The document outlines a load analysis for a facility, detailing general lighting loads totaling 2,670 VA and various receptacle and appliance loads amounting to 56,440 VA. After applying a 70% demand factor, the recommended circuit requirements include specific circuit breakers and main feeder conductors to handle a total current of 174.77 Amperes. Additionally, it specifies the need for a 175AT molded case circuit breaker for main feeder protection.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3 views

Load Analysis

The document outlines a load analysis for a facility, detailing general lighting loads totaling 2,670 VA and various receptacle and appliance loads amounting to 56,440 VA. After applying a 70% demand factor, the recommended circuit requirements include specific circuit breakers and main feeder conductors to handle a total current of 174.77 Amperes. Additionally, it specifies the need for a 175AT molded case circuit breaker for main feeder protection.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD ANALYSIS

1. General Lighting Loads:


Total covered area at approximately 111.25 mm²
( 111.25 mm² x 24VA/mm²) 2,670.00 VA

2. Receptacle Outlet / Other loads;


a. 40 W LED Lights 152unit/s 6,080.00 VA
b. 180 W Convenience Outlet 101 unit/s 18,180.00 VA
c. 2760 W ACCU Provision 1 unit/s 2,760.00 VA
d. 2300 W ACCU Provision 3 nit/s 6,900.00 VA
e. 1840 W ACCU Provision 3 unit/s 5,520.00 VA
f. 4000 W Water Heater 3 unit/s 12,000.00 VA
g. 1130 W Auxiliary Provision 1 unit/s 1,130.00 VA
h. 600 W Ceiling Fan 2 unit/s 1,200.00 VA
TOTAL CONNECTED LOADS: 56,440.00 VA

Application of Demand Factor:


@ 70 %Demand Factor 39,508 VA
3. Recommendation Circuit Requirements:

Use: 7 - 20AT, 2P Circuit Breaker


Use: 15 -30AT, 2P Circuit Breaker
Use: 3 - 40AT, 2P Circuit Breaker

4. For Main Feeder Conductors:

I Total = [39,508+ 25%(2760)]/230 V = 174.77 Amperes


Use: 2 - 80mm² THHN & 30 mm² THHN in 40mm RSC

5. For Main Feeder Protection:

I Total = [39,508 + 25%(2760)]/230 V = 174.77 Amperes


Use: 175AT/175AF Molded Case Circuit Breaker, 25KAIC