The document provides an air system sizing summary for a single zone office project located in Cairo, Egypt, detailing the necessary cooling and heating loads. It specifies the peak sensible cooling load as 6.3 kW with a corresponding airflow of 558 L/s, and a heating load of 0.8 kW. The calculations include various factors such as solar loads, wall transmission, and equipment loads to determine the overall system requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
4 views
ONE ZONE@4C
The document provides an air system sizing summary for a single zone office project located in Cairo, Egypt, detailing the necessary cooling and heating loads. It specifies the peak sensible cooling load as 6.3 kW with a corresponding airflow of 558 L/s, and a heating load of 0.8 kW. The calculations include various factors such as solar loads, wall transmission, and equipment loads to determine the overall system requirements.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3
Air System Sizing Summary for SYSTEM(one zone at 4 C
Project Name: 2201-OFFICE WORK 01/14/2022
Prepared by: MIC 12:39PM
Air System Information
Air System Name SYSTEM(one zone at 4 C Number of zones 1 Equipment Class TERM Floor Area 71.2 m² Air System Type 2P-FC Location Cairo, Egypt
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Hourly Analysis Program v4.90 Page 1 of 3
Zone Sizing Summary for SYSTEM(one zone at 4 C Project Name: 2201-OFFICE WORK 01/14/2022 Prepared by: MIC 12:39PM
Air System Information
Air System Name SYSTEM(one zone at 4 C Number of zones 1 Equipment Class TERM Floor Area 71.2 m² Air System Type 2P-FC Location Cairo, Egypt
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 6.3 558 558 Jun 1400 0.8 71.2 7.84
Terminal Unit Sizing Data - Cooling
Total Sens Coil Coil Water Time
Coil Coil Entering Leaving Flow of Load Load DB / WB DB / WB @ 4.0 °K Peak Zone Name (kW) (kW) (°C) (°C) (L/s) Load Zone 1 7.3 6.2 25.4 / 19.3 16.1 / 15.5 0.44 Jun 1200
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating Htg Coil
Heating Coil Water Fan OA Vent Coil Ent/Lvg Flow Design Fan Fan Design Load DB @11.1 °K Airflow Motor Motor Airflow Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s) Zone 1 0.0 -18.3 / -18.3 0.00 558 0.113 0.090 0
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 OFFICE-01 1 6.3 Jun 1400 558 0.8 71.2 7.84
Hourly Analysis Program v4.90 Page 2 of 3
Air System Design Load Summary for SYSTEM(one zone at 4 C Project Name: 2201-OFFICE WORK 01/14/2022 Prepared by: MIC 12:39PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1200 HEATING DATA AT DES HTG COOLING OA DB / WB 36.9 °C / 19.6 °C HEATING OA DB / WB 7.2 °C / 3.2 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 20 m² 1223 - 20 m² - - Wall Transmission 3 m² 61 - 3 m² 56 - Roof Transmission 0 m² 0 - 0 m² 0 - Window Transmission 20 m² 365 - 20 m² 454 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 15 m² 0 - 15 m² 0 - Partitions 105 m² 274 - 105 m² 267 - Ceiling 0 m² 0 - 0 m² 0 - Overhead Lighting 533 W 533 - 0 0 - Task Lighting 0W 0 - 0 0 - Electric Equipment 2500 W 2500 - 0 0 - People 18 1292 1081 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Zone Loads - 6248 1081 - 777 0 Zone Conditioning - 6117 1081 - 81 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Exhaust Fan Load 0 L/s 0 - 0 L/s 0 - Ventilation Load 0 L/s 0 0 0 L/s 0 0 Ventilation Fan Load 0 L/s 0 - 0 L/s 0 - Space Fan Coil Fans - 90 - - -90 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 6207 1081 - -9 0 Terminal Unit Cooling - 6207 1092 - 0 0 Terminal Unit Heating - 0 - - 0 - >> Total Conditioning - 6207 1092 - 0 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads