0% found this document useful (0 votes)
6 views3 pages

Efsr25012681791pm 6463 Anil

The document details a preventive maintenance service performed on a GSK Diesel genset at the Parhladpur-2 site on January 30, 2025. Key findings include the satisfactory condition of various systems such as air, lubrication, cooling, fuel, and electrical, while noting issues like a faulty DC charging alternator and damaged panel components. The next preventive maintenance is scheduled for April 30, 2025.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views3 pages

Efsr25012681791pm 6463 Anil

The document details a preventive maintenance service performed on a GSK Diesel genset at the Parhladpur-2 site on January 30, 2025. Key findings include the satisfactory condition of various systems such as air, lubrication, cooling, fuel, and electrical, while noting issues like a faulty DC charging alternator and damaged panel components. The next preventive maintenance is scheduled for April 30, 2025.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Preventive Maintenance

eFSR Details
GSK Diesel Sales EFSR25012681791P
MAGIEC Code EBU44226 MAGIEC Name eFSR ID
And Service M
Engine Serial 8051107 Site Id I-DL-DLHI-ENB-6463 Comm Site ID I-DL-DLHI-ENB-6463
Number
Reliance Digital Date And Time
Customer Name Platform & Project Application Genset 30-Jan-2025 16:35
Attended
Service Limited
Parhladpur-2
Site Name I-DL-DLHI-ENB-6463 Location Cluster / District North
DL6DELHI0239G

28.742719/77.09938
Circle / State Delhi DG Supplied By NA Lat / Log
04
Engine Model R3105ZD-F Engine KVA 30 Running Hour 1893
PIU Running Hrs

Engine Serial Number Site Condition - Pre-Service Hour Meter Reading


Ticket Details
Ticket Registered
Ticket Number SR25017702374 on date 30-Jan-2025 Type of Service PM
MAGIEC Job Ref
Details Preventive Maintenance No. NA
Air System
Inner Element Outer Element
Air System Type Dry OK OK
Primary Secondary
Condition of
OK Condition of Hoses OK
Vaccume Indicator
Clean Wire mesh NO Oil Bath Replaced NO Element NA
Lub System
Qty.of Oil Filled
Oil Level Top Up 3.00
(Ltr.)
Oil Leakage NO No image

Oil Level in FIP Replaced Oil Filter Replaced


Cooling System
Coolant Level OK Coolant Leakage NO
Condition of
Condition of Recovery Bottle & No image
Radiator Cap OK Its Hose OK
Connection

1
Condition of Radiator
Radiator Cleanliness Check
fins & Clean Using OK
blower
No image
Gap Between Cowl Coolant
& Radiator (Visual OK Temperature(Deg. 80.00
Check) Cen)
Condition of Hoses Condition Of Fan Condition Exhaust
OK belt OK Bellow OK

Fuel System
Fuel Filter Primary Replaced Fuel Pipe OK
Fuel Filter
Replaced Fuel Leakage NO
Secondary No image
FIP Feed Pump
Diesel Tank Open Found Clean
filter
Engine Electrical System
Battery Charging
Battery Available 13.5
Voltage(V)
Battery Electrolite Battery AH Rating
Level OK (AH) 88

Specififc Gravity of Alternator Charging Available And


Battery 02
Unit Working Fine

Condition of
Wiring Harness OK Alternator Bracket OK OK
terminal
Main Alternator & AMF Panel
Condition of
Alternator & Load Cable Meters, Lamps on
Terminal Box OK condition in Main OK OK
Panel For
Condition alternator Functionality
Check Cable
Check The Check Operation Of
OK Connections & OK Working
Controller Setting AMF
Earthing
Automation Solenoid Pulse
Automation LLOP Operation OK 09:00
Functional Corrected
All Safeties
False HWT Operation OK GSU Operation OK
connected to PIU
Main Alternator Main Alternator
earthing - Body Connected earthing - Neutral Connected
Radiator Water
OK Solenoid Operation Solenoid
Level Switch
Condition of 4ST Solenoid Pulse /
Switch OK PIU Stop timing 10:00
Check Genset
Check Genset
OK Overload 30
Overload Setting Setting(amp)
General Check
Output Voltage(AC Engine RPM On
Three phase Engine RPM Max 1530.00 1500
Volts) Load
Visibility of Smoke
Normal Frequency (Hz) 51.00 Oil Pressure (Bar) 4.60
colour
Condition &
Output Voltage 240.00/240.00/239.0 Load Opening of
[R/Y/B] Current[R/Y/B] 18.00/12.00/15.00 Breather Tube Vent OK
0 outside Canopy

Sr.No. Spare Part Code Spare Part Name Qty Failed Part
Recommendation
Not Applicable Important Info NA
for Overhaul

2
Customer
representative Vikram Singh Designation NA Phone No 9891583887
Name
Satisfied with the
Job Done. YES
Customer Remark /
Experience Customer representative Photograph. Customer representative Signature.
DG NRV Faulty and
panel glass damage
DC charging
alternator faulty
panel hing damage 4
relay card problem
need to be replace
Magiec
representative Rustom Phone No 9355442859 Next PM Due Date 30-04-2025
Name
Magiec
representative Magiec representative Signature
Remarks

DG NRV Faulty and


panel glass damage
DC charging
alternator faulty
panel hing damage 4
relay card problem
need to be replace

Engine Sr. : 8051107 / eFSRId : / Hours : / eFSR start Date&Time : 30-Jan-2025 12:00 AM / ServerSaveTime : 30-Jan-2025 04:35 PM / LAT26 : 28.742719 / LOG84 :