opc-quick-client-manual

The OPC Quick Client is a tool designed for testing and developing OPC Data Access servers, supporting both local and remote connections. It allows users to manage server connections, groups, and items, and perform various operations such as connecting, disconnecting, and enumerating groups. The document provides detailed instructions on using the client, including setting up connections, managing data types, and understanding the operational interface.

Uploaded by

Uğur Yildirim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views27 pages

opc-quick-client-manual

The OPC Quick Client is a tool designed for testing and developing OPC Data Access servers, supporting both local and remote connections. It allows users to manage server connections, groups, and items, and perform various operations such as connecting, disconnecting, and enumerating groups. The document provides detailed instructions on using the client, including setting up connections, managing data types, and understanding the operational interface.

Uploaded by

Uğur Yildirim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

OPC Quick Client

© 2016 PTC Inc. All Rights Reserved.


2 OPC Quick Client

Table of Contents
OPC Quick Client 1

Table of Contents 2

OPC Quick Client 3

Overview 3

Main Window 4

Server Connection 6

Group 9

Items 10

Data Types Description 13

Operations 14

Options 17

Test Mode 20

License Agreement 25

Index 26

www. kepware.com
OPC Quick Client 3

OPC Quick Client


Help version 1.035

CONTENTS

Overview
What is the OPC Quick Client and how is it used?

Main Window
What does the OPC Quick Client do?

Server Connection
How do I connect to a server and start receiving data?

Operations
What type of operations can I perform?

Test Mode
How can I perform a series of tests on an OPC server?

License Agreement
It is recommended that users review the license agreement.

Overview
The OPC Quick Client assists in the testing and development of the OPC Data Access 1.0 and 2.0 servers. It
supports both local and remote OPC server connections. Remote connections are handled through the
operating system's DCOM interface.

Note: The OPC Quick Client does not fully support OPC DA 3.0. This help file assumes the use of Windows XP
or Server 2003. Service Pack 4 is recommended.

Client Preparation
For information on how to prepare the client, follow the instructions below.

1. To start, create a server connection (which will be used to connect to an OPC server).

2. Next, add a group to the connection that contains varying properties (such as update rate, dead band
and time bias).

3. Add items to the individual groups. The groups contain properties such as an initial active state, data
type, and access path.

Note: Active items will automatically receive data change notifications. The current value and quality will be
displayed in the Item View.

See Also: Server, Group, and Items.

www. kepware.com
4 OPC Quick Client

Main Window
The following image is a view of the application.

Title Bar
The Title Bar displays the name of the loaded project file. An asterisk (*) following the name indicates that it
has been modified.

Toolbar
Descriptions of the icons are as follows:

Creates a new project.


Opens an existing project from disk.
Saves the current project to disk.
Creates a new server connection.
Creates a new group.
Creates a new item.
Edits the properties of the selected server, group, or item.
Cuts the current selection to the clipboard.
Copies the current selection to the clipboard.
Pastes the server, group, or items from the clipboard.
Deletes the current selection.

Group Window
The Group window manages a list of server connections along with their group objects. To display a menu of
options applicable to the server/group, right-click on it. To display the property sheet for the server/group,
double-click on it. For more information, refer to Server and Group.

Item Window
The Item window displays a list of item information for the selected group. To display a menu of options
applicable to the item, right-click on it. To display the properties dialog for the item, double-click on it. For
more information, refer to Items.

www. kepware.com
OPC Quick Client 5

Note: Clicking on the Item ID column heading will cause the item list to be sorted based on the Item ID. To
change column widths, click and drag the header for the desired column to the left or right end of the header
button until the column is the desired size.

Message Log
The Message Log window logs status messages generated by the application. As with the Item window, the
column headers may be resized. This window does not support sorting.

www. kepware.com
6 OPC Quick Client

Server Connection
A server connection provides a link between an OPC server and this client. Groups are added through this
connection. To create a new server connection, click Edit | New Server Connection. Alternatively, click the
New Server toolbar button.

Descriptions of the parameters are as follows:

l Prog ID: This parameter specifies the Prog ID of the OPC Server to which the client will connect. Use
the tree display to browse for registered servers. The Prog ID field can be automatically updated by
double-clicking on any registered server.
l Remote Machine Name: This parameter specifies the name of the machine on which the OPC
server resides. This field should be left blank if the server is located on the same machine as the
client.
l Connection Type: This parameter specifies the type of connection the client should establish with
the OPC server on the local machine. The options are InProc, Local, or Any. If the server is
registered as InProc, then an InProc connection is attempted; otherwise, a Local connection will be
attempted. This option is not available when connecting to a remote machine.

