502012004【b】sun (3 10) k g03 组串说明书 ver2.0 deye 12.5a 1

This user manual provides essential information on the installation, operation, and maintenance of the Grid-tied PV String Inverter, including safety warnings and instructions. It outlines the inverter's components, electrical connections, and installation procedures while emphasizing the importance of adhering to local safety regulations. The manual also includes guidance on selecting an appropriate installation location and ensuring proper electrical connections to prevent hazards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views44 pages

502012004【b】sun (3 10) k g03 组串说明书 ver2.0 deye 12.5a 1

This user manual provides essential information on the installation, operation, and maintenance of the Grid-tied PV String Inverter, including safety warnings and instructions. It outlines the inverter's components, electrical connections, and installation procedures while emphasizing the importance of adhering to local safety regulations. The manual also includes guidance on selecting an appropriate installation location and ensuring proper electrical connections to prevent hazards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

R

Grid-tied PV String Inverter

User Manual
About This Manual
The manual mainly describes the product informa�on, guidelines for installa�on, opera�on and
maintenance. The manual cannot include complete informa�on about the photovoltaic (PV) system.

How to Use This Manual


Read the manual and other related documents before performing any opera�on on the inverter.
Documents must be stored carefully and be available at all �mes. Contents may be periodically
updated or revised due to product development. The informa�on in this manual is subject to
change without no�ce. The latest manual can be acquired via [email protected]

Photovoltaic Grid-connected System

PV array Inverter Metering Power grid

Family load
Applica�on of inverter in photovoltaic power system

1. Introduc�on
1.1 Appearance Introduc�on
On-grid Inverter can convert solar panel DC power into AC power which can directly input to
the grid. Its appearance is shown below.These models contain SUN-3K-G03, SUN-4K-G03,
SUN-5K-G03, SUN-6K-G03, SUN-7K-G03, SUN-8K-G03, SUN-10K-G03.
The following is collec�vely referred to as “inverter”.

RS232 485
ON
M16X1.5

OFF RS485

M12X1.5

DC SWITCH limiter
DC AC Normal Alarm

Pic 1.1 Front view Pic 1.2 Bo�om view


1.2 Parts list
Please check the following table, to see whether all the parts are included in the package

DC AC Normal Alarm

Moun�ng stainless steel


Grid-�ed PV String Inverter Wall moun�ng bracket x1 screws M4×12
x1 x4

DC power connectors Stainless steel an�-collision


AC power connectors x1 (including Inserted spring) bolt M6×80
x2 x4

User
manual

Square hole sealing plate


User manual x1 Datalogger (op�onal) x1 (For WIFI func�on)
x1

SUN limiter(op�onal) x 1 *Sensor Clamp x 3


Meter(op�onal)
When ordering the sun limiter, it will includes 3pcs CT. x1
2. Safety warnings and instruc�ons
Improper use may result in poten�al electric shock hazards or burns.This manual contains
important instruc�ons that should be followed during installa�on and maintenance. Please
read these instruc�ons carefully before use and keep them for future reference.

2.1 Safety signs


Safety symbols used in this manual, which highlight poten�al safety risks and important safety
informa�on, are listed as follows:

Warning:
Warning symbol indicates important safety instruc�ons, which if not correctly
followed, could result in serious injury or death.

Shock Hazard:
Cau�on, risk of electric shock symbol indicates important safety instruc�ons,
which if not correctly followed, could result in electric shock.

Safety Hint:
Note symbol indicates important safety instruc�ons, which if not correctly
followed, could result in some damage or the destruc�on of the inverter.

High Temperature Hazard:


Cau�on, hot surface symbol indicates safety instruc�ons, which if not correctly
followed, could result in burns.

2.2 Safety instruc�ons

Warning:
Electrical installa�on of the inverter must conform to the safety opera�on rules
of the country or local area.

Warning:
Inverter adopts non-isolated topology structure, hence must insure DC input and
AC output are electrical isolated before opera�ng the inverter.
Strictly prohibit grounding the posi�ve and nega�ve poles of the PV string.
Otherwise it will damage the inverter.

Shock Hazard:
Prohibit disassembling inverter case, there exis�ng shock hazard, which may
cause serious injury or death, please ask qualified person to repair.
Shock Hazard:
When PV module is exposed to sunlight, the output will generate DC voltage.
Prohibit touching to avoid shock hazard.

Shock Hazard:
While disconnect the input and output of the inverter for maintenance, please
waits for at least 5 mins un�l the inverter discharge the remnant electricity.

High Temperature Hazard:


Local temperature of inverter may exceed 80 while under opera�ng.
Please do not touch the inverter case.

2.3 Notes for using


The three phase string power inverter is designed and tested under related safety regula�ons.
It can ensure the personal safety of the user. But as a electric device,it may cause shock or
injury by incorrect opera�on. Please operate the unit under below requirements:

1. Inverter should be installed and maintained by qualified person under local standard
regula�ons.
2. Must disconnect the AC side first, then disconnect DC side while doing installa�on and
maintenance, a�er that, please wait at least 5 mins to avoid ge�ng shocked.
3. Local temperature of the inverter may exceed 60 ℃ while under opera�ng.Do not touch
to avoid ge�ng injured.
4. All electrical installa�on must be in accord with local electrical standards, and a�er
obtaining the permission of the local power supply department, the professionals can
connect the inverter to the grid.
5. Please take appropriate an�-sta�c measure.
6. Please install where children can not touch.
7. When star�ng the inverters, first close the circuit breaker at the grid side, then close the
DC side; when closing the inverters, first disconnect the circuit breaker at the AC side, then
disconnect the DC side.
8. Don’t insert or remove AC and DC terminals when the inverter is in normal opera�on.
9. The DC input voltage of the inverter must not exceed the maximum value of the model.
3. Opera�on Interface
3.1 Interface View

DC AC Normal Alarm

Pic 3.1 Front panel display

3.2 Status Indicator


There are four LED status indicator lights in the front panel of the inverter. Please see table 3.1
for details.

