Transformer lecture
Transformer lecture
What is a Transformer?
A Transformer is a static electrical machine which transfers AC
electrical power from one circuit to the other circuit at the constant
frequency, but the voltage level can be altered that means voltage can be
increased or decreased according to the requirement.
Fig (1)
Necessity of a Transformer
In Iraq, usually, electrical power is generated at 11Kv. For
economical reasons AC power is transmitted at very high
voltages say 132 kV or 400 kV over long distances.
Therefore a step up transformer is applied at the
generating stations. Now for safety reasons the voltage is
stepped down to different levels by step down transformer
at various substations to feed the power to the different
locations and thus the utilization of power is done at
1
If (V2 > V1) the voltage is raised on the output side and is
known as Step-up transformer
If (V2 < V1) the voltage level is lowered on the output side
and is known as Step down transformer
Construction of a Transformer
It mainly consists of
Transformer Construction
The construction of a simple two-winding transformer consists
of each winding being wound on a separate limb or core of the
soft iron form which provides the necessary magnetic circuit.
This magnetic circuit, know more commonly as the
“transformer core” is designed to provide a path for the
magnetic field to flow around, which is necessary for induction
of the voltage between the two windings.
2
As well as providing a low reluctance path for the magnetic
field, the core is designed to prevent circulating electric currents
within the iron core itself. Circulating currents, called “eddy
currents”, cause heating and energy losses within the core
decreasing the transformers efficiency.
These losses are due mainly to voltages induced in the iron
circuit, which is constantly being subjected to the alternating
magnetic fields setup by the external sinusoidal supply voltage.
One way to reduce these unwanted power losses is to construct
the transformer core from thin steel laminations.
3
Transformer Construction of the Core
Generally, the name associated with the construction of a transformer is
dependant upon how the primary and secondary windings are wound
around the central laminated steel core. The two most common and basic
designs of transformer construction are the Closed-core transformer and
the Shell-core Transformer.
In the “closed-core” type (core form) transformer, the primary and
secondary windings are wound outside and surround the core ring. In the
“shell type” (shell form) transformer, the primary and secondary
windings pass inside the steel magnetic circuit (core) which forms a shell
around the windings as shown below.
In both types of transformer core design, the magnetic flux linking the
primary and secondary windings travels entirely within the core with no
loss of magnetic flux through air. In the core type transformer
construction, one half of each winding is wrapped around each leg (or
limb) of the transformers magnetic circuit as shown above.
The coils are not arranged with the primary winding on one leg and the
secondary on the other but instead half of the primary winding and half of
the secondary winding are placed one over the other concentrically on
each leg in order to increase magnetic coupling allowing practically all of
the magnetic lines of force go through both the primary and secondary
windings at the same time. However, with this type of transformer
construction, a small percentage of the magnetic lines of force flow
outside of the core, and this is called “leakage flux”.
4
Shell type transformer cores overcome this leakage flux as both the
primary and secondary windings are wound on the same centre leg or
limb which has twice the cross-sectional area of the two outer limbs. The
advantage here is that the magnetic flux has two closed magnetic paths to
flow around external to the coils on both left and right hand sides before
returning back to the central coils.
This means that the magnetic flux circulating around the outer limbs of
this type of transformer construction is equal to Φ/2. As the magnetic flux
has a closed path around the coils, this has the advantage of decreasing
core losses and increasing overall efficiency.
Transformer Laminations
But you may be wondering as to how the primary and secondary
windings are wound around these laminated iron or steel cores for this
types of transformer constructions. The coils are firstly wound on a
former which has a cylindrical, rectangular or oval type cross section to
suit the construction of the laminated core. In both the shell and core type
transformer constructions, in order to mount the coil windings, the
individual laminations are stamped or punched out from larger steel
sheets and formed into strips of thin steel resembling the
letters “E’s”, “L’s”, “U’s” and “I’s” as shown below.
5
These lamination stampings when connected together form the
required core shape. For example, two “E” stampings plus two end
closing “I” stampings to give an E-I core forming one element of a
standard shell-type transformer core. These individual laminations
are tightly butted together during the transformers construction to
reduce the reluctance of the air gap at the joints producing a highly
saturated magnetic flux density.