Server Properties
Once the client makes a successful connection to a server, the Server Properties dialog may be invoked by
clicking Edit | Properties.

Status
The Status tab is the default display, and details the server's current status.

www. kepware.com
OPC Quick Client 7

The client queries the server's status and obtains the following information:

Status Item Description


Prog ID The Prog ID of the OPC Server to which the client will connect.
Vendor A string that specifies vendor-specific information.
Start Time Time at which the server was started.
Current Time Current time as recognized by the server.
Last Update Time that the server sent the last data update to the client on this connection.
Time
Server State The current state of the server. Valid states are Running, Failure, No Configuration,
Suspended, and Test.
Major Version Major version of the server software.
Minor Version Minor version of the server software.
Build Number Build number of the server software.
Connection Type of connection with the server. This connection may be inproc, local, or any that the
Type OS chooses.

Interfaces
The Interfaces tab lists the interfaces that are required at the server level. Interfaces that are not required
are considered optional. The Supported column states which interfaces are supported.

www. kepware.com
8 OPC Quick Client

Identification
The Identification tab allows users to enter an optional name to identify the client to the server. The default
client name is "Quick Client".

Visual/Operational Changes
When the OPC Quick Client adds, connects, or disconnects a server connection, there will be a change in its
appearance. The image that appears to the left of each server connection will change to one of the
following:

The client is connected to the server.


The client is disconnected from the server.
The client could not connect to the server (the server may not be properly registered).

www. kepware.com
OPC Quick Client 9

Group
A group is used to organize a collection of items with a common set of properties. The group also specifies
several properties, such as group name, update rate, time bias, percent dead band, Language ID, active
state, and the data connection type (among others). To create a new group, click Edit | New Group.
Alternatively, click New Group in the toolbar.

General

Descriptions of the parameters are as follows:

l Name: This parameter specifies a name that will identify the group. If it is left empty, the OPC server
will generate a unique name.
l Update Rate: This parameter specifies how often the OPC server will provide updates for changing
data. The default setting is 1000 milliseconds.
l Time Bias: This parameter specifies the time difference between the client/server and the actual
device. The information allows the client to convert the timestamp received by the server back to the
local time of the device. The default setting is 0 minutes.
l Percent Dead Band: This parameter specifies the percent change in data required to notify the
client of a data change. When scaling is enabled for the item, the required data change will be
calculated using the scaled range. When scaling is not enabled for the item, the required data change
will be calculated using the full range of the specified data type. The default setting is 0.
l Language ID: This parameter specifies the language that will be used by the server when returning
values as text for operations on this group.
l Update Notification: This parameter specifies the method to be used when receiving data change
notifications or initiating asynchronous requests. Valid selections are OPC 1.0 (No Timestamp), OPC
1.0 (With Timestamp) and OPC 2.0/3.0. Data Access 2.0/3.0 servers automatically supply timestamps
with all data transactions.

www. kepware.com
10 OPC Quick Client

l Active State: This parameter specifies the active state of the group. When the group is active, the
client will receive data change updates for all active items at the specified update rate. The default
setting is checked.
l Keep Alive Rate: This parameter specifies the amount of time between keep-alive messages sent
from the server to the client. The default setting is 0 milliseconds.

Interfaces
Once a group has been successfully added to the project, click Edit | Properties and then select Interfaces.
This will display the information on the interfaces that are required at the group level.

Note: Interfaces that are not required are considered optional. The Supported column states which group
interfaces are supported by the server.

Visual/Operational Changes
When the OPC Quick Client adds, activates, or deactivates a group, the appearance of the folder icon will
change to one of the following:

The group is active.


The group is inactive.
The client could not add the specified group to the server connection.

Items
Items represent data that may be accessed via an OPC server. An item specifies the following properties:
Item ID, access path, requested data type, and active state. To define an item using the Item Editor dialog,
click Edit | New Item. Alternatively, click New Item on the toolbar.

www. kepware.com
OPC Quick Client 11

Descriptions of the parameters are as follows:

l Access Path: This parameter is required by some OPC servers to complete an item definition. To
determine whether an access path is needed, refer to the OPC server's help documentation.
l Item ID: This parameter specifies the OPC server item that will be used to reference data. To
determine valid item names for the location in question, refer to the OPC server's help
documentation. If the server supports tag browsing, then an item can be selected by using the
browse controls.
l Data Type: This parameter specifies the requested data type that will be used when communicating
between the OPC server and the OPC Quick Client. This should be specified to agree with the size and
type of the register or memory location that is being addressed. For more information, refer to Data
Types Description.
l Active: This parameter specifies the item's initial active state. It may be changed later. The default
setting is checked.
l Browse flat address space on selected branch: When checked, this option modifies the item list by
attaching the channel and device name. The default setting is unchecked.
l Validate item before adding it to the list: When checked, this option validates the item before it is
added to the item list. The default setting is checked.
l Add Leaves: When clicked, this button adds the item that is currently selected in the item list to the
Item ID field.