Indicator status Explanation


on Inverter detects DC input
off Low DC input voltage
on Grid Connected
off Grid Unavailable
on Under normal opera�ng
off Stop opera�ng
on Detected faults or report faults
off Under normal opera�ng

Table 3.1 Status indicator lights


3.3 Bu�ons
There are four keys in the front panel of the Inverter(from le� to right): Esc, Up, Down and
Enter keys. The keypad is used for:

● Scrolling through the displayed op�ons (the Up and Down keys);


● Access to modify the adjustable se�ngs (the Esc and Enter keys).

Esc Up Down Enter

3.4 LCD Display


The two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter, which
shows the following informa�on:
● Inverter opera�on status and data;
● Service messages for operator;
● Alarm messages and fault indica�ons.
4. Product installa�on
4.1 Select installa�on loca�on
To select a loca�on for the inverter, the following criteria should be considered:
WARNING: Risk of fire
● Do not install the inverter in areas containing highly flammable materials or gases.
● Do not install the inverter in poten�ally explosive atmospheres.
● Do not install in small closed spaces where air can not circulate freely. To avoid overhea�ng,
always make sure the flow of air around the inverter is not blocked.
● Exposure to direct sunlight will increase the opera�onal temperature of the inverter and
may cause output power limi�ng. It is recommended that inverter installed to avoid direct
sunlight or raining.
● To avoid overhea�ng ambient air temperature must be considered when choosing the
inverter installa�on loca�on. It is recommended that using a sun shade minimizing direct
sunlight when the ambient air temperature around the unit exceeds 100°F/40.

Pic 4.1 Recommended installa�on place


● Install on a wall or strong structure capable of bearing the weight.
● Install ver�cally with a maximum incline of +/-15°. If the mounted inverter is �lted to an
angle greater than the maximum noted, heat dissipa�on can be inhibited, and may result in
less than expected output power.
● If install more than one inverter, must leave at least 500mm gap between each inverter. And
each inverter must be at least 500mm above and below. And must install the inverter at the
place where children cannot touch. Please see picture 4.3.
● Consider whether the installa�on environment is helpful to see the inverter LCD display and
indicator status clearly.
● Must offer a ven�late environment if inverter installed in the air�ght house.

Safety Hint:
Do not place or store any items next to the inverter.

1 5

Pic 4.2 Installa�on Angle


5 00mm

5 00mm

Pic 4.3 Installa�on Gap

4.2 Inverter Installa�on


The inverter is designed according to the wall mounted type installa�on, please use the wall
mounted (the brick wall of the expansion bolt) when installing.

Anchoring

Moun�ng bracket

Stainless steel screws

Inverter

Pic 4.4 Inverter Installa�on


Procedure shows below:
1. Locate on the appropriate wall according to the bolt posi�on on the moun�ng bracket, then
mark the hole.On the brick wall, the installa�on must be suitable for the expansion bolt
installa�on.

Pic 4.5 Inverter hanging plate installa�on

2. Ensure that the posi�on of the installa�on holes on the wall is in accordance with the
moun�ng plate, and the moun�ng rack is horizontally placed.
3. Hang the inverter to the top of the moun�ng rack and then use the M4 screw in the
accessory to lock inverter heat sink to the hanging plate, to ensure that the inverter will not
move.

Pic 4.6 Inverter installa�on


5 Electrical Connec�on
5.1 DC input terminal connec�on
1. Switch the Grid Supply Main Switch(AC)OFF.
2. Switch the DC lsolator OFF.
3. Assemble PV input connector to the inverter.

Safety Hint:
Please don’t connect PV array posi�ve or nega�ve pole to the ground, it could
cause serious damages to the inverter.

Safety Hint:
Before connec�on, please make sure the polarity of the output voltage of PV
array matches the “DC+” and “DC-” symbols.

Safety Hint:
Before connec�ng inverter, please make sure the PV array open circuit voltage is
within the 1000V of the inverter.

Pic 5.1 DC+connector (MC4) Pic 5.2 DC-connector (MC4)

Safety Hint:
Please use approved DC cable for PV system.

Cross section
Cable type
Range Recommended value
Industry generic PV cable 4.0~6.0
4.0(12AWG)
(model: PV1-F) (12~10AWG)

Table 5.1 DC Cable Specifica�ons


The steps to assemble the DC connectors are listed as follows:
a) Strip off the DC wire about 7mm, disassemble the connector cap nut (see picture 5.3)

Pic 5.3 Disassemble the connector cap nut

b) Crimping metal terminals with crimping pliers as shown in picture 5.4.

Pic 5.4 Crimp the contact pin to the wire

c) Insert the contact pin to the top part of the connector and screw up the cap nut to the top
part of the connector. (as shown in picture 5.5).

Pic 5.5 connector with cap nut screwed on


d) Finally insert the DC connector into the posi�ve and nega�ve input of the inverter,shown as
picture 5.6

Pic 5.6 DC input connec�on

Warning:
Sunlight shines on the panel will generate voltage, high voltage in series may
cause danger to life. Therefore, before connec�ng the DC input line, the solar
panel needs to be blocked by the opaque material and the DC switch should
be 'OFF', otherwise, the high voltage of the inverter may lead to life-
threatening condi�ons.

5.2 AC input terminal connec�on


Do not close the DC switch a�er the DC terminal is connected.Connect the AC terminal to the
AC side of the inverter, the AC side is equipped with Three phase AC terminals that can be
conveniently connected. Flexible cords are recommended for easy installa�on. The specifica-
�ons are as shown in Table 5.2.

Warning:
Prohibit using a single circuit breaker for mul�ple inverters, prohibit the
connec�on of load between inverter circuit breakers.

