Multi V 5 Cooling Only 2023-12

The document provides specifications for the Multi V 5 Cooling Only outdoor units, including model names ARUV096BTE5 and ARUV121BTE5. It details their cooling capacities, power inputs, EER ratings, dimensions, weight, sound levels, and protection devices. Additionally, it includes notes on installation requirements and performance conditions, as well as information on the environmental impact of the refrigerant used.

Uploaded by

alex
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views1 page

Multi V 5 Cooling Only 2023-12

The document provides specifications for the Multi V 5 Cooling Only outdoor units, including model names ARUV096BTE5 and ARUV121BTE5. It details their cooling capacities, power inputs, EER ratings, dimensions, weight, sound levels, and protection devices. Additionally, it includes notes on installation requirements and performance conditions, as well as information on the environmental impact of the refrigerant used.

Uploaded by

alex
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Multi V 5 Cooling Only Outdoor Units

1. Specifications
1.1 220V
RT 8 10
Combination Unit ARUV096BTE5 ARUV121BTE5
ARUV096BTE5 ARUV121BTE5
Model Name
Independent Unit

Btu/h 96,000 120,000


Cooling (Norminal)
kW 28.1 35.2
Capacity
Btu/h 92,000 114,000
Cooling (Rated)
kW 27.0 33.4
Cooling (Norminal) kW 5.90 8.51
Input
Cooling (Rated) kW 5.49 7.86
EER (Norminal) 4.76 4.14
EER (Rated) 4.92 4.25
Power Factor Rated - 0.93 0.93
Color Morning Gray / Dawn Gray Morning Gray / Dawn Gray
Exterior
RAL (Classic) RAL 7038 / RAL 7037 RAL 7038 / RAL 7037
Heat Exchanger Wide Louver Plus Wide Louver Plus
Type Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm3/rev 62.1 62.1
Number of Revolution rev/min 3,600 3,600
Compressor
Motor Output x Number W x No. 5,300 × 1 5,300 × 1
Starting Method Inverter Inverter
Oil Type FW68D(PVE) FW68D(PVE)
Type Propeller fan Propeller fan
Motor Output x Number W 1,200 × 1 1,200 × 1
m3/min 240 × 1 240 × 1
Fan Air Flow Rate(High)
ft3/min 8,476 × 1 8,476 × 1
Drive DC INVERTER DC INVERTER
Discharge Side / Top TOP TOP
Pipe Liquid mm(inch) 9.52(3/8) 12.7(1/2)
Connctions Gas mm(inch) 22.2(7/8) 28.58(1-1/8)
mm (930 × 1,690 × 760) × 1 (930 × 1,690 × 760) × 1
Dimensions(W x H x D)
inch (36-5/8 × 66-17/32 × 29-29/32) × 1 (36-5/8 × 66-17/32 × 29-29/32) × 1
kg 188 × 1 188 × 1
Net Weight
lbs 414 × 1 414 × 1
Sound Pressure Level (Cooling) dB(A) 58.0 59.0
Sound Power Level (Cooling) dB(A) 78.0 79.0
High pressure protection High pressure sensor / High pressure switch
Protection
Compressor/Fan Over-heat protection / Fan driver overload protector
Devices
Inverter Over-heat protection / Over-current protection
Communication Cable (VCTF-SB) No.×㎟ 2C × 1.0 ~ 1.5 2C × 1.0 ~ 1.5
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
6. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
7. *** : The number in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160~200%).
The recommended ratio is 130%.
8. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)