Button Definitions
Descriptions of the icons are as follows:

www. kepware.com
12 OPC Quick Client

Applies changes to the current tag and fills the dialog with properties of the previous tag in the list.
Applies changes to the current tag and fills the dialog with properties of the next tag in the list. If no next
tag exists, the client will attempt to automatically increment the current Item ID.
Creates a new item definition.
Duplicate (decimal, hexadecimal, or octal format) current item definition up to 32,767 items
(automatically increments).
Deletes the current item definition.
Validates the current item definition.

Browsing
If the server supports browsing, the browsing controls will be available for use in searching for selected
items. Filters can be applied as needed in order to simplify the search.

Visual/Operational Changes
When the OPC Quick Client adds, activates, or deactivates an item, the appearance of the tag icon will
change to one of the following:

The item is active.


The item is inactive.
The client could not add the specified item to the group.

www. kepware.com
OPC Quick Client 13

Data Types Description


The OPC Quick Client supports the data types listed in the table below. Their default description is
determined by the OPC server.

Native Description
Boolean Single bit
Boolean Array Single bit array
Char Signed 8-bit value
Char Array Signed 8-bit value array
Byte Unsigned 8-bit value
Byte Array Unsigned 8-bit value array
Short Signed 16-bit value
Short Array Signed 16-bit value array
Word Unsigned 16-bit value.
Word Array Unsigned 16-bit value array
Long Signed 32-bit value
Long Array Signed 32-bit value array
DWord Unsigned 32-bit value
DWord Array Unsigned 32-bit value array
LLong Signed 64-bit value
LLong Array Signed 64-bit value array
QWord Unsigned 64-bit value
QWord Array Unsigned 64-bit value array
Float Single precision floating-point value (32 bits)*
Float Array Single precision floating-point value (32 bits) array*
Double Double precision floating-point value (64 bits)*
Double Array Double precision floating-point value (64 bits) array*
String Zero-terminated character array
String Array Zero-terminated string array
Date YYYY-MM-DDThh:mm:ss.000

*When a floating-point value is Infinite, Indeterminate, or NaN, the following is displayed in the Value column
of its Item Properties:

l 1.#INF
l -1.#INF
l -1.#IND
l 1.#QNAN
l -1.#QNAN

See Also: Options and Items.

www. kepware.com
14 OPC Quick Client

Operations
The OPC Quick Client performs operations on an OPC server at the Server, Group, and Item level. This allows
users to test the functionality of an OPC server.

Server Operations
Connect
To establish a connection to the server, click Tools | Server and then select Connect. All groups and items
will be added.

Disconnect
To disconnect from the server, click Tools | Server and then select Disconnect.

Reconnect
To re-establish a connection to the server, click Tools | Server and then select Reconnect.

Get Error String


To obtain an error description for any valid error codes, click Tools | Server and then select Get Error
String.

Note: To request an error description from the server, enter the error code and then press Apply. If the
server can translate the error code, the description will appear. An OPC server should be able to translate
any OPC error code, in addition to Win32 errors.

This operation tests the following server functionality: IOPCServer::GetErrorString ( ).

Enumerate Groups
To enumerate groups available to the server connection, click Tools | Server and then select Enumerate
Groups.

www. kepware.com
OPC Quick Client 15

Note: The server can be requested to enumerate groups by name or by object. When enumerating by
name, the server passes back an enumeration of strings each containing the name of a group. When
enumerating by object, the server passes back an enumeration of group interface pointers (IUnknown),
which the client can make use of by querying for other interfaces. Either way, the client uses both
mechanisms to obtain the same results: a list of group names along with the properties of each group. The
client can request that only private groups (groups this client added to the server connection), public groups
(groups that may have been added by another client, but are made available) or all groups be enumerated.