Model Cable CSA Cable outer dia AWG Breaker Max cable length

SUN-3K/4K/5K/6K Outside cable


4mm 15-18mm 10 20A/400V
7K/8K/10K-G03 (3+N+PE)20m

Table 5.2 Cable informa�on


The AC output connector is divided into three parts: matching socket, sleeve and sealing-
sleeve, as shown in picture 5.7, the steps are as follows:

Step 1: Remove the cable sealing ring and sleeve in sequence from the AC connector.
Step 2: Use strippers to strip the protec�ve sheath and insula�on layer of the AC cable to the
right length, as shown in Picture 5.8.

1. Matching socket 2.Sleeve 3.Sealing core 4.Sealing nut


Pic 5.7 AC connector structure

Step 3: Insert the cable (L1, L2, L3, NPE) into the sealing sleeve.

Pic 5.8 Strip AC cable

Warning:
Be careful to dis�nguish the L1, L2,L3,N and PE of the AC cables.

Step 4: Use the hexagon screwdriver, loosen the bolts of the socket in turn, and insert each
cable core into the corresponding jack, and set each screw. The connec�on hole of AC
connec�on terminal labeling is shown in Picture 5.9.
Pic 5.9 AC Connector Hole Pa�ern

Step 5: Set the sleeve and sealing ring in place.


Step 6: Connect the terminals to the inverter as shown in picture 5.10.

Pic 5.10 AC input connec�on


5.3 The connec�on of the ground line
Good grounding is good for resis�ng surge voltage shock and improving EMI perfor-
mance.Therefore, before connec�ng AC, DC and communica�on cables, you need to ground
the cable firstly. For a single system, just ground the PE cable. For mul�ple machine systems,
all PE cables of the inverter need to be connected to the same grounding copper platoon to
ensure the equipoten�al connec�on. The installa�on of the shell ground wire is shown as
picture 5.11.

Pic 5.11The installa�on of the shell ground wire

Warning:
Inverter has built-in leakage current detec�on circuit, If an external leakage
current protec�on device is connected, its opera�ng current must be greater
than 300 mA or higher, otherwise inverter may not work properly.
5.4 Max. over current protec�on device
In order to protect the inverter AC connec�on, it is recommended to install a circuit breaker to
prevent overcurrent. See table 5.3 below.

Rated output Rated output Current for protection


Inverter
voltage(V) current(A) device(A)
SUN-3K-G03 230 4.3 20
SUN-4K-G03 230 5.8 20
SUN-5K-G03 230 7.2 20
SUN-6K-G03 230 8.7 20
SUN-7K-G03 230 10.1 20
SUN-8K-G03 230 11.6 20
SUN-10K-G03 230 14.5 20

Table 5.3 Recommended current protector specifica�ons

5.5 Inverter monitoring connec�on


Inverter has the func�on of wireless remote monitoring. The inverter with Wi-Fi func�on is
equipped with Wi-Fi Plug to connect the inverter and network. Wi-Fi Plug's opera�on,
installa�on, Internet access, APP downloading and other processes are detailed in the
instruc�ons.

Phone

GPRS

Router Web Server


WIFI

PC

Pic 5.12 Internet monitoring solu�on


5.6 Installa�on of datalogger
When the inverter is out of the factory, the installa�on loca�on of datalogger is sealed by a sealed
plate as shown in Picture 5.13. When installing the datalogger, remove the sealing plate, replace it
with the sealing plate with square hole in the accessories, and �ghten the screws. Insert the
datalogger into the interface and fix it with a screw. The configura�on of the datalogger needs to
be performed a�er various electrical connec�ons have been completed and the inverter DC power
on. When the inverter is on the DC power, it is determined whether the datalogger is normally
electrified (The LED light shines out of the shell).

Pic 5.13 Datalogger installa�on diagram

5.7 Configura�on of datalogger


For the configura�on of datalogger, please refer to illustra�ons of the datalogger.
6. Startup and Shutdown
Before star�ng the inverter, make sure that the inverter can meet the following condi�ons,
otherwise it may result in fire or damage to the inverter. In this case, we do not undertake
any responsibility. At the same �me, to op�mize the system configura�on, it is recommended
that the two inputs be connected to the same number of photovoltaic modules.

a). The maximum open voltage of each set of photovoltaic modules shall not exceed
1000Vdc under any condi�ons.

b). Each input of the inverter be�er use the same type of photovoltaic module in series.

c). Total output power of pv shall not exceed the maximum input power of inverter, each
photovoltaic modules shall not exceed the rated power of each channel.

6.1 Start up the inverter

When start up the three phase string inverter, should fellow below steps

1. First switch on the AC breaker.

2. Turn on the DC switch of the photovoltaic module, and if the panel provides sufficient
star�ng voltage and power, the inverter will start.

3. When the ac voltage and DC voltage are normal, the inverter start-up is readyto begin.
The inverter will first check the internal parameters and the grid parameters, while the liquid
crystal will show that the inverter is self-checking.

4. If the parameter is within acceptable range, the inverter will generate energy.
NORMAL indicator light is on.

6.2 Inverter Shutdown

Must follow below steps while shu�ng down the inverter:

1. Switch off the AC breaker.

2. Wait for 30 seconds, turn off the DC switch (if any), or simply disconnect the DC input
connector. The inverter will close the LCD and all LED within two minutes.
7 Zero export func�on via SUN limiter
The inverter has external zero export func�on. This func�on is op�onal. It can collect counter-
current power to control the output power of the inverter, so that the power of inverter and
load can be offset, and the excess power will not be fed back to the grid. If you purchase the
inverter with zero export func�on, an external zero export device ( SUN limiter or energy meter)
will be included in the package which is necessary for the func�on.The SUN limiter shows as
Pic 7.1.You can see corresponding line mark next to the green interface. The green terminals
on the le� are the interface of three-phase AC line (L1, L2, L3) and N Line (N), and the the right
are the interface between three sets of current sensor and one set of control terminals. SUN limiter
will collect voltage and current from these interfaces and send control signals to the inverter.

