0% found this document useful (0 votes)
32 views5 pages

22 1 EVCYAC GB Carly - 2022

The document provides detailed specifications for stainless steel vibration eliminators used in refrigeration systems, highlighting their applications, functional features, and advantages. It outlines installation precautions, technical features, and customization options available for the products. Additionally, it includes information on weights, packaging, and specific recommendations for assembly and maintenance.

Uploaded by

michelle
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views5 pages

22 1 EVCYAC GB Carly - 2022

The document provides detailed specifications for stainless steel vibration eliminators used in refrigeration systems, highlighting their applications, functional features, and advantages. It outlines installation precautions, technical features, and customization options available for the products. Additionally, it includes information on weights, packaging, and specific recommendations for assembly and maintenance.

Uploaded by

michelle
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Refrigeration Components Solutions 22.

Stainless steel vibration eliminators, CTCY-EN - 22.1-7 / 06-2022

nickel-plated connections
EVCYAC
C

n Applications

• Reduction of the mechanical vibrations transmitted by the


compressor to the discharge, liquid, suction and oil return lines,
and indirectly, of the noises they generate, and elimination of
stresses linked with piping thermal expansion in refrigerating and
air conditioning installations.
• The vibration eliminators have no effect on the reduction of the
noises caused by the gas pulsations in the discharge lines. This
is the role of the mufflers SCY.

n Functional features n CARLY advantages

• Products are compatible with HCFCs, HFCs, HFOs, CO2, as • Maximal working pressure: until 46 bar.
well as with their associated oils and additives. Products are • Specifically designed in order to resist frost and major
designed for use of non-hazardous refrigerants from group 2 of temperature shifts, from - 40 °C to + 140 °C.
PED 2014/68/EU. To use CARLY components with fluids of the
• Principle for connecting the components together (stainless
hydrocarbon group 1, contact CARLY technical department.
steel hose + ait-tightness ring + braid + connection) by
• Product classification in CE categories is performed using the stainless steel TIG weld. Contrary to a braze, this weld
PED 2014/68/EU table, corresponding to a nominal diameter- eliminates all risks of deteriorating the vibration eliminator by
based selection. heat transfer during connection to the installation’s piping.
• Flexible wavy stainless steel metallic hoses constituted of • Very high mechanical resistance to corrosion.
parallel waves from a tube welded end to end and covered with
• Long brazed or welded connections, in order to facilitate
a stainless steel wire braid (see sketch n° 2).
connection to installation.
• Nickel-plated steel connections, for the standards models.
• Unity helium air-tightness inspection.
• Vibration eliminators are cleaned and dried before individual
• Marking meets perfectly the requirements of PED 2014/68/EU.
packaging under heat-sealed plastic tubular film.

Possible customization on request,


even for unit needs :
• Specific lengths
• Stainless steel connections, for better resistance to corrosive
environments (e.g. railway and maritime application, ...)
• Specific flanges or connections
22.2 Refrigeration Components Solutions

Stainless steel vibration eliminators, CTCY-EN - 22.1-7 / 06-2022

nickel-plated connections
EVCYAC
C

n Warning
Before selecting or installing any component, please refer to the chapter 0 - WARNING.

n General assembly precautions


The installation of a component in RECOMMENDATIONS SPECIFIC part • The recommendations relating to the
a refrigeration system by a skilled defined hereafter ; CARLY components for the subcritical
professional, requires some precautions: • Other are general to all CARLY components, CO2 applications are also developed in
• Some are specific to each component, they are presented in the chapter 115 – chapter 115 – GENERAL ASSEMBLY
and in this case, they are specified in the GENERAL ASSEMBLY PRECAUTIONS. PRECAUTIONS.