This operation tests the following server functionality: IOPCServer::CreateGroupEnumerator ( ).,


IOPCServer::GetGroupByName ( ), IOPCGroupStateMgt::GetState ( ).

Get Group By Name


To obtain group properties by name, click Tools | Server and then select Get Group By Name.

www. kepware.com
16 OPC Quick Client

Note: To request group properties by name, enter the name of the group and then press Apply. If the
server can resolve the group name, the client will proceed to obtain the properties for that group.

This operation tests the following server functionality: IOPCServer::GetGroupByName ( ),


IOPCGroupStateMgt::GetState ( ).

Auto Create Tags


To automatically create tags from the connected OPC server, click Tools | Server and then select Auto
Create Tags. For more information, refer to Options.

Group Operations
Clone Group
To clone the selected group, click Tools | Group and then select Clone Group. The OPC server should
create a new group with a unique name and with identical properties to the group that is being cloned. If the
cloned group contains items, those items should also be cloned. The state of the cloned group and items
should be set to inactive.

This operation tests the following server functionality: IOPCGroupStateMgt::CloneGroup, SetState ( ),


IOPCItemMgt::CreateEnumerator, SetClientHandles ( ), IEnumOPCItemAttributes::Reset, Next ( ).

Asynchronous Refresh (Cache/Device)


To perform an asynchronous refresh from cache/device on the selected items, click Tools | Group and then
select Asynchronous 1.0/2.0 Cache Refresh or Asynchronous 1.0/2.0 Device Refresh. Refreshes done
using 1.0 use IAdviseSink to return refresh notifications. Refreshes done using 2.0 use connection points to
exchange data between client and server.

www. kepware.com
OPC Quick Client 17

Item Operations
Set Active/Inactive
To activate/inactivate the selected item(s), click Tools | Item and then select Set Active | Inactive. Only
active items should receive on data change updates.

Note: The group must be set to active.

Synchronous Read (Cache/Device)


To perform a synchronous read from the cache/device on the selected items, click Tools | Item and then
select Synchronous Cache Read or Synchronous Device Read.

Asynchronous Read (Cache/Device)


To perform an asynchronous read from the cache/device on the selected items, click Tools | Item and then
select Asynchronous 1.0/2.0 Cache Read or Asynchronous 1.0/2.0 Device Read. Reads done using 1.0
use IAdviseSink to return read complete notifications. Reads done using 2.0 use connection points to
exchange data between the client and server.

Synchronous/Asynchronous Write
To perform a synchronous/asynchronous write on the selected items, click Tools | Item and then select
Synchronous Write or Asynchronous 1.0/2.0 Write.

Note: Both types of writes utilize the same dialog. The dialog displays the current value at a 100 millisecond
refresh rate. To send the data to the server, enter the data to write in the Write Value column and then press
Apply. To apply the write and close the dialog, click OK. To abort the operation, click Cancel.

Options
The OPC Quick Client is used to configure many settings. To open the Options dialog, click Tools | Options.

www. kepware.com
18 OPC Quick Client

Descriptions of the parameters are as follows:

l Automatically Build a Client Project When Launched by the Server: When checked, the OPC
Quick Client will automatically build a client project with all the tags in the OPC server when it is
launched from the OPC server. The default setting is checked.
l Ignore Browse Paths Containing Leading Underscores When Auto-Building: When checked,
items that belong to browse path segments beginning with an underscore will not be included in
automatically built projects. These paths may include system or internal device tags. The default
setting is unchecked (all available items will be included in the project).
l Prompt to Save Project on Exit: When checked, users will be prompted to save the project before
exiting the application. The default setting is checked.
l Default Group Update Rate (ms): This parameter specifies the default update rate for
automatically generated groups. The update rate determines how often the OPC server will provide
updates for changing data. The default setting is 1000 milliseconds. For more information, refer to
Group.
l Auto-Generated Group Name Depth: This field specifies the depth level for names of automatically
generated groups. The default setting is 3. For more information, refer to "Group Name Depth"
below.
l Show hexadecimal value for floating point numbers: When enabled, this option will affect how
floating point numbers are displayed and written.

l In terms of display, this option causes Float or Double data types to display the floating point
number in addition to the hexadecimal value. For example, "12.34 (0X414570A4)".
l In terms of writing, this option allows hexadecimal values to be written for Float and Double
data types. The hexadecimal value should be in the form "0x12345678" for Floats (8 digits)
and "0x123456789ABCDEF1" for Doubles (16 digits). Inputs that are not in a hexadecimal
format will be treated as normal floating point inputs.

l Use DCOM for remote security: When checked, the OPC Quick Client, opens on next launch with
system-level DCOM security settings. When unchecked, the OPC Quick Client opens with “wide-open”
DCOM security settings. The default is unchecked.