6
This method of identifying the orientation or direction of a transformers
windings is called the “dot convention”. Then transformers windings are
wound so that the correct phase relations exist between the winding
voltages with the transformers polarity being defined as the relative
polarity of the secondary voltage with respect to the primary voltage as
shown below.
The first transformer shows its two “dots” side by side on the two
windings. The current leaving the secondary dot is “in-phase” with the
current entering the primary side dot. Thus the polarities of the voltages
at the dotted ends are also in-phase so when the voltage is positive at the
dotted end of the primary coil, the voltage across the secondary coil is
also positive at the dotted end.
The second transformer shows the two dots at opposite ends of the
windings which means that the transformers primary and secondary coil
windings are wound in opposite directions. The result of this is that the
current leaving the secondary dot is 180o “out-of-phase” with the current
entering the primary dot. So the polarities of the voltages at the dotted
ends are also out-of-phase so when the voltage is positive at the dotted
7
end of the primary coil, the voltage across the corresponding secondary
coil will be negative.
Then the construction of a transformer can be such that the secondary
voltage may be either “in-phase” or “out-of-phase” with respect to the
primary voltage. In transformers which have a number of different
secondary windings, each of which is electrically isolated from each other
it is important to know the dot polarity of the secondary windings so that
they can be connected together in series-aiding (secondary voltage is
summed) or series-opposing (the secondary voltage is the difference)
configurations.
The ability to adjust the turns ratio of a transformer is often desirable to
compensate for the effects of variations in the primary supply voltage, the
regulation of the transformer or varying load conditions. Voltage control
of the transformer is generally performed by changing the turns ratio and
therefore its voltage ratio whereby a part of the primary winding on the
high voltage side is tapped out allowing for easy adjustment. The tapping
is preferred on the high voltage side as the volts per turn are lower than
the low voltage secondary side.
In this simple example, the primary tap changes are calculated for a
supply voltage change of ±5%, but any value can be chosen. Some
transformers may have two or more primary or two or more secondary
windings for use in different applications providing different voltages
from a single core.
8
Laminating the Iron Core
Copper Losses
But there is also another type of energy loss associated with transformers
called “copper losses”. Transformer Copper Losses are mainly due to the
electrical resistance of the primary and secondary windings. Most
transformer coils are made from copper wire which has resistance in
Ohms, ( Ω ). This resistance opposes the magnetizing currents flowing
through them.
9
When a load is connected to the transformers secondary winding, large
electrical currents flow in both the primary and the secondary windings,
electrical energy and power ( or the I2 R ) losses occur as heat. Generally
copper losses vary with the load current, being almost zero at no-load,
and at a maximum at full-load when current flow is at maximum.
A transformers VA rating can be increased by better design and
transformer construction to reduce these core and copper losses.
Transformers with high voltage and current ratings require conductors of
large cross-section to help minimize their copper losses. Increasing the
rate of heat dissipation (better cooling) by forced air or oil, or by
improving the transformers insulation so that it will withstand higher
temperatures can also increase a transformers VA rating.
In the next tutorial about Transformers we will look at Transformer
Loading of the secondary winding with respect to an electrical load and
see the effect a “NO-load” and a “ON-load” connected transformer has
on the primary winding current.
Types of Transformer
Core type
Shell type
11
2. According to the transformation ratio or number of turns
in the windings ( On the basis of their purpose)
Step up transformer
Step down transformer
3. Types of services
Power transformer
Distribution transformer
Instrument transformer
Current transformer
Potential transformer
Auto transformer
Single phase
Three phase
11
The transformer consists of two separate windings placed
over the laminated silicon steel core. The winding to which
AC supply is connected is called primary winding and to
which load is connected is called secondary winding as
shown in the figure below. It works on the alternating
current only because an alternating flux is required for
mutual induction between the two windings.
12
I1
(N dϕ/dt).
Transformer on DC supply
As discussed above, the transformer works on AC supply,
and it cannot work not DC supply. If the rated DC voltage
is applied across the primary winding, a constant
magnitude flux will set up in the core of the transformer
and hence there will not be any self-induced emf
generation, as for the linkage of flux with the secondary
13
winding there must be an alternating flux required and not
a constant flux.
Turn Ratio
It is defined as the ratio of primary to secondary turns.
