0% found this document useful (0 votes)
4 views

ONE ZONE@4C

The document provides an air system sizing summary for a single zone office project located in Cairo, Egypt, detailing the necessary cooling and heating loads. It specifies the peak sensible cooling load as 6.3 kW with a corresponding airflow of 558 L/s, and a heating load of 0.8 kW. The calculations include various factors such as solar loads, wall transmission, and equipment loads to determine the overall system requirements.

Uploaded by

Ahmad aboulsoud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

ONE ZONE@4C

The document provides an air system sizing summary for a single zone office project located in Cairo, Egypt, detailing the necessary cooling and heating loads. It specifies the peak sensible cooling load as 6.3 kW with a corresponding airflow of 558 L/s, and a heating load of 0.8 kW. The calculations include various factors such as solar loads, wall transmission, and equipment loads to determine the overall system requirements.

Uploaded by

Ahmad aboulsoud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Air System Sizing Summary for SYSTEM(one zone at 4 C

Project Name: 2201-OFFICE WORK 01/14/2022


Prepared by: MIC 12:39PM

Air System Information


Air System Name SYSTEM(one zone at 4 C Number of zones 1
Equipment Class TERM Floor Area 71.2 m²
Air System Type 2P-FC Location Cairo, Egypt

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Hourly Analysis Program v4.90 Page 1 of 3


Zone Sizing Summary for SYSTEM(one zone at 4 C
Project Name: 2201-OFFICE WORK 01/14/2022
Prepared by: MIC 12:39PM

Air System Information


Air System Name SYSTEM(one zone at 4 C Number of zones 1
Equipment Class TERM Floor Area 71.2 m²
Air System Type 2P-FC Location Cairo, Egypt

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6.3 558 558 Jun 1400 0.8 71.2 7.84

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 4.0 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 7.3 6.2 25.4 / 19.3 16.1 / 15.5 0.44 Jun 1200

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.0 -18.3 / -18.3 0.00 558 0.113 0.090 0

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
OFFICE-01 1 6.3 Jun 1400 558 0.8 71.2 7.84

Hourly Analysis Program v4.90 Page 2 of 3


Air System Design Load Summary for SYSTEM(one zone at 4 C
Project Name: 2201-OFFICE WORK 01/14/2022
Prepared by: MIC 12:39PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1200 HEATING DATA AT DES HTG
COOLING OA DB / WB 36.9 °C / 19.6 °C HEATING OA DB / WB 7.2 °C / 3.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 20 m² 1223 - 20 m² - -
Wall Transmission 3 m² 61 - 3 m² 56 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 20 m² 365 - 20 m² 454 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 105 m² 274 - 105 m² 267 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 533 W 533 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2500 W 2500 - 0 0 -
People 18 1292 1081 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6248 1081 - 777 0
Zone Conditioning - 6117 1081 - 81 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 90 - - -90 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6207 1081 - -9 0
Terminal Unit Cooling - 6207 1092 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 6207 1092 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 3