Pic 7.1 SUN Limiter view

7.1 SUN Limiter func�on wiring diagram

When you are reading this, we believe that you have completed the connec�on according to the
requirements of chapter 5, if you has been running your inverter , and you want to use the limiter
func�on, please turn off AC and DC switch of the inverter, and wait for 5 minutes un�l the inverter
completely discharged.In order to make it easier for you to use the limiter func�on, we have
specifically given the wiring diagram, as shown in Picture 7.2, the yellow/green/red live line
(L1,L2,L3) connected to the u�lity grid live line (U/V/W), blue line means the neutral line.
We recommend installing an AC switch between the inverter outlet and the u�lity grid, the specs
of the AC switchis determined by the load capacity. The AC switch we recommend to connect to
the inverter output refer to Table 5.2.

L1(L)
L1(K)
Solar panels
L2(L)
L2(K)
L3(L)
L3(K)
Limiter
L1
DC AC Normal Alarm

L2
L3
N

Control signal V

DC AC Normal Alarm
N

Distribution Box

Control signal
Load

Pic 7.2 Wiring diagram

7.2 Connect the SUN limiter to inverter

The SUN limiter will measure the voltage and current of three phases separately, and this manual
only introduces the installa�on steps of one phase, the other two phases are the same. The
specific installa�on steps are as follows:

(1) Connect SUN limiter to the grid. Connected to the grid is to measure the voltage of grid. Before
connect to the grid, please turn off the switch to avoid the risk of electric shock. Choose one wire
from the bo�om of the three-phase DC switch. (any phase of U,V,W) to connect with L1 terminal,
then �ghten the line with a screwdriver.

(2) Connect SUN limiter to clamp senor. Clamp senor can measure the current of the AC side, it
should be connected to the front side of the load (domes�c appliance ect.) to achieve this func�on.
Only when the SUN limiter collects the voltage and current of the same phase can it judge the
power of the phase. So the clamp senor should be connected to the same phase as the before.
Open the side buckle of the clamp senor, then clamp the senor to the AC line on the DC switch,
the arrow direc�on on the senor should towards that of the load. The clamp senor has two lines
(shown as below), and the white line corresponds to K terminal, black line corresponds to L
terminal. Connect the white line to the L1(L) and L1(K) terminal refer to the line mark of the SUN
limiter and �ghten the line with screwdriver. This is the whole installa�on process of one phase.
Load

Pic 7.3 Clamp Senor Pic 7.4 Clamp Senor internal arrow

(3) A�er you finish the installa�on in process 1 and 2, connect the N line (N) to the N terminal
of the limiter and �ghten the line.

(4) Connect the control line. There are two numbers 1 and 2 on the interface of SUN limiter, and
the same on the waterproof terminal of the inverter. Twist the waterproof terminal and connect
the red line to number 1 and black line to number 2 shown as the picture. A�er that connect
the terminal to the interface of the SUN limiter. The other side of the line should be connected to
the control terminal.

Pic 7.5 Waterproof terminal Pic 7.6 Connect limiter to inverter


Pic 7.7 Connect terminal to inverter

7.3 Use of zero export func�on


When the connec�on is completed, the following steps should be referenced to use this func�on:
1. Turn on the AC switch
2. Turn on the DC switch, Wai�ng inverter LCD ligh�ng up
3. Press Enter bu�on on the LCD panel in the main interface into the menu op�ons, select
[parameter se�ng] to Enter setup submenu, and then select [running parameters] as shown in
figure 7.8, at this �me please Input the default password 1234 through pressing the bu�on [up
down, confirm], enter the opera�on parameter se�ng interface, Shown as figure:

System Param << *Fun GFDI OFF


Run Param Limiter 0FF <<
Pic7.8 Parameter se�ng Pic 7.9 Limit switch
4. Operate the bu�on [up down], move se�ng cursor to limit func�on and press the bu�on [enter].
At this �me you can turn on or turn off the limit func�on by choosing [up down] bu�on, please
press [enter] bu�on to confirm when se�ng done.
5. Move the cursor to [confirm] , press ENTER to save the se�ngs and exit the running parameters
page, otherwise the se�ngs are invalid.

6.If set up successfully, you can return to the menu interface, and display the LCD to [home page]
by press the [up down] bu�on. If it displayed as [u�lity power], the limiter func�on se�ngs will
be completed. Shown as picture 7.10.
*Fun GFDI OFF Utility Power:
Limiter ON << 20W
* This item is not avaiable for some FW verison
Pic 7.10 Limiter func�on turn on
7. [u�lity power] showing posi�ve means grid power is consuming energy, and there is no
backflow. If [u�lity power] shows nega�ve, which means there’s excess PV energy flows to
grid or current transformer arrow direc�on is in wrong direc�on. Please read more on
chapter 7.9.

8. A�er properly connec�on is done, wait for inverter star�ng. If the power of the PV array
meets the current power consump�on, the inverter will maintain a certain output to
counteract the power of the grid without backflow .

7.4 Zero-export func�on (Op�on)


The string inverter supports zero-export func�on via Energy meter / SUN-Limiter. Based on
con�nuously data communica�on, once the Limiter or energy meter detects power export to
the grid, it will send the informa�on to the inverter and then inverter will ramp down its ac�ve
power according to match the load demand and achieve zero export. The Zero-export func�on
is op�onal. If you buy the inverter with zero-export func�on via energy meter, energy meter
will be included in the package which is necessary for zero-export func�on.