Transformation Ratio
The transformation ratio is defined as the ratio of the
secondary voltage to the primary voltage. It is denoted by
K.
14
Ideal Transformer
An ideal transformer is one which has no ohmic resistance and no
magnetic leakage flux that means 100% flux passes through the core and
links with the primary as well as with the secondary winding. It has no
iron and copper losses. There are two purely inductive coils in the Ideal
Transformer, which are wound on a core. As in Ideal transformer, there
are no losses. Hence, the core of the transformer is free from the losses.
15
Since E2 ∞ N2 and E1 ∞ N1, also E1 is similar to V1 and
E2 is similar to V2
Let
16
Φ is the flux per turn in Weber
By Faraday’s Law
Where Ψ = N1ϕ
17
Since ϕ is due to AC supply ϕ = ϕm Sinwt
But w = 2πf
18
Similarly
19
21
21
Example .2
Solution:
Part A:
The ratio of primary voltage to secondary voltage is directly proportional to the ratio of
number of turns on the primary to number of turns on the secondary:
To solve for the number of turns required for the secondary, the equation is rearranged
solving for :
22
Part B:
The voltage across the secondary is given in the problem statement as 120 volts. Using
ohms law, , we can solve for the current in the loop ( ).
Part C:
The ratio of primary current to secondary current is inversely proportional to the ratio of
number of turns on the primary to number of turns on the secondary:
Part D:
The induced emf of the secondary can be calculated by: for , we can calculate the
23
Phasor Diagram of Ideal Transformer
24
Phasor Diagram of an Ideal Transformer
The alternating flux links with both the primary and the
secondary winding. When it links with the primary
winding, it produces self-induced emf E1 which is in the
opposite direction to the applied voltage V1. Similarly,
when this alternating flux links with the secondary winding
it produces induced emf E2known as mutually induced emf
in the opposite direction to the applied voltage. Both
E1 and E2 lags behind the flux ϕ by 90◦.
25
Transformer on No Load Condition
When the transformer is operating at no load, the secondary winding is
open circuited, which means there is no load on the secondary side of the
transformer and, therefore, current in the secondary will be zero, while
primary winding carries a small current I0 called no load current which is
2 to 10% of the rated current. This current is responsible for supplying the
iron losses (hysteresis and eddy current losses) in the core and a very
small amount of copper losses in the primary winding. The angle of lag
depends upon the losses in the transformer. The power factor is very low
and varies from 0.1 to 0.15.
26
the iron losses and a small amount of primary copper
loss).
27
28
Example 3. A 230 VI 115 V single-phase transformer takes a
no-load current of 2 A at a power factor of 0.2 lagging with
low voltage winding kept open. If the
29
Example 4. The number of turns on the primary and
secondary windings of a transformer are 1000 and 200
respectively. When the load current on the secondary is 100
A at 0.8 power factor lagging, the primary current is 30 A at
0.707 power factor lagging. Determine the no-load current
of the transformer and its phase with respect to the voltage.
Solution. Primary turns N1 = 1000
Secondary turns, N2 = 200
Secondary current I2 = 100
Power factor, cos ɸ2 = 0.8 or ɸ2 = 36.9° or 36°54’
Primary current, I1 = 30 A
Power factor, cos ɸ1 = 0.707 or ɸ1 = 45°
No-load current, I0, ɸ0:
Refer Fig. 43. I1 is the vector sum of I0 and I2’. Let I0 lag
behind V1 by an angle ɸ0.
Resolving currents into their X and Y components, we get
I0 cos ɸ0 + 20 cos 36.9° = 30 cos 45°
I0 cos ɸ0 = 30 cos 45° – 20 cos 36.9°
= 21.21 – 16 = 5.21 A (i)
I0 sin ɸ0 + 20 sin 36.9° = 30 sin 45°
I0 sin ɸ0 = 30 sin 45° – 20 sin 36.9°
31
From (i) and (ii), we get
31
Equivalent Circuit of Transformer
Referred to Primary
For drawing equivalent circuit of transformer referred to
primary, first we have to establish general equivalent circuit of
transformer then, we will modify it for referring from primary side.
