The document outlines a load analysis for a facility, detailing general lighting loads totaling 2,670 VA and various receptacle and appliance loads amounting to 56,440 VA. After applying a 70% demand factor, the recommended circuit requirements include specific circuit breakers and main feeder conductors to handle a total current of 174.77 Amperes. Additionally, it specifies the need for a 175AT molded case circuit breaker for main feeder protection.
The document outlines a load analysis for a facility, detailing general lighting loads totaling 2,670 VA and various receptacle and appliance loads amounting to 56,440 VA. After applying a 70% demand factor, the recommended circuit requirements include specific circuit breakers and main feeder conductors to handle a total current of 174.77 Amperes. Additionally, it specifies the need for a 175AT molded case circuit breaker for main feeder protection.
Total covered area at approximately 111.25 mm² ( 111.25 mm² x 24VA/mm²) 2,670.00 VA
2. Receptacle Outlet / Other loads;
a. 40 W LED Lights 152unit/s 6,080.00 VA b. 180 W Convenience Outlet 101 unit/s 18,180.00 VA c. 2760 W ACCU Provision 1 unit/s 2,760.00 VA d. 2300 W ACCU Provision 3 nit/s 6,900.00 VA e. 1840 W ACCU Provision 3 unit/s 5,520.00 VA f. 4000 W Water Heater 3 unit/s 12,000.00 VA g. 1130 W Auxiliary Provision 1 unit/s 1,130.00 VA h. 600 W Ceiling Fan 2 unit/s 1,200.00 VA TOTAL CONNECTED LOADS: 56,440.00 VA
Application of Demand Factor:
@ 70 %Demand Factor 39,508 VA 3. Recommendation Circuit Requirements: