Kohler-150KW Spect

The Kohler 150ERESC generator is EPA-certified for stationary emergency applications with a standby rating range of 106-150 kW. It features a brushless, rare-earth permanent magnet alternator, a one-year limited warranty, and options for extended warranties. The generator is designed for natural gas or LPG use, with detailed specifications on performance, fuel consumption, and operational requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views4 pages

Kohler-150KW Spect

The Kohler 150ERESC generator is EPA-certified for stationary emergency applications with a standby rating range of 106-150 kW. It features a brushless, rare-earth permanent magnet alternator, a one-year limited warranty, and options for extended warranties. The generator is designed for natural gas or LPG use, with detailed specifications on performance, fuel consumption, and operational requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Model: 150ERESC

208--480 V Gas

EPA-Certified for Stationary Standard Features


Emergency Applications D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are prototype-tested,
factory-built, and production-tested.
Ratings Range
60 Hz D UL 2200 listing is available.
Standby: kW 106--150 D CSA approval is available.
kVA 106--188 D The generator set accepts rated load in one step.
D The 60 Hz generator set engine is certified by the
Environmental Protection Agency (EPA) to conform to the
New Source Performance Standard (NSPS) for stationary
spark-ignited emissions.
D A one-year limited warranty covers all systems and
components. Two- and five-year extended warranties are
also available.
D Alternator features:
d The unique Fast-Responset X excitation system delivers
excellent voltage response and short-circuit capability
using a rare-earth permanent magnet (PM)-excited
alternator.
d The brushless, rotating-field alternator has broadrange
reconnectability.
D Other features:
d Kohlerr APM402 controller. See Controllers on page 3.
d The electronic, isochronous governor incorporates an
integrated drive-by-wire throttle body actuator delivering
precise frequency regulation.
D Quick-ship (QS) models with selected features and a
five-year basic warranty are available. See your Kohler
distributor for details.
Generator Set Ratings
Natural Gas LPG
130_C Rise 130_C Rise
Standby Rating Standby Rating
Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps
120/208 3 60 137/171 475 137/171 475
127/220 3 60 143/179 469 137/171 449
120/240 3 60 137/171 412 137/171 412
4R13X 120/240 1 60 107/107 446 107/107 446
139/240 * 3 60 150/188 454 137/171 412
220/380 * 3 60 124/155 235 124/155 234
277/480 3 60 150/188 226 137/171 206
120/208 3 60 150/188 520 137/171 475
127/220 3 60 150/188 492 137/171 449
120/240 3 60 150/188 451 137/171 412
4S12X 120/240 1 60 106/106 442 106/106 442
139/240 * 3 60 150/188 451 137/171 412
220/380 * 3 60 140/175 266 137/171 260
277/480 3 60 150/188 226 137/171 206
120/208 3 60 150/188 520 139/174 482
127/220 3 60 150/188 492 139/174 456
120/240 3 60 150/188 451 139/174 418
4S13X 120/240 1 60 113/113 471 113/113 471
139/240 * 3 60 150/188 451 139/174 418
220/380 * 3 60 150/188 285 139/174 264
277/480 3 60 150/188 226 139/174 209
4T13X 120/240 1 60 144/144 600 134/134 557
* Voltage configuration not available from the factory. Field-adjustable by an authorized service technician.
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source.
The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited
running time and continuous ratings, consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves
the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATING: Altitude: Derate 1.3% per 100 m (328 ft.) elevation
above 200 m (656 ft.) up to a maximum elevation of 3000 m (9842 ft.). Temperature: Derate 2.0% per 10_C (18_F) temperature above 25_C (77_F) up to 50_C (122_F). For units having enclosures
with enclosed silencers, add 5_C (9_F) to the ambient temperature. For dual fuel engines, use the LPG ratings for both the primary and secondary fuels.
G4-224 (150ERESC) 7/18e
Alternator Specifications
Specifications Alternator D NEMA MG1, IEEE, and ANSI standards compliance for
Manufacturer Kohler
temperature rise and motor starting.
Type 4-Pole, Rotating-Field D Sustained short-circuit current of up to 300% of the rated
Exciter type Brushless, Rare-Earth current for up to 10 seconds.
Permanent- Magnet
Leads: quantity, type D Sustained short-circuit current enabling downstream circuit
4RX, 4SX 12, Reconnectable breakers to trip without collapsing the alternator field.
4TX 4, 120/240
D Self-ventilated and dripproof construction.
Voltage regulator Solid State, Volts/Hz
Insulation: NEMA MG1 D Vacuum-impregnated windings with fungus-resistant epoxy
Material Class H varnish for dependability and long life.
Temperature rise 130_C, Standby
Bearing: quantity, type 1, Sealed D Superior voltage waveform from a two-thirds pitch stator and
Coupling Flexible Disc skewed rotor.
Amortisseur windings Full D Total harmonic distortion (THD) from no load to full load with
Voltage regulation, no-load to full-load ±0.5% a linear load is less than 4%.
Unbalanced load capability 100% of Rated Standby
Current
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
480 V 4R13X (12 lead) 540 (60 Hz)
480 V 4S12X (12 lead) 480 (60 Hz)
480 V 4S13X (12 lead) 570 (60 Hz)
240 V 4T13X (4 lead) 440 (60 Hz)