For doing this, first we need to recall the complete vector diagram
of a transformer which is shown in the figure below. Let us consider
the transformation ratio be,
From the vector diagram above, it is found that the total primary
current I1 has two components, one is no - load component Io and
the other is load component I2′. As this primary current has two
components or branches, so there must be a parallel path with
primary winding of transformer. This parallel path of current is
known as excitation branch of equivalent circuit of transformer. The
resistive and reactive branches of the excitation circuit can be
represented as
32
The load component I2′ flows through the primary winding of
transformer and induced voltage across the winding is E1 as shown
in the figure right. This induced voltage E1 transforms to secondary
and it is E2 and load component of primary current I2′ is
transformed to secondary as secondary current I2. Current of
secondary is I2. So the voltage E2 across secondary winding is partly
dropped by I2Z2 or I2R2 + j.I2X2 before it appears across load. The
load voltage is V2.
The complete equivalent circuit of transformer is shown below.
Therefore,
33
So, the complete equivalent circuit of transformer referred to
primary is shown in the figure below,
34
Equivalent Circuit of Transformer
Referred to Secondary
In similar way, approximate equivalent circuit of transformer
referred to secondary can be drawn. Where equivalent impedance
of transformer referred to secondary, can be derived as
35
copper loss = I22 R02 = 1502 × 0.05 = 1125 W. (Total Ans.)
36
Example 2. The full load copper loss on h.v. side of 100
kVA, 11000/317 V 1-phase transformer is 0.62 kW and on
the l.v. side is 0.48 kW.
(i) Calculate R1, R2 and R2’ in ohms:
(ii) The total reactance is 4 percent, find X1, X2 and X2’ in
ohms if the reactance is divided in the same proportion as
resistance.
37
38
Example 3. A 12 kVA 4000/400 V transformer has primary
and secondary winding resistance of 13 Ω and 0.15 Ωand
leakage reactance of 20 Ωand 0.25 Ω respectively. The
magnetising reactance is 6000 Ω and the resistance
representing core loss is 12000 Ω. Determine :
(i) Equivalent resistance and reactance as referred to
primary.
(ii) Input current with secondary terminals open circuited.
(iii) Input current when the secondary load current is 30 A
at 0.8 power factor lagging.
39
41
Theory of Transformer on Load
With no resistive and leakage reactace.
42
consider one transformer which has internal resistance in
the winding but no leakage reactance. As the windings are
resistive, there would be a voltage drop in the windings.
43
transformer. Let leakage reactances of primary and
secondary windings of the transformer are X1 and X2
respectively. Hence total impedance of primary and
secondary winding of transformer with resistance R1 and
R2 respectively, can be represented as,
44
Example 13. A single phase transformer has the following
data:
Turn ratio 20: 1; R1= 20Ω ,X1 = 80 Ω
R2 = 0.04 Ω,X2 = 0.2 Ω
No-load current = 1.2 A leading the flux by 300.
The secondary delivers 180 A at a terminal voltage of 400 V
and at a power factor of 0.8 lagging.
Determine by the aid of a vector diagram:
(i) The primary applied voltage.
(ii) The primary power factor
(iii) The efficiency.
Solution. Refer Fig. 44:
(i) Primary applied voltage, V1 :
45
46
(ii) Primary power factor, cosɸ1 :
Phase angle between V1 and I1,
ɸ1= Primary power factor = =7.303 (lag). (Ans.)
(iii) Efficiency:
No-load primary input power
= V1I₀ cos ɸ₀= 9269 × 1.2 × cos( 60) = 5561.4 W
47
48
Types of Losses in a Transformer
There are various types of losses in the transformer such as iron losses,
copper losses, hysteresis losses, eddy current losses, stray loss, and
dielectric losses. The various types of losses are explained below in
detail.
Iron Losses
Hysteresis Loss
The core of the transformer is subjected to an alternating
magnetizing force and for each cycle of emf, a hysteresis
loop is traced out. Power is dissipated in the form of heat
known as hysteresis loss and given by the equation shown
below
Where
49
KȠ is a proportionality constant which depends upon the
volume and quality of the material of the core used in
the transformer.
f is the supply frequency
Bmax is the maximum or peak value of the flux density
Where,
51
V – volume of magnetic material in m3
Stray Loss
The occurrence of these stray losses is due to the
presence of leakage field. The percentage of these losses
is very small as compared to the iron and copper losses so
they can be neglected.
