0% found this document useful (0 votes)
13 views

System P-KEMA type test#1

The document is a test report for the Prisma Plus system P low-voltage switchgear and controlgear assembly by Schneider Electric, detailing its specifications such as rated insulation voltage, operational voltage, and current ratings. It includes information about the temperature-rise limits verification tests conducted at Schneider Electric's facility in Grenoble, France, with observations by KEMA Quality B.V. representatives. The tests were performed under a frequency of 50 Hz, and the assembly is designed for various degrees of protection ranging from IP30 to IP55.

Uploaded by

m.ramadan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views

System P-KEMA type test#1

The document is a test report for the Prisma Plus system P low-voltage switchgear and controlgear assembly by Schneider Electric, detailing its specifications such as rated insulation voltage, operational voltage, and current ratings. It includes information about the temperature-rise limits verification tests conducted at Schneider Electric's facility in Grenoble, France, with observations by KEMA Quality B.V. representatives. The tests were performed under a frequency of 50 Hz, and the assembly is designed for various degrees of protection ranging from IP30 to IP55.

Uploaded by

m.ramadan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

TEST REPORT 2030444.

07-QUA/COM Page 2 of 41

Low-voltage switchgear and controlgear assembly

Tradename : SCHNEIDER-ELECTRIC/ MERLIN GERIN,SQUARE


D, TELEMECANIQUE
Type : Prisma Plus system P
Rated insulation voltage (Ui) : up to 1000 V, depending on the used
components
Rated operational voltage (Ue) : up to 1000 V, depending on the used
components
Rated frequency : 50 – 60 Hz
Rated impulse withstand voltage : 4 kV up to 12 kV, depending on the used
components
Rated current : panel up to 2820 A
Degree of protection : IP30 to IP55

Type Rated operational current (A)


IP30 IP55
Panel 1000A 1000 1000
Panel 1600A 1473 1365
Panel 3200A 2820 2530

Identification of the low-voltage switch- and controlgear assembly, see attached drawings, for the verification of
the temperature rise limits with degree of protection IP30 to IP55, for the rated current up to 2820 A, rated
operational voltage and rated insulation voltage associated.

Prisma Plus system P equipped with: Main system of low-voltage switch and distribution boards. The boards
contain the elements of the system main structure, busbars system, and the connections to the outgoing groups
as well as the installation of the equipment, all accommodated in the sheet-steel enclosures.

Summary of type tests

- 1 Verification of temperature-rise limits, clause 8.2.1 of IEC 60439-1

Location of the tests

The tests were carried out in Schneider Electric SAS, Volta, A7, 2, Rue Volta, Grenoble, France

Tests were carried out by

E. Fernandez Schneider Electric SAS, Volta, Grenoble, France

Manufacturer's representatives during tests

L. Kismoune Schneider Electric SAS, Grenoble, France


S. Bonente Schneider Electric SAS, Grenoble, France
TEST REPORT 2030444.07-QUA/COM Page 3 of 41

The tests were observed by

H.L. Schendstok KEMA Quality B.V., Arnhem, The Netherlands


L.J.W. van Megen KEMA Quality B.V., Arnhem, The Netherlands
T. Pasman KEMA Quality B.V., Arnhem, The Netherlands

General notes on tests:

The frequency during the tests was 50 Hz.