inteligen 500 g2 2.3.0 new features list
inteligen 500 g2 2.3.0 new features list
SW version 2.3.0
1 General information 2
2 Changes in the version 2.3.0 3
3 Changes in the version 2.2.0 5
4 Changes in the version 2.1.1 8
5 Changes in the version 2.1.0 9
6 Notes 13
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
2.3 Repairs
Resolution of RPM regulation for Cummins CM2358 was increased
Previous resolution was ±15 RPM
It was not possible to change the language of a controller without a logged-in user
During SUS, electrical protections were evaluated already after Minimal Stabilization Time and not after
Maximal Stabilization Time
Behavior of the LBO SOFT LOAD during a single genset operation in parallel to Mains was fixed
Improved communication with ECU MAN MFR
When an antenna for calculating a GPS position was disconnected from a controlelr, no alarm was issued
LBOs STOP SOLENOID and STOP PULSE were not activated during acranking fail pause
Switching of Modbus communicationbaud rate was not processed even when the setpoint was changed
Only when CM-RS232-485 was used
LBOs for ECU fault codes were active for only 1-2 s even if the alarm was still active
Power format was evaluated incorrectly when active power was negative
Next Engine Stop Delay was not applied and a genset went directly to a cooling phase
nd
Only after 2 and each following Remote Start/Stop signal
In MAN mode during the Idle time period, it was not possible to skip to the Running phase by pressing the
Start button
Evaluation of ECU BOUTs was incorrect when
One ECU with more than 32 BOUTs was configured
5 ECUs with at least 1 BOUT were configured
The Total Fuel Consumption of Doosan G2 EDC17 was incorrect
The decimal point was shifted by one place
Protection Starting Overspeed Sd was not evaluated accordingly if the level was set higher than for the
protection Overspeed Sd
LBOs ROCOF ACTIVE and VECTOR SHIFT ACTIVE were not activated during active ROCOF and Vector
Shift protections, respectively
Role 8: Modbus
Role 9: SNMP
Extended range of the selected setpoints up to 32 000 kW
Nominal power
Nominal power split phase
Extended range of the setpoint Earth Fault CT Ratio for a BIO8 module up to 10 000 A
Extended range of the setpoint Cranking Attempts up to 20
The setpoint group Loss of Mains Protections (Vector shift and ROCOF protections) is visible and
configurable also in MINT
Default value of the setpoint MCB Open Window is changed to 1%
Values from LAIs OIL PRESSURE, COOLANT TEMPERATURE and FUEL LEVEL are visible in Values
New temperature sensors are supported
PT100 (°C)
PT1000 (°C)
NI100 (°C)
NI1000 (°C)
PT100 (°F)
PT1000 (°F)
NI100 (°F)
NI1000 (°F)
3.3 Repairs
SNMP trap identifiers for protections
Value Mains Load Character is displayed correctly
Improved stability of communication over in-built ethernet port
Wrn MCB Fail to Open alarm handling
The alarm becomes inactive when Mains gets healthy and MCB is closed ang GCB is open
Setpoint AirGate Connection is not affected by history or vice-versa
Improved email notifications
Improved Modbus communication
MCB keeps closing/opening in case of open transfer in SPtM applications when a setpoint Open Transfer
Min Break > 3 s
Incorrect display of a controller mode on a display when using LBI SWITCH TO OFF/MAN/AUTO
AMF procedure is interrupted in case the Mains gets healthy again before the load is supplied by gensets
4.1 Repairs
User UID - incorrect visibility in InteliConfig
Ethernet communication improvment
Force Idle
Related FW 2.1.0 Related applications MINT, SPTM
Description
This LBI activates Force Idle function.
A breaker control was improved.
Amount of attempts to close breaker – Setpoint Attempts To Close Breaker
The delay between the attempts – Setpoint Delay Between Closing Attempts
Waiting time for breaker feedback - Setpoint Waiting for breaker Feedback
Idle Bypass
Description
When this LBI is active, controller will skip Idle phase.
LBI is active before Idle Time - controller goes directly to Stabilization phase
LBI is activated during Idle Time - Idle Time is skipped and controller goes to Stabilization phase
Alarm type for Maintenance Timers was change to Slow Stop type
Support of predefined linear sensors
Modbus communication was improved
Setpoint Modbus Mode was implemented
Modbus RTU Timing was fixed
Setpoint Nominal Frequency has 1 decimal place
Support of 8C and 16C communication modes on CAN2 line - setpoint CAN Intercontroller Comm Mode
User keys
LBOs User Key X State - LBO is active when user key (gray buttons on controller front facia) is pushed
Actual values of exercise timers are visible
Support of Leroy Sommer D500 series protocol
LBO History Record Indication Pulse added - This LBO triggers 1s pulse when new history record is
created in history log.
A function detecting a number of controllers on CAN2 line added
Voltage Droop
Description
If this LBI is active, Voltage regulation is forced to Droop regardless of the setpoint Load/VAr Sharing
Regulation Type.
5.3 Repairs
SNMP Traps
correct text for SNMP traps generated from universal binary and analog protections
correct OID for SNMP traps generated from universal binary and analog protections
Airgate Status incorrectly displayed on ICD
Incorerct default value of setpoint Airgate Port
Change of setpoints Time and Date was not written into history
Detected voltage in function Voltage Autodetect was not used for Mains/Bus side
Alarm Stp Request under Minimal PTM was disabled
Mains Power Factor and Mains Import S were not calculated when using Analog Input measurement