Dielectric Loss
Dielectric loss occurs in the insulating material of the
transformer that is in the oil of the transformer, or in the
solid insulations. When the oil gets deteriorated or the
solid insulation get damaged, or its quality decreases and
because of this, the efficiency of transformer is effected.
51
Phasor Diagram of the Transformer on Inductive Load
Similarly
53
Phasor Diagram of the Transformer on Capacitive Load
54
terminal voltage V2 is the phasor difference of E2 and
voltage drop.
V2 = E2 – voltage drops
The power factor of the secondary side depends upon the type
of load connected to the transformer.
55
where,
E2 – secondary terminal voltage at no load
56
less for the better performance of the transformer.
57
Here, from the above diagram,
58
Voltage Regulation of Transformer for Leading
Power Factor
Let's derive the expression of voltage regulation with
leading current, say leading power factor of the load is
cosθ2, that means angle between secondary current and
voltage is θ2.
Voltage regulation of
transformer at leading power factor,
59
61
Example 2. The primary and secondary winding resistance of
a 30 kVA, 6600/250 V single-phase transformer are
8 Ω and 0.015 Ω respectively. The equivalent leakage
reactance as referred to the primary winding is 30 Ω. Find
the full-load regulation for load power factors of:
(i) Unity
(ii) 0.8 Lagging
(iii) 0.8 leading
61
62
Transformer Efficiency
The Efficiency of the transformer is defined as the ratio of useful power
output to the input power, the two being measured in the same unit. Its
unit is either in Watts (W) or KW. Transformer efficiency is denoted by
Ƞ.
Where,
63
Maximum Efficiency Condition of a Transformer
The transformer efficiency at a given load and power
factor is given by the relation shown below
Iron losses = Pi
65
The above equation (5) is the maximum efficiency
condition of a transformer
66
Circuit Diagram of Open Circuit Test on Transformer
W0 – wattmeter reading
V1 – voltmeter reading
I0 – ammeter reading
67
Then the iron loss of the transformer Pi = W0 and
Working component Iw is
Magnetizing component is
68
The phasor diagram of transformer at no load or when an
open circuit test is performed is shown below
69
calculation of the efficiency of the transformer. This test
also helps in determining the equivalent impedance (Zes
or Zep), resistance (Res or Rep) and the leakage
reactance (Xes or Xep) of the transformer referred to the
winding in which the measuring instruments are
connected. By knowing these parameters the voltage drop
can be calculated and thus voltage regulation can be
determined.
Wc – Wattmeter reading
V2sc – voltmeter reading
I2sc – ammeter reading
71
Phasor Diagram of Short Circuit Test
72
small as compared to copper loss so, the core loss can be
neglected.
73
74
Polarity Test of Transformer
Polarity means the direction of the induced voltages in the
primary and the secondary winding of the transformer. If the
two transformers are connected in parallel, then the polarity
should be known for the proper connection of the transformer.
There are two types of polarity one is Additive, and another
is Subtractive.
75
Additive Polarity: In additive polarity the same
terminals of the primary and the secondary windings of
the transformer are connected
76
then the polarity is said to be additive. If A1 is connected
to a2 and A2 to a1, that means the opposite terminals are
connected to each other, and thus the voltmeter will read
the subtractive polarity.
77
Steps to Perform Polarity Test
78
All Day Efficiency of a Transformer
Definition: The all day efficiency is defined as the ratio of output in kilo
watt hour (KWh) or watt hour (Wh) to the input in kWh or Wh of a
transformer over 24 hours.
79
is computed on the basis of energy consumed during a
period of 24 hours.
To find this all day efficiency, firstly you have to know the
load cycle of the transformer
1. Air Natural
2. Air Blast or forced
3. Oil Natural Air Natural
4. Oil Natural Air Forced
5. Oil Forced Air Forced
6. Oil Natural Water Forced
7. Oil Forced Water Forced
81
Methods of Cooling of Transformer
The detailed description of cooling methods, one by one is
given below
81
transformer goes beyond the standard safe level, an
alarm is activated, and the fans and blowers are switched
ON automatically. this method is used for transformer
rating up to 15MVA.