7.4.1 Zero-export func�on via energy meter


When you are reading this, we believe that you have completed the connec�on according to
the requirements of chapter 5, if you have been running your inverter at this �me, and you
want to use the zero-export func�on, please turn off AC and DC switch of the inverter, and
wait for 5 minutes un�l the inverter completely discharged. Please follow below Picture 7.11
to connect the energy meter.
For system wiring diagram, the red line refers to L line (L1, L2, L3), the black line refers to the
neutral line (N). Connec�ng energy meter RS485 cable to inverter's RS485 port. It's recom-
mended to install an AC switch between the inverter and the u�lity grid, the specs of the AC
switch are determined by the power of load.
If there is no integrated DC switch inside the inverter you purchased, we commend you to
connect the DC switch. The voltage and current of the switch depend on the PV array you
access.
RS 485

Pic 7.11 CHINT meter

Inverter Grid
Solar Panel array

DC AC Normal Alarm

N N
L3 L3
L2 L2
L1 L1

meter
RS485 Communication

VCC_5V 2 3 485_A

GND 1 4 485_B

Family load
Pic 7.12 Connec�on diagram of CHINT meter

Warning:
Ensuring grid input cables connect 1/4/7/10 port of energy meter, and inverter
AC output cables connect 3/6/9/10 port of energy meter when connec�ng.
7.4.2 Use of zero-export func�on
When the connec�on is completed, the following steps should be refered to use this func�on:
1. Turn on the AC switch.
2. Turn on the DC switch, wai�ng for the inverter's LCD is turned on.
3. Press Enter bu�on on the LCD panel in the main interface into the menu op�ons, select
[parameter se�ng] to enter setup submenu, and then select [running parameters] as shown
in picture 7.13, at this �me please input the default password 1234 through pressing the
bu�on [up down, enter], enter the opera�on parameter se�ng interface, shown as
picture 7.14.

System Param << Island OFF


Run Param Meter 0FF <<
Pic 7.13 Parameter se�ng Pic 7.14 Meter switch

4. Operate the bu�on [up down], move se�ng cursor to energy meter and press the bu�on
[enter]. At this �me you can turn on or turn off the energy meter by choosing [up down]
bu�on, please press [enter] bu�on to confirm when se�ng done.
5. Move the cursor to [OK], press [enter] to save the se�ngs and exit the running
parameters page, otherwise the se�ngs are invalid.
6. If set up successfully, you can return to the menu interface, and display the LCD to [home
page] by press the [up down] bu�on. If it displays [meter power XXW], the zero-export
func�on se�ng is completed. Shown as picture 7.15.

Meter Power:
20W
Pic 7.15 Zero-export func�on via energy meter turn on

7. Meter power XXW shows posi�ve means grid is supplying the load, and no power fed into
grid. if meter power shows nega�ve, it means PV energy is being sold to grid or energy meter
wiring connce�on has problem.
8. A�er properly connec�on is done, wait for inverter star�ng. If the power of the PV array
meets the current power consump�on, the inverter will keep a certain output to counteract
the power of the grid without backflow .
7.5 Notes while using zero export func�on
For your safety and the opera�on of limiter func�on of the inverter, we put forward the
following sugges�ons and precau�ons:

Warning:
Under zero export mode we strongly recommend that the two PV arrays are
formed by the same number of PV panels of the same size, which will make the
inverter more responsive to limit the power.

Safety Hint:
While the u�lity power is nega�ve and inverter has no output power, that means
the orienta�on of the current sensor is wrong, please turn off the inverter and
change orienta�on of the current sensor.
(when using SUN limiter, the arrow of current sensor points to the load)

High Temperature Hazard:


When using SUN limiter, the current sensor of limiter func�on needs to be
clamped on the fire line of the grid connected to the inverter, otherwise inverter
cannot able to normal operate.
8. General Opera�on
During normal opera�on, the LCD shows the current status of the inverter, including the
current power, total genera�on, a bar chart of power opera�on and inverter ID,etc. Press the
Up key and the Down key to see the current DC voltage, DC current, AC voltage, AC current,in-
verter radiator temperature,so�ware version number and Wifi connec�on state of the
inverter.

LCD Main menu

PV1 Produc�on data

UA and UB Device
informa�on

UC and Freq Tes�ng data


Fault record
Start E-Day and E-Total

Time System param


ON/OFF
Meter
Running param
ImPEP and Total
Setup
Expep and Total Protec�on param

Load PV VA
Comm param
LoadEp

Pic 8.1 LCD opera�on flow chart

8.1 The ini�al interface

From the ini�al interface, you can check PV power, PV voltage, grid voltage, inverter ID, model
and other infoma�on.
Power: 0W Power: 0W
State: Standby State: Com.Error
Pic 8.2 The ini�al interface

Press UP or Down, you can check inverter DC voltage, DC current, AC voltage, AC current and
inverter temperature.

PV1: 0.0V 0.0A Load


Power: 0W
Pic 8.3 PV input voltage and current Pic 8.4 Load power
informa�on

UA: 234V 0.0A UC: 0V 0.0A


UB: 0V 0.0A Freq: 0.00Hz
Pic 8.5 Grid voltage and current informa�on Pic 8.6 Grid voltage and frequency

21 - 05 - 2020 Meter
15 : 57 : 08 Power: 0W
Pic 8.7 Time Pic 8.8 Meter power

ImpEp: Daily energy purchased from grid;


ImpEp: 0.00KWh Total: Total energy purchased from grid.

Total : 0.00KWh
Pic 8.9 Electrical energy

ExpEp: Daily energy sold to grid;


ExpEp: 0.00KWh Total: Total energy sold to grid.

Total : 0.00KWh
Pic 8.10 Electrical energy
LoadEp: Daily consump�on;
LoadEp: 0.00KWh Total: Total energy consump�on.

Total : 0.00KWh
Pic 8.11 Load consump�on

E-Day: Daily genera�on;


E-Day : 0Wh E-Total: Total genera�on.

E-Total : 134KWh
Pic 8.12 PV genera�on

8.2 Submenus in the Main Menu


There are five submenus in the Main Menu.

8.2.1 Device informa�on


You can see the LCD so�ware Ver0201 and control board so�ware Ver1970. In this interface,
there are parameters such as rated power communica�on addresses.