Application Data
Engine Engine Electrical
Engine Specifications Engine Electrical System
Manufacturer PSI Ignition system Individual Coil
Engine: model, type Industrial 8.8 L, 4-Cycle, Near Plug Ignition
Turbocharged and Battery charging alternator:
Charge Cooled Ground (negative/positive) Negative
Cylinder arrangement V-8 Volts (DC) 12
Displacement, L (cu. in.) 8.8 (537) Ampere rating 70
Bore and stroke, mm (in.) 110 x 114 (4.35 x 4.5) Starter motor rated voltage (DC) 12
Compression ratio 10.1:1
Battery, recommended cold cranking
Piston speed, m/min. (ft./min.) 411 (1350)
amps (CCA):
Main bearings: quantity, type 5, Bi-Metal Steel and
Aluminum Qty., rating for --18_C (0F) One, 630
Rated rpm 1800 Battery voltage (DC) 12
Max. power at rated rpm, NG, kW (HP) 193 (259)
Max. power at rated rpm, LP, kW (HP) 169 (226) Fuel
Cylinder head material Cast Iron Fuel System
Piston type and material Flat Top, Hypereutectic Fuel type Natural Gas, LPG, or
Cast Alum. Dual Fuel
Crankshaft material Forged Steel, Induction Fuel supply line inlet 1.5 NPTF
Hardened, Tangential Fillet Natural gas fuel supply pressure, kPa
Valve (exhaust) material Int.-A193 Exh. Inconel (in. H2O) 1.74--2.74 (7-11)
Governor type Electronic LPG vapor withdrawal fuel supply
Frequency regulation, no-load to full-load Isochronous pressure, kPa (in. H2O) 1.24--2.74 (5-11)
Frequency regulation, steady state 0.5% Dual fuel engine, LP vapor withdrawal
Frequency Fixed fuel supply pressure, kPa (in. H2O) 1.24 (5)
Air cleaner type, all models Dry
Fuel Composition Limits * Nat. Gas LPG
Exhaust Methane, % by volume 90 min. 1.2 max.
Ethane, % by volume 4.0 max. 10 max
Exhaust System Propane, % by volume 1.0 max. 96 max.
Exhaust manifold type Dry Propene, % by volume 0.1 max. 3 max.
Exhaust flow at rated kW, m3/min. (cfm) 27.5 (971) C4 and higher, % by volume 0.3 max. 3 max.
Exhaust temperature at rated kW, dry Sulfur, ppm mass 25 max. 25 max.
exhaust, _C (_F) 649 (1200) Lower heating value,
Maximum allowable back pressure, MJ/m3 (Btu/ft3), min. 33.2 (890) 78.8 (2116)
kPa (in. Hg) 10.2 (3.0)
* Fuels with other compositions may be acceptable. If your fuel is
Exhaust outlet size at engine hookup See ADV drawing
outside the listed specifications, contact your local distributor for
further analysis and advice.

G4-224 (150ERESC) 7/18e


Application Data
Lubrication Controller
Lubricating System
Type Full Pressure
Oil pan capacity, L (qt.) w 8.0 (8.5)
Oil pan capacity with filter, L (qt.) w 8.5 (9.0)
Oil filter: quantity, type w 1, Cartridge
w Kohler recommends the use of Kohler Genuine oil and filters.

