The F690A is a redundant fieldbus power conditioner designed for high availability applications, supporting four fieldbus segments with two levels of power redundancy. It features hot-swappable power modules, an integrated alarm module for fault detection, and flexible mounting options. The system ensures continuous operation by allowing component replacements without interrupting power or communication on the fieldbus.

Uploaded by

Thiago Felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

F690A

The F690A is a redundant fieldbus power conditioner designed for high availability applications, supporting four fieldbus segments with two levels of power redundancy. It features hot-swappable power modules, an integrated alarm module for fault detection, and flexible mounting options. The system ensures continuous operation by allowing component replacements without interrupting power or communication on the fieldbus.

Uploaded by

Thiago Felipe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Redundant fieldbus

power system

Relcom
F690A

◆ Redundant power conditioner for ◆ Component failure alarm


high availability applications
◆ Integrated fieldbus terminator
◆ Replace power modules without
◆ Simplified power wiring
resetting the fieldbus
◆ High power output
◆ Two levels of power redundancy
The F690A is part of a range of MTL-Relcom power module and two input power supply LEDs
redundant fieldbus power systems (FPS-Series), on the alarm module give clear visual indication that
which provides redundant power conditioning, and components are functioning properly.
facilitates the connection of redundant input power
Left- and right-hand carrier versions are
supplies. The F690A supports four fieldbus segments
available, providing flexibility in cabinet design. The
and provides redundant fieldbus power conditioners
F690A-Lx kits provide field connections on the left
for host systems that do not use a “standard” system
side of the carrier while the F690A-Rx kits have them
cable to connect to the fieldbus.
on the right. Accessories are available for T-section
Each fieldbus segment has two FPS-IPM and G-section DIN rail or surface mounting.
plug-in, power-conditioning modules that provide
The F690A provides connections to fieldbus
impedance between the input DC power supply and
host cards and field wiring. Field connections are
the fieldbus. This impedance is necessary to prevent
available with either screw terminal (-PB & -PS
the incoming DC power supply from degrading the
versions), or pluggable spring clamp terminals (-
digital fieldbus signal. A fieldbus segment terminator
PA & -PC versions). For redundant operation, two
is built in to each segment.
separate DC power supplies should be connected
A single or redundant host connection option to each F690A. Connections are also provided for
is provided. The single connection option is ideal for redundant power input, screen grounding and the
use with Emerson’s Delta V system which has one alarm contacts. The alarm contacts from several
segment connection in single and redundant fieldbus backplanes can be bussed together and connected
card configurations. The redundant host connection to a control system DI channel.
option would suit the ABB LD800HSE linking device
Each segment is supplied with 350mA at
when redundant linking devices are selected.
25V DC. This output is maintained, even if only
A separate FPS-ALM alarm module, one power module is installed per segment. This
galvanically isolated from the fieldbus segments level of output power allows for construction of very
and input power supplies, monitors the eight long fieldbus segments with a large number of bus-
power conditioning modules and the redundant powered transmitters.
power inputs. If a fault is detected on any of these
components, the alarm relay opens and a red The system is fully ‘hot-swappable’ meaning
alarm LED indicates a fault condition. This allows that individual power conditioning modules and input
failed components to be replaced so that power power supplies can be replaced without interrupting
system integrity is maintained. Green LEDs on each power or communication on the fieldbus segment.

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
Sept 2005
E-mail: [email protected] Web site: www.mtl-inst.com
F690A FIELDBUS
POWER SYSTEM

F690A-L 200mm
25mm

1A 1B 2A 2B
A1

ALARM A2

001-1057
SEGMENT
+
GDT1 ALARM 1 S
1
+ MODULE
-
S +
- 2 S

CON 301
D3

-
R1
C13

GDT2
SEGMENT PWR PWR ALM
A B
+
2 3 S
+
-
130mm

D18

D15

D16

D20
D17

D19

D14

D13

D10
D8
+

150mm
-
D7

D9

4 S
D4
R2

-
C14

SEGMENT CON1A
GDT3
3
+ D11

S
- D1
D5

+24VA
R3
C15

C2

C1
0VA

D21
GDT4 SEGMENT
4 0VB

C4

C3
+ +24VB
S
-
D6

D12
R4
C16

D2
3A 3B 4A 4B
10mm

150mm

F690A-R 200mm
25mm

2B 2A 1B 1A
A1

A2
ALARM

+ SEGMENT
S 1 ALARM GDT1
1
- MODULE +
+ S
S 2 -
D3
CON 301

-
R1

C13

+ PWR PWR ALM


A B
SEGMENT
GDT2
S 3 2
+
150mm

130mm

-
D20

D16

D15

D18

D13

D14

D19

D17

S
D10

D8

+ -
D9

D7

4
D4

S
R2

C14

-
SEGMENT GDT3

D11
3 +
S
D1
-
D5

+24VA
R3

C15
C1

C2

0VA
D21

GDT4
SEGMENT
C3

C4

0VB
4
+24VB +
S
-
D6

D12
R4

C16
D2

4B 4A 3B 3A
10mm

150mm

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
Sept 2005
E-mail: [email protected] Web site: www.mtl-inst.com
SPECIFICATION ENVIRONMENTAL