82
Oil Natural Air Natural Cooling of Transformer
83
and air is done naturally because a fan and blowers are
attached as an extra cooling equipment in this method.
84
Oil Forced Air Forced Cooling of Transformer
85
Oil Forced Water Forced Cooling of Transformer
86
Power Transformer
The Power Transformer is installed at various power stations for
generation and transmission of power. It acts as a step-up or a
step-down transformer for increasing and decreasing of the level of
voltages as per the requirement, and it’s also used as an
interconnection between two power stations.
Distribution Transformer
The Distribution Transformer is used to bring down or step down
the voltage and current level of a transmission line to a predefined
level, which is called safety level for the end user consumer in
domestic and industrial purpose.
87
Auto Transformer
An Auto Transformer is a transformer with only one winding wound on
a laminated core. An auto transformer is similar to a two winding
transformer but differ in the way the primary and secondary winding are
interrelated. A part of the winding is common to both primary and
secondary sides. On load condition, a part of the load current is obtained
directly from the supply and the remaining part is obtained by
transformer action. An Auto transformer works as a voltage regulator.
88
There are two types of auto transformer based on the
construction. In one type of transformer, there is
continuous winding with the taps brought out at
convenient points determined by desired secondary
voltage and in another type of auto transformer, there are
two or more distinct coils which are electrically connected
to form a continuous winding. The construction of Auto
transformer is shown in the figure below.
89
E1 is induced in the winding AB. A part of this induced emf
is taken in the secondary circuit.
Let,
V1 = E1 and V2 = E2
Equation (1) and (2) shows that the ampere turns due to
91
section BC and AC balance each other which is
characteristic of the transformer action.
Therefore
Therefore,
91
Now, the ratio of the weight of the copper in an auto
transformer to the weight of copper in an ordinary
transformer is given as
Therefore,
92
Advantages of Auto transformer
Less costly
Better regulation
Low losses as compared to ordinary two winding
transformer of the same rating.
93
Parallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase Transformer means that the two or
more transformers having same polarities, same turn ratios, same phase
sequence and the same voltage ratio are connected in parallel with each
other.
94
parallel to fulfill the extra demand because, it is not
economical from business point of view to install a
bigger rated single transformer by forecasting the
increased future demand as it is unnecessary
investment of money. Again if future demand is
decreased, transformers running in parallel can be
removed from system to balance the capital
investment and its return.
95
other words, percentage impedance or per unit values of
impedance should be identical for all the transformers that
run in parallel.
Same Polarity
Polarity of all transformers that run in parallel, should be
the same otherwise huge circulating current that flows in
the transformer but no load will be fed from these
transformers. Polarity of transformer means the
instantaneous direction of induced emf in secondary. If
the instantaneous directions of induced secondary emf in
two transformers are opposite to each other when same
input power is fed to both of the transformers, the
transformers are said to be in opposite polarity. If the
instantaneous directions of induced secondary emf in two
transformers are same when same input power is fed to
the both of the transformers, the transformers are said to
be in same polarity.
96
The circuit diagram of two single phase transformer A and
B connected in parallel are shown below
Let,
97
IB is the current supplied to the load by the secondary of
the transformer BVL is the secondary load voltage
IL is the load current
98
current in the secondary windings of the single phase
transformer.
99
This condition ensures that the load sharing between the
two single phase transformers is according to the rating of
each transformer. If the per unit equivalent impedance
are not equal, then the transformer will not share the load
in proportion to their kVA ratings. As a result, the overall
rating of the transformer bank will be reduced.
111
Equating the equation (11) and (12) we will get
111
The Current and potential Transformer
112
Now, the secondary current is measured with the help of an AC
113
shown. This allows a higher value current transformer to provide the
maximum output current for the ammeter when used on smaller primary
current lines.
114
transformers have large number of primary turns and smaller
number of secondary turns.
115
circuit should be placed across the secondary terminals first to eliminate
the risk of shock.
116
Advantages of Using Tertiary Winding in Transformer
Tertiary winding is provided in electrical power
transformer to meet one or more of the following
requirements-
117
Isolation transformer
An isolation transformer is a transformer used to transfer electrical
power from a source of alternating current (AC) power to some
equipment or device while isolating the powered device from the
power source, usually for safety reasons.
118
Vector Group of Transformer
119
111
111