Note: This option will also increase the Floating Point Precision to 17.

Group Name Depth

www. kepware.com
OPC Quick Client 19

The higher the group name depth, the more sub-groups that will be created. For example, tags structured
like "Channel1.Device1.Tag1" and "Channel1.Device1.Group1.Tag1" in OPC server will be added differently
in OPC Quick Client depending on the Group Name depth setting.

Depth Level Description


1 The group "Channel1" (name depth: 1) will be created. Both tags will be added to this
group.
2 The group "Channel1.Device1" (name depth: 2) will be created. Both tags will be added
to this group.
3 The group "Channel1.Device1" (name depth: 3. Tag names do not form a part of the
group name) will be created. The tag "Channel.Device1.Tag1" will be added to this
group.

The group "Channel1.Device1.Group1" (name depth: 3) will be created. The tag


"Channel.Device1.Group1.Tag1" will be added to this group.

Note: The maximum allowed group name depth is 3. In the example above, if there were any more sub-
groups inside Group1, they would be added to the OPC Quick Client group "Channel1.Device1.Group1".

www. kepware.com
20 OPC Quick Client

Test Mode
The OPC Quick Client Test Mode includes both functional and performance tests to run on projects. Projects
must contain at least one server connection with one group that contains one item.

Functional Test
Functional tests perform set routines on the project. When enabled, the OPC Quick Client will run the first
test in the selected list for the amount of time specified in the Test Interval parameter (which may be 1 to
360 minutes). Once the interval expires, the client will stop the first test and move onto the next. When the
last test in the list has finished, the client will sit idle for the same interval before repeating the test suite.

Note: Users cannot change the project while the functional test is running.

Test 1 Description
This test simulates an HMI product by treating each group as a panel. The test first sets all items to an
inactive state. Then, it selects the first group in the list, sets all of the group's items active, and receives data
updates for approximately 5 seconds. After the 5 second period, the active items are set to an inactive state
and the test proceeds to the next group. The procedure continues cycling through all the groups and starting
over when the last group is complete.

www. kepware.com
OPC Quick Client 21

Test 2 Description
This test performs read, write, and refresh operations on active and inactive items. The test first sets all
items to an inactive state. Then, it proceeds through the following sequence:

1. Select the next group in the list.

2. Perform a synchronous read from device for all items (all group items are active).

3. Perform a synchronous write to all items (all group items are active).

4. Perform a synchronous read from device for all items (all group items are inactive).

5. Perform a synchronous write to all items (all group items are inactive).

6. Perform an asynchronous read from device for all items (all group items are active).

7. Perform an asynchronous write to all items (all group items are active).

8. Perform an asynchronous read from device for all items (all group items are inactive).

9. Perform an asynchronous write to all items (all group items are inactive).

10. Perform an asynchronous refresh from device (all group items are active).

The sequence will repeat until the test interval time is reached.

Test 3 Description
This test duplicates Test 2, except all operations are done from cache instead of device.

Test 4 Description
This test performs synchronous read and write operations on active items. The test first sets all items in the
project to an active state. Then, it performs a synchronous write every 2 seconds and a synchronous read
from device every 5 seconds. If there is more than one group, the test performs 2 writes to 1 read, and then
moves onto the next group.

Test 5 Description
This test duplicates Test 4, except that all operations are done from cache instead of device.

Test 6 Description
This test performs the adding and removal of all items in the project. The test first removes all items in the
project. After a 2 second period the test re-adds all the items in the project. The test continues to transition
between the two states every 2 seconds.

Test 7 Description
This test shows the performance of the server when reading items from cache. The test first activates all
items in the project, which is a requirement for cache reads. Then, it proceeds to the first group in the
project and performs as many synchronous reads as it can in 1 second. The number of items read in 1
second is displayed in the message log. The test continues by selecting the next group and proceeding with
the same tests.

Note: If a group contains multiple items, each synchronous read request includes all the items in one call to
the server.

Test 8 Description
This test activates all items in a project (including all connections and groups). It updates the display window,
pauses for the test interval selected by the user, and then inactivates all items.

www. kepware.com
22 OPC Quick Client

The sequence will complete once per test interval.