Cooling APM402 Controller


Provides advanced control, system monitoring, and system diagnostics
Radiator System
for optimum performance and compatibility.
Ambient temperature, _C (_F) 45 (113) D Digital display and menu control provide easy local data access
Engine jacket water capacity, L (gal.) 13.4 (3.54) D Measurements are selectable in metric or English units
Radiator system capacity, including D Remote communication thru a PC via network or
engine, L (gal.) 25.5 (5.6) serial configuration
Engine jacket water flow, Lpm (gpm) 125 (33) D Controller supports Modbusr protocol
Heat rejected to cooling water at rated D Integrated hybrid voltage regulator with 0.5% regulation
kW, dry exhaust, kW (Btu/min.) 88.2 (5021) D Built-in alternator thermal overload protection
Heat rejected to charge cooling air at D NFPA 110 Level 1 capability
rated kW, dry exhaust, kW (Btu/min.) 11.3 (642) Refer to G6-161 for additional controller features and accessories.
Heat rejected to engine oil at rated kW,
dry exhaust, kW (Btu/min.) 1.4 (81)
Water pump type
Fan diameter, including blades, mm (in.)
Centrifugal
711 (28.0)
Sound Enclosure
Fan, kWm (HP) 18.7 (25)
D Sound level (8 point logarithmic average) at 7 m (23 ft.) with full load:
Max. restriction of cooling air, intake and 73 dB(A).
discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
D Sound level compared to competitor ratings with no load: 70 dB(A).*
Operation Requirements D Sound attenuating enclosure uses acoustic insulation that meets
UL 94 HF1 flammability classification and repels moisture absorption.
Air Requirements
D Vertical air inlet and outlet discharge with 90 degree bends to redirect
Radiator-cooled cooling air,
air and reduce noise.
m3/min. (scfm) [ 340 (12000)
Combustion air, m3/min. (cfm) 8.9 (314) D Internal-mounted critical silencer and flexible exhaust connector.
Heat rejected to ambient air: D Skid-mounted, steel (standard) or aluminum (optional) construction
Engine, kW (Btu/min.) 24.9 (1476) with hinged doors.
Alternator, kW (Btu/min.) 15.7 (893) D Fade-, scratch-, and corrosion-resistant Kohlerr Cashmere Power
[ Air density = 1.20 kg/m3 (0.075 lbm/ft3) Armort textured e-coat paint.
D Lockable, flush-mounted door latches.
Fuel Consumption] Standby Rating
D Certified to withstand 241 kph (150 mph) wind load rating (aluminum
Natural Gas, m3/hr. (cfh) at % load enclosures only).
100% 55.7 (1965)
* Lowest of 8 points measured around the generator. Sound levels at
75% 43.3 (1529)
other points around generator may be higher depending on installation
50% 31.2 (1102) parameters.
25% 19.5 (688)
0% 8.1 (286)
LPG, m3/hr. (cfh) at % load
100% 20.2 (713)
75% 15.5 (547)
50% 11.3 (399)
25% 7.2 (254)
0% 4.6 (164)
] Nominal fuel rating: Natural gas, 37 MJ/m3 (1000 Btu/ft3)
LPG, 93 MJ/m3 (2500 Btu/ft3)

LPG conversion factors:


8.58 ft.3 = 1 lb.
0.535 m3 = 1 kg.
36.39 ft.3 = 1 gal.

G4-224 (150ERESC) 7/18e


KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com

Additional Standard Features Miscellaneous


D Alternator Protection - Air Cleaner Restrictor Indicator
D Battery Rack and Cables - Crankcase Ventilation (CCV) Heater
D Electronic, Isochronous Governor [recommended for ambient temperatures below 0C (32F)]
D Gas Fuel System (includes fuel mixer, electronic secondary gas - Engine Fluids Added
regulator, gas solenoid valve, and flexible fuel line between the - Rated Power Factor Testing
engine and the skid-mounted fuel system components) - Rodent Guards
D Integral Vibration Isolation
Literature
D Local Emergency Stop Switch
- General Maintenance
D Oil Drain Extension
- Overhaul
D Operation and Installation Literature - Production
D Steel Sound Enclosure
D Three-Way Exhaust Catalyst Warranty
- 2-Year Basic Limited Warranty
- 5-Year Basic Limited Warranty
Available Options - 5-Year Comprehensive Limited Warranty
Approvals and Listings
Other Options
- CSA Approval
- _______________________________________________
- UL 2200 Listing
- _______________________________________________
Enclosure - _______________________________________________
- Aluminum Sound Enclosure - _______________________________________________
- _______________________________________________
Fuel System
- _______________________________________________
- Dual Fuel NG/LPG (automatic changeover) - _______________________________________________
- Flexible Fuel Line - _______________________________________________
(required when the generator set skid is spring mounted)
- Gas Filter
- LP Liquid Withdrawal (vaporizer)
- Second Gas Solenoid Valve
Controller Dimensions and Weights
- Common Fault Relay
- Communication Products and PC Software Overall Size, L x W x H, mm (in.) : 3526 x 1153 x 1696
- Two Input/Five Output Module (139 x 45.4 x 66.8)
Weight, wet, kg (lb.):
- Remote Annunciator Panel
With steel sound enclosure 1897 (4183)
- Remote Emergency Stop With aluminum sound enclosure 1730 (3813)
- Run Relay
Weight includes generator set with the 4S alternator, engine fluids, sound
Cooling System enclosure, and silencer.
- Block Heater, 1800 W, 110--120 V
- Block Heater, 2000 W, 190--240 V
Required for ambient temperatures below 10C (50F)
- Block Heater, 2000 W, 120 V
(Only available with LP liquid withdrawal)
Electrical System H
- Alternator Strip Heater
- Battery
- Battery Charger, Equalize/Float Type
- Battery Heater W L
- Line Circuit Breaker (NEMA1 enclosure)
- Line Circuit Breaker with Shunt Trip (NEMA1 enclosure) NOTE: This drawing is provided for reference only and should not be
used for planning installation. Contact your local distributor for more
detailed information.
DISTRIBUTED BY:

 2012, 2013, 2018 by Kohler Co. All rights reserved.


G4-224 (150ERESC) 7/18e