ansi4
ansi4
11.156
cussed how the ANSI Standards are applied
31.378
to determine the appropriate interrupting From a system standpoint, in-plant genera-
68
duty (1-4 cycle) symmetrical currents as well
.7
42
BUS-1
tion provides some components of both
as asymmetrical multipliers for an NACD “Local” and “Remote” current to each fault.
ratio of 0.0 (Local) or 1.0 (Remote) at the
0.268
This can best be modeled by interpolation
fault point. One point I did not make clear CLR-1
based on weighting the importance of
in the previous articles, is that the terms “Local” and “Remote” for all generation.
NACD, "Local", and "Remote" are not used The suggested weighting is based on estimat-
in ANSI C37.010. They are defined in [1] ing the “Local” portion of an in-plant gener-
and [2] to help in understanding the stan- LOAD
ator contribution for faults not directly on its
dard, as well as, to provide more accurate terminals.
calculations.
L-1
COMP
For the example in Figure-4B, the generator
In this issue, we will discuss how the stan- contributes 3.044 kA to the fault. By
dard is applied to determine high voltage weighting the current to the “Local”
Figure-4A
interrupting currents where the NACD ratio (0.4*I”g) limit, the “Local” portion of the
falls somewhere between 0.0 and 1.0. GEN-1 generator current is 3.044/4.464 = 68.2 per-
UTIL-2
cent, and the remote portion is 31.8 percent.
By definition, an NACD ratio between 0.0 These values give us an NACD ratio of
3.044
and 1.0 implies that both "Remote" and [8.560 + 3.044*0.318] / 11.867 = 0.803.
8.560
CLR-1 application.
NACD = Remote Source Contributions
Total Contributions
11.595