Test 9 Description
This test activates all items in a project (including all connections and groups). It performs a random number
of synchronous writes (between 5 and 100) to all items in a project in the following sequence:

1. Get the first connection, first group.

2. Perform a random number of synchronous writes (between 5 and 100) to each item in the group.

3. Pause for 1 second between each item in the group.

4. Pause for 10 seconds between groups.

5. Repeat for each connection in the project.

The sequence will repeat until the test interval time is reached.

Test 10 Description
This test activates all items in a project (including all connections and groups). It performs an asynchronous
read for all items in a project in the following sequence:

1. Get the first connection, first group.

2. Perform an asynchronous read for all items in the group.

3. Pause for 1 second between each item in the group.

4. Pause for 10 seconds between groups.

5. Repeat for each connection in the project.

The sequence will repeat until the test interval time is reached.

Test 11 Description
This test inactivates all items in a project (including all connections and groups). It performs an
asynchronous read for all items in a project in the following sequence:

1. Get the first connection, first group.

2. Perform an asynchronous read for all items in the group.

3. Pause for 1 second between each item in the group.

4. Pause for 10 seconds between groups.

5. Repeat for each connection in the project.

The sequence will repeat until the test interval time is reached.

Test 12 Description
This test is a server connection stress test. It creates the maximum allowable number of server connections.
In a separate thread for each connection, it automatically creates tags and performs random sync and async
Read and Write requests to all items in all non-system groups. The test will verify that incomplete
transactions are handled correctly when the client disconnects with a transaction pending. After writing to
each non-system group, each thread in Test 12 will close its connection.

The sequence will end when all connections are closed or the test interval time is reached.

Performance Test

www. kepware.com
OPC Quick Client 23

Performance tests measure the amount of time it takes to execute an operation on each item configured in
the OPC Quick Client.

Descriptions of the parameters are as follows:

l Test Type: This parameter specifies the test type. Tests are named after the operation that they
perform. Options include Sync Device Read, Sync Cache Read, and Sync Write (which writes a random
value to each item). The default setting is Sync Device Read.
l Iterations: This parameter specifies the iteration. An iteration is complete when the test has
performed once on each item. Options include Cycles and Duration. The default setting is 100 cycles.
Descriptions of the options are as follows:

l Cycles: The test will iterate for as many times as entered in the field.
l Duration (ms): The test will run for as many milliseconds as entered in the field.
l Results: This parameter displays the results of the performance test. The following fields will be
displayed:

l Average: This specifies the median time per iteration in milliseconds.


l Max: This specifies the maximum time for an iteration in milliseconds.
l Min: This specifies the minimum time for an iteration in milliseconds.
l Iterations: This specifies the number of iterations.

Running a Performance Test


For more information, refer to the instructions below.

www. kepware.com
24 OPC Quick Client

1. To start, use the drop-down menu to specify the test type.

2. Next, select the type of iteration. Then, specify the amount.

3. Click Run.

Note: Users can stop a test at any time by clicking Stop. A progress bar will display how far the test has
progressed.

www. kepware.com
OPC Quick Client 25

License Agreement
License and Warranty
The license and warranty refer to the OPC Quick Client provided with the OPC server. It does not refer to any
other software provided by the supplier.

The OPC Quick Client Software accompanying this license agreement is the property of supplier and is
protected by copyright law. A user's rights and obligations in its use are described as follows:

1. Users may not modify or attempt to reverse engineer the software, or make any attempt to change
or examine the source code of the Software.

2. Users may not give or distribute copies of the Software or written materials associated with the
Software to others.

3. Users may not sub-license, sell or lease the Software to any person or business.

Warranty
The Supplier does not guarantee that the Software will satisfy application needs or be error free.

Disclaimer of Damages
Even if the Software does not satisfy the customer's needs or is viewed as failing to perform, in no event will
the Supplier be liable to users for any direct or indirect damages, including lost profits or lost data. The
Supplier's liability shall never exceed the purchase price for the Software.

www. kepware.com
26 OPC Quick Client

Index

Access Path 10
Asynchronous Refresh 16

Browsing Items 10

Data Type 10
Data Types Description 13

Enumerate Groups 14

Get Error String 14


Get Group By Name 15
Group 9
Group Name 9

Item Active State 10


Item ID 10
Items 10

Language ID 9
License Agreement 25

www. kepware.com
OPC Quick Client 27

Main Window 4

OPC Quick Client Help 3


Operations 14
Options 17
Overview 3

Prog ID 6

Remote Machine Name 6

Server Connection 6
Server Interfaces 6

Test Mode 20
Time Bias 9