Location of equipment Ambient temp


Safe area Operating, optimum orientation*
–40°C to +65°C
OUTPUT Storage
–40°C to +85°C
Number of channels Ingress Protection
Four IP20 to BS EN 60529 (Additional protection by means of
Voltage enclosure)
Minimum 25.0V DC
*Optimum orientation is when the DIN rail is mounted horizontally on a
Current
vertical surface
0 to 350mA
Output ripple
ELECTRICAL
Complies with clause 22.6.2 of the fieldbus standard
Minimum load EMC compliance
No load To EN 61326:1998 Electrical equipment for measurement,
Isolation control and laboratory use - EMC requirements
Fieldbus to power supply: 250V AC rms withstand LED indicators
Alarm module
INPUT
Input power health - PWR A, PWR B (green)
Input voltage Alarm condition - ALM (red)
19.2 - 30V DC IPM module power - Power on (green)
Current consumption (4 segments each with 350mA output
load) PHYSICAL NETWORKS
3.4A (typical) at 19.2V
2.4A (typical) at 24V IEC 61158-2
2.1A (typical) at 28V Foundation Fieldbus H1
Power dissipation (4 segments each with 350mA output load) Profibus PA
20.3W (typical)
ALARMS
Alarm contact rating: 1A max @ 30V DC max
Alarm contact status: Normally closed
Alarm threshold: Input <18V DC
Output <22V DC
MECHANICAL
Mounting options
DIN-rail (G–section, T–section, 35mm x 7.5mm or 35mm x
15mm) to EN 50022, using mounting kit DMK01, or
flat surface using mounting kit - SMS01.
A vertical surface is recommended for mounting the F690A.
CONNECTIONS
Power Input and Alarm Contact
Fixed rising cage clamp screw terminals
Conductor size: 0.14 to 2.5mm2
Fieldbus Terminals
Pluggable rising cage clamp screw terminals (-PB, -PS versions)
Conductor size: 0.14 to 2.5mm2
Pluggable spring clamp terminals (-PA, -PC versions)
Conductor size: 0.2 to 2.5mm2 flexible or rigid
Host connectors:
Separate connections to redundant host cards (-PA, -PB).
Single connection to host cards (-PC, -PS).
Fixed rising cage clamp screw terminals (-PA, -PB).
Conductor size: 0.14 to 2.5mm2
Pluggable rising cage clamp screw terminals (-PS).
Conductor size: 0.14 to 2.5mm2
Pluggable spring clamp terminals (-PC).
Conductor size: 0.2 to 2.5mm2
Screen Ground
To connect all fieldbus cable screens to a common
point (cabinet earth).

TERMINATORS
Fixed terminator for each fieldbus segment.

EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
Sept 2005
E-mail: [email protected] Web site: www.mtl-inst.com
ORDERING INFORMATION
For simplicity, the F690A can be purchased as a system kit that
includes a carrier, power modules and an alarm module. The
following table explains what each F690A-xx kit comprises.
Individual components can also be ordered; please refer to the
component and accessories list below the table.
Host Connection Redundant host connection to host card Single host connection to host card
Fixed screw terminal Pluggable spring clamp Pluggable screw terminal
Segment Connection Pluggable spring clamp Pluggable screw terminal Pluggable spring clamp Pluggable screw terminal
Left hand Right hand Left hand Right hand Left hand Right hand Left hand Right hand
System No. F690A-LA F690A-RA F690A-LB F690A-RB F690A-LC F690A-RC F690A-LS F690A-RS
FPS-IPM x8 x8 x8 x8 x8 x8 x8 x8
FPS-ALM x1 x1 x1 x1 x1 x1 x1 x1
F690A-CL-PA x1
F690A-CR-PA x1
F690A-CL-PB x1
F690A-CR-PB x1
F690A-CL-PC x1
F690A-CR-PC x1
F690A-CL-PS x1
F690A-CR-PS x1

COMPONENTS AND ACCESSORIES

PART No DESCRIPTION
FPS-IPM Power Module
FPS-ALM Alarm Module
F690A-CL-PA F690A carrier, Left Hand
F690A-CR-PA F690A carrier, Right Hand
F690A-CL-PB F690A carrier, Left Hand
F690A-CR-PB F690A carrier, Right Hand
F690A-CL-PC F690A carrier, Left Hand, Pluggable spring clamp
F690A-CR-PC F690A carrier, Right Hand, Pluggable spring clamp
F690A-CL-PS F690A carrier, Left Hand, Pluggable screw
terminals
F690A-CR-PS F690A carrier, Right Hand, Pluggable screw
terminals
DMK01 DIN-rail m ounting kit, T or G section (pack of
40)†
SMS01 Surface mounting kit, (pack of 40)†
BMK08 Mounting kit for one F690A
FPS-BLK10 Blanking Module (pack of 10)*

† Sufficient to mount 10 x F690A systems

* Segments that do not require the high availability provided by redundant


power conditioning may be operated with only a single FPS-IPM. In this
event, a blanking module should be fitted to the unused slot to prevent an
alarm condition.