Device Info. << GL1030 SN-01


Fault Record ID:0000000012

ID:0000000012
Ver0201 Ver1970
Pic 8.13 Device informa�on
8.2.2 Fault Record
It can keep Eight fault records in the menu including �me, customer can deal with it depends
on the error code.

Device Info. 1 F35 200521 15


Fault Record << 2 F56 200519 17
Pic 8.14 Fault Record
8.2.3 ON/OFF se�ng

ON / OFF << Turn ON <<


Setup Turn OFF

Turn ON Turn OFF


OK << Cancel OK << Cancel
Pic 8.15 ON/OFF se�ng
When the inverter is turned off, it stops working immediately, and go to standby mode and
then will go to self-test program again. If it passed the self-test, it will start to work again.

8.2.4 PV VA se�ng

Setup Branch 1 : 0.0A


PV VA << Branch 2 : 0.0A
Pic 8.16 PV String current

Each PV string current and this func�on is op�onal.

8.2.5 Parameter se�ng


There are five submenus in the setup.Se�ng includes system param, run param, protect
param, commparam. All of these informa�on for maintenance reference.

Setup << System Param <<


PV VA Run Param

Protect Param
Comm. Param <<
Pic 8.17 Submenus of the parameter setup
8.3 System param se�ng
System Param includes �me set, language set, display set and factory reset.

Time Set << Display Set


Language Set Factory Reset <<
Pic 8.18 System Param

20200522 OK English <<


08:11:21 Cancel Angielski
Pic 8.19 Time Pic 8.20 Language

Bright Keep << Delay time 055


Delay time 055 OK << Cancel
Pic 8.21 LCD Screen se�ngs Pic 8.22 Delay �me set

Confirm Reset <<


Cancel
Pic 8.23 Reset to factory se�ng

8.4 Running param set

Note:
Password required-- only for access-authorized engineer. Un-authorized access
may avoid the warranty. The ini�al password is 1234.

PassWord

Pic 8.24 Password


8.4.1 Ac�veP set
Adjust the output ac�ve power in %
ActiveP 0% Reac�veP: Adjust reac�ve power output in %

ReactiveP 0% <<
Pic 8.25

Fun_ISO: Insula�on resistance detec�on


PF 1.000
Fun - ISO OFF <<
Pic 8.26

Fun_RCD: Residual current detec�on


Fun - RCD OFF Self-check: Inverter's self-check �me.The
default value 60s
SelfCheck 0s <<
Pic 8.27

Island: An�-islanding protec�on


Island OFF Meter: Energy meter.If inverter will connect
meter,then set here to ON
Meter OFF <<
Pic 8.28

Limiter: If inverter will connect SUN limiter,


Limiter ON then set here to ON
P. Factor: Reac�ve power genera�on
P.Factor 0.00 << correc�on factor

Pic 8.29

WindTurbine: when connec�ng windturbine,


MPPT Num 0 << turn on this item.

WindTurbine
Pic 8.30
Those parameters is used for setup wind
WindTurbine << trubine MPPT curve.

OK Cancel

V1: 0.0V << DC1->Wind OFF <<


0.0A DC2->Wind OFF <<

OK <<
Cancel
Pic 8.31 WindTurbine set

8.5 Protect Param

Note:
Engineer Only.
We will set the param depends on the safety requirements, so customers don't
need to reset it. The password is same as 8.4 Running param

PassWord

Pic 8.32 Password

00 INMETRO 00 EN50438
00 EN50549 << 00 IEC61727 <<

00 CUSTOM
OK Cancel <<
Note:
Engineer only.
AC OverVoltage << AC LowVoltage <<
265.0V 185.0V

AC OverFreq << AC LowFreq <<


51.50Hz 47.50Hz
Pic 8.33 “CUSTOMIZED”

Please set the proper grid parameters according to the requirements of your current country's
grid regula�ons.If you are not clear about it, please consult your installer.

8.6 Com. param set

Address: 16 <<
BaudRate: 9600
Pic 8.34 Com. Param

9. Repair and Maintenance


String type inverter doesn’t need regular maintenance. However,debris or dust will affect heat
sink’s thermal performance. It is be�er to clean it with a so� brush. If the surface is too dirty
and affect the reading of LCD and LED lamp, you can use wet cloth to clean it up.

Warning:
When the device is running, the local temperature is too high and the touch can
cause burns. Turn off the inverter and wait for it cooling, then you can clean and
maintain.

Warning:
No solvent, abrasive materials or corrosive materials can be used for cleaning
any parts of the inverter.

10.Error informa�on and processing


Inverter has been designed in accordance with interna�onal grid �ed standards for safety,
and electromagne�c compa�bility requirements. Before delivering to the customer the
inverter has been subjected to several tests to ensure its op�mal opera�on and reliability.
10.1 Error code
If there is any failure,the LCD screen will display an alarm message. In this case,the inverter
may stop feeding energy into the grid. The alarm descrip�on and their corresponding alarm
messages are listed Table 10.1

Error code Description Ongrid - Three Phase


F01 DC input polarity reverse fault Check the PV input polarity

F02 DC insula�on impedance Check the grounding cable of inverter.


permanent fault

F03 DC leakage current fault Hardly appear the code. Never ever happened so far

F04 Ground fault GFDI Check the solar panel output connec�on.

F05 Read the memory error Failure in reading memory (EEPROM). Restart the inverter if the
fault s�ll exists, contact your installer or Deye service.

F06 Write the memory error Failure in wri�ng memory (EEPROM). Restart the inverter if the
fault s�ll exists, contact your installer or Deye service.

F07 GFDI blown fuse Hardly appear the code. Never ever happened so far

F08 GFDI grounding touch failure Hardly appear the code. Never ever happened so far

F09 IGBT damaged by excessive drop Hardly appear the code. Never ever happened so far.
voltage

Auxiliary switch power supply 1. It tells the DC 12V is not existed.


F10 failure 2. Restart the inverter, if the fault s�ll exists, please contact
your installer.