n Recommendations specific to EVCYAC vibration eliminators


• Mounting of vibration eliminators should content (38 % minimum) and the use • For semi-static use, the assembly must
be performed: of a neutral gas inside the vibration be qualified by the machine manufacturer.
➜ on a piping straight-up part eliminators in order to not trigger internal The product lifetime can vary enormously
➜ As close as possible of the vibration corrosion phenomena. depending on:
generator: compressor, evaporator, • During the brazing operation, be careful ➜ Pulsating effects and water hammers
condenser, etc... imperatively in that the scouring flux used does not ➜ Pressure variations
horizontal position at compressor’s come in contact with the hose and its ➜ Rapid and intermittent movements
suction. braid. ➜ Frequent temperature changes
➜ without twisting, extension or axial • The connections’ nickel lining holds ready ➜ Environment
compression stress. The vibration nicely during temperature increase; it is
• When properly assembled and used for the
eliminator must be perfectly straight. nevertheless recommended to protect
intended purpose, vibration eliminators are
➜ preferably 90° in relation to vibration the connections after brazing with an
durable, robust and virtually maintenance-
source (refer to sketch No1). appropriate product, against corrosion
free products. Vibration eliminators shall be
• Warning, when put under pressure, the risks.
subject to regular visual inspection by the user.
vibration eliminators can present a slight • Provide for clamping of the vibration In particular, attention should be paid to the
extension (about 2 % of initial length); it eliminator ends that are located opposite possible presence of damage such as buckling,
is therefore necessary to take this into the vibration source (refer to sketch No1). braid failure, corrosion and dirt. The component
account during the assembly operation. • All arrangements must be taken, in order is to be replaced as soon as one of these
• For the brazing operation, we recommend to prevent water concentration that may anomalies appears.
the use of a filler metal with a high silver freeze and then deteriorate the vibration
eliminator.

Compressor

Compressor

Clamping

Clamping Sketch No 1
Refrigeration Components Solutions 22.3

Stainless steel vibration eliminators, CTCY-EN - 22.1-7 / 06-2022

nickel-plated connections
EVCYAC
C

n Technical features

Connections Connections Dimensions


To solder To solder mm
CARLY CARLY
ODF ODF
references references
Ø1 Ø2 L1 L2 L3
inch mm
Schéma à intégrer dans chapitre EVCYAC - EVCYDEAC
EVCYAC 2 S 1/4 EVCYAC 2 MMS 6,0 14 9 200 6 16
EVCYAC 3 S 3/8 EVCYAC 3 MMS 10,0 18 13 221 9 21
EVCYAC 4 S 1/2 EVCYAC 4 MMS 12,0 19 16 242 11 24
EVCYAC 5 S 5/8 EVCYAC 5 MMS 15,0 25 19 288 14 29
EVCYAC 6 S 3/4 EVCYAC 6 MMS 18,0 30 22 318 16 33
EVCYAC 7 S/MMS 7/8 EVCYAC 7 S/MMS 22,0 30 25 318 18 42
EVCYAC 9 S 1 1/8 EVCYAC 9 MMS 28,0 36 32 360 20 51
EVCYAC 11 S/MMS 1 3/8 EVCYAC 11 S/MMS 35,0 47 40 408 30 56
EVCYAC 13 S 1 5/8 EVCYAC 13 MMS 42,0 58 48 472 30 68
EVCYAC 17 S/MMS 2 1/8 EVCYAC 17 S/MMS 54,0 69 60 560 40 88
EVCYAC 21 S 2 5/8 EVCYAC 21 MMS 67,0 84 75 670 50 105
EVCYAC 25 S 3 1/8 EVCYAC 25 MMS 80,0 107 88 760 55 124
EVCYAC 29 S 3 5/8 EVCYAC 29 MMS 88,9 132 102 895 55 142
EVCYAC 33 S 4 1/8 EVCYAC 33 MMS 108,0 132 114 930 60 160

