
11 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/
recessed Steel/ PVC conduit as required.
a) 1 run of cable Mtr 250
b) 2 run of cable Mtr 150
Total of SH-II
SH-III ( Automatic Fire Alarm and PA Systems)
No Description of Items Unit Qty.

1 Supplying, installation, testing and commissioning of micro processor based


intelligent addressable main fire alarm panel, central processing unit with
the following loop modules and capable of supporting not less than 240
devices (including detectors) and minimum 120 detectors per loop and loop
length up to 2 km, network communication card, minimum 320 character
graphics/ LCD display with touch screen or other keypad and minimum 4000
events history log in the non volatile memory (EPROM), power supply unit
(230 + 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free
batteries with automatic charger. The panel shall have facility to connect
printer to printout log and facility to have seamless integration with
analog/digital voice evacuation system (which is part of the schedule of work
under SH: PA System) and shall be complete with all accessories . The
panel shall be compatible for IBMS system with open protocol BACnet/
Modbus over IP complete as per specifications.
a) Two Loop Panel. Each 1
2 Supplying, installation, testing & commissioning of intelligent analog
addressable photothermal detector complete with mounting base complete
as required. Each 60
3 Supplying, installation, testing & commissioning of response indicator on
surface/recessed MS Box having two LED, metallic cover complete with all
connections etc as required. Each 30
4 Supplying, installation, testing & commisssioning of intelligent addressable
programmable sounder complete as required. Each 6
5 Supplying, installation, testing & commissioning of fault isolator complete
with base as required. Each 6
6 Supplying, installation, testing & commissioning of addressable fire control
module complete as required. Each 6
7 Supplying, installation, testing & commissioning of addressable manual call
point complete as required. Each 4
8 Supplying, installation, testing & commissioning of fire fighter telephone
handset complete as required. Each 1
9 Supplying, installation, testing & commissioning of fire fighter phone jack
complete as required. Each 2
10 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V
rated with annealed copper conductor having XLPE insulation, steel wire
armouring & FRLS outer sheath complete as required. Mtr 500
11 Supplying, installation, testing & commissioning of Dry powder type(ABC
type) fire extinguisher of 4 kg capacity (IS-15683) in MS cylinder fitted with
pressure gauge , discharge mechanism, with discharge pipe fully charged
i/c providing & fixing suitable bracket etc. as required. Each 12
12 Supplying, installation, testing & commissioning of CO2 type fire
extinguisher of 9 kg capacity ( IS 15222 ) in MS cylinder fitted with pressure
gauge , discharge mechanism, with discharge pipe fully charged i/c
providing & fixing suitable bracket etc. as required.
Each 4
13 Supplying, installation, testing & commissioning of 6 zone, voice alarm
controller with USB, MP3 player (including 6 zone button paging station)
with seamless integration facility with main fire alarm panel for voice
evacuation complete as required Each 1
14 Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker
complete as required. Each 30
15 Supplying, installation, testing & commissioning of digital audio amplifier 75
Watt, 25V rms operating at 240 Volt AC Supply complete as required. Each 1
16 Supplying, installation, testing & commissioning of Voice command keypad
6 zone, with microphone assembly complete as required. Each 1
17 Supplying and drawing of cable Fire Retardant PVC insulated copper
conductor cable in the existing surface / recessed steel conduit of following
pairs, cores and size including connections and interconnections etc. as
required.
a) speaker cable Single pair, 2-core, 1.5 sqmm Mtr 350
b) speaker cable Two pair, 2-core, 1.5 sqmm Mtr 150
Total of SH-III