F11 AC main contactor errors Hardly appear the code. Never ever happened so far

F12 AC auxiliary contactor errors Hardly appear the code. Never ever happened so far

1. Lost of one phase or AC voltage detec�on circuit or relays not


F13 Working mode changed/Grid closed (old inverter not have relays detec�on func�on).
mode changed 2. Restart the inverter, if the error s�ll exists, please contact your
installer or Deye service.

F14 DC firmware over current Hardly appear the code. Never ever happened so far.

1. The internal AC sensor or detec�on circuit on control board


F15 or connec�on wire may loose.
AC firmware over current 2. Restart the inverter, if the error s�ll exists, please contact
your installer or Deye service.

1. This fault means the average leakage current is over 300mA.


Check whether DC power supply or solar panels is ok, then
GFCI(RCD) Ac leakage current check 'Test data'-> 'diL'value is about 40; Then check the
F16 fault leakage current sensor or circuit (the following picture).
Checking test data needs using big LCD.
2. Restart the inverter, if the error s�ll exists, please contact your
installer or Deye service.

F17 Three phase current, Hardly appear the code. Never ever happened so far.
over-current fault

1. Check AC sensor or detec�on circuit on control board or


F18 connec�on wire.
AC over current fault of hardware 2. Restart the inverter or factory reset, if the error s�ll exists,
please contact your installer or Deye service.

F19 All hardware failure synthesis Hardly appear the code. Never ever happened so far.
Error code Description Ongrid - Three Phase
1. Check whether solar panel output current is within the
allowed range.
F20 DC over current fault of the 2. Check DC current sensor and its detec�on circuit.
hardware 3. Check if the inverter FW version is suitable for the hardware.
4. Restart the inverter, if the error s�ll exists, please contact your
installer or Deye service.

F21 DC leakage flow fault Hardly appear the code. Never ever happened so far.

F22 Crash stop (if there is a stop Contact your installer for help.
bu�on)

1. This fault means the leakage current is above 30mA suddenly.


Check whether DC power supply or solar panels is ok, then
AC leakage current is transient check 'Test data'-> 'diL'value is about 40; Then check the
F23 over current leakage current sensor or circuit. Check test data needs
using big LCD.
2. Restart the inverter, if the fault s�ll exists, contact your installer
or Deye service.

1. Check Vpe resistance on main board or detec�on on control


board. Check PV panels is OK. Many �mes this issue is the PV
problem.
2. Check whether the PV panel (aluminum frame) is grounded
F24 DC insula�on impedance failure well and inverter is grounded well. Open the cover of inverter
and then check the inside ground cable is fixed well on the shell.
3. Check if the AC/DC cable, terminal block are shorted to ground
or the insula�on is damaged.
4. Restart the inverter, if the fault s�ll exists, contact your installer
or Deye service.

F25 DC feedback fault Hardly appear the code. Never ever happened so far

1. Check whether the 'BUSN' cable or driver board power supply


F26 cable is loose.
The DC busbar is unbalanced 2. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

F27 DC end insula�on error Hardly appear the code. Never ever happened so far

F28 Inverter 1 DC high fault Hardly appear the code. Never ever happened so far

F29 AC load switch failure Hardly appear the code. Never ever happened so far

1. Check relays and AC voltage of relays.


2. Check relays driver circuit. Check if the so�ware is not suitable
F30 for this inverter. (Old inverter not have relays detec�on
AC main contactor failure func�on)
3. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

1. At least one Relay can't be closed. Check relays and its driver
F31 signal. (Old inverter not have relays detec�on func�on)
Dc boost so� start 2. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

F32 Inverter 2 dc high fault Hardly appear the code. Never ever happened so far

F33 AC over current Hardly appear the code. Never ever happened so far

F34 AC current over load Hardly appear the code. Never ever happened so far

1. Check AC grid voltage. Check AC voltage detec�on circuit.


F35 Check if the AC connector in good condi�on. Check whether
No AC grid the AC grid is normal in voltage.
2. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.
Error code Description Ongrid - Three Phase
F36 AC grid phase error Hardly appear the code. Never ever happened so far

F37 AC three-phase voltage unbalance Hardly appear the code. Never ever happened so far.
failure

F38 AC three-phase current unbalance Hardly appear the code. Never ever happened so far.
failure

1. Check AC current sensor and its circuit.


F39 AC over current(one cycle) 2. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

F40 DC over current Hardly appear the code. Never ever happened so far

Check the AC voltage protec�on se�ng. And Check if the AC


F41 AC Line W,U over voltage cable is too thin.Check the voltage difference between LCD and
meter.

Check the AC voltage protec�on se�ng. Check the voltage


F42 AC Line W,U low voltage difference between LCD and meter. Also need to check whether
AC cables are all firmly and correctly connected.

Check the AC voltage protec�on se�ng.And Check if the AC


F43 AC Line V,W over voltage cable is too thin.Check the voltage difference between LCD and
meter.

Check the AC voltage protec�on se�ng. Check the voltage


F44 AC Line V,W low voltage difference between LCD and meter. Also need to check whether
AC cables are all firmly and correctly connected.

Check the AC voltage protec�on se�ng.And Check if the AC


F45 AC Line U,V over voltage cable is too thin.Check the voltage difference between LCD and
meter.

F46 AC Line U,V low voltage Check the AC voltage protec�on se�ng.

F47 AC Over frequency Check the frequency protec�on se�ng.

F48 AC lower frequency Check the frequency protec�on se�ng.