L3
L2
1

L1
22.4 Refrigeration Components Solutions

Stainless steel vibration eliminators, CTCY-EN - 22.1-7 / 06-2022

nickel-plated connections
EVCYAC
C

n Technical features

Connec- Connec- Maximal Working Maximal Minimal Working


tions tions working pressure working working temperature CE
CARLY CARLY pressure (1)
temperature temperature (1)
To solder To solder Category
references references (2)
ODF ODF PS PS BT TS maxi* TS mini TS BT
inch inch bar bar °C °C °C
EVCYAC 2 S 1/4 EVCYAC 2 MMS 6,0 46 15 140 -40 -30 Art4§3
EVCYAC 3 S 3/8 EVCYAC 3 MMS 10,0 46 15 140 -40 -30 Art4§3
EVCYAC 4 S 1/2 EVCYAC 4 MMS 12,0 46 15 140 -40 -30 Art4§3
EVCYAC 5 S 5/8 EVCYAC 5 MMS 15,0 46 15 140 -40 -30 Art4§3
EVCYAC 6 S 3/4 EVCYAC 6 MMS 18,0 42 15 100 -40 -30 Art4§3
EVCYAC 7 S/MMS 7/8 EVCYAC 7 S/MMS 22,0 42 15 100 -40 -30 Art4§3
EVCYAC 9 S 1 1/8 EVCYAC 9 MMS 28,0 42 15 100 -40 -30 Art4§3
EVCYAC 11 S/MMS 1 3/8 EVCYAC 11 S/MMS 35,0 35 15 120 -40 -30 I
EVCYAC 13 S 1 5/8 EVCYAC 13 MMS 42,0 35 15 120 -40 -30 I
EVCYAC 17 S/MMS 2 1/8 EVCYAC 17 S/MMS 54,0 34 15 120 -40 -30 I
EVCYAC 21 S 2 5/8 EVCYAC 21 MMS 67,0 25 15 120 -40 -30 I
EVCYAC 25 S 3 1/8 EVCYAC 25 MMS 80,0 20 15 120 -40 -30 I
EVCYAC 29 S 3 5/8 EVCYAC 29 MMS 88,9 20 15 120 -40 -30 I
EVCYAC 33 S 4 1/8 EVCYAC 33 MMS 108,0 20 15 120 -40 -30 I
(1)
The working pressure is limited to the PS BT value when working temperature is lower than or equal to TS BT value.
(2)
Classification by diameter, according to PED 2014/68/EU
Croquis N°2(refer to chapter
- A intégrer dans0). chapitreEVCYAC & EVCYDEAC
* Other WT (working temperatures) possible on demand.

Ajouter tableau excel joint


dans le mail
(Rep1 à 5)
1

3 1 - Nickel plated steel connections


(or, stainless steel, on request)

4 2 - TIG weld

3 - Stainless steel ring


5 Inox 1.4307 - AISI 304L 1.

4 - Stainless steel wire braid


Inox 1.4307 - AISI 304L 1.

5 - Flexible wavy stainless steel hose


Inox 1.4404 - AISI 316L ou 1.4541 AISI
EVCYAC 2 to 17, flexible type 1-10
according EN ISO 10380
EVCYAC 21 to 33, flexible type 2-10
according EN ISO 10380

Sketch No 2
Refrigeration Components Solutions 22.5

Stainless steel vibration eliminators, CTCY-EN - 22.1-7 / 06-2022

nickel-plated connections
EVCYAC
C

n Weights and packaging

Unit weight Unit weight


CARLY kg Packaging CARLY kg Packaging
references With Without number of pieces references With Without number of pieces
packaging packaging packaging packaging
EVCYAC 2 S et MMS 0,06 0,06 1 EVCYAC 11 S/MMS 0,77 0,76 1
EVCYAC 3 S & MMS 0,07 0,07 1 EVCYAC 13 S et MMS 1,36 1,35 1
EVCYAC 4 S et MMS 0,10 0,10 1 EVCYAC 17 S/MMS 2,13 2,12 1
EVCYAC 5 S & MMS 0,15 0,15 1 EVCYAC 21 S et MMS 3,90 3,85 1
EVCYAC 6 S et MMS 0,25 0,25 1 EVCYAC 25 S & MMS 5,65 5,60 1
EVCYAC 7 S/MMS 0,25 0,25 1 EVCYAC 29 S et MMS 8,60 8,55 1
EVCYAC 9 S et MMS 0,43 0,42 1 EVCYAC 33 S & MMS 9,20 9,15 1