Ground System
Ground System
One during fault what will be the fault current i.e Ifa, Ifb, Ifc. Another was the service continuity, i.e
Phase current variation of Ia, Ib, Ic
ETAP calculation is based on fault current analysis Ifa, Ifb and Ifc analysis during a fault. ½ cycle, -Cycle
and 30 cycle. And the summary is that, at I/2 cycle the value shall be not zero for Ifa and Ifb because of
the capacitance effect and also from motor side there shall be some current value due to imbalance and
asynchronous effect might be but after 30 cycle i.e steady state fault, only faulty phase ground haas a
current and other two phase fault current Ifa and Ifb shall be zero.
Now what happened to Phase current and voltage shall be discussed later.
Observations:
Fault current seen by Zero sequence CT for ½ cycle is 260A (Vector sum; show link below). Here other
phases current is not zero also. Rest will be contributed through Motor because at the instant of fault
motor will operate as generator and contribute.
Fault current seen by Zero sequence CT for 4 cycle also around 270A (Vector sum; show link below). Here
other phases current is not zero also. Rest will be contributed through Motor because at the instant of
fault motor will operate as generator and contribute.
Fault current seen by Zero sequence CT for 30 cycle shall be 500A. Here other phases currents are zero.
No contribution from motor.
Here, Fault current shall be high and unbalance also high even for 5A resistance earth as phase fault
is there.
Link:
https://www.calculators-math.com/complex-number-calculator/
https://ejl.neocities.org/rectangToPolar
2nd: Phase current analysis
In a single phase-to-ground fault on a high resistance grounding system, the current in the remaining
two phases will be essentially unchanged and close to their normal operating current; the fault current is
limited to a very low value by the high resistance grounding resistor, meaning the other phases are not
significantly affected by the fault.
Fault after Motor Terminal: Say Fault current is set to 1A and the CT measure 10-5-1=1A. As the zero
sequence fault not zero, CT will sense a fault. Similarly, for 5A
Hence, for HRG system there will be service continuity but for LRG or Solid ground fault it will not be
there, and we need to trip the system
For HRG, It allows the system to stay in service but it is highly recommended to try and correct the fault
as soon as safely possible due to high voltage system application of two un faulted phases.
During 1Ph to ground fault, the neutral has been shifted. Say fault occurred in Ph-B. Voltage of the R
point Ph-Ground shall be Phase voltage+ Voltage drop across the resistor and it can go up to the line
voltage.
Hence, during ground fault conditions, the voltage to ground on the two unfaulted phases to be
considered is equal to the line-to-line voltage. The equipment rating has to be rated at 173% of their
line-to-neutral voltages.
LRG System
Low resistance grounding is normally used on medium-voltage to high-voltage systems to limit the
ground return current to a high level, typically 100 A or more. The resistance must be low enough to let
high current flow and allow detection by the protective devices, which in turn trip the circuit offline.
Now, does the Zero sequence CT shows 500A at steady state and value shall be 500:5?
As per Siemens tech topic ZCT rating shall be 50:5 and this CT has a limit to measure 10 times current
with 10% error.
https://www.siemens.com/us/en/products/energy/techtopics/techtopics-98.html
Phasor Diagram of Grounding system
Solid Grounding:
https://www.youtube.com/watch?v=1dQ_vnsn--U
Condition:
Now the capacitance will form (stray capacitance) on each phase. Now say B phase is faulty and volage
across this capacitance is 0 hence can be neglected.
Now look the capacitor current is not related to fault and wheather fault occur or not this value will not
change. It will be leading the respective voltage by 90 degrees.
From the phasor diagram we can see that Icf and If are opposite and nullyfying the effect of capacitive
current and hence there will no arching ground for solidly grounded system
https://www.youtube.com/watch?v=KtiZqZCKjvA
Reactance Grounding:
For greater than 33KV as ICF (Capacitive resultant current) can be is very high.
Fault current in resister shall be If-Icf
If the system capacitive current requirement is more, say for Synchronous condenser, long cable, cap
bank, transmission line without transformer etc. Capacitive component will be more. Hence the
requirement of If sin fy will be more and automatically IF requirement will be more .
So fault through the NGR shall be 200A but IF shall be high, say 500A.
If the capacitive current is more we need to go with reactance grounding.
As per IEEE it means grounding through impedance. So, it is not an ideal inductor but some resistance
can be present.
By phasor diagram, no sign components are there and Capacitive current is completely eliminating by IF
fault current. Weather resistive case sine Fy component is eliminating. This vector diagram is like Solid
ground. It is used when the capacitive currents are more.
Disadvantage is that due to lightning strick the inductor will be open circuited and the entire wave will
be reflected back. So the switching surges will be high.
If there is a long distance in between transformer and switchgear during fault the fault current will
travel to remote earth. We can avoid by placing the Zig Zag or open delta
If there is a long distance in between transformer and switchgear during fault the
fault current will travel to remote earth. We can avoid by placing the Zig Zag or
open delta
Here the current shall be limited by the resistance of transformer. Calculation shall
be like zig Zag
Broken Delta Grounding System:
If there is a long distance in between transformer and switchgear during fault the fault current will
travel to remote earth. We can avoid by placing the Zig Zag or open delta
The best way to ground an ungrounded delta system (existing or new) is to derive a neutral point
through grounding transformers as shown in figure above. The resistor inserted in the “broken delta” leg
is reflected to the primary underground fault conditions and limits the current to a nominal value as
dictated by its design.
VFD Grounding:
Normal GFR can’t measure unbalance due to HRG system as lea than30% unbalance it shouldn’t trip.
Moreover at OG is not sinusoidal and hence normal GFR can’t measure. Dtartco EL731 can measure as
they demand. Even if CT can placed at output of VFD.