F49 U phase grid current DC Hardly appear the code. Never ever happened so far.
component over current

F50 V phase grid current DC Hardly appear the code. Never ever happened so far.
component over current

F51 W phase grid current DC Hardly appear the code. Never ever happened so far.
component over current

F52 AC inductor A, phase current Hardly appear the code. Never ever happened so far.
DC current high

F53 AC inductor B, phase current Hardly appear the code. Never ever happened so far.
DC current high

F54 AC inductor C, phase current Hardly appear the code. Never ever happened so far.
DC current high

1. Check PV voltage and Ubus voltage and its detec�on circuit.


F55 If the PV input voltage exceeds the limit, please reduce the
DC busbar voltage is too high number of solar panels in series.
2. For Ubus voltage, please check the LCD display.
Error code Description Ongrid - Three Phase
1. It tells the PV input voltage is low and it always happens in the
early morning.
2. Check PV voltage and Ubus voltage. When inverter is running,
F56 DC busbar voltage is too low then showing F56, maybe Loss of driver or need update
firmware.
3. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

F57 AC reverse irriga�on AC reverse irriga�on.

F58 AC grid U over current Hardly appear the code. Never ever happened so far.

F59 AC grid V over current Hardly appear the code. Never ever happened so far.

F60 AC grid W over current Hardly appear the code. Never ever happened so far.

F61 Reactor A phase over current Hardly appear the code. Never ever happened so far.

F62 Reactor B phase over current Hardly appear the code. Never ever happened so far.

F63 Reactor C phase over current Hardly appear the code. Never ever happened so far.

1. Check temperature sensor. Check if firmware is suitable for


F64 the hardware. Check if the inverter is its right model.
IGBT heat sink high temperature 2. Restart the inverter, if the fault s�ll exists, contact your
installer or Deye service.

Table 10.1 Error codes and their solu�ons

Note:
If your string inverter has any of the fault informa�on shown in Table 10-1,and
when you reset the machine and s�ll don’t solve the problem,please contact our
distributor and provide the below details:

1Serial number of the inverter;


2The distributor/dealer of the inverter(if available);
3Installa�on date;
4The discrip�on of problem (include LCD'error code and LED starus indicator lights);
5Your contact details.
11.Specifica�on
Model SUN-3K-G03 SUN-4K-G03 SUN-5K-G03 SUN-6K-G03
Input Side
Max.DC Power(kW) 3.9 5.2 6.5 7.8
Max.DC Input Voltage(V) 1000
Start-up DC Input Voltage(V) 140
MPPT Opera�ng Range(V) 120~850
Max.DC Input Current(A) 12.5+12.5
Number of MPPT/Strings per MPPT 2/1
Output Side
Rated Output Power(kW) 3 4 5 6
Max.Ac�ve Power(kW) 3.3 4.4 5.5 6.6
Rated AC Grid Voltage(V) 220380, 230 400
AC Grid Voltage Range(V) 277 ~ 460 (this may vary with grid standards)
Rated Grid Frequency(Hz) 50/60(Op�onal)
Opera�ng Phase Three phase
Rated AC Grid Output Current(A) 4.3 5.8 7.2 8.7
Max.AC Output Current(A) 4.8 6.4 8 9.6
Output Power Factor 0.8 leading~0.8 lagging
Grid Current THD <2%
DC Injec�on Current(mA) <0.5%
Grid Frequency Range 47-52 or 57-62op�onal
Efficiency
Max.Efficiency 98.3%
Euro Efficiency 97.5%
MPPT Efficiency >99%
General Data
Size(mm, W×H×D) 330×430×177
Weight(kg) 15
Topology Transformerless
Internal consump�on <1W(Night)
Opera�ng temperature -25 ~ 65
Ingress protec�on IP65
Noise Emission(Typical) <25 dB
Cooling Concept Natural cooling
Max. opera�on al�tude 2000m
Designed Life�me >20Years

Grid Connec�on Standard EN50549, IEC61727, VDE 0126-1-1, IEC62109-1-2

Opera�on surrounding humidity 0~100%


Sta�y EMC / Standard IEC62109-1/-2,EN61000-6-1,EN61000-6-3
General Data
DC Connec�on MC-4 mateable
AC Connec�on IP65 rated plug
Display LCD1602
Interface RS485/RS232/Wifi/LAN
Model SUN-7K-G03 SUN-8K-G03 SUN-10K-G03
Input Side
Max.DC Power(kW) 9.1 10.4 13
Max.DC Input Voltage(V) 1000
Start-up DC Input Voltage(V) 140
MPPT Opera�ng Range(V) 120~850
Max.DC Input Current(A) 12.5+12.5
Number of MPPT/Strings per MPPT 2/1
Output Side
Rated Output Power(kW) 7 8 10
Max.Ac�ve Power(kW) 7.7 8.8 11
Rated AC Grid Voltage(V) 220380, 230 400
AC Grid Voltage Range(V) 277 ~ 460 (this may vary with grid standards)
Rated Grid Frequency(Hz) 50/60(Op�onal)
Opera�ng Phase Three phase
Rated AC Grid Output Current(A) 10.1 11.6 14.5
Max.AC Output Current(A) 11.1 12.8 15.9
Output Power Factor 0.8 leading~0.8 lagging
Grid Current THD <2%
DC Injec�on Current(mA) <0.5%
Grid Frequency Range 47-52 or 57-62op�onal
Efficiency
Max.Efficiency 98.3%
Euro Efficiency 97.5%
MPPT Efficiency >99%
General Data
Size(mm, W×H×D) 330×430×177
Weight(kg) 15
Topology Transformerless
Internal consump�on <1W(Night)
Opera�ng temperature -25 ~ 65
Ingress protec�on IP65
Noise Emission(Typical) <25 dB
Cooling Concept Natural cooling
Max. opera�on al�tude 2000m
Designed Life�me >20Years

Grid Connec�on Standard EN50549, IEC61727, VDE 0126-1-1, IEC62109-1-2

Opera�on surrounding humidity 0~100%


Sta�y EMC / Standard IEC62109-1/-2,EN61000-6-1,EN61000-6-3
General Data
DC Connec�on MC-4 mateable
AC Connec�on IP65 rated plug
Display LCD1602
Interface RS485/RS232/Wifi/LAN
502012004 Ver: 2.0, 2020-11